OIDNameAccessStatusDescription
1.3.6.1.4.1.232.165NodecpqPower
1.3.6.1.4.1.232.165.1NodepowerDevice
1.3.6.1.4.1.232.165.1NodetrapCriticalA critical alarm has occurred. Action: Check the Trap Details for more information.
1.3.6.1.4.1.232.165.1.1NodetrapInfo
1.3.6.1.4.1.232.165.1.1.1ScalartrapCoderead-onlymandatoryA number identifying the event for the trap that was sent. Mapped unique trap code per unique event to be used by ISEE's decoder ring.
1.3.6.1.4.1.232.165.1.1.2ScalartrapDescriptionread-onlymandatoryA string identifying the event for that last trap that was sent.
1.3.6.1.4.1.232.165.1.1.3ScalartrapDeviceMgmtUrlread-onlymandatoryA string contains the URL for the management software.
1.3.6.1.4.1.232.165.1.1.4ScalartrapDeviceDetailsread-onlymandatoryA string details information about the UPS such as SN (serial number), PN (part number), and MN (Model Name).
1.3.6.1.4.1.232.165.1.1.5ScalartrapDeviceNameread-onlymandatoryA string contains the name of the HP Management Module.
1.3.6.1.4.1.232.165.1.2NodemanagementModuleIdent
1.3.6.1.4.1.232.165.1.2.1ScalardeviceManufacturerread-onlymandatoryThe device's manufacturer.
1.3.6.1.4.1.232.165.1.2.2ScalardeviceModelread-onlymandatoryThe device's model.
1.3.6.1.4.1.232.165.1.2.3ScalardeviceFirmwareVersionread-onlymandatoryThe device's firmware version(s).
1.3.6.1.4.1.232.165.1.2.4ScalardeviceHardwareVersionread-onlymandatoryThe device's hardware version.
1.3.6.1.4.1.232.165.1.2.5ScalardeviceIdentNameread-writemandatoryA string identifying the device. it came from sysName entered by user
1.3.6.1.4.1.232.165.1.2.6ScalardevicePartNumberread-onlymandatoryThe device's part number.
1.3.6.1.4.1.232.165.1.2.7ScalardeviceSerialNumberread-onlymandatoryThe device's serial number.
1.3.6.1.4.1.232.165.1.2.8ScalardeviceMACAddressread-onlymandatoryThe device's MAC address.
1.3.6.1.4.1.232.165.2Nodepdu
1.3.6.1.4.1.232.165.2NodetrapWarningA warning alarm has occurred. Action: Check the Trap Details for more information.
1.3.6.1.4.1.232.165.2.1NodepduIdent
1.3.6.1.4.1.232.165.2.1.1ScalarnumOfPduread-onlymandatoryThe number of PDUs.
1.3.6.1.4.1.232.165.2.1.2TablepduIdentTablenot-accessiblemandatoryThe Aggregate Object with number of entries equal to NumOfPdu and including the PduIdent group.
1.3.6.1.4.1.232.165.2.1.2.1RowpduIdentEntrynot-accessiblemandatoryThe ident table entry containing the name, model, manufacturer, firmware version, part number, etc.
1.3.6.1.4.1.232.165.2.1.2.1.1ColumnpduIdentIndexread-onlymandatoryIndex for the PduIdentEntry table.
1.3.6.1.4.1.232.165.2.1.2.1.2ColumnpduNameread-writemandatoryThe string identify the device.
1.3.6.1.4.1.232.165.2.1.2.1.3ColumnpduModelread-onlymandatoryThe Device Model.
1.3.6.1.4.1.232.165.2.1.2.1.4ColumnpduManufacturerread-onlymandatoryThe Device Manufacturer Name (e.g. Hewlett-Packard).
1.3.6.1.4.1.232.165.2.1.2.1.5ColumnpduFirmwareVersionread-onlymandatoryThe firmware revision level of the device.
1.3.6.1.4.1.232.165.2.1.2.1.6ColumnpduPartNumberread-onlymandatoryThe device part number.
1.3.6.1.4.1.232.165.2.1.2.1.7ColumnpduSerialNumberread-onlymandatoryThe device serial number.
1.3.6.1.4.1.232.165.2.1.2.1.8ColumnpduStatusread-onlymandatoryThe overall status of the device. A value of OK(2) indicates the device is operating normally. A value of degraded(3) indicates the device is operating with wa…
1.3.6.1.4.1.232.165.2.1.2.1.9ColumnpduControllableread-onlymandatoryThis object indicates whether or not the device is controllable.
1.3.6.1.4.1.232.165.2.2NodepduInput
1.3.6.1.4.1.232.165.2.2.1TablepduInputTablenot-accessiblemandatoryThe Aggregate Object with number of entries equal to NumOfPdu and including the PduInput group.
1.3.6.1.4.1.232.165.2.2.1.1RowpduInputEntrynot-accessiblemandatoryThe input table entry containing the voltage and current for the PDU
1.3.6.1.4.1.232.165.2.2.1.1.1ColumnpduInputIndexread-onlymandatoryIndex for the PduInputEntry table.
1.3.6.1.4.1.232.165.2.2.1.1.2ColumninputVoltageread-onlymandatoryThe measured input voltage from the PDU meters in volts.
1.3.6.1.4.1.232.165.2.2.1.1.3ColumninputCurrentread-onlymandatoryThe measured input current from the PDU meters in hundredths of Amp.
1.3.6.1.4.1.232.165.2.3NodepduOutput
1.3.6.1.4.1.232.165.2.3.1TablepduOutputTablenot-accessiblemandatoryThe Aggregate Object with number of entries equal to NumOfPdu and including the PduInput group.
1.3.6.1.4.1.232.165.2.3.1.1RowpduOutputEntrynot-accessiblemandatoryThe input table entry containing the name, heat load, current load, power load, firmware, etc.
1.3.6.1.4.1.232.165.2.3.1.1.1ColumnpduOutputIndexread-onlymandatoryIndex for the PduOutputEntry table.
1.3.6.1.4.1.232.165.2.3.1.1.2ColumnpduOutputLoadread-onlymandatoryThe device output load in percent of rated capacity. A value of -1 will be returned if the heat load is unable to be measured.
1.3.6.1.4.1.232.165.2.3.1.1.3ColumnpduOutputHeatread-onlymandatoryThe total heat load measured on the PDU in BTUs. A value of -1 will be returned if the heat load is unable to be measured.
1.3.6.1.4.1.232.165.2.3.1.1.4ColumnpduOutputPowerread-onlymandatoryThe total power load measured on the PDU in watts. A value of -1 will be returned if the power load is unable to be measured.
1.3.6.1.4.1.232.165.2.3.1.1.5ColumnpduOutputNumBreakersread-onlymandatoryThe number of breakers for the device. This variable indicates the number of rows in the breakers table.
1.3.6.1.4.1.232.165.2.3.2TablepduOutputBreakerTablenot-accessiblemandatoryList of breaker table entries. The number of entries is given by pduOutputNumBreakers .
1.3.6.1.4.1.232.165.2.3.2.1RowpduOutputBreakerEntrynot-accessiblemandatoryAn entry containing information applicable to an breaker.
1.3.6.1.4.1.232.165.2.3.2.1.1ColumnbreakerIndexread-onlymandatoryThe breaker identifier.
1.3.6.1.4.1.232.165.2.3.2.1.2ColumnbreakerVoltageread-onlymandatoryThe breaker voltage in volts.
1.3.6.1.4.1.232.165.2.3.2.1.3ColumnbreakerCurrentread-onlymandatoryThe breaker current draw in hundredths of Amp.
1.3.6.1.4.1.232.165.2.3.2.1.4ColumnbreakerPercentLoadread-onlymandatoryThe breaker load in percent.
1.3.6.1.4.1.232.165.2.3.2.1.5ColumnbreakerStatusread-onlymandatoryThis object indicates the status of the breaker. A value of normal(1) indicates the breaker is operating normally. A value of overloadWarning(2) indicates the …
1.3.6.1.4.1.232.165.3NodetrapInformationAn informational alarm has occurred. Action: Check the Trap Details for more information.
1.3.6.1.4.1.232.165.3Nodeups
1.3.6.1.4.1.232.165.3.1NodeupsIdent
1.3.6.1.4.1.232.165.3.1.1ScalarupsIdentManufacturerread-onlymandatoryThe UPS Manufacturer Name (e.g. Hewlett-Packard).
1.3.6.1.4.1.232.165.3.1.2ScalarupsIdentModelread-onlymandatoryThe UPS Model;Part number;Serial number (e.g. HP R5500 XR;204451-B21;B00123456W).
1.3.6.1.4.1.232.165.3.1.3ScalarupsIdentSoftwareVersionsread-onlymandatoryThe firmware revision level(s) of the UPS microcontroller(s).
1.3.6.1.4.1.232.165.3.1.4ScalarupsIdentOemCoderead-onlymandatoryA binary code indicating vendor. This should be a ?0x0c? for HP
1.3.6.1.4.1.232.165.3.2NodeupsBattery
1.3.6.1.4.1.232.165.3.2.1ScalarupsBatTimeRemainingread-onlymandatoryBattery run time in seconds before UPS turns off due to low battery.
1.3.6.1.4.1.232.165.3.2.2ScalarupsBatVoltageread-onlymandatoryBattery voltage as reported by the UPS meters.
1.3.6.1.4.1.232.165.3.2.3ScalarupsBatCurrentread-onlymandatoryBattery Current as reported by the UPS metering. Current is positive when discharging, negative when recharging the battery.
1.3.6.1.4.1.232.165.3.2.4ScalarupsBatCapacityread-onlymandatoryBattery percent charge.
1.3.6.1.4.1.232.165.3.2.5ScalarupsBatteryAbmStatusread-onlymandatoryGives the status of the Advanced Battery Management; batteryFloating(3) status means that the charger is temporarily charging the battery to its float voltage;…
1.3.6.1.4.1.232.165.3.3NodeupsInput
1.3.6.1.4.1.232.165.3.3.1ScalarupsInputFrequencyread-onlymandatoryThe utility line frequency in tenths of Hz.
1.3.6.1.4.1.232.165.3.3.2ScalarupsInputLineBadsread-onlymandatoryThe number of times the Input was out of tolerance in voltage or frequency.
1.3.6.1.4.1.232.165.3.3.3ScalarupsInputNumPhasesread-onlymandatory
1.3.6.1.4.1.232.165.3.3.4TableupsInputTablenot-accessiblemandatoryThe Aggregate Object with number of entries equal to NumPhases and including the UpsInput group.
1.3.6.1.4.1.232.165.3.3.4.1RowupsInputEntrynot-accessiblemandatoryThe input table entry containing the current, voltage, etc.
1.3.6.1.4.1.232.165.3.3.4.1.1ColumnupsInputPhaseread-onlymandatoryThe number of the phase. Serves as index for input table.
1.3.6.1.4.1.232.165.3.3.4.1.2ColumnupsInputVoltageread-onlymandatoryThe measured input voltage from the UPS meters in volts.
1.3.6.1.4.1.232.165.3.3.4.1.3ColumnupsInputCurrentread-onlymandatoryThe measured input current from the UPS meters in amps.
1.3.6.1.4.1.232.165.3.3.4.1.4ColumnupsInputWattsread-onlymandatoryThe measured input real power in watts. Most UPSs do not report this XCP data
1.3.6.1.4.1.232.165.3.3.5ScalarupsInputSourceread-onlymandatoryThe present external source of input power. The enumeration none(2) indicates that there is no external source of power, for example, the UPS is On Battery (an…
1.3.6.1.4.1.232.165.3.4NodeupsOutput
1.3.6.1.4.1.232.165.3.4.1ScalarupsOutputLoadread-onlymandatoryThe UPS output load in percent of rated capacity.
1.3.6.1.4.1.232.165.3.4.2ScalarupsOutputFrequencyread-onlymandatoryThe measured UPS output frequency in tenths of Hz.
1.3.6.1.4.1.232.165.3.4.3ScalarupsOutputNumPhasesread-onlymandatoryThe number of metered output phases, serves as the table index.
1.3.6.1.4.1.232.165.3.4.4TableupsOutputTablenot-accessiblemandatoryThe Aggregate Object with number of entries equal to NumPhases and including the UpsOutput group.
1.3.6.1.4.1.232.165.3.4.4.1RowupsOutputEntrynot-accessiblemandatoryOutput Table Entry containing voltage, current, etc.
1.3.6.1.4.1.232.165.3.4.4.1.1ColumnupsOutputPhaseread-onlymandatoryThe number {1..3} of the output phase.
1.3.6.1.4.1.232.165.3.4.4.1.2ColumnupsOutputVoltageread-onlymandatoryThe measured output voltage from the UPS metering in volts.
1.3.6.1.4.1.232.165.3.4.4.1.3ColumnupsOutputCurrentread-onlymandatoryThe measured UPS output current in amps.
1.3.6.1.4.1.232.165.3.4.4.1.4ColumnupsOutputWattsread-onlymandatoryThe measured real output power in watts.
1.3.6.1.4.1.232.165.3.4.5ScalarupsOutputSourceread-onlymandatoryThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the…
1.3.6.1.4.1.232.165.3.5NodeupsBypass
1.3.6.1.4.1.232.165.3.5.1ScalarupsBypassFrequencyread-onlymandatoryThe bypass frequency in tenths of Hz.
1.3.6.1.4.1.232.165.3.5.2ScalarupsBypassNumPhasesread-onlymandatoryThe number of lines in the UPS bypass table.
1.3.6.1.4.1.232.165.3.5.3TableupsBypassTablenot-accessiblemandatory
1.3.6.1.4.1.232.165.3.5.3.1RowupsBypassEntrynot-accessiblemandatoryEntry in the UpsBypassTable.
1.3.6.1.4.1.232.165.3.5.3.1.1ColumnupsBypassPhaseread-onlymandatoryThe Bypass Phase, index for the table.
1.3.6.1.4.1.232.165.3.5.3.1.2ColumnupsBypassVoltageread-onlymandatoryThe measured UPS bypass voltage in volts.
1.3.6.1.4.1.232.165.3.6NodeupsEnvironment
1.3.6.1.4.1.232.165.3.6.1ScalarupsEnvAmbientTempread-onlymandatoryThe reading of the ambient temperature in the vicinity of the UPS or SNMP agent.
1.3.6.1.4.1.232.165.3.6.2ScalarupsEnvAmbientLowerLimitread-writemandatoryThe Lower Limit of the ambient temperature; if UpsEnvAmbientTemp falls below this value, the UpsAmbientTempBad alarm will occur.
1.3.6.1.4.1.232.165.3.6.3ScalarupsEnvAmbientUpperLimitread-writemandatoryThe Upper Limit of the ambient temperature; if UpsEnvAmbientTemp rises above this value, the UpsAmbientTempBad alarm will occur. This value should be greater t…
1.3.6.1.4.1.232.165.3.6.4ScalarupsEnvAmbientHumidityread-onlymandatoryThe reading of the ambient humidity in the vicinity of the UPS or SNMP agent.
1.3.6.1.4.1.232.165.3.6.5ScalarupsEnvRemoteTempread-onlymandatoryThe reading of a remote temperature sensor connected to the UPS or SNMP agent.
1.3.6.1.4.1.232.165.3.6.6ScalarupsEnvRemoteHumidityread-onlymandatoryThe reading of a remote humidity sensor connected to the UPS or SNMP agent.
1.3.6.1.4.1.232.165.3.6.7ScalarupsEnvNumContactsread-onlymandatoryThe number of Contacts in the UpsContactsTable. This object indicates the number of rows in the UpsContactsTable.
1.3.6.1.4.1.232.165.3.6.8TableupsContactsTablenot-accessiblemandatoryA list of Contact Sensing table entries. The number of entries is given by the value of UpsEnvNumContacts.
1.3.6.1.4.1.232.165.3.6.8.1RowupsContactsTableEntrynot-accessiblemandatoryAn entry containing information applicable to a particular Contact input.
1.3.6.1.4.1.232.165.3.6.8.1.1ColumnupsContactIndexread-onlymandatoryThe Contact identifier; identical to the Contact Number.
1.3.6.1.4.1.232.165.3.6.8.1.2ColumnupsContactTyperead-writemandatoryThe normal state for this contact. The 'other' state is the Active state for generating the UpstdContactActiveNotice trap. If anyChange(3) is selected, then th…
1.3.6.1.4.1.232.165.3.6.8.1.3ColumnupsContactStateread-onlymandatoryThe current state of the Contact input; the value is based on the open/closed input state and the setting for UpsContactType. When entering the openWithNotice(…
1.3.6.1.4.1.232.165.3.6.8.1.4ColumnupsContactDescrread-writemandatoryA label identifying the Contact. This object should be set by the administrator.
1.3.6.1.4.1.232.165.3.6.9ScalarupsEnvRemoteTempLowerLimitread-writemandatoryThe Lower Limit of the remote temperature; if UpsEnvRemoteTemp falls below this value, the UpsRemoteTempBad alarm will occur.
1.3.6.1.4.1.232.165.3.6.10ScalarupsEnvRemoteTempUpperLimitread-writemandatoryThe Upper Limit of the remote temperature; if UpsEnvRemoteTemp rises above this value, the UpsRemoteTempBad alarm will occur. This value should be greater than…
1.3.6.1.4.1.232.165.3.6.11ScalarupsEnvRemoteHumidityLowerLimitread-writemandatoryThe Lower Limit of the remote humidity reading; if UpsEnvRemoteHumidity falls below this value, the UpsRemoteHumidityBad alarm will occur.
1.3.6.1.4.1.232.165.3.6.12ScalarupsEnvRemoteHumidityUpperLimitread-writemandatoryThe Upper Limit of the remote humidity reading; if UpsEnvRemoteHumidity rises above this value, the UpsRemoteHumidityBad alarm will occur. This value should be…
1.3.6.1.4.1.232.165.3.7NodeupsTest
1.3.6.1.4.1.232.165.3.7.1ScalarupsTestBatteryread-writemandatorySetting this variable to startTest initiates the battery test. All other set values are invalid.
1.3.6.1.4.1.232.165.3.7.2ScalarupsTestBatteryStatusread-onlymandatoryReading this enumerated value gives an indication of the UPS Battery test status.
1.3.6.1.4.1.232.165.3.7.3ScalarupsTestTrapread-writemandatorySetting startTestTrap to 1 will initiate a TrapTest is sent out from HPMM. All other set values are invalid.
1.3.6.1.4.1.232.165.3.8NodeupsControl
1.3.6.1.4.1.232.165.3.8.1ScalarupsControlOutputOffDelayread-writemandatorySetting this value to other than zero will cause the UPS output to turn off after the number of seconds. Setting it to 0 will cause an attempt to abort a pendi…
1.3.6.1.4.1.232.165.3.8.2ScalarupsControlOutputOnDelayread-writemandatorySetting this value to other than zero will cause the UPS output to turn on after the number of seconds. Setting it to 0 will cause an attempt to abort a pendin…
1.3.6.1.4.1.232.165.3.8.3ScalarupsControlOutputOffTrapDelayread-writemandatoryWhen UpsControlOutputOffDelay reaches this value, a trap will be sent.
1.3.6.1.4.1.232.165.3.8.4ScalarupsControlOutputOnTrapDelayread-writedeprecatedWhen UpsControlOutputOnDelay reaches this value, a UpsOutputOff trap will be sent.
1.3.6.1.4.1.232.165.3.8.5ScalarupsControlToBypassDelayread-writemandatorySetting this value to other than zero will cause the UPS output to go to Bypass after the number of seconds. If the Bypass is unavailable, this may cause the U…
1.3.6.1.4.1.232.165.3.8.6ScalarupsLoadShedSecsWithRestartread-writemandatorySetting this value will cause the UPS output to turn off after the set number of seconds, then restart (after a UPS-defined 'down time') when the utility is ag…
1.3.6.1.4.1.232.165.3.9NodeupsConfig
1.3.6.1.4.1.232.165.3.9.1ScalarupsConfigOutputVoltageread-onlymandatoryThe nominal UPS Output voltage per phase in volts.
1.3.6.1.4.1.232.165.3.9.2ScalarupsConfigInputVoltageread-onlymandatoryThe nominal UPS Input voltage per phase in volts.
1.3.6.1.4.1.232.165.3.9.3ScalarupsConfigOutputWattsread-onlymandatoryThe nominal UPS available real power output in watts.
1.3.6.1.4.1.232.165.3.9.4ScalarupsConfigOutputFreqread-onlymandatoryThe nominal output frequency in tenths of Hz.
1.3.6.1.4.1.232.165.3.9.5ScalarupsConfigDateAndTimeread-writemandatoryDate and time information for the UPS. Setting this variable will initiate a set UPS date and time to this value. Reading this variable will return the UPS tim…
1.3.6.1.4.1.232.165.3.9.6ScalarupsConfigLowOutputVoltageLimitread-onlymandatoryThe Lower limit for acceptable Output Voltage, per the UPS specifications.
1.3.6.1.4.1.232.165.3.9.7ScalarupsConfigHighOutputVoltageLimitread-onlymandatoryThe Upper limit for acceptable Output Voltage, per the UPS specifications.
1.3.6.1.4.1.232.165.3.10NodeupsRecep
1.3.6.1.4.1.232.165.3.10.1ScalarupsNumReceptaclesread-onlymandatoryThe number of independently controllable Receptacles, as described in the UpsRecepTable.
1.3.6.1.4.1.232.165.3.10.2TableupsRecepTablenot-accessiblemandatoryThe Aggregate Object with number of entries equal to NumReceptacles and including the UpsRecep group.
1.3.6.1.4.1.232.165.3.10.2.1RowupsRecepEntrynot-accessiblemandatoryThe Recep table entry, etc.
1.3.6.1.4.1.232.165.3.10.2.1.1ColumnupsRecepIndexread-onlymandatoryThe number of the Receptacle. Serves as index for Receptacle table.
1.3.6.1.4.1.232.165.3.10.2.1.2ColumnupsRecepStatusread-onlymandatoryThe Recep Status 1=On/Close, 2=Off/Open, 3=On w/Pending Off, 4=Off w/Pending ON, 5=Unknown.
1.3.6.1.4.1.232.165.3.10.2.1.3ColumnupsRecepOffDelaySecsread-writemandatoryThe Delay until the Receptacle is turned Off. Setting this value to other than -1 will cause the UPS output to turn off after the number of seconds (0 is immed…
1.3.6.1.4.1.232.165.3.10.2.1.4ColumnupsRecepOnDelaySecsread-writemandatoryThe Delay until the Receptacle is turned On. Setting this value to other than -1 will cause the UPS output to turn on after the number of seconds (0 is immedia…
1.3.6.1.4.1.232.165.3.10.2.1.5ColumnupsRecepAutoOffDelayread-writemandatoryThe delay after going On Battery until the Receptacle is automatically turned Off. A value of -1 means that this Output should never be turned Off automaticall…
1.3.6.1.4.1.232.165.3.10.2.1.6ColumnupsRecepAutoOnDelayread-writemandatorySeconds delay after the Outlet is signaled to turn On before the Output is Automatically turned ON. A value of -1 means that this Output should never be turned…
1.3.6.1.4.1.232.165.3.10.2.1.7ColumnupsRecepShedSecsWithRestartread-writemandatorySetting this value will cause the UPS output to turn off after the set number of seconds, then restart (after a UPS-defined 'down time') when the utility is ag…
1.3.6.1.4.1.232.165.3.11NodeupsTopology
1.3.6.1.4.1.232.165.3.11.1ScalarupsTopologyTyperead-onlymandatoryValue which denotes the type of UPS by its power topology. Values are the same as those described in the XCP Topology block's Overall Topology field.
1.3.6.1.4.1.232.165.3.11.2ScalarupsTopoMachineCoderead-onlymandatoryID Value which denotes the Compaq/HP model of the UPS for software. Values are the same as those described in the XCP Configuration block's Machine Code field.
1.3.6.1.4.1.232.165.3.11.3ScalarupsTopoUnitNumberread-onlymandatoryIdentifies which unit and what type of data is being reported. A value of 0 means that this MIB information comes from the top-level system view (eg, manifold …
1.3.6.1.4.1.232.165.3.11.4ScalarupsTopoPowerStrategyread-writemandatoryValue which denotes which Power Strategy is currently set for the UPS. The values are: highAlert(1) - The UPS shall optimize its operating state to maximize it…
1.3.6.1.4.1.232.165.4Nodepdr
1.3.6.1.4.1.232.165.4NodetrapClearedAn alarm has cleared. Action: Check the Trap Details for more information.
1.3.6.1.4.1.232.165.4.1NodepdrIdent
1.3.6.1.4.1.232.165.4.1.1ScalarpdrNameread-writemandatoryThe string identify the device.
1.3.6.1.4.1.232.165.4.1.2ScalarpdrModelread-onlymandatoryThe Device Model.
1.3.6.1.4.1.232.165.4.1.3ScalarpdrManufacturerread-onlymandatoryThe Device Manufacturer Name (e.g. Hewlett-Packard).
1.3.6.1.4.1.232.165.4.1.4ScalarpdrFirmwareVersionread-onlymandatoryThe firmware revision level of the device.
1.3.6.1.4.1.232.165.4.1.5ScalarpdrPartNumberread-onlymandatoryThe device part number.
1.3.6.1.4.1.232.165.4.1.6ScalarpdrSerialNumberread-onlymandatoryThe PDR's serial number.
1.3.6.1.4.1.232.165.4.1.7ScalarpdrVARatingread-onlymandatoryThe VA Rating of this PDR (all phases)
1.3.6.1.4.1.232.165.4.1.8ScalarpdrNominalOutputVoltageread-onlymandatoryThe nominal Output Voltage may differ from the nominal Input Voltage if the PDR has an input transformer
1.3.6.1.4.1.232.165.4.1.9ScalarpdrNumPhasesread-onlymandatoryThe number of phases for this PDR
1.3.6.1.4.1.232.165.4.1.10ScalarpdrNumPanelsread-onlymandatoryThe number of panels or subfeeds in this PDR
1.3.6.1.4.1.232.165.4.1.11ScalarpdrNumBreakersread-onlymandatoryThe number of breakers in this PDR
1.3.6.1.4.1.232.165.4.2NodepdrPanel
1.3.6.1.4.1.232.165.4.2.1TablepdrPanelTablenot-accessiblemandatoryAggregate Object with number of entries equal to pdrNumPanels
1.3.6.1.4.1.232.165.4.2.1.1RowpdrPanelEntrynot-accessiblemandatoryThe panel table entry containing all power parameters for each panel.
1.3.6.1.4.1.232.165.4.2.1.1.1ColumnpdrPanelIndexread-onlymandatoryIndex for the pdrPanelEntry table.
1.3.6.1.4.1.232.165.4.2.1.1.2ColumnpdrPanelFrequencyread-onlymandatoryThe present frequency reading for the panel voltage.
1.3.6.1.4.1.232.165.4.2.1.1.3ColumnpdrPanelPowerread-onlymandatoryThe present power of the panel.
1.3.6.1.4.1.232.165.4.2.1.1.4ColumnpdrPanelRatedCurrentread-onlymandatoryThe present rated current of the panel.
1.3.6.1.4.1.232.165.4.2.1.1.5ColumnpdrPanelMonthlyKWHread-onlymandatoryThe accumulated KWH for this panel since the beginning of this calendar month or since the last reset.
1.3.6.1.4.1.232.165.4.2.1.1.6ColumnpdrPanelYearlyKWHread-onlymandatoryThe accumulated KWH for this panel since the beginning of this calendar year or since the last reset.
1.3.6.1.4.1.232.165.4.2.1.1.7ColumnpdrPanelTotalKWHread-onlymandatoryThe accumulated KWH for this panel since it was put into service or since the last reset.
1.3.6.1.4.1.232.165.4.2.1.1.8ColumnpdrPanelVoltageAread-onlymandatoryThe measured panel output voltage.
1.3.6.1.4.1.232.165.4.2.1.1.9ColumnpdrPanelVoltageBread-onlymandatoryThe measured panel output voltage.
1.3.6.1.4.1.232.165.4.2.1.1.10ColumnpdrPanelVoltageCread-onlymandatoryThe measured panel output voltage.
1.3.6.1.4.1.232.165.4.2.1.1.11ColumnpdrPanelCurrentAread-onlymandatoryThe measured panel output current.
1.3.6.1.4.1.232.165.4.2.1.1.12ColumnpdrPanelCurrentBread-onlymandatoryThe measured panel output current.
1.3.6.1.4.1.232.165.4.2.1.1.13ColumnpdrPanelCurrentCread-onlymandatoryThe measured panel output current.
1.3.6.1.4.1.232.165.4.2.1.1.14ColumnpdrPanelLoadAread-onlymandatoryThe percentage of load is the ratio of each output current to the rated output current to the panel.
1.3.6.1.4.1.232.165.4.2.1.1.15ColumnpdrPanelLoadBread-onlymandatoryThe percentage of load is the ratio of each output current to the rated output current to the panel.
1.3.6.1.4.1.232.165.4.2.1.1.16ColumnpdrPanelLoadCread-onlymandatoryThe percentage of load is the ratio of each output current to the rated output current to the panel.
1.3.6.1.4.1.232.165.4.3NodepdrBreaker
1.3.6.1.4.1.232.165.4.3.1TablepdrBreakerTablenot-accessiblemandatoryList of breaker table entries. The number of entries is given by pdrNumBreakers for this panel.
1.3.6.1.4.1.232.165.4.3.1.1RowpdrBreakerEntrynot-accessiblemandatoryAn entry containing information applicable to a particular output breaker of a particular panel.
1.3.6.1.4.1.232.165.4.3.1.1.1ColumnpdrBreakerIndexread-onlymandatoryThe index of breakers. 42 breakers in each panel, arranged in odd and even columns
1.3.6.1.4.1.232.165.4.3.1.1.2ColumnpdrBreakerPanelread-onlymandatoryThe index of panel that these breakers are installed on.
1.3.6.1.4.1.232.165.4.3.1.1.3ColumnpdrBreakerNumPositionread-onlymandatoryThe position of this breaker in the panel, 1-phase breaker or n-m breaker for 2-phase or n-m-k breaker for 3-phase.
1.3.6.1.4.1.232.165.4.3.1.1.4ColumnpdrBreakerNumPhasesread-onlymandatoryThe number of phase for this particular breaker.
1.3.6.1.4.1.232.165.4.3.1.1.5ColumnpdrBreakerNumSequenceread-onlymandatoryThe sequence of this breaker. i.e. 1 for single phase 1,2 for 2-phase or 1,2,3 for 3-phase.
1.3.6.1.4.1.232.165.4.3.1.1.6ColumnpdrBreakerRatedCurrentread-onlymandatoryThe rated current in Amps for this particular breaker.
1.3.6.1.4.1.232.165.4.3.1.1.7ColumnpdrBreakerMonthlyKWHread-onlymandatoryThe accumulated KWH for this breaker since the beginning of this calendar month or since the last reset.
1.3.6.1.4.1.232.165.4.3.1.1.8ColumnpdrBreakerYearlyKWHread-onlymandatoryThe accumulated KWH for this breaker since the beginning of this calendar year or since the last reset.
1.3.6.1.4.1.232.165.4.3.1.1.9ColumnpdrBreakerTotalKWHread-onlymandatoryThe accumulated KWH for this breaker since it was put into service or since the last reset.
1.3.6.1.4.1.232.165.4.3.1.1.10ColumnpdrBreakerCurrentread-onlymandatoryThe measured output current for this breaker Current.
1.3.6.1.4.1.232.165.4.3.1.1.11ColumnpdrBreakerCurrentPercentread-onlymandatoryThe ratio of output current over rated current for each breaker.
1.3.6.1.4.1.232.165.4.3.1.1.12ColumnpdrBreakerPowerread-onlymandatoryThe power for this breaker in Watts.
1.3.6.1.4.1.232.165.4.3.1.1.13ColumnpdrBreakerPercentWarningread-onlymandatoryThe percentage of Warning set for this breaker.
1.3.6.1.4.1.232.165.4.3.1.1.14ColumnpdrBreakerPercentOverloadread-onlymandatoryThe percentage of Overload set for this breaker.
1.3.6.1.4.1.232.165.5Nodempdu
1.3.6.1.4.1.232.165.5NodetrapTestTest trap sent to a trap receiver to check proper reception of traps
1.3.6.1.4.1.232.165.5.1NodempduIdent
1.3.6.1.4.1.232.165.5.1.1ScalarmpduNumMPDUread-onlymandatoryThe number of Modular PDUs (Core) detected.
1.3.6.1.4.1.232.165.5.1.2TablempduIdentTablenot-accessiblemandatoryIndexed by mpduNumMPDU. So aggregate objects for each entry equal to mpduNumMPDU before go to the next entry. i.e if 4 MPDU detected, display 4 indexes, 4 Manu…
1.3.6.1.4.1.232.165.5.1.2.1RowmpduIdentEntrynot-accessiblemandatoryThe table entry containing the identifications of each MPDU as well as names of PDR panel, location of MPDU in a Data Center.
1.3.6.1.4.1.232.165.5.1.2.1.1ColumnmpduIdentIndexread-onlymandatoryIndex for the MpduIdentEntry table. Start with 1
1.3.6.1.4.1.232.165.5.1.2.1.2ColumnmpduManufacturerread-onlymandatoryThe Core PDU manufacturer. StringLength=[21]
1.3.6.1.4.1.232.165.5.1.2.1.3ColumnmpduModelread-onlymandatoryThe Core PDU model, marketing name. StringLength=[40].
1.3.6.1.4.1.232.165.5.1.2.1.4ColumnmpduNameread-onlymandatoryThe Core PDU name, descriptive name or hostname. StringLength=[16].
1.3.6.1.4.1.232.165.5.1.2.1.5ColumnmpduFirmwareVersionread-onlymandatoryThe Core PDU firmware version(s). StringLength=[12].
1.3.6.1.4.1.232.165.5.1.2.1.6ColumnmpduHardwareVersionread-onlymandatoryThe Core PDU hardware version. StringLength=[8].
1.3.6.1.4.1.232.165.5.1.2.1.7ColumnmpduPartNumberread-onlymandatoryThe Core PDU part number. StringLength=[21].
1.3.6.1.4.1.232.165.5.1.2.1.8ColumnmpduSerialNumberread-onlymandatoryThe PDU external serial number. StringLength=[21].
1.3.6.1.4.1.232.165.5.1.2.1.9ColumnmpduUUIDread-onlymandatoryThe PDU's UUID equals PN add SN then canonical conversion. StringLength=[37].
1.3.6.1.4.1.232.165.5.1.2.1.10ColumnmpduIPread-onlymandatoryThe PDU's assigned IP. StringLength=[16].
1.3.6.1.4.1.232.165.5.1.2.1.11ColumnmpduMACAddressread-onlymandatoryThe Core PDU MAC address. StringLength=[18].
1.3.6.1.4.1.232.165.5.1.2.1.12ColumnmpduControlStatusread-onlymandatoryThe Core PDU Control Status: master or slave units. StringLength=[31].
1.3.6.1.4.1.232.165.5.1.2.1.13ColumnmpduRegionread-onlymandatoryThe PDU's Region: NA, Intl, Japan... StringLength=[7].
1.3.6.1.4.1.232.165.5.1.2.1.14ColumnmpduTyperead-onlymandatoryThe PDU's Type: Delta, Wye, single, Wye+lowline. StringLength=[24].
1.3.6.1.4.1.232.165.5.1.2.1.15ColumnmpduPowerRatingread-onlymandatoryThe PDU's Power Rating in KVA (Name Plate). Value is presented in 1/100 of the KVA. i.e. 1750 means 17.50 KVA
1.3.6.1.4.1.232.165.5.1.2.1.16ColumnmpduInputRatingread-onlymandatoryThe PDU's Input Current Rating in A (Name Plate)
1.3.6.1.4.1.232.165.5.1.2.1.17ColumnmpduInputPlugread-onlymandatoryThe PDU's Input Plug: IEC60309 516P6,NEMA L15-30P... StringLength=[16].
1.3.6.1.4.1.232.165.5.1.2.1.18ColumnmpduNumBreakersread-onlymandatoryThe number of breakers used in each MPDU (6 by default).
1.3.6.1.4.1.232.165.5.1.2.1.19ColumnmpduNumOutletread-onlymandatoryThe number of outlets of each MPDU (6 by default).
1.3.6.1.4.1.232.165.5.1.2.1.20ColumnmpduUHeightread-onlymandatoryThe MPDU U Height 1U or 2 U (1U by default).
1.3.6.1.4.1.232.165.5.1.2.1.21ColumnmpduRedundantStatusread-onlymandatoryStatus of Core PDU in paired or not: Stand-alone or Redundant. StringLength=[12].
1.3.6.1.4.1.232.165.5.1.2.1.22ColumnmpduNumSmartExtBarread-onlymandatorytotal number of detected Smart Sticks connecting to each PDU.
1.3.6.1.4.1.232.165.5.1.2.1.23ColumnmpduPanelNameread-onlymandatoryName of Panel that was entered by customer in GUI. StringLength=[50].
1.3.6.1.4.1.232.165.5.1.2.1.24ColumnmpduPanelBreakerNameread-onlymandatoryName of breakers or Panel Position entered by customer in GUI. StringLength=[50].
1.3.6.1.4.1.232.165.5.1.2.1.25ColumnmpduPanelBreakerRatingread-onlymandatoryBreaker rating of the PDR Panel.
1.3.6.1.4.1.232.165.5.1.2.1.26ColumnmpduACFeedNameread-onlymandatoryit would be A, B, Red, or White... StringLength=[50].
1.3.6.1.4.1.232.165.5.1.2.1.27ColumnmpduFloorNameread-onlymandatoryName of building floor entered by customer in GUI. StringLength=[50].
1.3.6.1.4.1.232.165.5.1.2.1.28ColumnmpduRoomNameread-onlymandatoryName of the room entered by customer in GUI. StringLength=[50].
1.3.6.1.4.1.232.165.5.1.2.1.29ColumnmpduRowread-onlymandatoryData Center Row entered by customer in GUI. StringLength=[11].
1.3.6.1.4.1.232.165.5.1.2.1.30ColumnmpduRowPositionread-onlymandatoryPosition in Row entered by customer in GUI. Null will be returned if not detected. StringLength=[11].
1.3.6.1.4.1.232.165.5.1.2.1.31ColumnmpduRackNameread-onlymandatoryName of the Rack entered by customer in GUI. Null will be returned if not detected. StringLength=[50].
1.3.6.1.4.1.232.165.5.1.2.1.32ColumnmpduRackHeightread-onlymandatoryRack Type (22U, 42U, 50U...). Null will be returned if not detected. StringLength=[3].
1.3.6.1.4.1.232.165.5.1.2.1.33ColumnmpduRackIDread-onlymandatoryAn unique ID to identify a rack, i.e. Rack SN. Null will be returned if not detected. StringLength=[50].
1.3.6.1.4.1.232.165.5.1.2.1.34ColumnmpduUPositionread-onlymandatoryPDU Rack bottom U Start position, core U position. Null will be returned if not detected.
1.3.6.1.4.1.232.165.5.1.2.1.35ColumnmpduPairedPDUUUIDread-onlymandatoryUUID of the PDU paired with this one. Null will be returned if not detected. StringLength=[50].
1.3.6.1.4.1.232.165.5.1.2.1.36ColumnmpduPairedPDUIPread-onlymandatoryIP address of the PDU paired with this one. Null will be returned if not detected. StringLength=[16].
1.3.6.1.4.1.232.165.5.1.2.1.37ColumnmpduInstalledLocationread-onlymandatory0=Left 0U side area or rack frame, 1= Right 0U side area or rack frame, 2= front RETMA rail, 3=back RETMA rail) - spatial location. A value of -1 will be retur…
1.3.6.1.4.1.232.165.5.1.2.1.38ColumnmpduTotalPowerWattread-onlymandatoryThe total power for the whole iPDU in Watts. A value of -1 will be returned if the power is unable to be calculated.
1.3.6.1.4.1.232.165.5.1.2.1.39ColumnmpduTotalPowerVAread-onlymandatoryThe total power for the whole iPDU in VA. A value of -1 will be returned if the power is unable to be calculated.
1.3.6.1.4.1.232.165.5.1.2.1.40ColumnmpduTotalPercentLoadread-onlymandatoryThe whole iPDU's load in percent of rated capacity. Value is presented in 1/10 of the percentage i.e. 125 is 12.5%. A value of -1 will be returned if the curre…
1.3.6.1.4.1.232.165.5.1.2.1.41ColumnmpduRegionalNominalVoltageread-onlymandatoryvalue is either America(208V), Japan(202V) or blank for International Model
1.3.6.1.4.1.232.165.5.2NodempduOutput
1.3.6.1.4.1.232.165.5.2.1TablempduOutputTablenot-accessiblemandatoryIndexed by mpduNumOutlet. So aggregate objects for each entry equal to (mpduNumMPDU multiplies mpduNumOutlet) before go to the next entry. i.e if 4 MPDU detect…
1.3.6.1.4.1.232.165.5.2.1.1RowmpduOutputEntrynot-accessiblemandatoryThe output table entry containing the voltage, current, PF, percent load, VA, Watts for the Modular PDU.
1.3.6.1.4.1.232.165.5.2.1.1.1ColumnmpduOutputIndexread-onlymandatoryIndex for the MpduOutputEntry table.
1.3.6.1.4.1.232.165.5.2.1.1.2ColumnmpduOutputStatusread-onlymandatoryThe overall status of the device: off, on, problem. StringLength=[7].
1.3.6.1.4.1.232.165.5.2.1.1.3ColumnmpduOutputBreakerRatingread-onlymandatoryThe rating of each MPDU Output in Ampere.
1.3.6.1.4.1.232.165.5.2.1.1.4ColumnmpduOutputSmartDeviceread-onlymandatoryA smart cord device detected: False, True. StringLength=[5].
1.3.6.1.4.1.232.165.5.2.1.1.5ColumnmpduOutputPercentLoadread-onlymandatoryThe MPDU's each output load in percent of rated capacity. Value is presented in 1/10 of the percentage i.e. 125 is 12.5%. A value of -1 will be returned if the…
1.3.6.1.4.1.232.165.5.2.1.1.6ColumnmpduOutputVoltageread-onlymandatoryThe measured output voltage from the PDU meters in volts. Value is presented in 1/10 of the Volt i.e. 2095 is 209.5 V. A value of -1 will be returned if the vo…
1.3.6.1.4.1.232.165.5.2.1.1.7ColumnmpduOutputCurrentread-onlymandatoryThe measured output current from the PDU meters in amps. Value is presented in 1/100 of the Ampere i.e. 175 is 1.75 A. A value of -1 will be returned if the cu…
1.3.6.1.4.1.232.165.5.2.1.1.8ColumnmpduOutputPowerVAread-onlymandatoryThe total VA load (VI) measured on the PDU in VA. A value of -1 will be returned if the power is unable to be calculated.
1.3.6.1.4.1.232.165.5.2.1.1.9ColumnmpduOutputPowerWattread-onlymandatoryThe total power load measured on the PDU in Watts. A value of -1 will be returned if the power is unable to be calculated.
1.3.6.1.4.1.232.165.5.2.1.1.10ColumnmpduOutputPowerFactorread-onlymandatoryThe power factor is presented in 1/100 of the unit i.e. 98 is 0.98. A value of -1 will be returned if the power factor is unable to be measured.
1.3.6.1.4.1.232.165.5.2.1.1.11ColumnmpduOutputWarningThresholdread-onlymandatoryReport the User-set threshhold limit for Warning in percentage
1.3.6.1.4.1.232.165.5.2.1.1.12ColumnmpduOutputCriticalThresholdread-onlymandatoryReport the User-set threshhold limit for Critical in percentage
1.3.6.1.4.1.232.165.5.2.1.1.13ColumnmpduOutputPowerWattHourread-onlymandatorySupport Billing Grade Energy Metering in Watt-Hour. A value of -1 will be returned if the power is unable to be calculated.
1.3.6.1.4.1.232.165.5.3NodempduDeviceIdent
1.3.6.1.4.1.232.165.5.3.1TablempduDeviceIdentTablenot-accessiblemandatoryIndexed by mpduNumOutlet. So aggregate objects for each entry equal to (mpduNumMPDU multiplies mpduNumOutlet) before go to the next entry. i.e if 4 MPDU detect…
1.3.6.1.4.1.232.165.5.3.1.1RowmpduDeviceIdentEntrynot-accessiblemandatoryThe ident table entry containing the name, model, manufacturer, firmware version, part number... for each smart device, null value for unknown device.
1.3.6.1.4.1.232.165.5.3.1.1.1ColumnmpduDeviceIdentIndexread-onlymandatoryIndex is based on the total number of Smart Extension Bars plus smart devices (with smart power cord i.e. blades) detected.
1.3.6.1.4.1.232.165.5.3.1.1.2ColumnmpduDeviceStatusread-onlymandatoryThe overall status of the device: off, on, problem. StringLength=[8].
1.3.6.1.4.1.232.165.5.3.1.1.3ColumnmpduDeviceUIDStatusread-onlymandatoryThe overall status of the device UID: off, on, blink. StringLength=[8].
1.3.6.1.4.1.232.165.5.3.1.1.4ColumnmpduDeviceNumOutletread-onlymandatoryThe number of outlets of detected the device. This variable indicates the number of rows in the breakers table. Default is 5
1.3.6.1.4.1.232.165.5.3.1.1.5ColumnmpduDeviceUHeightread-onlymandatoryThe Unit height of ext bar or device. Some device supports non-integer. Present value x100, when read back, divided by 100 to get 2 decimal points.
1.3.6.1.4.1.232.165.5.3.1.1.6ColumnmpduDevicePowerRatingread-onlymandatoryThe device's Power Rating in VA. Null will be returned if not detected. StringLength=[8].
1.3.6.1.4.1.232.165.5.3.1.1.7ColumnmpduDeviceManufacturerread-onlymandatoryThe Device Manufacturer Name (e.g. Hewlett-Packard). Null will be returned if not detected. StringLength=[16].
1.3.6.1.4.1.232.165.5.3.1.1.8ColumnmpduDeviceTyperead-onlymandatoryThe Device's Type: Ext Bar, server, or network device... StringLength=[16].
1.3.6.1.4.1.232.165.5.3.1.1.9ColumnmpduDeviceModelread-onlymandatoryThe Device Model is Managed or Non-managed Ext Bar. Null will be returned if not detected. StringLength=[24].
1.3.6.1.4.1.232.165.5.3.1.1.10ColumnmpduDeviceNameread-onlymandatoryThe string identify the Device. i.e. 'BAR#1' (descriptive name) Null will be returned if not detected. StringLength=[32].
1.3.6.1.4.1.232.165.5.3.1.1.11ColumnmpduDeviceFirmwareVersionread-onlymandatoryThe firmware revision level of Sm Ext Bar. Null will be returned if not detected. StringLength=[8].
1.3.6.1.4.1.232.165.5.3.1.1.12ColumnmpduDeviceHardwareVersionread-onlymandatoryThe hardware version of Sm Ext Bar. Null will be returned if not detected. StringLength=[8].
1.3.6.1.4.1.232.165.5.3.1.1.13ColumnmpduDevicePartNumberread-onlymandatoryThe device's part number. Null will be returned if not detected. StringLength=[21].
1.3.6.1.4.1.232.165.5.3.1.1.14ColumnmpduDeviceSerialNumberread-onlymandatoryThe device's serial number. Null will be returned if not detected. StringLength=[21].
1.3.6.1.4.1.232.165.5.3.1.1.15ColumnmpduDeviceUUIDread-onlymandatoryThe device's UUID. Null will be returned if not detected. StringLength=[37].
1.3.6.1.4.1.232.165.5.3.1.1.16ColumnmpduDeviceIPread-onlymandatoryThe device's IP Address. Null will be returned if not detected. StringLength=[16].
1.3.6.1.4.1.232.165.5.3.1.1.17ColumnmpduDeviceMACread-onlymandatoryThe device mgmt processor MAC Address. Null will be returned if not detected. StringLength=[18].
1.3.6.1.4.1.232.165.5.3.1.1.18ColumnmpduDevicePSUSlotNoread-onlymandatoryDevice power supply logical slot number.
1.3.6.1.4.1.232.165.5.3.1.1.19ColumnmpduDeviceUPositionread-onlymandatoryDevice U start position.
1.3.6.1.4.1.232.165.5.3.1.1.20ColumnmpduDeviceDetectionThresholdread-onlymandatoryRead device detection threshold between 10 and 50mA.
1.3.6.1.4.1.232.165.5.4NodempduSmExtBarOutlet
1.3.6.1.4.1.232.165.5.4.1TablempduSmExtBarOutletTablenot-accessiblemandatoryIndexed by mpduDeviceNumOutlet. So aggregate objects for each entry equal to (mpduNumMPDU multiplies mpduNumOutlet multiplies mpduDeviceNumOutlet) before go to…
1.3.6.1.4.1.232.165.5.4.1.1RowmpduSmExtBarOutletEntrynot-accessiblemandatoryEntries contain status, measurements for each outlet (no PowerVA) Display null if it can't be measured or no device detected.
1.3.6.1.4.1.232.165.5.4.1.1.1ColumnmpduSmExtBarOutletIndexread-onlymandatoryThe Index of Smart Extension Bar.
1.3.6.1.4.1.232.165.5.4.1.1.2ColumnmpduSmExtBarOutletStatusread-onlymandatoryThe overall status of the Smart Extension Bar's outlet: off, on, problem... StringLength=[3].
1.3.6.1.4.1.232.165.5.4.1.1.3ColumnmpduSmExtBarOutletUIDStatusread-onlymandatoryThe overall status of the Smart Extension Bar's UID: off, on, blink... StringLength=[8].
1.3.6.1.4.1.232.165.5.4.1.1.4ColumnmpduSmExtBarOutletRatingread-onlymandatorySm Ext Bar Outlet's Rating in Amp. A value of -1 will be returned if the stick is unable to detect. StringLength=[8].
1.3.6.1.4.1.232.165.5.4.1.1.5ColumnmpduSmExtBarOutletVoltageread-onlymandatoryThe SM Ext Bar voltage in volts. Value is presented 1/10 of the Volt i.e. 2098 means 209.8 V. A value of -1 will be returned if the voltage is unable to be mea…
1.3.6.1.4.1.232.165.5.4.1.1.6ColumnmpduSmExtBarOutletCurrentread-onlymandatoryThe SM Ext Bar current draw in Amps. Value is presented in 1/100 of the Ampere i.e. 127 means 1.27 A. A value of -1 will be returned if the current is unable t…
1.3.6.1.4.1.232.165.5.4.1.1.7ColumnmpduSmExtBarOutletPowerWattread-onlymandatoryThe Sm Ext Bar's Power measured in Watts. A value of -1 will be returned if the power is unable to be measured.
1.3.6.1.4.1.232.165.5.4.1.1.8ColumnmpduSmExtBarOutletPowerFactorread-onlymandatoryThe outlet's power factor in 0.01 unit. It is presented in 1/100 of the unit. i.e. 98 means 0.98. A value of -1 will be returned if the voltage is unable to be…
1.3.6.1.4.1.232.165.5.4.1.1.9ColumnmpduSmExtBarOutletDeviceNameread-onlymandatoryThe Device (Blade/Server/Storage) Name that connects to this Sm Ext Bar Outlet. Null will be returned if not detected. StringLength=[50].
1.3.6.1.4.1.232.165.5.4.1.1.10ColumnmpduSmExtBarOutletDeviceUUIDread-onlymandatoryThe Device (Blade/Server/Storage) UUID that connects to this Sm Ext Bar Outlet. Null will be returned if not detected. StringLength=[37].
1.3.6.1.4.1.232.165.5.4.1.1.11ColumnmpduSmExtBarOutletDeviceProductread-onlymandatoryThe Device (Blade/Server/Storage) Model that connects to this Sm Ext Bar Outlet. Null will be returned if not detected. StringLength=[40].
1.3.6.1.4.1.232.165.5.4.1.1.12ColumnmpduSmExtBarOutletDeviceIPread-onlymandatoryThe Device (Blade/Server/Storage) IP of iLO that connects to this Sm Ext Bar Outlet. Null will be returned if not detected. StringLength=[16].
1.3.6.1.4.1.232.165.5.4.1.1.13ColumnmpduSmExtBarOutletAutoDiscoveredread-onlymandatoryBoolean values of 0 or 1. 1 means this Sm Ext Bar Outlet is able to get information from a blade with smart power supply (auto discovery is enabled)...
1.3.6.1.4.1.232.165.5.4.1.1.14ColumnmpduSmExtBarOutletDeviceMACread-onlymandatoryThe Device (Blade/Server/Storage) MAC address that connects to this Sm Ext Bar Outlet. Null will be returned if not detected. StringLength=[18].
1.3.6.1.4.1.232.165.5.4.1.1.15ColumnmpduSmExtBarOutletDeviceSNread-onlymandatoryThe Device (Blade/Server/Storage) Serial Number that connects to this Sm Ext Bar Outlet. Null will be returned if not detected. StringLength=[21].
1.3.6.1.4.1.232.165.5.4.1.1.16ColumnmpduSmExtBarOutletDevicePSSlotNoread-onlymandatoryThe Device (Blade/Server/Storage) Power Supply' Slot Number that connects to this Sm Ext Bar Outlet. A value of -1 will be returned if not detected.
1.3.6.1.4.1.232.165.5.4.1.1.17ColumnmpduSmExtBarOutletDeviceUPositionread-onlymandatoryDevice U start position. A value of -1 will be returned if not detected.
1.3.6.1.4.1.232.165.5.4.1.1.18ColumnmpduSmExtBarOutletDeviceUHeightread-onlymandatoryDevice U height. Enter -1 if not detected. Some device supports non-integer. Present value x100, when read back, divided by 100 to get 2 decimal points.
1.3.6.1.4.1.232.165.5.4.1.1.19ColumnmpduSmExtBarOutletDeviceInstalledLocationread-onlymandatory0=Left 0U side area or rack frame, 1= Right 0U side area or rack frame, 2= front RETMA rail, 3=back RETMA rail) - spatial location. A value of -1 will be retur…
1.3.6.1.4.1.232.165.5.4.1.1.20ColumnmpduSmExtBarOutletPowerWattHourread-onlymandatoryThe Sm Ext Bar's Power measured in Watt-Hour support Billing Grade Energy Metering. A value of -1 will be returned if the power is unable to be measured.
1.3.6.1.4.1.232.165.6NodedeviceTrapInitializationThis trap is sent each time a power device is initialized.
1.3.6.1.4.1.232.165.6Nodeoups
1.3.6.1.4.1.232.165.6.1NodeoupsIdent
1.3.6.1.4.1.232.165.6.1.1ScalaroupsIdentManufacturerread-onlymandatoryThe UPS Manufacturer Name (e.g. Hewlett-Packard).
1.3.6.1.4.1.232.165.6.1.2ScalaroupsIdentModelread-onlymandatoryThe UPS Model such as R-1500 G3.
1.3.6.1.4.1.232.165.6.1.3ScalaroupsIdentSystemFWVersionread-onlymandatoryDisplay System firmware version.
1.3.6.1.4.1.232.165.6.1.4ScalaroupsIdentPowerModuleFWVersionread-onlymandatoryDisplay Power Module firmware version.
1.3.6.1.4.1.232.165.6.1.5ScalaroupsIdentOemCoderead-onlymandatoryA binary code indicating vendor. This should be a ?0x0c? for HP
1.3.6.1.4.1.232.165.6.1.6ScalaroupsIdentSerialNumberread-onlymandatoryGet the UPS Serial Number (i.e. B00123456W).
1.3.6.1.4.1.232.165.6.1.7ScalaroupsIdentPartNumberread-onlymandatoryGet the UPS Part Number (i.e. 204451-B21).
1.3.6.1.4.1.232.165.6.2NodeoupsBattery
1.3.6.1.4.1.232.165.6.2.1ScalaroupsBatTimeRemainingread-onlymandatoryBattery run time in seconds before UPS turns off due to low battery.
1.3.6.1.4.1.232.165.6.2.2ScalaroupsBatVoltageread-onlymandatoryRead the Total Battery voltage.
1.3.6.1.4.1.232.165.6.2.3ScalaroupsBatCapacityread-onlymandatoryBattery percent charge.
1.3.6.1.4.1.232.165.6.2.4ScalaroupsBatAbmStatusread-onlymandatoryGives the status of the Advanced Battery Management; example: batteryResting(3) is the state when the battery is fully charged and none of the other actions (c…
1.3.6.1.4.1.232.165.6.2.5ScalaroupsBatTestStatusread-onlymandatoryBattery Test Status. UPS will support schedule testing only 7, 14, 30, or 60 days. Default is 14 days.
1.3.6.1.4.1.232.165.6.2.6ScalaroupsBatLatestTestDateread-onlymandatoryGet time and date of the latest battery test.
1.3.6.1.4.1.232.165.6.2.7ScalaroupsBatReplacementDateBP1read-onlymandatoryGet the battery replacement date of BP1.
1.3.6.1.4.1.232.165.6.2.8ScalaroupsBatReplacementDateBP2read-onlymandatoryGet the battery replacement date of BP2.
1.3.6.1.4.1.232.165.6.2.9ScalaroupsBatToACDelayread-onlymandatoryGet delay time switching from Battery mode to AC mode in ms. Default is 0ms, unit is increased per 100ms
1.3.6.1.4.1.232.165.6.2.10ScalaroupsBatChargeDelayread-onlymandatoryGet battery charge delay in second. Default is 0 (random) unit is increased per 10sec.
1.3.6.1.4.1.232.165.6.2.11ScalaroupsBatNumModulesread-onlymandatoryNumber of battery modules detected by power unit.
1.3.6.1.4.1.232.165.6.2.12ScalaroupsBatModelread-onlymandatoryReport 1U, 2U, or 3U Battery Pack, both BPs must be the same model.
1.3.6.1.4.1.232.165.6.2.13ScalaroupsBatChargingPowerLevelUtilityread-onlymandatory3 charging power levels: 1100W, 555W, 190W.
1.3.6.1.4.1.232.165.6.2.14ScalaroupsBatChargingPowerLevelGeneratorread-onlymandatory4 charging power levels: 1100W, 555W, 190W, No Charge.
1.3.6.1.4.1.232.165.6.2.15ScalaroupsBatSharedConfigread-onlymandatoryexpect 3 values for shared BP configuration: PU single, PU master, PU slave.
1.3.6.1.4.1.232.165.6.2.16ScalaroupsBatPackFWVerBP1read-onlymandatoryDisplay Battery Pack 1 FW version.
1.3.6.1.4.1.232.165.6.2.17ScalaroupsBatPackFWVerBP2read-onlymandatoryDisplay Battery Pack 2 FW version.
1.3.6.1.4.1.232.165.6.3NodeoupsInput
1.3.6.1.4.1.232.165.6.3.1ScalaroupsInputFrequencyread-onlymandatoryThe utility line frequency in tenths of Hz.
1.3.6.1.4.1.232.165.6.3.2ScalaroupsInputLineBadsread-onlymandatoryThe number of times the Input was out of tolerance in voltage or frequency.
1.3.6.1.4.1.232.165.6.3.3ScalaroupsInputNumPhasesread-onlymandatory
1.3.6.1.4.1.232.165.6.3.4TableoupsInputTablenot-accessiblemandatoryAggregate Object with number of entries equal to NumPhases and including the UpsInput group.
1.3.6.1.4.1.232.165.6.3.4.1RowoupsInputEntrynot-accessiblemandatoryThe input table entry containing the current, voltage, etc.
1.3.6.1.4.1.232.165.6.3.4.1.1ColumnoupsInputPhaseread-onlymandatoryThe number of the phase. Serves as index for input table.
1.3.6.1.4.1.232.165.6.3.4.1.2ColumnoupsInputVoltageread-onlymandatoryThe measured input voltage from the UPS meters in volts.
1.3.6.1.4.1.232.165.6.3.4.1.3ColumnoupsInputCurrentread-onlymandatoryThe measured input current from the UPS meters in amps.
1.3.6.1.4.1.232.165.6.3.4.1.4ColumnoupsInputWattsread-onlymandatoryThe measured input power in watts.
1.3.6.1.4.1.232.165.6.3.5ScalaroupsInputPowerFactorread-onlymandatoryThe measured real Input power factor with 2 decimals.
1.3.6.1.4.1.232.165.6.3.6ScalaroupsInputDBTyperead-onlymandatoryRead the input Distribution Box type: 1- 480V-Y (US-5W NEMA plugs), 2- 480V-V (US-5W IEC plugs), 3- 415V-Y (EURO-5W IEC plugs), 4- 415V-Y (US/INTL-5W IEC plugs…
1.3.6.1.4.1.232.165.6.3.7ScalaroupsInputUpperVoltageread-onlymandatoryRead the upper voltage range, 5 to 10 percent above the nominal voltage. Factory default is 10 percent.
1.3.6.1.4.1.232.165.6.3.8ScalaroupsInputLowerVoltageread-onlymandatoryRead the lower voltage range, 5 to 15 percent below the nominal voltage. Factory default is -15 percent.
1.3.6.1.4.1.232.165.6.3.9ScalaroupsGeneratorDetectionread-writemandatoryATS sets a value of 1 to signal UPS that a generator is started so the UPS will charge Battery Pack using a different setting while it's on generator (intent t…
1.3.6.1.4.1.232.165.6.3.10ScalaroupsInputWithGeneratorread-onlymandatoryA value of 1 when user known for sure Input has no Generator backup; a value of 2 tells Input Source could be from either Utility or Generator.
1.3.6.1.4.1.232.165.6.4NodeoupsOutput
1.3.6.1.4.1.232.165.6.4.1ScalaroupsOutputLoadread-onlymandatoryThe total UPS output load in percentage of rated capacity.
1.3.6.1.4.1.232.165.6.4.2ScalaroupsOutputFrequencyread-onlymandatoryThe measured UPS output frequency in tenths of Hz.
1.3.6.1.4.1.232.165.6.4.3ScalaroupsOutputNumPhasesread-onlymandatoryThe number of metered output phases, serves as the table index.
1.3.6.1.4.1.232.165.6.4.4TableoupsOutputTablenot-accessiblemandatoryThe Aggregate Object with number of entries equal to NumPhases and including the UpsOutput group.
1.3.6.1.4.1.232.165.6.4.4.1RowoupsOutputEntrynot-accessiblemandatoryOutput Table Entry containing voltage, current, etc.
1.3.6.1.4.1.232.165.6.4.4.1.1ColumnoupsOutputPhaseread-onlymandatoryThe number {1..3} of the output phase.
1.3.6.1.4.1.232.165.6.4.4.1.2ColumnoupsOutputVoltageread-onlymandatoryThe measured output voltage from the UPS metering in volts.
1.3.6.1.4.1.232.165.6.4.4.1.3ColumnoupsOutputCurrentread-onlymandatoryThe measured UPS output current in amps.
1.3.6.1.4.1.232.165.6.4.4.1.4ColumnoupsOutputWattsread-onlymandatoryThe measured real output power in watts.
1.3.6.1.4.1.232.165.6.4.4.1.5ColumnoupsOutputLoadPerPhaseread-onlymandatoryThe UPS output load per phase in percentage of rated capacity.
1.3.6.1.4.1.232.165.6.4.5ScalaroupsOutputPowerFactorread-onlymandatoryThe measured real output power factor with 2 decimals.
1.3.6.1.4.1.232.165.6.4.6ScalaroupsOutputSourceread-onlymandatoryIndicate the source that UPS operating from when providing output.
1.3.6.1.4.1.232.165.6.5NodeoupsMonitor
1.3.6.1.4.1.232.165.6.5.1ScalaroupsMonitorAmbientTempread-onlymandatoryThe reading of the internal PU Ambient temperature.
1.3.6.1.4.1.232.165.6.5.2ScalaroupsMonitorBypassSCRTempread-onlymandatoryThe reading of the internal PU Bypass SCR temperature.
1.3.6.1.4.1.232.165.6.5.3ScalaroupsMonitorDDTempread-onlymandatoryThe reading of the internal PU DD temperature.
1.3.6.1.4.1.232.165.6.5.4ScalaroupsMonitorInverterTempread-onlymandatoryThe reading of the internal PU DD temperature.
1.3.6.1.4.1.232.165.6.5.5ScalaroupsMonitorChargerTempread-onlymandatoryThe reading of the internal PU Charger temperature.
1.3.6.1.4.1.232.165.6.5.6ScalaroupsMonitorBP1Tempread-onlymandatoryDisplay Battery Pack 1 Temeprature in F. If BP1 not connected the PU will return 255 and displayed as -not connect-
1.3.6.1.4.1.232.165.6.5.7ScalaroupsMonitorBP2Tempread-onlymandatoryDisplay Battery Pack 2 Temperature in F. If BP2 not connected the PU will return 255 and displayed as -not connect-
1.3.6.1.4.1.232.165.6.5.8ScalaroupsMonitorRestartDelayread-onlymandatoryThe reading of the AC Turn On Delay (Restart Delay). The value can be changed via front LCD Menu or inserted Module GUI. Default is 0ms, unit is increased per …
1.3.6.1.4.1.232.165.6.5.9ScalaroupsMonitorACCLoadLevelread-onlymandatoryRead the set load level that ACC would be active from 0 to this percentage. Default is 20 percent. Select 0 to set it as Always On
1.3.6.1.4.1.232.165.6.5.10ScalaroupsMonitorOperatingModeread-onlymandatoryCheck if UPS is normal op, or on bypass, on inverter or ACC Active,
1.3.6.1.4.1.232.165.6.5.11ScalaroupsMonitorOperationTyperead-onlymandatoryCheck if UPS is operating as an UPS or ACC (PU only, no BP).
1.3.6.1.4.1.232.165.6.5.12ScalaroupsTestTrapread-writemandatorySetting startTestTrap to 1 will initiate a TrapTest is sent out from Management Module. All other set values are invalid.
1.3.6.1.4.1.232.165.6.5.13ScalaroupsOnGenDurationread-writemandatoryWhen read, show the current On-Generator Duration set by user on UPS LCD or GUI .
1.3.6.1.4.1.232.165.6.5.14ScalaroupsRuntimeLimitationread-writemandatoryshow the current setting for Runtime Limitation. When enable, it can last for 70sec or 3min.
1.3.6.1.4.1.232.165.6.6NodeoupsRackDiscovery
1.3.6.1.4.1.232.165.6.6.1ScalaroupsRackTagVersionread-onlymandatoryGet the 1-wire contact FW version from EEPROM's Tag Version. Initial tag is 01
1.3.6.1.4.1.232.165.6.6.2ScalaroupsRackIDread-onlymandatoryGet 10-digit Serial Number from the Location Discovery Strip mount in the front of the rack
1.3.6.1.4.1.232.165.6.6.3ScalaroupsRackPartNumberread-onlymandatoryGet 10 or 12-digit Part Number xxxxxx-001 from the Location Discovery Strip mount in the front of the rack
1.3.6.1.4.1.232.165.6.6.4ScalaroupsRackProductDescriptionread-onlymandatoryGet spatial data of rack: description of the Rack Name.
1.3.6.1.4.1.232.165.6.6.5ScalaroupsRackEncULocationread-onlymandatoryTell where the Location Discovery Strip is mounted in the rack. B for Back, F for Front, L for Left and R for Right.
1.3.6.1.4.1.232.165.6.6.6ScalaroupsRackUHeightread-onlymandatoryGet spatial data of rack: U-height of the rack can be 36U, 42U, or 47U model.
1.3.6.1.4.1.232.165.6.6.7ScalaroupsRackPUUPositionread-onlymandatoryGet the U-position of the PU where it is installed in the rack. The U position range is from 1-50.
1.3.6.1.4.1.232.165.6.6.8ScalaroupsRackPUUHeightread-onlymandatoryGet the U-Height of the Power Unit. PU height is either 1U or 2U.
1.3.6.1.4.1.232.165.6.6.9ScalaroupsRackBP1UPositionread-onlymandatoryGet the U-Position of the Battery Pack 1, installed right below the PU. Range is from 1 to 50.
1.3.6.1.4.1.232.165.6.6.10ScalaroupsRackBP1UHeightread-onlymandatoryGet the U-Height of the BP 1. BP is either 1U, 2U, and 3U
1.3.6.1.4.1.232.165.6.6.11ScalaroupsRackBP2UPositionread-onlymandatoryGet the U-Position of the Battery Pack 2, installed right below the BP1. Range is from 1 to 50.
1.3.6.1.4.1.232.165.6.6.12ScalaroupsRackBP2UHeightread-onlymandatoryGet the U-Height of the BP 2. BP is either 1U, 2U, and 3U
1.3.6.1.4.1.232.165.7Nodepdu2
1.3.6.1.4.1.232.165.7.1Nodepdu2Ident
1.3.6.1.4.1.232.165.7.1.1Scalarpdu2NumberPDUread-onlymandatoryThe number of PDUs detected (in its daisy chain).
1.3.6.1.4.1.232.165.7.1.2Tablepdu2IdentTablenot-accessiblemandatoryAggregate Object with number of entries equal to pdu2NumberPDU .
1.3.6.1.4.1.232.165.7.1.2.1Rowpdu2IdentEntrynot-accessiblemandatoryThe ident table entry containing the name, model, manufacturer, firmware version, part number, etc.
1.3.6.1.4.1.232.165.7.1.2.1.1Columnpdu2IdentIndexread-onlymandatoryIndex for the Pdu2IdentEntry table.
1.3.6.1.4.1.232.165.7.1.2.1.2Columnpdu2Nameread-onlymandatoryThe string identify the device in daisy chain. Example PDU A.
1.3.6.1.4.1.232.165.7.1.2.1.3Columnpdu2Modelread-onlymandatoryThe Device Model.
1.3.6.1.4.1.232.165.7.1.2.1.4Columnpdu2Manufacturerread-onlymandatoryThe Device Manufacturer Name (e.g. Hewlett-Packard).
1.3.6.1.4.1.232.165.7.1.2.1.5Columnpdu2FirmwareVersionread-onlymandatoryThe firmware revision level of the device.
1.3.6.1.4.1.232.165.7.1.2.1.6Columnpdu2PartNumberread-onlymandatoryThe device part number. Example AF400A.
1.3.6.1.4.1.232.165.7.1.2.1.7Columnpdu2SerialNumberread-onlymandatoryThe device serial number, 10- or 16-digit.
1.3.6.1.4.1.232.165.7.1.2.1.8Columnpdu2Statusread-onlymandatoryThe overall status of the device. A value of OK(2) indicates the device is operating normally. A value of degraded(3) indicates the device is operating with wa…
1.3.6.1.4.1.232.165.7.1.2.1.9Columnpdu2Controllableread-onlymandatoryThis object indicates whether or not the device is controllable.
1.3.6.1.4.1.232.165.7.1.2.1.10Columnpdu2InputPhaseCountread-onlymandatoryThe number of input phase on this pdu 1,2,3.
1.3.6.1.4.1.232.165.7.1.2.1.11Columnpdu2GroupCountread-onlymandatoryThe number of groups (breakers) on this pdu.
1.3.6.1.4.1.232.165.7.1.2.1.12Columnpdu2OutletCountread-onlymandatoryThe number of outlets in this PDU.
1.3.6.1.4.1.232.165.7.2Nodepdu2Input
1.3.6.1.4.1.232.165.7.2.1Tablepdu2InputTablenot-accessiblemandatoryAggregate Object with number of entries equal to pdu2NumberPDU .
1.3.6.1.4.1.232.165.7.2.1.1Rowpdu2InputEntrynot-accessiblemandatoryThe ident table entry containing the VA, Watts, WH, etc.
1.3.6.1.4.1.232.165.7.2.1.1.1Columnpdu2InputTyperead-onlymandatoryType of input - single phase, split phase, three phase delta, or three phase wye.
1.3.6.1.4.1.232.165.7.2.1.1.2Columnpdu2InputFrequencyread-onlymandatoryThe measured input frequency from the PDU meters in tenths of Hz.
1.3.6.1.4.1.232.165.7.2.1.1.3Columnpdu2InputFrequencyStatusread-onlymandatoryStatus of the measured input frequency relative to the nominal frequency and the admitted tolerance.
1.3.6.1.4.1.232.165.7.2.1.1.4Columnpdu2InputPowerVAread-onlymandatoryA total input VA of all phases. Units are VA. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.2.1.1.5Columnpdu2InputPowerWattsread-onlymandatoryA total input Watts of all phases. Units are Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.2.1.1.6Columnpdu2InputPowerWattHourread-onlymandatoryA total input Watt-Hour value for all phases. Units are WH. This value can be reset to 0 using GUI. In that case, the pdu2InputPowerWattHourTimer will be reset…
1.3.6.1.4.1.232.165.7.2.1.1.7Columnpdu2InputPowerWattHourTimerread-onlymandatoryA Timestamp of when the Total Input WH was last reset.
1.3.6.1.4.1.232.165.7.2.1.1.8Columnpdu2InputPowerFactorread-onlymandatoryAn input PF value. Units are in thousandths, for example a power factor of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value …
1.3.6.1.4.1.232.165.7.2.1.1.9Columnpdu2InputPowerVARread-onlymandatoryAn input VAR value. Units are VAR. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.2.2Tablepdu2InputPhaseTablenot-accessiblemandatoryAggregate Object with number of entries equal to number of PDUs (pdu2NumberPDU) and number of input phase (pdu2InputPhaseCount).
1.3.6.1.4.1.232.165.7.2.2.1Rowpdu2InputPhaseEntrynot-accessiblemandatoryThe input table entry containing the voltage, current, frequency, power for each phase. Entries are given with number of pdu and number of input phase 1, 2, or…
1.3.6.1.4.1.232.165.7.2.2.1.1Columnpdu2InputPhaseIndexread-onlymandatoryIndex for the Pdu2InputEntry table.
1.3.6.1.4.1.232.165.7.2.2.1.2Columnpdu2InputPhaseVoltageMeasTyperead-onlymandatoryValue indicates what input voltage is being measured in this table row - single phase voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phas…
1.3.6.1.4.1.232.165.7.2.2.1.3Columnpdu2InputPhaseVoltageread-onlymandatoryAn input voltage measurement value. Units are millivolts.
1.3.6.1.4.1.232.165.7.2.2.1.4Columnpdu2InputPhaseVoltageThStatusread-onlymandatoryStatus of the measured input voltage relative to the configured thresholds.
1.3.6.1.4.1.232.165.7.2.2.1.5Columnpdu2InputPhaseVoltageThLowerWarningread-onlymandatoryLower warning threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.2.2.1.6Columnpdu2InputPhaseVoltageThLowerCriticalread-onlymandatoryLower critical threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.2.2.1.7Columnpdu2InputPhaseVoltageThUpperWarningread-onlymandatoryUpper warning threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.2.2.1.8Columnpdu2InputPhaseVoltageThUpperCriticalread-onlymandatoryUpper critical threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.2.2.1.9Columnpdu2InputPhaseCurrentMeasTyperead-onlymandatoryWhich input wire is being measured in this table row - single phase, neutral, phase 1, phase 2, or phase 3.
1.3.6.1.4.1.232.165.7.2.2.1.10Columnpdu2InputPhaseCurrentRatingread-onlymandatoryRated current capacity of the input. A negative value indicates that the hardware current capacity is unknown. Units are milliamps.
1.3.6.1.4.1.232.165.7.2.2.1.11Columnpdu2InputPhaseCurrentread-onlymandatoryAn input current measurement value. Units are milliamps.
1.3.6.1.4.1.232.165.7.2.2.1.12Columnpdu2InputPhaseCurrentThStatusread-onlymandatoryStatus of the measured input current relative to the configured thresholds.
1.3.6.1.4.1.232.165.7.2.2.1.13Columnpdu2InputPhaseCurrentThLowerWarningread-onlymandatoryLower warning threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.2.2.1.14Columnpdu2InputPhaseCurrentThLowerCriticalread-onlymandatoryLower critical threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.2.2.1.15Columnpdu2InputPhaseCurrentThUpperWarningread-onlymandatoryUpper warning threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.2.2.1.16Columnpdu2InputPhaseCurrentThUpperCriticalread-onlymandatoryUpper critical threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.2.2.1.17Columnpdu2InputPhaseCurrentCrestFactorread-onlymandatoryCurrent crest factor. Units are in milli, for example a crest factor of 1.414 will be returned as 1414. A negative value indicates that this object is not avai…
1.3.6.1.4.1.232.165.7.2.2.1.18Columnpdu2InputPhaseCurrentPercentLoadread-onlymandatoryCurrent percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this o…
1.3.6.1.4.1.232.165.7.2.2.1.19Columnpdu2InputPhasePowerMeasTyperead-onlymandatoryWhich input wire is being measured in this table row - single phase, neutral, phase 1, phase 2, or phase 3.
1.3.6.1.4.1.232.165.7.2.2.1.20Columnpdu2InputPhasePowerVAread-onlymandatoryAn input VA value. Units are VA. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.2.2.1.21Columnpdu2InputPhasePowerWattsread-onlymandatoryAn input Watts value. Units are Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.2.2.1.22Columnpdu2InputPhasePowerWattHourread-onlymandatoryA Watt-Hour value for each Input phase. Units are WH. This value can be reset to 0 using GUI. In that case, the pdu2InputPhasePowerWattHourTimer will be reset …
1.3.6.1.4.1.232.165.7.2.2.1.23Columnpdu2InputPhasePowerWattHourTimerread-onlymandatoryTimestamp of when input Watt-hours (inputWh) was last reset.
1.3.6.1.4.1.232.165.7.2.2.1.24Columnpdu2InputPhasePowerFactorread-onlymandatoryAn input PF value. Units are in thousandths, for example a power factor of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value …
1.3.6.1.4.1.232.165.7.2.2.1.25Columnpdu2InputPhasePowerVARread-onlymandatoryAn input VAR value. Units are VAR. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.3Nodepdu2Group
1.3.6.1.4.1.232.165.7.3.1Tablepdu2GroupTablenot-accessiblemandatoryAggregate Object with number of entries equal to number of PDUs and number of breakers (pdu2GroupCount).
1.3.6.1.4.1.232.165.7.3.1.1Rowpdu2GroupEntrynot-accessiblemandatoryThe input table entry containing the name, voltages, currents, power, etc.
1.3.6.1.4.1.232.165.7.3.1.1.1Columnpdu2GroupIndexread-onlymandatoryIndex for the Pdu2GroupEntry table.
1.3.6.1.4.1.232.165.7.3.1.1.2Columnpdu2GroupNameread-onlymandatoryA descriptive name for the group.
1.3.6.1.4.1.232.165.7.3.1.1.3Columnpdu2GroupTyperead-onlymandatoryThe type of the group. (5) has no breaker
1.3.6.1.4.1.232.165.7.3.1.1.4Columnpdu2GroupVoltageMeasTyperead-onlymandatoryValue indicates what input voltage is being measured in this table row - single phase voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phas…
1.3.6.1.4.1.232.165.7.3.1.1.5Columnpdu2GroupVoltageread-onlymandatoryUnits are millivolts.
1.3.6.1.4.1.232.165.7.3.1.1.6Columnpdu2GroupVoltageThStatusread-onlymandatoryStatus of the measured group voltage relative to the configured thresholds.
1.3.6.1.4.1.232.165.7.3.1.1.7Columnpdu2GroupVoltageThLowerWarningread-onlymandatoryLower warning threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.3.1.1.8Columnpdu2GroupVoltageThLowerCriticalread-onlymandatoryLower critical threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.3.1.1.9Columnpdu2GroupVoltageThUpperWarningread-onlymandatoryUpper warning threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.3.1.1.10Columnpdu2GroupVoltageThUpperCriticalread-onlymandatoryUpper critical threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.3.1.1.11Columnpdu2groupCurrentRatingread-onlymandatoryRated current capacity of the group. Units are milliamps. A negative value indicates that the hardware current capacity is unknown (it will always be unknown f…
1.3.6.1.4.1.232.165.7.3.1.1.12Columnpdu2GroupCurrentread-onlymandatoryA group current measurement value. Units are milliamps.
1.3.6.1.4.1.232.165.7.3.1.1.13Columnpdu2GroupCurrentThStatusread-onlymandatoryStatus of the measured group current relative to the configured thresholds.
1.3.6.1.4.1.232.165.7.3.1.1.14Columnpdu2GroupCurrentThLowerWarningread-onlymandatoryLower warning threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.3.1.1.15Columnpdu2GroupCurrentThLowerCriticalread-onlymandatoryLower critical threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.3.1.1.16Columnpdu2GroupCurrentThUpperWarningread-onlymandatoryUpper warning threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.3.1.1.17Columnpdu2GroupCurrentThUpperCriticalread-onlymandatoryUpper critical threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.3.1.1.18Columnpdu2GroupCurrentCrestFactorread-onlymandatoryCurrent crest factor. Units are in milli, for example a crest factor of 1.414 will be returned as 1414. A negative value indicates that this object is not avai…
1.3.6.1.4.1.232.165.7.3.1.1.19Columnpdu2GroupCurrentPercentLoadread-onlymandatoryCurrent percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this o…
1.3.6.1.4.1.232.165.7.3.1.1.20Columnpdu2GroupPowerVAread-onlymandatoryA group VA value. Units are VA. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.3.1.1.21Columnpdu2GroupPowerWattsread-onlymandatoryA group Watts value. Units are Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.3.1.1.22Columnpdu2GroupPowerWattHourread-onlymandatoryA Watt-Hour value for each section. Units are WH. This value can be reset to 0 using GUI. In that case, the pdu2GroupPowerWattHourTimer will be reset as well. …
1.3.6.1.4.1.232.165.7.3.1.1.23Columnpdu2GroupPowerWattHourTimerread-onlymandatoryTimestamp of when group Watt-hours (groupWh) was last reset.
1.3.6.1.4.1.232.165.7.3.1.1.24Columnpdu2GroupPowerFactorread-onlymandatoryA group PF value. Units are in thousandths, for example a power factor of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value i…
1.3.6.1.4.1.232.165.7.3.1.1.25Columnpdu2GroupPowerVARread-onlymandatoryA group VAR value. Units are VAR. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.3.1.1.26Columnpdu2GroupOutletCountread-onlymandatoryThe number of outlets in each group (breaker).
1.3.6.1.4.1.232.165.7.3.1.1.27Columnpdu2GroupBreakerStatusread-onlymandatoryOnly applicable to groups with breaker. Indicates whether a breaker is turned off or on.
1.3.6.1.4.1.232.165.7.4Nodepdu2Environment
1.3.6.1.4.1.232.165.7.4.1Tablepdu2EnvProbeTablenot-accessiblemandatoryA list of environment probe (1 per PDU) for temperature, humidity, and contacts. The number of entries is given by number of PDUs in daisy chain.
1.3.6.1.4.1.232.165.7.4.1.1Rowpdu2EnvProbeEntrynot-accessiblemandatoryAggregate entries equal to number of PDUs.
1.3.6.1.4.1.232.165.7.4.1.1.1Columnpdu2TemperatureScaleread-onlymandatoryScale used to return temperature objects.
1.3.6.1.4.1.232.165.7.4.1.1.2Columnpdu2TemperatureCountread-onlymandatoryMax number of temperature measurements (1 per probe).
1.3.6.1.4.1.232.165.7.4.1.1.3Columnpdu2HumidityCountread-onlymandatoryMax number of humidity measurements (1 per probe).
1.3.6.1.4.1.232.165.7.4.1.1.4Columnpdu2ContactCountread-onlymandatoryMax number of contact sensors (1 per probe).
1.3.6.1.4.1.232.165.7.4.2Tablepdu2TemperatureTablenot-accessiblemandatoryA list of temperature probe measurements. The number of entries are given by number of pdu and pdu2TemperatureCount.
1.3.6.1.4.1.232.165.7.4.2.1Rowpdu2TemperatureEntrynot-accessiblemandatoryAn entry for a temperature measurement.
1.3.6.1.4.1.232.165.7.4.2.1.1Columnpdu2TemperatureIndexread-onlymandatoryA unique value for each temperature probe measurement. Its value ranges from 1 to temperatureCount.
1.3.6.1.4.1.232.165.7.4.2.1.2Columnpdu2TemperatureNameread-onlymandatoryA descriptive name for the temperature probe.
1.3.6.1.4.1.232.165.7.4.2.1.3Columnpdu2TemperatureProbeStatusread-onlymandatoryIndicates whether a probe is connected or not.
1.3.6.1.4.1.232.165.7.4.2.1.4Columnpdu2TemperatureValueread-onlymandatoryUnits are in tenths of a degree (either Fahrenheit or Celsius). Divide by ten to get degrees.
1.3.6.1.4.1.232.165.7.4.2.1.5Columnpdu2TemperatureThStatusread-onlymandatoryStatus of the measured temperature relative to the configured thresholds.
1.3.6.1.4.1.232.165.7.4.2.1.6Columnpdu2TemperatureThLowerWarningread-onlymandatoryLower warning threshold. Units are tenths of a degree. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.4.2.1.7Columnpdu2TemperatureThLowerCriticalread-onlymandatoryLower critical threshold. Units are tenths of a degree. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.4.2.1.8Columnpdu2TemperatureThUpperWarningread-onlymandatoryUpper warning threshold. Units are tenths of a degree. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.4.2.1.9Columnpdu2TemperatureThUpperCriticalread-onlymandatoryUpper critical threshold. Units are tenths of a degree. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.4.3Tablepdu2HumidityTablenot-accessiblemandatoryA list of humidity probe measurements. The number of entries are given by number of pdu and pdu2HumidityCount.
1.3.6.1.4.1.232.165.7.4.3.1Rowpdu2HumidityEntrynot-accessiblemandatoryAn entry for a humidity measurement.
1.3.6.1.4.1.232.165.7.4.3.1.1Columnpdu2HumidityIndexread-onlymandatoryA unique value for each humidity probe measurement. Its value ranges from 1 to pdu2HumidityCount per pdu.
1.3.6.1.4.1.232.165.7.4.3.1.2Columnpdu2HumidityNameread-onlymandatoryA descriptive name for the humidity probe.
1.3.6.1.4.1.232.165.7.4.3.1.3Columnpdu2HumidityProbeStatusread-onlymandatoryIndicates whether a probe is connected or not.
1.3.6.1.4.1.232.165.7.4.3.1.4Columnpdu2HumidityValueread-onlymandatoryUnits are tenths of a percent relative humidity. Divide the value by 10 to get %RH.
1.3.6.1.4.1.232.165.7.4.3.1.5Columnpdu2HumidityThStatusread-onlymandatoryStatus of the measured humidity relative to the configured thresholds.
1.3.6.1.4.1.232.165.7.4.3.1.6Columnpdu2HumidityThLowerWarningread-onlymandatoryLower warning threshold. Units are 0.1 %RH. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.4.3.1.7Columnpdu2HumidityThLowerCriticalread-onlymandatoryLower critical threshold. Units are 0.1 %RH. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.4.3.1.8Columnpdu2HumidityThUpperWarningread-onlymandatoryUpper warning threshold. Units are 0.1 %RH. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.4.3.1.9Columnpdu2HumidityThUpperCriticalread-onlymandatoryUpper critical threshold. Units are 0.1 %RH. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.4.4Tablepdu2ContactTablenot-accessiblemandatoryA list of contact sensors. The number of entries are given by number of pdu and pdu2ContactCount.
1.3.6.1.4.1.232.165.7.4.4.1Rowpdu2ContactEntrynot-accessiblemandatoryAn entry for a contact sensor
1.3.6.1.4.1.232.165.7.4.4.1.1Columnpdu2ContactIndexread-onlymandatoryA unique value for each contact sensor. Its value ranges from 1 to contactCount.
1.3.6.1.4.1.232.165.7.4.4.1.2Columnpdu2ContactNameread-onlymandatoryA descriptive name for the contact sensor.
1.3.6.1.4.1.232.165.7.4.4.1.3Columnpdu2ContactProbeStatusread-onlymandatoryIndicates whether a probe is connected or not. Will not be returned if the contact sensor is internal to the ePDU, in that case only contactState should be rea…
1.3.6.1.4.1.232.165.7.4.4.1.4Columnpdu2ContactStateread-onlymandatoryThe state of the contact sensor.
1.3.6.1.4.1.232.165.7.5Nodepdu2Outlet
1.3.6.1.4.1.232.165.7.5.1Tablepdu2OutletTablenot-accessiblemandatoryAggregate Object with number of entries equal to Number of PDU (pdu2IdentIndex) and Number of outlet per PDU (pdu2OutletIndex).
1.3.6.1.4.1.232.165.7.5.1.1Rowpdu2OutletEntrynot-accessiblemandatoryThe Outlet table entry containing the type, voltage, current etc.
1.3.6.1.4.1.232.165.7.5.1.1.1Columnpdu2OutletIndexread-onlymandatoryIndex for each outlet, value from 1 to the number of outlets per PDU.
1.3.6.1.4.1.232.165.7.5.1.1.2Columnpdu2OutletNameread-onlymandatoryA descriptive name for the outlet.
1.3.6.1.4.1.232.165.7.5.1.1.3Columnpdu2OutletTyperead-onlymandatoryType of this outlet - C13, C19.
1.3.6.1.4.1.232.165.7.5.1.1.4Columnpdu2OutletCurrentRatingread-onlymandatoryRated current capacity of this outlet. Units are milliamps. A negative value indicates that the hardware current capacity is unknown.
1.3.6.1.4.1.232.165.7.5.1.1.5Columnpdu2OutletCurrentread-onlymandatoryA outlet current measurement value. Units are milliamps.
1.3.6.1.4.1.232.165.7.5.1.1.6Columnpdu2OutletCurrentThStatusread-onlymandatoryStatus of the measured outlet current relative to the configured thresholds.
1.3.6.1.4.1.232.165.7.5.1.1.7Columnpdu2OutletCurrentThLowerWarningread-onlymandatoryLower warning threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.5.1.1.8Columnpdu2OutletCurrentThLowerCriticalread-onlymandatoryLower critical threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.5.1.1.9Columnpdu2OutletCurrentThUpperWarningread-onlymandatoryUpper warning threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.5.1.1.10Columnpdu2OutletCurrentThUpperCriticalread-onlymandatoryUpper critical threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.5.1.1.11Columnpdu2OutletCurrentCrestFactorread-onlymandatoryCurrent crest factor. Units are in milli, for example a crest factor of 1.414 will be returned as 1414. A negative value indicates that this object is not avai…
1.3.6.1.4.1.232.165.7.5.1.1.12Columnpdu2OutletCurrentPercentLoadread-onlymandatoryCurrent percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this o…
1.3.6.1.4.1.232.165.7.5.1.1.13Columnpdu2OutletVAread-onlymandatoryA outlet VA value. Units are VA. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.5.1.1.14Columnpdu2OutletWattsread-onlymandatoryA outlet Watts value. Units are Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.5.1.1.15Columnpdu2OutletWhread-onlymandatoryA Watt-Hour value for each outlet. Units are WH. This object is writable so that it can be reset to 0. When it is written to, the pdu2OutletWhTimer will be res…
1.3.6.1.4.1.232.165.7.5.1.1.16Columnpdu2OutletWhTimerread-onlymandatoryTimestamp (date and time) of outlet Watt-hours was last reset.
1.3.6.1.4.1.232.165.7.5.1.1.17Columnpdu2OutletPowerFactorread-onlymandatoryAn outlet PF value. Units are in thousandths, for example a power factor of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value…
1.3.6.1.4.1.232.165.7.5.1.1.18Columnpdu2OutletVARread-onlymandatoryAn outlet VAR value. Units are VAR. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.7.5.2Tablepdu2OutletControlTablenot-accessiblemandatoryAggregate Object with number of entries equal to Number of PDU (pdu2IdentIndex) and Number of outlets per PDU (pdu2OutletIndex).
1.3.6.1.4.1.232.165.7.5.2.1Rowpdu2OutletControlEntrynot-accessiblemandatoryThe Outlet table entry containing the type, voltage, current etc.
1.3.6.1.4.1.232.165.7.5.2.1.1Columnpdu2OutletControlStatusread-onlymandatorycurrent state of a control outlet.
1.3.6.1.4.1.232.165.7.5.2.1.2Columnpdu2OutletControlOffCmdread-writemandatoryWhen write, once issued, the outlet will turn Off immediately. 0-n: Time in seconds until the outlet command is issued -1: Cancel a pending outlet Off command …
1.3.6.1.4.1.232.165.7.5.2.1.3Columnpdu2OutletControlOnCmdread-writemandatoryWhen write, once issued, the outlet will turn On immediately. 0-n: Time in seconds until the outlet command is issued -1: Cancel a pending outlet On command Wh…
1.3.6.1.4.1.232.165.7.5.2.1.4Columnpdu2OutletControlRebootCmdread-writemandatoryWhen write, for outlets that are On prior to this Reboot command, they will switch Off immediately when the command is issued, remain Off for outletControlRebo…
1.3.6.1.4.1.232.165.7.5.2.1.5Columnpdu2OutletControlPowerOnStateread-writemandatoryDetermines the outlet state when power is applied to the unit. 1 : not restart at device startup 2 : should sequence back ON in line with outletControlSequence…
1.3.6.1.4.1.232.165.7.5.2.1.6Columnpdu2OutletControlSequenceDelayread-writemandatoryTime delay in seconds from when a Global Sequence On command is issued to when the command is executed on this outlet. This delay is also used as a power-on de…
1.3.6.1.4.1.232.165.7.5.2.1.7Columnpdu2OutletControlRebootOffTimeread-writemandatoryTime delay in seconds that the outlet should remain in the Off state when executing a Reboot command.
1.3.6.1.4.1.232.165.7.5.2.1.8Columnpdu2OutletControlSwitchableread-writemandatoryDetermines the outlet capability to be controlled On/Off from the communication channels. 1 : control On/Off enabled 2 : control On/Off disabled.
1.3.6.1.4.1.232.165.7.5.2.1.9Columnpdu2OutletControlShutoffDelayread-writemandatoryTime delay in seconds that could be taken in account before shutting of the outlet. An application which need to shutoff properly an outlet will read this para…
1.3.6.1.4.1.232.165.9Nodehpdu
1.3.6.1.4.1.232.165.9.1NodehpduIdent
1.3.6.1.4.1.232.165.9.1.1ScalarhpduNumPhaseread-onlymandatoryfor 3 phases
1.3.6.1.4.1.232.165.9.1.2TablehpduIdentTablenot-accessiblemandatoryIndexed by 1 Hpdu unit.
1.3.6.1.4.1.232.165.9.1.2.1RowhpduIdentEntrynot-accessiblemandatoryThe table entry containing the identifications of HPDU
1.3.6.1.4.1.232.165.9.1.2.1.1ColumnhpduIdentIndexread-onlymandatoryIndex for the MpduIdentEntry table. Start with 1
1.3.6.1.4.1.232.165.9.1.2.1.2ColumnhpduManufacturerread-onlymandatoryThe Core PDU manufacturer. StringLength=[21]
1.3.6.1.4.1.232.165.9.1.2.1.3ColumnhpduModelread-onlymandatoryThe Core PDU model, marketing name. StringLength=[40].
1.3.6.1.4.1.232.165.9.1.2.1.4ColumnhpduNameread-onlymandatoryThe Core PDU name, descriptive name or hostname. StringLength=[16].
1.3.6.1.4.1.232.165.9.1.2.1.5ColumnhpduFirmwareVersionread-onlymandatoryThe Core PDU firmware version(s). StringLength=[12].
1.3.6.1.4.1.232.165.9.1.2.1.6ColumnhpduHardwareVersionread-onlymandatoryThe Core PDU hardware version. StringLength=[8].
1.3.6.1.4.1.232.165.9.1.2.1.7ColumnhpduPartNumberread-onlymandatoryThe Core PDU part number. StringLength=[21].
1.3.6.1.4.1.232.165.9.1.2.1.8ColumnhpduSerialNumberread-onlymandatoryThe PDU external serial number. StringLength=[21].
1.3.6.1.4.1.232.165.9.1.2.1.9ColumnhpduUUIDread-onlymandatoryThe PDU's UUID equals PN add SN, canonical conversion. StringLength=[37].
1.3.6.1.4.1.232.165.9.1.2.1.10ColumnhpduTyperead-onlymandatoryThe PDU's Type: Delta, Wye, single, Wye+lowline. StringLength=[24].
1.3.6.1.4.1.232.165.9.1.2.1.11ColumnhpduPowerRatingread-onlymandatoryThe PDU's Power Rating in KVA (Name Plate). Value is presented in 1/100 of the KVA. i.e. 1750 means 17.50 KVA
1.3.6.1.4.1.232.165.9.1.2.1.12ColumnhpduInputRatingread-onlymandatoryThe PDU's Input Current Rating in A (Name Plate)
1.3.6.1.4.1.232.165.9.1.2.1.13ColumnhpduRegionalNominalVoltageread-onlymandatoryvalue is either America(208V), Japan(202V) or blank for International Model
1.3.6.1.4.1.232.165.9.1.2.1.14ColumnhpduNumOutputBreakersread-onlymandatoryThe number of outlets with breakers of each hpdu.
1.3.6.1.4.1.232.165.9.1.2.1.15ColumnhpduNumMonitoredOutletread-onlymandatoryThe number of measured outlets (with CT, VT) of each hpdu.
1.3.6.1.4.1.232.165.9.1.2.1.16ColumnhpduFanStatusread-onlymandatoryReport fan status: OK or FAIL
1.3.6.1.4.1.232.165.9.1.2.1.17ColumnhpduTemperatureread-onlymandatoryThe internal temperature in Celcius. Value is presented in 1/10 of a degree i.e. 251 is 25.1. A value of -1 will be returned if the temperature is unable to be…
1.3.6.1.4.1.232.165.9.2NodehpduInput
1.3.6.1.4.1.232.165.9.2.1TablehpduInputTablenot-accessiblemandatoryIndexed by hpduNumPhase.
1.3.6.1.4.1.232.165.9.2.1.1RowhpduInputEntrynot-accessiblemandatoryThe Input table entry containing the voltage, current, PF, percent load, VA, Watts for the HPDU.
1.3.6.1.4.1.232.165.9.2.1.1.1ColumnhpduInputIndexread-onlymandatoryIndex for the hpduInputEntry table.
1.3.6.1.4.1.232.165.9.2.1.1.2ColumnhpduInputStatusread-onlymandatoryThe overall status of the Input: off, on, problem. StringLength=[7].
1.3.6.1.4.1.232.165.9.2.1.1.3ColumnhpduInputBreakerRatingread-onlymandatoryThe rating of each hpdu Input in Ampere.
1.3.6.1.4.1.232.165.9.2.1.1.4ColumnhpduInputVoltageread-onlymandatoryThe measured Input voltage from the PDU meters in volts. Value is presented in 1/10 of the Volt i.e. 2095 is 209.5 V. A value of -1 will be returned if the vol…
1.3.6.1.4.1.232.165.9.2.1.1.5ColumnhpduInputCurrentread-onlymandatoryThe measured Input current from the PDU meters in amps. Value is presented in 1/100 of the Ampere i.e. 175 is 1.75 A. A value of -1 will be returned if the cur…
1.3.6.1.4.1.232.165.9.2.1.1.6ColumnhpduInputPowerVAread-onlymandatoryThe total Input Power measured in VA. A value of -1 will be returned if the power is unable to be calculated.
1.3.6.1.4.1.232.165.9.2.1.1.7ColumnhpduInputPowerWattread-onlymandatoryThe total Input power measured in Watts. A value of -1 will be returned if the power is unable to be calculated.
1.3.6.1.4.1.232.165.9.2.1.1.8ColumnhpduInputPowerFactorread-onlymandatoryThe Input power factor is presented in 1/100 of the unit i.e. 98 is 0.98. A value of -1 will be returned if the power factor is unable to be measured.
1.3.6.1.4.1.232.165.9.2.1.1.9ColumnhpduInputWarningThresholdread-onlymandatoryReport the User-setting Input threshhold limit for Warning in percentage
1.3.6.1.4.1.232.165.9.2.1.1.10ColumnhpduInputCriticalThresholdread-onlymandatoryReport the User-setting Input threshhold limit for Critical in percentage
1.3.6.1.4.1.232.165.9.2.1.1.11ColumnhpduInputPowerWattHourread-onlymandatorySupport Billing Grade Energy Metering in Watt-Hour. A value of -1 will be returned if the power is unable to be calculated.
1.3.6.1.4.1.232.165.9.2.1.1.12ColumnhpduInputTotalEnergySinceread-onlymandatoryDisplay the date and time that starts to accumulate the per Load segment energy in WH. Date and Time can be set by user on GUI.
1.3.6.1.4.1.232.165.9.2.1.1.13ColumnhpduInputEnergyMeteringTotalHoursread-onlymandatoryTotal hours of collecting measurement data. A value of -1 will be returned if the value is unable to be calculated.
1.3.6.1.4.1.232.165.9.3NodehpduOutlet
1.3.6.1.4.1.232.165.9.3.1TablehpduOutletTablenot-accessiblemandatoryIndexed by hpduNumMonitoredOutlet and hpduNumPhase . So aggregate objects for each entry equal to (hpduNumMonitoredOutlet x hpduNumPhase). Start with 1.
1.3.6.1.4.1.232.165.9.3.1.1RowhpduOutletEntrynot-accessiblemandatoryThe Outlet table entry containing the voltage, current, PF, percent load, VA, Watts for the Modular PDU.
1.3.6.1.4.1.232.165.9.3.1.1.1ColumnhpduOutletIndexread-onlymandatoryIndex for the hpduOutletEntry table.
1.3.6.1.4.1.232.165.9.3.1.1.2ColumnhpduOutletStatusread-onlymandatoryThe overall status of the breaker: off, on, problem. StringLength=[7].
1.3.6.1.4.1.232.165.9.3.1.1.3ColumnhpduOutletBreakerRatingread-onlymandatoryThe rating of each hpdu Outlet in Ampere.
1.3.6.1.4.1.232.165.9.3.1.1.4ColumnhpduOutletPercentLoadread-onlymandatoryThe hpdu's each Outlet load in percent of rated capacity. Value is presented in 1/10 of the percentage i.e. 125 is 12.5%. A value of -1 will be returned if the…
1.3.6.1.4.1.232.165.9.3.1.1.5ColumnhpduOutletVoltageread-onlymandatoryThe measured Outlet voltage from the PDU meters in volts. Value is presented in 1/10 of the Volt i.e. 2095 is 209.5 V. A value of -1 will be returned if the vo…
1.3.6.1.4.1.232.165.9.3.1.1.6ColumnhpduOutletCurrentread-onlymandatoryThe measured Outlet current from the PDU meters in amps. Value is presented in 1/100 of the Ampere i.e. 175 is 1.75 A. A value of -1 will be returned if the cu…
1.3.6.1.4.1.232.165.9.3.1.1.7ColumnhpduOutletPowerVAread-onlymandatoryThe total VA load (VI) measured on the PDU in VA. A value of -1 will be returned if the power is unable to be calculated.
1.3.6.1.4.1.232.165.9.3.1.1.8ColumnhpduOutletPowerWattread-onlymandatoryThe total power load measured on the PDU in Watts. A value of -1 will be returned if the power is unable to be calculated.
1.3.6.1.4.1.232.165.9.3.1.1.9ColumnhpduOutletPowerFactorread-onlymandatoryThe power factor is presented in 1/100 of the unit i.e. 98 is 0.98. A value of -1 will be returned if the power factor is unable to be measured.
1.3.6.1.4.1.232.165.9.3.1.1.10ColumnhpduOutletWarningThresholdread-onlymandatoryReport the User-set threshhold limit for Warning in percentage
1.3.6.1.4.1.232.165.9.3.1.1.11ColumnhpduOutletCriticalThresholdread-onlymandatoryReport the User-set threshhold limit for Critical in percentage
1.3.6.1.4.1.232.165.9.3.1.1.12ColumnhpduOutletPowerWattHourread-onlymandatorySupport Billing Grade Energy Metering in Watt-Hour. A value of -1 will be returned if the power is unable to be calculated.
1.3.6.1.4.1.232.165.9.3.1.1.13ColumnhpduOutletTotalEnergySinceread-onlymandatoryDisplay the date and time that starts to accumulate the per Load segment energy in WH. Date and Time can be set by user on GUI.
1.3.6.1.4.1.232.165.9.3.1.1.14ColumnhpduOutletEnergyMeteringTotalHoursread-onlymandatoryTotal hours of collecting measurement data. A value of -1 will be returned if the value is unable to be calculated.
1.3.6.1.4.1.232.165.11Nodepdu3
1.3.6.1.4.1.232.165.11.1Nodepdu3Ident
1.3.6.1.4.1.232.165.11.1.1Scalarpdu3NumberPDUread-onlymandatoryThe number of PDUs detected (in its daisy chain).
1.3.6.1.4.1.232.165.11.1.2Tablepdu3IdentTablenot-accessiblemandatoryAggregate Object with number of entries equal to pdu3NumberPDU .
1.3.6.1.4.1.232.165.11.1.2.1Rowpdu3IdentEntrynot-accessiblemandatoryThe ident table entry containing the name, model, manufacturer, firmware version, part number, etc.
1.3.6.1.4.1.232.165.11.1.2.1.1Columnpdu3IdentIndexread-onlymandatoryIndex for the Pdu3IdentEntry table.
1.3.6.1.4.1.232.165.11.1.2.1.2Columnpdu3Nameread-onlymandatoryThe string identify the device in daisy chain. Example PDU A.
1.3.6.1.4.1.232.165.11.1.2.1.3Columnpdu3Modelread-onlymandatoryThe Device Model.
1.3.6.1.4.1.232.165.11.1.2.1.4Columnpdu3Manufacturerread-onlymandatoryThe Device Manufacturer Name (e.g. Hewlett-Packard).
1.3.6.1.4.1.232.165.11.1.2.1.5Columnpdu3FirmwareVersionread-onlymandatoryThe firmware revision level of the device.
1.3.6.1.4.1.232.165.11.1.2.1.6Columnpdu3FirmwareVersionTimeStampread-onlymandatoryTimestamp of when the PDU firmware was last updated
1.3.6.1.4.1.232.165.11.1.2.1.7Columnpdu3PartNumberread-onlymandatoryThe device part number. Example AF400A.
1.3.6.1.4.1.232.165.11.1.2.1.8Columnpdu3SerialNumberread-onlymandatoryThe device serial number, 10- or 16-digit.
1.3.6.1.4.1.232.165.11.1.2.1.9Columnpdu3Statusread-onlymandatoryThe overall status of the device. A value of OK(2) indicates the device is operating normally. A value of degraded(3) indicates the device is operating with wa…
1.3.6.1.4.1.232.165.11.1.2.1.10Columnpdu3Controllableread-onlymandatoryThis object indicates whether or not the device is controllable.
1.3.6.1.4.1.232.165.11.1.2.1.11Columnpdu3InputPhaseCountread-onlymandatoryThe number of input phase on this pdu 1,2,3.
1.3.6.1.4.1.232.165.11.1.2.1.12Columnpdu3GroupCountread-onlymandatoryThe number of groups (breakers) on this pdu.
1.3.6.1.4.1.232.165.11.1.2.1.13Columnpdu3OutletCountread-onlymandatoryThe number of outlets in this PDU.
1.3.6.1.4.1.232.165.11.1.2.1.14Columnpdu3MACAddressread-onlymandatoryThe assigned MAC address for this PDU.
1.3.6.1.4.1.232.165.11.1.2.1.15Columnpdu3IPv4Addressread-onlymandatoryThe current IPv4 Address. A value of 0.0.0.0 indicates an error or an unset option.
1.3.6.1.4.1.232.165.11.1.2.1.16Columnpdu3IPv6Addressread-onlymandatoryThe current IPv6 Address. A vale of 0.0.0.0.0.0 indicates an error or an unset option.
1.3.6.1.4.1.232.165.11.1.3Tablepdu3ConfigTablenot-accessiblemandatoryAggregate Object with number of entries equal to pdu3NumberPDU .
1.3.6.1.4.1.232.165.11.1.3.1Rowpdu3ConfigEntrynot-accessiblemandatoryRead Configuration data from the PDU being queried.
1.3.6.1.4.1.232.165.11.1.3.1.1Columnpdu3ConfigIndexread-onlymandatoryThe index of PDU configuration entry.
1.3.6.1.4.1.232.165.11.1.3.1.2Columnpdu3ConfigSshread-onlymandatorySetting this OID to off(0) will disable the SSH conneciton. Setting this OID to on(1) will enable the SSH connection.
1.3.6.1.4.1.232.165.11.1.3.1.3Columnpdu3ConfigFtpsread-onlymandatorySetting this OID to off(0) will disable the FTPS connection. Setting this OID to on(1) will enable the FTPS connection.
1.3.6.1.4.1.232.165.11.1.3.1.4Columnpdu3ConfigHttpread-onlymandatorySetting this OID to off(0) will disable the HTTP connection. Setting this OID to on(1) will enable the HTTP connection.
1.3.6.1.4.1.232.165.11.1.3.1.5Columnpdu3ConfigHttpsread-onlymandatorySetting this OID to off(0) will disable the HTTPS connection. Setting this OID to on(1) will enable the HTTPS connection.
1.3.6.1.4.1.232.165.11.1.3.1.6Columnpdu3ConfigIPv4IPv6Switchread-onlymandatorySetting this OID to IPv4(1) will enable the IPv4 configuration. Setting this OID to IPv6(2) will enable the IPv6 configuration. Setting this OID to IPv4&IPv6(3…
1.3.6.1.4.1.232.165.11.1.3.1.7Columnpdu3ConfigRedfishAPIread-writemandatorySetting this OID to off(0) will disable the Redfish API. Setting this OID to on(1) will enable the Redfish API.
1.3.6.1.4.1.232.165.11.1.3.1.8Columnpdu3ConfigOledDispalyOrientationread-writemandatoryIndicates the intended physical orientation of OLED display. displayNormal(1) indicates normal orientation. displayReverse(2) indicates upside down orientation.
1.3.6.1.4.1.232.165.11.1.3.1.9Columnpdu3ConfigEnergyResetread-writemandatorySetting this OID to reset(2) will cause the device energy meter value to be reset to zero. Getting this OID in models that support this feature will do nothing…
1.3.6.1.4.1.232.165.11.1.3.1.10Columnpdu3ConfigNetworkManagementCardResetread-writemandatoryGetting this OID will return noOperation(0). Getting this OID to reset(1) will reset NMC.
1.3.6.1.4.1.232.165.11.1.3.1.11Columnpdu3ConfigDaisyChainStatusread-writemandatorySetting this OID to daisychain(0) will enable daisychain mode.
1.3.6.1.4.1.232.165.11.2Nodepdu3Input
1.3.6.1.4.1.232.165.11.2.1Tablepdu3InputTablenot-accessiblemandatoryAggregate Object with number of entries equal to pdu3NumberPDU .
1.3.6.1.4.1.232.165.11.2.1.1Rowpdu3InputEntrynot-accessiblemandatoryThe ident table entry containing the VA, Watts, WH, etc.
1.3.6.1.4.1.232.165.11.2.1.1.1Columnpdu3InputTyperead-onlymandatoryType of input - single phase, split phase, three phase delta, or three phase wye.
1.3.6.1.4.1.232.165.11.2.1.1.2Columnpdu3InputFrequencyread-onlymandatoryThe measured input frequency from the PDU meters in tenths of Hz.
1.3.6.1.4.1.232.165.11.2.1.1.3Columnpdu3InputFrequencyStatusread-onlymandatoryStatus of the measured input frequency relative to the nominal frequency and the admitted tolerance.
1.3.6.1.4.1.232.165.11.2.1.1.4Columnpdu3InputPowerVAread-onlymandatoryA total input VA of all phases. Units are 0.001 VA. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.2.1.1.5Columnpdu3InputPowerWattsread-onlymandatoryA total input Watts of all phases. Units are 0.001 Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.2.1.1.6Columnpdu3InputTotalEnergyread-onlymandatoryA total input Watt-Hour value for all phases. Units are KWh. This value is accumulated since PDU in service. A negative value indicates that this object is not…
1.3.6.1.4.1.232.165.11.2.1.1.7Columnpdu3InputPowerWattHourTimerread-onlymandatoryA Timestamp of when the Total Input WH was last reset.
1.3.6.1.4.1.232.165.11.2.1.1.8Columnpdu3InputResettableEnergyread-onlymandatoryA total input Watt-Hour value for all phases. Units are 0.001 Wh. This value can be reset to 0 using GUI. In that case, the pdu3InputPowerWattHourTimer will be…
1.3.6.1.4.1.232.165.11.2.1.1.9Columnpdu3InputPowerFactorread-onlymandatoryAn input PF value. Units are in thousandths, for example a power factor of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value …
1.3.6.1.4.1.232.165.11.2.1.1.10Columnpdu3InputPowerVARread-onlymandatoryAn input VAR value. Units are 0.001 VAR. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.2.2Tablepdu3InputPhaseTablenot-accessiblemandatoryAggregate Object with number of entries equal to number of PDUs (pdu3NumberPDU) and number of input phase (pdu3InputPhaseCount).
1.3.6.1.4.1.232.165.11.2.2.1Rowpdu3InputPhaseEntrynot-accessiblemandatoryThe input table entry containing the voltage, current, frequency, power for each phase. Entries are given with number of pdu and number of input phase 1, 2, or…
1.3.6.1.4.1.232.165.11.2.2.1.1Columnpdu3InputPhaseIndexread-onlymandatoryIndex for the Pdu3InputEntry table.
1.3.6.1.4.1.232.165.11.2.2.1.2Columnpdu3InputPhaseVoltageMeasTyperead-onlymandatoryValue indicates what input voltage is being measured in this table row - single phase voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phas…
1.3.6.1.4.1.232.165.11.2.2.1.3Columnpdu3InputPhaseVoltageread-onlymandatoryAn input voltage measurement value. Return value is divided by 10.
1.3.6.1.4.1.232.165.11.2.2.1.4Columnpdu3InputPhaseVoltageThStatusread-onlymandatoryStatus of the measured input voltage relative to the configured thresholds.
1.3.6.1.4.1.232.165.11.2.2.1.5Columnpdu3InputPhaseVoltageThLowerWarningread-onlymandatoryLower warning threshold. Return value is divided by 10. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.2.2.1.6Columnpdu3InputPhaseVoltageThLowerCriticalread-onlymandatoryLower critical threshold. Return value is divided by 10. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.2.2.1.7Columnpdu3InputPhaseVoltageThUpperWarningread-onlymandatoryUpper warning threshold. Return value is divided by 10. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.2.2.1.8Columnpdu3InputPhaseVoltageThUpperCriticalread-onlymandatoryUpper critical threshold. Return value is divided by 10. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.2.2.1.9Columnpdu3InputPhaseCurrentMeasTyperead-onlymandatoryWhich input wire is being measured in this table row - single phase, neutral, phase 1, phase 2, or phase 3.
1.3.6.1.4.1.232.165.11.2.2.1.10Columnpdu3InputPhaseCurrentRatingread-onlymandatoryRated current capacity of the input. A negative value indicates that the hardware current capacity is unknown. Return value is divided by 100.
1.3.6.1.4.1.232.165.11.2.2.1.11Columnpdu3InputPhaseCurrentread-onlymandatoryAn input current measurement value. Return value is divided by 100.
1.3.6.1.4.1.232.165.11.2.2.1.12Columnpdu3InputPhaseCurrentThStatusread-onlymandatoryStatus of the measured input current relative to the configured thresholds.
1.3.6.1.4.1.232.165.11.2.2.1.13Columnpdu3InputPhaseCurrentThLowerWarningread-onlymandatoryLower warning threshold. Return value is divided by 100. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.2.2.1.14Columnpdu3InputPhaseCurrentThLowerCriticalread-onlymandatoryLower critical threshold. Return value is divided by 100. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.2.2.1.15Columnpdu3InputPhaseCurrentThUpperWarningread-onlymandatoryUpper warning threshold. Return value is divided by 100. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.2.2.1.16Columnpdu3InputPhaseCurrentThUpperCriticalread-onlymandatoryUpper critical threshold. Return value is divided by 100. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.2.2.1.17Columnpdu3InputPhaseCurrentPercentLoadread-onlymandatoryCurrent percent load, based on the rated current capacity. Units are percentage, for example 80.9 % will be returned as 809. A negative value indicates that th…
1.3.6.1.4.1.232.165.11.2.2.1.18Columnpdu3InputPhasePowerMeasTyperead-onlymandatoryWhich input wire is being measured in this table row - single phase, neutral, phase 1, phase 2, or phase 3.
1.3.6.1.4.1.232.165.11.2.2.1.19Columnpdu3InputPhasePowerVAread-onlymandatoryAn input VA value. Units are VA. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.2.2.1.20Columnpdu3InputPhasePowerWattsread-onlymandatoryAn input Watts value. Units are Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.2.2.1.21Columnpdu3InputPhasePowerWattHourread-onlymandatoryA kWatt-Hour value for each Input phase. Units are kWh. This value can be reset to 0 using GUI. In that case, the pdu3InputPhasePowerWattHourTimer will be rese…
1.3.6.1.4.1.232.165.11.2.2.1.22Columnpdu3InputPhasePowerWattHourTimerread-onlymandatoryTimestamp of when input phase kWatt-hours (kWh) was last reset.
1.3.6.1.4.1.232.165.11.2.2.1.23Columnpdu3InputPhasePowerFactorread-onlymandatoryAn input PF value. Return value is divided by 100, for example a power factor of 0.95 would be returned as 95. A negative value indicates that this object is n…
1.3.6.1.4.1.232.165.11.2.2.1.24Columnpdu3InputPhasePowerVARread-onlymandatoryAn input VA Reactive value. Units are in VAR. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.3Nodepdu3Group
1.3.6.1.4.1.232.165.11.3.1Tablepdu3GroupTablenot-accessiblemandatoryAggregate Object with number of entries equal to number of PDUs and number of breakers (pdu3GroupCount).
1.3.6.1.4.1.232.165.11.3.1.1Rowpdu3GroupEntrynot-accessiblemandatoryThe input table entry containing the name, voltages, currents, power, etc.
1.3.6.1.4.1.232.165.11.3.1.1.1Columnpdu3GroupIndexread-onlymandatoryIndex for the Pdu3GroupEntry table.
1.3.6.1.4.1.232.165.11.3.1.1.2Columnpdu3GroupNameread-onlymandatoryA descriptive name for the group.
1.3.6.1.4.1.232.165.11.3.1.1.3Columnpdu3GroupTyperead-onlymandatoryThe type of the group. (5) has no breaker
1.3.6.1.4.1.232.165.11.3.1.1.4Columnpdu3GroupVoltageMeasTyperead-onlymandatoryValue indicates what input voltage is being measured in this table row - single phase voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phas…
1.3.6.1.4.1.232.165.11.3.1.1.5Columnpdu3GroupVoltageread-onlymandatoryReturn value is divided by 10 to get one decimal point, unit is in Volt.
1.3.6.1.4.1.232.165.11.3.1.1.6Columnpdu3GroupVoltageThStatusread-onlymandatoryStatus of the measured group voltage relative to the configured thresholds.
1.3.6.1.4.1.232.165.11.3.1.1.7Columnpdu3GroupVoltageThLowerWarningread-onlymandatoryLower warning threshold. Return value is divided by 10 to get one decimal point, unit is in Volt. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.3.1.1.8Columnpdu3GroupVoltageThLowerCriticalread-onlymandatoryLower critical threshold. Return value is divided by 10 to get one decimal point, unit is in Volt. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.3.1.1.9Columnpdu3GroupVoltageThUpperWarningread-onlymandatoryUpper warning threshold. Return value is divided by 10 to get one decimal point, unit is in Volt. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.3.1.1.10Columnpdu3GroupVoltageThUpperCriticalread-onlymandatoryUpper critical threshold. Return value is divided by 10 to get one decimal point, unit is in Volt. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.3.1.1.11Columnpdu3groupCurrentRatingread-onlymandatoryRated current capacity of the group. Return value is divided by 100 to get two decimal points, unit is in Amps. A negative value indicates that the hardware cu…
1.3.6.1.4.1.232.165.11.3.1.1.12Columnpdu3GroupCurrentread-onlymandatoryA group current measurement value. Return value is divided by 100 to get two decimal points.
1.3.6.1.4.1.232.165.11.3.1.1.13Columnpdu3GroupCurrentThStatusread-onlymandatoryStatus of the measured group current relative to the configured thresholds.
1.3.6.1.4.1.232.165.11.3.1.1.14Columnpdu3GroupCurrentThLowerWarningread-onlymandatoryLower warning threshold. Return value is divided by 100 to get two decimal points. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.3.1.1.15Columnpdu3GroupCurrentThLowerCriticalread-onlymandatoryLower critical threshold. Return value is divided by 100 to get two decimal points. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.3.1.1.16Columnpdu3GroupCurrentThUpperWarningread-onlymandatoryUpper warning threshold. Return value is divided by 100 to get two decimal points. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.3.1.1.17Columnpdu3GroupCurrentThUpperCriticalread-onlymandatoryUpper critical threshold. Return value is divided by 100 to get two decimal points. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.3.1.1.18Columnpdu3GroupCurrentPercentLoadread-onlymandatoryCurrent percent load, based on the rated current capacity. Units are percentage, for example 80.9 % will be returned as 809. A negative value indicates that th…
1.3.6.1.4.1.232.165.11.3.1.1.19Columnpdu3GroupPowerVAread-onlymandatoryA group VA value. Units are VA. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.3.1.1.20Columnpdu3GroupPowerWattsread-onlymandatoryA group power value. Units are Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.3.1.1.21Columnpdu3GroupPowerWattHourread-onlymandatoryAn energy consumption value for each load segment. Units are kWh. This value can be reset to 0 using GUI. In that case, the pdu3GroupPowerWattHourTimer will be…
1.3.6.1.4.1.232.165.11.3.1.1.22Columnpdu3GroupPowerWattHourTimerread-onlymandatoryTimestamp when group kilo Watt-hours (group kWh) is reset.
1.3.6.1.4.1.232.165.11.3.1.1.23Columnpdu3GroupPowerFactorread-onlymandatoryA group PF value. Return value is divided by 100, for example a power factor of 0.95 would be returned as 95. A negative value indicates that this object is no…
1.3.6.1.4.1.232.165.11.3.1.1.24Columnpdu3GroupPowerVARread-onlymandatoryA measurement for group/load segment power reactive. Units are VAR. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.3.1.1.25Columnpdu3GroupOutletCountread-onlymandatoryThe number of outlets in each group (breaker).
1.3.6.1.4.1.232.165.11.3.1.1.26Columnpdu3GroupBreakerStatusread-onlymandatoryOnly applicable to groups with breaker. Indicates whether a breaker is turned off or on.
1.3.6.1.4.1.232.165.11.4Nodepdu3Environment
1.3.6.1.4.1.232.165.11.4.1Tablepdu3EnvProbeTablenot-accessiblemandatoryA list of environment probe (1 per PDU) for temperature, humidity, and contacts. The number of entries is given by number of PDUs in daisy chain.
1.3.6.1.4.1.232.165.11.4.1.1Rowpdu3EnvProbeEntrynot-accessiblemandatoryAggregate entries equal to number of PDUs.
1.3.6.1.4.1.232.165.11.4.1.1.1Columnpdu3TemperatureScaleread-onlymandatoryScale used to return temperature objects.
1.3.6.1.4.1.232.165.11.4.1.1.2Columnpdu3TemperatureCountread-onlymandatoryMax number of temperature measurements (1 per probe).
1.3.6.1.4.1.232.165.11.4.1.1.3Columnpdu3HumidityCountread-onlymandatoryMax number of humidity measurements (1 per probe).
1.3.6.1.4.1.232.165.11.4.1.1.4Columnpdu3ContactCountread-onlymandatoryMax number of contact sensors (1 per probe).
1.3.6.1.4.1.232.165.11.4.2Tablepdu3TemperatureTablenot-accessiblemandatoryA list of temperature probe measurements. The number of entries are given by number of pdu and pdu3TemperatureCount.
1.3.6.1.4.1.232.165.11.4.2.1Rowpdu3TemperatureEntrynot-accessiblemandatoryAn entry for a temperature measurement.
1.3.6.1.4.1.232.165.11.4.2.1.1Columnpdu3TemperatureIndexread-onlymandatoryA unique value for each temperature probe measurement. Its value ranges from 1 to temperatureCount.
1.3.6.1.4.1.232.165.11.4.2.1.2Columnpdu3TemperatureNameread-onlymandatoryA descriptive name for the temperature probe.
1.3.6.1.4.1.232.165.11.4.2.1.3Columnpdu3TemperatureProbeStatusread-onlymandatoryIndicates whether a probe is connected or not.
1.3.6.1.4.1.232.165.11.4.2.1.4Columnpdu3TemperatureValueread-onlymandatoryUnits are in tenths of a degree (either Fahrenheit or Celsius). Return value is divided by 10 to get degrees.
1.3.6.1.4.1.232.165.11.4.2.1.5Columnpdu3TemperatureThStatusread-onlymandatoryStatus of the measured temperature relative to the configured thresholds.
1.3.6.1.4.1.232.165.11.4.2.1.6Columnpdu3TemperatureThLowerWarningread-onlymandatoryLower warning threshold. Return value is divided by 10 to get degree. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.4.2.1.7Columnpdu3TemperatureThLowerCriticalread-onlymandatoryLower critical threshold. Return value is divided by 10 to get degree. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.4.2.1.8Columnpdu3TemperatureThUpperWarningread-onlymandatoryUpper warning threshold. Return value is divided by 10 to get degree. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.4.2.1.9Columnpdu3TemperatureThUpperCriticalread-onlymandatoryUpper critical threshold. Return value is divided by 10 to get degree. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.4.3Tablepdu3HumidityTablenot-accessiblemandatoryA list of humidity probe measurements. The number of entries are given by number of pdu and pdu3HumidityCount.
1.3.6.1.4.1.232.165.11.4.3.1Rowpdu3HumidityEntrynot-accessiblemandatoryAn entry for a humidity measurement.
1.3.6.1.4.1.232.165.11.4.3.1.1Columnpdu3HumidityIndexread-onlymandatoryA unique value for each humidity probe measurement. Its value ranges from 1 to pdu3HumidityCount per pdu.
1.3.6.1.4.1.232.165.11.4.3.1.2Columnpdu3HumidityNameread-onlymandatoryA descriptive name for the humidity probe.
1.3.6.1.4.1.232.165.11.4.3.1.3Columnpdu3HumidityProbeStatusread-onlymandatoryIndicates whether a probe is connected or not.
1.3.6.1.4.1.232.165.11.4.3.1.4Columnpdu3HumidityValueread-onlymandatoryUnits are tenths of a percent relative humidity. Return value is divided by 10 to get %RH.
1.3.6.1.4.1.232.165.11.4.3.1.5Columnpdu3HumidityThStatusread-onlymandatoryStatus of the measured humidity relative to the configured thresholds.
1.3.6.1.4.1.232.165.11.4.3.1.6Columnpdu3HumidityThLowerWarningread-onlymandatoryLower warning threshold. Return value is divided by 10 to get %RH. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.4.3.1.7Columnpdu3HumidityThLowerCriticalread-onlymandatoryLower critical threshold. Return value is divided by 10 to get %RH. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.4.3.1.8Columnpdu3HumidityThUpperWarningread-onlymandatoryUpper warning threshold. Return value is divided by 10 to get %RH. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.4.3.1.9Columnpdu3HumidityThUpperCriticalread-onlymandatoryUpper critical threshold. Return value is divided by 10 to get %RH. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.4.4Tablepdu3ContactTablenot-accessiblemandatoryA list of contact sensors. The number of entries are given by number of pdu and pdu3ContactCount.
1.3.6.1.4.1.232.165.11.4.4.1Rowpdu3ContactEntrynot-accessiblemandatoryAn entry for a contact sensor
1.3.6.1.4.1.232.165.11.4.4.1.1Columnpdu3ContactIndexread-onlymandatoryA unique value for each contact sensor. Its value ranges from 1 to contactCount.
1.3.6.1.4.1.232.165.11.4.4.1.2Columnpdu3ContactNameread-onlymandatoryA descriptive name for the contact sensor.
1.3.6.1.4.1.232.165.11.4.4.1.3Columnpdu3ContactProbeStatusread-onlymandatoryIndicates whether a probe is connected or not. Will not be returned if the contact sensor is internal to the ePDU, in that case only contactState should be rea…
1.3.6.1.4.1.232.165.11.4.4.1.4Columnpdu3ContactStateread-onlymandatoryThe state of the contact sensor.
1.3.6.1.4.1.232.165.11.5Nodepdu3Outlet
1.3.6.1.4.1.232.165.11.5.1Tablepdu3OutletTablenot-accessiblemandatoryAggregate Object with number of entries equal to Number of PDU (pdu3IdentIndex) and Number of outlet per PDU (pdu3OutletIndex).
1.3.6.1.4.1.232.165.11.5.1.1Rowpdu3OutletEntrynot-accessiblemandatoryThe Outlet table entry containing the type, voltage, current etc.
1.3.6.1.4.1.232.165.11.5.1.1.1Columnpdu3OutletIndexread-onlymandatoryIndex for each outlet, value from 1 to the number of outlets per PDU.
1.3.6.1.4.1.232.165.11.5.1.1.2Columnpdu3OutletNameread-onlymandatoryA descriptive name for the outlet.
1.3.6.1.4.1.232.165.11.5.1.1.3Columnpdu3OutletTyperead-onlymandatoryType of this outlet - C13, C19.
1.3.6.1.4.1.232.165.11.5.1.1.4Columnpdu3OutletCurrentRatingread-onlymandatoryRated current capacity of this outlet. Return value is divided by 100 to get amps. A negative value indicates that the hardware current capacity is unknown.
1.3.6.1.4.1.232.165.11.5.1.1.5Columnpdu3OutletCurrentread-onlymandatoryA outlet current measurement value. Return value is divided by 100 to get amps.
1.3.6.1.4.1.232.165.11.5.1.1.6Columnpdu3OutletActivePowerThStatusread-onlymandatoryStatus of the measured outlet active power relative to the configured thresholds.
1.3.6.1.4.1.232.165.11.5.1.1.7Columnpdu3OutletActivePowerThLowerWarningread-onlymandatoryLower warning threshold. Units are Watts(W). A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.5.1.1.8Columnpdu3OutletActivePowerThLowerCriticalread-onlymandatoryLower critical threshold. Units are Watts(W). A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.5.1.1.9Columnpdu3OutletActivePowerThUpperWarningread-onlymandatoryUpper warning threshold. Units are Watts(W). A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.5.1.1.10Columnpdu3OutletActivePowerThUpperCriticalread-onlymandatoryUpper critical threshold. Units are Watts(W). A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.5.1.1.11Columnpdu3OutletCurrentPercentLoadread-onlymandatoryCurrent percent load, based on the rated current capacity. Units are percentage, for example 80.5% will be returned as 805. A negative value indicates that thi…
1.3.6.1.4.1.232.165.11.5.1.1.12Columnpdu3OutletVAread-onlymandatoryA outlet power VA value. Units are VA. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.5.1.1.13Columnpdu3OutletWattsread-onlymandatoryA outlet power in Watts value. Units are Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.5.1.1.14Columnpdu3OutletWhread-onlymandatoryAn energy in kWatt-Hour value for each outlet. Units are kWh. This object is writable so that it can be reset to 0. When it is written to, the pdu3OutletWhTime…
1.3.6.1.4.1.232.165.11.5.1.1.15Columnpdu3OutletWhTimerread-onlymandatoryTimestamp (date and time) of outlet energy in kWh is reset.
1.3.6.1.4.1.232.165.11.5.1.1.16Columnpdu3OutletPowerFactorread-onlymandatoryAn outlet PF value. Return value is divided by 100, for example a power factor of 0.95 would be returned as 95. A negative value indicates that this object is …
1.3.6.1.4.1.232.165.11.5.1.1.17Columnpdu3OutletVARread-onlymandatoryAn outlet power reactive in VAR value. Units are VAR. A negative value indicates that this object is not available.
1.3.6.1.4.1.232.165.11.5.2Tablepdu3OutletControlTablenot-accessiblemandatoryAggregate Object with number of entries equal to Number of PDU (pdu3IdentIndex) and Number of outlets per PDU (pdu3OutletIndex).
1.3.6.1.4.1.232.165.11.5.2.1Rowpdu3OutletControlEntrynot-accessiblemandatoryThe Outlet table entry containing the type, voltage, current etc.
1.3.6.1.4.1.232.165.11.5.2.1.1Columnpdu3OutletControlStatusread-onlymandatorycurrent state of a control outlet.
1.3.6.1.4.1.232.165.11.5.2.1.2Columnpdu3OutletControlOffCmdread-writemandatoryWhen write, once issued, the outlet will turn Off immediately. 0-n: Time in seconds until the outlet command is issued -1: Cancel a pending outlet Off command …
1.3.6.1.4.1.232.165.11.5.2.1.3Columnpdu3OutletControlOnCmdread-writemandatoryWhen write, once issued, the outlet will turn On immediately. 0-n: Time in seconds until the outlet command is issued -1: Cancel a pending outlet On command Wh…
1.3.6.1.4.1.232.165.11.5.2.1.4Columnpdu3OutletControlRebootCmdread-writemandatoryWhen write, for outlets that are On prior to this Reboot command, they will switch Off immediately when the command is issued, remain Off for outletControlRebo…
1.3.6.1.4.1.232.165.11.5.2.1.5Columnpdu3OutletControlPowerOnStateread-writemandatoryDetermines the outlet state when power is applied to the unit. 1 : not restart at device startup 2 : should sequence back ON in line with outletControlSequence…
1.3.6.1.4.1.232.165.11.5.2.1.6Columnpdu3OutletControlSequenceDelayread-writemandatoryTime delay in seconds from when a Global Sequence On command is issued to when the command is executed on this outlet. This delay is also used as a power-on de…
1.3.6.1.4.1.232.165.11.5.2.1.7Columnpdu3OutletControlRebootOffTimeread-writemandatoryTime delay in seconds that the outlet should remain in the Off state when executing a Reboot command.
1.3.6.1.4.1.232.165.11.5.2.1.8Columnpdu3OutletControlSwitchableread-writemandatoryDetermines the outlet capability to be controlled On/Off from the communication channels. 1 : control On/Off enabled 2 : control On/Off disabled.
1.3.6.1.4.1.232.165.11.5.2.1.9Columnpdu3OutletControlShutoffDelayread-writemandatoryTime delay in seconds that could be taken in account before shutting of the outlet. An application which need to shutoff properly an outlet will read this para…