MIB Viewer

ACS-MIB

252 objects
This module defines the Avocent MIB extensions to ACS60xx products.
Imported Objects
IF-MIBInterfaceIndex InterfaceIndexOrZero
RFC-1215TRAP-TYPE
RFC1155-SMICounter Gauge IpAddress NetworkAddress TimeTicks
RFC1213-MIBPhysAddress
SNMPv2-SMIenterprises Integer32 MODULE-IDENTITY OBJECT-IDENTITY OBJECT-TYPE
SNMPv2-TCDisplayString
OIDNameAccessStatusDescription
1.3.6.1.4.1.10418.16IdentityacsThis module defines the Avocent MIB extensions to ACS60xx products.
1.3.6.1.4.1.10418.16.1NodeacsProducts
1.3.6.1.4.1.10418.16.1.1Nodeacs6016
1.3.6.1.4.1.10418.16.1.2Nodeacs6032
1.3.6.1.4.1.10418.16.1.3Nodeacs6048
1.3.6.1.4.1.10418.16.1.4Nodeacs6004
1.3.6.1.4.1.10418.16.1.5Nodeacs6008
1.3.6.1.4.1.10418.16.2NodeacsManagement
1.3.6.1.4.1.10418.16.2.1NodeacsAppliance
1.3.6.1.4.1.10418.16.2.1.1ScalaracsHostNameread-onlycurrentThe appliance name
1.3.6.1.4.1.10418.16.2.1.2ScalaracsProductModelread-onlycurrentThe appliance product model
1.3.6.1.4.1.10418.16.2.1.3ScalaracsPartNumberread-onlycurrentThe part number of this appliance as shown on the label attached or imprinted on the appliance.
1.3.6.1.4.1.10418.16.2.1.4ScalaracsSerialNumberread-onlycurrentThe serial number of this appliance as shown on the label attached or imprinted on the appliance.
1.3.6.1.4.1.10418.16.2.1.5ScalaracsEIDNumberread-onlycurrentThe electronic ID number (EID) of this appliance as shown on the label attached or imprinted on the appliance.
1.3.6.1.4.1.10418.16.2.1.6ScalaracsBootcodeVersionread-onlycurrentThe version of the bootcode of this appliance.
1.3.6.1.4.1.10418.16.2.1.7ScalaracsFirmwareVersionread-onlycurrentThe version of the firmware of this appliance.
1.3.6.1.4.1.10418.16.2.1.8IdentityacsPowerSupplycurrentIt gives information about Power Supply of this appliance
1.3.6.1.4.1.10418.16.2.1.8.1ScalaracsPowerSupplyNumberread-onlycurrentNumber of the power supplies of this appliance
1.3.6.1.4.1.10418.16.2.1.8.2ScalaracsPowerSupplyStatePw1read-onlycurrentState of the first power supply
1.3.6.1.4.1.10418.16.2.1.8.3ScalaracsPowerSupplyStatePw2read-onlycurrentState of the second power supply
1.3.6.1.4.1.10418.16.2.1.9ScalaracsRebootread-writecurrentA set value of reboot(2) will reboot the appliance. noAction(1) = always returned in a GET. Does nothing if SET. reboot(2) = when SET the appliance immediately…
1.3.6.1.4.1.10418.16.2.2NodeacsSessions
1.3.6.1.4.1.10418.16.2.2.1ScalaracsActiveSessionsNumberOfSessionread-onlycurrentNumber of active sessions.
1.3.6.1.4.1.10418.16.2.2.2TableacsActiveSessionsTablenot-accessiblecurrentThis table contains the list of active sessions.
1.3.6.1.4.1.10418.16.2.2.2.1RowacsActiveSessionsTableEntrynot-accessiblecurrenteach entry has the information about the active session
1.3.6.1.4.1.10418.16.2.2.2.1.1ColumnacsActiveSessionsTableIndexread-onlycurrentA unique index representing an entry in this table.
1.3.6.1.4.1.10418.16.2.2.2.1.2ColumnacsActiveSessionsTableUserread-onlycurrentThe name of the user that opens this session.
1.3.6.1.4.1.10418.16.2.2.2.1.3ColumnacsActiveSessionsTableGroupread-onlycurrentThe name of the group that the user belongs to.
1.3.6.1.4.1.10418.16.2.2.2.1.4ColumnacsActiveSessionsTableTyperead-onlycurrentThe session type.
1.3.6.1.4.1.10418.16.2.2.2.1.5ColumnacsActiveSessionsTableConnectionread-onlycurrentConnection type.
1.3.6.1.4.1.10418.16.2.2.2.1.6ColumnacsActiveSessionsTableSessionTimeread-onlycurrentTime of the session
1.3.6.1.4.1.10418.16.2.2.2.1.7ColumnacsActiveSessionsTableFromread-onlycurrentThe source IP address of the session.
1.3.6.1.4.1.10418.16.2.2.2.1.8ColumnacsActiveSessionsTableKillread-writecurrentA set value of killSession(2) will kill the session. noAction(1) = always returned in a GET. Does nothing if SET. killSession(2)= when SET the appliance immedi…
1.3.6.1.4.1.10418.16.2.3NodeacsSerialPort
1.3.6.1.4.1.10418.16.2.3.1ScalaracsSerialPortNumberOfPortsread-onlycurrentNumber of Serial Ports (physical serial port plus Aux Port.
1.3.6.1.4.1.10418.16.2.3.2TableacsSerialPortTablenot-accessiblecurrentThis table contains information about serial ports.
1.3.6.1.4.1.10418.16.2.3.2.1RowacsSerialPortTableEntrynot-accessiblecurrenteach entry has the information about specific serial port.
1.3.6.1.4.1.10418.16.2.3.2.1.1ColumnacsSerialPortTableNumberread-onlycurrentA unique index representing an entry in this table. It is the number of the serial port. For AUX port, the number will be the number of physical serial ports p…
1.3.6.1.4.1.10418.16.2.3.2.1.2ColumnacsSerialPortTableDeviceNameread-onlycurrentThe associated device name for the serial port.
1.3.6.1.4.1.10418.16.2.3.2.1.3ColumnacsSerialPortTableStatusread-onlycurrentThe status of the serial port: disabled(1) = it was configured as disable. idle(2) = there is not any session opened in this port. inUse(3) = there is session(…
1.3.6.1.4.1.10418.16.2.3.2.1.4ColumnacsSerialPortTableNameread-onlycurrentName associated with this serial port.
1.3.6.1.4.1.10418.16.2.3.2.1.5ColumnacsSerialPortTableProfileread-onlycurrentConfigured profile for this serial port.
1.3.6.1.4.1.10418.16.2.3.2.1.6ColumnacsSerialPortTablePinOutread-onlycurrentRJ45 Pin-out configured for this serial port.
1.3.6.1.4.1.10418.16.2.3.2.1.7ColumnacsSerialPortTableComSpeedread-onlycurrentSpeed configured for this serial port.
1.3.6.1.4.1.10418.16.2.3.2.1.8ColumnacsSerialPortTableComParityread-onlycurrentParity configured for this serial port.
1.3.6.1.4.1.10418.16.2.3.2.1.9ColumnacsSerialPortTableComDataSizeread-onlycurrentData Size configured for this serial port.
1.3.6.1.4.1.10418.16.2.3.2.1.10ColumnacsSerialPortTableComStopBitsread-onlycurrentNumber of Stop Bits configured for this serial port.
1.3.6.1.4.1.10418.16.2.3.2.1.11ColumnacsSerialPortTableComFlowControlread-onlycurrentFlow Control configured for this serial port.
1.3.6.1.4.1.10418.16.2.3.2.1.12ColumnacsSerialPortTableSignalStateDTRread-onlycurrentState of the DTR RS-232C signal.
1.3.6.1.4.1.10418.16.2.3.2.1.13ColumnacsSerialPortTableSignalStateDCDread-onlycurrentState of the DCD RS-232C signal.
1.3.6.1.4.1.10418.16.2.3.2.1.14ColumnacsSerialPortTableSignalStateRTSread-onlycurrentState of the RTS RS-232C signal.
1.3.6.1.4.1.10418.16.2.3.2.1.15ColumnacsSerialPortTableSignalStateCTSread-onlycurrentState of the CTS RS-232C signal.
1.3.6.1.4.1.10418.16.2.3.2.1.16ColumnacsSerialPortTableTxBytesread-onlycurrentThe number of transmited bytes by the serial port.
1.3.6.1.4.1.10418.16.2.3.2.1.17ColumnacsSerialPortTableRxBytesread-onlycurrentThe number of received bytes by the serial port.
1.3.6.1.4.1.10418.16.2.3.2.1.18ColumnacsSerialPortTableFrameErrorread-onlycurrentThe number of frame error detected in the serial port.
1.3.6.1.4.1.10418.16.2.3.2.1.19ColumnacsSerialPortTableParityErrorread-onlycurrentThe number of parity error detected in the serial port.
1.3.6.1.4.1.10418.16.2.3.2.1.20ColumnacsSerialPortTableBreakread-onlycurrentThe number of break detected in the serial port.
1.3.6.1.4.1.10418.16.2.3.2.1.21ColumnacsSerialPortTableOverrunread-onlycurrentThe number of overrun error detected in the serial port.
1.3.6.1.4.1.10418.16.2.5NodeacsPowerMgmt
1.3.6.1.4.1.10418.16.2.5.1ScalaracsPowerMgmtNumSerialPortsread-onlycurrentThe number of Serial Ports that has PDU connected on the appliance.
1.3.6.1.4.1.10418.16.2.5.2TableacsPowerMgmtSerialTablenot-accessiblecurrentInformation about each serial port thas has PDU connect.
1.3.6.1.4.1.10418.16.2.5.2.1RowacsPowerMgmtSerialTableEntrynot-accessiblecurrentInformation about each serial port thas has PDU connect.
1.3.6.1.4.1.10418.16.2.5.2.1.1ColumnacsPowerMgmtSerialTableIndexread-onlycurrentThe index of the register.
1.3.6.1.4.1.10418.16.2.5.2.1.2ColumnacsPowerMgmtSerialTablePortNumberread-onlycurrentThe number of the serial port when the PDU is connected.
1.3.6.1.4.1.10418.16.2.5.2.1.3ColumnacsPowerMgmtSerialTableDeviceNameread-onlycurrentThe device name of this serial port.
1.3.6.1.4.1.10418.16.2.5.2.1.4ColumnacsPowerMgmtSerialTableNumberPDUsread-onlycurrentTotal number of units connected in this serial port.
1.3.6.1.4.1.10418.16.2.5.3TableacsPowerMgmtPDUTablenot-accessiblecurrentThis table contains the list of detected PDUs.
1.3.6.1.4.1.10418.16.2.5.3.1RowacsPowerMgmtPDUTableEntrynot-accessiblecurrenteach entry has the information about the PDU.
1.3.6.1.4.1.10418.16.2.5.3.1.1ColumnacsPowerMgmtPDUTablePortNumberread-onlycurrentNumber of serial port when the PDU is connected.
1.3.6.1.4.1.10418.16.2.5.3.1.2ColumnacsPowerMgmtPDUTablePduIndexread-onlycurrentA PDU position in the chain.
1.3.6.1.4.1.10418.16.2.5.3.1.3ColumnacsPowerMgmtPDUTablePduIdread-onlycurrentPDU identification.
1.3.6.1.4.1.10418.16.2.5.3.1.4ColumnacsPowerMgmtPDUTablePortNameread-onlycurrentName of serial port when the PDU is connected.
1.3.6.1.4.1.10418.16.2.5.3.1.5ColumnacsPowerMgmtPDUTableModelread-onlycurrentModel of the PDU.
1.3.6.1.4.1.10418.16.2.5.3.1.6ColumnacsPowerMgmtPDUTableVendorread-onlycurrentVendor of the PDU.
1.3.6.1.4.1.10418.16.2.5.3.1.7ColumnacsPowerMgmtPDUTableFirmwareVersionread-onlycurrentVersion of the PDU firmware.
1.3.6.1.4.1.10418.16.2.5.3.1.8ColumnacsPowerMgmtPDUTableNumberOfOutletsread-onlycurrentNumber of outlets of the PDU.
1.3.6.1.4.1.10418.16.2.5.3.1.9ColumnacsPowerMgmtPDUTableCurrentNOSread-onlyobsoleteNumber of current sensors in the PDU.
1.3.6.1.4.1.10418.16.2.5.3.1.10ColumnacsPowerMgmtPDUTableCurrent1Valueread-onlyobsoleteCurrent of the sensor 1 in this PDU unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : valu…
1.3.6.1.4.1.10418.16.2.5.3.1.11ColumnacsPowerMgmtPDUTableCurrent1Maxread-writeobsoleteMaximum current of the sensor 1 in this PDU unit in AMP. When the PDU does not have support for maximum value, the value will be 0. The value of this object is…
1.3.6.1.4.1.10418.16.2.5.3.1.12ColumnacsPowerMgmtPDUTableCurrent2Valueread-onlyobsoleteCurrent of the sensor 2 in this PDU unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : valu…
1.3.6.1.4.1.10418.16.2.5.3.1.13ColumnacsPowerMgmtPDUTableCurrent2Maxread-writeobsoleteMaximum current of the sensor 2 in this PDU unit in AMP. When the PDU does not have support for maximum value, the value will be 0. The value of this object is…
1.3.6.1.4.1.10418.16.2.5.3.1.14ColumnacsPowerMgmtPDUTableCurrent3Valueread-onlyobsoleteCurrent of the sensor 3 in this PDU unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : valu…
1.3.6.1.4.1.10418.16.2.5.3.1.15ColumnacsPowerMgmtPDUTableCurrent3Maxread-writeobsoleteMaximum current of the sensor 3 in this PDU unit in AMP. When the PDU does not have support for maximum value, the value will be 0. The value of this object is…
1.3.6.1.4.1.10418.16.2.5.3.1.16ColumnacsPowerMgmtPDUTableTemperatureNOSread-onlyobsoleteNumber of temperature sensors in the PDU.
1.3.6.1.4.1.10418.16.2.5.3.1.17ColumnacsPowerMgmtPDUTableTemperature1Valueread-onlyobsoleteTemperature of this PM unit in Celsius degrees. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (E…
1.3.6.1.4.1.10418.16.2.5.3.1.18ColumnacsPowerMgmtPDUTableTemperature1Maxread-writeobsoleteMaximum temperature detected in this PM unit in Celsius degrees. The value will be Zero when the PDU does not have support for maximum value. The value of this…
1.3.6.1.4.1.10418.16.2.5.3.1.19ColumnacsPowerMgmtPDUTableTemperature2Valueread-onlyobsoleteTemperature of this PM unit in Celsius degrees. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (E…
1.3.6.1.4.1.10418.16.2.5.3.1.20ColumnacsPowerMgmtPDUTableTemperature2Maxread-writeobsoleteMaximum temperature detected in this PM unit in Celsius degrees. The value will be Zero when the PDU does not have support for maximum value. The value of this…
1.3.6.1.4.1.10418.16.2.5.3.1.21ColumnacsPowerMgmtPDUTableTemperature3Valueread-onlyobsoleteTemperature of this PM unit in Celsius degrees. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (E…
1.3.6.1.4.1.10418.16.2.5.3.1.22ColumnacsPowerMgmtPDUTableTemperature3Maxread-writeobsoleteMaximum temperature detected in this PM unit in Celsius degrees. The value will be Zero when the PDU does not have support for maximum value. The value of this…
1.3.6.1.4.1.10418.16.2.5.3.1.23ColumnacsPowerMgmtPDUTableHumidityNOSread-onlyobsoleteNumber of humidity sensors in the PDU.
1.3.6.1.4.1.10418.16.2.5.3.1.24ColumnacsPowerMgmtPDUTableHumidity1Valueread-onlyobsoleteHumidity of this PM unit . If the humidity measurement is not installed this value will be 0.
1.3.6.1.4.1.10418.16.2.5.3.1.25ColumnacsPowerMgmtPDUTableHumidity1Maxread-writeobsoleteMaximum humidity detected in this PM unit. If the humidity measurement is not installed or the PDU does not have support for maximum value this value will be 0…
1.3.6.1.4.1.10418.16.2.5.3.1.26ColumnacsPowerMgmtPDUTableHumidity2Valueread-onlyobsoleteHumidity of this PM unit . If the humidity measurement is not installed this value will be 0.
1.3.6.1.4.1.10418.16.2.5.3.1.27ColumnacsPowerMgmtPDUTableHumidity2Maxread-writeobsoleteMaximum humidity detected in this PM unit. If the humidity measurement is not installed or the PDU does not have support for maximum value this value will be 0…
1.3.6.1.4.1.10418.16.2.5.3.1.28ColumnacsPowerMgmtPDUTableHumidity3Valueread-onlyobsoleteHumidity of this PM unit . If the humidity measurement is not installed this value will be 0.
1.3.6.1.4.1.10418.16.2.5.3.1.29ColumnacsPowerMgmtPDUTableHumidity3Maxread-writeobsoleteMaximum humidity detected in this PM unit. If the humidity measurement is not installed or the PDU does not have support for maximum value this value will be 0…
1.3.6.1.4.1.10418.16.2.5.3.1.30ColumnacsPowerMgmtPDUTableVoltageNOSread-onlyobsoleteNumber of voltage sensors in the PDU.
1.3.6.1.4.1.10418.16.2.5.3.1.31ColumnacsPowerMgmtPDUTableVoltage1Valueread-onlyobsoleteVoltage of this sensor in this PDU unit.
1.3.6.1.4.1.10418.16.2.5.3.1.32ColumnacsPowerMgmtPDUTableVoltage1Maxread-writeobsoleteMaximum voltage of this sensor in this PDU unit. Set with Zero value to clear the maximum voltage.
1.3.6.1.4.1.10418.16.2.5.3.1.33ColumnacsPowerMgmtPDUTableVoltage2Valueread-onlyobsoleteVoltage of this sensor in this PDU unit.
1.3.6.1.4.1.10418.16.2.5.3.1.34ColumnacsPowerMgmtPDUTableVoltage2Maxread-writeobsoleteMaximum voltage of this sensor in this PDU unit. Set with Zero value to clear the maximum voltage.
1.3.6.1.4.1.10418.16.2.5.3.1.35ColumnacsPowerMgmtPDUTableVoltage3Valueread-onlyobsoleteVoltage of this sensor in this PDU unit.
1.3.6.1.4.1.10418.16.2.5.3.1.36ColumnacsPowerMgmtPDUTableVoltage3Maxread-writeobsoleteMaximum voltage of this sensor in this PDU unit. Set with Zero value to clear the maximum voltage.
1.3.6.1.4.1.10418.16.2.5.3.1.37ColumnacsPowerMgmtPDUTableNumberOfPhasesread-onlycurrentNumber of phases of this PDU unit.
1.3.6.1.4.1.10418.16.2.5.3.1.38ColumnacsPowerMgmtPDUTableNumberOfBanksread-onlycurrentNumber of banks of this PDU unit.
1.3.6.1.4.1.10418.16.2.5.3.1.39ColumnacsPowerMgmtPDUTableCurrentValueread-onlycurrentActual value of current sensor in this PDU.( A x 10 )
1.3.6.1.4.1.10418.16.2.5.3.1.40ColumnacsPowerMgmtPDUTableCurrentMaxread-onlycurrentMax detected value of current sensor in this PDU.( A x 10 )
1.3.6.1.4.1.10418.16.2.5.3.1.41ColumnacsPowerMgmtPDUTableCurrentMinread-onlycurrentMin detected value of current sensor in this PDU.( A x 10 )
1.3.6.1.4.1.10418.16.2.5.3.1.42ColumnacsPowerMgmtPDUTableCurrentAvgread-onlycurrentAverage value for current sensor in this PDU.( A x 10 )
1.3.6.1.4.1.10418.16.2.5.3.1.43ColumnacsPowerMgmtPDUTableCurrentResetread-writecurrentReset max, min and avg values of current.
1.3.6.1.4.1.10418.16.2.5.3.1.44ColumnacsPowerMgmtPDUTableVoltageTyperead-onlycurrentType of voltage values.
1.3.6.1.4.1.10418.16.2.5.3.1.45ColumnacsPowerMgmtPDUTableVoltageValueread-onlycurrentActual value of voltage sensor in this PDU unit.( V )
1.3.6.1.4.1.10418.16.2.5.3.1.46ColumnacsPowerMgmtPDUTableVoltageMaxread-onlycurrentMax detected value of voltage sensor in this PDU unit.( V )
1.3.6.1.4.1.10418.16.2.5.3.1.47ColumnacsPowerMgmtPDUTableVoltageMinread-onlycurrentMin detected value of voltage sensor in this PDU unit.( V )
1.3.6.1.4.1.10418.16.2.5.3.1.48ColumnacsPowerMgmtPDUTableVoltageAvgread-onlycurrentAverage value for voltage sensor in this PDU unit.( V )
1.3.6.1.4.1.10418.16.2.5.3.1.49ColumnacsPowerMgmtPDUTableVoltageResetread-writecurrentReset max, min and avg values of voltage.
1.3.6.1.4.1.10418.16.2.5.3.1.50ColumnacsPowerMgmtPDUTablePowerTyperead-onlycurrentType of power consumption values.( W x 10 )
1.3.6.1.4.1.10418.16.2.5.3.1.51ColumnacsPowerMgmtPDUTablePowerValueread-onlycurrentActual value of power consumption in this PDU unit.( W x 10 )
1.3.6.1.4.1.10418.16.2.5.3.1.52ColumnacsPowerMgmtPDUTablePowerMaxread-onlycurrentMax detected value of power consumption in this PDU unit.( W x 10 )
1.3.6.1.4.1.10418.16.2.5.3.1.53ColumnacsPowerMgmtPDUTablePowerMinread-onlycurrentMin detected value of power consumption in this PDU unit.( W x 10 )
1.3.6.1.4.1.10418.16.2.5.3.1.54ColumnacsPowerMgmtPDUTablePowerAvgread-onlycurrentAverage value for power consumption in this PDU unit.( W x 10 )
1.3.6.1.4.1.10418.16.2.5.3.1.55ColumnacsPowerMgmtPDUTablePowerResetread-writecurrentReset max, min and avg values of power consumption.
1.3.6.1.4.1.10418.16.2.5.3.1.56ColumnacsPowerMgmtPDUTablePowerFactorTyperead-onlycurrentType of power factor values.
1.3.6.1.4.1.10418.16.2.5.3.1.57ColumnacsPowerMgmtPDUTablePowerFactorValueread-onlycurrentActual value of power factor in this PDU unit.( PF x 100 )
1.3.6.1.4.1.10418.16.2.5.3.1.58ColumnacsPowerMgmtPDUTablePowerFactorMaxread-onlycurrentMax detected value of power factor in this PDU unit.( PF x 100 )
1.3.6.1.4.1.10418.16.2.5.3.1.59ColumnacsPowerMgmtPDUTablePowerFactorMinread-onlycurrentMin detected value of power factor in this PDU unit.( PF x 100 )
1.3.6.1.4.1.10418.16.2.5.3.1.60ColumnacsPowerMgmtPDUTablePowerFactorAvgread-onlycurrentAverage value for power factor in this PDU unit.( PF x 100 )
1.3.6.1.4.1.10418.16.2.5.3.1.61ColumnacsPowerMgmtPDUTablePowerFactorResetread-writecurrentReset max, min and avg values of power factor.
1.3.6.1.4.1.10418.16.2.5.3.1.62ColumnacsPowerMgmtPDUTableAlarmread-onlycurrentShow the PDU alarm status.
1.3.6.1.4.1.10418.16.2.5.3.1.63ColumnacsPowerMgmtPDUTableEnvSensorsread-onlycurrentNumber of environmental sensor in this PDU.
1.3.6.1.4.1.10418.16.2.5.4ScalaracsPowerMgmtTotalNumberOfOutletsread-onlycurrentNumber of outlets managed by the appliance.
1.3.6.1.4.1.10418.16.2.5.5TableacsPowerMgmtOutletsTablenot-accessiblecurrentThis table contains the information about outlets.
1.3.6.1.4.1.10418.16.2.5.5.1RowacsPowerMgmtOutletsTableEntrynot-accessiblecurrenteach entry has the information about the outlet.
1.3.6.1.4.1.10418.16.2.5.5.1.1ColumnacsPowerMgmtOutletsTablePortNumberread-onlycurrentSerial Port number.
1.3.6.1.4.1.10418.16.2.5.5.1.2ColumnacsPowerMgmtOutletsTablePduNumberread-onlycurrentIndex.
1.3.6.1.4.1.10418.16.2.5.5.1.3ColumnacsPowerMgmtOutletsTableNumberread-onlycurrentNumber of the outlet in the PDU.
1.3.6.1.4.1.10418.16.2.5.5.1.4ColumnacsPowerMgmtOutletsTableNameread-onlycurrentName of the outlet.
1.3.6.1.4.1.10418.16.2.5.5.1.5ColumnacsPowerMgmtOutletsTableStatusread-onlycurrentStatus of the outlet.
1.3.6.1.4.1.10418.16.2.5.5.1.6ColumnacsPowerMgmtOutletsTablePowerControlread-writecurrentA set value of power*(2-6) will send command to PDU. noAction(1) = always returned in a GET. Does nothing if SET. powerOn(2) = when SET the power On command is…
1.3.6.1.4.1.10418.16.2.5.5.1.7ColumnacsPowerMgmtOutletsTablePortNameread-onlycurrentSerial Port Name where the PDU is connected.
1.3.6.1.4.1.10418.16.2.5.5.1.8ColumnacsPowerMgmtOutletsTablePduIdread-onlycurrentPDU identification.
1.3.6.1.4.1.10418.16.2.5.6ScalaracsPowerMgmtNumberOfOutletGroupread-onlycurrentNumber of configured group of outlets.
1.3.6.1.4.1.10418.16.2.5.7TableacsPowerMgmtGroupTablenot-accessiblecurrentThis table contains the information about group of outlets.
1.3.6.1.4.1.10418.16.2.5.7.1RowacsPowerMgmtGroupTableEntrynot-accessiblecurrenteach entry has the information about group of outlets.
1.3.6.1.4.1.10418.16.2.5.7.1.1ColumnacsPowerMgmtGroupTableIndexread-onlycurrentIndex of the group.
1.3.6.1.4.1.10418.16.2.5.7.1.2ColumnacsPowerMgmtGroupTableNameread-onlycurrentName of the group of outlets.
1.3.6.1.4.1.10418.16.2.5.7.1.3ColumnacsPowerMgmtGroupTableStatusread-onlycurrentStatus of the group of outlet.
1.3.6.1.4.1.10418.16.2.5.7.1.4ColumnacsPowerMgmtGroupTablePowerControlread-writecurrentA set value of power*(2-6) will send command to PDU. noAction(1) = always returned in a GET. Does nothing if SET. powerOn(2) = when SET the power On command is…
1.3.6.1.4.1.10418.16.2.5.8TableacsPowerMgmtPhasesTablenot-accessiblecurrentThis table contains data monitoring of each detected phase.
1.3.6.1.4.1.10418.16.2.5.8.1RowacsPowerMgmtPhasesTableEntrynot-accessiblecurrenteach entry has the data monitoring about phases.
1.3.6.1.4.1.10418.16.2.5.8.1.1ColumnacsPowerMgmtPhasesTablePortNumberread-onlycurrentNumber of serial port when the PDU is connected.
1.3.6.1.4.1.10418.16.2.5.8.1.2ColumnacsPowerMgmtPhasesTablePduIndexread-onlycurrentA PDU position in the chain.
1.3.6.1.4.1.10418.16.2.5.8.1.3ColumnacsPowerMgmtPhasesTablePhaseIndexread-onlycurrentphase index in the PDU.
1.3.6.1.4.1.10418.16.2.5.8.1.4ColumnacsPowerMgmtPhasesTablePhaseNameread-onlycurrentphase name in the PDU.
1.3.6.1.4.1.10418.16.2.5.8.1.5ColumnacsPowerMgmtPhasesTablePduIdread-onlycurrentPDU identification.
1.3.6.1.4.1.10418.16.2.5.8.1.6ColumnacsPowerMgmtPhasesTablePortNameread-onlycurrentName of serial port when the PDU is connected.
1.3.6.1.4.1.10418.16.2.5.8.1.7ColumnacsPowerMgmtPhasesTableCurrentValueread-onlycurrentActual value of current sensor in this phase.( A x 10 )
1.3.6.1.4.1.10418.16.2.5.8.1.8ColumnacsPowerMgmtPhasesTableCurrentMaxread-onlycurrentMax detected value of current sensor in this phase.( A x 10 )
1.3.6.1.4.1.10418.16.2.5.8.1.9ColumnacsPowerMgmtPhasesTableCurrentMinread-onlycurrentMin detected value of current sensor in this phase.( A x 10 )
1.3.6.1.4.1.10418.16.2.5.8.1.10ColumnacsPowerMgmtPhasesTableCurrentAvgread-onlycurrentAverage value for current sensor in this phase.( A x 10 )
1.3.6.1.4.1.10418.16.2.5.8.1.11ColumnacsPowerMgmtPhasesTableCurrentResetread-writecurrentReset max, min and avg values of current.
1.3.6.1.4.1.10418.16.2.5.8.1.12ColumnacsPowerMgmtPhasesTableVoltageTyperead-onlycurrentType of voltage values.
1.3.6.1.4.1.10418.16.2.5.8.1.13ColumnacsPowerMgmtPhasesTableVoltageValueread-onlycurrentActual value of voltage sensor in this phase.( V )
1.3.6.1.4.1.10418.16.2.5.8.1.14ColumnacsPowerMgmtPhasesTableVoltageMaxread-onlycurrentMax detected value of voltage sensor in this phase.( V )
1.3.6.1.4.1.10418.16.2.5.8.1.15ColumnacsPowerMgmtPhasesTableVoltageMinread-onlycurrentMin detected value of voltage sensor in this phase.( V )
1.3.6.1.4.1.10418.16.2.5.8.1.16ColumnacsPowerMgmtPhasesTableVoltageAvgread-onlycurrentAverage value for voltage sensor in this phase.( V )
1.3.6.1.4.1.10418.16.2.5.8.1.17ColumnacsPowerMgmtPhasesTableVoltageResetread-writecurrentReset max, min and avg values of voltage.
1.3.6.1.4.1.10418.16.2.5.8.1.18ColumnacsPowerMgmtPhasesTablePowerTyperead-onlycurrentType of power consumption values.
1.3.6.1.4.1.10418.16.2.5.8.1.19ColumnacsPowerMgmtPhasesTablePowerValueread-onlycurrentActual value of power consumption in this phase.( W x 10 )
1.3.6.1.4.1.10418.16.2.5.8.1.20ColumnacsPowerMgmtPhasesTablePowerMaxread-onlycurrentMax detected value of power consumption in this phase.( W x 10 )
1.3.6.1.4.1.10418.16.2.5.8.1.21ColumnacsPowerMgmtPhasesTablePowerMinread-onlycurrentMin detected value of power consumption in this phase.( W x 10 )
1.3.6.1.4.1.10418.16.2.5.8.1.22ColumnacsPowerMgmtPhasesTablePowerAvgread-onlycurrentAverage value for power consumption in this phase.( W x 10 )
1.3.6.1.4.1.10418.16.2.5.8.1.23ColumnacsPowerMgmtPhasesTablePowerResetread-writecurrentReset max, min and avg values of power consumption.
1.3.6.1.4.1.10418.16.2.5.8.1.24ColumnacsPowerMgmtPhasesTablePowerFactorTyperead-onlycurrentType of power factor values.
1.3.6.1.4.1.10418.16.2.5.8.1.25ColumnacsPowerMgmtPhasesTablePowerFactorValueread-onlycurrentActual value of power factor in this phase.( PF x 100 )
1.3.6.1.4.1.10418.16.2.5.8.1.26ColumnacsPowerMgmtPhasesTablePowerFactorMaxread-onlycurrentMax detected value of power factor in this phase.( PF x 100 )
1.3.6.1.4.1.10418.16.2.5.8.1.27ColumnacsPowerMgmtPhasesTablePowerFactorMinread-onlycurrentMin detected value of power factor in this phase.( PF x 100 )
1.3.6.1.4.1.10418.16.2.5.8.1.28ColumnacsPowerMgmtPhasesTablePowerFactorAvgread-onlycurrentAverage value for power factor in this phase.( PF x 100 )
1.3.6.1.4.1.10418.16.2.5.8.1.29ColumnacsPowerMgmtPhasesTablePowerFactorResetread-writecurrentReset max, min and avg values of power factor.
1.3.6.1.4.1.10418.16.2.5.8.1.30ColumnacsPowerMgmtPhasesTableAlarmread-onlycurrentShow the phase alarm status.
1.3.6.1.4.1.10418.16.2.5.9TableacsPowerMgmtBanksTablenot-accessiblecurrentThis table contains data monitoring of each detected bank.
1.3.6.1.4.1.10418.16.2.5.9.1RowacsPowerMgmtBanksTableEntrynot-accessiblecurrenteach entry has the data monitoring about bank.
1.3.6.1.4.1.10418.16.2.5.9.1.1ColumnacsPowerMgmtBanksTablePortNumberread-onlycurrentNumber of serial port when the PDU is connected.
1.3.6.1.4.1.10418.16.2.5.9.1.2ColumnacsPowerMgmtBanksTablePduIndexread-onlycurrentA PDU position in the chain.
1.3.6.1.4.1.10418.16.2.5.9.1.3ColumnacsPowerMgmtBanksTableBankIndexread-onlycurrentBank index in the PDU.
1.3.6.1.4.1.10418.16.2.5.9.1.4ColumnacsPowerMgmtBanksTableBankNameread-onlycurrentBank name in the PDU.
1.3.6.1.4.1.10418.16.2.5.9.1.5ColumnacsPowerMgmtBanksTablePduIdread-onlycurrentPDU identification.
1.3.6.1.4.1.10418.16.2.5.9.1.6ColumnacsPowerMgmtBanksTablePortNameread-onlycurrentName of serial port when the PDU is connected.
1.3.6.1.4.1.10418.16.2.5.9.1.7ColumnacsPowerMgmtBanksTableCurrentValueread-onlycurrentActual value of current sensor in this bank.( A x 10 )
1.3.6.1.4.1.10418.16.2.5.9.1.8ColumnacsPowerMgmtBanksTableCurrentMaxread-onlycurrentMax detected value of current sensor in this bank.( A x 10 )
1.3.6.1.4.1.10418.16.2.5.9.1.9ColumnacsPowerMgmtBanksTableCurrentMinread-onlycurrentMin detected value of current sensor in this bank.( A x 10 )
1.3.6.1.4.1.10418.16.2.5.9.1.10ColumnacsPowerMgmtBanksTableCurrentAvgread-onlycurrentAverage value for current sensor in this bank.( A x 10 )
1.3.6.1.4.1.10418.16.2.5.9.1.11ColumnacsPowerMgmtBanksTableCurrentResetread-writecurrentReset max, min and avg values of current.
1.3.6.1.4.1.10418.16.2.5.9.1.12ColumnacsPowerMgmtBanksTableVoltageTyperead-onlycurrentType of voltage values.
1.3.6.1.4.1.10418.16.2.5.9.1.13ColumnacsPowerMgmtBanksTableVoltageValueread-onlycurrentActual value of voltage sensor in this bank.( V )
1.3.6.1.4.1.10418.16.2.5.9.1.14ColumnacsPowerMgmtBanksTableVoltageMaxread-onlycurrentMax detected value of voltage sensor in this bank.( V )
1.3.6.1.4.1.10418.16.2.5.9.1.15ColumnacsPowerMgmtBanksTableVoltageMinread-onlycurrentMin detected value of voltage sensor in this bank.( V )
1.3.6.1.4.1.10418.16.2.5.9.1.16ColumnacsPowerMgmtBanksTableVoltageAvgread-onlycurrentAverage value for voltage sensor in this bank.( V )
1.3.6.1.4.1.10418.16.2.5.9.1.17ColumnacsPowerMgmtBanksTableVoltageResetread-writecurrentReset max, min and avg values of voltage.
1.3.6.1.4.1.10418.16.2.5.9.1.18ColumnacsPowerMgmtBanksTablePowerTyperead-onlycurrentType of power consumption values.
1.3.6.1.4.1.10418.16.2.5.9.1.19ColumnacsPowerMgmtBanksTablePowerValueread-onlycurrentActual value of power consumption in this bank.( W x 10 )
1.3.6.1.4.1.10418.16.2.5.9.1.20ColumnacsPowerMgmtBanksTablePowerMaxread-onlycurrentMax detected value of power consumption in this bank.( W x 10 )
1.3.6.1.4.1.10418.16.2.5.9.1.21ColumnacsPowerMgmtBanksTablePowerMinread-onlycurrentMin detected value of power consumption in this bank.( W x 10 )
1.3.6.1.4.1.10418.16.2.5.9.1.22ColumnacsPowerMgmtBanksTablePowerAvgread-onlycurrentAverage value for power consumption in this bank.( W x 10 )
1.3.6.1.4.1.10418.16.2.5.9.1.23ColumnacsPowerMgmtBanksTablePowerResetread-writecurrentReset max, min and avg values of power consumption.
1.3.6.1.4.1.10418.16.2.5.9.1.24ColumnacsPowerMgmtBanksTablePowerFactorTyperead-onlycurrentType of power factor values.
1.3.6.1.4.1.10418.16.2.5.9.1.25ColumnacsPowerMgmtBanksTablePowerFactorValueread-onlycurrentActual value of power factor in this bank.( PF x 100 )
1.3.6.1.4.1.10418.16.2.5.9.1.26ColumnacsPowerMgmtBanksTablePowerFactorMaxread-onlycurrentMax detected value of power factor in this bank.( PF x 100 )
1.3.6.1.4.1.10418.16.2.5.9.1.27ColumnacsPowerMgmtBanksTablePowerFactorMinread-onlycurrentMin detected value of power factor in this bank.( PF x 100 )
1.3.6.1.4.1.10418.16.2.5.9.1.28ColumnacsPowerMgmtBanksTablePowerFactorAvgread-onlycurrentAverage value for power factor in this bank.( PF x 100 )
1.3.6.1.4.1.10418.16.2.5.9.1.29ColumnacsPowerMgmtBanksTablePowerFactorResetread-writecurrentReset max, min and avg values of power factor.
1.3.6.1.4.1.10418.16.2.5.9.1.30ColumnacsPowerMgmtBanksTableAlarmread-onlycurrentShow the bank alarm status.
1.3.6.1.4.1.10418.16.2.5.10TableacsPowerMgmtEnvMonTablenot-accessiblecurrentThis table contains data monitoring of each detected environmental sensor.
1.3.6.1.4.1.10418.16.2.5.10.1RowacsPowerMgmtEnvMonTableEntrynot-accessiblecurrenteach entry has the data monitoring about environmental sensors.
1.3.6.1.4.1.10418.16.2.5.10.1.1ColumnacsPowerMgmtEnvMonTablePortNumberread-onlycurrentNumber of serial port when the PDU is connected.
1.3.6.1.4.1.10418.16.2.5.10.1.2ColumnacsPowerMgmtEnvMonTablePduIndexread-onlycurrentA PDU position in the chain.
1.3.6.1.4.1.10418.16.2.5.10.1.3ColumnacsPowerMgmtEnvMonTableIndexread-onlycurrentenvmon sensor index.
1.3.6.1.4.1.10418.16.2.5.10.1.4ColumnacsPowerMgmtEnvMonTableNameread-onlycurrentenvmon sensor name.
1.3.6.1.4.1.10418.16.2.5.10.1.5ColumnacsPowerMgmtEnvMonTablePduIdread-onlycurrentPDU identification.
1.3.6.1.4.1.10418.16.2.5.10.1.6ColumnacsPowerMgmtEnvMonTablePortNameread-onlycurrentName of serial port when the PDU is connected.
1.3.6.1.4.1.10418.16.2.5.10.1.7ColumnacsPowerMgmtEnvMonTableTyperead-onlycurrentThe type of environmental monitor.
1.3.6.1.4.1.10418.16.2.5.10.1.8ColumnacsPowerMgmtEnvMonTableStatusread-onlycurrentStatus of digital sensors: Dry-Contact, Water level, Smoke sensor, Motion sensor.
1.3.6.1.4.1.10418.16.2.5.10.1.9ColumnacsPowerMgmtEnvMonTableValueread-onlycurrentDetected value for envmon sensors. Temperature: C x 10. Humidity: %. Air flow: afu.
1.3.6.1.4.1.10418.16.2.5.10.1.10ColumnacsPowerMgmtEnvMonTableMaxValueread-onlycurrentMax detected value for envmon sensors. Temperature: C x 10. Humidity: %. Air flow: afu.
1.3.6.1.4.1.10418.16.2.5.11TableacsPowerMgmtOutElecMonTablenot-accessiblecurrentThis table contains the information about data monitoring of outlets.
1.3.6.1.4.1.10418.16.2.5.11.1RowacsPowerMgmtOutElecMonTableEntrynot-accessiblecurrenteach entry has the information about the outlet.
1.3.6.1.4.1.10418.16.2.5.11.1.1ColumnacsPowerMgmtOutElecMonTablePortNumberread-onlycurrentSerial Port number.
1.3.6.1.4.1.10418.16.2.5.11.1.2ColumnacsPowerMgmtOutElecMonTablePduNumberread-onlycurrentIndex.
1.3.6.1.4.1.10418.16.2.5.11.1.3ColumnacsPowerMgmtOutElecMonTableNumberread-onlycurrentNumber of the outlet in the PDU.
1.3.6.1.4.1.10418.16.2.5.11.1.4ColumnacsPowerMgmtOutElecMonTableCurrentValueread-onlycurrentActual value of outlet current sensor.( A x 10 )
1.3.6.1.4.1.10418.16.2.5.11.1.5ColumnacsPowerMgmtOutElecMonTableCurrentMaxread-onlycurrentMax detected value of outlet current sensor.( A x 10 )
1.3.6.1.4.1.10418.16.2.5.11.1.6ColumnacsPowerMgmtOutElecMonTableCurrentMinread-onlycurrentMin detected value of outlet current sensor.( A x 10 )
1.3.6.1.4.1.10418.16.2.5.11.1.7ColumnacsPowerMgmtOutElecMonTableCurrentAvgread-onlycurrentAverage value for outlet current sensor.( A x 10 )
1.3.6.1.4.1.10418.16.2.5.11.1.8ColumnacsPowerMgmtOutElecMonTableCurrentResetread-writecurrentReset max, min and avertage values of outlet current.
1.3.6.1.4.1.10418.16.2.5.11.1.9ColumnacsPowerMgmtOutElecMonTablePowerValueread-onlycurrentActual value of outlet power comsumption sensor.( W x 10 )
1.3.6.1.4.1.10418.16.2.5.11.1.10ColumnacsPowerMgmtOutElecMonTablePowerMaxread-onlycurrentMax detected value of outlet power comsumption sensor.( W x 10 )
1.3.6.1.4.1.10418.16.2.5.11.1.11ColumnacsPowerMgmtOutElecMonTablePowerMinread-onlycurrentMin detected value of outlet power comsumption sensor.( W x 10 )
1.3.6.1.4.1.10418.16.2.5.11.1.12ColumnacsPowerMgmtOutElecMonTablePowerAvgread-onlycurrentAverage value for outlet power comsumption sensor.( W x 10 )
1.3.6.1.4.1.10418.16.2.5.11.1.13ColumnacsPowerMgmtOutElecMonTablePowerResetread-writecurrentReset max, min and avertage values of outlet power comsumption.
1.3.6.1.4.1.10418.16.2.5.11.1.14ColumnacsPowerMgmtOutElecMonTableVoltageValueread-onlycurrentActual value of outlet voltage sensor.( V )
1.3.6.1.4.1.10418.16.2.5.11.1.15ColumnacsPowerMgmtOutElecMonTableVoltageMaxread-onlycurrentMax detected value of outlet voltage sensor.( V )
1.3.6.1.4.1.10418.16.2.5.11.1.16ColumnacsPowerMgmtOutElecMonTableVoltageMinread-onlycurrentMin detected value of outlet voltage sensor.( V )
1.3.6.1.4.1.10418.16.2.5.11.1.17ColumnacsPowerMgmtOutElecMonTableVoltageAvgread-onlycurrentAverage value for outlet voltage sensor.( V )
1.3.6.1.4.1.10418.16.2.5.11.1.18ColumnacsPowerMgmtOutElecMonTableVoltageResetread-writecurrentReset max, min and avertage values of outlet voltage.
1.3.6.1.4.1.10418.16.2.5.11.1.19ColumnacsPowerMgmtOutElecMonTablePowerFactorValueread-onlycurrentActual value of outlet power-factor sensor.( PF x 100 )
1.3.6.1.4.1.10418.16.2.5.11.1.20ColumnacsPowerMgmtOutElecMonTablePowerFactorMaxread-onlycurrentMax detected value of outlet power-factor sensor.( PF x 100 )
1.3.6.1.4.1.10418.16.2.5.11.1.21ColumnacsPowerMgmtOutElecMonTablePowerFactorMinread-onlycurrentMin detected value of outlet power-factor sensor.( PF x 100 )
1.3.6.1.4.1.10418.16.2.5.11.1.22ColumnacsPowerMgmtOutElecMonTablePowerFactorAvgread-onlycurrentAverage value for outlet power-factor sensor.( PF x 100 )
1.3.6.1.4.1.10418.16.2.5.11.1.23ColumnacsPowerMgmtOutElecMonTablePowerFactorResetread-writecurrentReset max, min and avertage values of outlet power-factor.
1.3.6.1.4.1.10418.16.2.5.11.1.24ColumnacsPowerMgmtOutElecMonTableAlarmread-onlycurrentShow the outlet alarm status.
1.3.6.1.4.1.10418.16.2.6NodeacsTrapObject