MIB Viewer

ALGPOWER_v2-MIB

58 objects
No module-level DESCRIPTION found.
Imported Objects
RFC-1212OBJECT-TYPE
RFC1155-SMIenterprises
RFC1213-MIBDisplayString
OIDNameAccessStatusDescription
1.3.6.1.4.1.49136Nodealgcom
1.3.6.1.4.1.49136.1NodeupsObjects
1.3.6.1.4.1.49136.1.1Nodeoutput
1.3.6.1.4.1.49136.1.1.1ScalaroutputVoltageread-onlymandatoryNumeric value of instantaneous output voltage from the source in tenths of a volt. To get the value actual in volt should be divided by 10. Example: Read value…
1.3.6.1.4.1.49136.1.1.2ScalaroutputCurrentread-onlymandatoryNumeric value of current output of converter AC/DC. Real value reading in milli ampere. Example: Read value 1087, Actual value 1.087 milli ampere or 1.087A. If…
1.3.6.1.4.1.49136.1.1.3ScalaroidNotUsed0read-onlymandatoryOID not used.
1.3.6.1.4.1.49136.1.1.4ScalaroidNotUsed1read-onlymandatoryOID not used.
1.3.6.1.4.1.49136.1.2Nodebattery
1.3.6.1.4.1.49136.1.2.1ScalarbatteryVoltageread-onlymandatoryNumeric value of instantaneous voltage of battery bank. To get the actual value in volt must be divided by 10. Example: Read value 240, actual value 24.0V.
1.3.6.1.4.1.49136.1.2.2ScalarbatteryCurrentread-onlymandatoryNumeric value of current in Battery bank. Real value reading in milli ampere. If the value is negative the Battery bank is provide energy for the output. If th…
1.3.6.1.4.1.49136.1.2.3ScalarchargerStatusread-onlymandatoryShow the status of battery charger: 0 - The battery is not connected in DC UPS; 1 - The battery is voltage incompatible with DC UPS; 2 - The DC UPS is in nobre…
1.3.6.1.4.1.49136.1.3Nodeinput
1.3.6.1.4.1.49136.1.3.1ScalaralarmOnBatteryread-onlymandatoryShows the operation mode of DC-UPS: 0 - The DC-UPS output is provide by AC energy. 1 - The DC-UPS output is provide by Battery
1.3.6.1.4.1.49136.1.3.2ScalaracFailread-onlymandatoryAlarm that alert about AC outages in the last 10 minutes: 0 - DC-UPS in normal operation. 1 - Occur a AC fail in the last 10 minutes.
1.3.6.1.4.1.49136.1.3.3ScalarbatteryChargingread-onlymandatoryShow the status of charging Battery: 1 - The battery is on charging. 0 - The battery is on discharging.
1.3.6.1.4.1.49136.1.3.4ScalarbatteryDischargingread-onlymandatoryShow the status of discharging Battery: 1 - The battery is on discharging. 0 - The battery is on charging.
1.3.6.1.4.1.49136.1.3.5Scalaroverheatread-onlymandatoryAlarm that alert about overtemperature of DC-UPS 1 - The DC-UPS is in condition of overtemperature. 0 - The DC-UPS is in normal condition.
1.3.6.1.4.1.49136.1.3.6Scalaroverloadread-onlymandatoryAlarm that alert about overload of DC-UPS 1 - The DC-UPS is in condition of overload. 0 - The DC-UPS is in normal condition.
1.3.6.1.4.1.49136.1.3.7ScalarfanAfailread-onlymandatoryAlarm that alert about fail in internal FAN A 1 - Internal FAN with fail. 0 - Internal FAN ok
1.3.6.1.4.1.49136.1.3.8ScalarfanBfailread-onlymandatoryAlarm that alert about fail in internal FAN B 1 - Internal FAN with fail. 0 - Internal FAN ok
1.3.6.1.4.1.49136.1.3.9ScalaroidNotUsed2read-onlymandatoryOID not used.
1.3.6.1.4.1.49136.1.3.10ScalaroidNotUsed3read-onlymandatoryOID not used.
1.3.6.1.4.1.49136.1.3.11ScalarupTimeread-onlymandatorySystem Up time in hours
1.3.6.1.4.1.49136.1.4Nodetemperature
1.3.6.1.4.1.49136.1.4.1ScalarinnerTemperatureread-onlymandatoryShow the internal temperature of power supply. Uses the unit degree Celsius. Example Read value: 25, temperature is 25ºC.
1.3.6.1.4.1.49136.1.4.2ScalarouterTemperatureread-onlymandatoryShow the temperature of external sensor (cable that comes with power supply). Uses the unit degree Celsius. Example Read value: 25, temperature is 25ºC.
1.3.6.1.4.1.49136.1.4.3ScalarheatSinkTemperatureread-onlymandatoryShow the temperature of sensor in the heatsink of power supply use the unit degree Celsius. Example Read value: 25, temperature is 25ºC.
1.3.6.1.4.1.49136.1.5Nodewatchdog
1.3.6.1.4.1.49136.1.5.1ScalarwatchdogPing1read-onlymandatoryAlarm indicating the action of watchdog 1 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from I…
1.3.6.1.4.1.49136.1.5.2ScalarwatchdogPing2read-onlymandatoryAlarm indicating the action of watchdog 2 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from I…
1.3.6.1.4.1.49136.1.5.3ScalarwatchdogPing3read-onlymandatoryAlarm indicating the action of watchdog 3 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from I…
1.3.6.1.4.1.49136.1.5.4ScalarwatchdogPing4read-onlymandatoryAlarm indicating the action of watchdog 4 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from I…
1.3.6.1.4.1.49136.1.5.5ScalarwatchdogPing5read-onlymandatoryAlarm indicating the action of watchdog 5 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from I…
1.3.6.1.4.1.49136.1.5.6ScalarwatchdogPing6read-onlymandatoryAlarm indicating the action of watchdog 6 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from I…
1.3.6.1.4.1.49136.1.5.7ScalarwatchdogPing7read-onlymandatoryAlarm indicating the action of watchdog 7 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from I…
1.3.6.1.4.1.49136.1.5.8ScalarwatchdogPing8read-onlymandatoryAlarm indicating the action of watchdog 8 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from I…
1.3.6.1.4.1.49136.1.5.9ScalarwatchdogPing9read-onlymandatoryAlarm indicating the action of watchdog 9 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from I…
1.3.6.1.4.1.49136.1.5.10ScalarwatchdogPing10read-onlymandatoryAlarm indicating the action of watchdog 10 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from …
1.3.6.1.4.1.49136.1.6Nodesupply
1.3.6.1.4.1.49136.1.6.1ScalarsupplyVoltageread-onlymandatoryThe supply AC voltage decivolt [dV] Numeric value of instantaneous input voltage. An optional sensor is required to read this value. To get the actual value in…
1.3.6.1.4.1.49136.1.7Nodeinstallation
1.3.6.1.4.1.49136.1.7.1ScalarpopNameread-onlymandatoryPoP name
1.3.6.1.4.1.49136.1.7.2ScalarfacilityAddrread-onlymandatoryFacility address
1.3.6.1.4.1.49136.1.7.3ScalarfacilityCityread-onlymandatoryFacility city
1.3.6.1.4.1.49136.1.7.4ScalarinstDateread-onlymandatoryInstallation date
1.3.6.1.4.1.49136.1.7.5ScalarbatCapacityread-onlymandatoryBattery capacity
1.3.6.1.4.1.49136.1.7.6ScalarbatBrandread-onlymandatoryBattery brand
1.3.6.1.4.1.49136.1.7.7ScalarbatInstDateread-onlymandatoryBattery installation date
1.3.6.1.4.1.49136.1.7.8ScalarrespPersread-onlymandatoryResponsible person
1.3.6.1.4.1.49136.1.8Nodebat_tst
1.3.6.1.4.1.49136.1.8.1Scalarbtst_dateread-onlymandatoryBattery test execution date (dd/mm/yyyy)
1.3.6.1.4.1.49136.1.8.2Scalarbtst_statusread-onlymandatoryBattery test status 0 - NEVER DONE 1 - Passed 2 - Running 3 - Aborted 4 - Failed
1.3.6.1.4.1.49136.1.8.3Scalarbtst_durationread-onlymandatoryProgrammed test duration in minutes * 999 - Perform the test until battery is fully discharged
1.3.6.1.4.1.49136.1.8.4Scalarbtst_elapsedread-onlymandatoryElapsed time in current\last battery test
1.3.6.1.4.1.49136.1.8.5Scalarbtst_volt_iread-onlymandatoryThe battery initial voltage [dV] Numeric value of battery voltage when starting the battery test. Example: Read value 241, actual value 24.1 V.
1.3.6.1.4.1.49136.1.8.6Scalarbtst_amp_iread-onlymandatoryThe battery initial cuurent [mA] Numeric value of battery current when starting the battery test. Example: Read value 1522, actual value 1.55 A.
1.3.6.1.4.1.49136.1.8.7Scalarbtst_volt_fread-onlymandatoryThe battery final voltage [dV] Numeric value of battery voltage when the battery test is done. Example: Read value 225, actual value 22.5 V.
1.3.6.1.4.1.49136.1.8.8Scalarbtst_amp_fread-onlymandatoryThe battery initial cuurent [mA] Numeric value of battery current when the battery test is done. Example: Read value 1485, actual value 1.48 A.