APNL-MODULAR-PDU-MIB
89 objects
This MIB module defines the modular PDU version of AP Nederland.
Imported Objects
| SNMPv2-SMI | enterprises Integer32 IpAddress MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE Unsigned32 |
| SNMPv2-TC | DateAndTime DisplayString |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.29640 | IdentityapNederland | This MIB module defines the modular PDU version of AP Nederland. | ||
| 1.3.6.1.4.1.29640.1 | NodeapnlDirectory | |||
| 1.3.6.1.4.1.29640.2 | NodeapnlMib | |||
| 1.3.6.1.4.1.29640.3 | NodeapnlTmp | |||
| 1.3.6.1.4.1.29640.4 | NodeapnlModules | |||
| 1.3.6.1.4.1.29640.4.1 | Nodecm | |||
| 1.3.6.1.4.1.29640.4.2 | NodecmTraps | |||
| 1.3.6.1.4.1.29640.4.3 | Nodepdu | |||
| 1.3.6.1.4.1.29640.4.3.1 | ScalarpduType | read-only | current | Type of the Pdu. PduModular (0) Modulaire OEC2 PDU communication through SNMPV3, MOD-BUS or AP-BUS in emulation mode. PduGateway1 (1) Gateway to connect OEC1 p… |
| 1.3.6.1.4.1.29640.4.3.2 | ScalarpduProductIdentifier | read-only | current | Unique serial number to identify a pdu, the number is between 1 and 65535. |
| 1.3.6.1.4.1.29640.4.3.3 | ScalarpduSerialNumber | read-only | current | PDU onboard Serial Number. |
| 1.3.6.1.4.1.29640.4.3.4 | ScalarpduStatus | read-only | current | Status of the Pdu. pduBusy (0) Indicates that an admin command is in progress. pduReady (1) The execution of an admin command was successfull. pduAlarm (2) Thi… |
| 1.3.6.1.4.1.29640.4.3.5 | ScalarpduPower | read-only | current | The total measured pdu power in Kilo Watt's*Hour. |
| 1.3.6.1.4.1.29640.4.3.6 | ScalarpduPowerL1 | read-only | current | The total measured pdu power in Kilo Watt's*Hour for phase 1. |
| 1.3.6.1.4.1.29640.4.3.7 | ScalarpduPowerL2 | read-only | current | The total measured pdu power in Kilo Watt's*Hour for phase 2. |
| 1.3.6.1.4.1.29640.4.3.8 | ScalarpduPowerL3 | read-only | current | The total measured pdu power in Kilo Watt's*Hour for phase 3. |
| 1.3.6.1.4.1.29640.4.3.9 | ScalarpduKvar | read-only | current | The total Reactive Power of the pdu. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux. |
| 1.3.6.1.4.1.29640.4.3.10 | ScalarpduKvarL1 | read-only | current | The total Reactive Power of the pdu for phase 1. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux. |
| 1.3.6.1.4.1.29640.4.3.11 | ScalarpduKvarL2 | read-only | current | The total Reactive Power of the pdu for phase 2. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux. |
| 1.3.6.1.4.1.29640.4.3.12 | ScalarpduKvarL3 | read-only | current | The total Reactive Power of the pdu for phase 3. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux. |
| 1.3.6.1.4.1.29640.4.3.13 | ScalarpdulAcurrent | read-only | current | The total measured ac current for the pdu (in 1/10th Amperes) . |
| 1.3.6.1.4.1.29640.4.3.14 | ScalarpduAcurrentL1 | read-only | current | The total measured ac current for phase 1 (in 1/10th Amperes). |
| 1.3.6.1.4.1.29640.4.3.15 | ScalarpduAcurrentL2 | read-only | current | The total measured ac current for phase 2 (in 1/10th Amperes). |
| 1.3.6.1.4.1.29640.4.3.16 | ScalarpduAcurrentL3 | read-only | current | The total measured ac current for phase 3 (in 1/10th Amperes). |
| 1.3.6.1.4.1.29640.4.3.17 | ScalarpduCurIpAddress | read-only | current | The current PDU IPv4 Address by which TCP/IP access is available. |
| 1.3.6.1.4.1.29640.4.3.18 | ScalarpduCurSubNetMask | read-only | current | The current PDU IPv4 Subnet Mask used by the Ipstack (e.g: 255.255.255.0). |
| 1.3.6.1.4.1.29640.4.3.19 | ScalarpduCurDefGwAddress | read-only | current | The current PDU IPv4 default gateway address used by the Ipstack (e.g: 192.168.1.1). |
| 1.3.6.1.4.1.29640.4.3.20 | ScalarpduNumberOfNodes | read-only | current | Number of items in the node table. |
| 1.3.6.1.4.1.29640.4.3.21 | ScalarpduNumberOfSensors | read-only | current | Number of items in the sensor table. |
| 1.3.6.1.4.1.29640.4.3.22 | ScalarpduSoftwareVersion | read-only | current | PDU software version number. |
| 1.3.6.1.4.1.29640.4.3.23 | ScalarpduFirmwareVersion | read-only | current | PDU firmware version number. |
| 1.3.6.1.4.1.29640.4.3.24 | ScalarpduBusProtocol | read-only | current | Selected protocol used on the external bus of the pdu. AP-BUS (0) Protocol used by OEC1 products or by OEC2 products in emulation mode. MOD-BUS (1) Protocol us… |
| 1.3.6.1.4.1.29640.4.3.25 | ScalarpduAdminCommand | read-write | current | PDU admin management Commands: noOp (0) No operation. rebootPdu (1) Reboot the PDU (to execute new settings). rediscover (2) Not supported. updateSofware (3) N… |
| 1.3.6.1.4.1.29640.4.3.26 | ScalarpduStartupIpAddress | read-write | current | Not supported. |
| 1.3.6.1.4.1.29640.4.3.27 | ScalarpduStartupSubNetMask | read-write | current | Not supported. |
| 1.3.6.1.4.1.29640.4.3.28 | ScalarpduStartupDefGwAddress | read-write | current | Not supported. |
| 1.3.6.1.4.1.29640.4.3.29 | ScalarpduRealTimeClock | read-write | current | PDU Real-Time Clock. Maybe set by the manager. |
| 1.3.6.1.4.1.29640.4.3.30 | ScalarpduEnableFeatures | read-write | current | Array of bits each one an specific feature within the pdu: globalWebEnabled (0) This bit enables the PDU webpages. globalUsbEnabled (1) This bit enables the US… |
| 1.3.6.1.4.1.29640.4.3.31 | ScalarpduBusAddress | read-write | current | Address used to access this PDU via the external bus. When MOD-BUS protocol is used the address is valid between 1-247. When AP-BUS protocol is used the addres… |
| 1.3.6.1.4.1.29640.4.3.32 | ScalarpduName | read-write | current | Name of the PDU. |
| 1.3.6.1.4.1.29640.4.3.33 | TablenodeTable | not-accessible | current | A table of the modules on the PDU. Each entry represents an module unit. |
| 1.3.6.1.4.1.29640.4.3.33.1 | RownodeEntry | not-accessible | current | An port entry in the port table. |
| 1.3.6.1.4.1.29640.4.3.33.1.1 | ColumnnodeIndex | not-accessible | current | The node table Index. |
| 1.3.6.1.4.1.29640.4.3.33.1.2 | ColumnnodeType | read-only | current | Type of the node. TypeUnknown (0) Unknown node. TypePresModChar (1) PM LCD Character Module. TypePresModMono (2) PM Mono Graphics Module. TypePresModGraph (3) … |
| 1.3.6.1.4.1.29640.4.3.33.1.3 | ColumnnodeOutlet | read-only | current | The number associated with the physical outlet of the node. The special value of 0 indicates that this entry is not associated with a physical port. |
| 1.3.6.1.4.1.29640.4.3.33.1.4 | ColumnnodeAlarmStatus | read-only | current | Array of bits each one indicates an alarm activated in the alarm selector value. TrapCurrHi (0) The current is to high against the high current threshold. Trap… |
| 1.3.6.1.4.1.29640.4.3.33.1.5 | ColumnnodePower | read-only | current | The measured node power in Kilo Watt's*Hour. |
| 1.3.6.1.4.1.29640.4.3.33.1.6 | ColumnnodeAcurrent | read-only | current | The measured ac current at the node (in 1/10th Amperes). |
| 1.3.6.1.4.1.29640.4.3.33.1.7 | ColumnnodePeakCurrent | read-only | current | The measured max current since last reset of the node (in 1/10th Amperes). |
| 1.3.6.1.4.1.29640.4.3.33.1.8 | ColumnnodeVoltage | read-only | current | The measured voltage on the node. |
| 1.3.6.1.4.1.29640.4.3.33.1.9 | ColumnnodeMinVoltage | read-only | current | The measured minimum voltage at the node since last reset. |
| 1.3.6.1.4.1.29640.4.3.33.1.10 | ColumnnodeKvar | read-only | current | The Reactive Power. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux. |
| 1.3.6.1.4.1.29640.4.3.33.1.11 | ColumnnodeFrequency | read-only | current | The frequency of alternating current in Hertz. e.g 50 in Europe or 60 in USA. |
| 1.3.6.1.4.1.29640.4.3.33.1.12 | ColumnnodePowerFactor | read-only | current | The effective power facton (Cosinus Phi) in percents of the node. |
| 1.3.6.1.4.1.29640.4.3.33.1.13 | ColumnnodeSwitchOperStatus | read-only | current | The actual operational Status of the node. Unknown (0) not known status. Off (1) switch is off. On (2) switch is on. |
| 1.3.6.1.4.1.29640.4.3.33.1.14 | ColumnnodeSwitchAdminStatus | read-write | current | The desired admin Status of the switch. Unknown (0) not known. Off (1) switch is off. On (2) switch is on. |
| 1.3.6.1.4.1.29640.4.3.33.1.15 | ColumnnodeCurrHiThresh | read-write | current | The current high threshold (in 1/10th Amperes). |
| 1.3.6.1.4.1.29640.4.3.33.1.16 | ColumnnodeCurrLoThresh | read-write | current | The current low threshold (in 1/10th Amperes). |
| 1.3.6.1.4.1.29640.4.3.33.1.17 | ColumnnodeVoltHiThresh | read-write | current | The voltage high threshold. |
| 1.3.6.1.4.1.29640.4.3.33.1.18 | ColumnnodeVoltLoThresh | read-write | current | The voltage low threshold. |
| 1.3.6.1.4.1.29640.4.3.33.1.19 | ColumnnodeAlarmSelector | read-write | current | Array of bits each one controls one alarm. TrapCurrHi (0) Enable/disable the high current alarm. TrapCurrLo (1) Enable/disable the low current alarm. TrapVoltH… |
| 1.3.6.1.4.1.29640.4.3.33.1.20 | ColumnnodeName | read-write | current | The node name. My be set by manager. |
| 1.3.6.1.4.1.29640.4.3.33.1.21 | ColumnnodePhase | read-write | current | The measured phase of the node. Maybe assigned when not configured in production. PhaseUnknown (0). PhaseL1 (1). PhaseL2 (2). PhaseL3 (3). |
| 1.3.6.1.4.1.29640.4.3.34 | TablesensorTable | not-accessible | current | A table of the Sensors on the PDU. Each entry represents an an Sensor unit. |
| 1.3.6.1.4.1.29640.4.3.34.1 | RowsensorEntry | not-accessible | current | An Sensor Entry in the Sensor table |
| 1.3.6.1.4.1.29640.4.3.34.1.1 | ColumnsensorIndex | not-accessible | current | The Sensor table Index. |
| 1.3.6.1.4.1.29640.4.3.34.1.2 | ColumnsensorType | read-only | current | Sensor Typ: Measured values are used according to sensor type. Other (0) unknown sensor type. Temperature (1) . Humidity (2). Smoke (3). CO1 (4). Vibration (5)… |
| 1.3.6.1.4.1.29640.4.3.34.1.3 | ColumnsensorAlarmStatus | read-only | current | Array of bits each one indicates an alarm activated in the alarm selector value. |
| 1.3.6.1.4.1.29640.4.3.34.1.4 | ColumnsensorValue | read-only | current | The measured value of the sensor, units are depending on sensor type. |
| 1.3.6.1.4.1.29640.4.3.34.1.5 | ColumnsensorSwitchOperStatus | read-only | current | The actual operational Status of the switch. |
| 1.3.6.1.4.1.29640.4.3.34.1.6 | ColumnsensorSwitchAdminStatus | read-write | current | The desired admin Status of the switch. |
| 1.3.6.1.4.1.29640.4.3.34.1.7 | ColumnsensorHiThresh | read-write | current | High threshold. |
| 1.3.6.1.4.1.29640.4.3.34.1.8 | ColumnsensorLoThresh | read-write | current | Low threshold. |
| 1.3.6.1.4.1.29640.4.3.34.1.9 | ColumnsensorAlarmSelector | read-write | current | Array of bits each one controls one alarm. E.g trap, beeper etc. |
| 1.3.6.1.4.1.29640.4.3.34.1.10 | ColumnsensorName | read-write | current | The sensor name. May be set by the manager. |
| 1.3.6.1.4.1.29640.4.4 | NodepduTraps | |||
| 1.3.6.1.4.1.29640.4.4.1 | ScalartrapType | accessible-for-notify | current | An enumation value to indicate an Alarm trap: pduPduAlarm. |
| 1.3.6.1.4.1.29640.4.4.2 | ScalarpduTableType | accessible-for-notify | current | The table type. |
| 1.3.6.1.4.1.29640.4.4.3 | ScalartrapTableIndex | accessible-for-notify | current | The index of the table entry for which the trap is issued. |
| 1.3.6.1.4.1.29640.4.4.4 | ScalartrapThreshHoldType | accessible-for-notify | current | The threshold type for which the trap is made. |
| 1.3.6.1.4.1.29640.4.4.5 | ScalartrapThreshHold | accessible-for-notify | current | The threshold reference value. |
| 1.3.6.1.4.1.29640.4.4.6 | NotificationpduVoltageAlarm | current | Voltage alarm. | |
| 1.3.6.1.4.1.29640.4.4.7 | NotificationpduCurrentAlarm | current | Current alaram. | |
| 1.3.6.1.4.1.29640.4.4.8 | NotificationpduPowerAlarm | current | Power alarm. | |
| 1.3.6.1.4.1.29640.4.4.9 | NotificationsensorAlarm | current | Sensor Alarm: Temperature, Humidity or another type. The sensorType indicates the type of alarm. The sensorValue indicate the measured value. | |
| 1.3.6.1.4.1.29640.4.4.10 | NotificationpduSwitchAlarm | current | Not supported. | |
| 1.3.6.1.4.1.29640.5 | NodeapnlTest | |||
| 1.3.6.1.4.1.29640.6 | NodeapnlDemo | |||
| 1.3.6.1.4.1.29640.7 | NodeapnlMIBConformance |