MIB Viewer

ASCO-QEM-72EE2

723 objects
This MIB applies to SNMP Agent implemented in ASCO QEM 72EE2 devices.
Imported Objects
SNMPv2-CONFMODULE-COMPLIANCE NOTIFICATION-GROUP OBJECT-GROUP
SNMPv2-SMIenterprises Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-IDENTITY OBJECT-TYPE
SNMPv2-TCDisplayString
OIDNameAccessStatusDescription
1.3.6.1.4.1.7777IdentityascoThis MIB applies to SNMP Agent implemented in ASCO QEM 72EE2 devices.
1.3.6.1.4.1.7777.1Nodedevice
1.3.6.1.4.1.7777.1.1Nodetransferswitch
1.3.6.1.4.1.7777.1.1.1Scalarphase_shift_between_normal_and_emergencyread-onlycurrentPhase shift between normal & emergency
1.3.6.1.4.1.7777.1.1.2Scalarnormal_frequencyread-onlycurrentNormal frequency
1.3.6.1.4.1.7777.1.1.3Scalaremergency_frequencyread-onlycurrentEmergency frequency
1.3.6.1.4.1.7777.1.1.4Scalarmain_on_normalread-onlycurrentMain on normal
1.3.6.1.4.1.7777.1.1.5Scalarmain_on_emergencyread-onlycurrentMain on emergency
1.3.6.1.4.1.7777.1.1.6Scalarauxiliary_on_normalread-onlycurrentAuxiliary on normal
1.3.6.1.4.1.7777.1.1.7Scalarauxiliary_on_emergencyread-onlycurrentAuxiliary on emergency
1.3.6.1.4.1.7777.1.1.8Scalarnormal_source_availableread-onlycurrentNormal source available
1.3.6.1.4.1.7777.1.1.9Scalaremergency_source_availableread-onlycurrentEmergency source available
1.3.6.1.4.1.7777.1.1.10Scalarengine_exerciser_with_load_activeread-onlycurrentEngine exerciser with load active
1.3.6.1.4.1.7777.1.1.11Scalarexternal_f17_is_activeread-onlycurrentExternal F17 is active
1.3.6.1.4.1.7777.1.1.12Scalarnormal_voltage_phase_ABread-onlycurrentNormal voltage phase AB
1.3.6.1.4.1.7777.1.1.13Scalarnormal_voltage_phase_BCread-onlycurrentNormal voltage phase BC
1.3.6.1.4.1.7777.1.1.14Scalarnormal_voltage_phase_CAread-onlycurrentNormal voltage phase CA
1.3.6.1.4.1.7777.1.1.15Scalarnormal_voltage_unbalanceread-onlycurrentNormal voltage unbalance
1.3.6.1.4.1.7777.1.1.18Scalaremergency_voltage_phase_CAread-onlycurrentEmergency voltage phase CA
1.3.6.1.4.1.7777.1.1.19Scalarnominal_voltageread-onlycurrentNominal voltage
1.3.6.1.4.1.7777.1.1.20Scalarnominal_frequencyread-onlycurrentNominal frequency
1.3.6.1.4.1.7777.1.1.21Scalarnormal_source_3phase_sensingread-onlycurrentNormal source 3 phase sensing
1.3.6.1.4.1.7777.1.1.22Scalartransfer_switch_typeread-onlycurrentTransfer switch type (OTTS,DTTS)
1.3.6.1.4.1.7777.1.1.23Scalartransfer_switch_ampere_ratingread-onlycurrentTransfer switch ampere rating
1.3.6.1.4.1.7777.1.1.24Scalarcontroller_software_versionread-onlycurrentController software version
1.3.6.1.4.1.7777.1.1.25Scalarcontroller_software_dateread-onlycurrentController software date
1.3.6.1.4.1.7777.1.1.26Scalarexternal_parameter_lock_is_activeread-onlycurrentExternal parameter lock is active
1.3.6.1.4.1.7777.1.1.27Scalarengine_runningread-onlycurrentEngine running
1.3.6.1.4.1.7777.1.1.28Scalarcontroller_stateread-onlycurrentController state
1.3.6.1.4.1.7777.1.1.29Scalarcontroller_status_state_dataread-onlycurrentController status state data
1.3.6.1.4.1.7777.1.1.30Scalartimer_bypass_feature_6B_statusread-onlycurrentTimer bypass (Feature 6B) status
1.3.6.1.4.1.7777.1.1.31Scalarremote_transfer_feature_17_statusread-onlycurrentRemote transfer (Feature 17) status
1.3.6.1.4.1.7777.1.1.32Scalarload_shed_feature_30_statusread-onlycurrentLoad shed (Feature 30) status
1.3.6.1.4.1.7777.1.1.33Scalartransfer_inhibit_to_emergency_feature_34B_statusread-onlycurrentTransfer inhibit to emergency (Feature 34B) status
1.3.6.1.4.1.7777.1.1.34Scalarlocal_test_feature_5_statusread-onlycurrentLocal test (Feature 5) status
1.3.6.1.4.1.7777.1.1.35Scalarmanual_transfer_to_emergency_feature_6ZE_statusread-onlycurrentManual transfer to emergency (Feature 6ZE) status
1.3.6.1.4.1.7777.1.1.36Scalarcurrent_sensingread-onlycurrentCurrent sensing
1.3.6.1.4.1.7777.1.1.37Scalarphase_A_currentread-onlycurrentPhase A current (A). With 1 or 2 CT selected this is labeled as I1
1.3.6.1.4.1.7777.1.1.38Scalarphase_B_currentread-onlycurrentPhase B current (A)
1.3.6.1.4.1.7777.1.1.39Scalarphase_C_currentread-onlycurrentPhase C current (A). With 2 CT selected this is labeled as I2
1.3.6.1.4.1.7777.1.1.40Scalarfailure_to_accept_timerread-onlycurrentFailure to accept timer
1.3.6.1.4.1.7777.1.1.41Scalarnormal_to_emergency_pretransfer_time_delay_feature_31_bypass_enabledread-onlycurrentNormal to emergency pretransfer time delay (Feature 31) bypass enabled
1.3.6.1.4.1.7777.1.1.42Scalaremergency_to_normal_pretransfer_time_delay_feature_31_bypass_enabledread-onlycurrentEmergency to normal pretransfer time delay (Feature 31) bypass enabled
1.3.6.1.4.1.7777.1.1.43Scalarcommit_to_transfer_enabledread-onlycurrentCommit to transfer enabled
1.3.6.1.4.1.7777.1.1.44Scalarbypass_DTTS_source_failure_enabledread-onlycurrentBypass DTTS source failure enabled - data for DTTS and Group1 emulation is NOT enabled
1.3.6.1.4.1.7777.1.1.45Scalarinphase_transfer_enabledread-onlycurrentInphase transfer enabled - only for OTTS
1.3.6.1.4.1.7777.1.1.46Scalarinphase_monitor_for_load_shed_feature_30_enabledread-onlycurrentInphase monitor for load shed (Feature 30) enabled
1.3.6.1.4.1.7777.1.1.47Scalarfail_accept_timer_enabledread-onlycurrentFail accept timer enabled
1.3.6.1.4.1.7777.1.1.48Scalartransfer_retransfer_time_delay_bypass_feature_6B_input_enabledread-onlycurrentTransfer/retransfer time delay bypass (Feature 6B) input enabled
1.3.6.1.4.1.7777.1.1.49Scalarremote_transfer_feature_17_input_enabledread-onlycurrentRemote transfer (Feature 17) input enabled - data for transfer switch in auto mode only
1.3.6.1.4.1.7777.1.1.50Scalarretransfer_to_normal_mode_selector_feature_6DL_input_enabledread-onlycurrentRetransfer to normal mode selector (Feature 6DL) enabled
1.3.6.1.4.1.7777.1.1.51Scalarserial_remote_transfer_feature_17_enabledread-onlycurrentSerial remote transfer (Feature 17) enabled
1.3.6.1.4.1.7777.1.1.52Scalarvoltage_unbalance_enabledread-onlycurrentVoltage unbalance enabled
1.3.6.1.4.1.7777.1.1.53Scalarcurrent_sensing_module_presentread-onlycurrentCurrent sensing module present
1.3.6.1.4.1.7777.1.1.54Scalaralert_LED_activeread-onlycurrentAlert LED active
1.3.6.1.4.1.7777.1.1.55Scalarnot_in_auto_LED_activeread-onlycurrentNot in Auto LED active
1.3.6.1.4.1.7777.1.1.58Scalardaylight_savingsread-onlycurrentDaylight savings
1.3.6.1.4.1.7777.1.1.59Scalarloss_of_emergency_when_connected_to_emergency_alarm_enabledread-onlycurrentLoss of emergency when connected to emergency alarm enabled
1.3.6.1.4.1.7777.1.1.60Scalarexpiration_of_failure_to_accept_timer_alarm_enabledread-onlycurrentExpiration of failure to accept timer alarm enabled
1.3.6.1.4.1.7777.1.1.61Scalarload_disconnect_enabled_DTTS_onlyread-onlycurrentLoad disconnect enabled (DTTS only)
1.3.6.1.4.1.7777.1.1.62Scalarop1_is_feature_31read-onlycurrentOP1 is Feature 31
1.3.6.1.4.1.7777.1.1.63Scalarop1_is_common_alarmread-onlycurrentOP1 is common alarm
1.3.6.1.4.1.7777.1.1.64Scalarop1_is_NR2read-onlycurrentOP1 is NR2
1.3.6.1.4.1.7777.1.1.65Scalarop1_is_not_in_autoread-onlycurrentOP1 is not in auto
1.3.6.1.4.1.7777.1.1.66Scalarop2_is_feature_31read-onlycurrentOP2 is Feature 31
1.3.6.1.4.1.7777.1.1.67Scalarop2_is_common_alarmread-onlycurrentOP2 is common alarm
1.3.6.1.4.1.7777.1.1.68Scalarop2_is_NR2read-onlycurrentOP2 is NR2
1.3.6.1.4.1.7777.1.1.69Scalarop2_is_not_in_autoread-onlycurrentOP2 is not in auto
1.3.6.1.4.1.7777.1.1.70Scalarop2_1G_enabledread-onlycurrentOP2 1G enabled
1.3.6.1.4.1.7777.1.1.71Scalarop3_is_feature_31read-onlycurrentOP3 is Feature 31
1.3.6.1.4.1.7777.1.1.72Scalarop3_is_common_alarmread-onlycurrentOP3 is common alarm
1.3.6.1.4.1.7777.1.1.73Scalarop3_is_NR2read-onlycurrentOP2 is NR2
1.3.6.1.4.1.7777.1.1.74Scalarop3_is_not_in_autoread-onlycurrentOP3 is not in auto
1.3.6.1.4.1.7777.1.1.75Scalarcontroller_serial_numberread-onlycurrentController serial number
1.3.6.1.4.1.7777.1.1.76Scalarengine_exerciser_F11C_advanced_program_numberread-onlycurrentEngine exerciser (F11C) advanced program number
1.3.6.1.4.1.7777.1.1.77Scalarengine_exerciser_F11C_enabledread-onlycurrentEngine exerciser (F11C) enabled
1.3.6.1.4.1.7777.1.1.78Scalarengine_exerciser_F11C_test_with_load_transfer_enabledread-onlycurrentEngine exerciser (F11C) test with load transfer enabled
1.3.6.1.4.1.7777.1.1.79Scalarengine_exerciser_F11C_start_weekread-onlycurrentEngine exerciser (F11C) start week
1.3.6.1.4.1.7777.1.1.80Scalarengine_exerciser_F11C_day_of_weekread-onlycurrentEngine exerciser (F11C) day of week
1.3.6.1.4.1.7777.1.1.82Scalarengine_exerciser_F11C_start_time_hoursread-onlycurrentEngine exerciser (F11C) start time hours
1.3.6.1.4.1.7777.1.1.83Scalarengine_exerciser_F11C_start_time_minutesread-onlycurrentEngine exerciser (F11C) start time minutes
1.3.6.1.4.1.7777.1.1.84Scalarengine_exerciser_F11C_run_time_hoursread-onlycurrentEngine exerciser (F11C) run time hours
1.3.6.1.4.1.7777.1.1.85Scalarengine_exerciser_F11C_run_time_minutesread-onlycurrentEngine exerciser (F11C) schedule run time minutes
1.3.6.1.4.1.7777.1.1.86Scalarnormal_voltage_dropoutread-onlycurrentNormal voltage dropout
1.3.6.1.4.1.7777.1.1.87Scalarnormal_voltage_pickupread-onlycurrentNormal voltage pickup
1.3.6.1.4.1.7777.1.1.88Scalarnormal_over_voltage_tripread-onlycurrentNormal over voltage trip
1.3.6.1.4.1.7777.1.1.89Scalarnormal_frequency_dropoutread-onlycurrentNormal frequency dropout
1.3.6.1.4.1.7777.1.1.90Scalarnormal_frequency_pickupread-onlycurrentNormal frequency pickup
1.3.6.1.4.1.7777.1.1.91Scalarnormal_over_frequency_tripread-onlycurrentNormal over frequency trip
1.3.6.1.4.1.7777.1.1.92Scalaremergency_voltage_dropoutread-onlycurrentEmergency voltage dropout
1.3.6.1.4.1.7777.1.1.93Scalaremergency_voltage_pickupread-onlycurrentEmergency voltage pickup
1.3.6.1.4.1.7777.1.1.94Scalaremergency_over_voltage_tripread-onlycurrentEmergency over voltage trip
1.3.6.1.4.1.7777.1.1.95Scalaremergency_frequency_dropoutread-onlycurrentEmergency frequency dropout
1.3.6.1.4.1.7777.1.1.96Scalaremergency_frequency_pickupread-onlycurrentEmergency frequency pickup
1.3.6.1.4.1.7777.1.1.97Scalaremergency_over_frequency_tripread-onlycurrentEmergency over frequency trip
1.3.6.1.4.1.7777.1.1.98Scalartimer_1C_engine_start_time_delayread-onlycurrentTimer 1C engine start time delay
1.3.6.1.4.1.7777.1.1.99Scalartimer_1F_engine_fail_time_delayread-onlycurrentTimer 1F engine fail time delay
1.3.6.1.4.1.7777.1.1.100Scalartimer_2B_transfer_N_to_E_time_delayread-onlycurrentTimer 2B transfer N to E time delay
1.3.6.1.4.1.7777.1.1.101Scalartimer_2E_engine_cool_down_time_delayread-onlycurrentTimer 2E engine cool down time delay
1.3.6.1.4.1.7777.1.1.102Scalartimer_3AF_transfer_E_to_N_on_source_fail_time_delayread-onlycurrentTimer 3AF transfer E to N on source fail time delay
1.3.6.1.4.1.7777.1.1.103Scalartimer_3A_T_transfer_E_to_N_on_test_time_delayread-onlycurrentTimer 3A T transfer E to N on test time delay
1.3.6.1.4.1.7777.1.1.104Scalartimer_31F_N_to_E_pre_transfer_signal_time_delayread-onlycurrentTimer 31F N to E pre transfer signal time delay
1.3.6.1.4.1.7777.1.1.105Scalartimer_31M_N_to_E_post_transfer_signal_time_delayread-onlycurrentTimer 31M N to E post transfer signal time delay
1.3.6.1.4.1.7777.1.1.106Scalartimer_31G_E_to_N_pre_transfer_signal_time_delayread-onlycurrentTimer 31G E to N pre transfer signal time delay
1.3.6.1.4.1.7777.1.1.107Scalartimer_31N_E_to_N_post_transfer_signal_time_delayread-onlycurrentTimer 31N E to N post transfer signal time delay
1.3.6.1.4.1.7777.1.1.108Scalardtts_load_disconnect_time_delayread-onlycurrentDTTS load disconnect time delay
1.3.6.1.4.1.7777.1.1.109Scalarcommit_to_transfer_after_engine_startread-onlycurrentCommit to transfer after engine start
1.3.6.1.4.1.7777.1.1.110Scalarreal_time_hourread-onlycurrentReal time hour
1.3.6.1.4.1.7777.1.1.111Scalarreal_time_minuteread-onlycurrentReal time minute
1.3.6.1.4.1.7777.1.1.112Scalarreal_time_secondread-onlycurrentReal time second
1.3.6.1.4.1.7777.1.1.113Scalarcalendar_yearread-onlycurrentCalendar year
1.3.6.1.4.1.7777.1.1.114Scalarcalendar_monthread-onlycurrentCalendar month
1.3.6.1.4.1.7777.1.1.115Scalarcalendar_day_of_monthread-onlycurrentCalendar day of month
1.3.6.1.4.1.7777.1.1.116Scalarcalendar_day_of_weekread-onlycurrentCalendar day of week
1.3.6.1.4.1.7777.1.1.117Scalartotal_time_E_has_been_acceptable_high_wordread-onlycurrentTotal time E has been acceptable(high word)
1.3.6.1.4.1.7777.1.1.118Scalartotal_time_E_has_been_acceptable_low_wordread-onlycurrentTotal time E has been acceptable(low word)
1.3.6.1.4.1.7777.1.1.119Scalartotal_time_N_has_been_acceptable_high_wordread-onlycurrentTotal time N has been acceptable(high word)
1.3.6.1.4.1.7777.1.1.120Scalartotal_time_N_has_been_acceptable_low_wordread-onlycurrentTotal time N has been acceptable(low word)
1.3.6.1.4.1.7777.1.1.121Scalartotal_number_of_days_CP_has_been_energizedread-onlycurrentTotal number of days CP has been energized
1.3.6.1.4.1.7777.1.1.122Scalartotal_number_of_TS_transfersread-onlycurrentTotal number of TS transfers
1.3.6.1.4.1.7777.1.1.123Scalartotal_number_of_TS_transfers_due_to_source_failuresread-onlycurrentTotal number of TS transfers due to source failures
1.3.6.1.4.1.7777.1.1.124Scalarcontroller_locationread-onlycurrentController location
1.3.6.1.4.1.7777.1.1.125Scalarexternal_feature_5_enabledread-onlycurrentExternal Feature 5 enabled
1.3.6.1.4.1.7777.1.1.126Scalarexternal_feature_34_enabledread-onlycurrentExternal Feature 34 enabled
1.3.6.1.4.1.7777.1.1.127Scalarinphase_filter_enabledread-onlycurrentIn-phase filter enabled
1.3.6.1.4.1.7777.1.1.128Scalarcurrent_sensing_option_installedread-onlycurrentCurrent sensing option installed
1.3.6.1.4.1.7777.1.1.129Scalaradvanced_11C_option_installedread-onlycurrentAdvanced 11C option Installed
1.3.6.1.4.1.7777.1.1.130Scalarevent_log_option_installedread-onlycurrentEvent log option Installed
1.3.6.1.4.1.7777.1.1.131Scalarrs485_communication_option_installedread-onlycurrentRS485 communication option Installed
1.3.6.1.4.1.7777.1.1.132Scalarop1_common_alarm_option_installedread-onlycurrentOP1 common alarm option Installed
1.3.6.1.4.1.7777.1.1.133Scalartotal_time_load_connected_to_normal_high_wordread-onlycurrentTotal time load connected to normal (high word)
1.3.6.1.4.1.7777.1.1.134Scalartotal_time_load_connected_to_normal_low_wordread-onlycurrentTotal time load connected to normal (low word)
1.3.6.1.4.1.7777.1.1.135Scalartotal_time_load_connected_to_emergency_high_wordread-onlycurrentTotal time load connected to emergency (high word)
1.3.6.1.4.1.7777.1.1.136Scalartotal_time_load_connected_to_emergency_low_wordread-onlycurrentTotal time load connected to emergency (low word)
1.3.6.1.4.1.7777.1.1.137Scalarrs485_port_addressread-onlycurrentRS-485 port address
1.3.6.1.4.1.7777.1.1.138Scalarrs485_port_baud_rateread-onlycurrentRS-485 port baud rate
1.3.6.1.4.1.7777.1.1.139Scalarrs485_port_protocolread-onlycurrentRS-485 port protocol
1.3.6.1.4.1.7777.1.1.140Scalaremulate_group_1read-onlycurrentEmulate Group 1
1.3.6.1.4.1.7777.1.1.141Scalardtts_load_disconnect_recovery_mode_manual_or_autoread-onlycurrentDTTS load disconnect recovery mode - manual or auto
1.3.6.1.4.1.7777.1.1.142Scalartimer_2B_transfer_N_to_E_on_test_time_delayread-onlycurrentTimer 2B transfer N to E on test time delay
1.3.6.1.4.1.7777.1.1.143Scalarinphase_monitor_time_delayread-onlycurrentInphase monitor time delay
1.3.6.1.4.1.7777.1.1.144Scalarats_total_transfer_time_in_10th_secondsread-onlycurrentATS total transfer time in 10th seconds (real value in seconds requires division by 10)
1.3.6.1.4.1.7777.1.1.145Scalardongle_installedread-onlycurrentDongle installed
1.3.6.1.4.1.7777.1.1.146Scalarlanguage_selection_settingread-onlycurrentLanguage selection setting
1.3.6.1.4.1.7777.1.1.147Scalarlcd_contrast_settingread-onlycurrentLCD contrast setting
1.3.6.1.4.1.7777.1.1.148Scalarcontroller_nameread-onlycurrentController name
1.3.6.1.4.1.7777.1.1.149Scalarboot_loader_versionread-onlycurrentBoot loader version
1.3.6.1.4.1.7777.1.1.150Scalarvoltage_display_phase_label_selectionread-onlycurrentVoltage display phase label selection
1.3.6.1.4.1.7777.1.1.151Scalarsource_1_or_source_2_selection_for_different_english_formatread-onlycurrentSource 1 or source 2 selection for different English format
1.3.6.1.4.1.7777.1.1.152Scalarexternal_battery_enabledread-onlycurrentExternal battery enabled
1.3.6.1.4.1.7777.1.1.153Scalarts_data_gen_start_dateread-onlycurrentTS data gen start date
1.3.6.1.4.1.7777.1.1.154Scalarts_data_gen_start_monthread-onlycurrentTS data gen start month
1.3.6.1.4.1.7777.1.1.155Scalarts_data_gen_start_yearread-onlycurrentTS data gen start year
1.3.6.1.4.1.7777.1.1.156Scalarts_data_gen_start_hourread-onlycurrentTS data gen start hour
1.3.6.1.4.1.7777.1.1.157Scalarts_data_gen_start_minutesread-onlycurrentTS data gen start minutes
1.3.6.1.4.1.7777.1.1.158Scalarts_data_gen_start_secondsread-onlycurrentTS data gen start seconds
1.3.6.1.4.1.7777.1.1.159Scalarts_data_gen_start_10th_of_secondsread-onlycurrentTS data gen start 10th of seconds
1.3.6.1.4.1.7777.1.1.160Scalarts_data_gen_start_elapsed_time_in_secondsread-onlycurrentTS data gen start elapsed time in seconds
1.3.6.1.4.1.7777.1.1.161Scalartotal_active_alarm_numberread-onlycurrentTotal active alarm number
1.3.6.1.4.1.7777.1.1.162Scalarload_shed_directionread-onlycurrentLoad shed direction
1.3.6.1.4.1.7777.1.1.163Scalardtts_only_load_shed_on_source_failureread-onlycurrentDTTS only - load shed on source failure
1.3.6.1.4.1.7777.1.1.164Scalardtts_only_load_shed_on_request_f17read-onlycurrentDTTS only - load shed on request F17
1.3.6.1.4.1.7777.1.1.165Scalarnormal_voltage_unbalance_dropoutread-onlycurrentNormal voltage unbalance dropout. Parameter settings display for 3 phase only
1.3.6.1.4.1.7777.1.1.166Scalarnormal_voltage_unbalance_pickupread-onlycurrentNormal voltage unbalance pickup. Parameter settings display for 3 phase only
1.3.6.1.4.1.7777.1.1.167Scalaremergency_voltage_unbalance_dropoutread-onlycurrentEmergency voltage unbalance dropout. Parameter settings display for 3 phase only
1.3.6.1.4.1.7777.1.1.168Scalaremergency_voltage_unbalance_pickupread-onlycurrentEmergency voltage unbalance pickup. Parameter settings display for 3 phase only
1.3.6.1.4.1.7777.1.1.169Scalaremergency_voltage_phase_abread-onlycurrentEmergency voltage phase AB
1.3.6.1.4.1.7777.1.1.170Scalaremergency_voltage_phase_bcread-onlycurrentEmergency voltage phase BC
1.3.6.1.4.1.7777.1.1.171Scalaremergency_voltage_unbalanceread-onlycurrentEmergency voltage unbalance
1.3.6.1.4.1.7777.1.1.172Scalaremergency_source_3phase_sensingread-onlycurrentEmergency source 3 phase sensing
1.3.6.1.4.1.7777.1.1.173Scalartransfer_switch_bypass_or_notread-onlycurrentTransfer Switch Bypass Setting
1.3.6.1.4.1.7777.1.1.174Scalartransfer_switch_or_dual_breakerread-onlycurrentTransfer Switch or Dual Breaker Setting
1.3.6.1.4.1.7777.1.1.175Scalartransfer_switch_locked_outread-onlycurrentTransfer Switch Locked out
1.3.6.1.4.1.7777.1.1.176Scalarctts_extended_parallel_alarmread-onlycurrentCTTS Extended Parallel Alarm
1.3.6.1.4.1.7777.1.1.177Scalarctts_failure_to_synch_alarmread-onlycurrentCTTS Failure To Synch Alarm
1.3.6.1.4.1.7777.1.1.178Scalardtts_load_disconnectread-onlycurrentDTTS Load Disconnect
1.3.6.1.4.1.7777.1.1.179Scalarnormal_breaker_trippedread-onlycurrentNormal Breaker Tripped
1.3.6.1.4.1.7777.1.1.180Scalaremergency_breaker_trippedread-onlycurrentEmergency Breaker Tripped
1.3.6.1.4.1.7777.1.1.181Scalarfeature_6bread-onlycurrentFeature 6B Status
1.3.6.1.4.1.7777.1.1.182Scalarfeature_6cread-onlycurrentFeature 6C Status
1.3.6.1.4.1.7777.1.1.183Scalarfeature_17_serialread-onlycurrentFeature 17 Serial Status
1.3.6.1.4.1.7777.1.1.184Scalarfeature_29read-onlycurrentFeature 29 Status
1.3.6.1.4.1.7777.1.1.185Scalarfeature_34aread-onlycurrentFeature 34A Status
1.3.6.1.4.1.7777.1.1.186Scalarfeature_89read-onlycurrentFeature 89 Status
1.3.6.1.4.1.7777.1.1.187Scalarfeature_ct_bypassread-onlycurrentFeature CT Bypass Status
1.3.6.1.4.1.7777.1.1.188Scalarfeature_alarm_resetread-onlycurrentFeature Alarm Reset Status
1.3.6.1.4.1.7777.1.1.189Scalarfeature_6dread-onlycurrentFeature 6D Status
1.3.6.1.4.1.7777.1.1.190Scalarfeature_34tread-onlycurrentFeature 34T Status
1.3.6.1.4.1.7777.1.1.191Scalarcontrol_panel_eventlog_enabledread-onlycurrentControl Panel Event Log Enabled
1.3.6.1.4.1.7777.1.1.192Scalarpt_ratio_numeratorread-onlycurrentPT Ratio Numerator
1.3.6.1.4.1.7777.1.1.193Scalarpt_ratio_denominatorread-onlycurrentPT Ratio Denominator
1.3.6.1.4.1.7777.1.1.194Scalarcontrol_panel_nameread-onlycurrentControl Panel Name
1.3.6.1.4.1.7777.1.1.195Scalarnormal_voltage_unbalance_enabledread-onlycurrentNormal Voltage Unbalance Enabled
1.3.6.1.4.1.7777.1.1.196Scalaremergency_voltage_unbalance_enabledread-onlycurrentEmergency Voltage Unbalance Enabled
1.3.6.1.4.1.7777.1.1.197Scalarbypass_31F_and_31M_on_N_source_failureread-onlycurrentBypass 31F and 31M on N source failure
1.3.6.1.4.1.7777.1.1.198Scalarbypass_31G_and_31N_on_E_source_failureread-onlycurrentBypass 31G and 31N on E source failure
1.3.6.1.4.1.7777.1.1.199Scalarexternal_battery_presentread-onlycurrentExternal Battery Present
1.3.6.1.4.1.7777.1.1.200Scalarctts_in_synch_monitor_time_delayread-onlycurrentCTTS In Synch Monitor Time Delay
1.3.6.1.4.1.7777.1.1.201Scalarctts_fail_to_synch_time_delayread-onlycurrentCTTS Fail To Synch Time Delay
1.3.6.1.4.1.7777.1.1.202Scalarctts_extended_parallel_time_delayread-onlycurrentCTTS Extended Parallel Time Delay
1.3.6.1.4.1.7777.1.1.203Scalarshed_load_in_phaseread-onlycurrentShed Load In Phase
1.3.6.1.4.1.7777.1.1.204Scalarisolate_load_on_source_failureread-onlycurrentIsolate Load On Source Failure
1.3.6.1.4.1.7777.1.1.205Scalarisolate_load_on_F17read-onlycurrentIsolate Load On F17
1.3.6.1.4.1.7777.1.1.206Scalarfail_to_sync_auto_ct_bypassread-onlycurrentFail To Sync Auto CT Bypass
1.3.6.1.4.1.7777.1.1.207Scalartransfer_in_phase_on_ct_bypass_if_load_disconnectread-onlycurrentTransfer In phase On CT Bypass If load is disconnected
1.3.6.1.4.1.7777.1.1.208Scalarnetwork_configurationread-onlycurrentControl Panel Network configuration
1.3.6.1.4.1.7777.1.2NodedpmMeter1
1.3.6.1.4.1.7777.1.2.1ScalardpmMeter1DPMNameread-onlycurrentNormal DPM name.
1.3.6.1.4.1.7777.1.2.2ScalardpmMeter1DPMLocaread-onlycurrentNormal DPM Location.
1.3.6.1.4.1.7777.1.2.3ScalardpmMeter1NominalVoltageread-onlycurrentNormal Nominal Voltage.
1.3.6.1.4.1.7777.1.2.4ScalardpmMeter1NominalCurrentread-onlycurrentNormal Nominal Current.
1.3.6.1.4.1.7777.1.2.5ScalardpmMeter1InstantaneousDemandKwMWread-onlycurrentNormal Instantaneous Demand kW MW
1.3.6.1.4.1.7777.1.2.6ScalardpmMeter1InstantaneousDemandDateread-onlycurrentNormal Demand Date.
1.3.6.1.4.1.7777.1.2.7ScalardpmMeter1InstantaneousDemandTimeread-onlycurrentNormal Demand Time.
1.3.6.1.4.1.7777.1.2.8ScalardpmMeter1BlockDemandforFullHouInkWread-onlycurrentNormal Block Demand for Full Hou In kW.
1.3.6.1.4.1.7777.1.2.9ScalardpmMeter1BlockDemandforFullDayInkWread-onlycurrentNormal Block Demand for Full Day In kW.
1.3.6.1.4.1.7777.1.2.10ScalardpmMeter1BlockDemandforFullMonthInKWread-onlycurrentNormal Block Demand for Full Month In kW.
1.3.6.1.4.1.7777.1.2.11ScalardpmMeter1BlockDemandforFullYearread-onlycurrentNormal Block Demand for Full Year In kW.
1.3.6.1.4.1.7777.1.2.12ScalardpmMeter1CurrentThdAread-onlycurrentNormal Phase A THD Current.In percentage
1.3.6.1.4.1.7777.1.2.13ScalardpmMeter1CurrentThdBread-onlycurrentNormal Phase B THD Current.In percentage
1.3.6.1.4.1.7777.1.2.14ScalardpmMeter1CurrentThdCread-onlycurrentNormal Phase C THD Current.In percentage
1.3.6.1.4.1.7777.1.2.15ScalardpmMeter1VoltageThdAread-onlycurrentNormal Phase A THD Voltage.In percentage
1.3.6.1.4.1.7777.1.2.16ScalardpmMeter1VoltageThdBread-onlycurrentNormal Phase B THD Voltage.In percentage
1.3.6.1.4.1.7777.1.2.17ScalardpmMeter1VoltageThdCread-onlycurrentNormal Phase C THD Voltage.In percentage
1.3.6.1.4.1.7777.1.2.18ScalardpmMeter1Vabread-onlycurrentNormal Vab Voltage.
1.3.6.1.4.1.7777.1.2.19ScalardpmMeter1Vbcread-onlycurrentNormal Vbc Voltage.
1.3.6.1.4.1.7777.1.2.20ScalardpmMeter1Vcaread-onlycurrentNormal Vca Voltage.
1.3.6.1.4.1.7777.1.2.21ScalardpmMeter1VolAverageread-onlycurrentNormal Vol Average.
1.3.6.1.4.1.7777.1.2.22ScalardpmMeter1VolUnbalread-onlycurrentNormal Vol Unbal.
1.3.6.1.4.1.7777.1.2.23ScalardpmMeter1Vanread-onlycurrentNormal Vol Van.
1.3.6.1.4.1.7777.1.2.24ScalardpmMeter1Vbnread-onlycurrentNormal Vbn..
1.3.6.1.4.1.7777.1.2.25ScalardpmMeter1Vcnread-onlycurrentNormal Vcn.
1.3.6.1.4.1.7777.1.2.26ScalardpmMeter1Vavgneutralread-onlycurrentNormal Avg neutral Volatagae.
1.3.6.1.4.1.7777.1.2.27ScalardpmMeter1Frequencyread-onlycurrentNormal Frequency.
1.3.6.1.4.1.7777.1.2.28ScalardpmMeter1PowerFactorread-onlycurrentNormal Power factor.
1.3.6.1.4.1.7777.1.2.29ScalardpmMeter1CurPhaseAread-onlycurrentNormal Phase A Current.
1.3.6.1.4.1.7777.1.2.30ScalardpmMeter1CurPhaseBread-onlycurrentNormal Phase B Current.
1.3.6.1.4.1.7777.1.2.31ScalardpmMeter1CurPhaseCread-onlycurrentNormal Phase C Current.
1.3.6.1.4.1.7777.1.2.32ScalardpmMeter1PhaseCurAvgread-onlycurrentNormal Phase Current aVG.
1.3.6.1.4.1.7777.1.2.33ScalardpmMeter1PhaseCurUnbalancecePercentageread-onlycurrentNormal Phase Cur Unbalancece Percentage.
1.3.6.1.4.1.7777.1.2.34ScalardpmMeter1RealTotalPowerread-onlycurrentNormal Real Total power factor.
1.3.6.1.4.1.7777.1.2.35ScalardpmMeter1ReactiveTotalPowerread-onlycurrentNormal Reactive Total power.
1.3.6.1.4.1.7777.1.2.36ScalardpmMeter1ApparentTotalPowerread-onlycurrentNormal AApparent Total power.
1.3.6.1.4.1.7777.1.2.37ScalardpmMeter1NetActiveEnergyread-onlycurrentNormal Net Active Energy.
1.3.6.1.4.1.7777.1.2.38ScalardpmMeter1FirmwareVersionread-onlycurrentNormal DPM Firmware .
1.3.6.1.4.1.7777.1.2.39ScalardpmMeter1ActivePowerAread-onlycurrentNormal Active Power Phase A.
1.3.6.1.4.1.7777.1.2.40ScalardpmMeter1ActivePowerBread-onlycurrentNormal Active Power Phase B.
1.3.6.1.4.1.7777.1.2.41ScalardpmMeter1ActivePowerCread-onlycurrentNormal Active Power Phase C.
1.3.6.1.4.1.7777.1.2.42ScalardpmMeter1ActivePowerTotalread-onlycurrentNormal Active Power Total.
1.3.6.1.4.1.7777.1.2.43ScalardpmMeter1ReactivePowerAread-onlycurrentNormal Reactive Power Phase A.
1.3.6.1.4.1.7777.1.2.44ScalardpmMeter1ReactivePowerBread-onlycurrentNormal Reactive Power Phase B.
1.3.6.1.4.1.7777.1.2.45ScalardpmMeter1ReactivePowerCread-onlycurrentNormal Reactive Power Phase C.
1.3.6.1.4.1.7777.1.2.46ScalardpmMeter1ReactivePowerTotalread-onlycurrentNormal Reactive Power Total.
1.3.6.1.4.1.7777.1.2.47ScalardpmMeter1PowerFactorAread-onlycurrentNormal Power factor Phase A.
1.3.6.1.4.1.7777.1.2.48ScalardpmMeter1PowerFactorBread-onlycurrentNormal Power factor Phase B.
1.3.6.1.4.1.7777.1.2.49ScalardpmMeter1PowerFactorCread-onlycurrentNormal Power factor Phase C.
1.3.6.1.4.1.7777.1.2.50ScalardpmMeter1PowerFactorTotalread-onlycurrentNormal Power factor Total.
1.3.6.1.4.1.7777.1.2.51ScalardpmMeter1VoltAmperePowerAread-onlycurrentNormal Volt-Ampere Power Phase A.
1.3.6.1.4.1.7777.1.2.52ScalardpmMeter1VoltAmperePowerBread-onlycurrentNormal Volt-Ampere Power Phase B.
1.3.6.1.4.1.7777.1.2.53ScalardpmMeter1VoltAmperePowerCread-onlycurrentNormal Volt-Ampere Power Phase C.
1.3.6.1.4.1.7777.1.2.54ScalardpmMeter1VoltAmperePowerTotalread-onlycurrentNormal Volt-Ampere Power Total.
1.3.6.1.4.1.7777.1.2.55ScalardpmMeter1MaxWattDemandread-onlycurrentNormal Maximum Watt Demand.
1.3.6.1.4.1.7777.1.2.56ScalardpmMeter1NORMALKWHNetread-onlycurrentNormal NORMAL KWH Net.
1.3.6.1.4.1.7777.1.2.57ScalardpmMeter1NORMALKVARHNetread-onlycurrentNormal NORMAL KVARH Net.
1.3.6.1.4.1.7777.1.2.58ScalardpmMeter1NORMALKVAHNetread-onlycurrentNormal NORMAL KVAH Net.
1.3.6.1.4.1.7777.1.2.59ScalardpmMeter1EMERGKWHNetread-onlycurrentNormal EMERGENCY KWH Net.
1.3.6.1.4.1.7777.1.2.60ScalardpmMeter1EMERGKVARHNetread-onlycurrentNormal EMERGENCY KVARH Net.
1.3.6.1.4.1.7777.1.2.61ScalardpmMeter1EMERGKVAHNetread-onlycurrentNormal EMERGENCY KVAH Net.
1.3.6.1.4.1.7777.1.2.62ScalardpmMeter1NORMALMinTotalActivePowerread-onlycurrentNormal NORMAL Min. Total Active Power.
1.3.6.1.4.1.7777.1.2.63ScalardpmMeter1NORMALMaxTotalActivePowerread-onlycurrentNormal NORMAL Max. Total Active Power.
1.3.6.1.4.1.7777.1.2.64ScalardpmMeter1NORMALMinTotalReactivePowerread-onlycurrentNormal NORMAL Min. Total reactive Power.
1.3.6.1.4.1.7777.1.2.65ScalardpmMeter1NORMALMaxTotalReactivePowerread-onlycurrentNormal NORMAL Max. Total Reactive Power.
1.3.6.1.4.1.7777.1.2.66ScalardpmMeter1NORMALMinTotalApparentPowerread-onlycurrentNormal NORMAL Min. Total Apparent Power.
1.3.6.1.4.1.7777.1.2.67ScalardpmMeter1NORMALMaxTotalApparentPowerread-onlycurrentNormal NORMAL Max. Total Apparent Power.
1.3.6.1.4.1.7777.1.2.68ScalardpmMeter1EMERGMinTotalActivePowerread-onlycurrentNormal EMERGENCY Min. Total Active Power.
1.3.6.1.4.1.7777.1.2.69ScalardpmMeter1EMERGMaxTotalActivePowerread-onlycurrentNormal EMERGENCY Max. Total Active Power.
1.3.6.1.4.1.7777.1.2.70ScalardpmMeter1EMERGMinTotalReactivePowerread-onlycurrentNormal EMERGENCY Min. Total Reactive Power.
1.3.6.1.4.1.7777.1.2.71ScalardpmMeter1EMERGMaxTotalReactivePowerread-onlycurrentNormal EMERGENCY Max. Total Reactive Power.
1.3.6.1.4.1.7777.1.2.72ScalardpmMeter1EMERGMinTotalApparentPowerread-onlycurrentNormal EMERGENCY Min. Total Apparent Power.
1.3.6.1.4.1.7777.1.2.73ScalardpmMeter1EMERGMaxTotalApparentPowerread-onlycurrentNormal EMERGENCY Max. Total Apparent Power.
1.3.6.1.4.1.7777.1.2.74ScalardpmMeter1CurrentMonthMaxDemandread-onlycurrentNormal Current Month Maximum Demand.
1.3.6.1.4.1.7777.1.2.75ScalardpmMeter1MostRecentMonthMaxDemandread-writecurrentDescription.
1.3.6.1.4.1.7777.1.2.76ScalardpmMeter12ndRecentMonthMaxDemandread-onlycurrentNormal 2nd Recent Month Maximum Demand.
1.3.6.1.4.1.7777.1.2.77ScalardpmMeter13rdRecentMonthMaxDemandread-onlycurrentNormal 3rd Recent Month Maximum Demand.
1.3.6.1.4.1.7777.1.2.78ScalardpmMeter14thRecentMonthMaxDemandread-onlycurrentNormal 4th Recent Month Maximum Demand.
1.3.6.1.4.1.7777.1.2.79ScalardpmMeter15thRecentMonthMaxDemandread-onlycurrentNormal 5th Recent Month Maximum Demand.
1.3.6.1.4.1.7777.1.2.80ScalardpmMeter16thRecentMonthMaxDemandread-onlycurrentNormal 6th Recent Month Maximum Demand.
1.3.6.1.4.1.7777.1.2.81ScalardpmMeter17thRecentMonthMaxDemandread-onlycurrentNormal 7th Recent Month Maximum Demand.
1.3.6.1.4.1.7777.1.2.82ScalardpmMeter18thRecentMonthMaxDemandread-onlycurrentNormal 8th Recent Month Maximum Demand.
1.3.6.1.4.1.7777.1.2.83ScalardpmMeter19thRecentMonthMaxDemandread-onlycurrentNormal 9th Recent Month Maximum Demand.
1.3.6.1.4.1.7777.1.2.84ScalardpmMeter110thRecentMonthMaxDemandread-onlycurrentNormal 10th Recent Month Maximum Demand.
1.3.6.1.4.1.7777.1.2.85ScalardpmMeter111thRecentMonthMaxDemandread-onlycurrentNormal 11th Recent Month Maximum Demand.
1.3.6.1.4.1.7777.1.2.86ScalardpmMeter112thRecentMonthMaxDemandread-onlycurrentNormal 12th Recent Month Maximum Demand.
1.3.6.1.4.1.7777.1.2.87ScalardpmMeter113thRecentMonthMaxDemandread-onlycurrentNormal 13th Recent Month Maximum Demand..
1.3.6.1.4.1.7777.1.2.88ScalardpmMeter114thRecentMonthMaxDemandread-onlycurrentNormal 14th Recent Month Maximum Demand.
1.3.6.1.4.1.7777.1.2.89ScalardpmMeter115thRecentMonthMaxDemandread-onlycurrentNormal 15th Recent Month Maximum Demand.
1.3.6.1.4.1.7777.1.2.90ScalardpmMeter116thRecentMonthMaxDemandread-onlycurrentNormal 16th Recent Month Maximum Demand.
1.3.6.1.4.1.7777.1.2.91ScalardpmMeter117thRecentMonthMaxDemandread-onlycurrentNormal 17th Recent Month Maximum Demand.
1.3.6.1.4.1.7777.1.2.92ScalardpmMeter118thRecentMonthMaxDemandread-onlycurrentNormal 18th Recent Month Maximum Demand.
1.3.6.1.4.1.7777.1.2.93ScalardpmMeter119thRecentMonthMaxDemandread-onlycurrentNormal 19th Recent Month Maximum Demand.
1.3.6.1.4.1.7777.1.2.94ScalardpmMeter120thRecentMonthMaxDemandread-onlycurrentNormal 20th Recent Month Maximum Demand.
1.3.6.1.4.1.7777.1.2.95ScalardpmMeter121stRecentMonthMaxDemandread-onlycurrentNormal 21st Recent Month Maximum Demand.
1.3.6.1.4.1.7777.1.2.96ScalardpmMeter122ndRecentMonthMaxDemandread-onlycurrentNormal 22nd Recent Month Maximum Demand.
1.3.6.1.4.1.7777.1.2.97ScalardpmMeter123rdRecentMonthMaxDemandread-onlycurrentNormal 23rd Recent Month Maximum Demand.
1.3.6.1.4.1.7777.1.2.98ScalardpmMeter124thRecentMonthMaxDemandread-onlycurrentNormal 24th Recent Month Maximum Demand.
1.3.6.1.4.1.7777.1.2.99ScalardpmMeter1MainAndAuxilliaryPositionsread-onlycurrentNormal Main & Auxiliary Switch positions.
1.3.6.1.4.1.7777.1.2.100ScalardpmMeter1ResettableEngineRunCounterread-onlycurrentNormal Resettable Engine Counter.
1.3.6.1.4.1.7777.1.2.101ScalardpmMeter1CumulativeEngineRunCounterread-onlycurrentNormal Cumulative Engine Run Counter.
1.3.6.1.4.1.7777.1.3NodedpmMeter2
1.3.6.1.4.1.7777.1.3.1ScalardpmMeter2DPMNameread-onlycurrentEmergency DPM name.
1.3.6.1.4.1.7777.1.3.2ScalardpmMeter2DPMLocaread-onlycurrentEmergency DPM Location.
1.3.6.1.4.1.7777.1.3.3ScalardpmMeter2NominalVoltageread-onlycurrentEmergency Nominal Voltage.
1.3.6.1.4.1.7777.1.3.4ScalardpmMeter2NominalCurrentread-onlycurrentEmergency Nominal Current.
1.3.6.1.4.1.7777.1.3.5ScalardpmMeter2InstantaneousDemandKwMWread-onlycurrentEmergency Instantaneous Demand kW MW
1.3.6.1.4.1.7777.1.3.6ScalardpmMeter2InstantaneousDemandDateread-onlycurrentEmergency Demand Date.
1.3.6.1.4.1.7777.1.3.7ScalardpmMeter2InstantaneousDemandTimeread-onlycurrentEmergency Demand Time.
1.3.6.1.4.1.7777.1.3.8ScalardpmMeter2BlockDemandforFullHouInkWread-onlycurrentEmergency Block Demand for Full Hou In kW.
1.3.6.1.4.1.7777.1.3.9ScalardpmMeter2BlockDemandforFullDayInkWread-onlycurrentEmergency Block Demand for Full Day In kW.
1.3.6.1.4.1.7777.1.3.10ScalardpmMeter2BlockDemandforFullMonthInKWread-onlycurrentEmergency Block Demand for Full Month In kW.
1.3.6.1.4.1.7777.1.3.11ScalardpmMeter2BlockDemandforFullYearread-onlycurrentEmergency Block Demand for Full Year In kW.
1.3.6.1.4.1.7777.1.3.12ScalardpmMeter2CurrentThdAread-onlycurrentEmergency Phase A THD Current.In percentage
1.3.6.1.4.1.7777.1.3.13ScalardpmMeter2CurrentThdBread-onlycurrentEmergency Phase B THD Current.In percentage
1.3.6.1.4.1.7777.1.3.14ScalardpmMeter2CurrentThdCread-onlycurrentEmergency Phase C THD Current.In percentage
1.3.6.1.4.1.7777.1.3.15ScalardpmMeter2VoltageThdAread-onlycurrentEmergency Phase A THD Voltage.In percentage
1.3.6.1.4.1.7777.1.3.16ScalardpmMeter2VoltageThdBread-onlycurrentEmergency Phase B THD Voltage.In percentage
1.3.6.1.4.1.7777.1.3.17ScalardpmMeter2VoltageThdCread-onlycurrentEmergency Phase C THD Voltage.In percentage
1.3.6.1.4.1.7777.1.3.18ScalardpmMeter2Vabread-onlycurrentEmergency Vab Voltage.
1.3.6.1.4.1.7777.1.3.19ScalardpmMeter2Vbcread-onlycurrentEmergency Vbc Voltage.
1.3.6.1.4.1.7777.1.3.20ScalardpmMeter2Vcaread-onlycurrentEmergency Vca Voltage.
1.3.6.1.4.1.7777.1.3.21ScalardpmMeter2VolAverageread-onlycurrentEmergency Vol Average.
1.3.6.1.4.1.7777.1.3.22ScalardpmMeter2VolUnbalread-onlycurrentEmergency Vol Unbal.
1.3.6.1.4.1.7777.1.3.23ScalardpmMeter2Vanread-onlycurrentEmergency Vol Van.
1.3.6.1.4.1.7777.1.3.24ScalardpmMeter2Vbnread-onlycurrentEmergency Vbn..
1.3.6.1.4.1.7777.1.3.25ScalardpmMeter2Vcnread-onlycurrentEmergency Vcn.
1.3.6.1.4.1.7777.1.3.26ScalardpmMeter2Vavgneutralread-onlycurrentEmergency Avg neutral Volatagae.
1.3.6.1.4.1.7777.1.3.27ScalardpmMeter2Frequencyread-onlycurrentEmergency Frequency.
1.3.6.1.4.1.7777.1.3.28ScalardpmMeter2PowerFactorread-onlycurrentEmergency Power factor.
1.3.6.1.4.1.7777.1.3.29ScalardpmMeter2CurPhaseAread-onlycurrentEmergency Phase A Current.
1.3.6.1.4.1.7777.1.3.30ScalardpmMeter2CurPhaseBread-onlycurrentEmergency Phase B Current.
1.3.6.1.4.1.7777.1.3.31ScalardpmMeter2CurPhaseCread-onlycurrentEmergency Phase C Current.
1.3.6.1.4.1.7777.1.3.32ScalardpmMeter2PhaseCurAvgread-onlycurrentEmergency Phase Current aVG.
1.3.6.1.4.1.7777.1.3.33ScalardpmMeter2PhaseCurUnbalancecePercentageread-onlycurrentEmergency Phase Cur Unbalancece Percentage.
1.3.6.1.4.1.7777.1.3.34ScalardpmMeter2RealTotalPowerread-onlycurrentEmergency Real Total power factor.
1.3.6.1.4.1.7777.1.3.35ScalardpmMeter2ReactiveTotalPowerread-onlycurrentEmergency Reactive Total power.
1.3.6.1.4.1.7777.1.3.36ScalardpmMeter2ApparentTotalPowerread-onlycurrentEmergency Apparent Total power.
1.3.6.1.4.1.7777.1.3.37ScalardpmMeter2NetActiveEnergyread-onlycurrentEmergency Net Active Energy.
1.3.6.1.4.1.7777.1.3.38ScalardpmMeter2FirmwareVersionread-onlycurrentEmergency DPM Firmware .
1.3.6.1.4.1.7777.1.3.39ScalardpmMeter2ActivePowerAread-onlycurrentEmergency Active Power phase A.
1.3.6.1.4.1.7777.1.3.40ScalardpmMeter2ActivePowerBread-onlycurrentEmergency Active Power phase B.
1.3.6.1.4.1.7777.1.3.41ScalardpmMeter2ActivePowerCread-onlycurrentEmergency Active Power phase C.
1.3.6.1.4.1.7777.1.3.42ScalardpmMeter2ActivePowerTotalread-onlycurrentEmergency Active Power total.
1.3.6.1.4.1.7777.1.3.43ScalardpmMeter2ReactivePowerAread-onlycurrentEmergency Reactive Power phase A.
1.3.6.1.4.1.7777.1.3.44ScalardpmMeter2ReactivePowerBread-onlycurrentEmergency Reactive Power phase B.
1.3.6.1.4.1.7777.1.3.45ScalardpmMeter2ReactivePowerCread-onlycurrentEmergency Reactive Power phase C.
1.3.6.1.4.1.7777.1.3.46ScalardpmMeter2ReactivePowerTotalread-onlycurrentEmergency Reactive Power Total.
1.3.6.1.4.1.7777.1.3.47ScalardpmMeter2PowerFactorAread-onlycurrentEmergency Power Factor phase A.
1.3.6.1.4.1.7777.1.3.48ScalardpmMeter2PowerFactorBread-onlycurrentEmergency Power Factor phase B.
1.3.6.1.4.1.7777.1.3.49ScalardpmMeter2PowerFactorCread-onlycurrentEmergency Power Factor phase C.
1.3.6.1.4.1.7777.1.3.50ScalardpmMeter2PowerFactorTotalread-onlycurrentEmergency Power Factor Total.
1.3.6.1.4.1.7777.1.3.51ScalardpmMeter2VoltAmperePowerAread-onlycurrentEmergency volt-ampere Power phase A.
1.3.6.1.4.1.7777.1.3.52ScalardpmMeter2VoltAmperePowerBread-onlycurrentEmergency volt-ampere Power phase B.
1.3.6.1.4.1.7777.1.3.53ScalardpmMeter2VoltAmperePowerCread-onlycurrentEmergency volt-ampere Power phase C.
1.3.6.1.4.1.7777.1.3.54ScalardpmMeter2VoltAmperePowerTotalread-onlycurrentEmergency volt-ampere Power Total.
1.3.6.1.4.1.7777.1.3.55ScalardpmMeter2MaxWattDemandread-onlycurrentEmergency Maximum Watt Demand.
1.3.6.1.4.1.7777.1.3.56ScalardpmMeter2NORMALKWHNetread-onlycurrentEmergency NORMAL kWH Net.
1.3.6.1.4.1.7777.1.3.57ScalardpmMeter2NORMALKVARHNetread-onlycurrentEmergency NORMAL kVarH Net.
1.3.6.1.4.1.7777.1.3.58ScalardpmMeter2NORMALKVAHNetread-onlycurrentEmergency NORMAL kVAH Net.
1.3.6.1.4.1.7777.1.3.59ScalardpmMeter2EMERGKWHNetread-onlycurrentEmergency EMERGENCY kWH Net.
1.3.6.1.4.1.7777.1.3.60ScalardpmMeter2EMERGKVARHNetread-onlycurrentEmergency EMERGENCY kVarH Net.
1.3.6.1.4.1.7777.1.3.61ScalardpmMeter2EMERGKVAHNetread-onlycurrentEmergency EMERGENCY kVAH Net.
1.3.6.1.4.1.7777.1.3.62ScalardpmMeter2NORMALMinTotalActivePowerread-onlycurrentEmergency NORMAL Minimum Total Active Power.
1.3.6.1.4.1.7777.1.3.63ScalardpmMeter2NORMALMaxTotalActivePowerread-onlycurrentEmergency NORMAL Maximum Total Active Power.
1.3.6.1.4.1.7777.1.3.64ScalardpmMeter2NORMALMinTotalReactivePowerread-onlycurrentEmergency NORMAL Minimum Total Reactive Power.
1.3.6.1.4.1.7777.1.3.65ScalardpmMeter2NORMALMaxTotalReactivePowerread-onlycurrentEmergency NORMAL Maximum Total Reactive Power.
1.3.6.1.4.1.7777.1.3.66ScalardpmMeter2NORMALMinTotalApparentPowerread-onlycurrentEmergency NORMAL Minimum Total Apparent Power.
1.3.6.1.4.1.7777.1.3.67ScalardpmMeter2NORMALMaxTotalApparentPowerread-onlycurrentEmergency NORMAL Maximum Total Apparent Power.
1.3.6.1.4.1.7777.1.3.68ScalardpmMeter2EMERGMinTotalActivePowerread-onlycurrentEmergency EMERGENCY Minimum Total Active Power.
1.3.6.1.4.1.7777.1.3.69ScalardpmMeter2EMERGMaxTotalActivePowerread-onlycurrentEmergency EMERGENCY Maximum Total Active Power.
1.3.6.1.4.1.7777.1.3.70ScalardpmMeter2EMERGMinTotalReactivePowerread-onlycurrentEmergency EMERGENCY Minimum Total Reactive Power.
1.3.6.1.4.1.7777.1.3.71ScalardpmMeter2EMERGMaxTotalReactivePowerread-onlycurrentEmergency EMERGENCY Maximum Total Reactive Power.
1.3.6.1.4.1.7777.1.3.72ScalardpmMeter2EMERGMinTotalApparentPowerread-onlycurrentEmergency EMERGENCY Minimum Total Apparent Power.
1.3.6.1.4.1.7777.1.3.73ScalardpmMeter2EMERGMaxTotalApparentPowerread-onlycurrentEmergency EMERGENCY Maximum Total Apparent Power.
1.3.6.1.4.1.7777.1.3.74ScalardpmMeter2CurrentMonthMaxDemandread-onlycurrentEmergency Current Month Maximum Demand.
1.3.6.1.4.1.7777.1.3.75ScalardpmMeter2MostRecentMonthMaxDemandread-writecurrentEmergency Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.3.76ScalardpmMeter22ndRecentMonthMaxDemandread-onlycurrentEmergency 2nd Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.3.77ScalardpmMeter23rdRecentMonthMaxDemandread-onlycurrentEmergency 3rd Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.3.78ScalardpmMeter24thRecentMonthMaxDemandread-onlycurrentEmergency 4th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.3.79ScalardpmMeter25thRecentMonthMaxDemandread-onlycurrentEmergency 5th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.3.80ScalardpmMeter26thRecentMonthMaxDemandread-onlycurrentEmergency 6th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.3.81ScalardpmMeter27thRecentMonthMaxDemandread-onlycurrentEmergency 7th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.3.82ScalardpmMeter28thRecentMonthMaxDemandread-onlycurrentEmergency 8th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.3.83ScalardpmMeter29thRecentMonthMaxDemandread-onlycurrentEmergency 9th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.3.84ScalardpmMeter210thRecentMonthMaxDemandread-onlycurrentEmergency 10th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.3.85ScalardpmMeter211thRecentMonthMaxDemandread-onlycurrentEmergency 11th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.3.86ScalardpmMeter212thRecentMonthMaxDemandread-onlycurrentEmergency 12th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.3.87ScalardpmMeter213thRecentMonthMaxDemandread-onlycurrentEmergency 13th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.3.88ScalardpmMeter214thRecentMonthMaxDemandread-onlycurrentEmergency 14th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.3.89ScalardpmMeter215thRecentMonthMaxDemandread-onlycurrentEmergency 15th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.3.90ScalardpmMeter216thRecentMonthMaxDemandread-onlycurrentEmergency 16th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.3.91ScalardpmMeter217thRecentMonthMaxDemandread-onlycurrentEmergency 17th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.3.92ScalardpmMeter218thRecentMonthMaxDemandread-onlycurrentEmergency 18th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.3.93ScalardpmMeter219thRecentMonthMaxDemandread-onlycurrentEmergency 19th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.3.94ScalardpmMeter220thRecentMonthMaxDemandread-onlycurrentEmergency 20th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.3.95ScalardpmMeter221stRecentMonthMaxDemandread-onlycurrentEmergency 21st Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.3.96ScalardpmMeter222ndRecentMonthMaxDemandread-onlycurrentEmergency 22nd Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.3.97ScalardpmMeter223rdRecentMonthMaxDemandread-onlycurrentEmergency 23rd Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.3.98ScalardpmMeter224thRecentMonthMaxDemandread-onlycurrentEmergency 24th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.3.99ScalardpmMeter2MainAndAuxilliaryPositionsread-onlycurrentEmergency Main & Auxiliary Switch positions.
1.3.6.1.4.1.7777.1.3.100ScalardpmMeter2ResettableEngineRunCounterread-onlycurrentEmergency Resettable Engine Runtime counter in Hours.
1.3.6.1.4.1.7777.1.3.101ScalardpmMeter2CumulativeEngineRunCounterread-onlycurrentEmergency Cumulative Engine Runtime counter in Hours.
1.3.6.1.4.1.7777.1.4NodedpmMeter3
1.3.6.1.4.1.7777.1.4.1ScalardpmMeter3DPMNameread-onlycurrentLoad DPM name.
1.3.6.1.4.1.7777.1.4.2ScalardpmMeter3DPMLocaread-onlycurrentLoad DPM Location.
1.3.6.1.4.1.7777.1.4.3ScalardpmMeter3NominalVoltageread-onlycurrentLoad Nominal Voltage.
1.3.6.1.4.1.7777.1.4.4ScalardpmMeter3NominalCurrentread-onlycurrentLoad Nominal Current.
1.3.6.1.4.1.7777.1.4.5ScalardpmMeter3InstantaneousDemandKwMWread-onlycurrentLoad Instantaneous Demand kW MW
1.3.6.1.4.1.7777.1.4.6ScalardpmMeter3InstantaneousDemandDateread-onlycurrentLoad Demand Date.
1.3.6.1.4.1.7777.1.4.7ScalardpmMeter3InstantaneousDemandTimeread-onlycurrentLoad Demand Time.
1.3.6.1.4.1.7777.1.4.8ScalardpmMeter3BlockDemandforFullHouInkWread-onlycurrentLoad Block Demand for Full Hou In kW.
1.3.6.1.4.1.7777.1.4.9ScalardpmMeter3BlockDemandforFullDayInkWread-onlycurrentLoad Block Demand for Full Day In kW.
1.3.6.1.4.1.7777.1.4.10ScalardpmMeter3BlockDemandforFullMonthInKWread-onlycurrentLoad Block Demand for Full Month In kW.
1.3.6.1.4.1.7777.1.4.11ScalardpmMeter3BlockDemandforFullYearread-onlycurrentLoad Block Demand for Full Year In kW.
1.3.6.1.4.1.7777.1.4.12ScalardpmMeter3CurrentThdAread-onlycurrentLoad Phase A THD Current.In percentage
1.3.6.1.4.1.7777.1.4.13ScalardpmMeter3CurrentThdBread-onlycurrentLoad Phase B THD Current.In percentage
1.3.6.1.4.1.7777.1.4.14ScalardpmMeter3CurrentThdCread-onlycurrentLoad Phase C THD Current.In percentage
1.3.6.1.4.1.7777.1.4.15ScalardpmMeter3VoltageThdAread-onlycurrentLoad Phase A THD Voltage.In percentage
1.3.6.1.4.1.7777.1.4.16ScalardpmMeter3VoltageThdBread-onlycurrentLoad Phase B THD Voltage.In percentage
1.3.6.1.4.1.7777.1.4.17ScalardpmMeter3VoltageThdCread-onlycurrentLoad Phase C THD Voltage.In percentage
1.3.6.1.4.1.7777.1.4.18ScalardpmMeter3Vabread-onlycurrentLoad Vab Volatage.
1.3.6.1.4.1.7777.1.4.19ScalardpmMeter3Vbcread-onlycurrentLoad Vbc Volatage.
1.3.6.1.4.1.7777.1.4.20ScalardpmMeter3Vcaread-onlycurrentLoad Vca Volatage.
1.3.6.1.4.1.7777.1.4.21ScalardpmMeter3VolAverageread-onlycurrentLoad Vol Average.
1.3.6.1.4.1.7777.1.4.22ScalardpmMeter3VolUnbalread-onlycurrentLoad Vol Unbal.
1.3.6.1.4.1.7777.1.4.23ScalardpmMeter3Vanread-onlycurrentLoad Vol Van.
1.3.6.1.4.1.7777.1.4.24ScalardpmMeter3Vbnread-onlycurrentLoad Vbn..
1.3.6.1.4.1.7777.1.4.25ScalardpmMeter3Vcnread-onlycurrentLoad Vcn.
1.3.6.1.4.1.7777.1.4.26ScalardpmMeter3Vavgneutralread-onlycurrentLoad Avg neutral Volatagae.
1.3.6.1.4.1.7777.1.4.27ScalardpmMeter3Frequencyread-onlycurrentLoad Frequency.
1.3.6.1.4.1.7777.1.4.28ScalardpmMeter3PowerFactorread-onlycurrentLoad Power factor.
1.3.6.1.4.1.7777.1.4.29ScalardpmMeter3CurPhaseAread-onlycurrentLoad Phase A Current.
1.3.6.1.4.1.7777.1.4.30ScalardpmMeter3CurPhaseBread-onlycurrentLoad Phase B Current.
1.3.6.1.4.1.7777.1.4.31ScalardpmMeter3CurPhaseCread-onlycurrentLoad Phase C Current.
1.3.6.1.4.1.7777.1.4.32ScalardpmMeter3PhaseCurAvgread-onlycurrentLoad Phase Current aVG.
1.3.6.1.4.1.7777.1.4.33ScalardpmMeter3PhaseCurUnbalancecePercentageread-onlycurrentLoad Phase Cur Unbalancece Percentage.
1.3.6.1.4.1.7777.1.4.34ScalardpmMeter3RealTotalPowerread-onlycurrentLoad Real Total power factor.
1.3.6.1.4.1.7777.1.4.35ScalardpmMeter3ReactiveTotalPowerread-onlycurrentLoad Reactive Total power.
1.3.6.1.4.1.7777.1.4.36ScalardpmMeter3ApparentTotalPowerread-onlycurrentLoad Apparent Total power.
1.3.6.1.4.1.7777.1.4.37ScalardpmMeter3NetActiveEnergyread-onlycurrentLoad Net Active Energy.
1.3.6.1.4.1.7777.1.4.38ScalardpmMeter3FirmwareVersionread-onlycurrentLoad DPM Firmware .
1.3.6.1.4.1.7777.1.4.39ScalardpmMeter3ActivePowerAread-onlycurrentLoad Active Power phase A.
1.3.6.1.4.1.7777.1.4.40ScalardpmMeter3ActivePowerBread-onlycurrentLoad Active Power phase B.
1.3.6.1.4.1.7777.1.4.41ScalardpmMeter3ActivePowerCread-onlycurrentLoad Active Power phase C.
1.3.6.1.4.1.7777.1.4.42ScalardpmMeter3ActivePowerTotalread-onlycurrentLoad Active Power Total.
1.3.6.1.4.1.7777.1.4.43ScalardpmMeter3ReactivePowerAread-onlycurrentLoad Reactive Power phase A.
1.3.6.1.4.1.7777.1.4.44ScalardpmMeter3ReactivePowerBread-onlycurrentLoad Reactive Power phase B.
1.3.6.1.4.1.7777.1.4.45ScalardpmMeter3ReactivePowerCread-onlycurrentLoad Reactive Power phase C.
1.3.6.1.4.1.7777.1.4.46ScalardpmMeter3ReactivePowerTotalread-onlycurrentLoad Reactive Power Total.
1.3.6.1.4.1.7777.1.4.47ScalardpmMeter3PowerFactorAread-onlycurrentLoad Reactive Power phase A.
1.3.6.1.4.1.7777.1.4.48ScalardpmMeter3PowerFactorBread-onlycurrentLoad Reactive Power phase B.
1.3.6.1.4.1.7777.1.4.49ScalardpmMeter3PowerFactorCread-onlycurrentLoad Reactive Power phase B.
1.3.6.1.4.1.7777.1.4.50ScalardpmMeter3PowerFactorTotalread-onlycurrentLoad Reactive Power Total.
1.3.6.1.4.1.7777.1.4.51ScalardpmMeter3VoltAmperePowerAread-onlycurrentLoad volt-ampere Power phase A.
1.3.6.1.4.1.7777.1.4.52ScalardpmMeter3VoltAmperePowerBread-onlycurrentLoad volt-ampere Power phase B.
1.3.6.1.4.1.7777.1.4.53ScalardpmMeter3VoltAmperePowerCread-onlycurrentLoad volt-ampere Power phase C.
1.3.6.1.4.1.7777.1.4.54ScalardpmMeter3VoltAmperePowerTotalread-onlycurrentLoad volt-ampere Power Total.
1.3.6.1.4.1.7777.1.4.55ScalardpmMeter3MaxWattDemandread-onlycurrentLoad Maximum Watt Demand.
1.3.6.1.4.1.7777.1.4.56ScalardpmMeter3NORMALKWHNetread-onlycurrentLoad NORMAL kWH Net.
1.3.6.1.4.1.7777.1.4.57ScalardpmMeter3NORMALKVARHNetread-onlycurrentLoad NORMAL kVarH Net.
1.3.6.1.4.1.7777.1.4.58ScalardpmMeter3NORMALKVAHNetread-onlycurrentLoad NORMAL kVaH Net.
1.3.6.1.4.1.7777.1.4.59ScalardpmMeter3EMERGKWHNetread-onlycurrentLoad EMERGENCY kWH Net.
1.3.6.1.4.1.7777.1.4.60ScalardpmMeter3EMERGKVARHNetread-onlycurrentLoad EMERGENCY kVarH Net.
1.3.6.1.4.1.7777.1.4.61ScalardpmMeter3EMERGKVAHNetread-onlycurrentLoad EMERGENCY kVaH Net.
1.3.6.1.4.1.7777.1.4.62ScalardpmMeter3NORMALMinTotalActivePowerread-onlycurrentLoad NORMAL Minimum Total Active Power.
1.3.6.1.4.1.7777.1.4.63ScalardpmMeter3NORMALMaxTotalActivePowerread-onlycurrentLoad NORMAL Maximum Total Active Power.
1.3.6.1.4.1.7777.1.4.64ScalardpmMeter3NORMALMinTotalReactivePowerread-onlycurrentLoad NORMAL Minimum Total Reactive Power.
1.3.6.1.4.1.7777.1.4.65ScalardpmMeter3NORMALMaxTotalReactivePowerread-onlycurrentLoad NORMAL Maximum Total Reactive Power.
1.3.6.1.4.1.7777.1.4.66ScalardpmMeter3NORMALMinTotalApparentPowerread-onlycurrentLoad NORMAL Minimum Total Apparent Power.
1.3.6.1.4.1.7777.1.4.67ScalardpmMeter3NORMALMaxTotalApparentPowerread-onlycurrentLoad NORMAL Maximum Total Apparent Power.
1.3.6.1.4.1.7777.1.4.68ScalardpmMeter3EMERGMinTotalActivePowerread-onlycurrentLoad EMERGENCY Minimum Total Active Power.
1.3.6.1.4.1.7777.1.4.69ScalardpmMeter3EMERGMaxTotalActivePowerread-onlycurrentLoad EMERGENCY Maximum Total Active Power.
1.3.6.1.4.1.7777.1.4.70ScalardpmMeter3EMERGMinTotalReactivePowerread-onlycurrentLoad EMERGENCY Minimum Total Reactive Power.
1.3.6.1.4.1.7777.1.4.71ScalardpmMeter3EMERGMaxTotalReactivePowerread-onlycurrentLoad EMERGENCY Maximum Total Reactive Power.
1.3.6.1.4.1.7777.1.4.72ScalardpmMeter3EMERGMinTotalApparentPowerread-onlycurrentLoad EMERGENCY Minimum Total Apparent Power.
1.3.6.1.4.1.7777.1.4.73ScalardpmMeter3EMERGMaxTotalApparentPowerread-onlycurrentLoad EMERGENCY Maximum Total Apparent Power.
1.3.6.1.4.1.7777.1.4.74ScalardpmMeter3CurrentMonthMaxDemandread-onlycurrentLoad Current Month Maximum Demand.
1.3.6.1.4.1.7777.1.4.75ScalardpmMeter3MostRecentMonthMaxDemandread-writecurrentLoad Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.4.76ScalardpmMeter32ndRecentMonthMaxDemandread-onlycurrentLoad 2nd Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.4.77ScalardpmMeter33rdRecentMonthMaxDemandread-onlycurrentLoad 3rd Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.4.78ScalardpmMeter34thRecentMonthMaxDemandread-onlycurrentLoad 4th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.4.79ScalardpmMeter35thRecentMonthMaxDemandread-onlycurrentLoad 5th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.4.80ScalardpmMeter36thRecentMonthMaxDemandread-onlycurrentLoad 6th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.4.81ScalardpmMeter37thRecentMonthMaxDemandread-onlycurrentLoad 7th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.4.82ScalardpmMeter38thRecentMonthMaxDemandread-onlycurrentLoad 8th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.4.83ScalardpmMeter39thRecentMonthMaxDemandread-onlycurrentLoad 9th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.4.84ScalardpmMeter310thRecentMonthMaxDemandread-onlycurrentLoad 10th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.4.85ScalardpmMeter311thRecentMonthMaxDemandread-onlycurrentLoad 11th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.4.86ScalardpmMeter312thRecentMonthMaxDemandread-onlycurrentLoad 12th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.4.87ScalardpmMeter313thRecentMonthMaxDemandread-onlycurrentLoad 13th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.4.88ScalardpmMeter314thRecentMonthMaxDemandread-onlycurrentLoad 14th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.4.89ScalardpmMeter315thRecentMonthMaxDemandread-onlycurrentLoad 15th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.4.90ScalardpmMeter316thRecentMonthMaxDemandread-onlycurrentLoad 16th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.4.91ScalardpmMeter317thRecentMonthMaxDemandread-onlycurrentLoad 17th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.4.92ScalardpmMeter318thRecentMonthMaxDemandread-onlycurrentLoad 18th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.4.93ScalardpmMeter319thRecentMonthMaxDemandread-onlycurrentLoad 19th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.4.94ScalardpmMeter320thRecentMonthMaxDemandread-onlycurrentLoad 20th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.4.95ScalardpmMeter321stRecentMonthMaxDemandread-onlycurrentLoad 21st Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.4.96ScalardpmMeter322ndRecentMonthMaxDemandread-onlycurrentLoad 22nd Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.4.97ScalardpmMeter323rdRecentMonthMaxDemandread-onlycurrentLoad 23rd Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.4.98ScalardpmMeter324thRecentMonthMaxDemandread-onlycurrentLoad 24th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.4.99ScalardpmMeter3MainAndAuxilliaryPositionsread-onlycurrentLoad Main & Auxiliary Switch positions.
1.3.6.1.4.1.7777.1.4.100ScalardpmMeter3ResettableEngineRunCounterread-onlycurrentLoad Resettable Engine Runtime counter in Hours.
1.3.6.1.4.1.7777.1.4.101ScalardpmMeter3CumulativeEngineRunCounterread-onlycurrentLoad Cumulative Engine Runtime counter in Hours.
1.3.6.1.4.1.7777.1.5NodedpmMeter4
1.3.6.1.4.1.7777.1.5.1ScalardpmMeter4DPMNameread-onlycurrentOther DPM name.
1.3.6.1.4.1.7777.1.5.2ScalardpmMeter4DPMLocaread-onlycurrentOther DPM Location.
1.3.6.1.4.1.7777.1.5.3ScalardpmMeter4NominalVoltageread-onlycurrentOther Nominal Voltage.
1.3.6.1.4.1.7777.1.5.4ScalardpmMeter4NominalCurrentread-onlycurrentOther Nominal Current.
1.3.6.1.4.1.7777.1.5.5ScalardpmMeter4InstantaneousDemandKwMWread-onlycurrentOther Instantaneous Demand kW MW
1.3.6.1.4.1.7777.1.5.6ScalardpmMeter4InstantaneousDemandDateread-onlycurrentOther Demand Date.
1.3.6.1.4.1.7777.1.5.7ScalardpmMeter4InstantaneousDemandTimeread-onlycurrentOther Demand Time.
1.3.6.1.4.1.7777.1.5.8ScalardpmMeter4BlockDemandforFullHouInkWread-onlycurrentOther Block Demand for Full Hou In kW.
1.3.6.1.4.1.7777.1.5.9ScalardpmMeter4BlockDemandforFullDayInkWread-onlycurrentOther Block Demand for Full Day In kW.
1.3.6.1.4.1.7777.1.5.10ScalardpmMeter4BlockDemandforFullMonthInKWread-onlycurrentOther Block Demand for Full Month In kW.
1.3.6.1.4.1.7777.1.5.11ScalardpmMeter4BlockDemandforFullYearread-onlycurrentOther Block Demand for Full Year In kW.
1.3.6.1.4.1.7777.1.5.12ScalardpmMeter4CurrentThdAread-onlycurrentOther Phase A THD Current.In percentage
1.3.6.1.4.1.7777.1.5.13ScalardpmMeter4CurrentThdBread-onlycurrentOther Phase B THD Current.In percentage
1.3.6.1.4.1.7777.1.5.14ScalardpmMeter4CurrentThdCread-onlycurrentOther Phase C THD Current.In percentage
1.3.6.1.4.1.7777.1.5.15ScalardpmMeter4VoltageThdAread-onlycurrentOther Phase A THD Voltage.In percentage
1.3.6.1.4.1.7777.1.5.16ScalardpmMeter4VoltageThdBread-onlycurrentOther Phase B THD Voltage.In percentage
1.3.6.1.4.1.7777.1.5.17ScalardpmMeter4VoltageThdCread-onlycurrentOther Phase C THD Voltage.In percentage
1.3.6.1.4.1.7777.1.5.18ScalardpmMeter4Vabread-onlycurrentOther Vab Voltage.
1.3.6.1.4.1.7777.1.5.19ScalardpmMeter4Vbcread-onlycurrentOther Vbc Voltage.
1.3.6.1.4.1.7777.1.5.20ScalardpmMeter4Vcaread-onlycurrentOther Vca Voltage.
1.3.6.1.4.1.7777.1.5.21ScalardpmMeter4VolAverageread-onlycurrentOther Vol Average.
1.3.6.1.4.1.7777.1.5.22ScalardpmMeter4VolUnbalread-onlycurrentOther Vol Unbal.
1.3.6.1.4.1.7777.1.5.23ScalardpmMeter4Vanread-onlycurrentOther Vol Van.
1.3.6.1.4.1.7777.1.5.24ScalardpmMeter4Vbnread-onlycurrentOther Vbn.
1.3.6.1.4.1.7777.1.5.25ScalardpmMeter4Vcnread-onlycurrentOther Vcn.
1.3.6.1.4.1.7777.1.5.26ScalardpmMeter4Vavgneutralread-onlycurrentOther Avg neutral Voltage.
1.3.6.1.4.1.7777.1.5.27ScalardpmMeter4Frequencyread-onlycurrentOther Frequency.
1.3.6.1.4.1.7777.1.5.28ScalardpmMeter4PowerFactorread-onlycurrentOther Power factor.
1.3.6.1.4.1.7777.1.5.29ScalardpmMeter4CurPhaseAread-onlycurrentOther Phase A Current.
1.3.6.1.4.1.7777.1.5.30ScalardpmMeter4CurPhaseBread-onlycurrentOther Phase B Current.
1.3.6.1.4.1.7777.1.5.31ScalardpmMeter4CurPhaseCread-onlycurrentOther Phase C Current.
1.3.6.1.4.1.7777.1.5.32ScalardpmMeter4PhaseCurAvgread-onlycurrentOther Phase Current aVG.
1.3.6.1.4.1.7777.1.5.33ScalardpmMeter4PhaseCurUnbalancecePercentageread-onlycurrentOther Phase Cur Unbalancece Percentage.
1.3.6.1.4.1.7777.1.5.34ScalardpmMeter4RealTotalPowerread-onlycurrentOther Real Total power factor.
1.3.6.1.4.1.7777.1.5.35ScalardpmMeter4ReactiveTotalPowerread-onlycurrentOther Reactive Total power.
1.3.6.1.4.1.7777.1.5.36ScalardpmMeter4ApparentTotalPowerread-onlycurrentOther AApparent Total power.
1.3.6.1.4.1.7777.1.5.37ScalardpmMeter4NetActiveEnergyread-onlycurrentOther Net Active Energy.
1.3.6.1.4.1.7777.1.5.38ScalardpmMeter4FirmwareVersionread-onlycurrentOther DPM Firmware .
1.3.6.1.4.1.7777.1.5.39ScalardpmMeter4ActivePowerAread-onlycurrentOther Active Power phase A.
1.3.6.1.4.1.7777.1.5.40ScalardpmMeter4ActivePowerBread-onlycurrentOther Active Power phase B.
1.3.6.1.4.1.7777.1.5.41ScalardpmMeter4ActivePowerCread-onlycurrentOther Active Power phase C.
1.3.6.1.4.1.7777.1.5.42ScalardpmMeter4ActivePowerTotalread-onlycurrentOther Active Power Total.
1.3.6.1.4.1.7777.1.5.43ScalardpmMeter4ReactivePowerAread-onlycurrentOther Reactive Power phase A.
1.3.6.1.4.1.7777.1.5.44ScalardpmMeter4ReactivePowerBread-onlycurrentOther Reactive Power phase B.
1.3.6.1.4.1.7777.1.5.45ScalardpmMeter4ReactivePowerCread-onlycurrentOther Reactive Power phase A.
1.3.6.1.4.1.7777.1.5.46ScalardpmMeter4ReactivePowerTotalread-onlycurrentOther Reactive Power Total.
1.3.6.1.4.1.7777.1.5.47ScalardpmMeter4PowerFactorAread-onlycurrentOther Reactive Power phase A.
1.3.6.1.4.1.7777.1.5.48ScalardpmMeter4PowerFactorBread-onlycurrentOther Reactive Power phase B.
1.3.6.1.4.1.7777.1.5.49ScalardpmMeter4PowerFactorCread-onlycurrentOther Reactive Power phase C.
1.3.6.1.4.1.7777.1.5.50ScalardpmMeter4PowerFactorTotalread-onlycurrentOther Reactive Power Total.
1.3.6.1.4.1.7777.1.5.51ScalardpmMeter4VoltAmperePowerAread-onlycurrentOther volt-ampere Power phase A.
1.3.6.1.4.1.7777.1.5.52ScalardpmMeter4VoltAmperePowerBread-onlycurrentOther volt-ampere Power phase B.
1.3.6.1.4.1.7777.1.5.53ScalardpmMeter4VoltAmperePowerCread-onlycurrentOther volt-ampere Power phase C.
1.3.6.1.4.1.7777.1.5.54ScalardpmMeter4VoltAmperePowerTotalread-onlycurrentOther volt-ampere Power Total.
1.3.6.1.4.1.7777.1.5.55ScalardpmMeter4MaxWattDemandread-onlycurrentOther Maximum Watt Demand.
1.3.6.1.4.1.7777.1.5.56ScalardpmMeter4NORMALKWHNetread-onlycurrentOther NORMAL kWH Net.
1.3.6.1.4.1.7777.1.5.57ScalardpmMeter4NORMALKVARHNetread-onlycurrentOther NORMAL kVarH Net.
1.3.6.1.4.1.7777.1.5.58ScalardpmMeter4NORMALKVAHNetread-onlycurrentOther NORMAL kVaH Net.
1.3.6.1.4.1.7777.1.5.59ScalardpmMeter4EMERGKWHNetread-onlycurrentOther EMERGENCY kWH Net.
1.3.6.1.4.1.7777.1.5.60ScalardpmMeter4EMERGKVARHNetread-onlycurrentOther EMERGENCY kVarH Net.
1.3.6.1.4.1.7777.1.5.61ScalardpmMeter4EMERGKVAHNetread-onlycurrentOther EMERGENCY kVaH Net.
1.3.6.1.4.1.7777.1.5.62ScalardpmMeter4NORMALMinTotalActivePowerread-onlycurrentOther NORMAL Minimum Total Active Power.
1.3.6.1.4.1.7777.1.5.63ScalardpmMeter4NORMALMaxTotalActivePowerread-onlycurrentOther NORMAL Maximum Total Active Power.
1.3.6.1.4.1.7777.1.5.64ScalardpmMeter4NORMALMinTotalReactivePowerread-onlycurrentOther NORMAL Minimum Total Reactive Power.
1.3.6.1.4.1.7777.1.5.65ScalardpmMeter4NORMALMaxTotalReactivePowerread-onlycurrentOther NORMAL Maximum Total Reactive Power.
1.3.6.1.4.1.7777.1.5.66ScalardpmMeter4NORMALMinTotalApparentPowerread-onlycurrentOther NORMAL Minimum Total Apparent Power.
1.3.6.1.4.1.7777.1.5.67ScalardpmMeter4NORMALMaxTotalApparentPowerread-onlycurrentOther NORMAL Maximum Total Apparent Power.
1.3.6.1.4.1.7777.1.5.68ScalardpmMeter4EMERGMinTotalActivePowerread-onlycurrentOther EMERGENCY Minimum Total Active Power.
1.3.6.1.4.1.7777.1.5.69ScalardpmMeter4EMERGMaxTotalActivePowerread-onlycurrentOther EMERGENCY Maximum Total Active Power.
1.3.6.1.4.1.7777.1.5.70ScalardpmMeter4EMERGMinTotalReactivePowerread-onlycurrentOther EMERGENCY Minimum Total Reactive Power.
1.3.6.1.4.1.7777.1.5.71ScalardpmMeter4EMERGMaxTotalReactivePowerread-onlycurrentOther EMERGENCY Maximum Total Reactive Power.
1.3.6.1.4.1.7777.1.5.72ScalardpmMeter4EMERGMinTotalApparentPowerread-onlycurrentOther EMERGENCY Minimum Total Apparent Power.
1.3.6.1.4.1.7777.1.5.73ScalardpmMeter4EMERGMaxTotalApparentPowerread-onlycurrentOther EMERGENCY Maximum Total Apparent Power.
1.3.6.1.4.1.7777.1.5.74ScalardpmMeter4CurrentMonthMaxDemandread-onlycurrentOther Current Month Maximum Demand.
1.3.6.1.4.1.7777.1.5.75ScalardpmMeter4MostRecentMonthMaxDemandread-writecurrentOther Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.5.76ScalardpmMeter42ndRecentMonthMaxDemandread-onlycurrentOther 2nd Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.5.77ScalardpmMeter43rdRecentMonthMaxDemandread-onlycurrentOther 3rd Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.5.78ScalardpmMeter44thRecentMonthMaxDemandread-onlycurrentOther 4th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.5.79ScalardpmMeter45thRecentMonthMaxDemandread-onlycurrentOther 5th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.5.80ScalardpmMeter46thRecentMonthMaxDemandread-onlycurrentOther 6th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.5.81ScalardpmMeter47thRecentMonthMaxDemandread-onlycurrentOther 7th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.5.82ScalardpmMeter48thRecentMonthMaxDemandread-onlycurrentOther 8th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.5.83ScalardpmMeter49thRecentMonthMaxDemandread-onlycurrentOther 9th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.5.84ScalardpmMeter410thRecentMonthMaxDemandread-onlycurrentOther 10th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.5.85ScalardpmMeter411thRecentMonthMaxDemandread-onlycurrentOther 11th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.5.86ScalardpmMeter412thRecentMonthMaxDemandread-onlycurrentOther 12th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.5.87ScalardpmMeter413thRecentMonthMaxDemandread-onlycurrentOther 13th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.5.88ScalardpmMeter414thRecentMonthMaxDemandread-onlycurrentOther 14th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.5.89ScalardpmMeter415thRecentMonthMaxDemandread-onlycurrentOther 15th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.5.90ScalardpmMeter416thRecentMonthMaxDemandread-onlycurrentOther 16th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.5.91ScalardpmMeter417thRecentMonthMaxDemandread-onlycurrentOther 17th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.5.92ScalardpmMeter418thRecentMonthMaxDemandread-onlycurrentOther 18th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.5.93ScalardpmMeter419thRecentMonthMaxDemandread-onlycurrentOther 19th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.5.94ScalardpmMeter420thRecentMonthMaxDemandread-onlycurrentOther 20th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.5.95ScalardpmMeter421stRecentMonthMaxDemandread-onlycurrentOther 21st Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.5.96ScalardpmMeter422ndRecentMonthMaxDemandread-onlycurrentOther 22nd Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.5.97ScalardpmMeter423rdRecentMonthMaxDemandread-onlycurrentOther 23rd Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.5.98ScalardpmMeter424thRecentMonthMaxDemandread-onlycurrentOther 24th Most Recent Month Max Demand.
1.3.6.1.4.1.7777.1.5.99ScalardpmMeter4MainAndAuxilliaryPositionsread-onlycurrentOther Main & Auxiliary Switch positions.
1.3.6.1.4.1.7777.1.5.100ScalardpmMeter4ResettableEngineRunCounterread-onlycurrentOther Resettable Engine Runtime counter in Hours.
1.3.6.1.4.1.7777.1.5.101ScalardpmMeter4CumulativeEngineRunCounterread-onlycurrentOther Cumulative Engine Runtime counter in Hours.
1.3.6.1.4.1.7777.1.6Nodetraps
1.3.6.1.4.1.7777.1.6.0IdentitytrapsATScurrentRoot node for the converted TRAP-TYPEs.
1.3.6.1.4.1.7777.1.6.0.2Notificationgenerator_start_signal_activated_SNMPSendcurrentGenerator Start Signal Activated.
1.3.6.1.4.1.7777.1.6.0.3Notificationgenerator_start_signal_removed_SNMPSendcurrentGenerator Start Signal Removed.
1.3.6.1.4.1.7777.1.6.0.4Notificationtransferred_from_normal_to_emergency_SNMPSendcurrentTransferred from Normal to Emergency.
1.3.6.1.4.1.7777.1.6.0.5Notificationtransferred_from_emergency_to_normal_SNMPSendcurrentTransferred from Emergency to Normal.
1.3.6.1.4.1.7777.1.6.0.6Notificationemergency_accepted_SNMPSendcurrentEmergency Accepted.
1.3.6.1.4.1.7777.1.6.0.7Notificationemergency_not_accepted_SNMPSendcurrentEmergency Not Accepted.
1.3.6.1.4.1.7777.1.6.0.8Notificationnormal_accepted_SNMPSendcurrentNormal Accepted.
1.3.6.1.4.1.7777.1.6.0.9Notificationnormal_not_accepted_SNMPSendcurrentNormal Not Accepted.
1.3.6.1.4.1.7777.1.6.0.10Notificationloss_of_emergency_when_on_emergency_SNMPSendcurrentLoss of Emergency when on Emergency.
1.3.6.1.4.1.7777.1.6.0.11Notificationload_disconnected_SNMPSendcurrentLoad Disconnected.
1.3.6.1.4.1.7777.1.6.0.12Notificationtransfer_switch_changed_to_non_automatic_mode_SNMPSendcurrentTransfer Switch Changed to Non-Automatic Mode.
1.3.6.1.4.1.7777.1.6.0.13Notificationtransfer_switch_changed_to_automatic_mode_SNMPSendcurrentTransfer Switch Changed to Automatic Mode.
1.3.6.1.4.1.7777.1.6.0.14Notificationemergency_not_accepted_in_time_SNMPSendcurrentEmergency Not Accepted in Time.
1.3.6.1.4.1.7777.1.6.0.15Notificationtransfer_not_successful_SNMPSendcurrentTransfer Not Successful.
1.3.6.1.4.1.7777.1.6.0.16Notificationtransfer_switch_position_not_determined_SNMPSendcurrentTransfer Switch Position Not Determined.
1.3.6.1.4.1.7777.1.6.0.17Notificationtransfer_switch_locked_out_SNMPSendcurrentTransfer Switch Locked Out.
1.3.6.1.4.1.7777.1.6.0.18Notificationctts_extended_parallel_alarm_SNMPSendcurrentCTTS Extended Parallel Alarm.
1.3.6.1.4.1.7777.1.6.0.19Notificationctts_failure_to_synchronize_SNMPSendcurrentCTTS Failure to Synchronize.
1.3.6.1.4.1.7777.1.6.0.20Notificationnormal_breaker_tripped_SNMPSendcurrentNormal Breaker Tripped.
1.3.6.1.4.1.7777.1.6.0.21Notificationemergency_breaker_tripped_SNMPSendcurrentEmergency Breaker Tripped.
1.3.6.1.4.1.7777.1.6.0.22Notificationy_y_primary_fail_active_SNMPSendcurrentY-Y Primary Fail is Active.
1.3.6.1.4.1.7777.1.6.0.23Notificationauxiliary_engine_input_activated_SNMPSendcurrentAuxiliary/Engine Input Activated.
1.3.6.1.4.1.7777.1.6.1ScalarpsAlarmVariableread-onlycurrentTraps notification.
1.3.6.1.4.1.7777.1.6.2IdentitytrapsBICcurrentRoot node for the converted TRAP-TYPEs for BIC.
1.3.6.1.4.1.7777.1.6.2.1NotificationbicTransferSwitchOnNormalcurrentBIC Transfer Switch On Normal Source.
1.3.6.1.4.1.7777.1.6.2.2NotificationbicTransferSwitchOffNormalcurrentBIC Transfer Switch Off Normal Source.
1.3.6.1.4.1.7777.1.6.2.3NotificationbicTransferSwitchOnEmergencycurrentBIC Transfer Switch On Emergency Source.
1.3.6.1.4.1.7777.1.6.2.4NotificationbicTransferSwitchOffEmergencycurrentBIC Transfer Switch Off Emergency Source.
1.3.6.1.4.1.7777.1.6.2.5NotificationbicBypassOnNormalcurrentBIC Bypass On Normal Source.
1.3.6.1.4.1.7777.1.6.2.6NotificationbicBypassOffNormalcurrentBIC Bypass Off Normal Source.
1.3.6.1.4.1.7777.1.6.2.7NotificationbicBypassOnEmergencycurrentBIC Bypass On Emergency Source.
1.3.6.1.4.1.7777.1.6.2.8NotificationbicBypassOffEmergencycurrentBIC Bypass Off Emergency Source.
1.3.6.1.4.1.7777.1.6.2.9NotificationbicNormalAvailablecurrentBIC Normal Source Available.
1.3.6.1.4.1.7777.1.6.2.10NotificationbicNormalNotAvailblecurrentBIC Normal Source Not Available.
1.3.6.1.4.1.7777.1.6.2.11NotificationbicEmergencyAvailablecurrentBIC Emergency Source Available.
1.3.6.1.4.1.7777.1.6.2.12NotificationbicEmergencyNotAvailablecurrentBIC Emergency Source Not Available.
1.3.6.1.4.1.7777.1.6.2.13NotificationbicLoadConnectedToNormalcurrentBIC Load Connected To Normal Source.
1.3.6.1.4.1.7777.1.6.2.14NotificationbicLoadDisConnectedFromNormalcurrentBIC Load Disconnected From Normal Source.
1.3.6.1.4.1.7777.1.6.2.15NotificationbicLoadConnectedToEmergencycurrentBIC Load Connected To Emergency Source.
1.3.6.1.4.1.7777.1.6.2.16NotificationbicLoadDisconnectedFromEmergencycurrentBIC Load Disconnected To Emergency Source.
1.3.6.1.4.1.7777.1.6.2.17NotificationbicInAutocurrentBIC In Auto.
1.3.6.1.4.1.7777.1.6.2.18NotificationbicNotInAutocurrentBIC Not In Auto.
1.3.6.1.4.1.7777.1.6.2.19NotificationbicBypassSwitchConnectedcurrentBIC Bypass Switch on Connected Mode.
1.3.6.1.4.1.7777.1.6.2.20NotificationbicBypassSwitchNotConnectedcurrentBIC Bypass Switch Not on Connected Mode.
1.3.6.1.4.1.7777.1.6.2.21NotificationbicBypassSwitchTestcurrentBIC Bypass Switch on Test Mode.
1.3.6.1.4.1.7777.1.6.2.22NotificationbicBypassSwitchNotTestcurrentBIC Bypass Switch Not on Test Mode.
1.3.6.1.4.1.7777.1.6.2.23NotificationbicBypassSwitchIsolatedcurrentBIC Bypass Switch on Isolation Mode.
1.3.6.1.4.1.7777.1.6.2.24NotificationbicBypassSwitchNotIsolatedcurrentBIC Bypass Switch Not on Isolation Mode.
1.3.6.1.4.1.7777.1.6.2.25NotificationbicManualEngineStartSignalActivecurrentBIC Manual Engine Start Signal is ON.
1.3.6.1.4.1.7777.1.6.2.26NotificationbicManualEngineStartSignalOffcurrentBIC Manual Engine Start Signal is OFF.
1.3.6.1.4.1.7777.1.6.2.27NotificationbicLoadEnergizedByNormalcurrentBIC Load Energized By Normal Source.
1.3.6.1.4.1.7777.1.6.2.28NotificationbicLoadNotEnergizedByNormalcurrentBIC Load Not Emergized By Normal Source.
1.3.6.1.4.1.7777.1.6.2.29NotificationbicLoadEnergizedByEmergencycurrentBIC Load Energized By Emergency Source.
1.3.6.1.4.1.7777.1.6.2.30NotificationbicLoadNotEnergizedByEmergencycurrentBIC Load Not Emergized By Emergency Source.
1.3.6.1.4.1.7777.1.6.2.31NotificationbicAlarmSignalActivecurrentBIC Alarm Signal is ON.
1.3.6.1.4.1.7777.1.6.2.32NotificationbicAlarmSignalOffcurrentBIC Alarm Signal is OFF.
1.3.6.1.4.1.7777.1.6.3IdentitytrapsIOModulecurrentDescription.
1.3.6.1.4.1.7777.1.6.3.1NotificationioModuleNotifycurrentDescription.
1.3.6.1.4.1.7777.1.7Nodebic
1.3.6.1.4.1.7777.1.7.13Scalarhr40013read-onlycurrentMODBUS HR 40013: Normal Frequency.
1.3.6.1.4.1.7777.1.7.14Scalarhr40014read-onlycurrentMODBUS HR 40014: Emergency Frequency.
1.3.6.1.4.1.7777.1.7.15Scalarhr40015read-onlycurrentMODBUS HR 40015: ATS, BTS & Load Status. 40015:00 ATS on Norm 40015:01 ATS on Emer 40015:02 Bypassed to Norm 40015:03 Bypassed to Emer 40015:04 Norm Avail 4001…
1.3.6.1.4.1.7777.1.7.19Scalarhr40019read-onlycurrentMODBUS HR 40019: Normal Voltage CA.
1.3.6.1.4.1.7777.1.7.23Scalarhr40023read-onlycurrentMODBUS HR 40023: Emergency Voltage CA.
1.3.6.1.4.1.7777.1.7.25Scalarhr40025read-onlycurrentMODBUS HR 40025: Nominal Voltage.
1.3.6.1.4.1.7777.1.7.26Scalarhr40026read-onlycurrentMODBUS HR 40026: Nominal Frequency.
1.3.6.1.4.1.7777.1.7.28Scalarhr40028read-onlycurrentMODBUS HR 40028-32: Control Panel Software Version.
1.3.6.1.4.1.7777.1.7.34Scalarhr40034read-onlycurrentMODBUS HR 40034-38: Control Panel Software Version.
1.3.6.1.4.1.7777.1.7.39Scalarhr40039read-onlycurrentMODBUS HR 40039: CPLD & BIC Hardware Version.
1.3.6.1.4.1.7777.1.7.43Scalarhr40043read-onlycurrentMODBUS HR 40043: ATS Control Inihibit.
1.3.6.1.4.1.7777.1.7.55Scalarhr40055read-onlycurrentMODBUS HR 40055: Total No. of Logged Events.
1.3.6.1.4.1.7777.1.7.81Scalarhr40081read-onlycurrentMODBUS HR 40081: CAN Communication Configurations. 40081:00-06 CAN Port Address 40081:07 Can Port Enable 40081:08-10 CAN Port Baud Rate
1.3.6.1.4.1.7777.1.7.87Scalarhr40087read-onlycurrentMODBUS HR 40087: BIC Output Status. 40087:00 notInAuto/ AA12 40087:01 isoRackOnConn/ AA 6 40087:02 isoRackOnTest/ AA 8 40087:03 isoRackOnIsolated/ AA 7 40087:0…
1.3.6.1.4.1.7777.1.7.88Scalarhr40088read-onlycurrentMODBUS HR 40088: BIC Sensor Input. 40088:00 Sensor Input Connect/Conn-Test 40088:01 Sensor Input Connected 40088:02 Sensor Input Conn-Test/Test/Test-Isolated 4…
1.3.6.1.4.1.7777.1.7.89Scalarhr40089read-onlycurrentMODBUS HR 40089: BIC & ATS Switch Position. 40089:00 BTS Position Inputs BTS Norm On 40089:01 BTS Position Inputs BTS Norm Off 40089:02 BTS Position Inputs BTS…
1.3.6.1.4.1.7777.1.7.90Scalarhr40090read-onlycurrentMODBUS HR 40090: CPLD DIP Switch Status. 40090:00 CPLD Dipswitch Bit 0 40090:01 CPLD Dipswitch Bit 1 40090:02 CPLD Dipswitch Bit 2 40090:03 CPLD Dipswitch Bit …
1.3.6.1.4.1.7777.1.7.91Scalarhr40091read-onlycurrentMODBUS HR 40091: BTS Coil Status. 40091:00 Coil Pwr Mon 1 40091:01 Coil Power Enable 40091:02 Coil Power Select
1.3.6.1.4.1.7777.1.7.92Scalarhr40092read-onlycurrentMODBUS HR 40091: BTS Handle Position Status. 40092:00 BTS Handle Position Off 40092:01 BTS Handle Position Norm 40092:02 BTS Handle Position Emer
1.3.6.1.4.1.7777.1.7.93Scalarhr40093read-onlycurrentMODBUS HR 40093-98: Serial Number.
1.3.6.1.4.1.7777.1.7.99Scalarhr40099read-onlycurrentMODBUS HR 40099: BIC PuchButton Status. 40099:00 BP to Norm 40099:01 BP to Emer 40099:02 Unbypass 40099:03 Lamp Test
1.3.6.1.4.1.7777.1.7.109Scalarhr40109read-onlycurrentMODBUS HR 40109-112: BIC Tag Name.
1.3.6.1.4.1.7777.1.7.119Scalarhr40119read-onlycurrentMODBUS HR 40119: Normal Voltage Dropout.
1.3.6.1.4.1.7777.1.7.120Scalarhr40120read-onlycurrentMODBUS HR 40120: Normal Voltage PickUp.
1.3.6.1.4.1.7777.1.7.121Scalarhr40121read-onlycurrentMODBUS HR 40121: Normal Over Voltage Trip.
1.3.6.1.4.1.7777.1.7.122Scalarhr40122read-onlycurrentMODBUS HR 40122: Normal Frequency DropOut.
1.3.6.1.4.1.7777.1.7.123Scalarhr40123read-onlycurrentMODBUS HR 40123: Normal Frequency PickUp.
1.3.6.1.4.1.7777.1.7.124Scalarhr40124read-onlycurrentMODBUS HR 40124: Normal Over Frequency Trip.
1.3.6.1.4.1.7777.1.7.126Scalarhr40126read-onlycurrentMODBUS HR 40126: Emergency Voltage Dropout.
1.3.6.1.4.1.7777.1.7.127Scalarhr40127read-onlycurrentMODBUS HR 40127: Emergency Voltage PickUp.
1.3.6.1.4.1.7777.1.7.128Scalarhr40128read-onlycurrentMODBUS HR 40128: Emergency Over Voltage Trip.
1.3.6.1.4.1.7777.1.7.129Scalarhr40129read-onlycurrentMODBUS HR 40129: Emergency Frequency DropOut.
1.3.6.1.4.1.7777.1.7.130Scalarhr40130read-onlycurrentMODBUS HR 40130: Emergency Frequency PickUp.
1.3.6.1.4.1.7777.1.7.131Scalarhr40131read-onlycurrentMODBUS HR 40131: Emergency Over Frequency Trip.
1.3.6.1.4.1.7777.1.7.165Scalarhr40165read-onlycurrentMODBUS HR 40165-174: BIC Location.
1.3.6.1.4.1.7777.1.7.254Scalarhr40254read-onlycurrentMODBUS HR 40254: Bypass LockOut Active.
1.3.6.1.4.1.7777.1.7.256Scalarhr40256read-onlycurrentMODBUS HR 40256: BIC Alarm Status. 40256:00 Alarm 40256:01 DiagnosticMode 40256:02 Isolation position sensor error 40256:03 ATS position switch error 40256:04 …
1.3.6.1.4.1.7777.1.8NodeioModules
1.3.6.1.4.1.7777.1.8.1Scalarhr46001m1read-onlycurrentASCO Etherenet IO Module 1 Digital Output When converted to Binary as shown below, Minimum Maximum 00000000 00000000 11111111 11111111 where each bit position …
1.3.6.1.4.1.7777.1.8.2Scalarhr46002m1read-onlycurrentASCO Etherenet IO Module 1 Digital Input When converted to Binary as shown below, Minimum Maximum 00000000 00000000 11111111 11111111 where each bit position d…
1.3.6.1.4.1.7777.1.8.3Scalarhr46001m2read-onlycurrentASCO Etherenet IO Module 2 Digital Output When converted to Binary as shown below, Minimum Maximum 00000000 00000000 11111111 11111111 where each bit position …
1.3.6.1.4.1.7777.1.8.4Scalarhr46002m2read-onlycurrentASCO Etherenet IO Module 2 Digital Input When converted to Binary as shown below, Minimum Maximum 00000000 00000000 11111111 11111111 where each bit position d…
1.3.6.1.4.1.7777.2NodeascoConformance
1.3.6.1.4.1.7777.2.1NodeascoGroups
1.3.6.1.4.1.7777.2.1.1GroupcurrentObjectGroupcurrentEnter the description of the created OBJECT-GROUP.
1.3.6.1.4.1.7777.2.1.2GroupcurrentNotificationGroupcurrentEnter the description of the created NOTIFICATION-GROUP.
1.3.6.1.4.1.7777.2.2NodeascoCompliances
1.3.6.1.4.1.7777.2.2.1CompliancebasicCompliancecurrentEnter the description of the created MODULE-COMPLIANCE.