ATEN PE MIB
OIDNameAccessStatusDescription
1.3.6.1.4.1.21317.1.3.2.3Identitype2ATEN PE MIB
1.3.6.1.4.1.21317.1.3.2.3.1Nodemanagement
1.3.6.1.4.1.21317.1.3.2.3.1.1ScalarstaCountread-onlycurrentThe available station count which includes master and slave stations.
1.3.6.1.4.1.21317.1.3.2.3.1.2TablestaStatusTablenot-accessiblecurrentStation status table.
1.3.6.1.4.1.21317.1.3.2.3.1.2.1RowstaStatusEntrynot-accessiblecurrentSingle entry containing station status info.
1.3.6.1.4.1.21317.1.3.2.3.1.2.1.1ColumnstaIdnot-accessiblecurrentStation ID.
1.3.6.1.4.1.21317.1.3.2.3.1.2.1.2ColumnstaStatusFWVerread-onlycurrentStation FW version. If the station is not available, it returns 'station N/A'.
1.3.6.1.4.1.21317.1.3.2.3.1.2.1.3ColumnstaStatusModelNameread-onlycurrentStation model name. If the station is not available, it returns 'station N/A'
1.3.6.1.4.1.21317.1.3.2.3.1.2.1.4ColumnstaStatusSwitchableread-onlycurrentOutlets of the station are switchable or not. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.1.2.1.5ColumnstaStatusPerPortReadingread-onlycurrentOutlets of the station are per-port reading or not. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.1.2.1.6ColumnstaStatusBankCountread-onlycurrentStation bank count. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.1.2.1.7ColumnstaStatusOutletCountread-onlycurrentStation outlet count. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.1.2.1.8ColumnstaStatusSensorCountread-onlycurrentStation sensor count. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.1.2.1.9ColumnstaStatusHasAutoPingread-onlycurrentThe station supports auto-ping or not. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.1.2.1.10ColumnstaStatusInletCountread-onlycurrentStation inlet count. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.1.3TablestaControlTablenot-accessiblecurrentStation control table.
1.3.6.1.4.1.21317.1.3.2.3.1.3.1RowstaControlEntrynot-accessiblecurrentSingle entry containing station control info.
1.3.6.1.4.1.21317.1.3.2.3.1.3.1.1ColumnstaControlRebootread-writecurrentReboot the station. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.1.4TablerackConfigTablenot-accessiblecurrentRack config table.
1.3.6.1.4.1.21317.1.3.2.3.1.4.1RowrackConfigEntrynot-accessiblecurrentSingle entry containing rack config info.
1.3.6.1.4.1.21317.1.3.2.3.1.4.1.1ColumnrackConfigNameread-writecurrentDisplay or set station's rack name. string length: 1~32 If the station is not available, it returns 'station N/A'. NOTE: Input string as /empty to set this obj…
1.3.6.1.4.1.21317.1.3.2.3.1.4.1.2ColumnrackConfigRowread-writecurrentDisplay or set station's rack row number. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.1.4.1.3ColumnrackConfigColumnread-writecurrentDisplay or set station's rack column number. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.1.5ScalarstaStateread-onlycurrentCascade stations' state. Return string length equals to the MAX support stations. If station N is alive, display 1 at the N's character, else, display 0. The f…
1.3.6.1.4.1.21317.1.3.2.3.2Nodeenergy
1.3.6.1.4.1.21317.1.3.2.3.2.1Nodedevice
1.3.6.1.4.1.21317.1.3.2.3.2.1.1TabledevStatusTablenot-accessiblecurrentDevice status table.
1.3.6.1.4.1.21317.1.3.2.3.2.1.1.1RowdevStatusEntrynot-accessiblecurrentSingle entry containing device status info.
1.3.6.1.4.1.21317.1.3.2.3.2.1.1.1.1ColumndevStatusRatedCurread-onlycurrentDevice input Current value. unit:(0.1mA) If the station does not support this OID, we show value 0. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.2.1.1.1.2ColumndevStatusRatedVolread-onlycurrentDevice input Voltage value. unit:(0.1mV) If the station does not support this OID, we show value 0. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.2.1.1.1.3ColumndevStatusRatedPowerread-onlycurrentDevice power Capacity value. unit:(0.1mVA) If the station does not support this OID, we show value 0. If the station is not available, it returns value -300000…
1.3.6.1.4.1.21317.1.3.2.3.2.1.1.1.4ColumndevStatusWiredTyperead-onlycurrentDevice circuit wired type Example: 1 for 1 phase, 2 for 3 phase wye, 3 for 3 phase delta If the station does not support this OID, we show value 0. If the stat…
1.3.6.1.4.1.21317.1.3.2.3.2.1.2TabledevConfigTablenot-accessiblecurrentDevice config table.
1.3.6.1.4.1.21317.1.3.2.3.2.1.2.1RowdevConfigEntrynot-accessiblecurrentSingle entry containing device config info.
1.3.6.1.4.1.21317.1.3.2.3.2.1.2.1.1ColumndevConfigDevNameread-writecurrentThe name of the device. string length: 1~39 If the station is not available, it returns 'station N/A'. NOTE: Input string as /empty to set this object to NULL.
1.3.6.1.4.1.21317.1.3.2.3.2.1.2.1.2ColumndevConfigPowerOnScheduleEnread-writecurrentDisplay or set whether power on schedule or not. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.2.1.2.1.3ColumndevConfigOutletsSequentialRebootEnread-writecurrentThis function is used to enable or disable all outlet ports to sequential reboot. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.2.1.2.1.4ColumndevConfigMinCurThreshread-writecurrentDisplay or set device minimum electric current measurement threshold. Example: range 0.0~32.0 represents 0~320. NOTICE: Minimum threshold should be smaller tha…
1.3.6.1.4.1.21317.1.3.2.3.2.1.2.1.5ColumndevConfigMaxCurThreshread-writecurrentDisplay or set device maximum electric current measurement threshold. Example: range 0.0~32.0 represents 0~320 NOTICE: Minimum threshold should be smaller than…
1.3.6.1.4.1.21317.1.3.2.3.2.1.2.1.6ColumndevConfigMinVolThreshread-writecurrentDisplay or set device minimum voltage measurement threshold. Example: range 90.0~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than max…
1.3.6.1.4.1.21317.1.3.2.3.2.1.2.1.7ColumndevConfigMaxVolThreshread-writecurrentDisplay or set device maximum voltage measurement threshold. Example: range 90.0~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than max…
1.3.6.1.4.1.21317.1.3.2.3.2.1.2.1.8ColumndevConfigMinPowerThreshread-writecurrentDisplay or set device minimum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maxi…
1.3.6.1.4.1.21317.1.3.2.3.2.1.2.1.9ColumndevConfigMaxPowerThreshread-writecurrentDisplay or set device maximum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maxi…
1.3.6.1.4.1.21317.1.3.2.3.2.1.2.1.10ColumndevConfigMaxPDThreshread-writecurrentDisplay or set device maximum power dissipation measurement threshold. Example: range 0.0 ~ 99999.0 represents 0~999990 NOTICE: Minimum threshold should be sma…
1.3.6.1.4.1.21317.1.3.2.3.2.1.3TabledevControlTablenot-accessiblecurrentDevice control table.
1.3.6.1.4.1.21317.1.3.2.3.2.1.3.1RowdevControlEntrynot-accessiblecurrentSingle entry containing device control info.
1.3.6.1.4.1.21317.1.3.2.3.2.1.3.1.1ColumndevControlOperationread-writecurrentThis function is used for outlet control of device. Set off(1) to turn off for outlet control of device. Set on(2) to turn on for all outlet control of device.…
1.3.6.1.4.1.21317.1.3.2.3.2.1.4TabledevReadingTablenot-accessiblecurrentDevice reading table.
1.3.6.1.4.1.21317.1.3.2.3.2.1.4.1RowdevReadingEntrynot-accessiblecurrentSingle entry containing device reading info.
1.3.6.1.4.1.21317.1.3.2.3.2.1.4.1.1ColumndevReadingCurread-onlycurrentDevice electric current value. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is n…
1.3.6.1.4.1.21317.1.3.2.3.2.1.4.1.2ColumndevReadingVolread-onlycurrentDevice voltage value. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is not availa…
1.3.6.1.4.1.21317.1.3.2.3.2.1.4.1.3ColumndevReadingPowerread-onlycurrentDevice power value. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is not availabl…
1.3.6.1.4.1.21317.1.3.2.3.2.1.4.1.4ColumndevReadingPDread-onlycurrentDevice power dissipation value. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is …
1.3.6.1.4.1.21317.1.3.2.3.2.1.4.1.5ColumndevReadingPFread-onlycurrentDevice power factor value. This value indicates that 100 times. If the station does not support this OID, it returns value -2000000. If the station is not avai…
1.3.6.1.4.1.21317.1.3.2.3.2.1.5TablepopConfigTablenot-accessiblecurrentPOP config table.
1.3.6.1.4.1.21317.1.3.2.3.2.1.5.1RowpopConfigEntrynot-accessiblecurrentSingle entry containing POP config info.
1.3.6.1.4.1.21317.1.3.2.3.2.1.5.1.1ColumnpopConfigOutletModeEnread-writecurrentDisplay or set whether outlet POP mode is enabled or not. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.2.1.5.1.2ColumnpopConfigLIFOModeEnread-writecurrentDisplay or set whether LIFO POP mode is enabled or not. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.2.1.5.1.3ColumnpopConfigPriorityModeEnread-writecurrentDisplay or set whether priority POP mode is enabled or not. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.2.1.5.1.4ColumnpopConfigPriorityListread-writecurrentIndicate Outlets' power OFF priorities under Priority POP mode. Outlet Separator ',' Bank Separator '#' Assign each priority in each bank by Outlet index or ze…
1.3.6.1.4.1.21317.1.3.2.3.2.1.6TablecapConfigTablenot-accessiblecurrentCAP config table.
1.3.6.1.4.1.21317.1.3.2.3.2.1.6.1RowcapConfigEntrynot-accessiblecurrentSingle entry containing CAP config info.
1.3.6.1.4.1.21317.1.3.2.3.2.1.6.1.1ColumncapConfigModeEnread-writecurrentDisplay or set whether CAP mode is enabled or not. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.2.1.7TablecapPriorityConfigTablenot-accessiblecurrentCAP priority config table.
1.3.6.1.4.1.21317.1.3.2.3.2.1.7.1RowcapPriorityConfigEntrynot-accessiblecurrentSingle entry containing CAP priority config info.
1.3.6.1.4.1.21317.1.3.2.3.2.1.7.1.1ColumncapPriorityConfigOutletread-writecurrentDisplay or set the CAP Priority of outlet. Priority 0 means this outlet does not support this OID. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.2.2Nodebank
1.3.6.1.4.1.21317.1.3.2.3.2.2.1TablebankStatusTablenot-accessiblecurrentBank status table.
1.3.6.1.4.1.21317.1.3.2.3.2.2.1.1RowbankStatusEntrynot-accessiblecurrentSingle entry containing bank status info.
1.3.6.1.4.1.21317.1.3.2.3.2.2.1.1.1ColumnbankIdnot-accessiblecurrentBank ID.
1.3.6.1.4.1.21317.1.3.2.3.2.2.1.1.2ColumnbankStatusRatedCurread-onlycurrentThe Bank Max Current value. unit: (0.1mA). If the station does not support this OID, it returns value -2000000. If the station is not available, it returns val…
1.3.6.1.4.1.21317.1.3.2.3.2.2.1.1.3ColumnbankStatusAttachStatusread-onlycurrentThe bank attached status. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.2.2.1.1.4ColumnbankStatusBreakerStatusread-onlycurrentThe breaker status. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.2.2.1.1.5ColumnbankStatusPhaseLayoutread-onlycurrentDisplay the phase layout of bank. Example: range 1 ~ 3 represents Line1-LineNeutral ~ Line3-lineNeutral. 4 ~ 6 represents Line1-Line2, Line2-Line3, Line3-Line1…
1.3.6.1.4.1.21317.1.3.2.3.2.2.2TablebankConfigTablenot-accessiblecurrentBank config table.
1.3.6.1.4.1.21317.1.3.2.3.2.2.2.1RowbankConfigEntrynot-accessiblecurrentSingle entry containing bank config info.
1.3.6.1.4.1.21317.1.3.2.3.2.2.2.1.1ColumnbankConfigNameread-writecurrentDisplay or set the name of the bank. When this model does not support the OID, we show n/a. string length: 0~15 If the station is not available, it returns 'st…
1.3.6.1.4.1.21317.1.3.2.3.2.2.2.1.2ColumnbankConfigMinCurThreshread-writecurrentDisplay or set the bank minimum electric current measurement threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller t…
1.3.6.1.4.1.21317.1.3.2.3.2.2.2.1.3ColumnbankConfigMaxCurThreshread-writecurrentDisplay or set the bank maximum electric current measurement threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller t…
1.3.6.1.4.1.21317.1.3.2.3.2.2.2.1.4ColumnbankConfigMinVolThreshread-writecurrentDisplay or set the bank minimum voltage measurement threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than …
1.3.6.1.4.1.21317.1.3.2.3.2.2.2.1.5ColumnbankConfigMaxVolThreshread-writecurrentDisplay or set the bank maximum voltage measurement threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than …
1.3.6.1.4.1.21317.1.3.2.3.2.2.2.1.6ColumnbankConfigMinPowerThreshread-writecurrentDisplay or set the bank minimum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than ma…
1.3.6.1.4.1.21317.1.3.2.3.2.2.2.1.7ColumnbankConfigMaxPowerThreshread-writecurrentDisplay or set the bank maximum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than ma…
1.3.6.1.4.1.21317.1.3.2.3.2.2.2.1.8ColumnbankConfigMaxPDThreshread-writecurrentDisplay or set the bank maximum power dissipation measurement threshold. Example: range 0.0 ~ 99999.0 represents 0~999990 NOTICE: Minimum threshold should be s…
1.3.6.1.4.1.21317.1.3.2.3.2.2.3TablebankControlTablenot-accessiblecurrentBank control table.
1.3.6.1.4.1.21317.1.3.2.3.2.2.3.1RowbankControlEntrynot-accessiblecurrentSingle entry containing bank control info.
1.3.6.1.4.1.21317.1.3.2.3.2.2.3.1.1ColumnbankControlOperationread-writecurrentThis function is used for outlet control of bank. Set off(1) to turn off for outlet control of bank. Set on(2) to turn on for all outlet control of bank. Set r…
1.3.6.1.4.1.21317.1.3.2.3.2.2.4TablebankReadingTablenot-accessiblecurrentBank reading table.
1.3.6.1.4.1.21317.1.3.2.3.2.2.4.1RowbankReadingEntrynot-accessiblecurrentSingle entry containing bank reading info.
1.3.6.1.4.1.21317.1.3.2.3.2.2.4.1.1ColumnbankReadingCurread-onlycurrentBank electric current value. This value indicates that 10,000 times. If this measurement value is not available, it returns value -1000000. If the station does…
1.3.6.1.4.1.21317.1.3.2.3.2.2.4.1.2ColumnbankReadingVolread-onlycurrentBank voltage value. This value indicates that 10,000 times. If this measurement value is not available, it returns value -1000000. If the station does not supp…
1.3.6.1.4.1.21317.1.3.2.3.2.2.4.1.3ColumnbankReadingPowerread-onlycurrentBank power value. This value indicates that 10,000 times. If this measurement value is not available, it returns value -1000000. If the station does not suppor…
1.3.6.1.4.1.21317.1.3.2.3.2.2.4.1.4ColumnbankReadingPDread-onlycurrentBank power dissipation value. This value indicates that 10,000 times. If this measurement value is not available, it returns value -1000000. If the station doe…
1.3.6.1.4.1.21317.1.3.2.3.2.2.4.1.5ColumnbankReadingPFread-onlycurrentBank power Factor value. This value indicates that 100 times. If the station does not support this OID, it returns value -2000000. If the station is not availa…
1.3.6.1.4.1.21317.1.3.2.3.2.3Nodeoutlet
1.3.6.1.4.1.21317.1.3.2.3.2.3.1TableoutletStatusTablenot-accessiblecurrentOutlet status table.
1.3.6.1.4.1.21317.1.3.2.3.2.3.1.1RowoutletStatusEntrynot-accessiblecurrentSingle entry containing outlet status info.
1.3.6.1.4.1.21317.1.3.2.3.2.3.1.1.1ColumnoutletIdnot-accessiblecurrentOutlet ID.
1.3.6.1.4.1.21317.1.3.2.3.2.3.1.1.2ColumnoutletStatusRatedCurread-onlycurrentOutlet Max Current value. unit: (0.1mA). If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value…
1.3.6.1.4.1.21317.1.3.2.3.2.3.1.1.3ColumnoutletStatusSwitchableread-onlycurrentOutlet switchable. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.2.3.1.1.4ColumnoutletStatusAutoPingread-onlycurrentOutlet latest auto-ping result. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.2.3.1.1.5ColumnoutletStatusPhaseLayoutread-onlycurrentDisplay the phase layout of outlet. Example: range 1 ~ 3 represents Line1-LineNeutral ~ Line3-lineNeutral. 4 ~ 6 represents Line1-Line2, Line2-Line3, Line3-Lin…
1.3.6.1.4.1.21317.1.3.2.3.2.3.2TableoutletConfigTablenot-accessiblecurrentOutlet config table.
1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1RowoutletConfigEntrynot-accessiblecurrentSingle entry containing outlet config info.
1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.1ColumnoutletConfigNameread-writecurrentDisplay or set the name of the outlet. If the station does not support this OID, we show n/a. string length: 0~48 If the station is not available, it returns '…
1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.2ColumnoutletConfigConfirmationEnread-writecurrentDisplay or set the confirmation of the outlet. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.3ColumnoutletConfigOnDelayTimeread-writecurrentDisplay or set the ON delay time of the outlet. When this model does not support the OID, we show value -1. If the station is not available, it returns value -…
1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.4ColumnoutletConfigOffDelayTimeread-writecurrentDisplay or set the OFF delay time of the outlet. When this model does not support the OID, we show value -1. If the station is not available, it returns value …
1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.5ColumnoutletConfigShutdownMethodread-writecurrentDisplay or set the shutdown method of the outlet. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.6ColumnoutletConfigMACread-writecurrentDisplay or set the MAC address of shutdown method. The value is hex format with length 12. If the station does not support this OID, it return '00-00-00-00-00-…
1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.7ColumnoutletConfigLocalAccessLockread-writecurrentDisplay or set whether the local access of the outlet is locked by remote or not. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.8ColumnoutletConfigMinCurThreshread-writecurrentDisplay or set the outlet minimum electric current measurement threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller…
1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.9ColumnoutletConfigMaxCurThreshread-writecurrentDisplay or set the outlet maximum electric current measurement threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller…
1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.10ColumnoutletConfigMinVolThreshread-writecurrentDisplay or set the outlet minimum voltage measurement threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller tha…
1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.11ColumnoutletConfigMaxVolThreshread-writecurrentDisplay or set the outlet maximum voltage measurement threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller tha…
1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.12ColumnoutletConfigMinPowerThreshread-writecurrentDisplay or set the outlet minimum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than …
1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.13ColumnoutletConfigMaxPowerThreshread-writecurrentDisplay or set the outlet maximum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than …
1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.14ColumnoutletConfigMaxPDThreshread-writecurrentDisplay or set the outlet maximum power dissipation measurement threshold. Example: range 0.0 ~ 99999.0 represents 0~999990 NOTICE: Minimum threshold should be…
1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.15ColumnoutletConfigAutoPingContFailTimesread-writecurrentDisplay or set the outlet auto-ping continuously-failed time to reset outlet. Example: range 0 ~ 5 Empty value: -3000. If the station does not support this OID…
1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.16ColumnoutletConfigAutoPingIntervalSecread-writecurrentDisplay or set the outlet auto-ping pinging interval in seconds. Example: range 10 ~ 600 Empty value: -3000. If the station does not support this OID, it retur…
1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.17ColumnoutletConfigAutoPingRetryTimesread-writecurrentDisplay or set the outlet auto-ping max retry times. Example: range 0 ~ 5 Empty value: -3000. If the station does not support this OID, it returns value -20000…
1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.18ColumnoutletConfigAutoPingPowerUpDelaySecread-writecurrentDisplay or set the outlet auto-ping first-ping-delay in seconds after outlet switches on. Example: range 10 ~ 600 Empty value: -3000. If the station does not s…
1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.19ColumnoutletConfigAutoPingRemoteIPAddrread-writecurrentOutlet auto-ping destination IP address. If the station does not support this OID, it returns value '0.0.0.0'. If the station is not available, it returns '0.0…
1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.20ColumnoutletConfigAutoPingEnableread-writecurrentDisplay or set the outlet auto-ping enable state. If the station does not support this OID, it returns value -2000000. If the station is not available, it retu…
1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.21ColumnoutletConfigAutoPingEnableRebootread-writecurrentDisplay or set the outlet auto-ping reboot enable state. If the station does not support this OID, it returns value -2000000. If the station is not available, …
1.3.6.1.4.1.21317.1.3.2.3.2.3.3TableoutletControlTablenot-accessiblecurrentOutlet control table.
1.3.6.1.4.1.21317.1.3.2.3.2.3.3.1RowoutletControlEntrynot-accessiblecurrentSingle entry containing outlet control info.
1.3.6.1.4.1.21317.1.3.2.3.2.3.3.1.1ColumnoutletControlOperationread-writecurrentThis function is used for the outlet control. Set off(1) to turn off the outlet. Set on(2) to turn on the outlet. Set reboot(3) to reboot the outlet. pending(3…
1.3.6.1.4.1.21317.1.3.2.3.2.3.4TableoutletReadingTablenot-accessiblecurrentOutlet reading table.
1.3.6.1.4.1.21317.1.3.2.3.2.3.4.1RowoutletReadingEntrynot-accessiblecurrentSingle entry containing outlet reading info.
1.3.6.1.4.1.21317.1.3.2.3.2.3.4.1.1ColumnoutletReadingCurread-onlycurrentOutlet electric current value. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is n…
1.3.6.1.4.1.21317.1.3.2.3.2.3.4.1.2ColumnoutletReadingVolread-onlycurrentOutlet voltage value. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is not availa…
1.3.6.1.4.1.21317.1.3.2.3.2.3.4.1.3ColumnoutletReadingPowerread-onlycurrentOutlet power value. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is not availabl…
1.3.6.1.4.1.21317.1.3.2.3.2.3.4.1.4ColumnoutletReadingPDread-onlycurrentOutlet power dissipation value. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is …
1.3.6.1.4.1.21317.1.3.2.3.2.3.4.1.5ColumnoutletReadingPFread-onlycurrentOutlet Power Factor value. This value indicates that 100 times. If the station does not support this OID, it returns value -2000000. If the station is not avai…
1.3.6.1.4.1.21317.1.3.2.3.2.3.5TableoutletAutoPingIpTablenot-accessiblecurrentOutlet auto-ping table.
1.3.6.1.4.1.21317.1.3.2.3.2.3.5.1RowoutletAutoPingIpEntrynot-accessiblecurrentSingle entry containing outlet auto-ping ip info.
1.3.6.1.4.1.21317.1.3.2.3.2.3.5.1.1ColumnoutletConfigAutoPingRemoteIPTyperead-onlycurrentRepresents the type of the corresponding instance of outletConfigAutoPingRemoteIP object. If the station does not support this OID, it returns value -2000000. …
1.3.6.1.4.1.21317.1.3.2.3.2.3.5.1.2ColumnoutletConfigAutoPingRemoteIPread-writecurrentOutlet auto-ping destination IP address. If the station does not support this OID, it returns value '0.0.0.0'. If the station is not available, it returns '0.0…
1.3.6.1.4.1.21317.1.3.2.3.2.4Nodeline
1.3.6.1.4.1.21317.1.3.2.3.2.4.1TablelineStatusTablenot-accessiblecurrentLine status table.
1.3.6.1.4.1.21317.1.3.2.3.2.4.1.1RowlineStatusEntrynot-accessiblecurrentSingle entry containing line status info.
1.3.6.1.4.1.21317.1.3.2.3.2.4.1.1.1ColumnlineIdnot-accessiblecurrentLine ID.
1.3.6.1.4.1.21317.1.3.2.3.2.4.1.1.2ColumnlineStatusRatedCurread-onlycurrentThe Max Line Current value. unit: (0.1mA) If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.2.4.2TablelineConfigTablenot-accessiblecurrentLine config table.
1.3.6.1.4.1.21317.1.3.2.3.2.4.2.1RowlineConfigEntrynot-accessiblecurrentSingle entry containing line config info.
1.3.6.1.4.1.21317.1.3.2.3.2.4.2.1.1ColumnlineConfigMinCurThreshread-writecurrentDisplay or set the line Minimum current measurement threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller than maxim…
1.3.6.1.4.1.21317.1.3.2.3.2.4.2.1.2ColumnlineConfigMaxCurThreshread-writecurrentDisplay or set the line Maximum electric current measurement threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller t…
1.3.6.1.4.1.21317.1.3.2.3.2.4.2.1.3ColumnlineConfigMinVolThreshread-writecurrentDisplay or set the line minimum voltage measurement threshold. Example: range 90.0 ~380.0 represents 900~3800 NOTICE: Minimum threshold should be smaller than …
1.3.6.1.4.1.21317.1.3.2.3.2.4.2.1.4ColumnlineConfigMaxVolThreshread-writecurrentDisplay or set the line maximum voltage measurement threshold. Example: range 90.0 ~380.0 represents 900~3800 NOTICE: Minimum threshold should be smaller than …
1.3.6.1.4.1.21317.1.3.2.3.2.4.2.1.5ColumnlineConfigMinPowerThreshread-writecurrentDisplay or set the line minimum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than ma…
1.3.6.1.4.1.21317.1.3.2.3.2.4.2.1.6ColumnlineConfigMaxPowerThreshread-writecurrentDisplay or set the line maximum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than ma…
1.3.6.1.4.1.21317.1.3.2.3.2.4.3TablelineReadingTablenot-accessiblecurrentLine reading table.
1.3.6.1.4.1.21317.1.3.2.3.2.4.3.1RowlineReadingEntrynot-accessiblecurrentSingle entry containing line reading info.
1.3.6.1.4.1.21317.1.3.2.3.2.4.3.1.1ColumnlineReadingCurread-onlycurrentLine current value. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is not availabl…
1.3.6.1.4.1.21317.1.3.2.3.2.4.3.1.2ColumnlineReadingVolread-onlycurrentLine voltage value. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is not availabl…
1.3.6.1.4.1.21317.1.3.2.3.2.4.3.1.3ColumnlineReadingPowerread-onlycurrentLine power value. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is not available,…
1.3.6.1.4.1.21317.1.3.2.3.2.4.4TableneutralStatusTablenot-accessiblecurrentLine reading table.
1.3.6.1.4.1.21317.1.3.2.3.2.4.4.1RowneutralStatusEntrynot-accessiblecurrentSingle entry containing line reading info.
1.3.6.1.4.1.21317.1.3.2.3.2.4.4.1.1ColumnneutralStatusLeakageCurread-onlycurrentNeutral leakage current status. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.2.5Nodeinlet
1.3.6.1.4.1.21317.1.3.2.3.2.5.1TableinletStatusTablenot-accessiblecurrentInlet status table.
1.3.6.1.4.1.21317.1.3.2.3.2.5.1.1RowinletStatusEntrynot-accessiblecurrentSingle entry containing inlet status info.
1.3.6.1.4.1.21317.1.3.2.3.2.5.1.1.1ColumninletIdnot-accessiblecurrentLine ID.
1.3.6.1.4.1.21317.1.3.2.3.2.5.1.1.2ColumninletStatusRatedCurread-onlycurrentThe Inlet Max Current value. unit: (0.1mA). If device is phase wye, then means L1 or L2 or L3 current. If device is phase delta, then means L1L2 or L2L3 or L3L…
1.3.6.1.4.1.21317.1.3.2.3.2.5.2TableinletConfigTablenot-accessiblecurrentInlet config table.
1.3.6.1.4.1.21317.1.3.2.3.2.5.2.1RowinletConfigEntrynot-accessiblecurrentSingle entry containing inlet config info.
1.3.6.1.4.1.21317.1.3.2.3.2.5.2.1.1ColumninletConfigMinCurThreshread-writecurrentDisplay or set the inlet Minimum current measurement threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller than maxi…
1.3.6.1.4.1.21317.1.3.2.3.2.5.2.1.2ColumninletConfigMaxCurThreshread-writecurrentDisplay or set the inlet Maximum electric current measurement threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller …
1.3.6.1.4.1.21317.1.3.2.3.2.5.2.1.3ColumninletConfigMinVolThreshread-writecurrentDisplay or set the inlet minimum voltage measurement threshold. Example: range 90.0 ~380.0 represents 900~3800 NOTICE: Minimum threshold should be smaller than…
1.3.6.1.4.1.21317.1.3.2.3.2.5.2.1.4ColumninletConfigMaxVolThreshread-writecurrentDisplay or set the inlet maximum voltage measurement threshold. Example: range 90.0 ~380.0 represents 900~3800 NOTICE: Minimum threshold should be smaller than…
1.3.6.1.4.1.21317.1.3.2.3.2.5.2.1.5ColumninletConfigMinPowerThreshread-writecurrentDisplay or set the inlet minimum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than m…
1.3.6.1.4.1.21317.1.3.2.3.2.5.2.1.6ColumninletConfigMaxPowerThreshread-writecurrentDisplay or set the inlet maximum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than m…
1.3.6.1.4.1.21317.1.3.2.3.2.5.2.1.7ColumninletConfigMaxPDThreshread-writecurrentDisplay or set the inlet maximum power dissipation measurement threshold. Example: range 0.0 ~ 99999.0 represents 0~999990 NOTICE: Minimum threshold should be …
1.3.6.1.4.1.21317.1.3.2.3.2.5.3TableinletReadingTablenot-accessiblecurrentInlet reading table.
1.3.6.1.4.1.21317.1.3.2.3.2.5.3.1RowinletReadingEntrynot-accessiblecurrentSingle entry containing inlet reading info.
1.3.6.1.4.1.21317.1.3.2.3.2.5.3.1.1ColumninletReadingCurread-onlycurrentInlet current value. If device is phase wye, then means L1 or L2 or L3 current. If device is phase delta, then means L1L2 or L2L3 or L3L1 current. This value i…
1.3.6.1.4.1.21317.1.3.2.3.2.5.3.1.2ColumninletReadingVolread-onlycurrentInlet voltage value. If device is phase wye, then means L1 or L2 or L3 voltage. If device is phase delta, then means L1L2 or L2L3 or L3L1 voltage. This value i…
1.3.6.1.4.1.21317.1.3.2.3.2.5.3.1.3ColumninletReadingPowerread-onlycurrentInlet power value. If device is phase wye, then means L1 or L2 or L3 power. If device is phase delta, then means L1L2 or L2L3 or L3L1 power. This value indicat…
1.3.6.1.4.1.21317.1.3.2.3.2.5.3.1.4ColumninletReadingPDread-onlycurrentInlet power value. If device is phase wye, then means L1 or L2 or L3 power dissipation. If device is phase delta, then means L1L2 or L2L3 or L3L1 power dissipa…
1.3.6.1.4.1.21317.1.3.2.3.3Nodeenvironment
1.3.6.1.4.1.21317.1.3.2.3.3.1Nodesensor
1.3.6.1.4.1.21317.1.3.2.3.3.1.3TablesensorConfigTablenot-accessiblecurrentSensor config table. Use port/addr as indexes to access sensor configurations.
1.3.6.1.4.1.21317.1.3.2.3.3.1.3.1RowsensorConfigEntrynot-accessiblecurrentSingle entry containing sensor config info.
1.3.6.1.4.1.21317.1.3.2.3.3.1.3.1.1ColumnsensorPortnot-accessiblecurrentSensor Port Number.
1.3.6.1.4.1.21317.1.3.2.3.3.1.3.1.2ColumnsensorAddrnot-accessiblecurrentSensor Address.
1.3.6.1.4.1.21317.1.3.2.3.3.1.3.1.3ColumnsensorConfigMinTempThreshread-writecurrentDisplay or set sensor minimum temperature measurement threshold. Example: range -20.0 ~ 60.0 represents -200~600 NOTICE: Minimum threshold should be smaller th…
1.3.6.1.4.1.21317.1.3.2.3.3.1.3.1.4ColumnsensorConfigMaxTempThreshread-writecurrentDisplay or set sensor maximum temperature measurement threshold. Example: range -20.0 ~ 60.0 represents -200~600 NOTICE: Minimum threshold should be smaller th…
1.3.6.1.4.1.21317.1.3.2.3.3.1.3.1.5ColumnsensorConfigMinHumThreshread-writecurrentDisplay or set sensor minimum humidity measurement threshold. Example: range 10.0 ~ 95.0 represents 100~950 NOTICE: Minimum threshold should be smaller than ma…
1.3.6.1.4.1.21317.1.3.2.3.3.1.3.1.6ColumnsensorConfigMaxHumThreshread-writecurrentDisplay or set sensor maximum humidity measurement threshold. Example: range 10.0 ~ 95.0 represents 100~950 NOTICE: Minimum threshold should be smaller than ma…
1.3.6.1.4.1.21317.1.3.2.3.3.1.3.1.7ColumnsensorConfigMinPressThreshread-writecurrentDisplay or set sensor minimum pressure measurement threshold. Example: range -250.0 ~ 250.0 represents -2500 ~ 2500 NOTICE: Minimum threshold should be smaller…
1.3.6.1.4.1.21317.1.3.2.3.3.1.3.1.8ColumnsensorConfigMaxPressThreshread-writecurrentDisplay or set sensor maximum pressure measurement threshold. Example: range -250.0 ~ 250.0 represents -2500 ~ 2500 NOTICE: Minimum threshold should be smaller…
1.3.6.1.4.1.21317.1.3.2.3.3.1.4TablesensorReadingTablenot-accessiblecurrentSensor reading table. Use port/addr as indexes to access sensor readings.
1.3.6.1.4.1.21317.1.3.2.3.3.1.4.1RowsensorReadingEntrynot-accessiblecurrentSingle entry containing sensor reading info.
1.3.6.1.4.1.21317.1.3.2.3.3.1.4.1.1ColumnsensorReadingTempread-onlycurrentSensor's Temperature value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the station does n…
1.3.6.1.4.1.21317.1.3.2.3.3.1.4.1.2ColumnsensorReadingHumread-onlycurrentSensor's Humidity value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the station does not …
1.3.6.1.4.1.21317.1.3.2.3.3.1.4.1.3ColumnsensorReadingPressread-onlycurrentSensor's Pressure value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the station does not …
1.3.6.1.4.1.21317.1.3.2.3.3.2NodedryContact
1.3.6.1.4.1.21317.1.3.2.3.3.2.1TabledryContactStatusTablenot-accessiblecurrentDry contact status table.
1.3.6.1.4.1.21317.1.3.2.3.3.2.1.1RowdryContactStatusEntrynot-accessiblecurrentSingle entry containing dry contact status info.
1.3.6.1.4.1.21317.1.3.2.3.3.2.1.1.1ColumndryContactIdnot-accessiblecurrentDry contact ID.
1.3.6.1.4.1.21317.1.3.2.3.3.2.1.1.2ColumndryContactStatusread-onlycurrentDisplay dry contact status. close(0) represents door close. open(1) represents door open. not-attached(2) represents door sensor don't attach to device. If the…
1.3.6.1.4.1.21317.1.3.2.3.3.2.2TabledryContactConfigTablenot-accessiblecurrentDry contact config table.
1.3.6.1.4.1.21317.1.3.2.3.3.2.2.1RowdryContactConfigEntrynot-accessiblecurrentSingle entry containing dry contact config info.
1.3.6.1.4.1.21317.1.3.2.3.3.2.2.1.1ColumndryContactConfigTyperead-writecurrentDisplay or set dry contact type. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.4Nodenetwork
1.3.6.1.4.1.21317.1.3.2.3.4.1TablenetStatusTablenot-accessiblecurrentNet status table.
1.3.6.1.4.1.21317.1.3.2.3.4.1.1RownetStatusEntrynot-accessiblecurrentSingle entry containing net status info.
1.3.6.1.4.1.21317.1.3.2.3.4.1.1.1ColumnnetStatusMACread-onlycurrentStation MAC address. The value is hex format with length 12. If the station does not support this OID, it return '00-00-00-00-00-00'. If the station is not ava…
1.3.6.1.4.1.21317.1.3.2.3.4.2TablehttpConfigTablenot-accessiblecurrentHTTP config table.
1.3.6.1.4.1.21317.1.3.2.3.4.2.1RowhttpConfigEntrynot-accessiblecurrentSingle entry containing HTTP config info.
1.3.6.1.4.1.21317.1.3.2.3.4.2.1.1ColumnhttpConfigHttpPortread-writecurrentDisplay or set the HTTP port of the station. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.4.2.1.2ColumnhttpConfigHttpsPortread-writecurrentDisplay or set the HTTPs port of the station. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.4.2.1.3ColumnhttpConfigHttpsOnlyEnread-writecurrentDisplay or set whether to use HTTPS only or HTTP/HTTPS for the web page. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.4.3TablenetConfigTablenot-accessiblecurrentNet config table.
1.3.6.1.4.1.21317.1.3.2.3.4.3.1RownetConfigEntrynot-accessiblecurrentSingle entry containing net config info.
1.3.6.1.4.1.21317.1.3.2.3.4.3.1.1ColumnnetCablePortnot-accessiblecurrentNetwork Port Number.
1.3.6.1.4.1.21317.1.3.2.3.4.3.1.2ColumnnetConfigAutoIPread-writecurrentDisplay or set IPv4 address automatically or not
1.3.6.1.4.1.21317.1.3.2.3.4.3.1.3ColumnnetConfigIPv4read-writecurrentDisplay or set fixed IPv4 address
1.3.6.1.4.1.21317.1.3.2.3.4.3.1.4ColumnnetConfigSubMaskread-writecurrentDisplay or set subnet mask address
1.3.6.1.4.1.21317.1.3.2.3.4.3.1.5ColumnnetConfigGatewayread-writecurrentDisplay or set gateway address
1.3.6.1.4.1.21317.1.3.2.3.4.3.1.6ColumnnetConfigAutoDNSread-writecurrentDisplay or set DNS address automatically or not
1.3.6.1.4.1.21317.1.3.2.3.4.3.1.7ColumnnetConfigPreferDNSIPv4read-writecurrentDisplay or set prefer DNS address
1.3.6.1.4.1.21317.1.3.2.3.4.3.1.8ColumnnetConfigAlterDNSIPv4read-writecurrentDisplay or set alternate DNS address
1.3.6.1.4.1.21317.1.3.2.3.5Nodeevent
1.3.6.1.4.1.21317.1.3.2.3.5.1Nodetrap
1.3.6.1.4.1.21317.1.3.2.3.5.1.1TabletrapConfigTablenot-accessiblecurrentTrap config table.
1.3.6.1.4.1.21317.1.3.2.3.5.1.1.1RowtrapConfigEntrynot-accessiblecurrentSingle entry containing trap config info.
1.3.6.1.4.1.21317.1.3.2.3.5.1.1.1.1ColumntrapConfigEnread-writecurrentDisplay or set whether this trap entry is enabled or not. You should set the username/auth-password/priv-password first, when choosing snmpv3. You should set t…
1.3.6.1.4.1.21317.1.3.2.3.5.1.1.1.2ColumntrapConfigVerread-writecurrentDisplay or set SNMP trap version for sending trap. You should set the username/auth-password/priv-password first, when choosing snmpv3. You should set the comm…
1.3.6.1.4.1.21317.1.3.2.3.5.1.2TabletrapReceiverConfigTablenot-accessiblecurrentSNMP agent trap setup table. If users want to use trap, they must set enable trap, IP and community first.
1.3.6.1.4.1.21317.1.3.2.3.5.1.2.1RowtrapReceiverConfigEntrynot-accessiblecurrentSingle entry containing trap receiver config info.
1.3.6.1.4.1.21317.1.3.2.3.5.1.2.1.1ColumntrapReceiverConfigIdxnot-accessiblecurrentIndex of trap receiver.
1.3.6.1.4.1.21317.1.3.2.3.5.1.2.1.2ColumntrapReceiverConfigIpread-writecurrentTrap receiver IP address. If the station does not support this OID, it returns value '0.0.0.0'. If the station is not available, it returns '0.0.0.0'.
1.3.6.1.4.1.21317.1.3.2.3.5.1.2.1.3ColumntrapReceiverConfigPortread-writecurrentNMS trap port to be used by agent to send trap. If the station does not support this OID, it returns value -2000000. If the station is not available, it return…
1.3.6.1.4.1.21317.1.3.2.3.5.1.2.1.4ColumntrapReceiverConfigCommunityread-writecurrentIf use SNMPv1/v2c to receive trap should set this community string. MAX string length: 20 If the station does not support this OID, it returns value 'not-suppo…
1.3.6.1.4.1.21317.1.3.2.3.5.1.2.1.5ColumntrapReceiverConfigUsernameread-writecurrentIf use SNMPv3 to receive trap should set this username string. MAX string length: 20. If the station does not support this OID, it returns value 'not-support'.…
1.3.6.1.4.1.21317.1.3.2.3.5.1.2.1.6ColumntrapReceiverConfigAuthPwdread-writecurrentIf use SNMPv3 to receive trap should set this auth password string. MAX string length: 20 If the station does not support this OID, it returns value 'not-suppo…
1.3.6.1.4.1.21317.1.3.2.3.5.1.2.1.7ColumntrapReceiverConfigPrivacyPwdread-writecurrentIf use SNMPv3 to receive trap should set this privacy password string. MAX string length: 20 If the station does not support this OID, it returns value 'not-su…
1.3.6.1.4.1.21317.1.3.2.3.5.1.3TabletrapReceiverIpTablenot-accessiblecurrentTrap Receiver Ip table.
1.3.6.1.4.1.21317.1.3.2.3.5.1.3.1RowtrapReceiverIpEntrynot-accessiblecurrentSingle entry containing trap receiver ip info.
1.3.6.1.4.1.21317.1.3.2.3.5.1.3.1.1ColumntrapReceiverIpIdxnot-accessiblecurrentIndex of trap receiver.
1.3.6.1.4.1.21317.1.3.2.3.5.1.3.1.2ColumntrapReceiverIpTyperead-onlycurrentRepresents the type of the corresponding instance of trapReceiverIp object. If the station does not support this OID, it returns value -2000000. If the station…
1.3.6.1.4.1.21317.1.3.2.3.5.1.3.1.3ColumntrapReceiverIpread-writecurrentOutlet auto-ping destination IP address. If the station does not support this OID, it returns value '0.0.0.0'. If the station is not available, it returns '0.0…
1.3.6.1.4.1.21317.1.3.2.3.50NodetrapNotification
1.3.6.1.4.1.21317.1.3.2.3.50.1TabletrapNotifConfigTablenot-accessiblecurrentTrap notification config table.
1.3.6.1.4.1.21317.1.3.2.3.50.1.1RowtrapNotifConfigEntrynot-accessiblecurrentSingle entry containing trap notification config info.
1.3.6.1.4.1.21317.1.3.2.3.50.1.1.1ColumntrapNotifConfigEnread-writecurrentDisplay or set whether this trap entry is enabled or not. You should set the username/auth-password/priv-password first, when choosing snmpv3. You should set t…
1.3.6.1.4.1.21317.1.3.2.3.50.2TabletrapNotifAlarmTablenot-accessiblecurrentTrap notification alarm table.
1.3.6.1.4.1.21317.1.3.2.3.50.2.1RowtrapNotifAlarmEntrynot-accessiblecurrentSingle entry containing trap notification alarm info.
1.3.6.1.4.1.21317.1.3.2.3.50.2.1.1ColumntrapNotifAlarmBreakerStatusread-onlycurrentStation breaker alarm status. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.50.2.1.2ColumntrapNotifAlarmCurrentStatusread-onlycurrentStation current alarm status. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.50.2.1.3ColumntrapNotifAlarmVoltageStatusread-onlycurrentStation voltage alarm status. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.50.2.1.4ColumntrapNotifAlarmPowerStatusread-onlycurrentStation power alarm status. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.50.2.1.5ColumntrapNotifAlarmSensorStatusread-onlycurrentStation sensor alarm status. If the station is not available, it returns value -3000000.
1.3.6.1.4.1.21317.1.3.2.3.50.3NotificationtrapNotifEventcurrentDisplay trap notification alarm status.
1.3.6.1.4.1.21317.1.3.2.3.150NodedeviceLock
1.3.6.1.4.1.21317.1.3.2.3.150.1ScalarstaCommunityLockread-writecurrentChange SNMPV1 or SNMPV2 community for California passes law. Please follow the format as readcommunity||writecommunity
1.3.6.1.4.1.21317.1.3.2.3.150.2ScalarstaPasswordLockread-writecurrentChange SNMPV3 password for California passes law. Please follow the format as authpassword||privpassword