Argus-Power-System-MIB

83 objects
This MIB defines the information block(s) available in CXC RMU as defined by the following list: - upsDevice: the CXC-series of controllers
Imported Objects
SNMPv2-SMIenterprises MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE
OIDNameAccessStatusDescription
1.3.6.1.4.1.7309IdentityargusThis MIB defines the information block(s) available in CXC RMU as defined by the following list: - upsDevice: the CXC-series of controllers
1.3.6.1.4.1.7309.6NodeupsPower
1.3.6.1.4.1.7309.6.1NodeupsDevice
1.3.6.1.4.1.7309.6.1.1NodeupsIdent
1.3.6.1.4.1.7309.6.1.1.1ScalarupsIdentManufacturerread-onlycurrentThe name of the UPS manufacturer.
1.3.6.1.4.1.7309.6.1.1.2ScalarupsIdentProductCoderead-onlycurrentThe UPS Model designation.
1.3.6.1.4.1.7309.6.1.1.3ScalarupsIdentModelread-onlycurrentThe UPS Product code designation.
1.3.6.1.4.1.7309.6.1.1.4ScalarupsIdentUPSSoftwareVersionread-onlycurrentThe UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.
1.3.6.1.4.1.7309.6.1.1.5ScalarupsIdentAgentSoftwareVersionread-onlycurrentThe UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.
1.3.6.1.4.1.7309.6.1.1.6ScalarupsIdentNameread-onlycurrentA string identifying the UPS. This object should be set by the administrator.
1.3.6.1.4.1.7309.6.1.1.7ScalarupsIdentAttachedDevicesread-onlycurrentA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.
1.3.6.1.4.1.7309.6.1.1.8ScalarupsIdentSiteNameread-writecurrentSite Name
1.3.6.1.4.1.7309.6.1.1.9ScalarupsIdentSiteCityread-writecurrentSite City
1.3.6.1.4.1.7309.6.1.1.10ScalarupsIdentSiteRegionread-writecurrentSite Region
1.3.6.1.4.1.7309.6.1.1.11ScalarupsIdentSiteCountryread-writecurrentSite Country
1.3.6.1.4.1.7309.6.1.1.12ScalarupsIdentContactNameread-writecurrentContact Name
1.3.6.1.4.1.7309.6.1.1.13ScalarupsIdentPhoneNumberread-writecurrentPhone Number
1.3.6.1.4.1.7309.6.1.1.14ScalarupsIdentDateread-writecurrentDate of the RMU-Novus
1.3.6.1.4.1.7309.6.1.1.15ScalarupsIdentTimeread-writecurrentTime of the RMU-Novus
1.3.6.1.4.1.7309.6.1.2NodeupsBattery
1.3.6.1.4.1.7309.6.1.2.1ScalarupsBatteryStatusread-onlycurrentThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfi…
1.3.6.1.4.1.7309.6.1.2.2ScalarupsMinutesOnBatteryread-onlycurrentThe accumulated elapsed time that the UPS system have been on battery.
1.3.6.1.4.1.7309.6.1.2.3ScalarupsBatteryVoltageread-onlycurrentThe magnitude of the present battery voltage.
1.3.6.1.4.1.7309.6.1.2.4ScalarupsBatteryChargingCurrentread-onlycurrentThe present battery charging current.
1.3.6.1.4.1.7309.6.1.2.5ScalarupsBatteryCapacityread-onlycurrentThe present battery capacity.
1.3.6.1.4.1.7309.6.1.2.6ScalarupsBatteryTemperatureread-onlycurrentThe ambient temperature at or near the UPS Battery casing.
1.3.6.1.4.1.7309.6.1.2.7ScalarupsBatteryLowWarningread-writecurrentThe set battery capacity percentage at which the unit will raise an alarm.
1.3.6.1.4.1.7309.6.1.3NodeupsInput
1.3.6.1.4.1.7309.6.1.3.1ScalarupsInputNumLinesread-onlycurrentThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.
1.3.6.1.4.1.7309.6.1.3.2TableupsInputTablenot-accessiblecurrentA list of input table entries. The number of entries is given by the value of upsInputNumLines.
1.3.6.1.4.1.7309.6.1.3.2.1RowupsInputEntrynot-accessiblecurrentAn entry containing information applicable to a particular input line.
1.3.6.1.4.1.7309.6.1.3.2.1.1ColumnupsInputLineIndexnot-accessiblecurrentThe input line identifier.
1.3.6.1.4.1.7309.6.1.3.2.1.2ColumnupsInputFrequencyread-onlycurrentThe present input frequency.
1.3.6.1.4.1.7309.6.1.3.2.1.3ColumnupsInputVoltageread-onlycurrentThe magnitude of the present input voltage.
1.3.6.1.4.1.7309.6.1.4NodeupsOutput
1.3.6.1.4.1.7309.6.1.4.1ScalarupsOutputSourceread-onlycurrentThe present source of output power. The enumeration line(2) indicates that the Novus is in line mode.
1.3.6.1.4.1.7309.6.1.4.2ScalarupsOutputFrequencyread-onlycurrentThe present output frequency.
1.3.6.1.4.1.7309.6.1.4.3ScalarupsOutputNumLinesread-onlycurrentThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.
1.3.6.1.4.1.7309.6.1.4.4TableupsOutputTablenot-accessiblecurrentA list of output table entries. The number of entries is given by the value of upsOutputNumLines.
1.3.6.1.4.1.7309.6.1.4.4.1RowupsOutputEntrynot-accessiblecurrentAn entry containing information applicable to a particular output line.
1.3.6.1.4.1.7309.6.1.4.4.1.1ColumnupsOutputLineIndexnot-accessiblecurrentThe output line identifier.
1.3.6.1.4.1.7309.6.1.4.4.1.2ColumnupsOutputVoltageread-onlycurrentThe present output voltage.
1.3.6.1.4.1.7309.6.1.4.4.1.3ColumnupsOutputCurrentread-onlycurrentThe present output current.
1.3.6.1.4.1.7309.6.1.4.4.1.4ColumnupsOutputPowerVAread-onlycurrentThe present output VA.
1.3.6.1.4.1.7309.6.1.4.4.1.5ColumnupsOutputPowerWattread-onlycurrentThe present output true power.
1.3.6.1.4.1.7309.6.1.4.4.1.6ColumnupsPowerFactorread-onlycurrentThe present power factor.
1.3.6.1.4.1.7309.6.1.4.4.1.7ColumnupsOutputPercentLoadread-onlycurrentThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent…
1.3.6.1.4.1.7309.6.1.5NodeupsAlarm
1.3.6.1.4.1.7309.6.1.5.1ScalarupsAlarmsPresentread-onlycurrentThe present number of active alarm conditions.
1.3.6.1.4.1.7309.6.1.5.2TableupsAlarmTablenot-accessiblecurrentA list of alarm table entries.
1.3.6.1.4.1.7309.6.1.5.2.1RowupsAlarmEntrynot-accessiblecurrentAn entry containing information applicable to a particular alarm.
1.3.6.1.4.1.7309.6.1.5.2.1.1ColumnupsAlarmIdnot-accessiblecurrentA unique identifier for an alarm condition. This value must remain constant.
1.3.6.1.4.1.7309.6.1.5.2.1.2ColumnupsAlarmDescrread-onlycurrentA unique description of the alarm.
1.3.6.1.4.1.7309.6.1.5.2.1.3ColumnupsAlarmStatusread-onlycurrent1 - ON or 0 - OFF.
1.3.6.1.4.1.7309.6.1.6NodeupsConfig
1.3.6.1.4.1.7309.6.1.6.1ScalarupsConfigLineQualifyTimeread-onlycurrentThis objects displays the line qualify time.
1.3.6.1.4.1.7309.6.1.6.2ScalarupsConfigLineOutputVoltageHighLimitread-onlycurrentThis object represents the Line output High Voltage Limit.
1.3.6.1.4.1.7309.6.1.6.3ScalarupsConfigLineOutputVoltageLowLimitread-onlycurrentThis object represents the Line output Low Voltage Limit.
1.3.6.1.4.1.7309.6.1.6.4ScalarupsConfigFanOnTemperatureread-onlycurrentThis object represents the Fan on temperature.
1.3.6.1.4.1.7309.6.1.6.5ScalarupsShutdownStatusread-writecurrentThis object tells us if output is disabled or enabled.
1.3.6.1.4.1.7309.6.1.6.6ScalarupsInverterOffDelayTimeread-writecurrentThis object represents the inverter off delay time.
1.3.6.1.4.1.7309.6.1.6.7ScalarupsConfigIPAddressread-writecurrentThis objects displays the IP address of the RMU.
1.3.6.1.4.1.7309.6.1.6.8ScalarupsConfigNetMaskread-writecurrentThis object displays the Net Mask of the RMU.
1.3.6.1.4.1.7309.6.1.6.9ScalarupsConfigGatewayread-writecurrentThis object displays the Gateway of the RMU.
1.3.6.1.4.1.7309.6.1.6.10ScalarupsConfigSnmpCommunityread-writecurrentThis object displays the SNMP community
1.3.6.1.4.1.7309.6.1.6.11ScalarupsConfigSnmpTrapIPDestinationread-writecurrentThis object displays the SNMP Trap IP destination.
1.3.6.1.4.1.7309.6.1.7NodeupsTraps
1.3.6.1.4.1.7309.6.1.7.0NodeupsTrap
1.3.6.1.4.1.7309.6.1.7.0.1NotificationupsAlarmTrapcurrentA trap issued from a change in state in one of the Alarms on the Novus controller
1.3.6.1.4.1.7309.6.1.7.0.2NotificationupsAgentStartupTrapcurrentA trap to indicate that the agent software has started up.
1.3.6.1.4.1.7309.6.1.7.0.3NotificationupsAgentShutdownTrapcurrentA trap to indicate that the agent software has shutdown.
1.3.6.1.4.1.7309.6.1.7.0.4NotificationupsAgentFaultTrapcurrentA trap issued from a change in state in one of the Faults on the Novus controller
1.3.6.1.4.1.7309.6.1.7.0.5NotificationupsAgentEventTrapcurrentA trap issued from a change in state in one of the Events on the Novus controller
1.3.6.1.4.1.7309.6.1.8NodeupsExtra
1.3.6.1.4.1.7309.6.1.8.1ScalarupsExtraCountread-onlycurrentNumber of extra variables
1.3.6.1.4.1.7309.6.1.8.2TableupsExtraTablenot-accessiblecurrentA table of CXC upstem controller extra variables
1.3.6.1.4.1.7309.6.1.8.2.1RowupsExtraEntrynot-accessiblecurrentAn entry into the CXC upstem controller extra variable table
1.3.6.1.4.1.7309.6.1.8.2.1.1ColumnupsExtraIndexread-onlycurrentThe index of the extra variable in the CXC upstem controller table
1.3.6.1.4.1.7309.6.1.8.2.1.2ColumnupsExtraNameread-onlycurrentThe description of the extra variable as reported by the CXC upstem controller
1.3.6.1.4.1.7309.6.1.8.2.1.3ColumnupsExtraIntegerValueread-onlycurrentThe integer value of the extra variable as reported by the CXC upstem controller
1.3.6.1.4.1.7309.6.1.8.2.1.4ColumnupsExtraStringValueread-onlycurrentThe string value of the extra variable as reported by the CXC upstem controller
Type Definitions
NameSyntaxStatusDescription
NonNegativeIntegerINTEGER (0..2147483647) DisplayString ::= OCTET STRING PhysAddress ::= OCTET STRINGcurrentThis data type is a non-negative value.
PositiveIntegerINTEGER (1..2147483647)currentThis data type is a non-zero and non-negative value.