BDFB-MIB

42 objects
Emerson Energy Systems North America(ESNA) mini-BDFB MIB. revision 1.0.0.0
Imported Objects
SNMPv2-CONFMODULE-COMPLIANCE NOTIFICATION-GROUP OBJECT-GROUP
SNMPv2-SMICounter32 enterprises Integer32 mib-2 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE
SNMPv2-TCDateAndTime DisplayString TEXTUAL-CONVENTION
OIDNameAccessStatusDescription
1.3.6.1.4.1.885NodeemersonESNA
1.3.6.1.4.1.885.5IdentitybdfbMIBEmerson Energy Systems North America(ESNA) mini-BDFB MIB. revision 1.0.0.0
1.3.6.1.4.1.885.5.1NodebdfbInformation
1.3.6.1.4.1.885.5.1.1ScalarbdfbMeterPanelVersionNumberread-onlycurrentMeter Panel Firmware Version Number.
1.3.6.1.4.1.885.5.1.2ScalarbdfbEthernetCardVersionNumberread-onlycurrentEthernet Card Firmware Version Number.
1.3.6.1.4.1.885.5.1.3ScalarbdfbIdentifierread-onlycurrentBDFB Identifier String.
1.3.6.1.4.1.885.5.2NodebdfbStatus
1.3.6.1.4.1.885.5.2.1NodebdfbMeasurement
1.3.6.1.4.1.885.5.2.1.1ScalarbdfbAverageBusVoltageread-onlycurrentAverage Bus Voltage.
1.3.6.1.4.1.885.5.2.1.2ScalarbdfbTotalBusCurrentread-onlycurrentTtotal Bus Current.
1.3.6.1.4.1.885.5.2.1.3ScalarbdfbAlarmread-onlycurrentAn Alarm Is Active.
1.3.6.1.4.1.885.5.2.2TablebdfbBusTablenot-accessiblecurrentBDFB Bus Table.
1.3.6.1.4.1.885.5.2.2.1RowbdfbBusEntrynot-accessiblecurrentBDFB Bus Table Entry.
1.3.6.1.4.1.885.5.2.2.1.1ColumnbdfbBusIndexread-onlycurrentBDFB Bus Number.
1.3.6.1.4.1.885.5.2.2.1.2ColumnbdfbBusIdentifierread-onlycurrentBDFB Bus Identifier.
1.3.6.1.4.1.885.5.2.2.1.3ColumnbdfbBusVoltageread-onlycurrentBDFB Bus Voltage.
1.3.6.1.4.1.885.5.2.2.1.4ColumnbdfbBusCurrentread-onlycurrentBDFB Bus Current.
1.3.6.1.4.1.885.5.2.3TablebdfbRelayTablenot-accessiblecurrentBDFB Relay Table.
1.3.6.1.4.1.885.5.2.3.1RowbdfbRelayEntrynot-accessiblecurrentBDFB Relay Table Entry.
1.3.6.1.4.1.885.5.2.3.1.1ColumnbdfbRelayIndexread-onlycurrentBDFB Relay Number.
1.3.6.1.4.1.885.5.2.3.1.2ColumnbdfbRelayIdentifierread-onlycurrentBDFB Relay Identifier String.
1.3.6.1.4.1.885.5.2.3.1.3ColumnbdfbRelayStatusread-onlycurrentBDFB Relay Status String.
1.3.6.1.4.1.885.5.3NodebdfbTraps
1.3.6.1.4.1.885.5.3.0NodebdfbSystemTraps
1.3.6.1.4.1.885.5.3.0.1NotificationalarmTrapBDFBRelay1currentBDFB Relay 1 Typically Configured as Major Remote.
1.3.6.1.4.1.885.5.3.0.2NotificationalarmTrapBDFBRelay2currentBDFB Relay 2 Typically Configured as Minor Remote.
1.3.6.1.4.1.885.5.3.0.3NotificationalarmTrapBDFBRelay3currentBDFB Relay 3 Typically Configured as Custom Remote.
1.3.6.1.4.1.885.5.3.0.4NotificationalarmTrapBDFBRelay4currentBDFB Relay 4 Typically Configured as Custom Remote.
1.3.6.1.4.1.885.5.3.0.5NotificationalarmTrapBDFBAuxABSFusecurrentAuxillary ABS Fuse Trap.
1.3.6.1.4.1.885.5.3.0.6NotificationalarmTrapBDFBCommFailcurrentCommunication failure between ethernet card and main board.
1.3.6.1.4.1.885.5.3.1NodebdfbBusTypeTraps
1.3.6.1.4.1.885.5.3.1.0NodebdfbBusTraps
1.3.6.1.4.1.885.5.3.1.0.2ScalartrapBusIdentifiernot-accessiblecurrentBus Identifier. This object cannot be accessed. It is used to clarify the source of a Bus trap
1.3.6.1.4.1.885.5.3.1.0.3NotificationtrapBDFBBusFusecurrentBDFB Bus Fuse Alarm.
1.3.6.1.4.1.885.5.3.1.0.4NotificationtrapBDFBBusLowVoltagecurrentBDFB Bus Low Voltage Alarm.
1.3.6.1.4.1.885.5.3.1.0.5NotificationtrapBDFBBusPowerLostcurrentBDFB Bus Power Lost Alarm.
1.3.6.1.4.1.885.5.3.1.0.6NotificationtrapBDFBBusHighCurrent1currentBDFB Bus High Current 1 Alarm.
1.3.6.1.4.1.885.5.3.1.0.7NotificationtrapBDFBBusHighCurrent2currentBDFB Bus High Current 2 Alarm.
1.3.6.1.4.1.885.5.4NodebdfbGroups
1.3.6.1.4.1.885.5.4.1GroupbdfbInformationGroupcurrentA collection of objects providing information to identify the BDFB plant and the version of monitoring software.
1.3.6.1.4.1.885.5.4.2GroupbdfbMeasurementGroupcurrentA collection of objects providing BDFB Plant measurements and status.
1.3.6.1.4.1.885.5.4.3GroupbdfbNotificationsGroupcurrentThe notifications which indicate BDFB Plant alarms.