BESTPOWER-MIB
245 objects
No module-level DESCRIPTION found.
Imported Objects
| RFC-1212 | OBJECT-TYPE |
| RFC-1215 | TRAP-TYPE |
| RFC1155-SMI | enterprises Gauge IpAddress |
| RFC1213-MIB | DisplayString |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.2947 | NodebestPower | |||
| 1.3.6.1.4.1.2947.1 | NodebestLink | |||
| 1.3.6.1.4.1.2947.1.1 | NodeupsIdent | |||
| 1.3.6.1.4.1.2947.1.1 | NodeupsTrapPowerFail | WARNING: Utility power not available. | ||
| 1.3.6.1.4.1.2947.1.1.1 | ScalarupsIdentUpsName | read-only | mandatory | An ID string identifying the Family of UPS. |
| 1.3.6.1.4.1.2947.1.1.2 | ScalarupsIdentModel | read-only | mandatory | The UPS model name (example: 'FE500VA'). |
| 1.3.6.1.4.1.2947.1.1.3 | ScalarupsIdentVARating | read-only | mandatory | The capacity rating of the UPS expressed in VoltAmperes(VA). |
| 1.3.6.1.4.1.2947.1.1.4 | ScalarupsIdentUpsType | read-only | mandatory | Type of UPS. |
| 1.3.6.1.4.1.2947.1.1.5 | ScalarupsIdentUpsSerialNumber | read-only | mandatory | A unique identification number provided by the factory. |
| 1.3.6.1.4.1.2947.1.1.7 | ScalarupsIdentFirmwareRevision | read-only | mandatory | The firmware revision of the UPS. |
| 1.3.6.1.4.1.2947.1.1.8 | ScalarupsIdentInstallationDate | read-write | mandatory | The date when the UPS was installed in mm/dd/yyyy format. |
| 1.3.6.1.4.1.2947.1.2 | NodeupsBattery | |||
| 1.3.6.1.4.1.2947.1.2 | NodeupsTrapPowerRestored | INFORMATION: Utility power has been restored. | ||
| 1.3.6.1.4.1.2947.1.2.1 | ScalarupsBatteryStatus | read-only | mandatory | The status of the inverter . |
| 1.3.6.1.4.1.2947.1.2.2 | ScalarupsBatteryTimeOnBattery | read-only | mandatory | The elapsed time in seconds since the UPS has switched to battery power. |
| 1.3.6.1.4.1.2947.1.2.3 | ScalarupsBatteryRuntimeRemaining | read-only | mandatory | The remaining time in minutes that the UPS will be able to run on battery power. |
| 1.3.6.1.4.1.2947.1.2.4 | ScalarupsBatteryVoltage | read-only | mandatory | The UPS battery voltage expressed in 1/10 VDC. |
| 1.3.6.1.4.1.2947.1.2.5 | ScalarupsBatteryCurrent | read-only | mandatory | The battery current expressed in 1/10 ADC. |
| 1.3.6.1.4.1.2947.1.2.6 | ScalarupsBatteryTemperature | read-only | mandatory | The internal UPS temperature expressed in 1/10 degree C. |
| 1.3.6.1.4.1.2947.1.2.7 | ScalarupsBatteryLastReplaceDate | read-write | mandatory | The date when the UPS system's batteries were last replaced in mm/dd/yyyy format. When the UPS batteries are replaced, this value should be reset by the admini… |
| 1.3.6.1.4.1.2947.1.2.8 | ScalarupsBatteryCellVoltage | read-only | mandatory | The UPS battery cell voltage expressed in 1/100 VDC. |
| 1.3.6.1.4.1.2947.1.2.9 | ScalarupsBatteryPositiveVoltage | read-only | mandatory | The UPS battery voltage measured from the most postive point in the battery string to the common reference point. The value is expressed in 1/10 VDC. |
| 1.3.6.1.4.1.2947.1.2.10 | ScalarupsBatteryNegativeVoltage | read-only | mandatory | The UPS battery voltage measured from the most negative point in the battery string to the common reference point. The value is expressed in 1/10 VDC. |
| 1.3.6.1.4.1.2947.1.3 | NodeupsInput | |||
| 1.3.6.1.4.1.2947.1.3 | NodeupsTrapUPSOnBattery | WARNING: The UPS has switched to battery backup power. | ||
| 1.3.6.1.4.1.2947.1.3.2 | ScalarupsInputFrequency | read-only | mandatory | The utility line frequency in 1/10 Hz. |
| 1.3.6.1.4.1.2947.1.3.3 | ScalarupsInputVoltage | read-only | mandatory | The utility line voltage in 1/10 VAC. |
| 1.3.6.1.4.1.2947.1.3.4 | ScalarupsInputCurrent | read-only | mandatory | The utility line current in 1/10 Ampere AC. |
| 1.3.6.1.4.1.2947.1.3.6 | NodeupsInput3PhaseCurrent | |||
| 1.3.6.1.4.1.2947.1.3.6.1 | ScalarupsInputCurrentL1 | read-only | mandatory | The magnitude of the present input current on L1. |
| 1.3.6.1.4.1.2947.1.3.6.2 | ScalarupsInputCurrentL2 | read-only | mandatory | The magnitude of the present input current on L2. |
| 1.3.6.1.4.1.2947.1.3.6.3 | ScalarupsInputCurrentL3 | read-only | mandatory | The magnitude of the present input current on L3. |
| 1.3.6.1.4.1.2947.1.3.7 | NodeupsInput3PhaseVoltageLtoN | |||
| 1.3.6.1.4.1.2947.1.3.7.1 | ScalarupsInputVoltageL1toN | read-only | mandatory | The magnitude of the present input voltage from L1 to Neutral. |
| 1.3.6.1.4.1.2947.1.3.7.2 | ScalarupsInputVoltageL2toN | read-only | mandatory | The magnitude of the present input voltage from L2 to Neutral. |
| 1.3.6.1.4.1.2947.1.3.7.3 | ScalarupsInputVoltageL3toN | read-only | mandatory | The magnitude of the present input voltage from L3 to Neutral. |
| 1.3.6.1.4.1.2947.1.3.8 | NodeupsInput3PhaseVoltageLtoL | |||
| 1.3.6.1.4.1.2947.1.3.8.1 | ScalarupsInputVoltageL1toL2 | read-only | mandatory | The magnitude of the present input voltage from L1 to L2. |
| 1.3.6.1.4.1.2947.1.3.8.2 | ScalarupsInputVoltageL2toL3 | read-only | mandatory | The magnitude of the present input voltage from L2 to L3. |
| 1.3.6.1.4.1.2947.1.3.8.3 | ScalarupsInputVoltageL3toL1 | read-only | mandatory | The magnitude of the present input voltage from L3 to L1. |
| 1.3.6.1.4.1.2947.1.4 | NodeupsOutput | |||
| 1.3.6.1.4.1.2947.1.4 | NodeupsTrapUPSNotOnBattery | INFORMATION: The UPS is not on battery power. | ||
| 1.3.6.1.4.1.2947.1.4.3 | ScalarupsOutputFrequency | read-only | mandatory | The output frequency of the UPS expressed in 1/10 Hz. |
| 1.3.6.1.4.1.2947.1.4.4 | ScalarupsOutputVoltage | read-only | mandatory | The output voltage of the UPS expressed in 1/10 VAC. |
| 1.3.6.1.4.1.2947.1.4.5 | ScalarupsOutputCurrent | read-only | mandatory | The output current of the UPS expressed in 1/10 AC Amperes. |
| 1.3.6.1.4.1.2947.1.4.6 | ScalarupsOutputTruePower | read-only | mandatory | The true output power of the UPS expressed in 1/100 Watts. |
| 1.3.6.1.4.1.2947.1.4.7 | ScalarupsOutputApparentPower | read-only | mandatory | The apparent output power of the UPS expressed in 1/100 VoltAmperes(VA). |
| 1.3.6.1.4.1.2947.1.4.8 | ScalarupsOutputPowerFactor | read-only | mandatory | The output powerfactor of the UPS expressed in +/- 1/100 units deviating from 1. |
| 1.3.6.1.4.1.2947.1.4.9 | ScalarupsOutputPercentFullLoad | read-only | mandatory | The percentage of the total UPS power capacity being used expressed in % of 100. |
| 1.3.6.1.4.1.2947.1.4.10 | NodeupsOutput3PhaseVoltageLtoN | |||
| 1.3.6.1.4.1.2947.1.4.10.1 | ScalarupsOutputVoltageL1toN | read-only | mandatory | The magnitude of the present Output voltage from L1 to Neutral. |
| 1.3.6.1.4.1.2947.1.4.10.2 | ScalarupsOutputVoltageL2toN | read-only | mandatory | The magnitude of the present Output voltage from L2 to Neutral. |
| 1.3.6.1.4.1.2947.1.4.10.3 | ScalarupsOutputVoltageL3toN | read-only | mandatory | The magnitude of the present Output voltage from L3 to Neutral. |
| 1.3.6.1.4.1.2947.1.4.11 | NodeupsOutput3PhaseVoltageLtoL | |||
| 1.3.6.1.4.1.2947.1.4.11.1 | ScalarupsOutputVoltageL1toL2 | read-only | mandatory | The magnitude of the present Output voltage from L1 to L2. |
| 1.3.6.1.4.1.2947.1.4.11.2 | ScalarupsOutputVoltageL2toL3 | read-only | mandatory | The magnitude of the present Output voltage from L2 to L3. |
| 1.3.6.1.4.1.2947.1.4.11.3 | ScalarupsOutputVoltageL3toL1 | read-only | mandatory | The magnitude of the present Output voltage from L3 to L1. |
| 1.3.6.1.4.1.2947.1.4.12 | NodeupsOutput3PhaseCurrent | |||
| 1.3.6.1.4.1.2947.1.4.12.1 | ScalarupsOutputCurrentL1 | read-only | mandatory | The magnitude of the present Output current on L1. |
| 1.3.6.1.4.1.2947.1.4.12.2 | ScalarupsOutputCurrentL2 | read-only | mandatory | The magnitude of the present Output current on L2. |
| 1.3.6.1.4.1.2947.1.4.12.3 | ScalarupsOutputCurrentL3 | read-only | mandatory | The magnitude of the present Output current on L3. |
| 1.3.6.1.4.1.2947.1.4.13 | NodeupsOutput3PhaseApparentPower | |||
| 1.3.6.1.4.1.2947.1.4.13.1 | ScalarupsOutputApparentPowerL1 | read-only | mandatory | The magnitude of the present Output ApparentPower on L1. |
| 1.3.6.1.4.1.2947.1.4.13.2 | ScalarupsOutputApparentPowerL2 | read-only | mandatory | The magnitude of the present Output ApparentPower on L2. |
| 1.3.6.1.4.1.2947.1.4.13.3 | ScalarupsOutputApparentPowerL3 | read-only | mandatory | The magnitude of the present Output ApparentPower on L3. |
| 1.3.6.1.4.1.2947.1.4.14 | NodeupsOutput3PhaseTruePower | |||
| 1.3.6.1.4.1.2947.1.4.14.1 | ScalarupsOutputTruePowerL1 | read-only | mandatory | The magnitude of the present Output TruePower on L1. |
| 1.3.6.1.4.1.2947.1.4.14.2 | ScalarupsOutputTruePowerL2 | read-only | mandatory | The magnitude of the present Output TruePower on L2. |
| 1.3.6.1.4.1.2947.1.4.14.3 | ScalarupsOutputTruePowerL3 | read-only | mandatory | The magnitude of the present Output TruePower on L3. |
| 1.3.6.1.4.1.2947.1.4.15 | NodeupsOutput3PhasePowerFactor | |||
| 1.3.6.1.4.1.2947.1.4.15.1 | ScalarupsOutputPowerFactorL1 | read-only | mandatory | The magnitude of the present Output PowerFactor on L1. |
| 1.3.6.1.4.1.2947.1.4.15.2 | ScalarupsOutputPowerFactorL2 | read-only | mandatory | The magnitude of the present Output PowerFactor on L2. |
| 1.3.6.1.4.1.2947.1.4.15.3 | ScalarupsOutputPowerFactorL3 | read-only | mandatory | The magnitude of the present Output PowerFactor on L3. |
| 1.3.6.1.4.1.2947.1.4.16 | NodeupsOutput3PhasePercentLoad | |||
| 1.3.6.1.4.1.2947.1.4.16.1 | ScalarupsOutputPercentLoadL1 | read-only | mandatory | The magnitude of the present Output PercentLoad on L1. |
| 1.3.6.1.4.1.2947.1.4.16.2 | ScalarupsOutputPercentLoadL2 | read-only | mandatory | The magnitude of the present Output PercentLoad on L2. |
| 1.3.6.1.4.1.2947.1.4.16.3 | ScalarupsOutputPercentLoadL3 | read-only | mandatory | The magnitude of the present Output PercentLoad on L3. |
| 1.3.6.1.4.1.2947.1.5 | NodeupsConfig | |||
| 1.3.6.1.4.1.2947.1.5 | NodeupsTrapLowRuntime | SEVERE: The runtime remaining on battery power is very short, and the UPS will soon shut down. | ||
| 1.3.6.1.4.1.2947.1.5.3 | ScalarupsConfigDelayBeforeShutdown | read-write | mandatory | The delay in seconds that the UPS waits before executing an off command upon request of an external device. |
| 1.3.6.1.4.1.2947.1.5.4 | TableupsConfigTestScheduleTable | not-accessible | mandatory | The table to schedule ups battery tests. |
| 1.3.6.1.4.1.2947.1.5.4.1 | RowupsConfigTestScheduleEntry | not-accessible | mandatory | The entries for each day. |
| 1.3.6.1.4.1.2947.1.5.4.1.1 | ColumnupsConfigTestScheduleIndex | read-only | mandatory | The index of scheduled events. |
| 1.3.6.1.4.1.2947.1.5.4.1.2 | ColumnupsConfigTestScheduleDay | read-write | mandatory | The weekday on which the UPS should shut down. |
| 1.3.6.1.4.1.2947.1.5.4.1.3 | ColumnupsConfigTestScheduleTime | read-write | mandatory | The time that the process of shutting down the UPS will be initiated |
| 1.3.6.1.4.1.2947.1.5.5 | TableupsConfigShutdownScheduleTable | not-accessible | mandatory | The table to schedule shutting down the ups. |
| 1.3.6.1.4.1.2947.1.5.5.1 | RowupsConfigShutdownScheduleEntry | not-accessible | mandatory | The entries for each day. |
| 1.3.6.1.4.1.2947.1.5.5.1.1 | ColumnupsConfigShutdownScheduleIndex | read-only | mandatory | The index of scheduled events. |
| 1.3.6.1.4.1.2947.1.5.5.1.2 | ColumnupsConfigScheduleShutdownDay | read-write | mandatory | The weekday on which the UPS should shut down. |
| 1.3.6.1.4.1.2947.1.5.5.1.3 | ColumnupsConfigScheduleShutdownTime | read-write | mandatory | The time that the process of shutting down the UPS will be initiated |
| 1.3.6.1.4.1.2947.1.5.5.1.4 | ColumnupsConfigScheduleRestartDay | read-write | mandatory | The weekday on which the UPS should restart |
| 1.3.6.1.4.1.2947.1.5.5.1.5 | ColumnupsConfigScheduleRestartTime | read-write | mandatory | The time the UPS will restart in hh:mm:ss format. |
| 1.3.6.1.4.1.2947.1.5.8 | NodeupsConfigbestLink | |||
| 1.3.6.1.4.1.2947.1.5.8.1 | ScalarbestLinkHistoryLogFrequency | read-write | mandatory | The frequency of updating the history log in minutes. |
| 1.3.6.1.4.1.2947.1.5.8.2 | ScalarbestLinkRefreshFrequency | read-write | mandatory | The frequency of saving configuration,history and event log data in non-volatile memory. If the value is set to 0, then saving data is disabled. |
| 1.3.6.1.4.1.2947.1.5.8.3 | ScalarbestLinkNetId | read-write | mandatory | The IP address of the device. Setting this parameter causes BestLink to reboot. |
| 1.3.6.1.4.1.2947.1.5.8.4 | ScalarbestLinkGateway | read-write | mandatory | The gateway address for the network BestLink is connected to. |
| 1.3.6.1.4.1.2947.1.5.8.5 | ScalarbestLinkNetMask | read-write | mandatory | The net mask of the device. |
| 1.3.6.1.4.1.2947.1.5.8.6 | ScalarbestLinkSysDate | read-write | mandatory | The system date of the device. The date is in mm/dd/yyyy format. The range of system date is from 1/1/1980 to 12/31/2037. |
| 1.3.6.1.4.1.2947.1.5.8.7 | ScalarbestLinkSysTime | read-write | mandatory | The system time of the device. The time is in hh:mm:ss format. |
| 1.3.6.1.4.1.2947.1.5.8.8 | ScalarbestLinkTftpFileName | read-write | mandatory | The tftp file name that contains the software upgrade image. |
| 1.3.6.1.4.1.2947.1.5.8.9 | ScalarbestLinkTftpHost | read-write | mandatory | The tftp host IP address from where to get the image. |
| 1.3.6.1.4.1.2947.1.5.8.10 | ScalarbestLinkFlashEEPROM | read-write | mandatory | Saves the history log, eventlog, and configuration data to non-volatile memory. |
| 1.3.6.1.4.1.2947.1.5.8.11 | ScalarbestLinkPrimaryTimeServer | read-write | mandatory | The primary time server is responsible for sending the correct time to the UPS. |
| 1.3.6.1.4.1.2947.1.5.8.12 | ScalarbestLinkSecondaryTimeServer | read-write | mandatory | The secondary time server responsible for sending the correct time to the UPS. |
| 1.3.6.1.4.1.2947.1.5.8.13 | ScalarbestLinkSoftwareVersion | read-only | mandatory | The version of BestLink software. |
| 1.3.6.1.4.1.2947.1.5.8.14 | ScalarbestLinkMIBVersion | read-only | mandatory | The version of MIB implemented in SNMP/WEB Card software. |
| 1.3.6.1.4.1.2947.1.5.8.15 | ScalarbestLinkDHCPControl | read-write | mandatory | Enable/Disable DHCP function of SNMP/WEB Card. |
| 1.3.6.1.4.1.2947.1.5.8.16 | ScalarbestLinkTelnetControl | read-write | mandatory | Enable/Disable Telnet function of SNMP/WEB Card. |
| 1.3.6.1.4.1.2947.1.5.8.17 | ScalarbestLinkTftpControl | read-write | mandatory | Enable/Disable TFTP function of SNMP/WEB Card. |
| 1.3.6.1.4.1.2947.1.5.8.18 | ScalarbestLinkResetToDefault | read-write | mandatory | Reset all parameters of SNMP/WEB Card to default setting. |
| 1.3.6.1.4.1.2947.1.5.8.19 | ScalarbestLinkRestartAgent | read-write | mandatory | Restart of SNMP/WEB Card. |
| 1.3.6.1.4.1.2947.1.5.9 | NodeupsConfigTrapsReceivers | |||
| 1.3.6.1.4.1.2947.1.5.9.1 | TableupsConfigTrapsReceiversTable | not-accessible | mandatory | A list of managers to send traps to. |
| 1.3.6.1.4.1.2947.1.5.9.1.1 | RowupsConfigTrapsReceiversEntry | not-accessible | mandatory | The managers to send traps to. |
| 1.3.6.1.4.1.2947.1.5.9.1.1.1 | ColumntrapsIndex | read-only | mandatory | The index to a trap receiver entry. |
| 1.3.6.1.4.1.2947.1.5.9.1.1.2 | ColumntrapsReceiverAddr | read-write | mandatory | The IP address of the manager to send a trap to. |
| 1.3.6.1.4.1.2947.1.5.9.1.1.3 | ColumnreceiverCommunityString | read-write | mandatory | The community name to use in the trap when sent to the manager. |
| 1.3.6.1.4.1.2947.1.5.9.1.1.4 | ColumnseverityLevel | read-write | mandatory | The severity threshold of traps to send to the manager. Traps are labeled by severity as informational(1), warning(2), severe(3). Only traps of equal or greate… |
| 1.3.6.1.4.1.2947.1.5.9.1.1.5 | ColumnreceiverAccept | read-write | mandatory | An entry will become active if yes, otherwise it will be disabled. |
| 1.3.6.1.4.1.2947.1.5.10 | NodeupsConfigRegisteredShutdownClients | |||
| 1.3.6.1.4.1.2947.1.5.10.1 | TableupsRegisteredShutdownClientsTable | not-accessible | mandatory | A list of registered shutdown client table entries. The table contains zero, one, or many rows at any moment, depending upon the number of Netwatch clients reg… |
| 1.3.6.1.4.1.2947.1.5.10.1.1 | RowupsRegisteredShutdownClientsEntry | not-accessible | mandatory | An entry containing information applicable to a particular registered shutdown client. |
| 1.3.6.1.4.1.2947.1.5.10.1.1.1 | ColumnupsRegisteredShutdownClientsIndex | read-only | mandatory | An index of alarm entries in the RegisteredShutdownClientsTable. |
| 1.3.6.1.4.1.2947.1.5.10.1.1.2 | ColumnupsRegisteredShutdownClientsIPAddress | read-only | mandatory | The IP Address of the registered shutdown client |
| 1.3.6.1.4.1.2947.1.5.10.2 | ScalarupsRegisteredShutdownClientsTotalNumberOf | read-only | mandatory | The total number of registered shutdown clients. |
| 1.3.6.1.4.1.2947.1.5.11 | ScalarupsConfigAutoRestart | read-write | mandatory | The status of the Auto Restart mode. |
| 1.3.6.1.4.1.2947.1.5.12 | NodeupsConfigACFailEventActions | |||
| 1.3.6.1.4.1.2947.1.5.12.1 | ScalarupsConfigDelayBeforeFirstWarningMessage | read-write | mandatory | The amount of time to delay in seconds before sending the first AC Fail message. |
| 1.3.6.1.4.1.2947.1.5.12.2 | ScalarupsConfigWarningInterval | read-write | mandatory | The amount of time to delay in seconds between sending the additional AC Fail messages. |
| 1.3.6.1.4.1.2947.1.5.12.3 | ScalarupsConfigClientOperatingSystemShutdown | read-write | mandatory | Determines whether or not to initiate a shutdown of all registered clients based on the AC Fail event with duration. |
| 1.3.6.1.4.1.2947.1.5.12.4 | ScalarupsConfigDelayBeforeClientShutdown | read-write | mandatory | The time allowed in seconds during an AC Fail condition before shutting down of all registered clients. |
| 1.3.6.1.4.1.2947.1.5.13 | NodeupsConfigLowBatteryEventActions | |||
| 1.3.6.1.4.1.2947.1.5.13.1 | ScalarupsConfigClientOsShutdown | read-write | mandatory | Determines whether or not to initiate a shutdown of all registered clients based on the Low Battery condition. |
| 1.3.6.1.4.1.2947.1.5.14 | ScalarupsConfigShutdownUPSAfterOSShdn | read-write | mandatory | Setting this value to 1, enables the UPS to be shutdown after the registered clients operating systems have shutdown. |
| 1.3.6.1.4.1.2947.1.6 | NodeupsControl | |||
| 1.3.6.1.4.1.2947.1.6 | NodeupsTrapUPSCanRunOnBattery | INFORMATION: The UPS has returned from a low runtime condition. | ||
| 1.3.6.1.4.1.2947.1.6.1 | ScalarupsControlTurnOffUPS | read-write | mandatory | Setting this variable to UpsOff(2) causes the UPS to shut off. When the UPS is in the off state, the UPS will remain off until the ON/OFF switch is manually to… |
| 1.3.6.1.4.1.2947.1.6.4 | ScalarupsControlActivateUpsScheduling | read-write | mandatory | Setting this variable to On(2) causes the UPS to activate the scheduling parameters that have been previously configured within the upsConfigDailyShutdownSched… |
| 1.3.6.1.4.1.2947.1.6.5 | ScalarupsControlEnableGeneratorSensitivity | read-write | mandatory | Setting this value to a value other than (disable) begins to increase the UPS ability to reject poor line sources for example from a poorly regulated AC genera… |
| 1.3.6.1.4.1.2947.1.7 | NodeupsTest | |||
| 1.3.6.1.4.1.2947.1.7 | NodeupsTrapNearLowBattery | SEVERE: The UPS batteries are low and will soon be exhausted. If utility power is not restored the UPS will put itself to 'sleep' and immediately cut power to … | ||
| 1.3.6.1.4.1.2947.1.7.1 | ScalarupsManualTests | read-write | mandatory | Setting this variable to any value other than (1) causes the UPS to perform a manual test or abort a particular test in progress. |
| 1.3.6.1.4.1.2947.1.8 | NodeupsAlarm | |||
| 1.3.6.1.4.1.2947.1.8 | NodeupsTrapHighBattery | WARNING: The battery charger voltage on the UPS has reached a value that is too high for safe battery maintenance. | ||
| 1.3.6.1.4.1.2947.1.8.1 | ScalarupsAlarmsPresent | read-only | mandatory | The present number of active alarm conditions. |
| 1.3.6.1.4.1.2947.1.8.2 | ScalarupsLastKnownAlarm | read-only | mandatory | A unique identifier for an alarm condition. This value must remain constant. Value 'noAlarm(37)' will be returned if no Alarm has occured till the point of GET… |
| 1.3.6.1.4.1.2947.1.8.3 | TableupsAlarmTable | not-accessible | mandatory | A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is … |
| 1.3.6.1.4.1.2947.1.8.3.1 | RowupsAlarmEntry | not-accessible | mandatory | An entry containing information applicable to a particular alarm. |
| 1.3.6.1.4.1.2947.1.8.3.1.1 | ColumnupsAlarmIndex | read-only | mandatory | An index of alarm entries in the alarm log. |
| 1.3.6.1.4.1.2947.1.8.3.1.2 | ColumnupsAlarmName | read-only | mandatory | A unique identifier for an alarm condition. This value must remain constant. |
| 1.3.6.1.4.1.2947.1.8.3.1.3 | ColumnupsAlarmTime | read-only | mandatory | The time that the alarm occurred in hh:mm:ss format. |
| 1.3.6.1.4.1.2947.1.8.4 | NodeupsWellKnownAlarms | |||
| 1.3.6.1.4.1.2947.1.8.4.1 | ScalarupsAlarmOnBattery | read-only | mandatory | The UPS is drawing power from the batteries. |
| 1.3.6.1.4.1.2947.1.8.4.2 | ScalarupsAlarmLowRuntime | read-only | mandatory | The remaining battery runtime is less than or equal to the upsConfigLowRuntimeSetpoint. |
| 1.3.6.1.4.1.2947.1.8.4.3 | ScalarupsAlarmNearLowBattery | read-only | mandatory | The battery voltage on the UPS has reached a value where the inverter will not be able to function very much longer. |
| 1.3.6.1.4.1.2947.1.8.4.4 | ScalarupsAlarmLowBattery | read-only | mandatory | The battery voltage on the UPS has reached a value where the inverter has stopped providing output power to the connected load equipment. The UPS has shutdown … |
| 1.3.6.1.4.1.2947.1.8.4.5 | ScalarupsAlarmHighBattery | read-only | mandatory | The battery charger voltage on the UPS has reached a value that is too high for safe battery maintenance. |
| 1.3.6.1.4.1.2947.1.8.4.6 | ScalarupsAlarmCheckBattery | read-only | mandatory | The periodic battery test has failed. A manual test of the batteries needs to be performed to determine which battery\batteries need replaced. |
| 1.3.6.1.4.1.2947.1.8.4.7 | ScalarupsAlarmReplaceBattery | read-only | mandatory | One or more batteries have been determined to require replacement. Compatibility: Fortress II |
| 1.3.6.1.4.1.2947.1.8.4.8 | ScalarupsAlarmCheckInverter | read-only | mandatory | The inverter has failed the automatic system test. |
| 1.3.6.1.4.1.2947.1.8.4.9 | ScalarupsAlarmBatteriesDisconnected | read-only | mandatory | The UPS has detected that the DC voltage needed to start up is too low or missing. |
| 1.3.6.1.4.1.2947.1.8.4.10 | ScalarupsAlarmOutputOverload | read-only | mandatory | The output load exceeds the UPS output capacity. |
| 1.3.6.1.4.1.2947.1.8.4.11 | ScalarupsAlarmLowAcOut | read-only | mandatory | The output load has exceeded the UPS output capacity, and the UPS has shut down. |
| 1.3.6.1.4.1.2947.1.8.4.12 | ScalarupsAlarmCircuitBreakerWarning | read-only | mandatory | To much load equipment has been connected to the UPS and has has caused excess current draw from the output. |
| 1.3.6.1.4.1.2947.1.8.4.13 | ScalarupsAlarmCircuitBreakerShdn | read-only | mandatory | The UPS has shut down due to an extended excess of current draw from the output. |
| 1.3.6.1.4.1.2947.1.8.4.14 | ScalarupsAlarmBypassOn | read-only | mandatory | The Bypass is presently engaged on the UPS. |
| 1.3.6.1.4.1.2947.1.8.4.15 | ScalarupsAlarmAutoBypass | read-only | mandatory | The UPS has gone into the Auto Bypass mode to redirect power around the UPS circuitry. |
| 1.3.6.1.4.1.2947.1.8.4.16 | ScalarupsAlarmSiteWiringFault | read-only | mandatory | The UPS has found a problem in your wall outlet. |
| 1.3.6.1.4.1.2947.1.8.4.17 | ScalarupsAlarmCheckFan | read-only | mandatory | The fan on the UPS has stopped |
| 1.3.6.1.4.1.2947.1.8.4.18 | ScalarupsAlarmHighAmbTemp | read-only | mandatory | The internal temperature inside the UPS is too hot. |
| 1.3.6.1.4.1.2947.1.8.4.19 | ScalarupsAlarmHighHSTemp | read-only | mandatory | The Inverter heatsink assembly inside the UPS is to hot . |
| 1.3.6.1.4.1.2947.1.8.4.20 | ScalarupsAlarmHighXFMRTemp | read-only | mandatory | The temperature of the main transformer inside the UPS is too hot . |
| 1.3.6.1.4.1.2947.1.8.4.21 | ScalarupsAlarmHighPFMTemp | read-only | mandatory | The temperature of the PFM module inside the UPS is too hot . |
| 1.3.6.1.4.1.2947.1.8.4.22 | ScalarupsAlarmProbeMissing | read-only | mandatory | One or all of the sense probes has been disconnected on the UPS. |
| 1.3.6.1.4.1.2947.1.8.4.23 | ScalarupsAlarmCheckPowerSupply | read-only | mandatory | The internal DC supply voltages are attenuated or missing. |
| 1.3.6.1.4.1.2947.1.8.4.24 | ScalarupsAlarmTapRegulator | read-only | mandatory | The UPS detected a possible failure in the tap changer (open or welded relay, etc.) |
| 1.3.6.1.4.1.2947.1.8.4.25 | ScalarupsAlarmRelayFailure | read-only | mandatory | There is a hardware problem inside the UPS. |
| 1.3.6.1.4.1.2947.1.8.4.26 | ScalarupsAlarmCheckFuse | read-only | mandatory | The failure of one or more fuses has been detected. |
| 1.3.6.1.4.1.2947.1.8.4.27 | ScalarupsAlarmCheckMOV | read-only | mandatory | One or more MOVs have failed due to a voltage surge. |
| 1.3.6.1.4.1.2947.1.8.4.28 | ScalarupsAlarmMemoryError | read-only | mandatory | The UPS has lost the programmed settings in the memory of the logic board. |
| 1.3.6.1.4.1.2947.1.8.4.29 | ScalarupsAlarmCallService | read-only | mandatory | A hardware malfunction has occurred inside the UPS. Please consult a factory authorized service representative for assistance. |
| 1.3.6.1.4.1.2947.1.8.4.30 | ScalarupsAlarmupsFailed | read-only | mandatory | A general fault in the UPS has been detected. |
| 1.3.6.1.4.1.2947.1.8.4.31 | ScalarupsAlarmUserTest | read-only | mandatory | A user test of the alarm beeper is in progress. |
| 1.3.6.1.4.1.2947.1.8.4.32 | ScalarupsAlarmTestInProgress | read-only | mandatory | A test is in progress. |
| 1.3.6.1.4.1.2947.1.8.4.33 | ScalarupsAlarmDiagnosticTestFailed | read-only | mandatory | The result of the last diagnostic test indicates a failure. |
| 1.3.6.1.4.1.2947.1.8.4.34 | ScalarupsAlarmEPO | read-only | mandatory | The Emergency Power OFF feature has been activiated at the RS-232 port on the UPS. |
| 1.3.6.1.4.1.2947.1.8.4.35 | ScalarupsAlarmUpsOff | read-only | mandatory | The output of the UPS is in the off state. |
| 1.3.6.1.4.1.2947.1.8.4.36 | ScalarupsAlarmCommunicationsLost | read-only | mandatory | A problem has been encountered in the communications between the agent and the UPS. |
| 1.3.6.1.4.1.2947.1.9 | NodeupsBypass | |||
| 1.3.6.1.4.1.2947.1.9 | NodeupsTrapBatteryOK | INFORMATION: The UPS has returned from a near low or high battery condition. | ||
| 1.3.6.1.4.1.2947.1.9.1 | ScalarupsBypassStatus | read-only | mandatory | The status of the bypass mode. |
| 1.3.6.1.4.1.2947.1.9.2 | NodeupsBypass3PhaseVoltageLtoN | |||
| 1.3.6.1.4.1.2947.1.9.2.1 | ScalarupsBypassVoltageL1toN | read-only | mandatory | The magnitude of the present Bypass voltage from L1 to Neutral. |
| 1.3.6.1.4.1.2947.1.9.2.2 | ScalarupsBypassVoltageL2toN | read-only | mandatory | The magnitude of the present Bypass voltage from L2 to Neutral. |
| 1.3.6.1.4.1.2947.1.9.2.3 | ScalarupsBypassVoltageL3toN | read-only | mandatory | The magnitude of the present Bypass voltage from L3 to Neutral. |
| 1.3.6.1.4.1.2947.1.9.3 | NodeupsBypass3PhaseVoltageLtoL | |||
| 1.3.6.1.4.1.2947.1.9.3.1 | ScalarupsBypassVoltageL1toL2 | read-only | mandatory | The magnitude of the present Bypass voltage from L1 to L2. |
| 1.3.6.1.4.1.2947.1.9.3.2 | ScalarupsBypassVoltageL2toL3 | read-only | mandatory | The magnitude of the present Bypass voltage from L2 to L3. |
| 1.3.6.1.4.1.2947.1.9.3.3 | ScalarupsBypassVoltageL3toL1 | read-only | mandatory | The magnitude of the present Bypass voltage from L3 to L1. |
| 1.3.6.1.4.1.2947.1.10 | NodeupsTrapLowBattery | SEVERE: The UPS will run for approximately 2 minutes more and then put itself to sleep to prevent a complete discharge of the batteries. | ||
| 1.3.6.1.4.1.2947.1.11 | NodeupsTrapCheckBattery | SEVERE: The UPS has failed a scheduled or manual battery test. | ||
| 1.3.6.1.4.1.2947.1.12 | NodeupsTrapReplaceBattery | SEVERE: One or more UPS batteries need to be replaced. | ||
| 1.3.6.1.4.1.2947.1.13 | NodeupsTrapCheckInverter | SEVERE: The UPS has failed a scheduled or manual inverter test. | ||
| 1.3.6.1.4.1.2947.1.14 | NodeupsTrapBatteriesDisconnected | WARNING: The UPS battery voltage is either too low or missing to start up. | ||
| 1.3.6.1.4.1.2947.1.15 | NodeupsTrapOutputOverload | WARNING: The output load exceeds the UPS output capacity. | ||
| 1.3.6.1.4.1.2947.1.16 | NodeupsTrapUPSNoLongerOverloaded | INFORMATION: The UPS has returned from an output overload condition. | ||
| 1.3.6.1.4.1.2947.1.17 | NodeupsTrapLowAcOut | SEVERE: The output load has exceeded the UPS output capacity, and the UPS has shut down. | ||
| 1.3.6.1.4.1.2947.1.18 | NodeupsTrapCircuitBreakerWarning | SEVERE: To much load equipment has been connected to the UPS and has has caused excess current draw from the output. | ||
| 1.3.6.1.4.1.2947.1.19 | NodeupsTrapCircuitBreakerOK | INFORMATION: The UPS has returned from a circuit breaker warning condition. | ||
| 1.3.6.1.4.1.2947.1.20 | NodeupsTrapCircuitBreakerShdn | SEVERE: The UPS has shut down due to an extended excess of current draw from the output. | ||
| 1.3.6.1.4.1.2947.1.21 | NodeupsTrapBypassOn | SEVERE: The Bypass is presently engaged on the UPS. | ||
| 1.3.6.1.4.1.2947.1.22 | NodeupsTrapUPSOnline | INFORMATION: The UPS has returned from an on bypass condition. | ||
| 1.3.6.1.4.1.2947.1.23 | NodeupsTrapSiteWiringFault | SEVERE: The UPS has found a problem in your wall outlet. | ||
| 1.3.6.1.4.1.2947.1.24 | NodeupsTrapCheckFan | SEVERE: The fan on the UPS has stopped . | ||
| 1.3.6.1.4.1.2947.1.25 | NodeupsTrapHighUPSTemp | SEVERE: The internal temperature inside the UPS is too hot. | ||
| 1.3.6.1.4.1.2947.1.26 | NodeupsTrapTempOK | INFORMATION: The UPS has returned from a high ambient temp condition. | ||
| 1.3.6.1.4.1.2947.1.27 | NodeupsTrapHighHSTemp | SEVERE: The Inverter heatsink assembly inside the UPS is too hot . | ||
| 1.3.6.1.4.1.2947.1.28 | NodeupsTrapHSTempOK | INFORMATION: The UPS has returned from a high heatsink temp condition. | ||
| 1.3.6.1.4.1.2947.1.29 | NodeupsTrapHighXFMRTemp | SEVERE: The temperature of the main transformer inside the UPS is too hot . | ||
| 1.3.6.1.4.1.2947.1.30 | NodeupsTrapHighPFMTemp | SEVERE: The temperature of the PFM module inside the UPS is too hot. | ||
| 1.3.6.1.4.1.2947.1.31 | NodeupsTrapProbeMissing | SEVERE: One or all of the temperature probes has been disconnected on the UPS. | ||
| 1.3.6.1.4.1.2947.1.32 | NodeupsTrapProbeReconnected | INFORMATION: The UPS has returned from a probe missing condition. | ||
| 1.3.6.1.4.1.2947.1.33 | NodeupsTrapCheckPowerSupply | SEVERE: The internal DC supply voltages are attenuated or missing. | ||
| 1.3.6.1.4.1.2947.1.34 | NodeupsTrapTapRegulatorFault | SEVERE: The UPS detected a possible failure in the tap changer (open or welded relay, etc.) | ||
| 1.3.6.1.4.1.2947.1.35 | NodeupsTrapRelayFailure | SEVERE: There is a hardware problem inside the UPS. | ||
| 1.3.6.1.4.1.2947.1.36 | NodeupsTrapCheckFuse | SEVERE: The failure of one or more fuses has been detected. | ||
| 1.3.6.1.4.1.2947.1.37 | NodeupsTrapCheckMOV | SEVERE: One or more MOVs have failed due to a voltage surge. | ||
| 1.3.6.1.4.1.2947.1.38 | NodeupsTrapMemoryError | SEVERE: The UPS has lost the programmed settings in the memory of the logic board. | ||
| 1.3.6.1.4.1.2947.1.39 | NodeupsTrapCallService | SEVERE: A hardware malfunction has occurred inside the UPS. Please consult a factory authorized service representative for assistance. | ||
| 1.3.6.1.4.1.2947.1.40 | NodeupsTrapManualAlarmBeeperTestInitiated | INFORMATION: A manual test of the alarm beeper is being performed on the UPS. | ||
| 1.3.6.1.4.1.2947.1.41 | NodeupsTrapManualAlarmBeeperTestAborted | INFORMATION: The test of UPS has completed. | ||
| 1.3.6.1.4.1.2947.1.42 | NodeupsTrapScheduledTestInProgress | INFORMATION: A test is in progress. | ||
| 1.3.6.1.4.1.2947.1.43 | NodeupsTrapScheduledTestFailed | SEVERE: The last test performed failed. | ||
| 1.3.6.1.4.1.2947.1.44 | NodeupsTrapCommunicationLost | SEVERE: Communication to the UPS has been lost. Steps to reestablish communication are in progress. | ||
| 1.3.6.1.4.1.2947.1.45 | NodeupsTrapCommunicationRestored | INFORMATION: Communication with the UPS has been restored. | ||
| 1.3.6.1.4.1.2947.1.46 | NodeupsTrapUPSGoingDown | WARNING: The ups has been given shutdown command by the management station. | ||
| 1.3.6.1.4.1.2947.1.47 | NodeupsTrapUPSTurnedOff | INFORMATION: The ups has been turned off by the management station. | ||
| 1.3.6.1.4.1.2947.1.48 | NodeupsTrapUPSSleeping | INFORMATION: The UPS has entered in 'sleep' mode. Power to the load has been cut off. | ||
| 1.3.6.1.4.1.2947.1.49 | NodeupsTrapUPSWokeUp | INFORMATION: The UPS woke up from 'sleep' mode. Power to the load has been restored. | ||
| 1.3.6.1.4.1.2947.1.50 | NodeupsTrapUPSRebooted | INFORMATION: The UPS is rebooted. | ||
| 1.3.6.1.4.1.2947.1.51 | NodeupsTrapEmergencyPowerOFF | SEVERE: The Emergency Power OFF feature has been activiated at the RS-232 port on the UPS. | ||
| 1.3.6.1.4.1.2947.1.52 | NodeupsTrapHistLogWarn | WARNING: The ups history log buffer is almost full. | ||
| 1.3.6.1.4.1.2947.1.53 | NodeupsTrapEventLogWarn | WARNING: The ups event log buffer is almost full. | ||
| 1.3.6.1.4.1.2947.1.54 | NodeupsTrapUPSFail | SEVERE: A critical fault has been detected inside the UPS. Power to the load has been shut off. |