OIDNameAccessStatusDescription
1.3.6.1.4.1.2947NodebestPower
1.3.6.1.4.1.2947.1NodebestLink
1.3.6.1.4.1.2947.1.1NodeupsIdent
1.3.6.1.4.1.2947.1.1NodeupsTrapPowerFailWARNING: Utility power not available.
1.3.6.1.4.1.2947.1.1.1ScalarupsIdentUpsNameread-onlymandatoryAn ID string identifying the Family of UPS.
1.3.6.1.4.1.2947.1.1.2ScalarupsIdentModelread-onlymandatoryThe UPS model name (example: 'FE500VA').
1.3.6.1.4.1.2947.1.1.3ScalarupsIdentVARatingread-onlymandatoryThe capacity rating of the UPS expressed in VoltAmperes(VA).
1.3.6.1.4.1.2947.1.1.4ScalarupsIdentUpsTyperead-onlymandatoryType of UPS.
1.3.6.1.4.1.2947.1.1.5ScalarupsIdentUpsSerialNumberread-onlymandatoryA unique identification number provided by the factory.
1.3.6.1.4.1.2947.1.1.7ScalarupsIdentFirmwareRevisionread-onlymandatoryThe firmware revision of the UPS.
1.3.6.1.4.1.2947.1.1.8ScalarupsIdentInstallationDateread-writemandatoryThe date when the UPS was installed in mm/dd/yyyy format.
1.3.6.1.4.1.2947.1.2NodeupsBattery
1.3.6.1.4.1.2947.1.2NodeupsTrapPowerRestoredINFORMATION: Utility power has been restored.
1.3.6.1.4.1.2947.1.2.1ScalarupsBatteryStatusread-onlymandatoryThe status of the inverter .
1.3.6.1.4.1.2947.1.2.2ScalarupsBatteryTimeOnBatteryread-onlymandatoryThe elapsed time in seconds since the UPS has switched to battery power.
1.3.6.1.4.1.2947.1.2.3ScalarupsBatteryRuntimeRemainingread-onlymandatoryThe remaining time in minutes that the UPS will be able to run on battery power.
1.3.6.1.4.1.2947.1.2.4ScalarupsBatteryVoltageread-onlymandatoryThe UPS battery voltage expressed in 1/10 VDC.
1.3.6.1.4.1.2947.1.2.5ScalarupsBatteryCurrentread-onlymandatoryThe battery current expressed in 1/10 ADC.
1.3.6.1.4.1.2947.1.2.6ScalarupsBatteryTemperatureread-onlymandatoryThe internal UPS temperature expressed in 1/10 degree C.
1.3.6.1.4.1.2947.1.2.7ScalarupsBatteryLastReplaceDateread-writemandatoryThe date when the UPS system's batteries were last replaced in mm/dd/yyyy format. When the UPS batteries are replaced, this value should be reset by the admini…
1.3.6.1.4.1.2947.1.2.8ScalarupsBatteryCellVoltageread-onlymandatoryThe UPS battery cell voltage expressed in 1/100 VDC.
1.3.6.1.4.1.2947.1.2.9ScalarupsBatteryPositiveVoltageread-onlymandatoryThe UPS battery voltage measured from the most postive point in the battery string to the common reference point. The value is expressed in 1/10 VDC.
1.3.6.1.4.1.2947.1.2.10ScalarupsBatteryNegativeVoltageread-onlymandatoryThe UPS battery voltage measured from the most negative point in the battery string to the common reference point. The value is expressed in 1/10 VDC.
1.3.6.1.4.1.2947.1.3NodeupsInput
1.3.6.1.4.1.2947.1.3NodeupsTrapUPSOnBatteryWARNING: The UPS has switched to battery backup power.
1.3.6.1.4.1.2947.1.3.2ScalarupsInputFrequencyread-onlymandatoryThe utility line frequency in 1/10 Hz.
1.3.6.1.4.1.2947.1.3.3ScalarupsInputVoltageread-onlymandatoryThe utility line voltage in 1/10 VAC.
1.3.6.1.4.1.2947.1.3.4ScalarupsInputCurrentread-onlymandatoryThe utility line current in 1/10 Ampere AC.
1.3.6.1.4.1.2947.1.3.6NodeupsInput3PhaseCurrent
1.3.6.1.4.1.2947.1.3.6.1ScalarupsInputCurrentL1read-onlymandatoryThe magnitude of the present input current on L1.
1.3.6.1.4.1.2947.1.3.6.2ScalarupsInputCurrentL2read-onlymandatoryThe magnitude of the present input current on L2.
1.3.6.1.4.1.2947.1.3.6.3ScalarupsInputCurrentL3read-onlymandatoryThe magnitude of the present input current on L3.
1.3.6.1.4.1.2947.1.3.7NodeupsInput3PhaseVoltageLtoN
1.3.6.1.4.1.2947.1.3.7.1ScalarupsInputVoltageL1toNread-onlymandatoryThe magnitude of the present input voltage from L1 to Neutral.
1.3.6.1.4.1.2947.1.3.7.2ScalarupsInputVoltageL2toNread-onlymandatoryThe magnitude of the present input voltage from L2 to Neutral.
1.3.6.1.4.1.2947.1.3.7.3ScalarupsInputVoltageL3toNread-onlymandatoryThe magnitude of the present input voltage from L3 to Neutral.
1.3.6.1.4.1.2947.1.3.8NodeupsInput3PhaseVoltageLtoL
1.3.6.1.4.1.2947.1.3.8.1ScalarupsInputVoltageL1toL2read-onlymandatoryThe magnitude of the present input voltage from L1 to L2.
1.3.6.1.4.1.2947.1.3.8.2ScalarupsInputVoltageL2toL3read-onlymandatoryThe magnitude of the present input voltage from L2 to L3.
1.3.6.1.4.1.2947.1.3.8.3ScalarupsInputVoltageL3toL1read-onlymandatoryThe magnitude of the present input voltage from L3 to L1.
1.3.6.1.4.1.2947.1.4NodeupsOutput
1.3.6.1.4.1.2947.1.4NodeupsTrapUPSNotOnBatteryINFORMATION: The UPS is not on battery power.
1.3.6.1.4.1.2947.1.4.3ScalarupsOutputFrequencyread-onlymandatoryThe output frequency of the UPS expressed in 1/10 Hz.
1.3.6.1.4.1.2947.1.4.4ScalarupsOutputVoltageread-onlymandatoryThe output voltage of the UPS expressed in 1/10 VAC.
1.3.6.1.4.1.2947.1.4.5ScalarupsOutputCurrentread-onlymandatoryThe output current of the UPS expressed in 1/10 AC Amperes.
1.3.6.1.4.1.2947.1.4.6ScalarupsOutputTruePowerread-onlymandatoryThe true output power of the UPS expressed in 1/100 Watts.
1.3.6.1.4.1.2947.1.4.7ScalarupsOutputApparentPowerread-onlymandatoryThe apparent output power of the UPS expressed in 1/100 VoltAmperes(VA).
1.3.6.1.4.1.2947.1.4.8ScalarupsOutputPowerFactorread-onlymandatoryThe output powerfactor of the UPS expressed in +/- 1/100 units deviating from 1.
1.3.6.1.4.1.2947.1.4.9ScalarupsOutputPercentFullLoadread-onlymandatoryThe percentage of the total UPS power capacity being used expressed in % of 100.
1.3.6.1.4.1.2947.1.4.10NodeupsOutput3PhaseVoltageLtoN
1.3.6.1.4.1.2947.1.4.10.1ScalarupsOutputVoltageL1toNread-onlymandatoryThe magnitude of the present Output voltage from L1 to Neutral.
1.3.6.1.4.1.2947.1.4.10.2ScalarupsOutputVoltageL2toNread-onlymandatoryThe magnitude of the present Output voltage from L2 to Neutral.
1.3.6.1.4.1.2947.1.4.10.3ScalarupsOutputVoltageL3toNread-onlymandatoryThe magnitude of the present Output voltage from L3 to Neutral.
1.3.6.1.4.1.2947.1.4.11NodeupsOutput3PhaseVoltageLtoL
1.3.6.1.4.1.2947.1.4.11.1ScalarupsOutputVoltageL1toL2read-onlymandatoryThe magnitude of the present Output voltage from L1 to L2.
1.3.6.1.4.1.2947.1.4.11.2ScalarupsOutputVoltageL2toL3read-onlymandatoryThe magnitude of the present Output voltage from L2 to L3.
1.3.6.1.4.1.2947.1.4.11.3ScalarupsOutputVoltageL3toL1read-onlymandatoryThe magnitude of the present Output voltage from L3 to L1.
1.3.6.1.4.1.2947.1.4.12NodeupsOutput3PhaseCurrent
1.3.6.1.4.1.2947.1.4.12.1ScalarupsOutputCurrentL1read-onlymandatoryThe magnitude of the present Output current on L1.
1.3.6.1.4.1.2947.1.4.12.2ScalarupsOutputCurrentL2read-onlymandatoryThe magnitude of the present Output current on L2.
1.3.6.1.4.1.2947.1.4.12.3ScalarupsOutputCurrentL3read-onlymandatoryThe magnitude of the present Output current on L3.
1.3.6.1.4.1.2947.1.4.13NodeupsOutput3PhaseApparentPower
1.3.6.1.4.1.2947.1.4.13.1ScalarupsOutputApparentPowerL1read-onlymandatoryThe magnitude of the present Output ApparentPower on L1.
1.3.6.1.4.1.2947.1.4.13.2ScalarupsOutputApparentPowerL2read-onlymandatoryThe magnitude of the present Output ApparentPower on L2.
1.3.6.1.4.1.2947.1.4.13.3ScalarupsOutputApparentPowerL3read-onlymandatoryThe magnitude of the present Output ApparentPower on L3.
1.3.6.1.4.1.2947.1.4.14NodeupsOutput3PhaseTruePower
1.3.6.1.4.1.2947.1.4.14.1ScalarupsOutputTruePowerL1read-onlymandatoryThe magnitude of the present Output TruePower on L1.
1.3.6.1.4.1.2947.1.4.14.2ScalarupsOutputTruePowerL2read-onlymandatoryThe magnitude of the present Output TruePower on L2.
1.3.6.1.4.1.2947.1.4.14.3ScalarupsOutputTruePowerL3read-onlymandatoryThe magnitude of the present Output TruePower on L3.
1.3.6.1.4.1.2947.1.4.15NodeupsOutput3PhasePowerFactor
1.3.6.1.4.1.2947.1.4.15.1ScalarupsOutputPowerFactorL1read-onlymandatoryThe magnitude of the present Output PowerFactor on L1.
1.3.6.1.4.1.2947.1.4.15.2ScalarupsOutputPowerFactorL2read-onlymandatoryThe magnitude of the present Output PowerFactor on L2.
1.3.6.1.4.1.2947.1.4.15.3ScalarupsOutputPowerFactorL3read-onlymandatoryThe magnitude of the present Output PowerFactor on L3.
1.3.6.1.4.1.2947.1.4.16NodeupsOutput3PhasePercentLoad
1.3.6.1.4.1.2947.1.4.16.1ScalarupsOutputPercentLoadL1read-onlymandatoryThe magnitude of the present Output PercentLoad on L1.
1.3.6.1.4.1.2947.1.4.16.2ScalarupsOutputPercentLoadL2read-onlymandatoryThe magnitude of the present Output PercentLoad on L2.
1.3.6.1.4.1.2947.1.4.16.3ScalarupsOutputPercentLoadL3read-onlymandatoryThe magnitude of the present Output PercentLoad on L3.
1.3.6.1.4.1.2947.1.5NodeupsConfig
1.3.6.1.4.1.2947.1.5NodeupsTrapLowRuntimeSEVERE: The runtime remaining on battery power is very short, and the UPS will soon shut down.
1.3.6.1.4.1.2947.1.5.3ScalarupsConfigDelayBeforeShutdownread-writemandatoryThe delay in seconds that the UPS waits before executing an off command upon request of an external device.
1.3.6.1.4.1.2947.1.5.4TableupsConfigTestScheduleTablenot-accessiblemandatoryThe table to schedule ups battery tests.
1.3.6.1.4.1.2947.1.5.4.1RowupsConfigTestScheduleEntrynot-accessiblemandatoryThe entries for each day.
1.3.6.1.4.1.2947.1.5.4.1.1ColumnupsConfigTestScheduleIndexread-onlymandatoryThe index of scheduled events.
1.3.6.1.4.1.2947.1.5.4.1.2ColumnupsConfigTestScheduleDayread-writemandatoryThe weekday on which the UPS should shut down.
1.3.6.1.4.1.2947.1.5.4.1.3ColumnupsConfigTestScheduleTimeread-writemandatoryThe time that the process of shutting down the UPS will be initiated
1.3.6.1.4.1.2947.1.5.5TableupsConfigShutdownScheduleTablenot-accessiblemandatoryThe table to schedule shutting down the ups.
1.3.6.1.4.1.2947.1.5.5.1RowupsConfigShutdownScheduleEntrynot-accessiblemandatoryThe entries for each day.
1.3.6.1.4.1.2947.1.5.5.1.1ColumnupsConfigShutdownScheduleIndexread-onlymandatoryThe index of scheduled events.
1.3.6.1.4.1.2947.1.5.5.1.2ColumnupsConfigScheduleShutdownDayread-writemandatoryThe weekday on which the UPS should shut down.
1.3.6.1.4.1.2947.1.5.5.1.3ColumnupsConfigScheduleShutdownTimeread-writemandatoryThe time that the process of shutting down the UPS will be initiated
1.3.6.1.4.1.2947.1.5.5.1.4ColumnupsConfigScheduleRestartDayread-writemandatoryThe weekday on which the UPS should restart
1.3.6.1.4.1.2947.1.5.5.1.5ColumnupsConfigScheduleRestartTimeread-writemandatoryThe time the UPS will restart in hh:mm:ss format.
1.3.6.1.4.1.2947.1.5.8NodeupsConfigbestLink
1.3.6.1.4.1.2947.1.5.8.1ScalarbestLinkHistoryLogFrequencyread-writemandatoryThe frequency of updating the history log in minutes.
1.3.6.1.4.1.2947.1.5.8.2ScalarbestLinkRefreshFrequencyread-writemandatoryThe frequency of saving configuration,history and event log data in non-volatile memory. If the value is set to 0, then saving data is disabled.
1.3.6.1.4.1.2947.1.5.8.3ScalarbestLinkNetIdread-writemandatoryThe IP address of the device. Setting this parameter causes BestLink to reboot.
1.3.6.1.4.1.2947.1.5.8.4ScalarbestLinkGatewayread-writemandatoryThe gateway address for the network BestLink is connected to.
1.3.6.1.4.1.2947.1.5.8.5ScalarbestLinkNetMaskread-writemandatoryThe net mask of the device.
1.3.6.1.4.1.2947.1.5.8.6ScalarbestLinkSysDateread-writemandatoryThe system date of the device. The date is in mm/dd/yyyy format. The range of system date is from 1/1/1980 to 12/31/2037.
1.3.6.1.4.1.2947.1.5.8.7ScalarbestLinkSysTimeread-writemandatoryThe system time of the device. The time is in hh:mm:ss format.
1.3.6.1.4.1.2947.1.5.8.8ScalarbestLinkTftpFileNameread-writemandatoryThe tftp file name that contains the software upgrade image.
1.3.6.1.4.1.2947.1.5.8.9ScalarbestLinkTftpHostread-writemandatoryThe tftp host IP address from where to get the image.
1.3.6.1.4.1.2947.1.5.8.10ScalarbestLinkFlashEEPROMread-writemandatorySaves the history log, eventlog, and configuration data to non-volatile memory.
1.3.6.1.4.1.2947.1.5.8.11ScalarbestLinkPrimaryTimeServerread-writemandatoryThe primary time server is responsible for sending the correct time to the UPS.
1.3.6.1.4.1.2947.1.5.8.12ScalarbestLinkSecondaryTimeServerread-writemandatoryThe secondary time server responsible for sending the correct time to the UPS.
1.3.6.1.4.1.2947.1.5.8.13ScalarbestLinkSoftwareVersionread-onlymandatoryThe version of BestLink software.
1.3.6.1.4.1.2947.1.5.8.14ScalarbestLinkMIBVersionread-onlymandatoryThe version of MIB implemented in SNMP/WEB Card software.
1.3.6.1.4.1.2947.1.5.8.15ScalarbestLinkDHCPControlread-writemandatoryEnable/Disable DHCP function of SNMP/WEB Card.
1.3.6.1.4.1.2947.1.5.8.16ScalarbestLinkTelnetControlread-writemandatoryEnable/Disable Telnet function of SNMP/WEB Card.
1.3.6.1.4.1.2947.1.5.8.17ScalarbestLinkTftpControlread-writemandatoryEnable/Disable TFTP function of SNMP/WEB Card.
1.3.6.1.4.1.2947.1.5.8.18ScalarbestLinkResetToDefaultread-writemandatoryReset all parameters of SNMP/WEB Card to default setting.
1.3.6.1.4.1.2947.1.5.8.19ScalarbestLinkRestartAgentread-writemandatoryRestart of SNMP/WEB Card.
1.3.6.1.4.1.2947.1.5.9NodeupsConfigTrapsReceivers
1.3.6.1.4.1.2947.1.5.9.1TableupsConfigTrapsReceiversTablenot-accessiblemandatoryA list of managers to send traps to.
1.3.6.1.4.1.2947.1.5.9.1.1RowupsConfigTrapsReceiversEntrynot-accessiblemandatoryThe managers to send traps to.
1.3.6.1.4.1.2947.1.5.9.1.1.1ColumntrapsIndexread-onlymandatoryThe index to a trap receiver entry.
1.3.6.1.4.1.2947.1.5.9.1.1.2ColumntrapsReceiverAddrread-writemandatoryThe IP address of the manager to send a trap to.
1.3.6.1.4.1.2947.1.5.9.1.1.3ColumnreceiverCommunityStringread-writemandatoryThe community name to use in the trap when sent to the manager.
1.3.6.1.4.1.2947.1.5.9.1.1.4ColumnseverityLevelread-writemandatoryThe severity threshold of traps to send to the manager. Traps are labeled by severity as informational(1), warning(2), severe(3). Only traps of equal or greate…
1.3.6.1.4.1.2947.1.5.9.1.1.5ColumnreceiverAcceptread-writemandatoryAn entry will become active if yes, otherwise it will be disabled.
1.3.6.1.4.1.2947.1.5.10NodeupsConfigRegisteredShutdownClients
1.3.6.1.4.1.2947.1.5.10.1TableupsRegisteredShutdownClientsTablenot-accessiblemandatoryA list of registered shutdown client table entries. The table contains zero, one, or many rows at any moment, depending upon the number of Netwatch clients reg…
1.3.6.1.4.1.2947.1.5.10.1.1RowupsRegisteredShutdownClientsEntrynot-accessiblemandatoryAn entry containing information applicable to a particular registered shutdown client.
1.3.6.1.4.1.2947.1.5.10.1.1.1ColumnupsRegisteredShutdownClientsIndexread-onlymandatoryAn index of alarm entries in the RegisteredShutdownClientsTable.
1.3.6.1.4.1.2947.1.5.10.1.1.2ColumnupsRegisteredShutdownClientsIPAddressread-onlymandatoryThe IP Address of the registered shutdown client
1.3.6.1.4.1.2947.1.5.10.2ScalarupsRegisteredShutdownClientsTotalNumberOfread-onlymandatoryThe total number of registered shutdown clients.
1.3.6.1.4.1.2947.1.5.11ScalarupsConfigAutoRestartread-writemandatoryThe status of the Auto Restart mode.
1.3.6.1.4.1.2947.1.5.12NodeupsConfigACFailEventActions
1.3.6.1.4.1.2947.1.5.12.1ScalarupsConfigDelayBeforeFirstWarningMessageread-writemandatoryThe amount of time to delay in seconds before sending the first AC Fail message.
1.3.6.1.4.1.2947.1.5.12.2ScalarupsConfigWarningIntervalread-writemandatoryThe amount of time to delay in seconds between sending the additional AC Fail messages.
1.3.6.1.4.1.2947.1.5.12.3ScalarupsConfigClientOperatingSystemShutdownread-writemandatoryDetermines whether or not to initiate a shutdown of all registered clients based on the AC Fail event with duration.
1.3.6.1.4.1.2947.1.5.12.4ScalarupsConfigDelayBeforeClientShutdownread-writemandatoryThe time allowed in seconds during an AC Fail condition before shutting down of all registered clients.
1.3.6.1.4.1.2947.1.5.13NodeupsConfigLowBatteryEventActions
1.3.6.1.4.1.2947.1.5.13.1ScalarupsConfigClientOsShutdownread-writemandatoryDetermines whether or not to initiate a shutdown of all registered clients based on the Low Battery condition.
1.3.6.1.4.1.2947.1.5.14ScalarupsConfigShutdownUPSAfterOSShdnread-writemandatorySetting this value to 1, enables the UPS to be shutdown after the registered clients operating systems have shutdown.
1.3.6.1.4.1.2947.1.6NodeupsControl
1.3.6.1.4.1.2947.1.6NodeupsTrapUPSCanRunOnBatteryINFORMATION: The UPS has returned from a low runtime condition.
1.3.6.1.4.1.2947.1.6.1ScalarupsControlTurnOffUPSread-writemandatorySetting this variable to UpsOff(2) causes the UPS to shut off. When the UPS is in the off state, the UPS will remain off until the ON/OFF switch is manually to…
1.3.6.1.4.1.2947.1.6.4ScalarupsControlActivateUpsSchedulingread-writemandatorySetting this variable to On(2) causes the UPS to activate the scheduling parameters that have been previously configured within the upsConfigDailyShutdownSched…
1.3.6.1.4.1.2947.1.6.5ScalarupsControlEnableGeneratorSensitivityread-writemandatorySetting this value to a value other than (disable) begins to increase the UPS ability to reject poor line sources for example from a poorly regulated AC genera…
1.3.6.1.4.1.2947.1.7NodeupsTest
1.3.6.1.4.1.2947.1.7NodeupsTrapNearLowBatterySEVERE: The UPS batteries are low and will soon be exhausted. If utility power is not restored the UPS will put itself to 'sleep' and immediately cut power to …
1.3.6.1.4.1.2947.1.7.1ScalarupsManualTestsread-writemandatorySetting this variable to any value other than (1) causes the UPS to perform a manual test or abort a particular test in progress.
1.3.6.1.4.1.2947.1.8NodeupsAlarm
1.3.6.1.4.1.2947.1.8NodeupsTrapHighBatteryWARNING: The battery charger voltage on the UPS has reached a value that is too high for safe battery maintenance.
1.3.6.1.4.1.2947.1.8.1ScalarupsAlarmsPresentread-onlymandatoryThe present number of active alarm conditions.
1.3.6.1.4.1.2947.1.8.2ScalarupsLastKnownAlarmread-onlymandatoryA unique identifier for an alarm condition. This value must remain constant. Value 'noAlarm(37)' will be returned if no Alarm has occured till the point of GET…
1.3.6.1.4.1.2947.1.8.3TableupsAlarmTablenot-accessiblemandatoryA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is …
1.3.6.1.4.1.2947.1.8.3.1RowupsAlarmEntrynot-accessiblemandatoryAn entry containing information applicable to a particular alarm.
1.3.6.1.4.1.2947.1.8.3.1.1ColumnupsAlarmIndexread-onlymandatoryAn index of alarm entries in the alarm log.
1.3.6.1.4.1.2947.1.8.3.1.2ColumnupsAlarmNameread-onlymandatoryA unique identifier for an alarm condition. This value must remain constant.
1.3.6.1.4.1.2947.1.8.3.1.3ColumnupsAlarmTimeread-onlymandatoryThe time that the alarm occurred in hh:mm:ss format.
1.3.6.1.4.1.2947.1.8.4NodeupsWellKnownAlarms
1.3.6.1.4.1.2947.1.8.4.1ScalarupsAlarmOnBatteryread-onlymandatoryThe UPS is drawing power from the batteries.
1.3.6.1.4.1.2947.1.8.4.2ScalarupsAlarmLowRuntimeread-onlymandatoryThe remaining battery runtime is less than or equal to the upsConfigLowRuntimeSetpoint.
1.3.6.1.4.1.2947.1.8.4.3ScalarupsAlarmNearLowBatteryread-onlymandatoryThe battery voltage on the UPS has reached a value where the inverter will not be able to function very much longer.
1.3.6.1.4.1.2947.1.8.4.4ScalarupsAlarmLowBatteryread-onlymandatoryThe battery voltage on the UPS has reached a value where the inverter has stopped providing output power to the connected load equipment. The UPS has shutdown …
1.3.6.1.4.1.2947.1.8.4.5ScalarupsAlarmHighBatteryread-onlymandatoryThe battery charger voltage on the UPS has reached a value that is too high for safe battery maintenance.
1.3.6.1.4.1.2947.1.8.4.6ScalarupsAlarmCheckBatteryread-onlymandatoryThe periodic battery test has failed. A manual test of the batteries needs to be performed to determine which battery\batteries need replaced.
1.3.6.1.4.1.2947.1.8.4.7ScalarupsAlarmReplaceBatteryread-onlymandatoryOne or more batteries have been determined to require replacement. Compatibility: Fortress II
1.3.6.1.4.1.2947.1.8.4.8ScalarupsAlarmCheckInverterread-onlymandatoryThe inverter has failed the automatic system test.
1.3.6.1.4.1.2947.1.8.4.9ScalarupsAlarmBatteriesDisconnectedread-onlymandatoryThe UPS has detected that the DC voltage needed to start up is too low or missing.
1.3.6.1.4.1.2947.1.8.4.10ScalarupsAlarmOutputOverloadread-onlymandatoryThe output load exceeds the UPS output capacity.
1.3.6.1.4.1.2947.1.8.4.11ScalarupsAlarmLowAcOutread-onlymandatoryThe output load has exceeded the UPS output capacity, and the UPS has shut down.
1.3.6.1.4.1.2947.1.8.4.12ScalarupsAlarmCircuitBreakerWarningread-onlymandatoryTo much load equipment has been connected to the UPS and has has caused excess current draw from the output.
1.3.6.1.4.1.2947.1.8.4.13ScalarupsAlarmCircuitBreakerShdnread-onlymandatoryThe UPS has shut down due to an extended excess of current draw from the output.
1.3.6.1.4.1.2947.1.8.4.14ScalarupsAlarmBypassOnread-onlymandatoryThe Bypass is presently engaged on the UPS.
1.3.6.1.4.1.2947.1.8.4.15ScalarupsAlarmAutoBypassread-onlymandatoryThe UPS has gone into the Auto Bypass mode to redirect power around the UPS circuitry.
1.3.6.1.4.1.2947.1.8.4.16ScalarupsAlarmSiteWiringFaultread-onlymandatoryThe UPS has found a problem in your wall outlet.
1.3.6.1.4.1.2947.1.8.4.17ScalarupsAlarmCheckFanread-onlymandatoryThe fan on the UPS has stopped
1.3.6.1.4.1.2947.1.8.4.18ScalarupsAlarmHighAmbTempread-onlymandatoryThe internal temperature inside the UPS is too hot.
1.3.6.1.4.1.2947.1.8.4.19ScalarupsAlarmHighHSTempread-onlymandatoryThe Inverter heatsink assembly inside the UPS is to hot .
1.3.6.1.4.1.2947.1.8.4.20ScalarupsAlarmHighXFMRTempread-onlymandatoryThe temperature of the main transformer inside the UPS is too hot .
1.3.6.1.4.1.2947.1.8.4.21ScalarupsAlarmHighPFMTempread-onlymandatoryThe temperature of the PFM module inside the UPS is too hot .
1.3.6.1.4.1.2947.1.8.4.22ScalarupsAlarmProbeMissingread-onlymandatoryOne or all of the sense probes has been disconnected on the UPS.
1.3.6.1.4.1.2947.1.8.4.23ScalarupsAlarmCheckPowerSupplyread-onlymandatoryThe internal DC supply voltages are attenuated or missing.
1.3.6.1.4.1.2947.1.8.4.24ScalarupsAlarmTapRegulatorread-onlymandatoryThe UPS detected a possible failure in the tap changer (open or welded relay, etc.)
1.3.6.1.4.1.2947.1.8.4.25ScalarupsAlarmRelayFailureread-onlymandatoryThere is a hardware problem inside the UPS.
1.3.6.1.4.1.2947.1.8.4.26ScalarupsAlarmCheckFuseread-onlymandatoryThe failure of one or more fuses has been detected.
1.3.6.1.4.1.2947.1.8.4.27ScalarupsAlarmCheckMOVread-onlymandatoryOne or more MOVs have failed due to a voltage surge.
1.3.6.1.4.1.2947.1.8.4.28ScalarupsAlarmMemoryErrorread-onlymandatoryThe UPS has lost the programmed settings in the memory of the logic board.
1.3.6.1.4.1.2947.1.8.4.29ScalarupsAlarmCallServiceread-onlymandatoryA hardware malfunction has occurred inside the UPS. Please consult a factory authorized service representative for assistance.
1.3.6.1.4.1.2947.1.8.4.30ScalarupsAlarmupsFailedread-onlymandatoryA general fault in the UPS has been detected.
1.3.6.1.4.1.2947.1.8.4.31ScalarupsAlarmUserTestread-onlymandatoryA user test of the alarm beeper is in progress.
1.3.6.1.4.1.2947.1.8.4.32ScalarupsAlarmTestInProgressread-onlymandatoryA test is in progress.
1.3.6.1.4.1.2947.1.8.4.33ScalarupsAlarmDiagnosticTestFailedread-onlymandatoryThe result of the last diagnostic test indicates a failure.
1.3.6.1.4.1.2947.1.8.4.34ScalarupsAlarmEPOread-onlymandatoryThe Emergency Power OFF feature has been activiated at the RS-232 port on the UPS.
1.3.6.1.4.1.2947.1.8.4.35ScalarupsAlarmUpsOffread-onlymandatoryThe output of the UPS is in the off state.
1.3.6.1.4.1.2947.1.8.4.36ScalarupsAlarmCommunicationsLostread-onlymandatoryA problem has been encountered in the communications between the agent and the UPS.
1.3.6.1.4.1.2947.1.9NodeupsBypass
1.3.6.1.4.1.2947.1.9NodeupsTrapBatteryOKINFORMATION: The UPS has returned from a near low or high battery condition.
1.3.6.1.4.1.2947.1.9.1ScalarupsBypassStatusread-onlymandatoryThe status of the bypass mode.
1.3.6.1.4.1.2947.1.9.2NodeupsBypass3PhaseVoltageLtoN
1.3.6.1.4.1.2947.1.9.2.1ScalarupsBypassVoltageL1toNread-onlymandatoryThe magnitude of the present Bypass voltage from L1 to Neutral.
1.3.6.1.4.1.2947.1.9.2.2ScalarupsBypassVoltageL2toNread-onlymandatoryThe magnitude of the present Bypass voltage from L2 to Neutral.
1.3.6.1.4.1.2947.1.9.2.3ScalarupsBypassVoltageL3toNread-onlymandatoryThe magnitude of the present Bypass voltage from L3 to Neutral.
1.3.6.1.4.1.2947.1.9.3NodeupsBypass3PhaseVoltageLtoL
1.3.6.1.4.1.2947.1.9.3.1ScalarupsBypassVoltageL1toL2read-onlymandatoryThe magnitude of the present Bypass voltage from L1 to L2.
1.3.6.1.4.1.2947.1.9.3.2ScalarupsBypassVoltageL2toL3read-onlymandatoryThe magnitude of the present Bypass voltage from L2 to L3.
1.3.6.1.4.1.2947.1.9.3.3ScalarupsBypassVoltageL3toL1read-onlymandatoryThe magnitude of the present Bypass voltage from L3 to L1.
1.3.6.1.4.1.2947.1.10NodeupsTrapLowBatterySEVERE: The UPS will run for approximately 2 minutes more and then put itself to sleep to prevent a complete discharge of the batteries.
1.3.6.1.4.1.2947.1.11NodeupsTrapCheckBatterySEVERE: The UPS has failed a scheduled or manual battery test.
1.3.6.1.4.1.2947.1.12NodeupsTrapReplaceBatterySEVERE: One or more UPS batteries need to be replaced.
1.3.6.1.4.1.2947.1.13NodeupsTrapCheckInverterSEVERE: The UPS has failed a scheduled or manual inverter test.
1.3.6.1.4.1.2947.1.14NodeupsTrapBatteriesDisconnectedWARNING: The UPS battery voltage is either too low or missing to start up.
1.3.6.1.4.1.2947.1.15NodeupsTrapOutputOverloadWARNING: The output load exceeds the UPS output capacity.
1.3.6.1.4.1.2947.1.16NodeupsTrapUPSNoLongerOverloadedINFORMATION: The UPS has returned from an output overload condition.
1.3.6.1.4.1.2947.1.17NodeupsTrapLowAcOutSEVERE: The output load has exceeded the UPS output capacity, and the UPS has shut down.
1.3.6.1.4.1.2947.1.18NodeupsTrapCircuitBreakerWarningSEVERE: To much load equipment has been connected to the UPS and has has caused excess current draw from the output.
1.3.6.1.4.1.2947.1.19NodeupsTrapCircuitBreakerOKINFORMATION: The UPS has returned from a circuit breaker warning condition.
1.3.6.1.4.1.2947.1.20NodeupsTrapCircuitBreakerShdnSEVERE: The UPS has shut down due to an extended excess of current draw from the output.
1.3.6.1.4.1.2947.1.21NodeupsTrapBypassOnSEVERE: The Bypass is presently engaged on the UPS.
1.3.6.1.4.1.2947.1.22NodeupsTrapUPSOnlineINFORMATION: The UPS has returned from an on bypass condition.
1.3.6.1.4.1.2947.1.23NodeupsTrapSiteWiringFaultSEVERE: The UPS has found a problem in your wall outlet.
1.3.6.1.4.1.2947.1.24NodeupsTrapCheckFanSEVERE: The fan on the UPS has stopped .
1.3.6.1.4.1.2947.1.25NodeupsTrapHighUPSTempSEVERE: The internal temperature inside the UPS is too hot.
1.3.6.1.4.1.2947.1.26NodeupsTrapTempOKINFORMATION: The UPS has returned from a high ambient temp condition.
1.3.6.1.4.1.2947.1.27NodeupsTrapHighHSTempSEVERE: The Inverter heatsink assembly inside the UPS is too hot .
1.3.6.1.4.1.2947.1.28NodeupsTrapHSTempOKINFORMATION: The UPS has returned from a high heatsink temp condition.
1.3.6.1.4.1.2947.1.29NodeupsTrapHighXFMRTempSEVERE: The temperature of the main transformer inside the UPS is too hot .
1.3.6.1.4.1.2947.1.30NodeupsTrapHighPFMTempSEVERE: The temperature of the PFM module inside the UPS is too hot.
1.3.6.1.4.1.2947.1.31NodeupsTrapProbeMissingSEVERE: One or all of the temperature probes has been disconnected on the UPS.
1.3.6.1.4.1.2947.1.32NodeupsTrapProbeReconnectedINFORMATION: The UPS has returned from a probe missing condition.
1.3.6.1.4.1.2947.1.33NodeupsTrapCheckPowerSupplySEVERE: The internal DC supply voltages are attenuated or missing.
1.3.6.1.4.1.2947.1.34NodeupsTrapTapRegulatorFaultSEVERE: The UPS detected a possible failure in the tap changer (open or welded relay, etc.)
1.3.6.1.4.1.2947.1.35NodeupsTrapRelayFailureSEVERE: There is a hardware problem inside the UPS.
1.3.6.1.4.1.2947.1.36NodeupsTrapCheckFuseSEVERE: The failure of one or more fuses has been detected.
1.3.6.1.4.1.2947.1.37NodeupsTrapCheckMOVSEVERE: One or more MOVs have failed due to a voltage surge.
1.3.6.1.4.1.2947.1.38NodeupsTrapMemoryErrorSEVERE: The UPS has lost the programmed settings in the memory of the logic board.
1.3.6.1.4.1.2947.1.39NodeupsTrapCallServiceSEVERE: A hardware malfunction has occurred inside the UPS. Please consult a factory authorized service representative for assistance.
1.3.6.1.4.1.2947.1.40NodeupsTrapManualAlarmBeeperTestInitiatedINFORMATION: A manual test of the alarm beeper is being performed on the UPS.
1.3.6.1.4.1.2947.1.41NodeupsTrapManualAlarmBeeperTestAbortedINFORMATION: The test of UPS has completed.
1.3.6.1.4.1.2947.1.42NodeupsTrapScheduledTestInProgressINFORMATION: A test is in progress.
1.3.6.1.4.1.2947.1.43NodeupsTrapScheduledTestFailedSEVERE: The last test performed failed.
1.3.6.1.4.1.2947.1.44NodeupsTrapCommunicationLostSEVERE: Communication to the UPS has been lost. Steps to reestablish communication are in progress.
1.3.6.1.4.1.2947.1.45NodeupsTrapCommunicationRestoredINFORMATION: Communication with the UPS has been restored.
1.3.6.1.4.1.2947.1.46NodeupsTrapUPSGoingDownWARNING: The ups has been given shutdown command by the management station.
1.3.6.1.4.1.2947.1.47NodeupsTrapUPSTurnedOffINFORMATION: The ups has been turned off by the management station.
1.3.6.1.4.1.2947.1.48NodeupsTrapUPSSleepingINFORMATION: The UPS has entered in 'sleep' mode. Power to the load has been cut off.
1.3.6.1.4.1.2947.1.49NodeupsTrapUPSWokeUpINFORMATION: The UPS woke up from 'sleep' mode. Power to the load has been restored.
1.3.6.1.4.1.2947.1.50NodeupsTrapUPSRebootedINFORMATION: The UPS is rebooted.
1.3.6.1.4.1.2947.1.51NodeupsTrapEmergencyPowerOFFSEVERE: The Emergency Power OFF feature has been activiated at the RS-232 port on the UPS.
1.3.6.1.4.1.2947.1.52NodeupsTrapHistLogWarnWARNING: The ups history log buffer is almost full.
1.3.6.1.4.1.2947.1.53NodeupsTrapEventLogWarnWARNING: The ups event log buffer is almost full.
1.3.6.1.4.1.2947.1.54NodeupsTrapUPSFailSEVERE: A critical fault has been detected inside the UPS. Power to the load has been shut off.