MIB Viewer

CAREL-ug40cdz-MIB

176 objects
This is the MIB module for the UG40 Close Control Uniflair device.
Imported Objects
RFC1213-MIBDisplayString
SNMPv2-CONFOBJECT-GROUP
SNMPv2-MIBsysContact sysLocation sysName
SNMPv2-SMIenterprises Integer32 MODULE-IDENTITY OBJECT-TYPE
OIDNameAccessStatusDescription
1.3.6.1.4.1.9839Nodecarel
1.3.6.1.4.1.9839.1Nodesystm
1.3.6.1.4.1.9839.1.1ScalaragentReleaseread-onlycurrentRelease of the Agent.
1.3.6.1.4.1.9839.1.2ScalaragentCoderead-onlycurrentCode of the Agent. 1=WebGate
1.3.6.1.4.1.9839.2Nodeinstruments
1.3.6.1.4.1.9839.2.0NodewebGateInfo
1.3.6.1.4.1.9839.2.0.1NodeagentParameters
1.3.6.1.4.1.9839.2.0.1.1ScalarnetSizeread-writecurrentNetwork size. It corresponds to the number of units connected to the WebGate.
1.3.6.1.4.1.9839.2.0.1.2ScalarbaudRateread-writecurrentBaudrate of the Carel network.
1.3.6.1.4.1.9839.2.0.2NodeunitTypeGroup
1.3.6.1.4.1.9839.2.0.2.1Scalarunit1-Typeread-onlycurrentType of the unit having serial address 1.
1.3.6.1.4.1.9839.2.0.3NodeunitCodeGroup
1.3.6.1.4.1.9839.2.0.3.1Scalarunit1-Coderead-onlycurrentCode of the unit having serial address 1.
1.3.6.1.4.1.9839.2.0.4NodeunitSoftwareReleaseGroup
1.3.6.1.4.1.9839.2.0.4.1Scalarunit1-SoftwareReleaseread-onlycurrentSoftware release of the unit having serial address 1.
1.3.6.1.4.1.9839.2.0.5NodeunitMinSoftwareReleaseGroup
1.3.6.1.4.1.9839.2.0.5.1Scalarunit1-MinSoftwareReleaseread-onlycurrentMinimum software release of the unit having serial address 1.
1.3.6.1.4.1.9839.2.0.6NodeunitMaxSoftwareReleaseGroup
1.3.6.1.4.1.9839.2.0.6.1Scalarunit1-MaxSoftwareReleaseread-onlycurrentMaximum software release of the unit having serial address 1.
1.3.6.1.4.1.9839.2.0.7NodeunitNoAnswerCounterGroup
1.3.6.1.4.1.9839.2.0.7.1Scalarunit1-NoAnswerCounterread-onlycurrentNo answer counter of the unit having serial address 1.
1.3.6.1.4.1.9839.2.0.8NodeunitErrorChecksumCounterGroup
1.3.6.1.4.1.9839.2.0.8.1Scalarunit1-ErrorChecksumCounterread-onlycurrentError checksum counter of the unit having serial address 1.
1.3.6.1.4.1.9839.2.0.9NodeunitTimeoutCounterGroup
1.3.6.1.4.1.9839.2.0.9.1Scalarunit1-TimeoutCounterread-onlycurrentTimeout counter of the unit having serial address 1.
1.3.6.1.4.1.9839.2.1Identityug40cdzMIBThis is the MIB module for the UG40 Close Control Uniflair device.
1.3.6.1.4.1.9839.2.1.1NodedigitalObjects
1.3.6.1.4.1.9839.2.1.1.1ScalarsystemOnread-onlycurrentSystem On (Fan)
1.3.6.1.4.1.9839.2.1.1.2Scalarcompressore1read-onlycurrentCompressor 1
1.3.6.1.4.1.9839.2.1.1.3Scalarcompressore2read-onlycurrentCompressor 2
1.3.6.1.4.1.9839.2.1.1.4Scalarcompressore3read-onlycurrentCompressor 3
1.3.6.1.4.1.9839.2.1.1.5Scalarcompressore4read-onlycurrentCompressor 4
1.3.6.1.4.1.9839.2.1.1.6Scalarheating1read-onlycurrentHeating 1
1.3.6.1.4.1.9839.2.1.1.7Scalarheating2read-onlycurrentHeating 2
1.3.6.1.4.1.9839.2.1.1.9ScalarhotGasCoilread-onlycurrentHot Gas Coil
1.3.6.1.4.1.9839.2.1.1.10Scalardehumidificationread-onlycurrentDehumidification
1.3.6.1.4.1.9839.2.1.1.11Scalarhumidificationread-onlycurrentHumidification
1.3.6.1.4.1.9839.2.1.1.12Scalaremergread-onlycurrentMain Power Loss
1.3.6.1.4.1.9839.2.1.1.20ScalaralarmAccessread-onlycurrentTampering Alarm
1.3.6.1.4.1.9839.2.1.1.21ScalaralarmRoomHTread-onlycurrentAlarm: Room High Temperature
1.3.6.1.4.1.9839.2.1.1.22ScalaralarmRoomLTread-onlycurrentAlarm: Room Low Temperature
1.3.6.1.4.1.9839.2.1.1.23ScalaralarmRoomHHread-onlycurrentAlarm: Room High Humidity
1.3.6.1.4.1.9839.2.1.1.24ScalaralarmRoomLHread-onlycurrentAlarm: Room Low Humidity
1.3.6.1.4.1.9839.2.1.1.25ScalaralarmRoomEAPread-onlycurrentRoom T+H Limits by External Sensors
1.3.6.1.4.1.9839.2.1.1.26ScalaralarmFilterread-onlycurrentAlarm: Clogged Filter
1.3.6.1.4.1.9839.2.1.1.27ScalaralarmFloodread-onlycurrentAlarm: Water Leakage Detected
1.3.6.1.4.1.9839.2.1.1.28ScalaralarmAirFlowread-onlycurrentAlarm: Loss of Air Flow
1.3.6.1.4.1.9839.2.1.1.29ScalaralarmHeaterread-onlycurrentAlarm: Heater Overheating
1.3.6.1.4.1.9839.2.1.1.30ScalaralarmHP1read-onlycurrentAlarm: Circuit 1 High Pressure
1.3.6.1.4.1.9839.2.1.1.31ScalaralarmHP2read-onlycurrentAlarm: Circuit 1 High Pressure
1.3.6.1.4.1.9839.2.1.1.32ScalaralarmLP1read-onlycurrentAlarm: Circuit 1 Low Pressure
1.3.6.1.4.1.9839.2.1.1.33ScalaralarmLP2read-onlycurrentAlarm: Circuit 2 Low Pressure
1.3.6.1.4.1.9839.2.1.1.34ScalaralarmEXV1read-onlycurrentAlarm: Circuit 1 Electronic Valve Failure
1.3.6.1.4.1.9839.2.1.1.35ScalaralarmEXV2read-onlycurrentAlarm: Circuit 2 Electronic Valve Failure
1.3.6.1.4.1.9839.2.1.1.36ScalaralarmPSEread-onlycurrentAlarm: Wrong Phase Sequence
1.3.6.1.4.1.9839.2.1.1.37ScalaralarmSmokeFireread-onlycurrentAlarm: SMOKE-FIRE DETECTED
1.3.6.1.4.1.9839.2.1.1.38ScalaralarmLANread-onlycurrentInterrupted LAN Alarm
1.3.6.1.4.1.9839.2.1.1.39ScalaralarmHUHCread-onlycurrentAlarm: Humidifier High Current
1.3.6.1.4.1.9839.2.1.1.40ScalaralarmHUPLread-onlycurrentAlarm: Humidifier Power Loss
1.3.6.1.4.1.9839.2.1.1.41ScalaralarmHUWLread-onlycurrentAlarm: Humidifier Water Loss
1.3.6.1.4.1.9839.2.1.1.42ScalaralarmCWDHTread-onlycurrentAlarm: CW Temperature too High for Dehumidification
1.3.6.1.4.1.9839.2.1.1.43ScalaralarmCWFread-onlycurrentAlarm: CW Valve Failure or Water Flow too Low
1.3.6.1.4.1.9839.2.1.1.44ScalaralarmCWFFread-onlycurrentAlarm: Loss of Water Flow
1.3.6.1.4.1.9839.2.1.1.45ScalaralarmCWHTread-onlycurrentAlarm: High Chilled Water Temperature
1.3.6.1.4.1.9839.2.1.1.46ScalaralarmRTSread-onlycurrentAlarm: Room Temp. Sensor Failed/Disconnected
1.3.6.1.4.1.9839.2.1.1.47ScalaralarmHWSread-onlycurrentAlarm: Hot Water Temp. Sensor Failed/Disconnected
1.3.6.1.4.1.9839.2.1.1.48ScalaralarmCWSread-onlycurrentAlarm: Chilled Water Temp. Sensor Failed/Disconnected
1.3.6.1.4.1.9839.2.1.1.49ScalaralarmOTSread-onlycurrentAlarm: Outdoor Temperature Sensor Failed/Disconnected
1.3.6.1.4.1.9839.2.1.1.50ScalaralarmDTSread-onlycurrentAlarm: Delivery Air Temp. Sensor Failed/Disconnected
1.3.6.1.4.1.9839.2.1.1.51ScalaralarmRHSread-onlycurrentAlarm: Room Humidity Sensor Failed/Disconnected
1.3.6.1.4.1.9839.2.1.1.52ScalaralarmCWOTSread-onlycurrentAlarm: Chilled Water Outlet T. Sensor Failed/Disconnected
1.3.6.1.4.1.9839.2.1.1.53ScalaralarmC1Hoursread-onlycurrentServiceAlarm: Compressor 1 hour counter threshold
1.3.6.1.4.1.9839.2.1.1.54ScalaralarmC2Hoursread-onlycurrentServiceAlarm: Compressor 2 hour counter threshold
1.3.6.1.4.1.9839.2.1.1.55ScalaralarmC3Hoursread-onlycurrentServiceAlarm: Compressor 3 hour counter threshold
1.3.6.1.4.1.9839.2.1.1.56ScalaralarmC4Hoursread-onlycurrentServiceAlarm: Compressor 4 hour counter threshold
1.3.6.1.4.1.9839.2.1.1.57ScalaralarmFilterHoursread-onlycurrentServiceAlarm: Air Filter hour counter threshold
1.3.6.1.4.1.9839.2.1.1.58ScalaralarmHeat1Hoursread-onlycurrentServiceAlarm: Heater 1 hour counter threshold
1.3.6.1.4.1.9839.2.1.1.59ScalaralarmHeat2Hoursread-onlycurrentServiceAlarm: Heater 1 hour counter threshold
1.3.6.1.4.1.9839.2.1.1.60ScalaralarmHumHoursread-onlycurrentServiceAlarm: Humidifier hour counter threshold
1.3.6.1.4.1.9839.2.1.1.61ScalaralarmUnitHoursread-onlycurrentServiceAlarm: Unit hour counter threshold
1.3.6.1.4.1.9839.2.1.1.62ScalaralarmDI2read-onlycurrentAlarm by Digital Input 2
1.3.6.1.4.1.9839.2.1.1.63ScalaralarmDI4read-onlycurrentAlarm by Digital Input 4
1.3.6.1.4.1.9839.2.1.1.64ScalaralarmDI6read-onlycurrentAlarm by Digital Input 6
1.3.6.1.4.1.9839.2.1.1.65ScalaralarmHumread-onlycurrentHumidifier General Alarm
1.3.6.1.4.1.9839.2.1.1.66ScalaralarmGeneralread-onlycurrentGeneral Alarm
1.3.6.1.4.1.9839.2.1.1.67Scalaralarm2ndLevelread-onlycurrentStandby Unit Switchover Alarm
1.3.6.1.4.1.9839.2.1.1.68ScalaralarmAread-onlycurrentType A Alarm
1.3.6.1.4.1.9839.2.1.1.69ScalaralarmBread-onlycurrentType B Alarm
1.3.6.1.4.1.9839.2.1.1.70ScalaralarmCread-onlycurrentType C Alarm
1.3.6.1.4.1.9839.2.1.1.71ScalarselDXCWread-writecurrentDX/CW Switch on TC Units
1.3.6.1.4.1.9839.2.1.1.72ScalarselSWread-writecurrentSummer/Winter Switchover
1.3.6.1.4.1.9839.2.1.1.75ScalarsystemOnOffread-writecurrentSystem On-Off
1.3.6.1.4.1.9839.2.1.1.76ScalarresetAlarmread-writecurrentAlarm Reset
1.3.6.1.4.1.9839.2.1.1.77ScalarresetHrsFiltread-writecurrentFilter Run Hours Reset
1.3.6.1.4.1.9839.2.1.1.78ScalarresetHrC1read-writecurrentCompressor 1 Run Hours Reset
1.3.6.1.4.1.9839.2.1.1.79ScalarresetHrC2read-writecurrentCompressor 2 Run Hours Reset
1.3.6.1.4.1.9839.2.1.1.80ScalarresetHrC3read-writecurrentCompressor 3 Run Hours Reset
1.3.6.1.4.1.9839.2.1.1.81ScalarresetHrC4read-writecurrentCompressor 4 Run Hours Reset
1.3.6.1.4.1.9839.2.1.1.82ScalarresetStC1read-writecurrentCompressor 1 Starting Counter Reset
1.3.6.1.4.1.9839.2.1.1.83ScalarresetStC2read-writecurrentCompressor 2 Starting Counter Reset
1.3.6.1.4.1.9839.2.1.1.84ScalarresetStC3read-writecurrentCompressor 3 Starting Counter Reset
1.3.6.1.4.1.9839.2.1.1.85ScalarresetStC4read-writecurrentCompressor 4 Starting Counter Reset
1.3.6.1.4.1.9839.2.1.1.86ScalarresetHrH1read-writecurrentHeater 1 Run Hours Reset
1.3.6.1.4.1.9839.2.1.1.87ScalarresetHrH2read-writecurrentHeater 2 Run Hours Reset
1.3.6.1.4.1.9839.2.1.1.88ScalarresetStH1read-writecurrentHeater 1 Starting Counter Reset
1.3.6.1.4.1.9839.2.1.1.89ScalarresetStH2read-writecurrentHeater 2 Starting Counter Reset
1.3.6.1.4.1.9839.2.1.1.90ScalarresetHrHUread-writecurrentHumidifier Run Hours Reset
1.3.6.1.4.1.9839.2.1.1.91ScalarresetStHUread-writecurrentHumidifier Starting Counter Reset
1.3.6.1.4.1.9839.2.1.1.92ScalarresetHrACUread-writecurrentUnit Run Hours Reset
1.3.6.1.4.1.9839.2.1.1.95Scalarsleepmoderead-writecurrentSetback Mode (Sleep Mode)
1.3.6.1.4.1.9839.2.1.1.96Scalarsmtestread-writecurrentSleep Mode Test
1.3.6.1.4.1.9839.2.1.1.97ScalarenablemeanTread-writecurrentLocal/Mean Usage of Values
1.3.6.1.4.1.9839.2.1.2NodeanalogObjects
1.3.6.1.4.1.9839.2.1.2.1ScalarroomTempread-onlycurrentRoom Temperature
1.3.6.1.4.1.9839.2.1.2.2ScalaroutdoorTempread-onlycurrentAmbient Temperature
1.3.6.1.4.1.9839.2.1.2.3ScalardeliveryTempread-writecurrentDelivery Air Temperature
1.3.6.1.4.1.9839.2.1.2.4ScalarcwTempread-onlycurrentChilled Water Temperature
1.3.6.1.4.1.9839.2.1.2.5ScalarhwTempread-onlycurrentHot Water Temperature
1.3.6.1.4.1.9839.2.1.2.6ScalarroomRHread-onlycurrentRoom Relative Humidity
1.3.6.1.4.1.9839.2.1.2.7ScalarcwoTempread-onlycurrentChilled Water Outlet Temperature
1.3.6.1.4.1.9839.2.1.2.8ScalarevapPress1read-writecurrentCircuit 1 Evaporating Pressure
1.3.6.1.4.1.9839.2.1.2.9ScalarevapPress2read-writecurrentCircuit 2 Evaporating Pressure
1.3.6.1.4.1.9839.2.1.2.10ScalarsuctTemp1read-onlycurrentCircuit 1 Suction Temperature
1.3.6.1.4.1.9839.2.1.2.11ScalarsuctTemp2read-onlycurrentCircuit 2 Suction Temperature
1.3.6.1.4.1.9839.2.1.2.12ScalarevapTemp1read-onlycurrentCircuit 1 Evap.Temperature
1.3.6.1.4.1.9839.2.1.2.13ScalarevapTemp2read-onlycurrentCircuit 2 Evap.Temperature
1.3.6.1.4.1.9839.2.1.2.14Scalarssh1read-onlycurrentCircuit 1 Superheat
1.3.6.1.4.1.9839.2.1.2.15Scalarssh2read-onlycurrentCircuit 2 Superheat
1.3.6.1.4.1.9839.2.1.2.16ScalarcoolRampread-onlycurrentCooling Valve Ramp
1.3.6.1.4.1.9839.2.1.2.17ScalarheatRampread-onlycurrentHeating Valve Ramp
1.3.6.1.4.1.9839.2.1.2.18ScalarfanSpeedread-onlycurrentEvapor. Fan Speed
1.3.6.1.4.1.9839.2.1.2.20ScalarcoolSetPread-writecurrentCooling Set Point
1.3.6.1.4.1.9839.2.1.2.21ScalarcoolDiffread-writecurrentCooling Prop.Band
1.3.6.1.4.1.9839.2.1.2.22Scalarcool2SetPread-writecurrentCooling 2nd Set Point
1.3.6.1.4.1.9839.2.1.2.23ScalarheatSetPread-writecurrentHeating Set point
1.3.6.1.4.1.9839.2.1.2.24Scalarheat2SetPread-writecurrentHeating 2nd Set point
1.3.6.1.4.1.9839.2.1.2.25ScalarheatDiffread-writecurrentHeating Prop.Band
1.3.6.1.4.1.9839.2.1.2.26ScalarthrsHTread-writecurrentHigh Room Temperature Alarm Threshold
1.3.6.1.4.1.9839.2.1.2.27ScalarthrsLTread-writecurrentLow Room Temperature Alarm Threshold
1.3.6.1.4.1.9839.2.1.2.28ScalarsmCoolSetpread-writecurrentSetback Mode: Cooling Setpoint
1.3.6.1.4.1.9839.2.1.2.29ScalarsmHeatSetpread-writecurrentSetback Mode: Heating Setpoint
1.3.6.1.4.1.9839.2.1.2.30ScalarcwDehumSetpread-writecurrentCW Setpoint to Start Dehumidification
1.3.6.1.4.1.9839.2.1.2.31ScalarcwHtThrshread-writecurrentCW High Temperature Alarm Threshold
1.3.6.1.4.1.9839.2.1.2.32ScalarcwModeSetpread-writecurrentCW Setpoint to start CW Operating Mode (Only TC Units)
1.3.6.1.4.1.9839.2.1.2.33ScalarradcoolSpESread-writecurrentRadcooler Setpoint in Energy Saving Mode
1.3.6.1.4.1.9839.2.1.2.34ScalarradcoolSpDXread-writecurrentRadcooler Setpoint in DX Mode
1.3.6.1.4.1.9839.2.1.2.35ScalardelTempLimitread-writecurrentDelivery Temperature Low Limit Setpoint
1.3.6.1.4.1.9839.2.1.2.36ScalardtAutChgMLTread-writecurrentDelta Temperature for Automatic Mean/Local Changeover
1.3.6.1.4.1.9839.2.1.3NodeintegerObjects
1.3.6.1.4.1.9839.2.1.3.1ScalarfilterWorkHread-onlycurrentAir Filter Working Houres
1.3.6.1.4.1.9839.2.1.3.2ScalarunitWorkHread-onlycurrentUnit Working Houres
1.3.6.1.4.1.9839.2.1.3.3Scalarcompr1WorkHread-onlycurrentCompressor 1 Run Hours
1.3.6.1.4.1.9839.2.1.3.4Scalarcompr2WorkHread-onlycurrentCompressor 2 Run Hours
1.3.6.1.4.1.9839.2.1.3.5Scalarcompr3WorkHread-onlycurrentCompressor 3 Run Hours
1.3.6.1.4.1.9839.2.1.3.6Scalarcompr4WorkHread-onlycurrentCompressor 4 Run Hours
1.3.6.1.4.1.9839.2.1.3.7Scalarheat1WorkHread-onlycurrentHeater 1 Run Hours
1.3.6.1.4.1.9839.2.1.3.8Scalarheat2WorkHread-onlycurrentHeater 2 Run Hours
1.3.6.1.4.1.9839.2.1.3.9ScalarhumiWorkHread-onlycurrentHumidifier Run Hours
1.3.6.1.4.1.9839.2.1.3.12ScalardehumPbandread-writecurrentDehumidification Prop.Band
1.3.6.1.4.1.9839.2.1.3.13ScalarhumidPbandread-writecurrentHumidification Prop.Band
1.3.6.1.4.1.9839.2.1.3.14ScalarhhAlarmThrshread-writecurrentHigh Humidity Alarm Threshold
1.3.6.1.4.1.9839.2.1.3.15ScalarlhAlarmThrshread-writecurrentLow Humidity Alarm Threshold
1.3.6.1.4.1.9839.2.1.3.16ScalardehumSetpread-writecurrentDehumidification Setpoint
1.3.6.1.4.1.9839.2.1.3.17ScalarsmDehumSetpread-writecurrentSetback Mode: Dehumidification Setpoint
1.3.6.1.4.1.9839.2.1.3.18ScalarhumidSetpread-writecurrentHumidification Setpoint
1.3.6.1.4.1.9839.2.1.3.19ScalarsmHumidSetpread-writecurrentSetback Mode: Humidification Setpoint
1.3.6.1.4.1.9839.2.1.3.20ScalarpwOnDelayread-writecurrentRestart Delay
1.3.6.1.4.1.9839.2.1.3.21ScalarregulDelayread-writecurrentRegulation Start Transitory
1.3.6.1.4.1.9839.2.1.3.22ScalarlowPdelayread-writecurrentLow Pressure Delay
1.3.6.1.4.1.9839.2.1.3.23ScalarthAlarmdelayread-writecurrentTemp./Humid.Limits Alarm Delay
1.3.6.1.4.1.9839.2.1.3.24ScalarregExcTimeread-writecurrentAnti-Hunting Constant
1.3.6.1.4.1.9839.2.1.3.25ScalarstdbyTimeread-writecurrentStand-by Cycle Base Time
1.3.6.1.4.1.9839.2.1.3.27ScalarlanUnitread-writecurrentNumber of LAN Units
1.3.6.1.4.1.9839.2.1.3.28ScalarsmCycleTimeread-writecurrentSleep Mode Testing Cycle Time
1.3.6.1.4.1.9839.2.1.3.29Scalarexv1stepsread-onlycurrentCircuit 1 EXV Valve Position
1.3.6.1.4.1.9839.2.1.3.30Scalarexv2stepsread-onlycurrentCircuit 2 EXV Valve Position