CPQCMC-MIB
242 objects
No module-level DESCRIPTION found.
Imported Objects
| CPQHOST-MIB | BEGIN IMPORTS compaq |
| RFC-1212 | OBJECT-TYPE |
| RFC-1215 | TRAP-TYPE |
| RFC1213-MIB | DisplayString sysContact sysDescr sysLocation sysName |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.232.153 | NodecpqCmc | |||
| 1.3.6.1.4.1.232.153.1 | NodecpqCmcMibRev | |||
| 1.3.6.1.4.1.232.153.1.1 | ScalarcpqCmcMibRevMajor | read-only | mandatory | The Major Revision level. A change in the major revision level represents a major change in the architecture of the MIB. A change in the major revision level m… |
| 1.3.6.1.4.1.232.153.1.2 | ScalarcpqCmcMibRevMinor | read-only | mandatory | The Minor Revision level. A change in the minor revision level may represent some minor additional support, no changes to any pre-existing information has occu… |
| 1.3.6.1.4.1.232.153.1.3 | ScalarcpqCmcMibCondition | read-only | mandatory | The overall condition (status) of the system (rack(s)) represented by this MIB. (2) OK (3) a minor problem, warning condition (yellow LED on CMC) (4) a major p… |
| 1.3.6.1.4.1.232.153.2 | NodecpqCmcComponent | |||
| 1.3.6.1.4.1.232.153.2.1 | NodecpqCmcInterface | |||
| 1.3.6.1.4.1.232.153.2.1.1 | NodecpqCmcOsCommon | |||
| 1.3.6.1.4.1.232.153.2.1.1.1 | ScalarcpqCmcOsCommonPollFreq | read-write | mandatory | The Insight Agent's polling frequency. The frequency, in seconds, at which the Insight Agent requests information from the device driver. A frequency of zero (… |
| 1.3.6.1.4.1.232.153.2.2 | NodecpqCmcDevice | |||
| 1.3.6.1.4.1.232.153.2.2.1 | ScalarcpqCmcDeviceCondition | read-only | mandatory | Condition of CMC device, (3) an overload of the 24V DC supply to the connected accessories occurred (4) the overload-protection (fuse) has released |
| 1.3.6.1.4.1.232.153.2.2.2 | NodecpqCmcSetup | |||
| 1.3.6.1.4.1.232.153.2.2.2.1 | NodecpqCmcSetupConfig | |||
| 1.3.6.1.4.1.232.153.2.2.2.1.1 | NodecpqCmcSetupGeneral | |||
| 1.3.6.1.4.1.232.153.2.2.2.1.1.1 | ScalarcpqCmcsetLanguage | read-write | mandatory | Language of LCD |
| 1.3.6.1.4.1.232.153.2.2.2.1.1.2 | ScalarcpqCmcsetTempUnit | read-write | mandatory | Unit of all temperature values and thresholds, Celsius or Fahrenheit |
| 1.3.6.1.4.1.232.153.2.2.2.1.1.3 | ScalarcpqCmcsetAudibleAlarm | read-write | mandatory | Audible alarm in CMC unit: (2): silencing with button on CMC is enabled (3): silencing with button on CMC is disabled (4): audible alarm is off (general). On/o… |
| 1.3.6.1.4.1.232.153.2.2.2.1.1.4 | ScalarcpqCmcPassword | read-write | mandatory | Password to get access to terminal or LCD |
| 1.3.6.1.4.1.232.153.2.2.2.1.1.5 | ScalarcpqCmcPasswordOption | read-write | mandatory | Enable or disable password entry to get access to terminal or LCD |
| 1.3.6.1.4.1.232.153.2.2.2.1.1.6 | ScalarcpqCmcquitRelay1 | read-write | mandatory | Enable or disable acknowledging currently active alarm relay 1 (with 'ENTER' on CMC). |
| 1.3.6.1.4.1.232.153.2.2.2.1.1.7 | ScalarcpqCmcquitRelay2 | read-write | mandatory | Enable or disable acknowledging currently active alarm relay 2 (with 'ENTER' on CMC). |
| 1.3.6.1.4.1.232.153.2.2.2.1.1.8 | ScalarcpqCmclogicRelay1 | read-write | mandatory | Logic of Relay 1: (2) Relay will pick up in case of an alarm (3) Relay will release in case of an alarm (4) not used |
| 1.3.6.1.4.1.232.153.2.2.2.1.1.9 | ScalarcpqCmclogicRelay2 | read-write | mandatory | Logic of Relay 2: (2) Relay will pick up in case of an alarm (3) Relay will release in case of an alarm (4) not used |
| 1.3.6.1.4.1.232.153.2.2.2.1.2 | NodecpqCmcSetupEvents | |||
| 1.3.6.1.4.1.232.153.2.2.2.1.2.1 | NodecpqCmcSetupTemp1 | |||
| 1.3.6.1.4.1.232.153.2.2.2.1.2.1.1 | ScalarcpqCmcSetupTemp1Avail | read-write | mandatory | Temperature sensor: (2) sensor available (3) sensor not available |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.1.2 | ScalarcpqCmcSetupTemp1RelaysWarn | read-write | mandatory | Alert handling of Alarm Relays in case of warning condition of temperature sensor 1: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.1.3 | ScalarcpqCmcSetupTemp1RelaysMax | read-write | mandatory | Alert handling of Alarm Relays in case of max. alarm condition of temperature sensor 1: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will swi… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.1.4 | ScalarcpqCmcSetupTemp1RelaysMin | read-write | mandatory | Alert handling of Alarm Relays in case of min. alarm condition of temperature sensor 1: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will swi… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.1.5 | ScalarcpqCmcSetupTemp1AudibleAlarmWarn | read-write | mandatory | Alert handling of Audible Alarm of in case of warning condition of temperature sensor 1: (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.1.6 | ScalarcpqCmcSetupTemp1AudibleAlarmMax | read-write | mandatory | Alert handling of Audible Alarm of in case of max. alarm condition of temperature sensor 1: (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.1.7 | ScalarcpqCmcSetupTemp1AudibleAlarmMin | read-write | mandatory | Alert handling of Audible Alarm of in case of min. alarm condition of temperature sensor 1: (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.2 | NodecpqCmcSetupTemp2 | |||
| 1.3.6.1.4.1.232.153.2.2.2.1.2.2.1 | ScalarcpqCmcSetupTemp2Avail | read-write | mandatory | Temperature sensor: (2) sensor available (3) sensor not available |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.2.2 | ScalarcpqCmcSetupTemp2RelaysWarn | read-write | mandatory | Alert handling of Alarm Relays in case of warning condition of temperature sensor 2: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.2.3 | ScalarcpqCmcSetupTemp2RelaysMax | read-write | mandatory | Alert handling of Alarm Relays in case of max. alarm condition of temperature sensor 2: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will swi… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.2.4 | ScalarcpqCmcSetupTemp2RelaysMin | read-write | mandatory | Alert handling of Alarm Relays in case of min. alarm condition of temperature sensor 2: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will swi… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.2.5 | ScalarcpqCmcSetupTemp2AudibleAlarmWarn | read-write | mandatory | Alert handling of Audible Alarm of in case of warning condition of temperature sensor 2: (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.2.6 | ScalarcpqCmcSetupTemp2AudibleAlarmMax | read-write | mandatory | Alert handling of Audible Alarm of in case of max. alarm condition of temperature sensor 2: (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.2.7 | ScalarcpqCmcSetupTemp2AudibleAlarmMin | read-write | mandatory | Alert handling of Audible Alarm of in case of min. alarm condition of temperature sensor 2: (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.3 | NodecpqCmcSetupFan1 | |||
| 1.3.6.1.4.1.232.153.2.2.2.1.2.3.1 | ScalarcpqCmcSetupFan1Avail | read-write | mandatory | Fan 1: (2) Fan 1 available (3) Fan 1 not available |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.3.2 | ScalarcpqCmcSetupFan1Relays | read-write | mandatory | Alert handling of Alarm Relays in case of alarm condition of Fan 1: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays … |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.3.3 | ScalarcpqCmcSetupFan1AudibleAlarm | read-write | mandatory | Alert handling of Audible Alarm of in case of alarm condition of Fan 1: (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.4 | NodecpqCmcSetupFan2 | |||
| 1.3.6.1.4.1.232.153.2.2.2.1.2.4.1 | ScalarcpqCmcSetupFan2Avail | read-write | mandatory | Fan 2: (2) Fan 2 available (3) Fan 2 not available |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.4.2 | ScalarcpqCmcSetupFan2Relays | read-write | mandatory | Alert handling of Alarm Relays in case of alarm condition of Fan 2: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays … |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.4.3 | ScalarcpqCmcSetupFan2AudibleAlarm | read-write | mandatory | Alert handling of Audible Alarm of in case of alarm condition of Fan 2: (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.5 | NodecpqCmcSetupVoltage | |||
| 1.3.6.1.4.1.232.153.2.2.2.1.2.5.1 | ScalarcpqCmcSetupVoltageAvail | read-write | mandatory | Voltage monitoring: (2) available (3) not available |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.5.2 | ScalarcpqCmcSetupVoltageRelaysMax | read-write | mandatory | Alert handling of Alarm Relays in case of max. alarm condition of voltage monitoring: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switc… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.5.3 | ScalarcpqCmcSetupVoltageRelaysMin | read-write | mandatory | Alert handling of Alarm Relays in case of min. alarm condition of voltage monitoring: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switc… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.5.4 | ScalarcpqCmcSetupVoltageAudibleAlarmMax | read-write | mandatory | Alert handling of Audible Alarm of in case of max. alarm condition of voltage monitoring: (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.5.5 | ScalarcpqCmcSetupVoltageAudibleAlarmMin | read-write | mandatory | Alert handling of Audible Alarm of in case of min. alarm condition of voltage monitoring: (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.6 | NodecpqCmcSetupHumidity | |||
| 1.3.6.1.4.1.232.153.2.2.2.1.2.6.1 | ScalarcpqCmcSetupHumidityAvail | read-write | mandatory | Humidity sensor: (2) available (3) not available |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.6.2 | ScalarcpqCmcSetupHumidityRelaysMax | read-write | mandatory | Alert handling of Alarm Relays in case of max. alarm condition of humidity monitoring: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will swit… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.6.3 | ScalarcpqCmcSetupHumidityRelaysMin | read-write | mandatory | Alert handling of Alarm Relays in case of min. alarm condition of humidity monitoring: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will swit… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.6.4 | ScalarcpqCmcSetupHumidityAudibleAlarmMax | read-write | mandatory | Alert handling of Audible Alarm of in case of max. alarm condition of humidity monitoring: (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.6.5 | ScalarcpqCmcSetupHumidityAudibleAlarmMin | read-write | mandatory | Alert handling of Audible Alarm of in case of min. alarm condition of humidity monitoring: (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.7 | NodecpqCmcSetupInput1 | |||
| 1.3.6.1.4.1.232.153.2.2.2.1.2.7.1 | ScalarcpqCmcSetupInput1Avail | read-write | mandatory | Input 1 sensor: (2) available (3) not available |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.7.2 | ScalarcpqCmcSetupInput1Relays | read-write | mandatory | Alert handling of Alarm Relays in case of a warning condition of Input 1 (Door/Sidewall open): (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 w… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.7.3 | ScalarcpqCmcSetupInput1AudibleAlarm | read-write | mandatory | Alert handling of Audible Alarm of in case of a warning condition of Input 1 (Door/Sidewall open): (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.7.4 | ScalarcpqCmcSetupInput1FansOff | read-write | mandatory | Fan switching off if Door/Sidewall 1 is opened: (2) both fans would be switched off (3) only fan1 will be switched off (4) only fan2 will be switched off (5) n… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.7.5 | ScalarcpqCmcSetupInput1ShockSensor | read-write | mandatory | Shock sensor function if Door/Sidewall 1 is opened: (2) Shock Sensor is off (disabled) (3) Shock Sensor is on (enabled) |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.7.6 | ScalarcpqCmcSetupInput1Description | read-write | mandatory | Descriptional text of Input1 |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.7.7 | ScalarcpqCmcSetupInput1Lock | read-write | mandatory | Door/Sidewall 1 is locked by: (2) no locking device (3) locking device 1 (4) locking device 2 (5) both locking devices |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.8 | NodecpqCmcSetupInput2 | |||
| 1.3.6.1.4.1.232.153.2.2.2.1.2.8.1 | ScalarcpqCmcSetupInput2Avail | read-write | mandatory | Input 2 sensor: (2) available (3) not available |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.8.2 | ScalarcpqCmcSetupInput2Relays | read-write | mandatory | Alert handling of Alarm Relays in case of a warning condition of Input 2 (Door/Sidewall open): (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 w… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.8.3 | ScalarcpqCmcSetupInput2AudibleAlarm | read-write | mandatory | Alert handling of Audible Alarm of in case of a warning condition of Input 2 (Door/Sidewall open): (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.8.4 | ScalarcpqCmcSetupInput2FansOff | read-write | mandatory | Fan switching off if Door/Sidewall 2 is opened: (2) both fans would be switched off (3) only fan1 will be switched off (4) only fan2 will be switched off (5) n… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.8.5 | ScalarcpqCmcSetupInput2ShockSensor | read-write | mandatory | Shock sensor function if Door/Sidewall 2 is opened: (2) Shock Sensor is off (disabled) (3) Shock Sensor is on (enabled) |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.8.6 | ScalarcpqCmcSetupInput2Description | read-write | mandatory | Descriptional text of Input2 |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.8.7 | ScalarcpqCmcSetupInput2Lock | read-write | mandatory | Door/Sidewall 2 is locked by: (2) no locking device (3) locking device 1 (4) locking device 2 (5) both locking devices |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.9 | NodecpqCmcSetupInput3 | |||
| 1.3.6.1.4.1.232.153.2.2.2.1.2.9.1 | ScalarcpqCmcSetupInput3Avail | read-write | mandatory | Input 3 sensor: (2) available (3) not available |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.9.2 | ScalarcpqCmcSetupInput3Relays | read-write | mandatory | Alert handling of Alarm Relays in case of a warning condition of Input 3 (Door/Sidewall open): (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 w… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.9.3 | ScalarcpqCmcSetupInput3AudibleAlarm | read-write | mandatory | Alert handling of Audible Alarm of in case of a warning condition of Input 3 (Door/Sidewall open): (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.9.4 | ScalarcpqCmcSetupInput3FansOff | read-write | mandatory | Fan switching off if Door/Sidewall 3 is opened: (2) both fans would be switched off (3) only fan1 will be switched off (4) only fan2 will be switched off (5) n… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.9.5 | ScalarcpqCmcSetupInput3ShockSensor | read-write | mandatory | Shock sensor function if Door/Sidewall 3 is opened: (2) Shock Sensor is off (disabled) (3) Shock Sensor is on (enabled) |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.9.6 | ScalarcpqCmcSetupInput3Description | read-write | mandatory | Descriptional text of Input3 |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.9.7 | ScalarcpqCmcSetupInput3Lock | read-write | mandatory | Door/Sidewall 3 is locked by: (2) no locking device (3) locking device 1 (4) locking device 2 (5) both locking devices |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.10 | NodecpqCmcSetupInput4 | |||
| 1.3.6.1.4.1.232.153.2.2.2.1.2.10.1 | ScalarcpqCmcSetupInput4Avail | read-write | mandatory | Input 4 sensor: (2) available (3) not available |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.10.2 | ScalarcpqCmcSetupInput4Relays | read-write | mandatory | Alert handling of Alarm Relays in case of a warning condition of Input 4 (Door/Sidewall open): (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 w… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.10.3 | ScalarcpqCmcSetupInput4AudibleAlarm | read-write | mandatory | Alert handling of Audible Alarm of in case of a warning condition of Input 4 (Door/Sidewall open): (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.10.4 | ScalarcpqCmcSetupInput4FansOff | read-write | mandatory | Fan switching off if Door/Sidewall 4 is opened: (2) both fans would be switched off (3) only fan1 will be switched off (4) only fan2 will be switched off (5) n… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.10.5 | ScalarcpqCmcSetupInput4ShockSensor | read-write | mandatory | Shock sensor function if Door/Sidewall 4 is opened: (2) Shock Sensor is off (disabled) (3) Shock Sensor is on (enabled) |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.10.6 | ScalarcpqCmcSetupInput4Description | read-write | mandatory | Descriptional text of Input4 |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.10.7 | ScalarcpqCmcSetupInput4Lock | read-write | mandatory | Door/Sidewall 4 is locked by: (2) no locking device (3) locking device 1 (4) locking device 2 (5) both locking devices |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.11 | NodecpqCmcSetupLock1 | |||
| 1.3.6.1.4.1.232.153.2.2.2.1.2.11.1 | ScalarcpqCmcSetupLock1Avail | read-write | mandatory | Door locking device 1: (2) device available (3) device not available, no alarm, if door is not locked |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.11.2 | ScalarcpqCmcSetupLock1Relays | read-write | mandatory | Alert handling of Alarm Relays in case of an alarm condition of Lock 1 (door not locked..): (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.11.3 | ScalarcpqCmcSetupLock1RelaysDevice | read-write | mandatory | Alert handling of Alarm Relays in case of an alarm condition of Locking device 1 (power fail, low battery...): (2) no switching of Relays (3) Relay 1 will swit… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.11.4 | ScalarcpqCmcSetupLock1AudibleAlarm | read-write | mandatory | Alert handling of Audible Alarm of in case of an alarm condition of Lock 1: (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.11.5 | ScalarcpqCmcSetupLock1AudibleAlarmDevice | read-write | mandatory | Alert handling of Audible Alarm of in case of an alarm condition of Locking device 1 (power fail, low battery..): (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.11.6 | ScalarcpqCmcSetupLock1Time | read-write | mandatory | Time in seconds while the lock 1 is unlocked after getting an unlock-command |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.11.7 | ScalarcpqCmcSetupLock1PwrFailUnlock | read-write | mandatory | Unlock door in case of power fail of locking device: (2) disabled (3) auto unlock the door (4) unlock door with remote signal |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.11.8 | ScalarcpqCmcSetupLock1BattLowUnlock | read-write | mandatory | Unlock door in case of low battery of locking device: (2) disabled (3) auto unlock the door (4) unlock door with remote signal |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.11.9 | ScalarcpqCmcSetupLock1NetFailUnlock | read-write | mandatory | Unlock door in case of network failure: (2) disabled (3) auto unlock the door (4) unlock door with remote signal |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.11.10 | ScalarcpqCmcSetupLock1LifeFailUnlock | read-write | mandatory | Unlock door in case of lifecheck failure (connection CMC<->locking device): (2) disabled (3) auto unlock the door (4) unlock door with remote signal |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.12 | NodecpqCmcSetupLock2 | |||
| 1.3.6.1.4.1.232.153.2.2.2.1.2.12.1 | ScalarcpqCmcSetupLock2Avail | read-write | mandatory | Door locking device 2: (2) device available (3) device not available, no alarm, if door is not locked |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.12.2 | ScalarcpqCmcSetupLock2Relays | read-write | mandatory | Alert handling of Alarm Relays in case of an alarm condition of Lock 2 (door not locked..): (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.12.3 | ScalarcpqCmcSetupLock2RelaysDevice | read-write | mandatory | Alert handling of Alarm Relays in case of an alarm condition of Locking device 2 (power fail, low battery...): (2) no switching of Relays (3) Relay 1 will swit… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.12.4 | ScalarcpqCmcSetupLock2AudibleAlarm | read-write | mandatory | Alert handling of Audible Alarm of in case of an alarm condition of Lock 2: (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.12.5 | ScalarcpqCmcSetupLock2AudibleAlarmDevice | read-write | mandatory | Alert handling of Audible Alarm of in case of an alarm condition of Locking device 2 (power fail, low battery..): (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.12.6 | ScalarcpqCmcSetupLock2Time | read-write | mandatory | Time in seconds while the lock 2 is unlocked after getting an unlock-command |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.12.7 | ScalarcpqCmcSetupLock2PwrFailUnlock | read-write | mandatory | Unlock door in case of power fail of locking device: (2) disabled (3) auto unlock the door (4) unlock door with remote signal |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.12.8 | ScalarcpqCmcSetupLock2BattLowUnlock | read-write | mandatory | Unlock door in case of low battery of locking device: (2) disabled (3) auto unlock the door (4) unlock door with remote signal |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.12.9 | ScalarcpqCmcSetupLock2NetFailUnlock | read-write | mandatory | Unlock door in case of network failure: (2) disabled (3) auto unlock the door (4) unlock door with remote signal |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.12.10 | ScalarcpqCmcSetupLock2LifeFailUnlock | read-write | mandatory | Unlock door in case of lifecheck failure (connection CMC<->locking device): (2) disabled (3) auto unlock the door (4) unlock door with remote signal |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.13 | NodecpqCmcSetupSmoke | |||
| 1.3.6.1.4.1.232.153.2.2.2.1.2.13.1 | ScalarcpqCmcSetupSmokeAvail | read-write | mandatory | Smoke sensor: (2) available (3) not available |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.13.2 | ScalarcpqCmcSetupSmokeRelays | read-write | mandatory | Alert handling of Alarm Relays in case of an alarm condition of Smoke Sensor: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) bo… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.13.3 | ScalarcpqCmcSetupSmokeAudibleAlarm | read-write | mandatory | Alert handling of Audible Alarm of in case of an alarm condition of Smoke Sensor: (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.13.4 | ScalarcpqCmcSetupSmokeFansOff | read-write | mandatory | Fan switching off if in case of smoke-alarm: (2) both fans would be switched off (3) only fan1 will be switched off (4) only fan2 will be switched off (5) no f… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.13.5 | ScalarcpqCmcSetupSmokeUnlock | read-write | mandatory | Lock is unlocked in case of smoke-alarm: (2) both locks will be unlocked (3) only lock1 will be unlocked (4) only lock2 will be unlocked (5) no lock will be un… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.14 | NodecpqCmcSetupShock | |||
| 1.3.6.1.4.1.232.153.2.2.2.1.2.14.1 | ScalarcpqCmcSetupShockAvail | read-write | mandatory | Shock sensor: (2) available (3) not available |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.14.2 | ScalarcpqCmcSetupShockRelays | read-write | mandatory | Alert handling of Alarm Relays in case of an alarm condition of Shock Sensor: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) bo… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.14.3 | ScalarcpqCmcSetupShockAudibleAlarm | read-write | mandatory | Alert handling of Audible Alarm of in case of an alarm condition of Shock Sensor: (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.14.4 | ScalarcpqCmcSetupShockSensitivity | read-write | mandatory | Sensitivity of shock-sensor. 1 = low sensitivity, 10 = high sensitivity |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.15 | NodecpqCmcSetupAux1 | |||
| 1.3.6.1.4.1.232.153.2.2.2.1.2.15.1 | ScalarcpqCmcSetupAux1Avail | read-write | mandatory | Aux 1 sensor: (2) available (3) not available |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.15.2 | ScalarcpqCmcSetupAux1Relays | read-write | mandatory | Alert handling of Alarm Relays in case of an alarm condition of Aux 1: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Rela… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.15.3 | ScalarcpqCmcSetupAux1AudibleAlarm | read-write | mandatory | Alert handling of Audible Alarm of in case of an alarm condition of Aux 1: (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.15.4 | ScalarcpqCmcSetupAux1InputType | read-write | mandatory | Type of other digital input (used for any digital signal): (2) contact is normally open, no alarm if contact is open, alarm if contact is closed (3) contact is… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.15.5 | ScalarcpqCmcSetupAux1Description | read-write | mandatory | Descriptional text of the digital input (Aux1) |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.15.6 | ScalarcpqCmcSetupAux1Unlock | read-write | mandatory | Lock will be unlocked with Aux-Input 1: (2) no lock will be unlocked (3) only lock1 will be unlocked (4) only lock2 will be unlocked (5) both locks will be unl… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.16 | NodecpqCmcSetupAux2 | |||
| 1.3.6.1.4.1.232.153.2.2.2.1.2.16.1 | ScalarcpqCmcSetupAux2Avail | read-write | mandatory | Aux 2 sensor: (2) available (3) not available |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.16.2 | ScalarcpqCmcSetupAux2Relays | read-write | mandatory | Alert handling of Alarm Relays in case of an alarm condition of Aux 2: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Rela… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.16.3 | ScalarcpqCmcSetupAux2AudibleAlarm | read-write | mandatory | Alert handling of Audible Alarm of in case of an alarm condition of Aux 2: (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.16.4 | ScalarcpqCmcSetupAux2InputType | read-write | mandatory | Type of other digital input (used for any digital signal): (2) contact is normally open, no alarm if contact is open, alarm if contact is closed (3) contact is… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.16.5 | ScalarcpqCmcSetupAux2Description | read-write | mandatory | Descriptional text of the digital input (Aux2) |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.16.6 | ScalarcpqCmcSetupAux2Unlock | read-write | mandatory | Lock will be unlocked with Aux-Input 2: (2) no lock will be unlocked (3) only lock1 will be unlocked (4) only lock2 will be unlocked (5) both locks will be unl… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.17 | NodecpqCmcSetupAlarm1 | |||
| 1.3.6.1.4.1.232.153.2.2.2.1.2.17.1 | ScalarcpqCmcSetupAlarm1Relays | read-write | mandatory | Alert handling of Alarm Relays in case of an alarm condition of Alarm 1: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Re… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.17.2 | ScalarcpqCmcSetupAlarm1AudibleAlarm | read-write | mandatory | Alert handling of Audible Alarm of in case of an alarm condition of Alarm 1: (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.17.3 | ScalarcpqCmcSetupAlarm1Description | read-write | mandatory | Descriptional text of alarm 1 |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.18 | NodecpqCmcSetupAlarm2 | |||
| 1.3.6.1.4.1.232.153.2.2.2.1.2.18.1 | ScalarcpqCmcSetupAlarm2Relays | read-write | mandatory | Alert handling of Alarm Relays in case of an alarm condition of Alarm 2: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Re… |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.18.2 | ScalarcpqCmcSetupAlarm2AudibleAlarm | read-write | mandatory | Alert handling of Audible Alarm of in case of an alarm condition of Alarm 2: (2) Start Audible Alarm (3) No Audible Alarm |
| 1.3.6.1.4.1.232.153.2.2.2.1.2.18.3 | ScalarcpqCmcSetupAlarm2Description | read-write | mandatory | Descriptional text of alarm 2 |
| 1.3.6.1.4.1.232.153.2.2.2.1.3 | NodecpqCmcSetupClock | |||
| 1.3.6.1.4.1.232.153.2.2.2.1.3.1 | ScalarcpqCmcSetupDate | read-write | mandatory | actual Date in format DD.MM.YYYY |
| 1.3.6.1.4.1.232.153.2.2.2.1.3.2 | ScalarcpqCmcSetupTime | read-write | mandatory | actual Time in format HH:MM:SS, HH (0-23), MM (0-59), SS (0-59) |
| 1.3.6.1.4.1.232.153.2.2.2.2 | NodecpqCmcSetupThreshold | |||
| 1.3.6.1.4.1.232.153.2.2.2.2.1 | ScalarcpqCmcThresholdMaxTemp1 | read-write | mandatory | Threshold value maximum temperature 1 |
| 1.3.6.1.4.1.232.153.2.2.2.2.2 | ScalarcpqCmcThresholdWarningTemp1 | read-write | mandatory | Threshold value warning temperature 1 |
| 1.3.6.1.4.1.232.153.2.2.2.2.3 | ScalarcpqCmcThresholdMinTemp1 | read-write | mandatory | Threshold value minimum temperature 1 |
| 1.3.6.1.4.1.232.153.2.2.2.2.4 | ScalarcpqCmcThresholdMaxTemp2 | read-write | mandatory | Threshold value maximum temperature 2 |
| 1.3.6.1.4.1.232.153.2.2.2.2.5 | ScalarcpqCmcThresholdWarningTemp2 | read-write | mandatory | Threshold value warning temperature 2 |
| 1.3.6.1.4.1.232.153.2.2.2.2.6 | ScalarcpqCmcThresholdMinTemp2 | read-write | mandatory | Threshold value minimum temperature 2 |
| 1.3.6.1.4.1.232.153.2.2.2.2.7 | ScalarcpqCmcThresholdFan1 | read-write | mandatory | Threshold Fan 1 in deg F or deg C, Fan 1 will start if temperature 1 exceeds this value |
| 1.3.6.1.4.1.232.153.2.2.2.2.8 | ScalarcpqCmcThresholdFan1Hysteresis | read-write | mandatory | Hystersis of Fan 1, Fan 1 will stop if temperature 1 falls below value of cpqCmcThresholdFan1 minus cpqCmcThresholdFan1Hysteresis |
| 1.3.6.1.4.1.232.153.2.2.2.2.9 | ScalarcpqCmcThresholdFan2 | read-write | mandatory | Threshold Fan 2 in deg F or deg C, Fan 2 will start if temperature 2 exceeds this value |
| 1.3.6.1.4.1.232.153.2.2.2.2.10 | ScalarcpqCmcThresholdFan2Hysteresis | read-write | mandatory | Hystersis of Fan 2, Fan 2 will stop if temperature 2 falls below value of cpqCmcThresholdFan2 minus cpqCmcThresholdFan2Hysteresis |
| 1.3.6.1.4.1.232.153.2.2.2.2.11 | ScalarcpqCmcThresholdMaxVoltage | read-write | mandatory | Threshold high value Voltage alarm |
| 1.3.6.1.4.1.232.153.2.2.2.2.12 | ScalarcpqCmcThresholdMinVoltage | read-write | mandatory | Threshold low value Voltage alarm |
| 1.3.6.1.4.1.232.153.2.2.2.2.13 | ScalarcpqCmcThresholdMaxHumidity | read-write | mandatory | Threshold high value Humidity alarm |
| 1.3.6.1.4.1.232.153.2.2.2.2.14 | ScalarcpqCmcThresholdMinHumidity | read-write | mandatory | Threshold low value Humidity alarm |
| 1.3.6.1.4.1.232.153.2.2.2.3 | NodecpqCmcTraps | |||
| 1.3.6.1.4.1.232.153.2.2.2.3.1 | ScalarcpqCmcTrapTableNumber | read-only | mandatory | Number of trapTable entries. The number of trap-receivers |
| 1.3.6.1.4.1.232.153.2.2.2.3.2 | TablecpqCmcTrapTable | not-accessible | mandatory | A list of trap-receiver entries |
| 1.3.6.1.4.1.232.153.2.2.2.3.2.1 | RowcpqCmcTrapEntry | not-accessible | mandatory | Entries of trapTable |
| 1.3.6.1.4.1.232.153.2.2.2.3.2.1.1 | ColumncpqCmcTrapIndex | read-only | mandatory | Index for the trap-receiver-table. Its value ranges between 1 and the value of cpqCmcTrapTableNumber |
| 1.3.6.1.4.1.232.153.2.2.2.3.2.1.2 | ColumncpqCmcTrapStatus | read-write | mandatory | Enable or disable trap receiver |
| 1.3.6.1.4.1.232.153.2.2.2.3.2.1.3 | ColumncpqCmcTrapIPaddress | read-write | mandatory | IP-address of trap-receiver |
| 1.3.6.1.4.1.232.153.2.2.3 | NodecpqCmcValues | |||
| 1.3.6.1.4.1.232.153.2.2.3.1 | ScalarcpqCmcValueTemp1 | read-only | mandatory | Actual temperature value of temperature sensor 1 in deg C or deg F |
| 1.3.6.1.4.1.232.153.2.2.3.2 | ScalarcpqCmcValueTemp2 | read-only | mandatory | Actual temperature value of temperature sensor 2 in deg C or deg F |
| 1.3.6.1.4.1.232.153.2.2.3.3 | ScalarcpqCmcValueVoltage | read-only | mandatory | Actual value of power supply (voltage monitoring and fans) in V |
| 1.3.6.1.4.1.232.153.2.2.3.4 | ScalarcpqCmcValueHumidity | read-only | mandatory | Actual value of humidity 0..100% |
| 1.3.6.1.4.1.232.153.2.2.3.5 | ScalarcpqCmcValueOperatingTime | read-only | mandatory | Operating time CMC-unit |
| 1.3.6.1.4.1.232.153.2.2.4 | NodecpqCmcStatus | |||
| 1.3.6.1.4.1.232.153.2.2.4.1 | ScalarcpqCmcStatusTemp1 | read-only | mandatory | The status of temperature 1, see thresholds of temperature 1: (2) temperature normal (3) temperature exceeds warning threshold (4) temperature exceeds max. thr… |
| 1.3.6.1.4.1.232.153.2.2.4.2 | ScalarcpqCmcStatusTemp2 | read-only | mandatory | The status of temperature 2, see thresholds of temperature 2: (2) temperature normal (3) temperature exceeds warning threshold (4) temperature exceeds max. thr… |
| 1.3.6.1.4.1.232.153.2.2.4.3 | ScalarcpqCmcStatusFan1 | read-only | mandatory | The status of fan 1: (2) fan is switched off by temperature sensor 1 (3) fan is switched on by temperature sensor 1 (4) fan is switched off by Manual Control (… |
| 1.3.6.1.4.1.232.153.2.2.4.4 | ScalarcpqCmcStatusFan2 | read-only | mandatory | The status of fan 2: (2) fan is switched off by temperature sensor 2 (3) fan is switched on by temperature sensor 2 (4) fan is switched off by Manual Control (… |
| 1.3.6.1.4.1.232.153.2.2.4.5 | ScalarcpqCmcStatusVoltage | read-only | mandatory | The voltage-status, see thresholds of power supply: (2) voltage normal (3) voltage exceeds max. threshold (4) voltage drops under min. threshold (5) no power c… |
| 1.3.6.1.4.1.232.153.2.2.4.6 | ScalarcpqCmcStatusHumidity | read-only | mandatory | The humidity-status, see thresholds of humidity: (2) humidity normal (3) humidity exceeds max. threshold (4) humidity drops under min. threshold (5) no sensor … |
| 1.3.6.1.4.1.232.153.2.2.4.7 | ScalarcpqCmcStatusInput1 | read-only | mandatory | The status of door/sidepanel 1, closed (2), open (3) or no sensor connected (4) |
| 1.3.6.1.4.1.232.153.2.2.4.8 | ScalarcpqCmcStatusInput2 | read-only | mandatory | The status of door/sidepanel 2, closed (2), open (3) or no sensor connected (4) |
| 1.3.6.1.4.1.232.153.2.2.4.9 | ScalarcpqCmcStatusInput3 | read-only | mandatory | The status of door/sidepanel 3, closed (2), open (3) or no sensor connected (4) |
| 1.3.6.1.4.1.232.153.2.2.4.10 | ScalarcpqCmcStatusInput4 | read-only | mandatory | The status of door/sidepanel 4, closed (2), open (3) or no sensor connected (4) |
| 1.3.6.1.4.1.232.153.2.2.4.11 | ScalarcpqCmcStatusLock1Lock | read-only | mandatory | The status of door locking 1 (2) Door locking-device is activated, door is locked (3) Door locking-device is not activated, door is unlocked by Network Managem… |
| 1.3.6.1.4.1.232.153.2.2.4.12 | ScalarcpqCmcStatusLock2Lock | read-only | mandatory | The status of door locking 2 (2) Door locking-device is activated, door is locked (3) Door locking-device is not activated, door is unlocked by Network Managem… |
| 1.3.6.1.4.1.232.153.2.2.4.13 | ScalarcpqCmcStatusSmoke | read-only | mandatory | Status smoke-sensor, OK (2), smoke detected (3) or no sensor connected (4) |
| 1.3.6.1.4.1.232.153.2.2.4.14 | ScalarcpqCmcStatusShock | read-only | mandatory | Status Shock sensor, OK (2), shock detected (3) or no sensor connected (4) |
| 1.3.6.1.4.1.232.153.2.2.4.15 | ScalarcpqCmcStatusAux1 | read-only | mandatory | Status aux. digital input |
| 1.3.6.1.4.1.232.153.2.2.4.16 | ScalarcpqCmcStatusAux2 | read-only | mandatory | Status aux. digital input |
| 1.3.6.1.4.1.232.153.2.2.4.17 | ScalarcpqCmcStatusAlarm1 | read-only | mandatory | Status of alarm 1, see cmpCmcsetAlarm1. This alarm can be set from the Network management system. A descriptional text for this alarm can be set in cpqCmcSetup… |
| 1.3.6.1.4.1.232.153.2.2.4.18 | ScalarcpqCmcStatusAlarm2 | read-only | mandatory | Status of alarm 2, see cmpCmcsetAlarm2. This alarm can be set from the Network management system. A descriptional text for this alarm can be set in cpqCmcSetup… |
| 1.3.6.1.4.1.232.153.2.2.4.19 | ScalarcpqCmcStatusLock1Dev | read-only | mandatory | The status of door-locking device 1 (2) OK (3) Power fail of door locking-device (4) Low Battery of door locking-device (5) Battery of door locking device need… |
| 1.3.6.1.4.1.232.153.2.2.4.20 | ScalarcpqCmcStatusLock2Dev | read-only | mandatory | The status of door-locking device 2 (2) OK (3) Power fail of door locking-device (4) Low Battery of door locking-device (5) Battery of door locking device need… |
| 1.3.6.1.4.1.232.153.2.2.5 | NodecpqCmcControl | |||
| 1.3.6.1.4.1.232.153.2.2.5.1 | ScalarcpqCmcStatusAccess | read-write | mandatory | Status access, for future use |
| 1.3.6.1.4.1.232.153.2.2.5.2 | ScalarcpqCmcSetLock1Lock | read-write | mandatory | Set door locking device 1, see table With this command the management-station can set the conditions for the door locking device (2) Door will be locked (3) Do… |
| 1.3.6.1.4.1.232.153.2.2.5.3 | ScalarcpqCmcSetLock1Key | read-write | mandatory | Enable or disable unlocking of the rack-door with external components like keypad or remote input. With this command the management station can set the conditi… |
| 1.3.6.1.4.1.232.153.2.2.5.4 | ScalarcpqCmcSetLock2Lock | read-write | mandatory | Set door locking device 2, see table With this command the management-station can set the conditions for the door locking device (2) Door will be locked (3) Do… |
| 1.3.6.1.4.1.232.153.2.2.5.5 | ScalarcpqCmcSetLock2Key | read-write | mandatory | Enable or disable unlocking of the rack-door with external components like keypad or remote input. With this command the management-station can set the conditi… |
| 1.3.6.1.4.1.232.153.2.2.5.6 | ScalarcpqCmcSetMessage | read-write | mandatory | Set message to CMC, for future use |
| 1.3.6.1.4.1.232.153.2.2.5.7 | ScalarcpqCmcSetAlarm1 | read-write | mandatory | Is used to set an alarm in the CMC from the management-station. With this command the management-station can i.e. switch on an alarm-relay or the AudibleAlarm … |
| 1.3.6.1.4.1.232.153.2.2.5.8 | ScalarcpqCmcSetAlarm2 | read-write | mandatory | Is used to set an alarm in the CMC from the management-station. With this command the management-station can i.e. switch on an alarm-relay or the AudibleAlarm … |
| 1.3.6.1.4.1.232.153.2.2.5.9 | ScalarcpqCmcSetFan1 | read-write | mandatory | Is used for run and stop control of fan1. (2) fan will run and stop according to temperature of sensor 1 and threshold of fan1 (3) fan will run independent of … |
| 1.3.6.1.4.1.232.153.2.2.5.10 | ScalarcpqCmcSetFan2 | read-write | mandatory | Is used for run and stop control of fan2. (2) fan will run and stop according to temperature of sensor 2 and threshold of fan2 (3) fan will run independent of … |
| 1.3.6.1.4.1.232.153.2.2.5.11 | ScalarcpqCmcSetQuitRelay1 | read-write | mandatory | Status and quit of alarm relay 1. (2) relay is switched because of an alarm (3) relay is not switched, no alarm (4) (set) will quit relay 1 in case of alarm |
| 1.3.6.1.4.1.232.153.2.2.5.12 | ScalarcpqCmcSetQuitRelay2 | read-write | mandatory | Status and quit of alarm relay 2. (2) relay is switched because of an alarm (3) relay is not switched, no alarm (4) (set) will quit relay 2 in case of alarm |
| 1.3.6.1.4.1.232.153.2.2.6 | NodecpqCmcLog | |||
| 1.3.6.1.4.1.232.153.2.2.6.1 | ScalarcpqCmcLogsNumber | read-only | mandatory | Number of Log-entries |
| 1.3.6.1.4.1.232.153.2.2.6.2 | TablecpqCmcLogTable | not-accessible | mandatory | Log-table |
| 1.3.6.1.4.1.232.153.2.2.6.2.1 | RowcpqCmcLogEntry | not-accessible | mandatory | Log-table entries |
| 1.3.6.1.4.1.232.153.2.2.6.2.1.1 | ColumncpqCmcLogIndex | read-only | mandatory | Index for the Log-table. Its value ranges between 1 and the value of cpqCmcLogsNumber |
| 1.3.6.1.4.1.232.153.2.2.6.2.1.2 | ColumncpqCmcLogDate | read-only | mandatory | Date of log information. |
| 1.3.6.1.4.1.232.153.2.2.6.2.1.3 | ColumncpqCmcLogTime | read-only | mandatory | Time of log information. |
| 1.3.6.1.4.1.232.153.2.2.6.2.1.4 | ColumncpqCmcLogText | read-only | mandatory | Log information. |
| 1.3.6.1.4.1.232.153.2.2.6.2.1.5 | ColumncpqCmcLogClass | read-only | mandatory | Status of log information. |
| 1.3.6.1.4.1.232.153.153001 | NodecpqCmcalarmTemp1 | The temperature at rack sensor 1 is outside the specified threshold. Action: Check the air handling system for the rack and refer to Trap Details for more info… | ||
| 1.3.6.1.4.1.232.153.153002 | NodecpqCmcalarmTemp2 | The temperature at rack sensor 2 is outside the specified threshold. Action: Check the air handling system for the rack and refer to Trap Details for more info… | ||
| 1.3.6.1.4.1.232.153.153003 | NodecpqCmcalarmFan1 | The status of Fan 1 has changed. Action: Refer to Trap Details for more information. | ||
| 1.3.6.1.4.1.232.153.153004 | NodecpqCmcalarmFan2 | The status of Fan 2 has changed. Action: Refer to Trap Details for more information. | ||
| 1.3.6.1.4.1.232.153.153005 | NodecpqCmcalarmVoltage | The AC voltage of the rack is outside the specified threshold. Action: Check the incoming power source and ensure all cables are inserted correctly. | ||
| 1.3.6.1.4.1.232.153.153006 | NodecpqCmcalarmHumidity | The humidity of the rack is outside the specified threshold. Action: Check the air handling system for the rack and refer to Trap Details for more information. | ||
| 1.3.6.1.4.1.232.153.153007 | NodecpqCmcalarmInput1 | The door or sidepanel of the rack has been opened (access point #1). Action: Check for unauthorized intrusion and refer to Trap Details for more information. | ||
| 1.3.6.1.4.1.232.153.153008 | NodecpqCmcalarmInput2 | The door or sidepanel of the rack has been opened (access point #2). Action: Check for unauthorized intrusion and refer to Trap Details for more information. | ||
| 1.3.6.1.4.1.232.153.153009 | NodecpqCmcalarmInput3 | The door or sidepanel of the rack has been opened (access point #3). Action: Check for unauthorized intrusion and refer to Trap Details for more information. | ||
| 1.3.6.1.4.1.232.153.153010 | NodecpqCmcalarmInput4 | The door or sidepanel of the rack has been opened (access point #4). Action: Check for unauthorized intrusion and refer to Trap Details for more information. | ||
| 1.3.6.1.4.1.232.153.153011 | NodecpqCmcalarmLock1 | Rack door lock #1 alarm. Action: Ensure the door is completely closed and check for unauthorized intrusion and refer to Trap Details for more information. | ||
| 1.3.6.1.4.1.232.153.153012 | NodecpqCmcalarmLock2 | Rack door lock #2 alarm. Action: Ensure the door is completely closed and check for unauthorized intrusion and refer to Trap Details for more information. | ||
| 1.3.6.1.4.1.232.153.153013 | NodecpqCmcalarmSmoke | The rack smoke detector has detected smoke. Action: Investigate rack for an over temperature condition and refer to Trap Details for more information. | ||
| 1.3.6.1.4.1.232.153.153014 | NodecpqCmcalarmShock | The rack shock detector has detected a vibration to the rack. Action: Investigate rack. | ||
| 1.3.6.1.4.1.232.153.153015 | NodecpqCmcalarmAux1 | The rack auxiliary alarm input #1 has been triggered. | ||
| 1.3.6.1.4.1.232.153.153016 | NodecpqCmcalarmAux2 | The rack auxiliary alarm input #2 has been triggered. | ||
| 1.3.6.1.4.1.232.153.153017 | NodecpqCmcalarm1 | Alarm 1, set from Network management | ||
| 1.3.6.1.4.1.232.153.153018 | NodecpqCmcalarm2 | Alarm 2, set from Network management | ||
| 1.3.6.1.4.1.232.153.153019 | NodecpqCmcalarmLock1Dev | The rack door locking device #1 has failed. Action: Check the device lock cable or failed battery and refer to Trap Details for more information. | ||
| 1.3.6.1.4.1.232.153.153020 | NodecpqCmcalarmLock2Dev | The rack door locking device #2 has failed. Action: Check the device lock cable or failed battery and refer to Trap Details for more information. | ||
| 1.3.6.1.4.1.232.153.153100 | NodecpqCmcSetupChanged | Setup of CMC has changed. |