CPQCMC-MIB

242 objects
No module-level DESCRIPTION found.
Imported Objects
CPQHOST-MIBBEGIN IMPORTS compaq
RFC-1212OBJECT-TYPE
RFC-1215TRAP-TYPE
RFC1213-MIBDisplayString sysContact sysDescr sysLocation sysName
OIDNameAccessStatusDescription
1.3.6.1.4.1.232.153NodecpqCmc
1.3.6.1.4.1.232.153.1NodecpqCmcMibRev
1.3.6.1.4.1.232.153.1.1ScalarcpqCmcMibRevMajorread-onlymandatoryThe Major Revision level. A change in the major revision level represents a major change in the architecture of the MIB. A change in the major revision level m…
1.3.6.1.4.1.232.153.1.2ScalarcpqCmcMibRevMinorread-onlymandatoryThe Minor Revision level. A change in the minor revision level may represent some minor additional support, no changes to any pre-existing information has occu…
1.3.6.1.4.1.232.153.1.3ScalarcpqCmcMibConditionread-onlymandatoryThe overall condition (status) of the system (rack(s)) represented by this MIB. (2) OK (3) a minor problem, warning condition (yellow LED on CMC) (4) a major p…
1.3.6.1.4.1.232.153.2NodecpqCmcComponent
1.3.6.1.4.1.232.153.2.1NodecpqCmcInterface
1.3.6.1.4.1.232.153.2.1.1NodecpqCmcOsCommon
1.3.6.1.4.1.232.153.2.1.1.1ScalarcpqCmcOsCommonPollFreqread-writemandatoryThe Insight Agent's polling frequency. The frequency, in seconds, at which the Insight Agent requests information from the device driver. A frequency of zero (…
1.3.6.1.4.1.232.153.2.2NodecpqCmcDevice
1.3.6.1.4.1.232.153.2.2.1ScalarcpqCmcDeviceConditionread-onlymandatoryCondition of CMC device, (3) an overload of the 24V DC supply to the connected accessories occurred (4) the overload-protection (fuse) has released
1.3.6.1.4.1.232.153.2.2.2NodecpqCmcSetup
1.3.6.1.4.1.232.153.2.2.2.1NodecpqCmcSetupConfig
1.3.6.1.4.1.232.153.2.2.2.1.1NodecpqCmcSetupGeneral
1.3.6.1.4.1.232.153.2.2.2.1.1.1ScalarcpqCmcsetLanguageread-writemandatoryLanguage of LCD
1.3.6.1.4.1.232.153.2.2.2.1.1.2ScalarcpqCmcsetTempUnitread-writemandatoryUnit of all temperature values and thresholds, Celsius or Fahrenheit
1.3.6.1.4.1.232.153.2.2.2.1.1.3ScalarcpqCmcsetAudibleAlarmread-writemandatoryAudible alarm in CMC unit: (2): silencing with button on CMC is enabled (3): silencing with button on CMC is disabled (4): audible alarm is off (general). On/o…
1.3.6.1.4.1.232.153.2.2.2.1.1.4ScalarcpqCmcPasswordread-writemandatoryPassword to get access to terminal or LCD
1.3.6.1.4.1.232.153.2.2.2.1.1.5ScalarcpqCmcPasswordOptionread-writemandatoryEnable or disable password entry to get access to terminal or LCD
1.3.6.1.4.1.232.153.2.2.2.1.1.6ScalarcpqCmcquitRelay1read-writemandatoryEnable or disable acknowledging currently active alarm relay 1 (with 'ENTER' on CMC).
1.3.6.1.4.1.232.153.2.2.2.1.1.7ScalarcpqCmcquitRelay2read-writemandatoryEnable or disable acknowledging currently active alarm relay 2 (with 'ENTER' on CMC).
1.3.6.1.4.1.232.153.2.2.2.1.1.8ScalarcpqCmclogicRelay1read-writemandatoryLogic of Relay 1: (2) Relay will pick up in case of an alarm (3) Relay will release in case of an alarm (4) not used
1.3.6.1.4.1.232.153.2.2.2.1.1.9ScalarcpqCmclogicRelay2read-writemandatoryLogic of Relay 2: (2) Relay will pick up in case of an alarm (3) Relay will release in case of an alarm (4) not used
1.3.6.1.4.1.232.153.2.2.2.1.2NodecpqCmcSetupEvents
1.3.6.1.4.1.232.153.2.2.2.1.2.1NodecpqCmcSetupTemp1
1.3.6.1.4.1.232.153.2.2.2.1.2.1.1ScalarcpqCmcSetupTemp1Availread-writemandatoryTemperature sensor: (2) sensor available (3) sensor not available
1.3.6.1.4.1.232.153.2.2.2.1.2.1.2ScalarcpqCmcSetupTemp1RelaysWarnread-writemandatoryAlert handling of Alarm Relays in case of warning condition of temperature sensor 1: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch…
1.3.6.1.4.1.232.153.2.2.2.1.2.1.3ScalarcpqCmcSetupTemp1RelaysMaxread-writemandatoryAlert handling of Alarm Relays in case of max. alarm condition of temperature sensor 1: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will swi…
1.3.6.1.4.1.232.153.2.2.2.1.2.1.4ScalarcpqCmcSetupTemp1RelaysMinread-writemandatoryAlert handling of Alarm Relays in case of min. alarm condition of temperature sensor 1: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will swi…
1.3.6.1.4.1.232.153.2.2.2.1.2.1.5ScalarcpqCmcSetupTemp1AudibleAlarmWarnread-writemandatoryAlert handling of Audible Alarm of in case of warning condition of temperature sensor 1: (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.1.6ScalarcpqCmcSetupTemp1AudibleAlarmMaxread-writemandatoryAlert handling of Audible Alarm of in case of max. alarm condition of temperature sensor 1: (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.1.7ScalarcpqCmcSetupTemp1AudibleAlarmMinread-writemandatoryAlert handling of Audible Alarm of in case of min. alarm condition of temperature sensor 1: (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.2NodecpqCmcSetupTemp2
1.3.6.1.4.1.232.153.2.2.2.1.2.2.1ScalarcpqCmcSetupTemp2Availread-writemandatoryTemperature sensor: (2) sensor available (3) sensor not available
1.3.6.1.4.1.232.153.2.2.2.1.2.2.2ScalarcpqCmcSetupTemp2RelaysWarnread-writemandatoryAlert handling of Alarm Relays in case of warning condition of temperature sensor 2: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch…
1.3.6.1.4.1.232.153.2.2.2.1.2.2.3ScalarcpqCmcSetupTemp2RelaysMaxread-writemandatoryAlert handling of Alarm Relays in case of max. alarm condition of temperature sensor 2: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will swi…
1.3.6.1.4.1.232.153.2.2.2.1.2.2.4ScalarcpqCmcSetupTemp2RelaysMinread-writemandatoryAlert handling of Alarm Relays in case of min. alarm condition of temperature sensor 2: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will swi…
1.3.6.1.4.1.232.153.2.2.2.1.2.2.5ScalarcpqCmcSetupTemp2AudibleAlarmWarnread-writemandatoryAlert handling of Audible Alarm of in case of warning condition of temperature sensor 2: (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.2.6ScalarcpqCmcSetupTemp2AudibleAlarmMaxread-writemandatoryAlert handling of Audible Alarm of in case of max. alarm condition of temperature sensor 2: (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.2.7ScalarcpqCmcSetupTemp2AudibleAlarmMinread-writemandatoryAlert handling of Audible Alarm of in case of min. alarm condition of temperature sensor 2: (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.3NodecpqCmcSetupFan1
1.3.6.1.4.1.232.153.2.2.2.1.2.3.1ScalarcpqCmcSetupFan1Availread-writemandatoryFan 1: (2) Fan 1 available (3) Fan 1 not available
1.3.6.1.4.1.232.153.2.2.2.1.2.3.2ScalarcpqCmcSetupFan1Relaysread-writemandatoryAlert handling of Alarm Relays in case of alarm condition of Fan 1: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays …
1.3.6.1.4.1.232.153.2.2.2.1.2.3.3ScalarcpqCmcSetupFan1AudibleAlarmread-writemandatoryAlert handling of Audible Alarm of in case of alarm condition of Fan 1: (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.4NodecpqCmcSetupFan2
1.3.6.1.4.1.232.153.2.2.2.1.2.4.1ScalarcpqCmcSetupFan2Availread-writemandatoryFan 2: (2) Fan 2 available (3) Fan 2 not available
1.3.6.1.4.1.232.153.2.2.2.1.2.4.2ScalarcpqCmcSetupFan2Relaysread-writemandatoryAlert handling of Alarm Relays in case of alarm condition of Fan 2: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays …
1.3.6.1.4.1.232.153.2.2.2.1.2.4.3ScalarcpqCmcSetupFan2AudibleAlarmread-writemandatoryAlert handling of Audible Alarm of in case of alarm condition of Fan 2: (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.5NodecpqCmcSetupVoltage
1.3.6.1.4.1.232.153.2.2.2.1.2.5.1ScalarcpqCmcSetupVoltageAvailread-writemandatoryVoltage monitoring: (2) available (3) not available
1.3.6.1.4.1.232.153.2.2.2.1.2.5.2ScalarcpqCmcSetupVoltageRelaysMaxread-writemandatoryAlert handling of Alarm Relays in case of max. alarm condition of voltage monitoring: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switc…
1.3.6.1.4.1.232.153.2.2.2.1.2.5.3ScalarcpqCmcSetupVoltageRelaysMinread-writemandatoryAlert handling of Alarm Relays in case of min. alarm condition of voltage monitoring: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switc…
1.3.6.1.4.1.232.153.2.2.2.1.2.5.4ScalarcpqCmcSetupVoltageAudibleAlarmMaxread-writemandatoryAlert handling of Audible Alarm of in case of max. alarm condition of voltage monitoring: (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.5.5ScalarcpqCmcSetupVoltageAudibleAlarmMinread-writemandatoryAlert handling of Audible Alarm of in case of min. alarm condition of voltage monitoring: (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.6NodecpqCmcSetupHumidity
1.3.6.1.4.1.232.153.2.2.2.1.2.6.1ScalarcpqCmcSetupHumidityAvailread-writemandatoryHumidity sensor: (2) available (3) not available
1.3.6.1.4.1.232.153.2.2.2.1.2.6.2ScalarcpqCmcSetupHumidityRelaysMaxread-writemandatoryAlert handling of Alarm Relays in case of max. alarm condition of humidity monitoring: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will swit…
1.3.6.1.4.1.232.153.2.2.2.1.2.6.3ScalarcpqCmcSetupHumidityRelaysMinread-writemandatoryAlert handling of Alarm Relays in case of min. alarm condition of humidity monitoring: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will swit…
1.3.6.1.4.1.232.153.2.2.2.1.2.6.4ScalarcpqCmcSetupHumidityAudibleAlarmMaxread-writemandatoryAlert handling of Audible Alarm of in case of max. alarm condition of humidity monitoring: (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.6.5ScalarcpqCmcSetupHumidityAudibleAlarmMinread-writemandatoryAlert handling of Audible Alarm of in case of min. alarm condition of humidity monitoring: (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.7NodecpqCmcSetupInput1
1.3.6.1.4.1.232.153.2.2.2.1.2.7.1ScalarcpqCmcSetupInput1Availread-writemandatoryInput 1 sensor: (2) available (3) not available
1.3.6.1.4.1.232.153.2.2.2.1.2.7.2ScalarcpqCmcSetupInput1Relaysread-writemandatoryAlert handling of Alarm Relays in case of a warning condition of Input 1 (Door/Sidewall open): (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 w…
1.3.6.1.4.1.232.153.2.2.2.1.2.7.3ScalarcpqCmcSetupInput1AudibleAlarmread-writemandatoryAlert handling of Audible Alarm of in case of a warning condition of Input 1 (Door/Sidewall open): (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.7.4ScalarcpqCmcSetupInput1FansOffread-writemandatoryFan switching off if Door/Sidewall 1 is opened: (2) both fans would be switched off (3) only fan1 will be switched off (4) only fan2 will be switched off (5) n…
1.3.6.1.4.1.232.153.2.2.2.1.2.7.5ScalarcpqCmcSetupInput1ShockSensorread-writemandatoryShock sensor function if Door/Sidewall 1 is opened: (2) Shock Sensor is off (disabled) (3) Shock Sensor is on (enabled)
1.3.6.1.4.1.232.153.2.2.2.1.2.7.6ScalarcpqCmcSetupInput1Descriptionread-writemandatoryDescriptional text of Input1
1.3.6.1.4.1.232.153.2.2.2.1.2.7.7ScalarcpqCmcSetupInput1Lockread-writemandatoryDoor/Sidewall 1 is locked by: (2) no locking device (3) locking device 1 (4) locking device 2 (5) both locking devices
1.3.6.1.4.1.232.153.2.2.2.1.2.8NodecpqCmcSetupInput2
1.3.6.1.4.1.232.153.2.2.2.1.2.8.1ScalarcpqCmcSetupInput2Availread-writemandatoryInput 2 sensor: (2) available (3) not available
1.3.6.1.4.1.232.153.2.2.2.1.2.8.2ScalarcpqCmcSetupInput2Relaysread-writemandatoryAlert handling of Alarm Relays in case of a warning condition of Input 2 (Door/Sidewall open): (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 w…
1.3.6.1.4.1.232.153.2.2.2.1.2.8.3ScalarcpqCmcSetupInput2AudibleAlarmread-writemandatoryAlert handling of Audible Alarm of in case of a warning condition of Input 2 (Door/Sidewall open): (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.8.4ScalarcpqCmcSetupInput2FansOffread-writemandatoryFan switching off if Door/Sidewall 2 is opened: (2) both fans would be switched off (3) only fan1 will be switched off (4) only fan2 will be switched off (5) n…
1.3.6.1.4.1.232.153.2.2.2.1.2.8.5ScalarcpqCmcSetupInput2ShockSensorread-writemandatoryShock sensor function if Door/Sidewall 2 is opened: (2) Shock Sensor is off (disabled) (3) Shock Sensor is on (enabled)
1.3.6.1.4.1.232.153.2.2.2.1.2.8.6ScalarcpqCmcSetupInput2Descriptionread-writemandatoryDescriptional text of Input2
1.3.6.1.4.1.232.153.2.2.2.1.2.8.7ScalarcpqCmcSetupInput2Lockread-writemandatoryDoor/Sidewall 2 is locked by: (2) no locking device (3) locking device 1 (4) locking device 2 (5) both locking devices
1.3.6.1.4.1.232.153.2.2.2.1.2.9NodecpqCmcSetupInput3
1.3.6.1.4.1.232.153.2.2.2.1.2.9.1ScalarcpqCmcSetupInput3Availread-writemandatoryInput 3 sensor: (2) available (3) not available
1.3.6.1.4.1.232.153.2.2.2.1.2.9.2ScalarcpqCmcSetupInput3Relaysread-writemandatoryAlert handling of Alarm Relays in case of a warning condition of Input 3 (Door/Sidewall open): (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 w…
1.3.6.1.4.1.232.153.2.2.2.1.2.9.3ScalarcpqCmcSetupInput3AudibleAlarmread-writemandatoryAlert handling of Audible Alarm of in case of a warning condition of Input 3 (Door/Sidewall open): (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.9.4ScalarcpqCmcSetupInput3FansOffread-writemandatoryFan switching off if Door/Sidewall 3 is opened: (2) both fans would be switched off (3) only fan1 will be switched off (4) only fan2 will be switched off (5) n…
1.3.6.1.4.1.232.153.2.2.2.1.2.9.5ScalarcpqCmcSetupInput3ShockSensorread-writemandatoryShock sensor function if Door/Sidewall 3 is opened: (2) Shock Sensor is off (disabled) (3) Shock Sensor is on (enabled)
1.3.6.1.4.1.232.153.2.2.2.1.2.9.6ScalarcpqCmcSetupInput3Descriptionread-writemandatoryDescriptional text of Input3
1.3.6.1.4.1.232.153.2.2.2.1.2.9.7ScalarcpqCmcSetupInput3Lockread-writemandatoryDoor/Sidewall 3 is locked by: (2) no locking device (3) locking device 1 (4) locking device 2 (5) both locking devices
1.3.6.1.4.1.232.153.2.2.2.1.2.10NodecpqCmcSetupInput4
1.3.6.1.4.1.232.153.2.2.2.1.2.10.1ScalarcpqCmcSetupInput4Availread-writemandatoryInput 4 sensor: (2) available (3) not available
1.3.6.1.4.1.232.153.2.2.2.1.2.10.2ScalarcpqCmcSetupInput4Relaysread-writemandatoryAlert handling of Alarm Relays in case of a warning condition of Input 4 (Door/Sidewall open): (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 w…
1.3.6.1.4.1.232.153.2.2.2.1.2.10.3ScalarcpqCmcSetupInput4AudibleAlarmread-writemandatoryAlert handling of Audible Alarm of in case of a warning condition of Input 4 (Door/Sidewall open): (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.10.4ScalarcpqCmcSetupInput4FansOffread-writemandatoryFan switching off if Door/Sidewall 4 is opened: (2) both fans would be switched off (3) only fan1 will be switched off (4) only fan2 will be switched off (5) n…
1.3.6.1.4.1.232.153.2.2.2.1.2.10.5ScalarcpqCmcSetupInput4ShockSensorread-writemandatoryShock sensor function if Door/Sidewall 4 is opened: (2) Shock Sensor is off (disabled) (3) Shock Sensor is on (enabled)
1.3.6.1.4.1.232.153.2.2.2.1.2.10.6ScalarcpqCmcSetupInput4Descriptionread-writemandatoryDescriptional text of Input4
1.3.6.1.4.1.232.153.2.2.2.1.2.10.7ScalarcpqCmcSetupInput4Lockread-writemandatoryDoor/Sidewall 4 is locked by: (2) no locking device (3) locking device 1 (4) locking device 2 (5) both locking devices
1.3.6.1.4.1.232.153.2.2.2.1.2.11NodecpqCmcSetupLock1
1.3.6.1.4.1.232.153.2.2.2.1.2.11.1ScalarcpqCmcSetupLock1Availread-writemandatoryDoor locking device 1: (2) device available (3) device not available, no alarm, if door is not locked
1.3.6.1.4.1.232.153.2.2.2.1.2.11.2ScalarcpqCmcSetupLock1Relaysread-writemandatoryAlert handling of Alarm Relays in case of an alarm condition of Lock 1 (door not locked..): (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will…
1.3.6.1.4.1.232.153.2.2.2.1.2.11.3ScalarcpqCmcSetupLock1RelaysDeviceread-writemandatoryAlert handling of Alarm Relays in case of an alarm condition of Locking device 1 (power fail, low battery...): (2) no switching of Relays (3) Relay 1 will swit…
1.3.6.1.4.1.232.153.2.2.2.1.2.11.4ScalarcpqCmcSetupLock1AudibleAlarmread-writemandatoryAlert handling of Audible Alarm of in case of an alarm condition of Lock 1: (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.11.5ScalarcpqCmcSetupLock1AudibleAlarmDeviceread-writemandatoryAlert handling of Audible Alarm of in case of an alarm condition of Locking device 1 (power fail, low battery..): (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.11.6ScalarcpqCmcSetupLock1Timeread-writemandatoryTime in seconds while the lock 1 is unlocked after getting an unlock-command
1.3.6.1.4.1.232.153.2.2.2.1.2.11.7ScalarcpqCmcSetupLock1PwrFailUnlockread-writemandatoryUnlock door in case of power fail of locking device: (2) disabled (3) auto unlock the door (4) unlock door with remote signal
1.3.6.1.4.1.232.153.2.2.2.1.2.11.8ScalarcpqCmcSetupLock1BattLowUnlockread-writemandatoryUnlock door in case of low battery of locking device: (2) disabled (3) auto unlock the door (4) unlock door with remote signal
1.3.6.1.4.1.232.153.2.2.2.1.2.11.9ScalarcpqCmcSetupLock1NetFailUnlockread-writemandatoryUnlock door in case of network failure: (2) disabled (3) auto unlock the door (4) unlock door with remote signal
1.3.6.1.4.1.232.153.2.2.2.1.2.11.10ScalarcpqCmcSetupLock1LifeFailUnlockread-writemandatoryUnlock door in case of lifecheck failure (connection CMC<->locking device): (2) disabled (3) auto unlock the door (4) unlock door with remote signal
1.3.6.1.4.1.232.153.2.2.2.1.2.12NodecpqCmcSetupLock2
1.3.6.1.4.1.232.153.2.2.2.1.2.12.1ScalarcpqCmcSetupLock2Availread-writemandatoryDoor locking device 2: (2) device available (3) device not available, no alarm, if door is not locked
1.3.6.1.4.1.232.153.2.2.2.1.2.12.2ScalarcpqCmcSetupLock2Relaysread-writemandatoryAlert handling of Alarm Relays in case of an alarm condition of Lock 2 (door not locked..): (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will…
1.3.6.1.4.1.232.153.2.2.2.1.2.12.3ScalarcpqCmcSetupLock2RelaysDeviceread-writemandatoryAlert handling of Alarm Relays in case of an alarm condition of Locking device 2 (power fail, low battery...): (2) no switching of Relays (3) Relay 1 will swit…
1.3.6.1.4.1.232.153.2.2.2.1.2.12.4ScalarcpqCmcSetupLock2AudibleAlarmread-writemandatoryAlert handling of Audible Alarm of in case of an alarm condition of Lock 2: (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.12.5ScalarcpqCmcSetupLock2AudibleAlarmDeviceread-writemandatoryAlert handling of Audible Alarm of in case of an alarm condition of Locking device 2 (power fail, low battery..): (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.12.6ScalarcpqCmcSetupLock2Timeread-writemandatoryTime in seconds while the lock 2 is unlocked after getting an unlock-command
1.3.6.1.4.1.232.153.2.2.2.1.2.12.7ScalarcpqCmcSetupLock2PwrFailUnlockread-writemandatoryUnlock door in case of power fail of locking device: (2) disabled (3) auto unlock the door (4) unlock door with remote signal
1.3.6.1.4.1.232.153.2.2.2.1.2.12.8ScalarcpqCmcSetupLock2BattLowUnlockread-writemandatoryUnlock door in case of low battery of locking device: (2) disabled (3) auto unlock the door (4) unlock door with remote signal
1.3.6.1.4.1.232.153.2.2.2.1.2.12.9ScalarcpqCmcSetupLock2NetFailUnlockread-writemandatoryUnlock door in case of network failure: (2) disabled (3) auto unlock the door (4) unlock door with remote signal
1.3.6.1.4.1.232.153.2.2.2.1.2.12.10ScalarcpqCmcSetupLock2LifeFailUnlockread-writemandatoryUnlock door in case of lifecheck failure (connection CMC<->locking device): (2) disabled (3) auto unlock the door (4) unlock door with remote signal
1.3.6.1.4.1.232.153.2.2.2.1.2.13NodecpqCmcSetupSmoke
1.3.6.1.4.1.232.153.2.2.2.1.2.13.1ScalarcpqCmcSetupSmokeAvailread-writemandatorySmoke sensor: (2) available (3) not available
1.3.6.1.4.1.232.153.2.2.2.1.2.13.2ScalarcpqCmcSetupSmokeRelaysread-writemandatoryAlert handling of Alarm Relays in case of an alarm condition of Smoke Sensor: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) bo…
1.3.6.1.4.1.232.153.2.2.2.1.2.13.3ScalarcpqCmcSetupSmokeAudibleAlarmread-writemandatoryAlert handling of Audible Alarm of in case of an alarm condition of Smoke Sensor: (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.13.4ScalarcpqCmcSetupSmokeFansOffread-writemandatoryFan switching off if in case of smoke-alarm: (2) both fans would be switched off (3) only fan1 will be switched off (4) only fan2 will be switched off (5) no f…
1.3.6.1.4.1.232.153.2.2.2.1.2.13.5ScalarcpqCmcSetupSmokeUnlockread-writemandatoryLock is unlocked in case of smoke-alarm: (2) both locks will be unlocked (3) only lock1 will be unlocked (4) only lock2 will be unlocked (5) no lock will be un…
1.3.6.1.4.1.232.153.2.2.2.1.2.14NodecpqCmcSetupShock
1.3.6.1.4.1.232.153.2.2.2.1.2.14.1ScalarcpqCmcSetupShockAvailread-writemandatoryShock sensor: (2) available (3) not available
1.3.6.1.4.1.232.153.2.2.2.1.2.14.2ScalarcpqCmcSetupShockRelaysread-writemandatoryAlert handling of Alarm Relays in case of an alarm condition of Shock Sensor: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) bo…
1.3.6.1.4.1.232.153.2.2.2.1.2.14.3ScalarcpqCmcSetupShockAudibleAlarmread-writemandatoryAlert handling of Audible Alarm of in case of an alarm condition of Shock Sensor: (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.14.4ScalarcpqCmcSetupShockSensitivityread-writemandatorySensitivity of shock-sensor. 1 = low sensitivity, 10 = high sensitivity
1.3.6.1.4.1.232.153.2.2.2.1.2.15NodecpqCmcSetupAux1
1.3.6.1.4.1.232.153.2.2.2.1.2.15.1ScalarcpqCmcSetupAux1Availread-writemandatoryAux 1 sensor: (2) available (3) not available
1.3.6.1.4.1.232.153.2.2.2.1.2.15.2ScalarcpqCmcSetupAux1Relaysread-writemandatoryAlert handling of Alarm Relays in case of an alarm condition of Aux 1: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Rela…
1.3.6.1.4.1.232.153.2.2.2.1.2.15.3ScalarcpqCmcSetupAux1AudibleAlarmread-writemandatoryAlert handling of Audible Alarm of in case of an alarm condition of Aux 1: (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.15.4ScalarcpqCmcSetupAux1InputTyperead-writemandatoryType of other digital input (used for any digital signal): (2) contact is normally open, no alarm if contact is open, alarm if contact is closed (3) contact is…
1.3.6.1.4.1.232.153.2.2.2.1.2.15.5ScalarcpqCmcSetupAux1Descriptionread-writemandatoryDescriptional text of the digital input (Aux1)
1.3.6.1.4.1.232.153.2.2.2.1.2.15.6ScalarcpqCmcSetupAux1Unlockread-writemandatoryLock will be unlocked with Aux-Input 1: (2) no lock will be unlocked (3) only lock1 will be unlocked (4) only lock2 will be unlocked (5) both locks will be unl…
1.3.6.1.4.1.232.153.2.2.2.1.2.16NodecpqCmcSetupAux2
1.3.6.1.4.1.232.153.2.2.2.1.2.16.1ScalarcpqCmcSetupAux2Availread-writemandatoryAux 2 sensor: (2) available (3) not available
1.3.6.1.4.1.232.153.2.2.2.1.2.16.2ScalarcpqCmcSetupAux2Relaysread-writemandatoryAlert handling of Alarm Relays in case of an alarm condition of Aux 2: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Rela…
1.3.6.1.4.1.232.153.2.2.2.1.2.16.3ScalarcpqCmcSetupAux2AudibleAlarmread-writemandatoryAlert handling of Audible Alarm of in case of an alarm condition of Aux 2: (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.16.4ScalarcpqCmcSetupAux2InputTyperead-writemandatoryType of other digital input (used for any digital signal): (2) contact is normally open, no alarm if contact is open, alarm if contact is closed (3) contact is…
1.3.6.1.4.1.232.153.2.2.2.1.2.16.5ScalarcpqCmcSetupAux2Descriptionread-writemandatoryDescriptional text of the digital input (Aux2)
1.3.6.1.4.1.232.153.2.2.2.1.2.16.6ScalarcpqCmcSetupAux2Unlockread-writemandatoryLock will be unlocked with Aux-Input 2: (2) no lock will be unlocked (3) only lock1 will be unlocked (4) only lock2 will be unlocked (5) both locks will be unl…
1.3.6.1.4.1.232.153.2.2.2.1.2.17NodecpqCmcSetupAlarm1
1.3.6.1.4.1.232.153.2.2.2.1.2.17.1ScalarcpqCmcSetupAlarm1Relaysread-writemandatoryAlert handling of Alarm Relays in case of an alarm condition of Alarm 1: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Re…
1.3.6.1.4.1.232.153.2.2.2.1.2.17.2ScalarcpqCmcSetupAlarm1AudibleAlarmread-writemandatoryAlert handling of Audible Alarm of in case of an alarm condition of Alarm 1: (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.17.3ScalarcpqCmcSetupAlarm1Descriptionread-writemandatoryDescriptional text of alarm 1
1.3.6.1.4.1.232.153.2.2.2.1.2.18NodecpqCmcSetupAlarm2
1.3.6.1.4.1.232.153.2.2.2.1.2.18.1ScalarcpqCmcSetupAlarm2Relaysread-writemandatoryAlert handling of Alarm Relays in case of an alarm condition of Alarm 2: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Re…
1.3.6.1.4.1.232.153.2.2.2.1.2.18.2ScalarcpqCmcSetupAlarm2AudibleAlarmread-writemandatoryAlert handling of Audible Alarm of in case of an alarm condition of Alarm 2: (2) Start Audible Alarm (3) No Audible Alarm
1.3.6.1.4.1.232.153.2.2.2.1.2.18.3ScalarcpqCmcSetupAlarm2Descriptionread-writemandatoryDescriptional text of alarm 2
1.3.6.1.4.1.232.153.2.2.2.1.3NodecpqCmcSetupClock
1.3.6.1.4.1.232.153.2.2.2.1.3.1ScalarcpqCmcSetupDateread-writemandatoryactual Date in format DD.MM.YYYY
1.3.6.1.4.1.232.153.2.2.2.1.3.2ScalarcpqCmcSetupTimeread-writemandatoryactual Time in format HH:MM:SS, HH (0-23), MM (0-59), SS (0-59)
1.3.6.1.4.1.232.153.2.2.2.2NodecpqCmcSetupThreshold
1.3.6.1.4.1.232.153.2.2.2.2.1ScalarcpqCmcThresholdMaxTemp1read-writemandatoryThreshold value maximum temperature 1
1.3.6.1.4.1.232.153.2.2.2.2.2ScalarcpqCmcThresholdWarningTemp1read-writemandatoryThreshold value warning temperature 1
1.3.6.1.4.1.232.153.2.2.2.2.3ScalarcpqCmcThresholdMinTemp1read-writemandatoryThreshold value minimum temperature 1
1.3.6.1.4.1.232.153.2.2.2.2.4ScalarcpqCmcThresholdMaxTemp2read-writemandatoryThreshold value maximum temperature 2
1.3.6.1.4.1.232.153.2.2.2.2.5ScalarcpqCmcThresholdWarningTemp2read-writemandatoryThreshold value warning temperature 2
1.3.6.1.4.1.232.153.2.2.2.2.6ScalarcpqCmcThresholdMinTemp2read-writemandatoryThreshold value minimum temperature 2
1.3.6.1.4.1.232.153.2.2.2.2.7ScalarcpqCmcThresholdFan1read-writemandatoryThreshold Fan 1 in deg F or deg C, Fan 1 will start if temperature 1 exceeds this value
1.3.6.1.4.1.232.153.2.2.2.2.8ScalarcpqCmcThresholdFan1Hysteresisread-writemandatoryHystersis of Fan 1, Fan 1 will stop if temperature 1 falls below value of cpqCmcThresholdFan1 minus cpqCmcThresholdFan1Hysteresis
1.3.6.1.4.1.232.153.2.2.2.2.9ScalarcpqCmcThresholdFan2read-writemandatoryThreshold Fan 2 in deg F or deg C, Fan 2 will start if temperature 2 exceeds this value
1.3.6.1.4.1.232.153.2.2.2.2.10ScalarcpqCmcThresholdFan2Hysteresisread-writemandatoryHystersis of Fan 2, Fan 2 will stop if temperature 2 falls below value of cpqCmcThresholdFan2 minus cpqCmcThresholdFan2Hysteresis
1.3.6.1.4.1.232.153.2.2.2.2.11ScalarcpqCmcThresholdMaxVoltageread-writemandatoryThreshold high value Voltage alarm
1.3.6.1.4.1.232.153.2.2.2.2.12ScalarcpqCmcThresholdMinVoltageread-writemandatoryThreshold low value Voltage alarm
1.3.6.1.4.1.232.153.2.2.2.2.13ScalarcpqCmcThresholdMaxHumidityread-writemandatoryThreshold high value Humidity alarm
1.3.6.1.4.1.232.153.2.2.2.2.14ScalarcpqCmcThresholdMinHumidityread-writemandatoryThreshold low value Humidity alarm
1.3.6.1.4.1.232.153.2.2.2.3NodecpqCmcTraps
1.3.6.1.4.1.232.153.2.2.2.3.1ScalarcpqCmcTrapTableNumberread-onlymandatoryNumber of trapTable entries. The number of trap-receivers
1.3.6.1.4.1.232.153.2.2.2.3.2TablecpqCmcTrapTablenot-accessiblemandatoryA list of trap-receiver entries
1.3.6.1.4.1.232.153.2.2.2.3.2.1RowcpqCmcTrapEntrynot-accessiblemandatoryEntries of trapTable
1.3.6.1.4.1.232.153.2.2.2.3.2.1.1ColumncpqCmcTrapIndexread-onlymandatoryIndex for the trap-receiver-table. Its value ranges between 1 and the value of cpqCmcTrapTableNumber
1.3.6.1.4.1.232.153.2.2.2.3.2.1.2ColumncpqCmcTrapStatusread-writemandatoryEnable or disable trap receiver
1.3.6.1.4.1.232.153.2.2.2.3.2.1.3ColumncpqCmcTrapIPaddressread-writemandatoryIP-address of trap-receiver
1.3.6.1.4.1.232.153.2.2.3NodecpqCmcValues
1.3.6.1.4.1.232.153.2.2.3.1ScalarcpqCmcValueTemp1read-onlymandatoryActual temperature value of temperature sensor 1 in deg C or deg F
1.3.6.1.4.1.232.153.2.2.3.2ScalarcpqCmcValueTemp2read-onlymandatoryActual temperature value of temperature sensor 2 in deg C or deg F
1.3.6.1.4.1.232.153.2.2.3.3ScalarcpqCmcValueVoltageread-onlymandatoryActual value of power supply (voltage monitoring and fans) in V
1.3.6.1.4.1.232.153.2.2.3.4ScalarcpqCmcValueHumidityread-onlymandatoryActual value of humidity 0..100%
1.3.6.1.4.1.232.153.2.2.3.5ScalarcpqCmcValueOperatingTimeread-onlymandatoryOperating time CMC-unit
1.3.6.1.4.1.232.153.2.2.4NodecpqCmcStatus
1.3.6.1.4.1.232.153.2.2.4.1ScalarcpqCmcStatusTemp1read-onlymandatoryThe status of temperature 1, see thresholds of temperature 1: (2) temperature normal (3) temperature exceeds warning threshold (4) temperature exceeds max. thr…
1.3.6.1.4.1.232.153.2.2.4.2ScalarcpqCmcStatusTemp2read-onlymandatoryThe status of temperature 2, see thresholds of temperature 2: (2) temperature normal (3) temperature exceeds warning threshold (4) temperature exceeds max. thr…
1.3.6.1.4.1.232.153.2.2.4.3ScalarcpqCmcStatusFan1read-onlymandatoryThe status of fan 1: (2) fan is switched off by temperature sensor 1 (3) fan is switched on by temperature sensor 1 (4) fan is switched off by Manual Control (…
1.3.6.1.4.1.232.153.2.2.4.4ScalarcpqCmcStatusFan2read-onlymandatoryThe status of fan 2: (2) fan is switched off by temperature sensor 2 (3) fan is switched on by temperature sensor 2 (4) fan is switched off by Manual Control (…
1.3.6.1.4.1.232.153.2.2.4.5ScalarcpqCmcStatusVoltageread-onlymandatoryThe voltage-status, see thresholds of power supply: (2) voltage normal (3) voltage exceeds max. threshold (4) voltage drops under min. threshold (5) no power c…
1.3.6.1.4.1.232.153.2.2.4.6ScalarcpqCmcStatusHumidityread-onlymandatoryThe humidity-status, see thresholds of humidity: (2) humidity normal (3) humidity exceeds max. threshold (4) humidity drops under min. threshold (5) no sensor …
1.3.6.1.4.1.232.153.2.2.4.7ScalarcpqCmcStatusInput1read-onlymandatoryThe status of door/sidepanel 1, closed (2), open (3) or no sensor connected (4)
1.3.6.1.4.1.232.153.2.2.4.8ScalarcpqCmcStatusInput2read-onlymandatoryThe status of door/sidepanel 2, closed (2), open (3) or no sensor connected (4)
1.3.6.1.4.1.232.153.2.2.4.9ScalarcpqCmcStatusInput3read-onlymandatoryThe status of door/sidepanel 3, closed (2), open (3) or no sensor connected (4)
1.3.6.1.4.1.232.153.2.2.4.10ScalarcpqCmcStatusInput4read-onlymandatoryThe status of door/sidepanel 4, closed (2), open (3) or no sensor connected (4)
1.3.6.1.4.1.232.153.2.2.4.11ScalarcpqCmcStatusLock1Lockread-onlymandatoryThe status of door locking 1 (2) Door locking-device is activated, door is locked (3) Door locking-device is not activated, door is unlocked by Network Managem…
1.3.6.1.4.1.232.153.2.2.4.12ScalarcpqCmcStatusLock2Lockread-onlymandatoryThe status of door locking 2 (2) Door locking-device is activated, door is locked (3) Door locking-device is not activated, door is unlocked by Network Managem…
1.3.6.1.4.1.232.153.2.2.4.13ScalarcpqCmcStatusSmokeread-onlymandatoryStatus smoke-sensor, OK (2), smoke detected (3) or no sensor connected (4)
1.3.6.1.4.1.232.153.2.2.4.14ScalarcpqCmcStatusShockread-onlymandatoryStatus Shock sensor, OK (2), shock detected (3) or no sensor connected (4)
1.3.6.1.4.1.232.153.2.2.4.15ScalarcpqCmcStatusAux1read-onlymandatoryStatus aux. digital input
1.3.6.1.4.1.232.153.2.2.4.16ScalarcpqCmcStatusAux2read-onlymandatoryStatus aux. digital input
1.3.6.1.4.1.232.153.2.2.4.17ScalarcpqCmcStatusAlarm1read-onlymandatoryStatus of alarm 1, see cmpCmcsetAlarm1. This alarm can be set from the Network management system. A descriptional text for this alarm can be set in cpqCmcSetup…
1.3.6.1.4.1.232.153.2.2.4.18ScalarcpqCmcStatusAlarm2read-onlymandatoryStatus of alarm 2, see cmpCmcsetAlarm2. This alarm can be set from the Network management system. A descriptional text for this alarm can be set in cpqCmcSetup…
1.3.6.1.4.1.232.153.2.2.4.19ScalarcpqCmcStatusLock1Devread-onlymandatoryThe status of door-locking device 1 (2) OK (3) Power fail of door locking-device (4) Low Battery of door locking-device (5) Battery of door locking device need…
1.3.6.1.4.1.232.153.2.2.4.20ScalarcpqCmcStatusLock2Devread-onlymandatoryThe status of door-locking device 2 (2) OK (3) Power fail of door locking-device (4) Low Battery of door locking-device (5) Battery of door locking device need…
1.3.6.1.4.1.232.153.2.2.5NodecpqCmcControl
1.3.6.1.4.1.232.153.2.2.5.1ScalarcpqCmcStatusAccessread-writemandatoryStatus access, for future use
1.3.6.1.4.1.232.153.2.2.5.2ScalarcpqCmcSetLock1Lockread-writemandatorySet door locking device 1, see table With this command the management-station can set the conditions for the door locking device (2) Door will be locked (3) Do…
1.3.6.1.4.1.232.153.2.2.5.3ScalarcpqCmcSetLock1Keyread-writemandatoryEnable or disable unlocking of the rack-door with external components like keypad or remote input. With this command the management station can set the conditi…
1.3.6.1.4.1.232.153.2.2.5.4ScalarcpqCmcSetLock2Lockread-writemandatorySet door locking device 2, see table With this command the management-station can set the conditions for the door locking device (2) Door will be locked (3) Do…
1.3.6.1.4.1.232.153.2.2.5.5ScalarcpqCmcSetLock2Keyread-writemandatoryEnable or disable unlocking of the rack-door with external components like keypad or remote input. With this command the management-station can set the conditi…
1.3.6.1.4.1.232.153.2.2.5.6ScalarcpqCmcSetMessageread-writemandatorySet message to CMC, for future use
1.3.6.1.4.1.232.153.2.2.5.7ScalarcpqCmcSetAlarm1read-writemandatoryIs used to set an alarm in the CMC from the management-station. With this command the management-station can i.e. switch on an alarm-relay or the AudibleAlarm …
1.3.6.1.4.1.232.153.2.2.5.8ScalarcpqCmcSetAlarm2read-writemandatoryIs used to set an alarm in the CMC from the management-station. With this command the management-station can i.e. switch on an alarm-relay or the AudibleAlarm …
1.3.6.1.4.1.232.153.2.2.5.9ScalarcpqCmcSetFan1read-writemandatoryIs used for run and stop control of fan1. (2) fan will run and stop according to temperature of sensor 1 and threshold of fan1 (3) fan will run independent of …
1.3.6.1.4.1.232.153.2.2.5.10ScalarcpqCmcSetFan2read-writemandatoryIs used for run and stop control of fan2. (2) fan will run and stop according to temperature of sensor 2 and threshold of fan2 (3) fan will run independent of …
1.3.6.1.4.1.232.153.2.2.5.11ScalarcpqCmcSetQuitRelay1read-writemandatoryStatus and quit of alarm relay 1. (2) relay is switched because of an alarm (3) relay is not switched, no alarm (4) (set) will quit relay 1 in case of alarm
1.3.6.1.4.1.232.153.2.2.5.12ScalarcpqCmcSetQuitRelay2read-writemandatoryStatus and quit of alarm relay 2. (2) relay is switched because of an alarm (3) relay is not switched, no alarm (4) (set) will quit relay 2 in case of alarm
1.3.6.1.4.1.232.153.2.2.6NodecpqCmcLog
1.3.6.1.4.1.232.153.2.2.6.1ScalarcpqCmcLogsNumberread-onlymandatoryNumber of Log-entries
1.3.6.1.4.1.232.153.2.2.6.2TablecpqCmcLogTablenot-accessiblemandatoryLog-table
1.3.6.1.4.1.232.153.2.2.6.2.1RowcpqCmcLogEntrynot-accessiblemandatoryLog-table entries
1.3.6.1.4.1.232.153.2.2.6.2.1.1ColumncpqCmcLogIndexread-onlymandatoryIndex for the Log-table. Its value ranges between 1 and the value of cpqCmcLogsNumber
1.3.6.1.4.1.232.153.2.2.6.2.1.2ColumncpqCmcLogDateread-onlymandatoryDate of log information.
1.3.6.1.4.1.232.153.2.2.6.2.1.3ColumncpqCmcLogTimeread-onlymandatoryTime of log information.
1.3.6.1.4.1.232.153.2.2.6.2.1.4ColumncpqCmcLogTextread-onlymandatoryLog information.
1.3.6.1.4.1.232.153.2.2.6.2.1.5ColumncpqCmcLogClassread-onlymandatoryStatus of log information.
1.3.6.1.4.1.232.153.153001NodecpqCmcalarmTemp1The temperature at rack sensor 1 is outside the specified threshold. Action: Check the air handling system for the rack and refer to Trap Details for more info…
1.3.6.1.4.1.232.153.153002NodecpqCmcalarmTemp2The temperature at rack sensor 2 is outside the specified threshold. Action: Check the air handling system for the rack and refer to Trap Details for more info…
1.3.6.1.4.1.232.153.153003NodecpqCmcalarmFan1The status of Fan 1 has changed. Action: Refer to Trap Details for more information.
1.3.6.1.4.1.232.153.153004NodecpqCmcalarmFan2The status of Fan 2 has changed. Action: Refer to Trap Details for more information.
1.3.6.1.4.1.232.153.153005NodecpqCmcalarmVoltageThe AC voltage of the rack is outside the specified threshold. Action: Check the incoming power source and ensure all cables are inserted correctly.
1.3.6.1.4.1.232.153.153006NodecpqCmcalarmHumidityThe humidity of the rack is outside the specified threshold. Action: Check the air handling system for the rack and refer to Trap Details for more information.
1.3.6.1.4.1.232.153.153007NodecpqCmcalarmInput1The door or sidepanel of the rack has been opened (access point #1). Action: Check for unauthorized intrusion and refer to Trap Details for more information.
1.3.6.1.4.1.232.153.153008NodecpqCmcalarmInput2The door or sidepanel of the rack has been opened (access point #2). Action: Check for unauthorized intrusion and refer to Trap Details for more information.
1.3.6.1.4.1.232.153.153009NodecpqCmcalarmInput3The door or sidepanel of the rack has been opened (access point #3). Action: Check for unauthorized intrusion and refer to Trap Details for more information.
1.3.6.1.4.1.232.153.153010NodecpqCmcalarmInput4The door or sidepanel of the rack has been opened (access point #4). Action: Check for unauthorized intrusion and refer to Trap Details for more information.
1.3.6.1.4.1.232.153.153011NodecpqCmcalarmLock1Rack door lock #1 alarm. Action: Ensure the door is completely closed and check for unauthorized intrusion and refer to Trap Details for more information.
1.3.6.1.4.1.232.153.153012NodecpqCmcalarmLock2Rack door lock #2 alarm. Action: Ensure the door is completely closed and check for unauthorized intrusion and refer to Trap Details for more information.
1.3.6.1.4.1.232.153.153013NodecpqCmcalarmSmokeThe rack smoke detector has detected smoke. Action: Investigate rack for an over temperature condition and refer to Trap Details for more information.
1.3.6.1.4.1.232.153.153014NodecpqCmcalarmShockThe rack shock detector has detected a vibration to the rack. Action: Investigate rack.
1.3.6.1.4.1.232.153.153015NodecpqCmcalarmAux1The rack auxiliary alarm input #1 has been triggered.
1.3.6.1.4.1.232.153.153016NodecpqCmcalarmAux2The rack auxiliary alarm input #2 has been triggered.
1.3.6.1.4.1.232.153.153017NodecpqCmcalarm1Alarm 1, set from Network management
1.3.6.1.4.1.232.153.153018NodecpqCmcalarm2Alarm 2, set from Network management
1.3.6.1.4.1.232.153.153019NodecpqCmcalarmLock1DevThe rack door locking device #1 has failed. Action: Check the device lock cable or failed battery and refer to Trap Details for more information.
1.3.6.1.4.1.232.153.153020NodecpqCmcalarmLock2DevThe rack door locking device #2 has failed. Action: Check the device lock cable or failed battery and refer to Trap Details for more information.
1.3.6.1.4.1.232.153.153100NodecpqCmcSetupChangedSetup of CMC has changed.