OIDNameAccessStatusDescription
1.3.6.1.4.1.232.154NodecpqRPM
1.3.6.1.4.1.232.154.1NodecpqRPMTrapInfo
1.3.6.1.4.1.232.154.1.1ScalarcpqRPMTrapDescriptionread-onlymandatoryText description of the event that caused the trap.
1.3.6.1.4.1.232.154.1.2ScalarcpqRPMTrapDeviceIdread-onlymandatoryA unique numeric identifier for the device that caused the trap.
1.3.6.1.4.1.232.154.1.3ScalarcpqRPMTrapDeviceNameread-onlymandatoryThe text name for the device.
1.3.6.1.4.1.232.154.1.4ScalarcpqRPMTrapDeviceAddressread-onlymandatoryThe hostname or ip address for the device.
1.3.6.1.4.1.232.154.1.5ScalarcpqRPMTrapTyperead-onlymandatoryIndicates the type of the event that caused the trap.
1.3.6.1.4.1.232.154.1.6ScalarcpqRPMTrapSeverityread-onlymandatoryIndicates the severity of the event that caused the trap.
1.3.6.1.4.1.232.154.1.7ScalarcpqRPMTrapCoderead-onlymandatoryA unique identifier for the alarm.
1.3.6.1.4.1.232.154.1.8ScalarcpqRPMTrapURLread-onlymandatoryThe URL for the management software.
1.3.6.1.4.1.232.154.2NodecpqRPMTraps
1.3.6.1.4.1.232.154.2.1NodecpqRPMTrapDeviceConnectedA UPS device is reporting a Connection Lost due to one of the following. 1. The serial cable connected to the UPS has been unplugged. 2. The Network cable conn…
1.3.6.1.4.1.232.154.2.2NodecpqRPMTrapConnectionLostA UPS device is reporting a Connection Lost due to one of the following. 1. The serial cable connected to the UPS has been unplugged. 2. The Network cable conn…
1.3.6.1.4.1.232.154.2.3NodecpqRPMTrapLookupFailedCRPM failed to find an IP address for the device hostname.
1.3.6.1.4.1.232.154.2.4NodecpqRPMTrapConnectionFailedCRPM failed to connect to a device.
1.3.6.1.4.1.232.154.2.5NodecpqRPMTrapDeviceSettingsChangedDevice settings have been changed by a user.
1.3.6.1.4.1.232.154.2.10001NodecpqRPMTrapCMCTemp1BelowMinA CMC device is reporting temperature 1 below minimum threshold.
1.3.6.1.4.1.232.154.2.10002NodecpqRPMTrapCMCTemp1AboveWarnA CMC device is reporting temperature 1 above warning threshold.
1.3.6.1.4.1.232.154.2.10003NodecpqRPMTrapCMCTemp1AboveMaxA CMC device is reporting temperature 1 above maximum threshold.
1.3.6.1.4.1.232.154.2.10004NodecpqRPMTrapCMCTemp1NormalA CMC device is reporting temperature 1 has returned to a normal temperature.
1.3.6.1.4.1.232.154.2.10005NodecpqRPMTrapCMCTemp2BelowMinA CMC device is reporting temperature 2 below minimum threshold.
1.3.6.1.4.1.232.154.2.10006NodecpqRPMTrapCMCTemp2AboveWarnA CMC device is reporting temperature 2 above warning threshold.
1.3.6.1.4.1.232.154.2.10007NodecpqRPMTrapCMCTemp2AboveMaxA CMC device is reporting temperature 2 above maximum threshold.
1.3.6.1.4.1.232.154.2.10008NodecpqRPMTrapCMCTemp2NormalA CMC device is reporting temperature 2 has returned to a normal temperature.
1.3.6.1.4.1.232.154.2.10011NodecpqRPMTrapCMCVoltUnderA CMC device is reporting voltage below minimum threshold.
1.3.6.1.4.1.232.154.2.10012NodecpqRPMTrapCMCVoltOverA CMC device is reporting voltage above maximum threshold.
1.3.6.1.4.1.232.154.2.10013NodecpqRPMTrapCMCVoltNormalA CMC device is reporting voltage has returned to normal.
1.3.6.1.4.1.232.154.2.10021NodecpqRPMTrapCMCHmdtUnderA CMC device is reporting humidity below minimum threshold.
1.3.6.1.4.1.232.154.2.10022NodecpqRPMTrapCMCHmdtOverA CMC device is reporting humidity above maximum threshold.
1.3.6.1.4.1.232.154.2.10023NodecpqRPMTrapCMCHmdtNormalA CMC device is reporting humidity has returned to normal.
1.3.6.1.4.1.232.154.2.10031NodecpqRPMTrapCMCSmokeDetectedA CMC device is reporting smoke detected.
1.3.6.1.4.1.232.154.2.10032NodecpqRPMTrapCMCSmokeClearedA CMC device is reporting smoke cleared.
1.3.6.1.4.1.232.154.2.10041NodecpqRPMTrapCMCShockDetectedA CMC device is reporting shock detected.
1.3.6.1.4.1.232.154.2.10042NodecpqRPMTrapCMCShockClearedA CMC device is reporting shock cleared.
1.3.6.1.4.1.232.154.2.10051NodecpqRPMTrapCMCAux1AlarmA CMC device has entered an alarm condition for auxiliary input 1.
1.3.6.1.4.1.232.154.2.10052NodecpqRPMTrapCMCAux1ClearedA CMC device is reporting auxiliary input 1 alarm cleared.
1.3.6.1.4.1.232.154.2.10053NodecpqRPMTrapCMCAux2AlarmA CMC device has entered an alarm condition for auxiliary input 2.
1.3.6.1.4.1.232.154.2.10054NodecpqRPMTrapCMCAux2ClearedA CMC device is reporting auxiliary input 2 alarm cleared.
1.3.6.1.4.1.232.154.2.10101NodecpqRPMTrapCMCInput1OpenedA CMC device is reporting input 1 has been opened.
1.3.6.1.4.1.232.154.2.10102NodecpqRPMTrapCMCInput1ClosedA CMC device is reporting input 1 has been closed.
1.3.6.1.4.1.232.154.2.10103NodecpqRPMTrapCMCInput2OpenedA CMC device is reporting input 2 has been opened.
1.3.6.1.4.1.232.154.2.10104NodecpqRPMTrapCMCInput2ClosedA CMC device is reporting input 2 has been closed.
1.3.6.1.4.1.232.154.2.10105NodecpqRPMTrapCMCInput3OpenedA CMC device is reporting input 3 has been opened.
1.3.6.1.4.1.232.154.2.10106NodecpqRPMTrapCMCInput3ClosedA CMC device is reporting input 3 has been closed.
1.3.6.1.4.1.232.154.2.10107NodecpqRPMTrapCMCInput4OpenedA CMC device is reporting input 4 has been opened.
1.3.6.1.4.1.232.154.2.10108NodecpqRPMTrapCMCInput4ClosedA CMC device is reporting input 4 has been closed.
1.3.6.1.4.1.232.154.2.10111NodecpqRPMTrapCMCLockset1UnlockedA CMC device is reporting lockset 1 has been unlocked.
1.3.6.1.4.1.232.154.2.10112NodecpqRPMTrapCMCLockset1FailedToLockA CMC device is reporting lockset 1 has failed to lock.
1.3.6.1.4.1.232.154.2.10113NodecpqRPMTrapCMCLockset1ErrorA CMC device is reporting an error with lockset 1.
1.3.6.1.4.1.232.154.2.10114NodecpqRPMTrapCMCLockset1LockedA CMC device is reporting lockset 1 has been locked.
1.3.6.1.4.1.232.154.2.10116NodecpqRPMTrapCMCLockset2UnlockedA CMC device is reporting lockset 2 has been unlocked.
1.3.6.1.4.1.232.154.2.10117NodecpqRPMTrapCMCLockset2FailedToLockA CMC device is reporting lockset 2 has failed to lock.
1.3.6.1.4.1.232.154.2.10118NodecpqRPMTrapCMCLockset2ErrorA CMC device is reporting an error with lockset 2.
1.3.6.1.4.1.232.154.2.10119NodecpqRPMTrapCMCLockset2LockedA CMC device is reporting lockset 2 has been locked.
1.3.6.1.4.1.232.154.2.10134NodecpqRPMTrapCMCLockset1NormalA CMC device is reporting lockset 2 is normal.
1.3.6.1.4.1.232.154.2.10135NodecpqRPMTrapCMCLockset2NormalA CMC device is reporting lockset 2 is normal.
1.3.6.1.4.1.232.154.2.20001NodecpqRPMTrapUPSInputVoltageBelowMinA UPS device is reporting input voltage below minimum threshold.
1.3.6.1.4.1.232.154.2.20002NodecpqRPMTrapUPSInputVoltageAboveMaxA UPS device is reporting input voltage above maximum threshold.
1.3.6.1.4.1.232.154.2.20003NodecpqRPMTrapUPSInputVoltageNormalA UPS device is reporting input voltage is out of range. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. …
1.3.6.1.4.1.232.154.2.20011NodecpqRPMTrapUPSOutputVoltageBelowMinA UPS device is reporting output voltage below minimum threshold.
1.3.6.1.4.1.232.154.2.20012NodecpqRPMTrapUPSOutputVoltageAboveMaxA UPS device is reporting output voltage above maximum threshold.
1.3.6.1.4.1.232.154.2.20014NodecpqRPMTrapUPSOutputOverloadA UPS device is reporting an overload condition. Recommendations: 1. Reduce the load on the UPS by moving some of the load to another UPS. 2. Consider moving t…
1.3.6.1.4.1.232.154.2.20015NodecpqRPMTrapUPSOutputOverloadClearedA UPS device is reporting an overload condition. Recommendations: 1. Reduce the load on the UPS by moving some of the load to another UPS. 2. Consider moving t…
1.3.6.1.4.1.232.154.2.20022NodecpqRPMTrapUPSBatteryDepletedA UPS device is a depleted battery.
1.3.6.1.4.1.232.154.2.20023NodecpqRPMTrapUPSBatteryLevelNormalA UPS device is reporting low battery. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. 2. When utility po…
1.3.6.1.4.1.232.154.2.20032NodecpqRPMTrapUPSOnBypassA UPS device is being bypassed.
1.3.6.1.4.1.232.154.2.20101NodecpqRPMTrapUPSTemperatureLowA UPS device is reporting temperature blow minimum threshold.
1.3.6.1.4.1.232.154.2.20102NodecpqRPMTrapUPSTemperatureHighA UPS device is reporting temperature above maximum threshold.
1.3.6.1.4.1.232.154.2.20103NodecpqRPMTrapUPSTemperatureNormalA UPS device is reporting temperature is out of range. Recommendations: 1. Check to make sure the UPS is in a well ventilated area. 2. Lower the ambient temper…
1.3.6.1.4.1.232.154.2.20111NodecpqRPMTrapUPSInternalFailureA UPS device is reporting a general UPS failure. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support.
1.3.6.1.4.1.232.154.2.20112NodecpqRPMTrapUPSInternalFailureClearedA UPS device is reporting a general UPS failure. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support.
1.3.6.1.4.1.232.154.2.20121NodecpqRPMTrapUPSBatteryFailureA UPS device is reporting a battery failure. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support. 3. Your battery…
1.3.6.1.4.1.232.154.2.20122NodecpqRPMTrapUPSBatteryFailureClearedA UPS device is reporting a battery failure. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support. 3. Your battery…
1.3.6.1.4.1.232.154.2.20131NodecpqRPMTrapUPSDiagnosticTestFailedA UPS device is reporting a diagnostic test failed. Recommendations: 1. Your battery may need to be replaced. 2. If this error persists contact technical suppo…
1.3.6.1.4.1.232.154.2.20132NodecpqRPMTrapUPSDiagnosticTestSucceededA UPS device is reporting a diagnostic test failed. Recommendations: 1. Your battery may need to be replaced. 2. If this error persists contact technical suppo…
1.3.6.1.4.1.232.154.2.20141NodecpqRPMTrapUPSInputUnderOverFreqInput (Utility) fault: measured input frequency is outside of either the upper or lower frequency limit specification for normal operation.
1.3.6.1.4.1.232.154.2.20142NodecpqRPMTrapUPSInputUnderOverFreqClearedMeasured input frequency is normal
1.3.6.1.4.1.232.154.2.20151NodecppqRPMtrapUPSStartedOnBatteryA UPS device has been started while on battery power. AC input power is not present. Recommendations: 1. Check to make sure the UPS is plugged into an outlet s…
1.3.6.1.4.1.232.154.2.20152NodecppqRPMtrapUPSStartedOnBatteryClearedA UPS device has been started while on battery power. AC input power is not present. Recommendations: 1. Check to make sure the UPS is plugged into an outlet s…
1.3.6.1.4.1.232.154.2.20161NodecpqRPMTrapUPSBypassNotAvailableA UPS device is reporting bypass not avaliable. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support.
1.3.6.1.4.1.232.154.2.20162NodecpqRPMTrapUPSBypassNotAvailableClearedA UPS device is reporting bypass not avaliable. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support.
1.3.6.1.4.1.232.154.2.20171NodecpqRPMTrapUPSUtilityFailIndicates that the utility input power is not within predetermined limits. This could be, but is not limited to, over voltage, under voltage, over frequency, u…
1.3.6.1.4.1.232.154.2.20172NodecpqRPMTrapUPSUtilityFailClearedIndicates that the utility input power is within predetermined limits.
1.3.6.1.4.1.232.154.2.20181NodecpqRPMTrapUPSUtilityNotPresentIndicates that the utility input is not present. This differs from alarm #57 in that the detected voltage is zero in this case.
1.3.6.1.4.1.232.154.2.20182NodecpqRPMTrapUPSUtilityNotPresentClearedIndicates that the utility input is present.
1.3.6.1.4.1.232.154.2.20191NodecpqRPMTrapUPSBypassManualTurnedOnThe bypass has been given a manual turn on command.
1.3.6.1.4.1.232.154.2.20192NodecpqRPMTrapUPSBypassManualTurnedOffThe bypass has been given a manual turn off command.
1.3.6.1.4.1.232.154.2.20201NodecpqRPMTrapUPSSiteWiringFaultA UPS device is reporting a fault in the input wiring, other than Phase Rotation: e.g., Ground/Neutral reversed. Recommendations: 1. Contact an electrician.
1.3.6.1.4.1.232.154.2.20202NodecpqRPMTrapUPSSiteWiringNormalA UPS device is reporting a fault in the input wiring, other than Phase Rotation: e.g., Ground/Neutral reversed. Recommendations: 1. Contact an electrician.
1.3.6.1.4.1.232.154.2.21007NodecpqRPMtrapUPSTemperatureOutOfRangeA UPS device is reporting temperature is out of range. Recommendations: 1. Check to make sure the UPS is in a well ventilated area. 2. Lower the ambient temper…
1.3.6.1.4.1.232.154.2.21008NodecpqRPMtrapUPSTemperatureOutOfRangeClearedA UPS device is reporting temperature is out of range. Recommendations: 1. Check to make sure the UPS is in a well ventilated area. 2. Lower the ambient temper…
1.3.6.1.4.1.232.154.2.21011NodecpqRPMTrapUPSShutdownPendingA UPS device is reporting shutdown pending condition. Recommendations: 1. Immediately restore power to the UPS. The UPS will not continue to supply power to de…
1.3.6.1.4.1.232.154.2.21012NodecpqRPMTrapUPSShutdownPendingClearedA UPS device is reporting shutdown pending condition. Recommendations: 1. Immediately restore power to the UPS. The UPS will not continue to supply power to de…
1.3.6.1.4.1.232.154.2.21013NodecpqRPMTrapUPSShutdownImminentA UPS device is reporting a shutdown imminent condition. Recommendations: 1. Immediately restore power to the UPS. The UPS will not continue to supply power to…
1.3.6.1.4.1.232.154.2.21014NodecpqRPMTrapUPSShutdownImminentClearedA UPS device is reporting a shutdown imminent condition. Recommendations: 1. Immediately restore power to the UPS. The UPS will not continue to supply power to…
1.3.6.1.4.1.232.154.2.21019NodecpqRPMtrapUPSOutputoutofRangeA UPS device is reporting output voltage is out of Range. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support.
1.3.6.1.4.1.232.154.2.21020NodecpqRPMTrapUPSOutputVoltageNormalA UPS device is reporting output voltage is out of Range. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support.
1.3.6.1.4.1.232.154.2.21021NodecpqRPMtrapUPSInputOutofRangeA UPS device is reporting input voltage is out of range. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. …
1.3.6.1.4.1.232.154.2.21022NodecpqRPMtrapUPSInputOutofRangeClearedA UPS device is reporting input voltage is out of range. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. …
1.3.6.1.4.1.232.154.2.21023NodecpqRPMTrapUPSLossOfRedundancyA UPS device is reporting a loss of redundancy due to one of the following. 1. One or more of the Electronics Modules has failed 2. One or more of the electron…
1.3.6.1.4.1.232.154.2.21024NodecpqRPMTrapUPSLossOfRedundancyClearedA UPS device is reporting a loss of redundancy due to one of the following. 1. One or more of the Electronics Modules has failed 2. One or more of the electron…
1.3.6.1.4.1.232.154.2.21029NodecpqRPMTrapUPSOnBuckA UPS device is reporting an On Buck condition due to the following. 1. Utility power has increased above recommended utility input levels. Recommendation: 1. …
1.3.6.1.4.1.232.154.2.21031NodecpqRPMTrapUPSOnBoostA UPS device is reporting an On Boost condition due to the following. 1. Utility power has dropped below recommended utility input levels. Recommendation: 1. C…
1.3.6.1.4.1.232.154.2.21033NodecpqRPMTrapUPSManualLoadDumpedThe UPS has been powered off with user interaction.
1.3.6.1.4.1.232.154.2.21034NodecpqRPMTrapUPSManualLoadDumpedClearedThe UPS has been powered off with user interaction.
1.3.6.1.4.1.232.154.2.21035NodecpqRPMTrapUPSFanFailureA UPS device is reporting a fan failure has occurred. Recommendations: 1. If this error persists contact technical support.
1.3.6.1.4.1.232.154.2.21036NodecpqRPMTrapUPSFanFailureClearedA UPS device is reporting a fan failure has occurred. Recommendations: 1. If this error persists contact technical support.
1.3.6.1.4.1.232.154.2.21037NodecpqRPMTrapUPSEPOInitiatedA UPS device is reporting an Emergency Power Off (EPO) command has been received to shutdown the UPS immediately with out delay. This command may come from a l…
1.3.6.1.4.1.232.154.2.21041NodecpqRPMTrapUPSCheckBreakerA UPS device is reporting an output Breaker or Relay has failed or may be stuck open or closed with this alarm. Recommendations: 1. Check all breakers on the U…
1.3.6.1.4.1.232.154.2.21042NodecpqRPMTrapUPSCheckBreakerClearedA UPS device is reporting an output Breaker or Relay has failed or may be stuck open or closed with this alarm. Recommendations: 1. Check all breakers on the U…
1.3.6.1.4.1.232.154.2.21045NodecpqRPMTrapUPSCabinetDoorOpenA UPS device is reporting a cover panel has been removed while utility power is present. Recommendations: 1. Reinstall all panels. 2. If this error persists co…
1.3.6.1.4.1.232.154.2.21046NodecpqRPMTrapUPSCabinetDoorOpenClearedA UPS device is reporting a cover panel has been removed while utility power is present. Recommendations: 1. Reinstall all panels. 2. If this error persists co…
1.3.6.1.4.1.232.154.2.21047NodecpqRPMtrapUPSBypassOnAutoA UPS device is operating in auto bypass mode. Recommendations: 1. In bypass mode, the UPS cannot support devices if there is a power failure. 2. Once maintena…
1.3.6.1.4.1.232.154.2.21048NodecpqRPMtrapUPSBypassOnAutoClearedA UPS device is operating in auto bypass mode. Recommendations: 1. In bypass mode, the UPS cannot support devices if there is a power failure. 2. Once maintena…
1.3.6.1.4.1.232.154.2.21053NodecpqRPMTrapUPSBatteriesDisconnectedA UPS device is reporting batteries are not connected to the UPS. Recomendations: 1. Connect the UPS Batteries. The UPS will not be capable of supporting it's …
1.3.6.1.4.1.232.154.2.21054NodecpqRPMTrapUPSBatteriesDisconnectedClearedA UPS device is reporting batteries are not connected to the UPS. Recomendations: 1. Connect the UPS Batteries. The UPS will not be capable of supporting it's …
1.3.6.1.4.1.232.154.2.21055NodecpqRPMTrapUPSBatteryLowA UPS device is reporting low battery. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. 2. When utility po…
1.3.6.1.4.1.232.154.2.21056NodecpqRPMTrapUPSBatteryLowClearedA UPS device is reporting low battery. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. 2. When utility po…
1.3.6.1.4.1.232.154.2.21057NodecpqRPMTrapUPSBatteryDischargedA UPS device is reporting batteries are completely discharged. Recommendations: 1. Connect the UPS to utility power to charge the batteries. The UPS will not b…
1.3.6.1.4.1.232.154.2.21058NodecpqRPMTrapUPSBatteryDischargedClearedA UPS device is reporting batteries are completely discharged. Recommendations: 1. Connect the UPS to utility power to charge the batteries. The UPS will not b…
1.3.6.1.4.1.232.154.2.21059NodecpqRPMtrapUPSBypassONManualA UPS device is operating in manual bypass mode. Recommendations: 1. In bypass mode, the UPS cannot support devices if there is a power failure. 2. Once mainte…
1.3.6.1.4.1.232.154.2.21060NodecpqRPMtrapUPSBypassOffManualA UPS device is operating in manual bypass mode. Recommendations: 1. In bypass mode, the UPS cannot support devices if there is a power failure. 2. Once mainte…
1.3.6.1.4.1.232.154.2.21063NodecpqRPMTrapUPSOnBatteryA UPS device is reporting on battery condition. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. If the UP…
1.3.6.1.4.1.232.154.2.21064NodecpqRPMTrapUPSOnUtilityPowerA UPS device is reporting on battery condition. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. If the UP…
1.3.6.1.4.1.232.154.2.29998NodecpqRPMTrapUPSDCStartOccurredThe UPS has been started on battery when AC input power is not present. This alarm is used to record the date and time of this event.
1.3.6.1.4.1.232.154.2.29999NodecpqRPMTrapUPSDCStartOccurredClearedThe UPS has been started on utility while AC input power is present.
1.3.6.1.4.1.232.154.2.50001NodecpqRPMTestTrapThis trap is sent to test SNMP setup.
1.3.6.1.4.1.232.154.3NodecpqPMTraps
1.3.6.1.4.1.232.154.3.1NodecpqPMTrapCriticalA critical alarm has occurred. Action: Check the Trap Details for more information.
1.3.6.1.4.1.232.154.3.2NodecpqPMTrapWarningA warning alarm has occurred. Action: Check the Trap Details for more information.
1.3.6.1.4.1.232.154.3.3NodecpqPMTrapInformationAn information alarm has occurred. Action: Check the Trap Details for more information.
1.3.6.1.4.1.232.154.3.4NodecpqPMTrapClearedAn alarm has cleared. Action: Check the Trap Details for more information.