CPQWCRM-MIB
138 objects
No module-level DESCRIPTION found.
Imported Objects
| CPQHOST-MIB | compaq |
| RFC-1212 | OBJECT-TYPE |
| RFC-1215 | TRAP-TYPE |
| RFC1213-MIB | DisplayString sysContact sysLocation sysName |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.232.167 | NodecpqWcrm | |||
| 1.3.6.1.4.1.232.167.1 | NodealarmSensorInternal | Internal Sensor Alarm | ||
| 1.3.6.1.4.1.232.167.1 | NodecpqWcrmMibRev | |||
| 1.3.6.1.4.1.232.167.1.1 | ScalarcpqWcrmMibMajRev | read-only | mandatory | The Major Revision level. A change in the major revision level represents a major change in the architecture of the MIB. A change in the major revision level m… |
| 1.3.6.1.4.1.232.167.1.2 | ScalarcpqWcrmMibMinRev | read-only | mandatory | The Minor Revision level. A change in the minor revision level may represent some minor additional support, no changes to any pre-existing information has occu… |
| 1.3.6.1.4.1.232.167.1.3 | ScalarcpqWcrmMibCondition | read-only | mandatory | The overall condition (status) of the system represented by this MIB. (2) OK (3) a minor problem, warning condition (yellow LED on Environmental Controller) (4… |
| 1.3.6.1.4.1.232.167.2 | NodealarmSensorWaterCoolUnit | Water Cool Unit Sensor Alarm | ||
| 1.3.6.1.4.1.232.167.2 | NodecpqWcrmStatus | |||
| 1.3.6.1.4.1.232.167.2.1 | ScalarcpqWcrmStatusDeviceEnvironmentalController | read-only | mandatory | General Status of Environmental Controller unit itself (1) failed (2) OK |
| 1.3.6.1.4.1.232.167.2.2 | ScalarcpqWcrmUnitsConnected | read-only | mandatory | Number of sensor units connected to the Environmental Controller, Port 1 to 2 |
| 1.3.6.1.4.1.232.167.2.3 | NodecpqWcrmStatusSensorInternal | |||
| 1.3.6.1.4.1.232.167.2.3.1 | ScalarcpqWcrmInternalTypeOfDevice | read-only | mandatory | Type of sensor unit connected to port 1 |
| 1.3.6.1.4.1.232.167.2.3.2 | ScalarcpqWcrmInternalText | read-write | mandatory | Descriptional text for sensor unit connected to port 1 |
| 1.3.6.1.4.1.232.167.2.3.3 | ScalarcpqWcrmInternalSerial | read-only | mandatory | Serialnumber of sensor unit connected to port 1 |
| 1.3.6.1.4.1.232.167.2.3.4 | ScalarcpqWcrmInternalStatus | read-only | mandatory | General Status sensor unit connected to port 1 (1) OK (2) error, e. g. value overflow (3) configuration of sensor unit has changed, confirmation required (4) r… |
| 1.3.6.1.4.1.232.167.2.3.5 | NodecpqWcrmStatusInternalSensors | |||
| 1.3.6.1.4.1.232.167.2.3.5.1 | ScalarcpqWcrmInternalNumberOfSensors | read-only | mandatory | Number of sensors connected to sensor unit 1 |
| 1.3.6.1.4.1.232.167.2.3.5.2 | TablecpqWcrmInternalSensorTable | not-accessible | mandatory | Headline of sensor table |
| 1.3.6.1.4.1.232.167.2.3.5.2.1 | RowcpqWcrmInternalSensorEntry | not-accessible | mandatory | Entries of sensor table |
| 1.3.6.1.4.1.232.167.2.3.5.2.1.1 | ColumninternalSensorIndex | read-only | mandatory | Index for the list of value entries. Its value ranges between 1 and the value of cpqWcrmInternalNumberOfSensors. |
| 1.3.6.1.4.1.232.167.2.3.5.2.1.2 | ColumninternalSensorType | read-only | mandatory | Type of sensor which is connected to internal sensor to sensor[internalSensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: sensor type 1… |
| 1.3.6.1.4.1.232.167.2.3.5.2.1.3 | ColumninternalSensorText | read-write | mandatory | Descriptional text for each sensor (entry in the table) |
| 1.3.6.1.4.1.232.167.2.3.5.2.1.4 | ColumninternalSensorStatus | read-only | mandatory | Actual status of the sensor |
| 1.3.6.1.4.1.232.167.2.3.5.2.1.5 | ColumninternalSensorValue | read-only | mandatory | Value of sensor |
| 1.3.6.1.4.1.232.167.2.3.5.2.1.6 | ColumninternalSensorSetHigh | read-write | mandatory | Value for high setpoint of sensor |
| 1.3.6.1.4.1.232.167.2.3.5.2.1.7 | ColumninternalSensorSetLow | read-write | mandatory | Value for low setpoint of sensor, also used as alarm delay |
| 1.3.6.1.4.1.232.167.2.3.5.2.1.8 | ColumninternalSensorSetWarn | read-write | mandatory | Value for warning setpoint of sensor, also used as fan threshold |
| 1.3.6.1.4.1.232.167.2.3.5.2.1.9 | ColumninternalSensorValueScale | read-only | mandatory | Scaling factor for scaled sensor value, e. g. -100 -> value has to be divided by 100 +100 -> value has to be multiplied by 100. |
| 1.3.6.1.4.1.232.167.2.3.5.2.1.10 | ColumninternalSensorScaledValue | read-only | mandatory | Scaled value of sensor |
| 1.3.6.1.4.1.232.167.2.3.6 | NodecpqWcrmStatusInternalOutputs | |||
| 1.3.6.1.4.1.232.167.2.3.6.1 | ScalarcpqWcrmInternalNumberOfOutputs | read-only | mandatory | Number of outputs available on internal sensor |
| 1.3.6.1.4.1.232.167.2.3.6.2 | TablecpqWcrmInternalOutputTable | not-accessible | mandatory | Headline of output table |
| 1.3.6.1.4.1.232.167.2.3.6.2.1 | RowcpqWcrmInternalOutputEntry | not-accessible | mandatory | Entries of output table |
| 1.3.6.1.4.1.232.167.2.3.6.2.1.1 | ColumninternalOutputIndex | read-only | mandatory | Index for the list of output entries. Its value ranges between 1 and the value of cpqWcrmInternalNumberOfOutputs. |
| 1.3.6.1.4.1.232.167.2.3.6.2.1.2 | ColumninternalOutputType | read-only | mandatory | Type of output which is connected to internal sensor to output[internalOutputIndex] 1: no output connected 2: output failure 3: value overflow 4: output type 6… |
| 1.3.6.1.4.1.232.167.2.3.6.2.1.3 | ColumninternalOutputText | read-write | mandatory | Descriptional text for each output (entry in the table) |
| 1.3.6.1.4.1.232.167.2.3.6.2.1.4 | ColumninternalOutputStatus | read-write | mandatory | Actual status of the output |
| 1.3.6.1.4.1.232.167.2.3.6.2.1.5 | ColumninternalOutputValue | read-write | mandatory | Value for output |
| 1.3.6.1.4.1.232.167.2.3.6.2.1.6 | ColumninternalOutputSet | read-write | mandatory | Command for output |
| 1.3.6.1.4.1.232.167.2.3.6.2.1.7 | ColumninternalOutputConfig | read-write | mandatory | Configuration for output 1: disable remote control (e.g. keypad) 2: enable remote control |
| 1.3.6.1.4.1.232.167.2.3.6.2.1.8 | ColumninternalOutputDelay | read-write | mandatory | Unsigned Value for delay, after this time the output will fall into the previous state |
| 1.3.6.1.4.1.232.167.2.3.6.2.1.9 | ColumninternalOutputTimeoutAction | read-write | mandatory | State for output if timeout (RS422) occurs |
| 1.3.6.1.4.1.232.167.2.3.7 | NodecpqWcrmStatusInternalMsg | |||
| 1.3.6.1.4.1.232.167.2.3.7.1 | ScalarcpqWcrmInternalNumberOfMsgs | read-only | mandatory | Number of messages that can be created with internal sensor |
| 1.3.6.1.4.1.232.167.2.3.7.2 | TablecpqWcrmInternalMsgTable | not-accessible | mandatory | Headline of message table |
| 1.3.6.1.4.1.232.167.2.3.7.2.1 | RowcpqWcrmInternalMsgEntry | not-accessible | mandatory | Entries of message table |
| 1.3.6.1.4.1.232.167.2.3.7.2.1.1 | ColumninternalMsgIndex | read-only | mandatory | Index for the list of message entries. Its value ranges between 1 and the value of cpqWcrmInternalNumberOfMsgs. |
| 1.3.6.1.4.1.232.167.2.3.7.2.1.2 | ColumninternalMsgText | read-write | mandatory | Descriptional text for each message (entry in the table) |
| 1.3.6.1.4.1.232.167.2.3.7.2.1.3 | ColumninternalMsgStatus | read-only | mandatory | Actual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of… |
| 1.3.6.1.4.1.232.167.2.3.7.2.1.4 | ColumninternalMsgRelay | read-write | mandatory | Setup of Alarm relay for this message/alarm 1: no switching of alarm relay 2: switching of alarm relay |
| 1.3.6.1.4.1.232.167.2.3.7.2.1.5 | ColumninternalMsgBeeper | read-write | mandatory | Setup of Alarm beeper for this alarm 1: no audible alarm 2: audible alarm |
| 1.3.6.1.4.1.232.167.2.3.7.2.1.6 | ColumninternalMsgTrap1 | read-write | mandatory | Trap receiver 1 activated |
| 1.3.6.1.4.1.232.167.2.3.7.2.1.7 | ColumninternalMsgTrap2 | read-write | mandatory | Trap receiver 2 activated |
| 1.3.6.1.4.1.232.167.2.3.7.2.1.8 | ColumninternalMsgTrap3 | read-write | mandatory | Trap receiver 3 activated |
| 1.3.6.1.4.1.232.167.2.3.7.2.1.9 | ColumninternalMsgTrap4 | read-write | mandatory | Trap receiver 4 and Event Logging activated |
| 1.3.6.1.4.1.232.167.2.3.7.2.1.10 | ColumninternalMsgReset | read-write | mandatory | Reset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key |
| 1.3.6.1.4.1.232.167.2.4 | NodecpqWcrmStatusSensorWaterCoolUnit | |||
| 1.3.6.1.4.1.232.167.2.4.1 | ScalarcpqWcrmWaterCoolUnitTypeOfDevice | read-only | mandatory | Type of sensor unit connected to port 2 |
| 1.3.6.1.4.1.232.167.2.4.2 | ScalarcpqWcrmWaterCoolUnitText | read-write | mandatory | Descriptional text for sensor unit connected to port 2 |
| 1.3.6.1.4.1.232.167.2.4.3 | ScalarcpqWcrmWaterCoolUnitSerial | read-only | mandatory | Serialnumber of sensor unit connected to port 2 |
| 1.3.6.1.4.1.232.167.2.4.4 | ScalarcpqWcrmWaterCoolUnitStatus | read-only | mandatory | General Status sensor unit connected to port 2 (1) OK (2) error (3) configuration of sensor unit has changed, confirmation required (4) reset from sensor unit … |
| 1.3.6.1.4.1.232.167.2.4.5 | NodecpqWcrmStatusWaterCoolUnitSensors | |||
| 1.3.6.1.4.1.232.167.2.4.5.1 | ScalarcpqWcrmWaterCoolUnitNumberOfSensors | read-only | mandatory | Number of sensors connected to water cool unit |
| 1.3.6.1.4.1.232.167.2.4.5.2 | TablecpqWcrmWaterCoolUnitSensorTable | not-accessible | mandatory | Headline of sensor table |
| 1.3.6.1.4.1.232.167.2.4.5.2.1 | RowcpqWcrmWaterCoolUnitSensorEntry | not-accessible | mandatory | Entries of sensor table |
| 1.3.6.1.4.1.232.167.2.4.5.2.1.1 | ColumnwaterCoolUnitSensorIndex | read-only | mandatory | Index for the list of value entries. Its value ranges between 1 and the value of cpqWcrmWaterCoolUnitNumberOfSensors. |
| 1.3.6.1.4.1.232.167.2.4.5.2.1.2 | ColumnwaterCoolUnitSensorType | read-only | mandatory | Type of sensor which is connected to internal sensor to sensor[internalSensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: average tempe… |
| 1.3.6.1.4.1.232.167.2.4.5.2.1.3 | ColumnwaterCoolUnitSensorText | read-write | mandatory | Descriptional text for each sensor (entry in the table) |
| 1.3.6.1.4.1.232.167.2.4.5.2.1.4 | ColumnwaterCoolUnitSensorStatus | read-only | mandatory | Actual status of the sensor |
| 1.3.6.1.4.1.232.167.2.4.5.2.1.5 | ColumnwaterCoolUnitSensorValue | read-only | mandatory | Value of sensor added to traps, msg index also added (waterCoolUnitMsgIndex) If msg index = 1, 5 or 6 This value represents the actual Server Intake Temperatur… |
| 1.3.6.1.4.1.232.167.2.4.5.2.1.6 | ColumnwaterCoolUnitSensorSetHigh | read-write | mandatory | Value for high setpoint of sensor |
| 1.3.6.1.4.1.232.167.2.4.5.2.1.7 | ColumnwaterCoolUnitSensorSetLow | read-write | mandatory | Value for low setpoint of sensor, also used as alarm delay |
| 1.3.6.1.4.1.232.167.2.4.5.2.1.8 | ColumnwaterCoolUnitSensorSetWarn | read-write | mandatory | Value for warning setpoint of sensor, also used as fan threshold |
| 1.3.6.1.4.1.232.167.2.4.5.2.1.9 | ColumnwaterCoolUnitSensorValueScale | read-only | mandatory | Scaling factor for scaled sensor value to get the unscaled value, e. g. -100 -> waterCoolUnitSensorScaledValue has to be divided by 100 +100 -> waterCoolUnitSe… |
| 1.3.6.1.4.1.232.167.2.4.5.2.1.10 | ColumnwaterCoolUnitSensorScaledValue | read-only | mandatory | Scaled value of sensor |
| 1.3.6.1.4.1.232.167.2.4.6 | NodecpqWcrmStatusWaterCoolUnitOutputs | |||
| 1.3.6.1.4.1.232.167.2.4.6.1 | ScalarcpqWcrmWaterCoolUnitNumberOfOutputs | read-only | mandatory | Number of outputs available on sensor water cool unit |
| 1.3.6.1.4.1.232.167.2.4.6.2 | TablecpqWcrmWaterCoolUnitOutputTable | not-accessible | mandatory | Headline of output table |
| 1.3.6.1.4.1.232.167.2.4.6.2.1 | RowcpqWcrmWaterCoolUnitOutputEntry | not-accessible | mandatory | Entries of output table |
| 1.3.6.1.4.1.232.167.2.4.6.2.1.1 | ColumnwaterCoolUnitOutputIndex | read-only | mandatory | Index for the list of output entries. Its value ranges between 1 and the value of cpqWcrmWaterCoolUnitNumberOfOutputs. |
| 1.3.6.1.4.1.232.167.2.4.6.2.1.2 | ColumnwaterCoolUnitOutputType | read-only | mandatory | Type of output which is connected to water cool unit to output[waterCoolUnitOutputIndex] 1: no output connected 2: output failure 3: value overflow 4: water va… |
| 1.3.6.1.4.1.232.167.2.4.6.2.1.3 | ColumnwaterCoolUnitOutputText | read-write | mandatory | Descriptional text for each output (entry in the table) |
| 1.3.6.1.4.1.232.167.2.4.6.2.1.4 | ColumnwaterCoolUnitOutputStatus | read-write | mandatory | Actual status of the output |
| 1.3.6.1.4.1.232.167.2.4.6.2.1.5 | ColumnwaterCoolUnitOutputValue | read-write | mandatory | Signed value for output |
| 1.3.6.1.4.1.232.167.2.4.6.2.1.6 | ColumnwaterCoolUnitOutputSet | read-write | mandatory | Command for output |
| 1.3.6.1.4.1.232.167.2.4.6.2.1.7 | ColumnwaterCoolUnitOutputConfig | read-write | mandatory | Configuration for output 1: disable remote control (e.g. keypad) 2: enable remote control |
| 1.3.6.1.4.1.232.167.2.4.6.2.1.8 | ColumnwaterCoolUnitOutputDelay | read-write | mandatory | Unsigned Value for delay, after this time the output will fall into the previous state |
| 1.3.6.1.4.1.232.167.2.4.6.2.1.9 | ColumnwaterCoolUnitOutputTimeoutAction | read-write | mandatory | State for output if timeout (RS422) occurs |
| 1.3.6.1.4.1.232.167.2.4.7 | NodecpqWcrmStatusWaterCoolUnitMsg | |||
| 1.3.6.1.4.1.232.167.2.4.7.1 | ScalarcpqWcrmWaterCoolUnitNumberOfMsgs | read-only | mandatory | Number of alarms that can be created with water cool unit |
| 1.3.6.1.4.1.232.167.2.4.7.2 | TablecpqWcrmWaterCoolUnitMsgTable | not-accessible | mandatory | Headline of message table |
| 1.3.6.1.4.1.232.167.2.4.7.2.1 | RowcpqWcrmWaterCoolUnitMsgEntry | not-accessible | mandatory | Entries of message table |
| 1.3.6.1.4.1.232.167.2.4.7.2.1.1 | ColumnwaterCoolUnitMsgIndex | read-only | mandatory | Index for the list of alarm entries. Its value ranges between 1 and the value of cpqWcrmWaterCoolUnitNumberOfMsgs. |
| 1.3.6.1.4.1.232.167.2.4.7.2.1.2 | ColumnwaterCoolUnitMsgText | read-write | mandatory | Descriptional text for each message (entry in the table) |
| 1.3.6.1.4.1.232.167.2.4.7.2.1.3 | ColumnwaterCoolUnitMsgStatus | read-only | mandatory | Actual message status 4: OK 5: alarm 6: warning 7: analog value too low, value reached low threshold 8: analog value too high, value reached high threshold |
| 1.3.6.1.4.1.232.167.2.4.7.2.1.4 | ColumnwaterCoolUnitMsgRelay | read-write | mandatory | Setup of Alarm relay for this alarm 2: no switching of alarm relay 1: switching of alarm relay |
| 1.3.6.1.4.1.232.167.2.4.7.2.1.5 | ColumnwaterCoolUnitMsgBeeper | read-write | mandatory | Setup of Alarm beeper for this alarm 2: no audible alarm 1: audible alarm |
| 1.3.6.1.4.1.232.167.2.4.7.2.1.6 | ColumnwaterCoolUnitMsgTrap1 | read-write | mandatory | Trap receiver 1 activated |
| 1.3.6.1.4.1.232.167.2.4.7.2.1.7 | ColumnwaterCoolUnitMsgTrap2 | read-write | mandatory | Trap receiver 2 activated |
| 1.3.6.1.4.1.232.167.2.4.7.2.1.8 | ColumnwaterCoolUnitMsgTrap3 | read-write | mandatory | Trap receiver 3 activated |
| 1.3.6.1.4.1.232.167.2.4.7.2.1.9 | ColumnwaterCoolUnitMsgTrap4 | read-write | mandatory | Trap receiver 4 and Event Logging activated |
| 1.3.6.1.4.1.232.167.2.4.7.2.1.10 | ColumnwaterCoolUnitMsgReset | read-write | mandatory | Reset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key |
| 1.3.6.1.4.1.232.167.2.7 | ScalarcpqWcrmURL | read-only | mandatory | URL of the management interface in the format http[s]://ipaddr[:port#][/page] |
| 1.3.6.1.4.1.232.167.3 | NodecpqWcrmSetup | |||
| 1.3.6.1.4.1.232.167.3.1 | NodecpqWcrmSetupGeneral | |||
| 1.3.6.1.4.1.232.167.3.1.1 | ScalarcpqWcrmSetTempUnit | read-write | mandatory | Unit of all temperature values and setpoints, Celsius or Fahrenheit |
| 1.3.6.1.4.1.232.167.3.1.2 | ScalarcpqWcrmSetBeeper | read-write | mandatory | Audible alarm in Environmental Controller unit: (2): beeper is on (1): beeper is off (general) |
| 1.3.6.1.4.1.232.167.3.1.3 | ScalarcpqWcrmResetRelay | read-write | mandatory | Enable or disable acknowledging currently active alarm relay (with 'C' on Environmental Controller). |
| 1.3.6.1.4.1.232.167.3.1.4 | ScalarcpqWcrmLogicRelay | read-write | mandatory | Logic of alarm relay: (1) Relay will pick up in case of an alarm (2) Relay will release in case of an alarm (3) Relay off (general) |
| 1.3.6.1.4.1.232.167.3.1.5 | ScalarcpqWcrmWebAccess | read-write | mandatory | Web access via HTTP: (1) view only (2) full Access, read and set (3) Web disabled (general) |
| 1.3.6.1.4.1.232.167.3.1.6 | ScalarcpqWcrmSetupDate | read-write | mandatory | actual Date in format DD.MM.YYYY |
| 1.3.6.1.4.1.232.167.3.1.7 | ScalarcpqWcrmSetupTime | read-write | mandatory | actual Time in format HH:MM:SS, HH (0-23), MM (0-59), SS (0-59) |
| 1.3.6.1.4.1.232.167.3.1.8 | NodecpqWcrmTimerTable1 | |||
| 1.3.6.1.4.1.232.167.3.1.8.1 | ScalarcpqWcrmTimerNumber | read-only | mandatory | Number of value-table entries=number of outlets available on this unit |
| 1.3.6.1.4.1.232.167.3.1.8.2 | TablecpqWcrmTimerTable | not-accessible | mandatory | Headline of status-table |
| 1.3.6.1.4.1.232.167.3.1.8.2.1 | RowcpqWcrmTimerEntry | not-accessible | mandatory | Entries of timer-table |
| 1.3.6.1.4.1.232.167.3.1.8.2.1.1 | ColumncpqWcrmTimerIndex | read-only | mandatory | Index for the list of timer entries. Its value ranges between 1 and the value of cpqWcrmTimerNumber. |
| 1.3.6.1.4.1.232.167.3.1.8.2.1.2 | ColumncpqWcrmTimerStatus | read-only | mandatory | Actual status of the timer |
| 1.3.6.1.4.1.232.167.3.1.8.2.1.3 | ColumncpqWcrmTimerDayOfWeek | read-write | mandatory | Selection of day of week for timer to switch |
| 1.3.6.1.4.1.232.167.3.1.8.2.1.4 | ColumncpqWcrmTimeOn | read-write | mandatory | Time to switch on current function, Format: HH:MM |
| 1.3.6.1.4.1.232.167.3.1.8.2.1.5 | ColumncpqWcrmTimeOff | read-write | mandatory | Time to switch off current function, Format: HH:MM |
| 1.3.6.1.4.1.232.167.3.1.8.2.1.6 | ColumncpqWcrmTimeControl | read-write | mandatory | Control via RTC |
| 1.3.6.1.4.1.232.167.3.1.8.2.1.7 | ColumncpqWcrmTimerFunction | read-write | mandatory | Function which is controlled via timer 1-4: sending Traps to this Trap receiver will be disabled 5 - 8: scheduled alarm off |
| 1.3.6.1.4.1.232.167.3.1.9 | ScalarcpqWcrmSetFlowUnit | read-write | mandatory | Unit of Water Flow, Liter/min or Gallon/min |
| 1.3.6.1.4.1.232.167.4 | NodecpqWcrmTrapControl | |||
| 1.3.6.1.4.1.232.167.4.7 | NodecpqWcrmTraps | |||
| 1.3.6.1.4.1.232.167.4.7.1 | ScalarcpqWcrmTraptableNumber | read-only | mandatory | Number of trapTable entries. The number of trap-receiver |
| 1.3.6.1.4.1.232.167.4.7.2 | TablecpqWcrmTrapTableTable | not-accessible | mandatory | A list of trap-receiver entries |
| 1.3.6.1.4.1.232.167.4.7.2.1 | RowcpqWcrmTrapTableEntry | not-accessible | mandatory | Entries of trapTable |
| 1.3.6.1.4.1.232.167.4.7.2.1.1 | ColumntrapIndex | read-only | mandatory | Index for the trap-receiver-table. Its value ranges between 1 and the value of traptableNumber |
| 1.3.6.1.4.1.232.167.4.7.2.1.2 | ColumntrapStatus | read-write | mandatory | Enable or disable trap receiver |
| 1.3.6.1.4.1.232.167.4.7.2.1.3 | ColumntrapIPaddress | read-write | mandatory | IP-address of trap-receiver |
| 1.3.6.1.4.1.232.167.4.7.2.1.4 | ColumntrapIPV4V6address | read-write | mandatory | IP-address of trap-receiver |
| 1.3.6.1.4.1.232.167.5 | NodealarmInternal | Internal Unit Alarm | ||
| 1.3.6.1.4.1.232.167.5 | NodecpqWcrmControl | |||
| 1.3.6.1.4.1.232.167.5.1 | ScalarcpqWcrmResetUnit | read-write | mandatory | Command to reset (acknowledge) alarms of Environmental Controller unit. Setting to 'reset' (2) will have same result as pressing 'C' on Units. Variable is auto… |
| 1.3.6.1.4.1.232.167.6 | NodealarmWaterCoolUnit | Water Cool Unit System Alarm | ||
| 1.3.6.1.4.1.232.167.10 | NodetestTrap | Test trap sent to a trap receiver to check proper reception of traps |