1.3.6.1.4.1.3808Nodecps
1.3.6.1.4.1.3808.1NodecommunicationLostSEVERE: Communication with the UPS has been lost.
1.3.6.1.4.1.3808.1Nodeproducts
1.3.6.1.4.1.3808.1.1Nodehardware
1.3.6.1.4.1.3808.1.1.1Nodeups
1.3.6.1.4.1.3808.1.1.1.1NodeupsIdent
1.3.6.1.4.1.3808.1.1.1.1.1NodeupsBaseIdent
1.3.6.1.4.1.3808.1.1.1.1.1.1ScalarupsBaseIdentModelread-onlymandatoryThe UPS model name.
1.3.6.1.4.1.3808.1.1.1.1.1.2ScalarupsBaseIdentNameread-writemandatoryThe UPS identified name could be set by the administrator.
1.3.6.1.4.1.3808.1.1.1.1.2NodeupsAdvanceIdent
1.3.6.1.4.1.3808.1.1.1.1.2.1ScalarupsAdvanceIdentFirmwareRevisionread-onlymandatoryThe UPS firmware revision.
1.3.6.1.4.1.3808.1.1.1.1.2.2ScalarupsAdvanceIdentDateOfManufactureread-onlymandatoryThe UPS manufacture date in mm/dd/yy format.
1.3.6.1.4.1.3808.1.1.1.1.2.3ScalarupsAdvanceIdentSerialNumberread-onlymandatoryThe UPS serial number in the internal microprocessor.
1.3.6.1.4.1.3808.1.1.1.1.2.4ScalarupsAdvanceIdentAgentFirmwareRevisionread-onlymandatoryThe SNMP agent firmware revision.
1.3.6.1.4.1.3808.1.1.1.1.2.5ScalarupsAdvanceIdentLCDFirmwareVersionread-onlymandatoryThe revision number of the UPS LCD firmware.
1.3.6.1.4.1.3808.1.1.1.1.2.6ScalarupsAdvanceIdentPowerRatingread-onlymandatoryThe Volt-Amp rating of the UPS.
1.3.6.1.4.1.3808.1.1.1.1.2.7ScalarupsAdvanceIdentLoadPowerread-onlymandatoryThe power rating(Watts) of the UPS.
1.3.6.1.4.1.3808.1.1.1.1.2.8ScalarupsAdvanceIdentCurrentRatingread-onlymandatoryThe output current rating of the UPS. Measured in tenths of Amps.
1.3.6.1.4.1.3808.1.1.1.2NodeupsBattery
1.3.6.1.4.1.3808.1.1.1.2.1NodeupsBaseBattery
1.3.6.1.4.1.3808.1.1.1.2.1.1ScalarupsBaseBatteryStatusread-onlymandatoryThe UPS battery status. A batteryLow(3) value means the battery will be exhausted soon under the current load. The amount of low battery run time can be config…
1.3.6.1.4.1.3808.1.1.1.2.1.2ScalarupsBaseBatteryTimeOnBatteryread-onlymandatoryThe UPS wasted battery time since the UPS has transfered to backup mode.
1.3.6.1.4.1.3808.1.1.1.2.1.3ScalarupsBaseBatteryLastReplaceDateread-writemandatoryThe UPS batteries last replaced date in mm/dd/yy format. This value is originally set when manufactured. If batteries replaced, administrator should reset this…
1.3.6.1.4.1.3808.1.1.1.2.2NodeupsAdvanceBattery
1.3.6.1.4.1.3808.1.1.1.2.2.1ScalarupsAdvanceBatteryCapacityread-onlymandatoryThe battery capacity expressed in percentage.
1.3.6.1.4.1.3808.1.1.1.2.2.2ScalarupsAdvanceBatteryVoltageread-onlymandatoryThe battery voltage expressed in 1/10 VDC.
1.3.6.1.4.1.3808.1.1.1.2.2.3ScalarupsAdvanceBatteryTemperatureread-onlymandatoryThe UPS battery temperature expressed in Celsius.
1.3.6.1.4.1.3808.1.1.1.2.2.4ScalarupsAdvanceBatteryRunTimeRemainingread-onlymandatoryThe UPS battery remaining run time.
1.3.6.1.4.1.3808.1.1.1.2.2.5ScalarupsAdvanceBatteryReplaceIndicatorread-onlymandatoryThis value indicates if UPS batteries need to be replaced.
1.3.6.1.4.1.3808.1.1.1.2.2.6ScalarupsAdvanceBatteryFullChargeVoltageread-onlymandatoryThe battery charged voltage expressed in 1/10 VDC.
1.3.6.1.4.1.3808.1.1.1.2.2.7ScalarupsAdvanceBatteryCurrentread-onlymandatoryThe battery current expressed in percentage.
1.3.6.1.4.1.3808.1.1.1.2.2.8ScalarupsAdvanceBatteryVoltageRatingread-onlymandatoryThe DC voltage rating of the battery set.
1.3.6.1.4.1.3808.1.1.1.3NodeupsInput
1.3.6.1.4.1.3808.1.1.1.3.1NodeupsBaseInput
1.3.6.1.4.1.3808.1.1.1.3.1.1ScalarupsBaseInputPhaseread-onlymandatoryThe AC input phase.
1.3.6.1.4.1.3808.1.1.1.3.2NodeupsAdvanceInput
1.3.6.1.4.1.3808.1.1.1.3.2.1ScalarupsAdvanceInputLineVoltageread-onlymandatoryThe input line voltage in 1/10 VAC.
1.3.6.1.4.1.3808.1.1.1.3.2.2ScalarupsAdvanceInputMaxLineVoltageread-onlymandatoryThe maximum input line voltage in 1/10 VAC over the previous 1 minute period.
1.3.6.1.4.1.3808.1.1.1.3.2.3ScalarupsAdvanceInputMinLineVoltageread-onlymandatoryThe minimum input line voltage in 1/10 VAC over the previous 1 minute period.
1.3.6.1.4.1.3808.1.1.1.3.2.4ScalarupsAdvanceInputFrequencyread-onlymandatoryThe input line frequency in 1/10 Hz.
1.3.6.1.4.1.3808.1.1.1.3.2.5ScalarupsAdvanceInputLineFailCauseread-onlymandatoryThe reason of UPS power failure. This value is set to: - noTransfer(1), if UPS is in utility mode. - highLineVoltage(2), if UPS switch to battery mode by reaso…
1.3.6.1.4.1.3808.1.1.1.3.2.6ScalarupsAdvanceInputStatusread-onlymandatoryDisplay the present status of the utility power supplied to the UPS.
1.3.6.1.4.1.3808.1.1.1.4NodeupsOutput
1.3.6.1.4.1.3808.1.1.1.4.1NodeupsBaseOutput
1.3.6.1.4.1.3808.1.1.1.4.1.1ScalarupsBaseOutputStatusread-onlymandatoryThe UPS output status.
1.3.6.1.4.1.3808.1.1.1.4.1.2ScalarupsBaseOutputPhaseread-onlymandatoryThe output phase.
1.3.6.1.4.1.3808.1.1.1.4.1.3ScalarupsBaseOutputWorkingFrequencyread-onlymandatoryThe frequency of the UPS output power.
1.3.6.1.4.1.3808.1.1.1.4.2NodeupsAdvanceOutput
1.3.6.1.4.1.3808.1.1.1.4.2.1ScalarupsAdvanceOutputVoltageread-onlymandatoryThe UPS output voltage in 1/10 VAC.
1.3.6.1.4.1.3808.1.1.1.4.2.2ScalarupsAdvanceOutputFrequencyread-onlymandatoryThe UPS output frequency in 1/10 Hz.
1.3.6.1.4.1.3808.1.1.1.4.2.3ScalarupsAdvanceOutputLoadread-onlymandatoryThe UPS output load expressed in percentage
1.3.6.1.4.1.3808.1.1.1.4.2.4ScalarupsAdvanceOutputCurrentread-onlymandatoryThe UPS output current in Amps.
1.3.6.1.4.1.3808.1.1.1.5NodeupsConfig
1.3.6.1.4.1.3808.1.1.1.5.1NodeupsBaseConfig
1.3.6.1.4.1.3808.1.1.1.5.1.1ScalarupsBaseConfigNumDevicesread-onlymandatoryThe number of equipment plugged into the UPS.
1.3.6.1.4.1.3808.1.1.1.5.1.2TableupsBaseConfigDeviceTablenot-accessiblemandatoryA list of equipment plugged into the UPS. The numbers of entries are given by the value of upsBaseConfigNumDevices.
1.3.6.1.4.1.3808.1.1.1.5.1.2.1RowupsBaseConfigDeviceEntrynot-accessiblemandatoryThe equipment plugged in to the UPS.
1.3.6.1.4.1.3808.1.1.1.5.1.2.1.1ColumndeviceIndexread-onlymandatoryThe index of the equipment plugged into the UPS.
1.3.6.1.4.1.3808.1.1.1.5.1.2.1.2ColumndeviceNameread-writemandatoryThe name of the equipment plugged into the UPS.
1.3.6.1.4.1.3808.1.1.1.5.1.2.1.3ColumnvaRatingread-writemandatoryThe VA rating of the equipment plugged into the UPS.
1.3.6.1.4.1.3808.1.1.1.5.1.2.1.4ColumnacceptThisDeviceread-writemandatoryAn equipment is plugged if yes, unplugged if no.
1.3.6.1.4.1.3808.1.1.1.5.2NodeupsAdvanceConfig
1.3.6.1.4.1.3808.1.1.1.5.2.1ScalarupsAdvanceConfigRatedOutputVoltageread-writemandatoryThe standard UPS output voltage in VAC. The possible values are 100, 110, 120, 127, 208, 220, 230, and 240. If a value other than a possible value is set, it w…
1.3.6.1.4.1.3808.1.1.1.5.2.2ScalarupsAdvanceConfigHighTransferVoltread-writemandatoryAdjust the high transfer vloltage in VAC. The high transfer vloltage will become the UPS default value subtracts this value. The allowed values depend on the o…
1.3.6.1.4.1.3808.1.1.1.5.2.3ScalarupsAdvanceConfigLowTransferVoltread-writemandatoryAdjust the low transfer vloltage in VAC. The low transfer vloltage will become the UPS default value adds this value. The allowed values depend on the output: …
1.3.6.1.4.1.3808.1.1.1.5.2.4ScalarupsAdvanceConfigAlarmread-writemandatoryThis value is set to handle audible alarms when power failure.
1.3.6.1.4.1.3808.1.1.1.5.2.5ScalarupsAdvanceConfigAlarmTimerread-writemandatoryThe time after power failure at which the UPS begins giving audible alarms. This timer is effective only if the value of upsAdvanceConfigAlarm is timed(1). Acc…
1.3.6.1.4.1.3808.1.1.1.5.2.6ScalarupsAdvanceConfigMinReturnCapacityread-writemandatoryThe minimum battery capacity that UPS will return from a low battery shutdown condition. The possible values are between 0 to 40. If a value other than a suppo…
1.3.6.1.4.1.3808.1.1.1.5.2.7ScalarupsAdvanceConfigSensitivityread-writemandatoryThe sensitivity of the UPS to power failure detection.
1.3.6.1.4.1.3808.1.1.1.5.2.8ScalarupsAdvanceConfigLowBatteryRunTimeread-writemandatoryThe desired run time, in seconds, UPS will enter in a low battery sequence. The possible values are 120, 300, 420, 600. If a value other than a supported value…
1.3.6.1.4.1.3808.1.1.1.5.2.9ScalarupsAdvanceConfigReturnDelayread-writemandatoryThe delay time the UPS will turn on after power recovery. The value is also used in a 'reboot' or 'wake up' sequence. The possible values are 0 to 600 seconds.…
1.3.6.1.4.1.3808.1.1.1.5.2.10ScalarupsAdvanceConfigShutoffDelayread-writemandatoryThe delay time the UPS will remain on after receiving a turn off command. The possible values are between 1 to 99 minutes. If a value other than a supported va…
1.3.6.1.4.1.3808.1.1.1.5.2.11ScalarupsAdvanceConfigSleepDelayread-writemandatoryThe delay time the UPS will enter sleep mode after receiving a sleep command. WThe possible values are between 1 to 99 minutes. If a value other than a support…
1.3.6.1.4.1.3808.1.1.1.5.2.12ScalarupsAdvanceConfigSetEEPROMDefaultsread-writemandatoryReset the UPS EEPROM parameters to default values.
1.3.6.1.4.1.3808.1.1.1.5.2.13ScalarupsAdvanceConfigAutoRestoreread-writemandatoryWhen this option is enabled, the UPS will restore output immediately when the utility power restores.When this option is disabled, the UPS will not restore out…
1.3.6.1.4.1.3808.1.1.1.5.2.14ScalarupsAdvanceConfigRechargedCapacityread-writemandatoryWhen the utility power restores, the UPS will start to recharge until the specified battery capacity in percentage is met before restoring output power. The po…
1.3.6.1.4.1.3808.1.1.1.5.2.15ScalarupsAdvanceConfigColdStartread-writemandatorySet the ability of the UPS can start in the absence of input power.When this option is enabled the UPS can be turned on without having input power.
1.3.6.1.4.1.3808.1.1.1.5.2.16ScalarupsAdvanceConfigDeepDischargeProtectionread-writemandatoryWhen the UPS is on Battery Mode with 0% load and the status remains for the time configured,the RMCARD will enforce the UPS to Sleep Mode and the output will b…
1.3.6.1.4.1.3808.1.1.1.5.2.17ScalarupsAdvanceConfigSleepAfterAllClientShutread-writemandatoryIf this option is enabled, UPS will enter sleep mode after utility power failed and remaining MSDT+2 minutes.More information about MSDT please reference to he…
1.3.6.1.4.1.3808.1.1.1.6NodeupsControl
1.3.6.1.4.1.3808.1.1.1.6.1NodeupsBaseControl
1.3.6.1.4.1.3808.1.1.1.6.1.1ScalarupsBaseControlConserveBatteryread-writemandatoryUPS on battery will enter sleeping when the variable is set to turnOffUpsToConserveBattery(2). When utility power recovers the UPS will turn back on. Trying to…
1.3.6.1.4.1.3808.1.1.1.6.2NodeupsAdvanceControl
1.3.6.1.4.1.3808.1.1.1.6.2.1ScalarupsAdvanceControlUpsOffread-writemandatoryUPS will shutdown when the variable is set to turnUpsOff(2). UPS will shutdown after a delay period specified by upsAdvanceConfigShutoffDelay when the variable…
1.3.6.1.4.1.3808.1.1.1.6.2.2ScalarupsAdvanceControlRebootUpsread-writemandatoryUPS will shutdown and turn back on when the variable is set to rebootUps(2). It is no effective to set this value to noRebootUps(1).
1.3.6.1.4.1.3808.1.1.1.6.2.3ScalarupsAdvanceControlUpsSleepread-writemandatoryUPS will enter sleep mode when the variable is set to putUpsToSleep(2). UPS will enter sleep mode after a delay period specified by upsAdvanceConfigSleepDelay …
1.3.6.1.4.1.3808.1.1.1.6.2.4ScalarupsAdvanceControlSimulatePowerFailread-writemandatoryUPS will transfer to backup mode when the variable is set to simulatePowerFailure(2). It is no effective to set this value to noFlashAndBeep(1).
1.3.6.1.4.1.3808.1.1.1.6.2.5ScalarupsAdvanceControlFlashAndBeepread-writemandatoryUPS will beep and simultaneously turn on the panel lights when the variable is set to flashAndBeep(2). It is no effective to set this value to noSimulatePowerF…
1.3.6.1.4.1.3808.1.1.1.6.2.6ScalarupsAdvanceControlTurnOnUPSread-writemandatoryUPS will turned on immediately when the variable is set to turnOnUPS(2). It is no effective to set this value to noTurnOnUPS(1).
1.3.6.1.4.1.3808.1.1.1.7NodeupsTest
1.3.6.1.4.1.3808.1.1.1.7.1NodeupsBaseTest
1.3.6.1.4.1.3808.1.1.1.7.2NodeupsAdvanceTest
1.3.6.1.4.1.3808.1.1.1.7.2.1ScalarupsAdvanceTestDiagnosticScheduleread-writemandatoryThe schedule of the UPS automatic selftest.
1.3.6.1.4.1.3808.1.1.1.7.2.2ScalarupsAdvanceTestDiagnosticsread-writemandatoryUPS will do a diagnostic selftest when the variable is set to testDiagnostics(2). It is no effective to set this value to noTestDiagnostics(1).
1.3.6.1.4.1.3808.1.1.1.7.2.3ScalarupsAdvanceTestDiagnosticsResultsread-onlymandatoryThe last UPS selftest result.
1.3.6.1.4.1.3808.1.1.1.7.2.4ScalarupsAdvanceTestLastDiagnosticsDateread-onlymandatoryThe last UPS selftest date in mm/dd/yy format.
1.3.6.1.4.1.3808.1.1.1.7.2.5ScalarupsAdvanceTestIndicatorsread-writemandatoryUPS will perform a panel indicator test when the variable is set to testIndicators(2). It is no effective to set this value to noTestIndicators(1).
1.3.6.1.4.1.3808.1.1.1.7.2.6ScalarupsAdvanceTestRuntimeCalibrationread-writemandatoryUPS will discharge to calibrate the UPS runtime when the variable is set to performCalibration(2). This test runs until the UPS is in a low battery condition. …
1.3.6.1.4.1.3808.1.1.1.7.2.7ScalarupsAdvanceTestCalibrationResultsread-onlymandatoryThe last runtime calibration result. This value means : - ok(1), if a successful runtime calibration. - invalidCalibration(2), if runtime calibration failure. …
1.3.6.1.4.1.3808.1.1.1.7.2.8ScalarupsAdvanceTestCalibrationDateread-onlymandatoryThe last UPS runtime calibration date
1.3.6.1.4.1.3808.1.1.1.8NodeupsOutlet
1.3.6.1.4.1.3808.1.1.1.8.1NodeupsBankOutletControl
1.3.6.1.4.1.3808.1.1.1.8.1.1TableupsBankOutletControlTablenot-accessiblemandatoryAllows for control of the outlet banks.
1.3.6.1.4.1.3808.1.1.1.8.1.1.1RowupsBankOutletControlEntrynot-accessiblemandatoryThe outlet to control.
1.3.6.1.4.1.3808.1.1.1.8.1.1.1.1ColumnupsBankControlIndexread-onlymandatoryThe index to the outlet entry.
1.3.6.1.4.1.3808.1.1.1.8.1.1.1.2ColumnupsBankControlOutletCommandread-writemandatoryGetting this variable will return the outlet bank state. If the outlet bank is on, the immediateOn (1) value will be returned. If the outlet bank is off, the i…
1.3.6.1.4.1.3808.1.1.2Nodeeswitch
1.3.6.1.4.1.3808.1.1.2.1NodeeSwitchIdent
1.3.6.1.4.1.3808.1.1.2.1.1ScalareSwitchIdentHardwareRevread-onlymandatoryThe hardware revision set at the factory.
1.3.6.1.4.1.3808.1.1.2.1.2ScalareSwitchIdentFirmwareRevread-onlymandatoryThe firmware revision set at the factory.
1.3.6.1.4.1.3808.1.1.2.1.3ScalareSwitchIdentDateOfManufactureread-onlymandatoryThe manufacture date in mm/dd/yy format.
1.3.6.1.4.1.3808.1.1.2.1.4ScalareSwitchIdentModelNameread-onlymandatoryThe model name set at the factory. This value need to consist with safty report.
1.3.6.1.4.1.3808.1.1.2.2NodeeSwitchBase
1.3.6.1.4.1.3808.1.1.2.2.1ScalareSwitchNumberread-onlymandatoryThe numbers of switch have been attached to the system.
1.3.6.1.4.1.3808.1.1.2.2.2TableeSwitchBaseTablenot-accessiblemandatoryA list of switch information. The number of entries is given by the value of eSwitchNumber.
1.3.6.1.4.1.3808.1.1.2.2.2.1RoweSwitchBaseEntrynot-accessiblemandatoryAn entry information of the individual switch.
1.3.6.1.4.1.3808.1.1.2.2.2.1.1ColumneSwitchIDread-onlymandatoryThe power switch ID number.
1.3.6.1.4.1.3808.1.1.2.2.2.1.2ColumneSwitchOutletNumread-onlymandatoryThe number of outlets provided in the switch.
1.3.6.1.4.1.3808.1.1.2.2.2.1.3ColumneSwitchOutletStateread-onlymandatoryGetting this OID will reply the status of all outlets in the switch. '0' for outlet off, '1' for outlet on. The index from left to right is outlet#8, #7, #6, #…
1.3.6.1.4.1.3808.1.1.2.2.3TableeSwitchBaseCtrTablenot-accessiblemandatoryA list of switch control parameters. The number of entries is given by the value of eSwitchNumber.
1.3.6.1.4.1.3808.1.1.2.2.3.1RoweSwitchBaseCtrEntrynot-accessiblemandatoryAn entry control information of individual switches.
1.3.6.1.4.1.3808.1.1.2.2.3.1.1ColumneSwitchCtrIDread-writemandatorySelect the switch ID to be controlled.
1.3.6.1.4.1.3808.1.1.2.2.3.1.2ColumneSwitchActOutletread-writemandatoryThe action outlets to be controlled.
1.3.6.1.4.1.3808.1.1.2.2.3.1.3ColumneSwitchActTyperead-writemandatoryThe on/off type of the action outlets. 1 for duration off, 2 for duration on, 3 for immediately off, 4 for immediately on, and 5 for reboot.
1.3.6.1.4.1.3808.1.1.3NodeePDU
1.3.6.1.4.1.3808.1.1.3.1NodeePDUIdent
1.3.6.1.4.1.3808.1.1.3.1.1ScalarePDUIdentNameread-writemandatoryThe name of the Rack PDU. The maximum string size is device dependent.
1.3.6.1.4.1.3808.1.1.3.1.2ScalarePDUIdentHardwareRevread-onlymandatoryThe hardware revision of the Rack PDU. This value is set at the factory.
1.3.6.1.4.1.3808.1.1.3.1.3ScalarePDUIdentFirmwareRevread-onlymandatoryAn 8-byte ID string identifying the Rack PDU firmware revision. This value is set at the factory.
1.3.6.1.4.1.3808.1.1.3.1.4ScalarePDUIdentDateOfManufactureread-onlymandatoryThe date when the Rack PDU was manufactured in mm/dd/yyyy format. This value is set at the factory. The year 2000 will be represented by 00.
1.3.6.1.4.1.3808.1.1.3.1.5ScalarePDUIdentModelNumberread-onlymandatoryA 10-character string identifying the model number of the Rack PDU. This value is set at the factory.
1.3.6.1.4.1.3808.1.1.3.1.6ScalarePDUIdentSerialNumberread-onlymandatoryA 12-character string identifying the serial number of the Rack PDU. This value is set at the factory.
1.3.6.1.4.1.3808.1.1.3.1.7ScalarePDUIdentDeviceRatingread-onlymandatoryGetting this OID will return the electrical rating of the device.
1.3.6.1.4.1.3808.1.1.3.1.8ScalarePDUIdentDeviceNumOutletsread-onlymandatoryGetting this OID will return the number of outlets contained in the device.
1.3.6.1.4.1.3808.1.1.3.1.9ScalarePDUIdentDeviceNumPhasesread-onlymandatoryGetting this OID will return the number of phases supported by the device.
1.3.6.1.4.1.3808.1.1.3.1.10ScalarePDUIdentDeviceNumBreakersread-onlymandatoryGetting this OID will return the number of circuit breakers supported by the device. This is the same as the number of banks of outlets. 0 will be returned if …
1.3.6.1.4.1.3808.1.1.3.1.11ScalarePDUIdentDeviceBreakerRatingread-onlymandatoryGetting this OID will return rating of the circuit breakers on the device if it has any.
1.3.6.1.4.1.3808.1.1.3.1.12ScalarePDUIdentDeviceOrientationread-onlymandatoryGetting this OID will return the intended physical orientation of the device. OrientHorizonatal(1) indicates Horizontal. OrientVertical(2) indicates Vertical.
1.3.6.1.4.1.3808.1.1.3.1.13ScalarePDUIdentDeviceOutletLayoutread-onlymandatoryGetting this OID will return outlet layout for the device. SeqPhaseToNeutral(1) indicates outlet layout as follows: 1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,... SeqPhaseT…
1.3.6.1.4.1.3808.1.1.3.1.14ScalarePDUIdentDeviceDisplayOrientationread-writemandatoryGetting this OID will return the intended physical orientation of the Seven-Segment Display. displayNormal(1) indicates Normal. displayReverse(2)indicates Upsi…
1.3.6.1.4.1.3808.1.1.3.1.15ScalarePDUIdentDeviceLinetoLineVoltageread-writemandatoryGetting/Setting this OID will return/set the Line to Line Volatage. The valid range is between 0V to 440V
1.3.6.1.4.1.3808.1.1.3.1.16ScalarePDUIdentIndicatorread-writemandatoryPDU will perform a panel indicator test when the variable is set to testIndicators(2). It is no effective to set this value to noTestIndicators(1).
1.3.6.1.4.1.3808.1.1.3.2NodeePDULoad
1.3.6.1.4.1.3808.1.1.3.2.1NodeePDULoadDevice
1.3.6.1.4.1.3808.1.1.3.2.1.1ScalarePDULoadDevMaxPhaseLoadread-onlymandatoryGetting this OID will return the maximum rated power that each phase of the Rack PDU can provide. It is represented in Amps. 0 will be returned if the unit is …
1.3.6.1.4.1.3808.1.1.3.2.1.2ScalarePDULoadDevNumPhasesread-onlymandatoryThe number of phases available with this Rack PDU.
1.3.6.1.4.1.3808.1.1.3.2.1.3ScalarePDULoadDevMaxBankLoadread-onlymandatoryGetting this OID will return the maximum rated power that a bank of the Rack PDU can provide. It is represented in Amps. 0 will be returned if the device does …
1.3.6.1.4.1.3808.1.1.3.2.1.4ScalarePDULoadDevNumBanksread-onlymandatoryThe number of banks of outlets available with this Rack PDU. A bank of outlets has a unique circuit breaker for a subset of the total number of outlets on the …
1.3.6.1.4.1.3808.1.1.3.2.1.5ScalarePDULoadDevBankTableSizeread-onlymandatoryThe size of the Bank Table.
1.3.6.1.4.1.3808.1.1.3.2.1.6TableePDULoadDevBankTablenot-accessiblemandatoryAllows for getting the Bank Max Load in the Rack PDU.
1.3.6.1.4.1.3808.1.1.3.2.1.6.1RowePDULoadDevBankEntrynot-accessiblemandatoryThe Rack PDU Banks Access.
1.3.6.1.4.1.3808.1.1.3.2.1.6.1.1ColumnePDULoadDevBankIndexread-onlymandatoryThe index to the Rack PDU bank entry.
1.3.6.1.4.1.3808.1.1.3.2.1.6.1.2ColumnePDULoadDevBankNumberread-onlymandatoryGetting this OID will return the bank number.
1.3.6.1.4.1.3808.1.1.3.2.1.6.1.3ColumnePDULoadDevBankMaxLoadread-onlymandatoryGetting this OID will return the maximum rated power that each bank of the Rack PDU can provide. It is represented in Amps.
1.3.6.1.4.1.3808.1.1.3.2.1.7ScalarePDULoadDevMaxOutletTableSizeread-onlymandatoryThe size of the Outlet Table.
1.3.6.1.4.1.3808.1.1.3.2.1.8TableePDULoadDevMaxOutletTablenot-accessiblemandatoryAllows for getting the Max Outlet Load in an Outlet Monitored Rack PDU.
1.3.6.1.4.1.3808.1.1.3.2.1.8.1RowePDULoadDevMaxOutletEntrynot-accessiblemandatoryThis gives access to Max Outlet Load of an Outlet Monitored Rack PDU
1.3.6.1.4.1.3808.1.1.3.2.1.8.1.1ColumnePDULoadDevOutletIndexread-onlymandatoryThe index to the Outlet Monitored Rack PDU Max Outlet Load entry.
1.3.6.1.4.1.3808.1.1.3.2.1.8.1.2ColumnePDULoadDevOutletNumberread-onlymandatoryGetting this OID will return the Outlet number.
1.3.6.1.4.1.3808.1.1.3.2.1.8.1.3ColumnePDULoadDevMaxOutletLoadread-onlymandatoryGetting this OID will return the maximum rated power that each Outlet of an Outlet Monitored Rack PDU can provide. It is represented in Amps.
1.3.6.1.4.1.3808.1.1.3.2.2NodeePDULoadPhaseConfig
1.3.6.1.4.1.3808.1.1.3.2.2.1TableePDULoadPhaseConfigTablenot-accessiblemandatoryAllows for configuration of each Rack PDU phase. The number of entries is contained in the ePDULoadDevNumPhases OID.
1.3.6.1.4.1.3808.1.1.3.2.2.1.1RowePDULoadPhaseConfigEntrynot-accessiblemandatoryThe Rack PDU phase to configure.
1.3.6.1.4.1.3808.1.1.3.2.2.1.1.1ColumnePDULoadPhaseConfigIndexread-onlymandatoryThe index to the Rack PDU phase entry.
1.3.6.1.4.1.3808.1.1.3.2.2.1.1.2ColumnePDULoadPhaseConfigLowLoadThresholdread-writemandatoryA threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in Amps. A warning will be issued when t…
1.3.6.1.4.1.3808.1.1.3.2.2.1.1.3ColumnePDULoadPhaseConfigNearOverloadThresholdread-writemandatoryA threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in Amps. A warning will be issued when the loa…
1.3.6.1.4.1.3808.1.1.3.2.2.1.1.4ColumnePDULoadPhaseConfigOverloadThresholdread-writemandatoryA threshold that indicates the power consumption of the load has entered an overload condition. It is represented in Amps. A warning will be issued when the lo…
1.3.6.1.4.1.3808.1.1.3.2.2.1.1.5ColumnePDULoadPhaseConfigAlarmread-onlymandatoryGetting this OID will return the current Phase Alarm.
1.3.6.1.4.1.3808.1.1.3.2.3NodeePDULoadStatus
1.3.6.1.4.1.3808.1.1.3.2.3.1TableePDULoadStatusTablenot-accessiblemandatoryAllows for getting of status of each Rack PDU phase/bank. The number of entries is calculated by adding the number of phases (ePDULoadDevNumPhases OID) and the…
1.3.6.1.4.1.3808.1.1.3.2.3.1.1RowePDULoadStatusEntrynot-accessiblemandatoryThe Rack PDU phase/bank to gather status from.
1.3.6.1.4.1.3808.1.1.3.2.3.1.1.1ColumnePDULoadStatusIndexread-onlymandatoryThe index to the Rack PDU phase/bank entry. All phase information will precede any bank information
1.3.6.1.4.1.3808.1.1.3.2.3.1.1.2ColumnePDULoadStatusLoadread-onlymandatoryGetting this OID will return the phase/bank load measured in tenths of Amps.
1.3.6.1.4.1.3808.1.1.3.2.3.1.1.3ColumnePDULoadStatusLoadStateread-onlymandatoryGetting this OID will return the phase/bank load state. loadNormal(1) indicates that the phase/bank is operating properly within the ePDULoadConfigLowLoadThres…
1.3.6.1.4.1.3808.1.1.3.2.3.1.1.4ColumnePDULoadStatusPhaseNumberread-onlymandatoryThe phase number to which this record refers.
1.3.6.1.4.1.3808.1.1.3.2.3.1.1.5ColumnePDULoadStatusBankNumberread-onlymandatoryThe bank number to which this record refers. A value of 0 will be returned if any bank is not present or if it is phase related.
1.3.6.1.4.1.3808.1.1.3.2.3.1.1.6ColumnePDULoadStatusVoltageread-onlymandatoryGetting this OID will return the phase/bank voltage measured in 0.1 volts.
1.3.6.1.4.1.3808.1.1.3.2.3.1.1.7ColumnePDULoadStatusActivePowerread-onlymandatoryGetting this OID will return the phase/bank active power measured in watts.
1.3.6.1.4.1.3808.1.1.3.2.3.1.1.8ColumnePDULoadStatusApparentPowerread-onlymandatoryGetting this OID will return the phase/bank apparent power measured in VA.
1.3.6.1.4.1.3808.1.1.3.2.3.1.1.9ColumnePDULoadStatusPowerFactorread-onlymandatoryGetting this OID will return power factor of the output measured in hundredths. A value of 100 representing a unity power factor (1.00).
1.3.6.1.4.1.3808.1.1.3.2.3.1.1.10ColumnePDULoadStatusEnergyread-onlymandatoryGetting this OID will return the phase/bank apparent power measured in 0.1 kilowatt-hours.
1.3.6.1.4.1.3808.1.1.3.2.3.1.1.11ColumnePDULoadStatusEnergyStartTimeread-onlymandatoryGetting this OID will return the date and time of the last energy meter reset
1.3.6.1.4.1.3808.1.1.3.2.4NodeePDULoadBankConfig
1.3.6.1.4.1.3808.1.1.3.2.4.1TableePDULoadBankConfigTablenot-accessiblemandatoryAllows for configuration of each Rack PDU bank. The number of entries is contained in the ePDULoadDevNumBanks OID.
1.3.6.1.4.1.3808.1.1.3.2.4.1.1RowePDULoadBankConfigEntrynot-accessiblemandatoryThe Rack PDU bank to configure.
1.3.6.1.4.1.3808.1.1.3.2.4.1.1.1ColumnePDULoadBankConfigIndexread-onlymandatoryThe index to the Rack PDU bank entry.
1.3.6.1.4.1.3808.1.1.3.2.4.1.1.2ColumnePDULoadBankConfigLowLoadThresholdread-writemandatoryA threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in Amps. A warning will be issued when t…
1.3.6.1.4.1.3808.1.1.3.2.4.1.1.3ColumnePDULoadBankConfigNearOverloadThresholdread-writemandatoryA threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in Amps. A warning will be issued when the loa…
1.3.6.1.4.1.3808.1.1.3.2.4.1.1.4ColumnePDULoadBankConfigOverloadThresholdread-writemandatoryA threshold that indicates the power consumption of the load has entered an overload condition. It is represented in Amps. A warning will be issued when the lo…
1.3.6.1.4.1.3808.1.1.3.2.4.1.1.5ColumnePDULoadBankConfigAlarmread-onlymandatoryGetting this OID will return the current Bank Alarm.
1.3.6.1.4.1.3808.1.1.3.3NodeePDUOutlet
1.3.6.1.4.1.3808.1.1.3.3.1NodeePDUOutletDevice
1.3.6.1.4.1.3808.1.1.3.3.1.1ScalarePDUOutletDevCommandread-writemandatorySetting this OID to immediateAllOn (2) will turn all outlets on immediately. Setting this OID to immediateAllOff (3) will turn all outlets off immediately. Set…
1.3.6.1.4.1.3808.1.1.3.3.1.2ScalarePDUOutletDevColdstartDelayread-writemandatoryThe amount of delay, in seconds, between when power is provided to the Switched Rack PDU and when the Switched Rack PDU provides basic master power to the outl…
1.3.6.1.4.1.3808.1.1.3.3.1.3ScalarePDUOutletDevNumCntrlOutletsread-onlymandatoryThe number of controlled outlets on this Switched Rack PDU.
1.3.6.1.4.1.3808.1.1.3.3.1.4ScalarePDUOutletDevNumTotalOutletsread-onlymandatoryThe total number of outlets on this Rack PDU.
1.3.6.1.4.1.3808.1.1.3.3.1.5ScalarePDUOutletDevMonitoredOutletsread-onlymandatoryThe total number of monitored outlets on this Rack PDU.
1.3.6.1.4.1.3808.1.1.3.3.1.6ScalarePDUOutletDevColdstartStateread-writemandatoryThe ePDU outlet state after coldstart. Allowed values are: 1 - all outlets on after coldstart. 2 - outlet status same as previous state.
1.3.6.1.4.1.3808.1.1.3.3.2NodeePDUOutletPhase
1.3.6.1.4.1.3808.1.1.3.3.2.1TableePDUOutletPhaseTablenot-accessiblemandatoryAllows for management of outlets on a per phase basis.
1.3.6.1.4.1.3808.1.1.3.3.2.1.1RowePDUOutletPhaseEntrynot-accessiblemandatoryThe phase to manage.
1.3.6.1.4.1.3808.1.1.3.3.2.1.1.1ColumnePDUOutletPhaseIndexread-onlymandatoryThe index to the Switched Rack PDU phase entry.
1.3.6.1.4.1.3808.1.1.3.3.2.1.1.2ColumnePDUOutletPhaseOverloadRestrictionread-writemandatoryThis OID controls the behavior of a Switched Rack PDU phase when an overload condition is possible and additional outlets are requested to be turned on. Settin…
1.3.6.1.4.1.3808.1.1.3.3.3NodeePDUOutletControl
1.3.6.1.4.1.3808.1.1.3.3.3.1TableePDUOutletControlTablenot-accessiblemandatoryAllows for control of the individual outlets. The number of entries is contained in the ePDUOutletDevNumCntrlOutlets OID.
1.3.6.1.4.1.3808.1.1.3.3.3.1.1RowePDUOutletControlEntrynot-accessiblemandatoryThe outlet to control.
1.3.6.1.4.1.3808.1.1.3.3.3.1.1.1ColumnePDUOutletControlIndexread-onlymandatoryThe index to the outlet entry.
1.3.6.1.4.1.3808.1.1.3.3.3.1.1.2ColumnePDUOutletControlOutletNameread-onlymandatoryThe name of the outlet. The maximum string size is device dependent. An error will be returned if the set request exceeds the max size. This OID is provided fo…
1.3.6.1.4.1.3808.1.1.3.3.3.1.1.3ColumnePDUOutletControlOutletPhaseread-onlymandatoryThe phase/s associated with this outlet. For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase…
1.3.6.1.4.1.3808.1.1.3.3.3.1.1.4ColumnePDUOutletControlOutletCommandread-writemandatoryGetting this variable will return the outlet state. If the outlet is on, the immediateOn (1) value will be returned. If the outlet is off, the immediateOff (2)…
1.3.6.1.4.1.3808.1.1.3.3.3.1.1.5ColumnePDUOutletControlOutletBankread-onlymandatoryThe bank associated with this outlet.
1.3.6.1.4.1.3808.1.1.3.3.4NodeePDUOutletConfig
1.3.6.1.4.1.3808.1.1.3.3.4.1TableePDUOutletConfigTablenot-accessiblemandatoryAllows for configuration of individual outlets. The number of entries is contained in the ePDUOutletDevNumCntrlOutlets OID.
1.3.6.1.4.1.3808.1.1.3.3.4.1.1RowePDUOutletConfigEntrynot-accessiblemandatoryThe outlet to configure.
1.3.6.1.4.1.3808.1.1.3.3.4.1.1.1ColumnePDUOutletConfigIndexread-onlymandatoryThe index to the outlet entry.
1.3.6.1.4.1.3808.1.1.3.3.4.1.1.2ColumnePDUOutletConfigOutletNameread-writemandatoryThe name of the outlet. The maximum string size is device dependent. An error will be returned if the set request exceeds the max size.
1.3.6.1.4.1.3808.1.1.3.3.4.1.1.3ColumnePDUOutletConfigOutletPhaseread-onlymandatoryThe phase/s associated with this outlet. For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase…
1.3.6.1.4.1.3808.1.1.3.3.4.1.1.4ColumnePDUOutletConfigPowerOnTimeread-writemandatoryThe amount of time (in seconds) the outlet will delay powering on at coldstart or when a command that requires a turn-on delay is issued. Allowed values are: -…
1.3.6.1.4.1.3808.1.1.3.3.4.1.1.5ColumnePDUOutletConfigPowerOffTimeread-writemandatoryThe amount of time (in seconds) the outlet will delay powering off when a command that requires a turn-off delay is issued. Allowed values are: -1 - never powe…
1.3.6.1.4.1.3808.1.1.3.3.4.1.1.6ColumnePDUOutletConfigRebootDurationread-writemandatoryDuring a reboot sequence, power is turned off and then back on. This OID defines the amount of time to wait, in seconds, after turning the power off, at the st…
1.3.6.1.4.1.3808.1.1.3.3.4.1.1.7ColumnePDUOutletConfigOutletBankread-onlymandatoryThe bank associated with this outlet.
1.3.6.1.4.1.3808.1.1.3.3.4.2ScalarePDUOutletConfigMonitoredTableSizeread-onlymandatoryThe size of the Outlet Config Monitored Table
1.3.6.1.4.1.3808.1.1.3.3.4.3TableePDUOutletConfigMonitoredTablenot-accessiblemandatoryAllows for getting/setting of outlet thresholds of an Outlet Monitored Rack PDU.
1.3.6.1.4.1.3808.1.1.3.3.4.3.1RowePDUOutletConfigMonitoredEntrynot-accessiblemandatoryThis gives access to Monitored Outlet entries
1.3.6.1.4.1.3808.1.1.3.3.4.3.1.1ColumnePDUOutletConfigMonitoredIndexread-onlymandatoryThe index to the RACK PDU Phase entry.
1.3.6.1.4.1.3808.1.1.3.3.4.3.1.2ColumnePDUOutletConfigMonitoredNameread-writemandatoryThe name of the Monitored Outlet. The maximum string size is device dependent. An error will be returned if the set request exceeds the max size.
1.3.6.1.4.1.3808.1.1.3.3.4.3.1.3ColumnePDUOutletConfigMonitoredNumberread-onlymandatoryThe outlet number of an Outlet Monitored RACK PDU.
1.3.6.1.4.1.3808.1.1.3.3.4.3.1.4ColumnePDUOutletConfigMonitoredLowLoadThresholdread-writemandatoryA threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in watts. A warning will be issued when …
1.3.6.1.4.1.3808.1.1.3.3.4.3.1.5ColumnePDUOutletConfigMonitoredNearOverloadThresholdread-writemandatoryA threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in watts. A warning will be issued when the lo…
1.3.6.1.4.1.3808.1.1.3.3.4.3.1.6ColumnePDUOutletConfigMonitoredOverloadThresholdread-writemandatoryA threshold that indicates the power consumption of the load has entered an overload condition. It is represented in watts. A warning will be issued when the l…
1.3.6.1.4.1.3808.1.1.3.3.4.3.1.7ColumnePDUOutletConfigMonitoredPeakLoadResetread-writemandatorySetting this OID to reset (2) will cause the existing peak power value to be replaced by the current load power value. Getting this oid will do nothing and ret…
1.3.6.1.4.1.3808.1.1.3.3.4.3.1.8ColumnePDUOutletConfigMonitoredEnergyResetread-writemandatorySetting this OID to reset (2) will cause the device energy meter value to be reset to zero. Getting this oid will do nothing and return noAction (1) if the PDU…
1.3.6.1.4.1.3808.1.1.3.3.5NodeePDUOutletStatus
1.3.6.1.4.1.3808.1.1.3.3.5.1TableePDUOutletStatusTablenot-accessiblemandatoryAllows for getting of status of individual outlets. The number of entries is contained in the ePDUOutletDevNumCntrlOutlets OID.
1.3.6.1.4.1.3808.1.1.3.3.5.1.1RowePDUOutletStatusEntrynot-accessiblemandatoryThe outlet to gather status from.
1.3.6.1.4.1.3808.1.1.3.3.5.1.1.1ColumnePDUOutletStatusIndexread-onlymandatoryThe index to the outlet entry.
1.3.6.1.4.1.3808.1.1.3.3.5.1.1.2ColumnePDUOutletStatusOutletNameread-onlymandatoryThe name of the outlet. The maximum string size is device dependent. This OID is provided for informational purposes only.
1.3.6.1.4.1.3808.1.1.3.3.5.1.1.3ColumnePDUOutletStatusOutletPhaseread-onlymandatoryThe phase/s associated with this outlet. For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase…
1.3.6.1.4.1.3808.1.1.3.3.5.1.1.4ColumnePDUOutletStatusOutletStateread-onlymandatoryGetting this variable will return the outlet state. If the outlet is on, the outletStatusOn (1) value will be returned. If the outlet is off, the outletStatusO…
1.3.6.1.4.1.3808.1.1.3.3.5.1.1.5ColumnePDUOutletStatusCommandPendingread-onlymandatoryGetting this variable will return the command pending state of the outlet. If a command is pending on the outlet, the outletStatusCommandPending (1) value will…
1.3.6.1.4.1.3808.1.1.3.3.5.1.1.6ColumnePDUOutletStatusOutletBankread-onlymandatoryThe bank associated with this outlet.
1.3.6.1.4.1.3808.1.1.3.3.5.1.1.7ColumnePDUOutletStatusLoadread-onlymandatoryGetting this OID will return the measured Outlet load for an Outlet Monitored Rack PDU in tenths of Amps.
1.3.6.1.4.1.3808.1.1.3.3.5.1.1.8ColumnePDUOutletStatusActivePowerread-onlymandatoryGetting this OID will return the measured Outlet load for an Outlet Monitored Rack PDU in watts
1.3.6.1.4.1.3808.1.1.3.3.5.1.1.9ColumnePDUOutletStatusAlarmread-onlymandatoryGetting this OID will return the current outlet alarm
1.3.6.1.4.1.3808.1.1.3.3.5.1.1.10ColumnePDUOutletStatusPeakPowerread-onlymandatoryThe peak power consumption of the Rack PDU load in watts. This value can be reset by setting the oid ePDUOutletConfigMonitoredPeakLoadReset to reset (2)
1.3.6.1.4.1.3808.1.1.3.3.5.1.1.11ColumnePDUOutletStatusPeakPowerTimeread-onlymandatoryGet this oid shows the date and time that peak power consumption occurred
1.3.6.1.4.1.3808.1.1.3.3.5.1.1.12ColumnePDUOutletStatusPeakPowerStartread-onlymandatoryGet this oid shows the date and time that peak power consumption started
1.3.6.1.4.1.3808.1.1.3.3.5.1.1.13ColumnePDUOutletStatusEnergyread-onlymandatoryEnergy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours. This value can be reset by setting the oid ePDUOutletConfigMonitoredEnergy…
1.3.6.1.4.1.3808.1.1.3.3.5.1.1.14ColumnePDUOutletStatusEnergyStartTimeread-onlymandatoryIndicates the date and time of the last device energy meter reset
1.3.6.1.4.1.3808.1.1.3.3.6NodeePDUOutletBank
1.3.6.1.4.1.3808.1.1.3.3.6.1TableePDUOutletBankTablenot-accessiblemandatoryAllows for management of outlets on a per bank basis.
1.3.6.1.4.1.3808.1.1.3.3.6.1.1RowePDUOutletBankEntrynot-accessiblemandatoryThe bank to manage.
1.3.6.1.4.1.3808.1.1.3.3.6.1.1.1ColumnePDUOutletBankIndexread-onlymandatoryThe index to the Switched Rack PDU bank entry.
1.3.6.1.4.1.3808.1.1.3.3.6.1.1.2ColumnePDUOutletBankOverloadRestrictionread-writemandatoryThis OID controls the behavior of a Switched Rack PDU bank when an overload condition is possible and additional outlets are requested to be turned on. Setting…
1.3.6.1.4.1.3808.1.1.3.4NodeePDUPowerSupply
1.3.6.1.4.1.3808.1.1.3.4.1NodeePDUPowerSupplyDevice
1.3.6.1.4.1.3808.1.1.3.4.1.1ScalarePDUPowerSupply1Statusread-onlymandatoryGetting this OID will return powerSupply1Ok(1) if power supply 1 is functioning normally. If not functioning normally, this OID will return powerSupply1Failed(…
1.3.6.1.4.1.3808.1.1.3.4.1.2ScalarePDUPowerSupply2Statusread-onlymandatoryGetting this OID will return powerSupply2Ok(1) if power supply 2 is functioning normally. If not functioning normally, this OID will return powerSupply2Failed(…
1.3.6.1.4.1.3808.1.1.3.4.1.3ScalarePDUPowerSupplyAlarmread-onlymandatoryGetting this OID will return powerSupply Alarm
1.3.6.1.4.1.3808.1.1.3.5NodeePDUStatus
1.3.6.1.4.1.3808.1.1.3.5.1ScalarePDUStatusBankTableSizeread-onlymandatoryThe size of the Status Bank Table
1.3.6.1.4.1.3808.1.1.3.5.2TableePDUStatusBankTablenot-accessiblemandatoryAllows for getting of status of each Rack PDU Bank
1.3.6.1.4.1.3808.1.1.3.5.2.1RowePDUStatusBankEntrynot-accessiblemandatoryThis gives access to Bank entries
1.3.6.1.4.1.3808.1.1.3.5.2.1.1ColumnePDUStatusBankIndexread-onlymandatoryThe index to the RACK PDU Bank entry.
1.3.6.1.4.1.3808.1.1.3.5.2.1.2ColumnePDUStatusBankNumberread-onlymandatoryGetting this OID will return the bank number.
1.3.6.1.4.1.3808.1.1.3.5.2.1.3ColumnePDUStatusBankStateread-onlymandatoryGetting this OID will return the bank load state. bankLoadNormal(1) indicates that the bank is operating properly within the ePDULoadBankConfigLowLoadThreshold…
1.3.6.1.4.1.3808.1.1.3.5.3ScalarePDUStatusPhaseTableSizeread-onlymandatoryThe size of the Status Phase Table
1.3.6.1.4.1.3808.1.1.3.5.4TableePDUStatusPhaseTablenot-accessiblemandatoryAllows for getting of status of each Rack PDU Phase
1.3.6.1.4.1.3808.1.1.3.5.4.1RowePDUStatusPhaseEntrynot-accessiblemandatoryThis gives access to Phase entries
1.3.6.1.4.1.3808.1.1.3.5.4.1.1ColumnePDUStatusPhaseIndexread-onlymandatoryThe index to the RACK PDU Phase entry.
1.3.6.1.4.1.3808.1.1.3.5.4.1.2ColumnePDUStatusPhaseNumberread-onlymandatoryGetting this OID will return the phase number.
1.3.6.1.4.1.3808.1.1.3.5.4.1.3ColumnePDUStatusPhaseStateread-onlymandatoryGetting this OID will return the Phase load state. phaseLoadNormal(1) indicates that the Phase is operating properly within the ePDULoadPhaseConfigLowLoadThres…
1.3.6.1.4.1.3808.1.1.3.5.5ScalarePDUStatusOutletTableSizeread-onlymandatoryThe size of the Status Outlet Table
1.3.6.1.4.1.3808.1.1.3.5.6TableePDUStatusOutletTablenot-accessiblemandatoryAllows for getting of status of each Outlet of an Outlet Monitored Rack PDU.
1.3.6.1.4.1.3808.1.1.3.5.6.1RowePDUStatusOutletEntrynot-accessiblemandatoryThis gives access to Outlet entries
1.3.6.1.4.1.3808.1.1.3.5.6.1.1ColumnePDUStatusOutletIndexread-onlymandatoryThe index to the RACK PDU Outlet entry.
1.3.6.1.4.1.3808.1.1.3.5.6.1.2ColumnePDUStatusOutletNumberread-onlymandatoryGetting this OID will return the Outlet number.
1.3.6.1.4.1.3808.1.1.3.5.6.1.3ColumnePDUStatusOutletStateread-onlymandatoryGetting this OID will return the Outlet load state. outletLoadNormal(1) indicates that the Outlet is operating properly within the ePDUOutletConfigMonitoredLow…
1.3.6.1.4.1.3808.1.1.3.5.7ScalarePDUStatusInputVoltageread-onlymandatoryThe input voltage in 0.1 Volt.
1.3.6.1.4.1.3808.1.1.3.5.8ScalarePDUStatusInputFrequencyread-onlymandatoryThe input frequency in 0.1 Hertz.
1.3.6.1.4.1.3808.1.1.4NodeenvironmentSensor
1.3.6.1.4.1.3808.1.1.4.1NodeenvirIdent
1.3.6.1.4.1.3808.1.1.4.1.1ScalarenvirIdentNameread-writemandatoryThe name of the environment sensor. The maximum string size is device dependent.
1.3.6.1.4.1.3808.1.1.4.1.2ScalarenvirIdentLocationread-writemandatoryThe location of the environment sensor. The maximum string size is device dependent.
1.3.6.1.4.1.3808.1.1.4.2NodeenvirTemp
1.3.6.1.4.1.3808.1.1.4.2.1ScalarenvirTemperatureread-onlymandatoryThe environment temperature expressed in 1/10 Fahrenheit
1.3.6.1.4.1.3808.1.1.4.2.2ScalarenvirTempHighThresholdread-writemandatoryThe high temperature threshold of the environment sensor. The value expressed in Fahrenheit.
1.3.6.1.4.1.3808.1.1.4.2.3ScalarenvirTempLowThresholdread-writemandatoryThe low temperature threshold of the environment sensor. The value expressed in Fahrenheit.
1.3.6.1.4.1.3808.1.1.4.2.4ScalarenvirTempRateOfChangeread-writemandatoryThe rate of change of the temperature. The value expressed in Fahrenheit per 5 minute.
1.3.6.1.4.1.3808.1.1.4.2.5ScalarenvirTempHysteresisread-writemandatoryThe number of degrees beyond the temperature thresholds at which an active temperature alarm will be cleared. This configuration setting applies to all tempera…
1.3.6.1.4.1.3808.1.1.4.3NodeenvirHumid
1.3.6.1.4.1.3808.1.1.4.3.1ScalarenvirHumidityread-onlymandatoryThe environment relative humidity expressed in persentage.
1.3.6.1.4.1.3808.1.1.4.3.2ScalarenvirHumidHighThresholdread-writemandatoryThe high relative humidity threshold of the environment sensor. The value expressed in persentage.
1.3.6.1.4.1.3808.1.1.4.3.3ScalarenvirHumidLowThresholdread-writemandatoryThe low relative humidity threshold of the environment sensor. The value expressed in persentage.
1.3.6.1.4.1.3808.1.1.4.3.4ScalarenvirHumidRateOfChangeread-writemandatoryThe rate of change of the relative humidity. The value expressed in persentage per 5 minute.
1.3.6.1.4.1.3808.1.1.4.3.5ScalarenvirHumidHysteresisread-writemandatoryThe number of degrees beyond the relative humidity thresholds at which an active relative humidity alarm will be cleared. This configuration setting applies to…
1.3.6.1.4.1.3808.1.1.4.4NodeenvirContact
1.3.6.1.4.1.3808.1.1.4.4.1ScalarenvirContactTableSizeread-onlymandatoryThe number of the contact in the environment sensor.
1.3.6.1.4.1.3808.1.1.4.4.2TableenvirContactTablenot-accessiblemandatoryAllows for getting of information of each contact of the environment sensor.
1.3.6.1.4.1.3808.1.1.4.4.2.1RowenvirContactEntrynot-accessiblemandatoryThis gives access to contact entries
1.3.6.1.4.1.3808.1.1.4.4.2.1.1ColumnenvirContactIndexread-onlymandatoryThe index to the contact of the environment sensor.
1.3.6.1.4.1.3808.1.1.4.4.2.1.2ColumnenvirContactNameread-writemandatoryGetting or setting the name of the contact of the environment sensor.
1.3.6.1.4.1.3808.1.1.4.4.2.1.3ColumnenvirContactStatusread-onlymandatoryGetting this OID will return the Contact Status.
1.3.6.1.4.1.3808.1.1.4.4.2.1.4ColumnenvirContactNormalStateread-writemandatorySet the contact normal state.
1.3.6.1.4.1.3808.1.1.5Nodeats
1.3.6.1.4.1.3808.1.1.5.1NodeatsIdent
1.3.6.1.4.1.3808.1.1.5.1.1ScalaratsIdentNameread-writemandatoryThe name of the ATS. The maximum string size is device dependent.
1.3.6.1.4.1.3808.1.1.5.1.2ScalaratsIdentModelNameread-onlymandatoryA string identifying the model name of the Automatic Transfer Switch. This value is set at the factory.
1.3.6.1.4.1.3808.1.1.5.1.3ScalaratsIdentHardwareRevread-onlymandatoryThe hardware revision of the Automatic Transfer Switch. This value is set at the factory.
1.3.6.1.4.1.3808.1.1.5.1.4ScalaratsIdentFirmwareRevread-onlymandatoryA string identifying the Automatic Transfer Switch firmware revision.
1.3.6.1.4.1.3808.1.1.5.1.5ScalaratsIdentSerialNumberread-onlymandatoryA string identifying the serial number of the Automatic Transfer Switch. This value is set at the factory.
1.3.6.1.4.1.3808.1.1.5.1.6ScalaratsIdentDateOfManufactureread-onlymandatoryThe date when the Automatic Transfer Switch was manufactured in mm/dd/yyyy format. This value is set at the factory.
1.3.6.1.4.1.3808.1.1.5.1.7ScalaratsIdentDeviceRatingVoltageread-onlymandatoryA string identifing the Automatic Transfer Switch rating voltage.
1.3.6.1.4.1.3808.1.1.5.1.8ScalaratsIdentDeviceRatingCurrentread-onlymandatoryThis gives the device rating current in Amps
1.3.6.1.4.1.3808.1.1.5.1.9ScalaratsIdentDeviceOutletNumread-onlymandatoryThis gives the outlet number of the device
1.3.6.1.4.1.3808.1.1.5.1.10ScalaratsIdentAgentModelNameread-onlymandatoryA string identifying the model name of the Agent.
1.3.6.1.4.1.3808.1.1.5.1.11ScalaratsIdentAgentHardwareRevisionread-onlymandatoryThe hardware revision of the Agent.
1.3.6.1.4.1.3808.1.1.5.1.12ScalaratsIdentAgentFirmwareRevisionread-onlymandatoryA string identifying the Agent firmware revision.
1.3.6.1.4.1.3808.1.1.5.1.13ScalaratsIdentAgentSerialNumberread-onlymandatoryA string identifying the serial number of the Agent.
1.3.6.1.4.1.3808.1.1.5.2NodeatsStatus
1.3.6.1.4.1.3808.1.1.5.2.1NodeatsStatusDevice
1.3.6.1.4.1.3808.1.1.5.2.1.1ScalaratsStatusCommStatusread-onlymandatoryThis variable returns the current communication status between the Automatic Transfer Switch and the Agent.
1.3.6.1.4.1.3808.1.1.5.2.1.2ScalaratsStatusSelectedSourceread-onlymandatoryThis variable returns the current source of power.
1.3.6.1.4.1.3808.1.1.5.2.1.3ScalaratsStatusRedundancyStateread-onlymandatoryThis variable returns the current redundancy state of the ATS. atsRedundancyLost(1) indicates that the ATS is unable to switch over to the alternate power sour…
1.3.6.1.4.1.3808.1.1.5.2.1.4ScalaratsStatusPhaseSyncStatusread-onlymandatoryThis variable returns the status of the phase sync.
1.3.6.1.4.1.3808.1.1.5.2.1.5ScalaratsStatusDevSourceRelayStatusread-onlymandatoryThis variable returns the status of the source relay.
1.3.6.1.4.1.3808.1.1.5.2.1.6ScalaratsStatusDevInRelayStatusread-onlymandatoryThis variable returns the status of the input relay.
1.3.6.1.4.1.3808.1.1.5.2.1.7ScalaratsStatusDevOutRelayStatusread-onlymandatoryThis variable returns the status of the Output relay.
1.3.6.1.4.1.3808.1.1.5.2.1.8ScalaratsStatusDevLCDCommStatusread-onlymandatoryThis variable returns the communication status of the LCD.
1.3.6.1.4.1.3808.1.1.5.2.1.9ScalaratsStatusDevDB9CommStatusread-onlymandatoryThis variable returns the communication status of the DB9.
1.3.6.1.4.1.3808.1.1.5.2.1.10TableatsStatusPowerSupplyTablenot-accessiblemandatoryA list of power supply table entries.
1.3.6.1.4.1.3808.1.1.5.2.1.10.1RowatsStatusPowerSupplyEntrynot-accessiblemandatoryAn entry containing power supply information applicable to a particular input.
1.3.6.1.4.1.3808.1.1.5.2.1.10.1.1ColumnatsStatusPowerSupplyTableIndexread-onlymandatoryThe input identifier.
1.3.6.1.4.1.3808.1.1.5.2.1.10.1.2ColumnatsStatusPowerSupplyInputSourceread-onlymandatoryThe input source to the power supply.
1.3.6.1.4.1.3808.1.1.5.2.1.10.1.3ColumnatsStatusPowerSupply12VStatusread-onlymandatoryThis variable returns the status of the power supply A 12V in system.
1.3.6.1.4.1.3808.1.1.5.2.1.10.1.4ColumnatsStatusPowerSupply5VStatusread-onlymandatoryThis variable returns the status of the power supply A 5V in system.
1.3.6.1.4.1.3808.1.1.5.2.1.10.1.5ColumnatsStatusPowerSupply3p3VStatusread-onlymandatoryThis variable returns the status of the power supply A 3.3V in system.
1.3.6.1.4.1.3808.1.1.5.2.2NodeatsStatusInput
1.3.6.1.4.1.3808.1.1.5.2.2.1ScalaratsStatusInputNumread-onlymandatoryThe number of input feeds to this device. This variable indicates the number of rows in the status input table.
1.3.6.1.4.1.3808.1.1.5.2.2.2TableatsStatusInputTablenot-accessiblemandatoryA list of input table entries. The number of entries is given by the value of atsNumInputs.
1.3.6.1.4.1.3808.1.1.5.2.2.2.1RowatsStatusInputEntrynot-accessiblemandatoryAn entry containing information applicable to a particular input.
1.3.6.1.4.1.3808.1.1.5.2.2.2.1.1ColumnatsStatusInputTableIndexread-onlymandatoryThe input identifier.
1.3.6.1.4.1.3808.1.1.5.2.2.2.1.2ColumnatsStatusInputNameread-writemandatoryA name given to a particular input.
1.3.6.1.4.1.3808.1.1.5.2.2.2.1.3ColumnatsStatusNumInputPhaseread-onlymandatoryThe number of input phases utilized in this device. The sum of all the atsStatusNumInputPhase variable indicates the number of rows in the status input phase t…
1.3.6.1.4.1.3808.1.1.5.2.2.2.1.4ColumnatsStatusInputVoltageOrientationread-onlymandatoryThe input voltage orientation: 1: unknown for this Source 2: singlePhase - phase 1 voltage is between Phase 1 and Neutral. 3: splitPhase - phase 1 voltage is b…
1.3.6.1.4.1.3808.1.1.5.2.2.2.1.5ColumnatsStatusInputVoltageread-onlymandatoryThe input voltage in 0.1 Volt.
1.3.6.1.4.1.3808.1.1.5.2.2.2.1.6ColumnatsStatusInputFrequencyread-onlymandatoryThe input frequency in 0.1 Hertz.
1.3.6.1.4.1.3808.1.1.5.2.2.2.1.7ColumnatsStatusInputVolStateread-onlymandatoryThe input voltage status.
1.3.6.1.4.1.3808.1.1.5.2.2.2.1.8ColumnatsStatusInputFreqStateread-onlymandatoryThe input frequency status.
1.3.6.1.4.1.3808.1.1.5.2.2.3TableatsStatusInputPhaseTablenot-accessiblemandatoryA list of input table entries. The number of entries is given by the sum of the atsNumInputPhases.
1.3.6.1.4.1.3808.1.1.5.2.2.3.1RowatsStatusInputPhaseEntrynot-accessiblemandatoryAn entry containing information applicable to a particular input phase.
1.3.6.1.4.1.3808.1.1.5.2.2.3.1.1ColumnatsStatusInputPhaseTableIndexread-onlymandatoryThe input identifier.
1.3.6.1.4.1.3808.1.1.5.2.2.3.1.2ColumnatsStatusInputPhaseIndexread-onlymandatoryThe input phase identifier.
1.3.6.1.4.1.3808.1.1.5.2.2.3.1.3ColumnatsStatusInputPhaseVoltageread-onlymandatoryThe input voltage in VAC, or -1 if it's unsupported by this Source.
1.3.6.1.4.1.3808.1.1.5.2.2.3.1.4ColumnatsStatusInputPhaseCurrentread-onlymandatoryThe input current in amperes, or -1 if it's unsupported by this Source.
1.3.6.1.4.1.3808.1.1.5.2.2.3.1.5ColumnatsStatusInputPhasePowerread-onlymandatoryThe input power in Watts, or -1 if it's unsupported by this Source.
1.3.6.1.4.1.3808.1.1.5.3NodeatsConfig
1.3.6.1.4.1.3808.1.1.5.3.1ScalaratsConfigPreferredSourceread-writemandatoryThis variable returns the preferred source of power when both sources are OK.
1.3.6.1.4.1.3808.1.1.5.3.2ScalaratsConfigNominalVoltageread-writemandatoryThis variable returns the nominal voltage of the input.
1.3.6.1.4.1.3808.1.1.5.3.3ScalaratsConfigVoltageSensitivityread-writemandatoryThis variable defines the sensitivity to changes in voltage: high(1) for best protection, low(3) for frequent small line voltage changes.
1.3.6.1.4.1.3808.1.1.5.3.4ScalaratsConfigTransferVoltageRangeread-writemandatoryThis variable defines the range of acceptable voltage from a power source. If the voltage measured from the selected input source is not within this range, the…
1.3.6.1.4.1.3808.1.1.5.3.5ScalaratsConfigNarrowRangeValueread-writemandatoryTo configure the Narrow Range value of acceptable voltage from a power source.
1.3.6.1.4.1.3808.1.1.5.3.6ScalaratsConfigMediumRangeValueread-writemandatoryTo configure the Medium Range value of acceptable voltage from a power source.
1.3.6.1.4.1.3808.1.1.5.3.7ScalaratsConfigWideRangeValueread-writemandatoryTo configure the Wide Range value of acceptable voltage from a power source.
1.3.6.1.4.1.3808.1.1.5.3.8ScalaratsConfigFrequencyDeviationread-writemandatoryTo configure the frequency deviation.
1.3.6.1.4.1.3808.1.1.5.3.9ScalaratsConfigDevLCDOffTimeread-writemandatoryThe amount of time (in seconds) which LCD turn off automatically after it remains idle for.
1.3.6.1.4.1.3808.1.1.5.4NodeatsControl
1.3.6.1.4.1.3808.1.1.5.4.1ScalaratsCtrlResetATSread-writemandatorySetting this variable will cause the Automatic Transfer Switch to reboot or reset relative setting to default value.
1.3.6.1.4.1.3808.1.1.5.4.2ScalaratsCtrlClearEventCountsread-writemandatorySetting this variable will clear all event counts in Automatic Transfer Switch. Returns (-1) if unsupported.
1.3.6.1.4.1.3808.1.1.5.5NodeatsLoad
1.3.6.1.4.1.3808.1.1.5.5.1NodeatsLoadDevice
1.3.6.1.4.1.3808.1.1.5.5.1.1ScalaratsLoadDevPhaseTableSizeread-onlymandatoryThe size of the Phase Table.
1.3.6.1.4.1.3808.1.1.5.5.1.2TableatsLoadDevPhaseTablenot-accessiblemandatoryAllows for getting the Phase Max Load in the ATS.
1.3.6.1.4.1.3808.1.1.5.5.1.2.1RowatsLoadDevPhaseEntrynot-accessiblemandatoryThe ATS Phases Access.
1.3.6.1.4.1.3808.1.1.5.5.1.2.1.1ColumnatsLoadDevPhaseTableIndexread-onlymandatoryThe index to ATS phase entry.
1.3.6.1.4.1.3808.1.1.5.5.1.2.1.2ColumnatsLoadDevPhaseread-onlymandatoryFor single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), phase3 (3), phase1-2 (…
1.3.6.1.4.1.3808.1.1.5.5.1.2.1.3ColumnatsLoadDevPhaseMaxLoadread-onlymandatoryGetting this OID will return the maximum rated power that each phase of the ATS can provide. It is represented in Amps.
1.3.6.1.4.1.3808.1.1.5.5.1.3ScalaratsLoadDevBankTableSizeread-onlymandatoryThe size of the Bank Table.
1.3.6.1.4.1.3808.1.1.5.5.1.4TableatsLoadDevBankTablenot-accessiblemandatoryAllows for getting the Bank Max Load in the ATS.
1.3.6.1.4.1.3808.1.1.5.5.1.4.1RowatsLoadDevBankEntrynot-accessiblemandatoryThe ATS Banks Access.
1.3.6.1.4.1.3808.1.1.5.5.1.4.1.1ColumnatsLoadDevBankTableIndexread-onlymandatoryThe index to the ATS bank entry.
1.3.6.1.4.1.3808.1.1.5.5.1.4.1.2ColumnatsLoadDevBankMaxLoadread-onlymandatoryGetting this OID will return the maximum rated power that each bank of the ATS can provide. It is represented in Amps.
1.3.6.1.4.1.3808.1.1.5.5.2NodeatsLoadStatus
1.3.6.1.4.1.3808.1.1.5.5.2.1ScalaratsLoadStatusPhaseTableSizeread-onlymandatoryThe size of the Phase Table.
1.3.6.1.4.1.3808.1.1.5.5.2.2TableatsLoadStatusPhaseTablenot-accessiblemandatoryAllows for getting the Phase Load status in the ATS.
1.3.6.1.4.1.3808.1.1.5.5.2.2.1RowatsLoadStatusPhaseEntrynot-accessiblemandatoryThe ATS Phases Access.
1.3.6.1.4.1.3808.1.1.5.5.2.2.1.1ColumnatsLoadStatusPhaseTableIndexread-onlymandatoryThe index to ATS phase entry.
1.3.6.1.4.1.3808.1.1.5.5.2.2.1.2ColumnatsLoadStatusPhaseread-onlymandatoryFor single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), phase3 (3), phase1-2 (…
1.3.6.1.4.1.3808.1.1.5.5.2.2.1.3ColumnatsLoadStatusPhaseLoadread-onlymandatoryThe output current in 0.1 amperes drawn by the load on the ATS
1.3.6.1.4.1.3808.1.1.5.5.2.2.1.4ColumnatsLoadStatusPhaseLoadStateread-onlymandatoryGetting this OID will return the phase load state.
1.3.6.1.4.1.3808.1.1.5.5.2.2.1.5ColumnatsLoadStatusPhasePowerread-onlymandatoryThe output power in Watts.
1.3.6.1.4.1.3808.1.1.5.5.2.3ScalaratsLoadStatusBankTableSizeread-onlymandatoryThe size of the Bank Table.
1.3.6.1.4.1.3808.1.1.5.5.2.4TableatsLoadStatusBankTablenot-accessiblemandatoryAllows for getting the Bank Load status in the ATS.
1.3.6.1.4.1.3808.1.1.5.5.2.4.1RowatsLoadStatusBankEntrynot-accessiblemandatoryThe ATS Bank Access.
1.3.6.1.4.1.3808.1.1.5.5.2.4.1.1ColumnatsLoadStatusBankTableIndexread-onlymandatoryThe index to ATS bank entry.
1.3.6.1.4.1.3808.1.1.5.5.2.4.1.2ColumnatsLoadStatusBankPhaseread-onlymandatoryGetting this OID will return the phase number.
1.3.6.1.4.1.3808.1.1.5.5.2.4.1.3ColumnatsLoadStatusBankLoadread-onlymandatoryThe output current in 0.1 amperes drawn by the load on the ATS
1.3.6.1.4.1.3808.1.1.5.5.2.4.1.4ColumnatsLoadStatusBankLoadStateread-onlymandatoryGetting this OID will return the bank load state.
1.3.6.1.4.1.3808.1.1.5.5.2.4.1.5ColumnatsLoadStatusBankPowerread-onlymandatoryThe output power in Watts.
1.3.6.1.4.1.3808.1.1.5.5.3NodeatsLoadConfig
1.3.6.1.4.1.3808.1.1.5.5.3.1ScalaratsLoadCfgPhaseTableSizeread-onlymandatoryThe size of the Phase Table.
1.3.6.1.4.1.3808.1.1.5.5.3.2TableatsLoadCfgPhaseTablenot-accessiblemandatoryAllows for configuration of each ATS phase.
1.3.6.1.4.1.3808.1.1.5.5.3.2.1RowatsLoadCfgPhaseEntrynot-accessiblemandatoryThe ATS phase to configure.
1.3.6.1.4.1.3808.1.1.5.5.3.2.1.1ColumnatsLoadCfgPhaseTableIndexread-onlymandatoryThe index to the ATS phase entry.
1.3.6.1.4.1.3808.1.1.5.5.3.2.1.2ColumnatsLoadCfgPhaseread-onlymandatoryFor single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), phase3 (3), phase1-2 (…
1.3.6.1.4.1.3808.1.1.5.5.3.2.1.3ColumnatsLoadCfgPhaseLowLoadread-writemandatoryA threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in Amps. A warning will be issued when t…
1.3.6.1.4.1.3808.1.1.5.5.3.2.1.4ColumnatsLoadCfgPhaseNearOverLoadread-writemandatoryA threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in Amps. A warning will be issued when the loa…
1.3.6.1.4.1.3808.1.1.5.5.3.2.1.5ColumnatsLoadCfgPhaseOverLoadread-writemandatoryA threshold that indicates the power consumption of the load has entered an overload condition. It is represented in Amps. A warning will be issued when the lo…
1.3.6.1.4.1.3808.1.1.5.5.3.2.1.6ColumnatsLoadCfgPhaseOutletRestrictionread-writemandatoryThis OID controls the behavior of a ATS phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to …
1.3.6.1.4.1.3808.1.1.5.5.3.3ScalaratsLoadCfgBankTableSizeread-onlymandatoryThe size of the Bank Table.
1.3.6.1.4.1.3808.1.1.5.5.3.4TableatsLoadCfgBankTablenot-accessiblemandatoryAllows for configuration of each ATS bank.
1.3.6.1.4.1.3808.1.1.5.5.3.4.1RowatsLoadCfgBankEntrynot-accessiblemandatoryThe ATS phase to configure.
1.3.6.1.4.1.3808.1.1.5.5.3.4.1.1ColumnatsLoadCfgBankTableIndexread-onlymandatoryThe index to the ATS bank entry.
1.3.6.1.4.1.3808.1.1.5.5.3.4.1.2ColumnatsLoadCfgBankLowLoadread-writemandatoryA threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in Amps. A warning will be issued when t…
1.3.6.1.4.1.3808.1.1.5.5.3.4.1.3ColumnatsLoadCfgBankNearOverLoadread-writemandatoryA threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in Amps. A warning will be issued when the loa…
1.3.6.1.4.1.3808.1.1.5.5.3.4.1.4ColumnatsLoadCfgBankOverLoadread-writemandatoryA threshold that indicates the power consumption of the load has entered an overload condition. It is represented in Amps. A warning will be issued when the lo…
1.3.6.1.4.1.3808.1.1.5.5.3.4.1.5ColumnatsLoadCfgBankOutletRestrictionread-writemandatoryThis OID controls the behavior of a ATS phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to …
1.3.6.1.4.1.3808.1.1.5.6NodeatsOutlet
1.3.6.1.4.1.3808.1.1.5.6.1NodeatsOutletDevice
1.3.6.1.4.1.3808.1.1.5.6.1.1ScalaratsOutletDevTotalOutletNumread-onlymandatoryThe total number of outlets on the ATS.
1.3.6.1.4.1.3808.1.1.5.6.1.2ScalaratsOutletDevCtrlOutletNumread-onlymandatoryThe number of controlled outlets on the ATS.
1.3.6.1.4.1.3808.1.1.5.6.1.3ScalaratsOutletDevColdStartDelayread-writemandatoryThe amount of delay, in seconds, between when power is provided to the ATS and when the ATS provides basic master power to the outlets. Allowed values are: -1 …
1.3.6.1.4.1.3808.1.1.5.6.1.4ScalaratsOutletDevColdStartStateread-writemandatoryThe ATS outlet state after coldstart. Allowed values are: 1 - all outlets on after coldstart. 2 - outlet status same as previous state.
1.3.6.1.4.1.3808.1.1.5.6.1.5ScalaratsOutletDevLocalCtrlread-writemandatoryTo configure enable or disable outlet local control function.
1.3.6.1.4.1.3808.1.1.5.6.1.6ScalaratsOutletDevCommandread-writemandatorySetting this OID to immediateAllOn (2) will turn all outlets on immediately. Setting this OID to immediateAllOff (3) will turn all outlets off immediately. Set…
1.3.6.1.4.1.3808.1.1.5.6.2ScalaratsOutletStatusTableSizeread-onlymandatoryThe size of the outlet status table.
1.3.6.1.4.1.3808.1.1.5.6.3TableatsOutletStatusTablenot-accessiblemandatoryAllows for getting of status of individual outlets.
1.3.6.1.4.1.3808.1.1.5.6.3.1RowatsOutletStatusEntrynot-accessiblemandatoryThe outlet to gather status from.
1.3.6.1.4.1.3808.1.1.5.6.3.1.1ColumnatsOutletStatusTableIndexread-onlymandatoryThe index to the outlet entry.
1.3.6.1.4.1.3808.1.1.5.6.3.1.2ColumnatsOutletStatusOutletNameread-onlymandatoryThe name of the outlet. The maximum string size is device dependent. This OID is provided for informational purposes only.
1.3.6.1.4.1.3808.1.1.5.6.3.1.3ColumnatsOutletStatusOutletStateread-onlymandatoryGetting this variable will return the outlet state. If the outlet is on, the outletStatusOn (1) value will be returned. If the outlet is off, the outletStatusO…
1.3.6.1.4.1.3808.1.1.5.6.3.1.4ColumnatsOutletStatusOutletCmdPendingread-onlymandatoryGetting this variable will return the command pending state of the outlet. If a command is pending on the outlet, the outletStatusCommandPending (1) value will…
1.3.6.1.4.1.3808.1.1.5.6.3.1.5ColumnatsOutletStatusOutletPhaseread-onlymandatoryThe phase/s associated with this outlet. For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase…
1.3.6.1.4.1.3808.1.1.5.6.3.1.6ColumnatsOutletStatusOutletBankread-onlymandatoryThe bank associated with this outlet.
1.3.6.1.4.1.3808.1.1.5.6.4ScalaratsOutletCtrlTableSizeread-onlymandatoryThe size of the outlet control table.
1.3.6.1.4.1.3808.1.1.5.6.5TableatsOutletCtrlTablenot-accessiblemandatoryAllows for control of the individual outlets.
1.3.6.1.4.1.3808.1.1.5.6.5.1RowatsOutletCtrlEntrynot-accessiblemandatoryThe outlet to control.
1.3.6.1.4.1.3808.1.1.5.6.5.1.1ColumnatsOutletCtrlTableIndexread-onlymandatoryThe index to the outlet entry.
1.3.6.1.4.1.3808.1.1.5.6.5.1.2ColumnatsOutletCtrlOutletNameread-onlymandatoryThe name of the outlet. The maximum string size is device dependent. An error will be returned if the set request exceeds the max size. This OID is provided fo…
1.3.6.1.4.1.3808.1.1.5.6.5.1.3ColumnatsOutletCtrlCommandread-writemandatoryGetting this variable will return the outlet state. If the outlet is on, the immediateOn (2) value will be returned. If the outlet is off, the immediateOff (2)…
1.3.6.1.4.1.3808.1.1.5.6.6ScalaratsOutletCfgTableSizeread-onlymandatoryThe size of the outlet config table.
1.3.6.1.4.1.3808.1.1.5.6.7TableatsOutletCfgTablenot-accessiblemandatoryAllows for configuration of individual outlets.
1.3.6.1.4.1.3808.1.1.5.6.7.1RowatsOutletCfgEntrynot-accessiblemandatoryThe outlet to configure.
1.3.6.1.4.1.3808.1.1.5.6.7.1.1ColumnatsOutletCfgTableIndexread-onlymandatoryThe index to the outlet entry.
1.3.6.1.4.1.3808.1.1.5.6.7.1.2ColumnatsOutletCfgOutletNameread-writemandatoryThe name of the outlet. The maximum string size is device dependent. An error will be returned if the set request exceeds the max size.
1.3.6.1.4.1.3808.1.1.5.6.7.1.3ColumnatsOutletCfgPowerOnTimeread-writemandatoryThe amount of time (in seconds) the outlet will delay powering on at coldstart or when a command that requires a turn-on delay is issued. Allowed values are: -…
1.3.6.1.4.1.3808.1.1.5.6.7.1.4ColumnatsOutletCfgPowerOffTimeread-writemandatoryThe amount of time (in seconds) the outlet will delay powering off when a command that requires a turn-off delay is issued. Allowed values are: -1 - never powe…
1.3.6.1.4.1.3808.1.1.5.6.7.1.5ColumnatsOutletCfgRebootDurationread-writemandatoryDuring a reboot sequence, power is turned off and then back on. This OID defines the amount of time to wait, in seconds, after turning the power off, at the st…
1.3.6.1.4.1.3808.1.1.6NodeePDU2
1.3.6.1.4.1.3808.1.1.6.1ScalarePDU2Roleread-onlymandatoryGet this oid shows the role the PDU played on Daisy Chain Group. The PDU as a Host can access whole ePDU2 content, and the PDU be standalong or a Slave can acc…
1.3.6.1.4.1.3808.1.1.6.2NodeePDU2Ident
1.3.6.1.4.1.3808.1.1.6.2.1ScalarePDU2IdentTableSizeread-onlymandatoryPDU as a Host response total PDU ident number on daisy chain. PDU as a Slave can only response 1.
1.3.6.1.4.1.3808.1.1.6.2.2TableePDU2IdentTablenot-accessiblemandatoryA table of Rack PDU identification information.
1.3.6.1.4.1.3808.1.1.6.2.2.1RowePDU2IdentEntrynot-accessiblemandatoryIdentification data from Rack PDU being queried.
1.3.6.1.4.1.3808.1.1.6.2.2.1.1ColumnePDU2IdentIndexread-onlymandatoryThe index to the Rack PDU identification table entry.
1.3.6.1.4.1.3808.1.1.6.2.2.1.2ColumnePDU2IdentModuleIndexread-onlymandatoryThe Rack PDU identification table entry numeric ID.
1.3.6.1.4.1.3808.1.1.6.2.2.1.3ColumnePDU2IdentNameread-onlymandatoryA user-defined string identifying the name of the Rack PDU.
1.3.6.1.4.1.3808.1.1.6.2.2.1.4ColumnePDU2IdentLocationread-onlymandatoryA user-defined string identifying the location of the Rack PDU.
1.3.6.1.4.1.3808.1.1.6.2.2.1.5ColumnePDU2IdentContactread-onlymandatoryA user-defined string identifying the person to contact of the Rack PDU.
1.3.6.1.4.1.3808.1.1.6.2.2.1.6ColumnePDU2IdentHardwareRevread-onlymandatoryThe Rack PDU hardware version.
1.3.6.1.4.1.3808.1.1.6.2.2.1.7ColumnePDU2IdentFirmwareRevread-onlymandatoryThe Rack PDU firmware version.
1.3.6.1.4.1.3808.1.1.6.2.2.1.8ColumnePDU2IdentDateOfManufactureread-onlymandatoryThe date the Rack PDU was manufactured in mm/dd/yyyy format.
1.3.6.1.4.1.3808.1.1.6.2.2.1.9ColumnePDU2IdentModelNameread-onlymandatoryThe Rack PDU model number.
1.3.6.1.4.1.3808.1.1.6.2.2.1.10ColumnePDU2IdentSerialNumberread-onlymandatoryThe Rack PDU serial number.
1.3.6.1.4.1.3808.1.1.6.2.2.1.11ColumnePDU2IdentIndicatorread-writemandatoryPDU will perform a panel indicator test when the variable is set to testIndicators(2). It is no effective to set this value to noTestIndicators(1).
1.3.6.1.4.1.3808.1.1.6.3NodeePDU2Device
1.3.6.1.4.1.3808.1.1.6.3.1ScalarePDU2DeviceTableSizeread-onlymandatoryA Host Rack PDU response total number of Rack PDUs on daisy chain. Rack PDU as a Slave can only response 1.
1.3.6.1.4.1.3808.1.1.6.3.2TableePDU2DeviceConfigTablenot-accessiblemandatoryA table of Rack PDU configuration data.
1.3.6.1.4.1.3808.1.1.6.3.2.1RowePDU2DeviceConfigEntrynot-accessiblemandatoryConfiguration data from Rack PDU being queried.
1.3.6.1.4.1.3808.1.1.6.3.2.1.1ColumnePDU2DeviceConfigIndexread-onlymandatoryThe index to the Rack PDU table entry.
1.3.6.1.4.1.3808.1.1.6.3.2.1.2ColumnePDU2DeviceConfigModuleIndexread-onlymandatoryThe Rack PDU numeric ID.
1.3.6.1.4.1.3808.1.1.6.3.2.1.3ColumnePDU2DeviceConfigNameread-writemandatoryA user-defined string identifying the name of Rack PDU.
1.3.6.1.4.1.3808.1.1.6.3.2.1.4ColumnePDU2DeviceConfigLocationread-writemandatoryA user-defined string identifying the location of the Rack PDU.
1.3.6.1.4.1.3808.1.1.6.3.2.1.5ColumnePDU2DeviceConfigContactread-writemandatoryA user-defined string identifying the person to contact of the Rack PDU.
1.3.6.1.4.1.3808.1.1.6.3.2.1.6ColumnePDU2DeviceConfigDisplayOrientationread-writemandatoryGetting this OID will return the intended physical orientation of the Seven-Segment Display. displayNormal(1) indicates Normal. displayReverse(2)indicates Upsi…
1.3.6.1.4.1.3808.1.1.6.3.2.1.7ColumnePDU2DeviceConfigColdstartDelayread-writemandatoryThe amount of delay, measured in seconds, between when power is provided to the Rack PDU and when the Rack PDU provides basic master power to the outlets. Allo…
1.3.6.1.4.1.3808.1.1.6.3.2.1.8ColumnePDU2DeviceConfigLowLoadThresholdread-writemandatoryUser-defined low current draw alarm threshold, measured in Amps.
1.3.6.1.4.1.3808.1.1.6.3.2.1.9ColumnePDU2DeviceConfigNearOverloadThresholdread-writemandatoryUser-defined near overload current threshold, measured in Amps.
1.3.6.1.4.1.3808.1.1.6.3.2.1.10ColumnePDU2DeviceConfigOverloadThresholdread-writemandatoryUser-defined current overload threshold, measured in Amps.
1.3.6.1.4.1.3808.1.1.6.3.2.1.11ColumnePDU2DeviceConfigPeakLoadResetread-writemandatorySetting this OID to resetAll (2) will cause the existing peak current value of Rack PDU and its outlets to be replaced by the current load current value. Setti…
1.3.6.1.4.1.3808.1.1.6.3.2.1.12ColumnePDU2DeviceConfigEnergyResetread-writemandatorySetting this OID to resetAll (2) will cause the device energy meter value to be reset to zero. Setting this OID to resetDevice (3) to reset the Rack PDU only. …
1.3.6.1.4.1.3808.1.1.6.3.3TableePDU2DeviceInfoTablenot-accessiblemandatoryA table of Rack PDU information.
1.3.6.1.4.1.3808.1.1.6.3.3.1RowePDU2DeviceInfoEntrynot-accessiblemandatoryInformation of the Rack PDU being queried.
1.3.6.1.4.1.3808.1.1.6.3.3.1.1ColumnePDU2DeviceInfoIndexread-onlymandatoryThe index to the Rack PDU Information table entry.
1.3.6.1.4.1.3808.1.1.6.3.3.1.2ColumnePDU2DeviceInfoModuleIndexread-onlymandatoryThe Rack PDU numeric ID.
1.3.6.1.4.1.3808.1.1.6.3.3.1.3ColumnePDU2DeviceInfoNameread-onlymandatoryA user-defined string identifying the name of the Rack PDU.
1.3.6.1.4.1.3808.1.1.6.3.3.1.4ColumnePDU2DeviceInfoRatingread-onlymandatoryThe electrical rating of the Rack PDU.
1.3.6.1.4.1.3808.1.1.6.3.3.1.5ColumnePDU2DeviceInfoNumOutletsread-onlymandatoryThe number of outlets on the Rack PDU.
1.3.6.1.4.1.3808.1.1.6.3.3.1.6ColumnePDU2DeviceInfoSwitchedOutletsread-onlymandatoryThe number of switched outlets on the Rack PDU.
1.3.6.1.4.1.3808.1.1.6.3.3.1.7ColumnePDU2DeviceInfoMeteredOutletsread-onlymandatoryThe number of metered outlets on the Rack PDU.
1.3.6.1.4.1.3808.1.1.6.3.3.1.8ColumnePDU2DeviceInfoNumPhasesread-onlymandatoryThe number of phases present in the Rack PDU.
1.3.6.1.4.1.3808.1.1.6.3.3.1.9ColumnePDU2DeviceInfoNumBreakersread-onlymandatoryThe number of metered banks present in the Rack PDU.
1.3.6.1.4.1.3808.1.1.6.3.3.1.10ColumnePDU2DeviceInfoBreakerRatingread-onlymandatoryThe maximum current rating, measured in Amps, for the Rack PDU. Getting this OID will return rating of the circuit breakers on the device if it has any.
1.3.6.1.4.1.3808.1.1.6.3.3.1.11ColumnePDU2DeviceInfoOrientationread-onlymandatoryRack PDU orientation.
1.3.6.1.4.1.3808.1.1.6.3.3.1.12ColumnePDU2DeviceInfoOutletLayoutread-onlymandatoryGetting this OID will return outlet layout for the device. SeqPhaseToNeutral(1) indicates outlet layout as follows: 1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,... SeqPhaseT…
1.3.6.1.4.1.3808.1.1.6.3.4TableePDU2DeviceStatusTablenot-accessiblemandatoryA table of Rack PDU current status.
1.3.6.1.4.1.3808.1.1.6.3.4.1RowePDU2DeviceStatusEntrynot-accessiblemandatoryStatus data from the Rack PDU being queried.
1.3.6.1.4.1.3808.1.1.6.3.4.1.1ColumnePDU2DeviceStatusIndexread-onlymandatoryThe index to the Rack PDU status table entry.
1.3.6.1.4.1.3808.1.1.6.3.4.1.2ColumnePDU2DeviceStatusModuleIndexread-onlymandatoryThe Rack PDU numeric ID
1.3.6.1.4.1.3808.1.1.6.3.4.1.3ColumnePDU2DeviceStatusNameread-onlymandatoryA user-defined string identifying the name of the Rack PDU.
1.3.6.1.4.1.3808.1.1.6.3.4.1.4ColumnePDU2DeviceStatusLoadStateread-onlymandatoryIndicates the present load status of the Rack PDU.
1.3.6.1.4.1.3808.1.1.6.3.4.1.5ColumnePDU2DeviceStatusLoadread-onlymandatoryThe power consumption of the Rack PDU load in tenths of amps.
1.3.6.1.4.1.3808.1.1.6.3.4.1.6ColumnePDU2DeviceStatusPeakLoadread-onlymandatoryThe peak power consumption of the Rack PDU load in tenths of amps.
1.3.6.1.4.1.3808.1.1.6.3.4.1.7ColumnePDU2DeviceStatusPeakLoadTimestampread-onlymandatoryIndicates the date and time that peak load current occurred.
1.3.6.1.4.1.3808.1.1.6.3.4.1.8ColumnePDU2DeviceStatusPeakLoadStartTimeread-onlymandatoryIndicates the date and time of the last device peak load reset.
1.3.6.1.4.1.3808.1.1.6.3.4.1.9ColumnePDU2DeviceStatusEnergyread-onlymandatoryA user resettable energy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours.
1.3.6.1.4.1.3808.1.1.6.3.4.1.10ColumnePDU2DeviceStatusEnergyStartTimeread-onlymandatoryIndicates the date and time of the last device energy meter reset.
1.3.6.1.4.1.3808.1.1.6.3.4.1.11ColumnePDU2DeviceStatusCommandPendingread-onlymandatoryIndicates whether or not the device is processing a pending command.
1.3.6.1.4.1.3808.1.1.6.3.4.1.12ColumnePDU2DeviceStatusPowerSupplyAlarmread-onlymandatoryIndicates a power supply alarm is active when value equals alarm (2).
1.3.6.1.4.1.3808.1.1.6.3.4.1.13ColumnePDU2DeviceStatusPowerSupply1Statusread-onlymandatoryIndicates whether or not an alarm is active in Power Supply 1.
1.3.6.1.4.1.3808.1.1.6.3.4.1.14ColumnePDU2DeviceStatusPowerSupply2Statusread-onlymandatoryIndicates whether or not an alarm is active in Power Supply 2.
1.3.6.1.4.1.3808.1.1.6.3.4.1.15ColumnePDU2DeviceStatusApparentPowerread-onlymandatoryThe apparent power consumption of the Rack PDU load in VoltAmps (VA).
1.3.6.1.4.1.3808.1.1.6.3.4.1.16ColumnePDU2DeviceStatusPowerFactorread-onlymandatoryThe power factor of the Rack PDU load in hundredths.
1.3.6.1.4.1.3808.1.1.6.3.4.1.17ColumnePDU2DeviceStatusRoleTyperead-onlymandatoryGet this oid shows the role the PDU played on Daisy Chain Group. The PDU as a Host can access whole ePDU2 content, and the PDU be standalong or a Slave can acc…
1.3.6.1.4.1.3808.1.1.6.3.5TableePDU2DeviceControlTablenot-accessiblemandatoryA table of Rack PDU control data.
1.3.6.1.4.1.3808.1.1.6.3.5.1RowePDU2DeviceControlEntrynot-accessiblemandatoryControl data from Rack PDU being queried.
1.3.6.1.4.1.3808.1.1.6.3.5.1.1ColumnePDU2DeviceControlIndexread-onlymandatoryThe index to the Rack PDU control table entry.
1.3.6.1.4.1.3808.1.1.6.3.5.1.2ColumnePDU2DeviceControlModuleIndexread-onlymandatoryThe Rack PDU numeric ID.
1.3.6.1.4.1.3808.1.1.6.3.5.1.3ColumnePDU2DeviceControlNameread-onlymandatoryA user-defined string identifying the name of the Rack PDU.
1.3.6.1.4.1.3808.1.1.6.3.5.1.4ColumnePDU2DeviceControlCommandread-writemandatorySetting this OID to immediateAllOn (1) will turn all outlets on immediately. Setting this OID to immediateAllOff (2) will turn all outlets off immediately. Set…
1.3.6.1.4.1.3808.1.1.6.4NodeePDU2Phase
1.3.6.1.4.1.3808.1.1.6.4.1ScalarePDU2PhaseTableSizeread-onlymandatoryA Host Rack PDU response total phase number of Rack PDUs on daisy chain. Rack PDU as a Slave can only response itself number of phase.
1.3.6.1.4.1.3808.1.1.6.4.2TableePDU2PhaseConfigTablenot-accessiblemandatoryA table of Rack PDU phase configuration data.
1.3.6.1.4.1.3808.1.1.6.4.2.1RowePDU2PhaseConfigEntrynot-accessiblemandatoryConfiguration data from currently queried Rack PDU phase.
1.3.6.1.4.1.3808.1.1.6.4.2.1.1ColumnePDU2PhaseConfigIndexread-onlymandatoryThe index to the Rack PDU phase configuration table entry.
1.3.6.1.4.1.3808.1.1.6.4.2.1.2ColumnePDU2PhaseConfigModuleIndexread-onlymandatoryThe Rack PDU numeric ID.
1.3.6.1.4.1.3808.1.1.6.4.2.1.3ColumnePDU2PhaseConfigNumberread-onlymandatoryThe numeric phase ID.
1.3.6.1.4.1.3808.1.1.6.4.2.1.4ColumnePDU2PhaseConfigOverloadRestrictionread-writemandatoryThis OID controls the behavior of a Switched Rack PDU phase when an overload condition is possible and additional outlets are requested to be turned on. Settin…
1.3.6.1.4.1.3808.1.1.6.4.2.1.5ColumnePDU2PhaseConfigLowLoadThresholdread-writemandatoryUser-defined low load phase current threshold in Amps.
1.3.6.1.4.1.3808.1.1.6.4.2.1.6ColumnePDU2PhaseConfigNearOverloadThresholdread-writemandatoryUser-defined near phase overload current warning threshold in Amps.
1.3.6.1.4.1.3808.1.1.6.4.2.1.7ColumnePDU2PhaseConfigOverloadThresholdread-writemandatoryUser-defined phase overload current threshold in Amps
1.3.6.1.4.1.3808.1.1.6.4.2.1.8ColumnePDU2PhaseConfigPhasePeakLoadResetread-writemandatorySetting this OID to reset (2) will cause the existing peak current value to be replaced by the present load current value. Getting this OID will do nothing and…
1.3.6.1.4.1.3808.1.1.6.4.3TableePDU2PhaseInfoTablenot-accessiblemandatoryA table of Rack PDU phase information.
1.3.6.1.4.1.3808.1.1.6.4.3.1RowePDU2PhaseInfoEntrynot-accessiblemandatoryInformation data from currently queried Rack PDU phase.
1.3.6.1.4.1.3808.1.1.6.4.3.1.1ColumnePDU2PhaseInfoIndexread-onlymandatoryThe index to the Rack PDU phase properties table entry.
1.3.6.1.4.1.3808.1.1.6.4.3.1.2ColumnePDU2PhaseInfoModuleIndexread-onlymandatoryThe Rack PDU numeric ID.
1.3.6.1.4.1.3808.1.1.6.4.3.1.3ColumnePDU2PhaseInfoNumberread-onlymandatoryThe numeric phase ID.
1.3.6.1.4.1.3808.1.1.6.4.4TableePDU2PhaseStatusTablenot-accessiblemandatoryA table of Rack PDU phase status data
1.3.6.1.4.1.3808.1.1.6.4.4.1RowePDU2PhaseStatusEntrynot-accessiblemandatoryStatus data from currently queried Rack PDU phase
1.3.6.1.4.1.3808.1.1.6.4.4.1.1ColumnePDU2PhaseStatusIndexread-onlymandatoryThe index to the Rack PDU phase status table entry.
1.3.6.1.4.1.3808.1.1.6.4.4.1.2ColumnePDU2PhaseStatusModuleIndexread-onlymandatoryThe Rack PDU numeric ID.
1.3.6.1.4.1.3808.1.1.6.4.4.1.3ColumnePDU2PhaseStatusNumberread-onlymandatoryThe numeric phase ID.
1.3.6.1.4.1.3808.1.1.6.4.4.1.4ColumnePDU2PhaseStatusLoadStateread-onlymandatoryIndicates the present load status of the Rack PDU phase being queried.
1.3.6.1.4.1.3808.1.1.6.4.4.1.5ColumnePDU2PhaseStatusLoadread-onlymandatoryIndicates the current draw, in tenths of Amps, of the load on the Rack PDU phase being queried.
1.3.6.1.4.1.3808.1.1.6.4.4.1.6ColumnePDU2PhaseStatusVoltageread-onlymandatoryIndicates the Voltage, in Volts, of the Rack PDU phase being queried
1.3.6.1.4.1.3808.1.1.6.4.4.1.7ColumnePDU2PhaseStatusPowerread-onlymandatoryIndicates the load power, in watts (kW), consumed on the Rack PDU phase being queried
1.3.6.1.4.1.3808.1.1.6.4.4.1.8ColumnePDU2PhaseStatusApparentPowerread-onlymandatoryIndicates the load apparent power, in hundredths of kiloVoltAmps (kVA), consumed on the Rack PDU phase being queried
1.3.6.1.4.1.3808.1.1.6.4.4.1.9ColumnePDU2PhaseStatusPowerFactorread-onlymandatoryIndicates the load power factor, in hundredths, of the Rack PDU phase being queried
1.3.6.1.4.1.3808.1.1.6.4.4.1.10ColumnePDU2PhaseStatusPeakLoadread-onlymandatoryThe peak current of the Rack PDU phase load in tenths of Amps
1.3.6.1.4.1.3808.1.1.6.4.4.1.11ColumnePDU2PhaseStatusPeakLoadTimestampread-onlymandatoryIndicates the date and time the phase peak current occurred.
1.3.6.1.4.1.3808.1.1.6.4.4.1.12ColumnePDU2PhaseStatusPeakLoadStartTimeread-onlymandatoryIndicates the date and time of the last phase peak current reset.
1.3.6.1.4.1.3808.1.1.6.5NodeePDU2Bank
1.3.6.1.4.1.3808.1.1.6.5.1ScalarePDU2BankTableSizeread-onlymandatoryA Host Rack PDU response total bank number of Rack PDUs on daisy chain. Rack PDU as a Slave can only response itself number of bank.
1.3.6.1.4.1.3808.1.1.6.5.2TableePDU2BankConfigTablenot-accessiblemandatoryA table of Rack PDU bank configuration data.
1.3.6.1.4.1.3808.1.1.6.5.2.1RowePDU2BankConfigEntrynot-accessiblemandatoryConfiguration data from currently queried Rack PDU bank.
1.3.6.1.4.1.3808.1.1.6.5.2.1.1ColumnePDU2BankConfigIndexread-onlymandatoryThe index to the Rack PDU bank configuration table entry.
1.3.6.1.4.1.3808.1.1.6.5.2.1.2ColumnePDU2BankConfigModuleIndexread-onlymandatoryThe Rack PDU numeric ID.
1.3.6.1.4.1.3808.1.1.6.5.2.1.3ColumnePDU2BankConfigNumberread-onlymandatoryThe numeric bank ID.
1.3.6.1.4.1.3808.1.1.6.5.2.1.4ColumnePDU2BankConfigOverloadRestrictionread-writemandatoryThis OID controls the behavior of a Switched Rack PDU bank when an overload condition is possible and additional outlets are requested to be turned on. Setting…
1.3.6.1.4.1.3808.1.1.6.5.2.1.5ColumnePDU2BankConfigLowLoadThresholdread-writemandatoryUser-defined low load bank current threshold in Amps.
1.3.6.1.4.1.3808.1.1.6.5.2.1.6ColumnePDU2BankConfigNearOverloadThresholdread-writemandatoryUser-defined near bank overload current warning threshold in Amps.
1.3.6.1.4.1.3808.1.1.6.5.2.1.7ColumnePDU2BankConfigOverloadThresholdread-writemandatoryUser-defined bank overload current threshold in Amps
1.3.6.1.4.1.3808.1.1.6.5.2.1.8ColumnePDU2BankConfigPeakLoadResetread-writemandatorySetting this OID to reset (2) will cause the existing peak current value to be replaced by the present load current value. Getting this OID will do nothing and…
1.3.6.1.4.1.3808.1.1.6.5.3TableePDU2BankInfoTablenot-accessiblemandatoryA table of Rack PDU bank information.
1.3.6.1.4.1.3808.1.1.6.5.3.1RowePDU2BankInfoEntrynot-accessiblemandatoryInformation data from currently queried Rack PDU bank.
1.3.6.1.4.1.3808.1.1.6.5.3.1.1ColumnePDU2BankInfoIndexread-onlymandatoryThe index to the Rack PDU bank properties table entry.
1.3.6.1.4.1.3808.1.1.6.5.3.1.2ColumnePDU2BankInfoModuleIndexread-onlymandatoryThe Rack PDU numeric ID.
1.3.6.1.4.1.3808.1.1.6.5.3.1.3ColumnePDU2BankInfoNumberread-onlymandatoryThe numeric bank ID.
1.3.6.1.4.1.3808.1.1.6.5.4TableePDU2BankStatusTablenot-accessiblemandatoryA table of Rack PDU bank status data
1.3.6.1.4.1.3808.1.1.6.5.4.1RowePDU2BankStatusEntrynot-accessiblemandatoryStatus data from currently queried Rack PDU bank
1.3.6.1.4.1.3808.1.1.6.5.4.1.1ColumnePDU2BankStatusIndexread-onlymandatoryThe index to the Rack PDU bank status table entry.
1.3.6.1.4.1.3808.1.1.6.5.4.1.2ColumnePDU2BankStatusModuleIndexread-onlymandatoryThe Rack PDU numeric ID.
1.3.6.1.4.1.3808.1.1.6.5.4.1.3ColumnePDU2BankStatusNumberread-onlymandatoryThe numeric bank ID.
1.3.6.1.4.1.3808.1.1.6.5.4.1.4ColumnePDU2BankStatusLoadStateread-onlymandatoryIndicates the present load status of the Rack PDU bank being queried.
1.3.6.1.4.1.3808.1.1.6.5.4.1.5ColumnePDU2BankStatusLoadread-onlymandatoryIndicates the current draw, in tenths of Amps, of the load on the Rack PDU bank being queried.
1.3.6.1.4.1.3808.1.1.6.5.4.1.6ColumnePDU2BankStatusPeakLoadread-onlymandatoryThe peak current of the Rack PDU bank load in tenths of Amps.
1.3.6.1.4.1.3808.1.1.6.5.4.1.7ColumnePDU2BankStatusPeakLoadTimestampread-onlymandatoryIndicates the date and time the bank peak current occurred.
1.3.6.1.4.1.3808.1.1.6.5.4.1.8ColumnePDU2BankStatusPeakLoadStartTimeread-onlymandatoryIndicates the date and time of the last bank peak current reset.
1.3.6.1.4.1.3808.1.1.6.6NodeePDU2Outlet
1.3.6.1.4.1.3808.1.1.6.6.1NodeePDU2OutletSwitched
1.3.6.1.4.1.3808.1.1.6.6.1.1ScalarePDU2OutletSwitchedTableSizeread-onlymandatoryThe number of switched outlets on connected Rack PDUs.
1.3.6.1.4.1.3808.1.1.6.6.1.2TableePDU2OutletSwitchedConfigTablenot-accessiblemandatoryA table of Rack PDU switched outlet configuration data.
1.3.6.1.4.1.3808.1.1.6.6.1.2.1RowePDU2OutletSwitchedConfigEntrynot-accessiblemandatoryConfiguration data from currently queried Rack PDU switched outlet.
1.3.6.1.4.1.3808.1.1.6.6.1.2.1.1ColumnePDU2OutletSwitchedConfigIndexread-onlymandatoryThe index to the Rack PDU switched outlet configuration table entry.
1.3.6.1.4.1.3808.1.1.6.6.1.2.1.2ColumnePDU2OutletSwitchedConfigModuleIndexread-onlymandatoryThe Rack PDU numeric ID.
1.3.6.1.4.1.3808.1.1.6.6.1.2.1.3ColumnePDU2OutletSwitchedConfigNumberread-onlymandatoryThe numeric switched outlet ID.
1.3.6.1.4.1.3808.1.1.6.6.1.2.1.4ColumnePDU2OutletSwitchedConfigNameread-writemandatoryThe user-defined switched outlet name string.
1.3.6.1.4.1.3808.1.1.6.6.1.2.1.5ColumnePDU2OutletSwitchedConfigPowerOnTimeread-writemandatoryThe amount of time (in seconds) the outlet will delay powering on at coldstart or when a command that requires a turn-on delay is issued. Allowed values are: -…
1.3.6.1.4.1.3808.1.1.6.6.1.2.1.6ColumnePDU2OutletSwitchedConfigPowerOffTimeread-writemandatoryThe amount of time (in seconds) the outlet will delay powering off when a command that requires a turn-off delay is issued. Allowed values are: -1 - never powe…
1.3.6.1.4.1.3808.1.1.6.6.1.2.1.7ColumnePDU2OutletSwitchedConfigRebootDurationread-writemandatoryDuring a reboot sequence, power is turned off and then back on. This OID defines the amount of time to wait, in seconds, after turning the power off, at the st…
1.3.6.1.4.1.3808.1.1.6.6.1.3TableePDU2OutletSwitchedInfoTablenot-accessiblemandatoryA table of Rack PDU switched outlet information.
1.3.6.1.4.1.3808.1.1.6.6.1.3.1RowePDU2OutletSwitchedInfoEntrynot-accessiblemandatoryInformation of the currently queried Rack PDU switched outlet.
1.3.6.1.4.1.3808.1.1.6.6.1.3.1.1ColumnePDU2OutletSwitchedInfoIndexread-onlymandatoryThe index to the Rack PDU switched outlet information table entry.
1.3.6.1.4.1.3808.1.1.6.6.1.3.1.2ColumnePDU2OutletSwitchedInfoModuleIndexread-onlymandatoryThe Rack PDU numeric ID.
1.3.6.1.4.1.3808.1.1.6.6.1.3.1.3ColumnePDU2OutletSwitchedInfoNumberread-onlymandatoryThe numeric switched outlet ID.
1.3.6.1.4.1.3808.1.1.6.6.1.3.1.4ColumnePDU2OutletSwitchedInfoNameread-onlymandatoryThe numeric switched outlet name.
1.3.6.1.4.1.3808.1.1.6.6.1.3.1.5ColumnePDU2OutletSwitchedInfoPhaseLayoutread-onlymandatoryThis OID describes the phase connections of the referenced outlet as follows: seqPhase1ToNeutral(1) indicates that the outlet is wired from Phase 1 to Neutral.…
1.3.6.1.4.1.3808.1.1.6.6.1.3.1.6ColumnePDU2OutletSwitchedInfoBankread-onlymandatoryThe numeric bank ID.
1.3.6.1.4.1.3808.1.1.6.6.1.4TableePDU2OutletSwitchedStatusTablenot-accessiblemandatoryA table of Rack PDU switched outlet status information.
1.3.6.1.4.1.3808.1.1.6.6.1.4.1RowePDU2OutletSwitchedStatusEntrynot-accessiblemandatoryStatus information for currently queried Rack PDU switched outlet.
1.3.6.1.4.1.3808.1.1.6.6.1.4.1.1ColumnePDU2OutletSwitchedStatusIndexread-onlymandatoryThe index to the Rack PDU switched outlet status information table entry.
1.3.6.1.4.1.3808.1.1.6.6.1.4.1.2ColumnePDU2OutletSwitchedStatusModuleIndexread-onlymandatoryThe Rack PDU numeric ID.
1.3.6.1.4.1.3808.1.1.6.6.1.4.1.3ColumnePDU2OutletSwitchedStatusNumberread-onlymandatoryThe numeric switched outlet ID.
1.3.6.1.4.1.3808.1.1.6.6.1.4.1.4ColumnePDU2OutletSwitchedStatusNameread-onlymandatoryThe user-defined switched outlet name string.
1.3.6.1.4.1.3808.1.1.6.6.1.4.1.5ColumnePDU2OutletSwitchedStatusStateread-onlymandatoryIndicates the present switch state of the Rack PDU switched outlet being queried.
1.3.6.1.4.1.3808.1.1.6.6.1.4.1.6ColumnePDU2OutletSwitchedStatusCommandPendingread-onlymandatoryGetting this variable will return the command pending state of the outlet. If a command is pending on the outlet, the outletStatusCommandPending (1) value will…
1.3.6.1.4.1.3808.1.1.6.6.1.5TableePDU2OutletSwitchedControlTablenot-accessiblemandatoryA table of Rack PDU switched outlet control data.
1.3.6.1.4.1.3808.1.1.6.6.1.5.1RowePDU2OutletSwitchedControlEntrynot-accessiblemandatoryControl data for currently queried Rack PDU switched outlet.
1.3.6.1.4.1.3808.1.1.6.6.1.5.1.1ColumnePDU2OutletSwitchedControlIndexread-onlymandatoryThe index to the Rack PDU switched outlet control data table entry.
1.3.6.1.4.1.3808.1.1.6.6.1.5.1.2ColumnePDU2OutletSwitchedControlModuleIndexread-onlymandatoryThe user-defined Rack PDU numeric ID.
1.3.6.1.4.1.3808.1.1.6.6.1.5.1.3ColumnePDU2OutletSwitchedControlNumberread-onlymandatoryThe numeric switched outlet ID.
1.3.6.1.4.1.3808.1.1.6.6.1.5.1.4ColumnePDU2OutletSwitchedControlNameread-onlymandatoryThe user-defined switched outlet name string.
1.3.6.1.4.1.3808.1.1.6.6.1.5.1.5ColumnePDU2OutletSwitchedControlCommandread-writemandatoryGetting this variable will return the outlet state. If the outlet is on, the immediateOn (1) value will be returned. If the outlet is off, the immediateOff (2)…
1.3.6.1.4.1.3808.1.1.6.6.2NodeePDU2OutletMetered
1.3.6.1.4.1.3808.1.1.6.6.2.1ScalarePDU2OutletMeteredTableSizeread-onlymandatoryThe number of metered outlets on connected Rack PDUs.
1.3.6.1.4.1.3808.1.1.6.6.2.2TableePDU2OutletMeteredConfigTablenot-accessiblemandatoryA table of Rack PDU metered outlet configuration data.
1.3.6.1.4.1.3808.1.1.6.6.2.2.1RowePDU2OutletMeteredConfigEntrynot-accessiblemandatoryConfiguration data from currently queried Rack PDU metered outlet.
1.3.6.1.4.1.3808.1.1.6.6.2.2.1.1ColumnePDU2OutletMeteredConfigIndexread-onlymandatoryThe index to the Rack PDU metered outlet configuration table entry.
1.3.6.1.4.1.3808.1.1.6.6.2.2.1.2ColumnePDU2OutletMeteredConfigModuleIndexread-onlymandatoryThe user-defined Rack PDU numeric ID.
1.3.6.1.4.1.3808.1.1.6.6.2.2.1.3ColumnePDU2OutletMeteredConfigNumberread-onlymandatoryThe numeric metered outlet ID.
1.3.6.1.4.1.3808.1.1.6.6.2.2.1.4ColumnePDU2OutletMeteredConfigNameread-writemandatoryThe user-defined metered outlet name string.
1.3.6.1.4.1.3808.1.1.6.6.2.2.1.5ColumnePDU2OutletMeteredConfigLowLoadThresholdread-writemandatoryUser-defined outlet low load current threshold in Watts.
1.3.6.1.4.1.3808.1.1.6.6.2.2.1.6ColumnePDU2OutletMeteredConfigNearOverloadThresholdread-writemandatoryUser-defined outlet near overload warning threshold in Watts.
1.3.6.1.4.1.3808.1.1.6.6.2.2.1.7ColumnePDU2OutletMeteredConfigOverloadThresholdread-writemandatoryUser-defined outlet overload current threshold in Watts.
1.3.6.1.4.1.3808.1.1.6.6.2.3TableePDU2OutletMeteredInfoTablenot-accessiblemandatoryA table of Rack PDU metered outlet information.
1.3.6.1.4.1.3808.1.1.6.6.2.3.1RowePDU2OutletMeteredInfoEntrynot-accessiblemandatoryInformation of currently queried Rack PDU metered outlet.
1.3.6.1.4.1.3808.1.1.6.6.2.3.1.1ColumnePDU2OutletMeteredInfoIndexread-onlymandatoryThe index to the Rack PDU metered information table entry.
1.3.6.1.4.1.3808.1.1.6.6.2.3.1.2ColumnePDU2OutletMeteredInfoModuleIndexread-onlymandatoryThe Rack PDU numeric ID.
1.3.6.1.4.1.3808.1.1.6.6.2.3.1.3ColumnePDU2OutletMeteredInfoNumberread-onlymandatoryThe numeric metered outlet ID.
1.3.6.1.4.1.3808.1.1.6.6.2.3.1.4ColumnePDU2OutletMeteredInfoNameread-onlymandatoryThe user-defined metered outlet name string.
1.3.6.1.4.1.3808.1.1.6.6.2.3.1.5ColumnePDU2OutletMeteredInfoLayoutread-onlymandatoryThis OID describes the phase connections of the referenced outlet as follows: seqPhase1ToNeutral(1) indicates that the outlet is wired from Phase 1 to Neutral.…
1.3.6.1.4.1.3808.1.1.6.6.2.3.1.6ColumnePDU2OutletMeteredInfoRatingread-onlymandatoryMaximum power rating of Rack PDU metered outlet.
1.3.6.1.4.1.3808.1.1.6.6.2.3.1.7ColumnePDU2OutletMeteredInfoBankread-onlymandatoryThis outlet's numeric bank ID.
1.3.6.1.4.1.3808.1.1.6.6.2.4TableePDU2OutletMeteredStatusTablenot-accessiblemandatoryA table of Rack PDU metered outlet status data.
1.3.6.1.4.1.3808.1.1.6.6.2.4.1RowePDU2OutletMeteredStatusEntrynot-accessiblemandatoryStatus data from currently queried Rack PDU metered outlet.
1.3.6.1.4.1.3808.1.1.6.6.2.4.1.1ColumnePDU2OutletMeteredStatusIndexread-onlymandatoryThe index to the Rack PDU metered status table entry.
1.3.6.1.4.1.3808.1.1.6.6.2.4.1.2ColumnePDU2OutletMeteredStatusModuleIndexread-onlymandatoryThe Rack PDU numeric ID.
1.3.6.1.4.1.3808.1.1.6.6.2.4.1.3ColumnePDU2OutletMeteredStatusNumberread-onlymandatoryThe numeric metered outlet ID.
1.3.6.1.4.1.3808.1.1.6.6.2.4.1.4ColumnePDU2OutletMeteredStatusNameread-onlymandatoryThe user-defined metered outlet name string.
1.3.6.1.4.1.3808.1.1.6.6.2.4.1.5ColumnePDU2OutletMeteredStatusAlarmread-onlymandatoryGetting this OID will return the current outlet alarm.
1.3.6.1.4.1.3808.1.1.6.6.2.4.1.6ColumnePDU2OutletMeteredStatusLoadread-onlymandatoryGetting this OID will return the measured Outlet load for an Outlet Monitored Rack PDU in tenths of Amps.
1.3.6.1.4.1.3808.1.1.6.6.2.4.1.7ColumnePDU2OutletMeteredStatusActivePowerread-onlymandatoryGetting this OID will return the measured Outlet load for an Outlet Monitored Rack PDU in watts.
1.3.6.1.4.1.3808.1.1.6.6.2.4.1.8ColumnePDU2OutletMeteredStatusPeakPowerread-onlymandatoryThe peak power consumption of the Rack PDU load in watts.
1.3.6.1.4.1.3808.1.1.6.6.2.4.1.9ColumnePDU2OutletMeteredStatusPeakPowerTimestampread-onlymandatoryGet this oid shows the date and time that peak power consumption occurred.
1.3.6.1.4.1.3808.1.1.6.6.2.4.1.10ColumnePDU2OutletMeteredStatusPeakPowerStartTimeread-onlymandatoryGet this oid shows the date and time that peak power consumption started.
1.3.6.1.4.1.3808.1.1.6.6.2.4.1.11ColumnePDU2OutletMeteredStatusEnergyread-onlymandatoryEnergy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours.
1.3.6.1.4.1.3808.1.1.6.6.2.4.1.12ColumnePDU2OutletMeteredStatusEnergyStartread-onlymandatoryIndicates the date and time of the last device energy meter reset.
1.3.6.1.4.1.3808.1.1.6.7NodeePDU2Sensor
1.3.6.1.4.1.3808.1.1.6.7.1ScalarePDU2SensorTableSizeread-onlymandatoryePDU2SensorTableSize
1.3.6.1.4.1.3808.1.1.6.8NodeePDU2Group
1.3.6.1.4.1.3808.1.1.6.8.1ScalarePDU2GroupNumberOfDevicesread-onlymandatoryGetting this OID will return the number of Rack PDU devices contributing to the Daisy Chain group power and energy values. Queries to slave units in an Daisy C…
1.3.6.1.4.1.3808.1.1.6.8.2ScalarePDU2GroupTotalPowerread-onlymandatoryGetting this OID will return the total power consumption of the Rack PDU Daisy Chain group devices in watts. Queries to slave units in an Daisy Chain group wil…
1.3.6.1.4.1.3808.1.1.6.8.3ScalarePDU2GroupTotalEnergyread-onlymandatoryGetting this OID will return the total energy consumption of the Rack PDU Daisy Chain group devices in tenths of kilowatt-hours. To reset the energy meters for…
1.3.6.1.4.1.3808.1.1.6.8.4ScalarePDU2GroupEnergyResetread-writemandatorySetting this OID to reset (2) will cause the device energy meter value on each device in the Rack PDU Daisy Chain group to be reset to zero. Getting this OID i…
1.3.6.1.4.1.3808.1.1.6.8.5ScalarePDU2GroupPeakRecordResetread-writemandatorySetting this OID to reset (2) will cause the device peak record value on each device in the Rack PDU Daisy Chain group to be reset to current load/power. Getti…
1.3.6.1.4.1.3808.1.1.7Nodebattmgr
1.3.6.1.4.1.3808.1.1.7.1NodebmIdent
1.3.6.1.4.1.3808.1.1.7.1.1ScalarbmIdentModelNameread-onlymandatoryBattery manager model name.
1.3.6.1.4.1.3808.1.1.7.1.2ScalarbmIdentHardwareRevread-onlymandatoryBattery manager hardware version.
1.3.6.1.4.1.3808.1.1.7.1.3ScalarbmIdentFirmwareRevread-onlymandatoryBattery manager firmware version.
1.3.6.1.4.1.3808.1.1.7.1.4ScalarbmIdentLCDHardwareRevread-onlymandatoryBattery manager LCD hardware version.
1.3.6.1.4.1.3808.1.1.7.1.5ScalarbmIdentLCDFirmwareRevread-onlymandatoryBattery manager LCD firmware version.
1.3.6.1.4.1.3808.1.1.7.1.6ScalarbmIdentDateOfManufactureread-onlymandatoryBattery manager manufacture date.
1.3.6.1.4.1.3808.1.1.7.1.7ScalarbmIdentSerialNumberread-onlymandatoryBattery manager serial number.
1.3.6.1.4.1.3808.1.1.7.1.8ScalarbmIdentNameread-writemandatoryBattery manager system identification name.
1.3.6.1.4.1.3808.1.1.7.1.9ScalarbmIdentLocationread-writemandatoryBattery manager system location.
1.3.6.1.4.1.3808.1.1.7.2NodebmProperty
1.3.6.1.4.1.3808.1.1.7.2.1ScalarbmPropertyStringMaxread-onlymandatoryBattery manager max string count supported.
1.3.6.1.4.1.3808.1.1.7.2.2ScalarbmPropertyMaxProbeOnStringread-onlymandatoryBattery manager max probes on a string supported.
1.3.6.1.4.1.3808.1.1.7.2.3ScalarbmPropertyInputVoltageRangeread-onlymandatoryBattery manager line input voltage range.
1.3.6.1.4.1.3808.1.1.7.3NodebmConfig
1.3.6.1.4.1.3808.1.1.7.3.1ScalarbmConfigBattAHread-writemandatoryBattery manager battery AH type configuration, unit in 0.1 AH.
1.3.6.1.4.1.3808.1.1.7.3.2ScalarbmConfigStringCountread-writemandatoryBattery manager string count setting.
1.3.6.1.4.1.3808.1.1.7.3.3ScalarbmConfigProbesCountOnStringread-writemandatoryBattery manager probe count on a string setting.
1.3.6.1.4.1.3808.1.1.7.3.4ScalarbmConfigLowVoltAlarmThresholdread-writemandatoryBattery low voltage alarm threshold setting, unit in 0.1 volt.
1.3.6.1.4.1.3808.1.1.7.3.5ScalarbmConfigHighVoltAlarmThresholdread-writemandatoryBattery high voltage alarm threshold setting, unit in 0.1 volt.
1.3.6.1.4.1.3808.1.1.7.3.6ScalarbmConfigVoltDiffAlarmThresholdread-writemandatoryBatteries within a string voltage difference threshold, unit in 0.1 volt.
1.3.6.1.4.1.3808.1.1.7.3.7ScalarbmConfigLowTempAlarmThresholdread-writemandatoryBattery low temperature alarm threshold, unit in 0.1 degree C.
1.3.6.1.4.1.3808.1.1.7.3.8ScalarbmConfigHighTempAlarmThresholdread-writemandatoryBattery high temperature alarm threshold, unit in 0.1 degree C.
1.3.6.1.4.1.3808.1.1.7.3.9ScalarbmConfigLowResAlarmThresholdread-writemandatoryBattery low resistance alarm threshold, unit in 0.01 mOhm.
1.3.6.1.4.1.3808.1.1.7.3.10ScalarbmConfigHighResAlarmThresholdread-writemandatoryBattery high resistance alarm threshold, unit in 0.01 mOhm.
1.3.6.1.4.1.3808.1.1.7.3.11ScalarbmConfigLowResWarnThresholdread-writemandatoryBattery low resistance warning threshold, unit in 0.01 mOhm.
1.3.6.1.4.1.3808.1.1.7.3.12ScalarbmConfigHighResWarnThresholdread-writemandatoryBattery high resistance warning threshold, unit in 0.01 mOhm.
1.3.6.1.4.1.3808.1.1.7.3.13ScalarbmConfigResHealthAlarmThresholdread-writemandatoryBattery resistance health alarm threshold, unit in percentage and should larger than 100.
1.3.6.1.4.1.3808.1.1.7.3.14ScalarbmConfigResHealthWarnThresholdread-writemandatoryBattery resistance health warn threshold, unit in percentage and should larger than 100.
1.3.6.1.4.1.3808.1.1.7.4NodebmControl
1.3.6.1.4.1.3808.1.1.7.4.1ScalarbmControlSysytemIdenticatorread-writemandatoryBattery manager will perform a panel indicator test when the variable is set to testIndicators(2). Get this oid will get noTestIndicators(1).
1.3.6.1.4.1.3808.1.1.7.4.2ScalarbmControlProbeIndicatorread-writemandatoryBattery manager will perform a probe indicator test when the variable is set to testIndicators(2). Get this oid will get noTestIndicators(1).
1.3.6.1.4.1.3808.1.1.7.5NodebmProbes
1.3.6.1.4.1.3808.1.1.7.5.1ScalarbmProbesNumread-onlymandatoryCurrent connected probe number.
1.3.6.1.4.1.3808.1.1.7.5.2ScalarbmProbesTableSizeread-onlymandatoryCurrent configured probe number.
1.3.6.1.4.1.3808.1.1.7.5.3TablebmProbesTablenot-accessiblemandatoryAllows for getting of status of probes.
1.3.6.1.4.1.3808.1.1.7.5.3.1RowbmProbesEntrynot-accessiblemandatoryThe status of probes installation to gather status from.
1.3.6.1.4.1.3808.1.1.7.5.3.1.1ColumnbmProbesIndexread-onlymandatoryProbes table index
1.3.6.1.4.1.3808.1.1.7.5.3.1.2ColumnbmProbesPackIndexread-onlymandatoryThe battery pack number the probe installed.
1.3.6.1.4.1.3808.1.1.7.5.3.1.3ColumnbmProbesStringIndexread-onlymandatoryThe string number the probe installed.
1.3.6.1.4.1.3808.1.1.7.5.3.1.4ColumnbmProbesBattIndexread-onlymandatoryThe battery number the probe installed.
1.3.6.1.4.1.3808.1.1.7.5.4ScalarbmProbesVoltageTableSizeread-onlymandatoryThe size of the battery voltage table
1.3.6.1.4.1.3808.1.1.7.5.5TablebmProbesVoltageTablenot-accessiblemandatoryAllows for getting of voltage of batteries.
1.3.6.1.4.1.3808.1.1.7.5.5.1RowbmProbesVoltageEntrynot-accessiblemandatoryBatteries voltage status.
1.3.6.1.4.1.3808.1.1.7.5.5.1.1ColumnbmProbesVoltageIndexread-onlymandatoryThe index of the voltage status entry.
1.3.6.1.4.1.3808.1.1.7.5.5.1.2ColumnbmProbesVoltagePackIndexread-onlymandatoryThe battery pack index to the voltage record.
1.3.6.1.4.1.3808.1.1.7.5.5.1.3ColumnbmProbesVoltageStringIndexread-onlymandatoryThe battery string index to the voltage record.
1.3.6.1.4.1.3808.1.1.7.5.5.1.4ColumnbmProbesVoltageBattIndexread-onlymandatoryThe battery index to the voltage record within its string.
1.3.6.1.4.1.3808.1.1.7.5.5.1.5ColumnbmProbesVoltageProbeIndexread-onlymandatoryThe probe index to the voltage record.
1.3.6.1.4.1.3808.1.1.7.5.5.1.6ColumnbmProbesVoltageAlarmStatusread-onlymandatoryThe battery voltage alarm status.
1.3.6.1.4.1.3808.1.1.7.5.5.1.7ColumnbmProbesVoltageread-onlymandatoryGetting this oid to get battery voltage, unit in 0.01 volt.
1.3.6.1.4.1.3808.1.1.7.5.5.1.8ColumnbmProbesVoltageEqualPercentageread-onlymandatoryGetting this oid to get battery voltage equalizing power, unit in percentage.
1.3.6.1.4.1.3808.1.1.7.5.6ScalarbmProbesTempTableSizeread-onlymandatoryThe size of the Temperature table
1.3.6.1.4.1.3808.1.1.7.5.7TablebmProbesTempTablenot-accessiblemandatoryAllows for getting of temperature of probes.
1.3.6.1.4.1.3808.1.1.7.5.7.1RowbmProbesTempEntrynot-accessiblemandatoryTemperature status entry.
1.3.6.1.4.1.3808.1.1.7.5.7.1.1ColumnbmProbesTempIndexread-onlymandatoryThe index of the temperature entry.
1.3.6.1.4.1.3808.1.1.7.5.7.1.2ColumnbmProbesTempPackIndexread-onlymandatoryThe battery pack index of the temperature entry.
1.3.6.1.4.1.3808.1.1.7.5.7.1.3ColumnbmProbesTempStringIndexread-onlymandatoryThe index to the string.
1.3.6.1.4.1.3808.1.1.7.5.7.1.4ColumnbmProbesTempBattIndexread-onlymandatoryThe index to the battery.
1.3.6.1.4.1.3808.1.1.7.5.7.1.5ColumnbmProbesTempProbeIndexread-onlymandatoryThe index to the probe.
1.3.6.1.4.1.3808.1.1.7.5.7.1.6ColumnbmProbesTempAlarmStatusread-onlymandatoryThe alarm status of the temperature.
1.3.6.1.4.1.3808.1.1.7.5.7.1.7ColumnbmProbesTemperatureread-onlymandatoryThe temperature record, measure in 0.1 degree C.
1.3.6.1.4.1.3808.1.1.7.5.8ScalarbmProbesResTableSizeread-onlymandatoryThe size of the Resistance table
1.3.6.1.4.1.3808.1.1.7.5.9TablebmProbesResTablenot-accessiblemandatoryAllows for getting of resistance of probes.
1.3.6.1.4.1.3808.1.1.7.5.9.1RowbmProbesResEntrynot-accessiblemandatoryThe resistance status entry.
1.3.6.1.4.1.3808.1.1.7.5.9.1.1ColumnbmProbesResIndexread-onlymandatoryThe index of the resistance entry.
1.3.6.1.4.1.3808.1.1.7.5.9.1.2ColumnbmProbesResPackIndexread-onlymandatoryThe battery pack index to the resistance entry.
1.3.6.1.4.1.3808.1.1.7.5.9.1.3ColumnbmProbesResStringIndexread-onlymandatoryThe index to the string.
1.3.6.1.4.1.3808.1.1.7.5.9.1.4ColumnbmProbesResBattIndexread-onlymandatoryThe index to the battery.
1.3.6.1.4.1.3808.1.1.7.5.9.1.5ColumnbmProbesResProbeIndexread-onlymandatoryThe index to the probe.
1.3.6.1.4.1.3808.1.1.7.5.9.1.6ColumnbmProbesResAlarmStatusread-onlymandatoryThe alarm status of the battery resistance.
1.3.6.1.4.1.3808.1.1.7.5.9.1.7ColumnbmProbesResistanceread-onlymandatoryThe resistance of the battery, unit in 0.01 mOhm.
1.3.6.1.4.1.3808.1.1.7.5.9.1.8ColumnbmProbesResHealthread-onlymandatoryThe resistance health status, unit in percentage.
1.3.6.1.4.1.3808.1.1.7.6NodebmFuncRes
1.3.6.1.4.1.3808.1.1.7.6.1NodebmFuncResMeasure
1.3.6.1.4.1.3808.1.1.7.6.1.1ScalarbmFuncResMeasureIntervalread-writemandatoryThe time interval for battery manager to exercising resistance measurement, unit in hour(s).
1.3.6.1.4.1.3808.1.1.7.6.1.2ScalarbmFuncResMeasureManualCmdread-writemandatoryThis oid allows user to manual resistance measurement. Set this oid to measureResNow(2) to measure resistance immediately. Get bmFuncResMeasureLastCmdResult oi…
1.3.6.1.4.1.3808.1.1.7.6.1.3ScalarbmFuncResMeasureManualResultread-onlymandatoryGet this oid to confirm the last manual command result.
1.3.6.1.4.1.3808.1.1.7.6.1.4ScalarbmFuncResMeasureLastUpdateread-onlymandatoryWhen resistance measurement complete either by auto or manual, this oid will update to the last update time.
1.3.6.1.4.1.3808.1.1.7.7NodebmFuncEqual
1.3.6.1.4.1.3808.1.1.7.7.1ScalarbmFuncEqualEnableread-writemandatoryBattery voltage equalization configuration.
1.3.6.1.4.1.3808.1.1.7.7.2ScalarbmFuncEqualActiveCondread-writemandatoryVolatge equalization will active when the voltage difference larger than this value, unit in 10mV.
1.3.6.1.4.1.3808.1.1.7.7.3ScalarbmFuncEqualStatusread-onlymandatoryThis oid shows the current equalization status.
1.3.6.1.4.1.3808.1.1.7.7.4ScalarbmFuncEqualStartTimeread-onlymandatoryThis oid shows the last equalization start time.
1.3.6.1.4.1.3808.1.1.7.7.5ScalarbmFuncEqualElapseTimeread-onlymandatoryThis oid shows the elapsed time since last equalization started.
1.3.6.1.4.1.3808.2Nodecpsmgmt
1.3.6.1.4.1.3808.2NodeupsOverloadSEVERE: The UPS has sensed an overload condition.
1.3.6.1.4.1.3808.2.1Nodemconfig
1.3.6.1.4.1.3808.2.1.1ScalarmconfigNumTrapAcceptersread-onlymandatoryThe number of receivers to send traps to.
1.3.6.1.4.1.3808.2.1.2TablemconfigTrapAccepterTablenot-accessiblemandatoryA list of receivers to send traps to. The numbers of entries are given by the value of mconfigNumTrapAccepters.
1.3.6.1.4.1.3808.2.1.2.1RowmconfigTrapAccepterEntrynot-accessiblemandatoryThe receivers to send traps to.
1.3.6.1.4.1.3808.2.1.2.1.1ColumntrapIndexnot-accessiblemandatoryThe trap receiver entry index.
1.3.6.1.4.1.3808.2.1.2.1.2ColumnaccepterAddrread-writemandatoryThe trap receiver IP address.
1.3.6.1.4.1.3808.2.1.2.1.3ColumncommunityStringread-writemandatoryThe trap receiver community name.
1.3.6.1.4.1.3808.2.1.2.1.4ColumnseverityDegreeread-onlymandatoryThe trap receiver severity level. Traps are marked in severity level as informational(1), warning(2), severe(3). Only send the traps of equal or greater severi…
1.3.6.1.4.1.3808.2.1.2.1.5ColumnaccepterActiveread-writemandatoryA receiver will accept traps if yes, and none if no.
1.3.6.1.4.1.3808.2.1.3ScalarmconfigDHCPEnabledread-writemandatoryThe system will automatically obtain its IP from a DHCP server if yes, and none if no.
1.3.6.1.4.1.3808.2.1.4ScalarmconfigMyAddrread-onlymandatoryThe system IP address.
1.3.6.1.4.1.3808.2.1.5NodemconfigClock
1.3.6.1.4.1.3808.2.1.5.1ScalarmconfigClockDateread-writemandatoryThe current date in the mm/dd/yyyy format. Example: 01/01/2000.
1.3.6.1.4.1.3808.2.1.5.2ScalarmconfigClockTimeread-writemandatoryThe current time in the hh:mm:ss 24H format.
1.3.6.1.4.1.3808.2.2Nodemtrapinfo
1.3.6.1.4.1.3808.2.2.1ScalarmtrapinfoIntegerread-onlymandatoryAllow CPS traps with an integer argument for providing detail information. Not being defined in the MIB, only reply 0.
1.3.6.1.4.1.3808.2.2.2ScalarmtrapinfoIpAddressread-onlymandatoryAllow CPS traps with an IP address argument for providing detail information. Not being defined in the MIB, only reply 0.0.0.0.
1.3.6.1.4.1.3808.2.2.3ScalarmtrapinfoStringread-onlymandatoryAllow CPS traps with an octet string argument for providing detail information. Not being defined in the MIB, only reply a NULL string.
1.3.6.1.4.1.3808.2.2.4ScalarmtrapinfoGaugeread-onlymandatoryAllow CPS traps with an Gauge argument for providing detail information. Not being defined in the MIB, only reply 0.
1.3.6.1.4.1.3808.2.2.5ScalarmtrapinfoTimeTicksread-onlymandatoryAllow CPS traps with an TimeTicks argument for providing detail information. Not being defined in the MIB, only reply 0.
1.3.6.1.4.1.3808.2.2.6ScalarmtrapinfoBmEventIdread-onlymandatoryAllow CPS traps with an integer argument for providing detail information about Battery Manager specific event identifier. Not being defined in the MIB, only r…
1.3.6.1.4.1.3808.2.3Nodemcontrol
1.3.6.1.4.1.3808.2.3.1ScalarmcontrolRestartread-writemandatorySetting this OID to restartCurrentSystem (2) will restart the current system. Setting this OID to restartCurrentAgent (3) will restart the current agent. Setti…
1.3.6.1.4.1.3808.2.3.2ScalarmcontrolResetread-writemandatorySetting this OID to resetCurrentSystem (2) will reset the current system. Setting this OID to resetCurrentAgent (3) will reset the current agent. Setting this …
1.3.6.1.4.1.3808.3NodeupsDiagnosticsFailedSEVERE: The UPS battery test failed.
1.3.6.1.4.1.3808.4NodeupsDischargedSEVERE: The UPS has started a runtime calibration process.
1.3.6.1.4.1.3808.5NodeupsOnBatteryWARNING: Utility power failed, transfer to backup mode.
1.3.6.1.4.1.3808.6NodeupsBoostOnWARNING: The UPS has enabled boost, low utility voltage.
1.3.6.1.4.1.3808.7NodelowBatterySEVERE: The UPS battery capacity is low than threshold, soon to be exhausted.
1.3.6.1.4.1.3808.8NodecommunicationEstablishedINFORMATIONAL: Communication to the UPS has been established.
1.3.6.1.4.1.3808.9NodepowerRestoredINFORMATIONAL: Utility power restored, return from backup mode.
1.3.6.1.4.1.3808.10NodeupsDiagnosticsPassedINFORMATIONAL: The UPS battery test passed.
1.3.6.1.4.1.3808.11NodereturnFromLowBatteryINFORMATIONAL: The UPS has returned from a low battery condition.
1.3.6.1.4.1.3808.12NodeupsTurnedOffWARNING: The UPS has been turned off.
1.3.6.1.4.1.3808.13NodeupsSleepingWARNING: The UPS entered sleep mode. Output power will not be provided.
1.3.6.1.4.1.3808.14NodeupsWokeUpINFORMATION: The UPS woke up from sleep mode. Output power is being provided.
1.3.6.1.4.1.3808.15NodeupsRebootStartedWARNING: The UPS started reboot sequence.
1.3.6.1.4.1.3808.16NodeupsOverTempSEVERE: The UPS inner temperature is too high.
1.3.6.1.4.1.3808.17NodereturnFromOverTempINFORMATIONAL: The UPS over temperature condition cleared.
1.3.6.1.4.1.3808.18NodeupsBuckOnWARNING: The UPS has enabled buck, high utility voltage.
1.3.6.1.4.1.3808.19NodereturnFromOverLoadINFORMATIONAL: The UPS has returned from an overload condition.
1.3.6.1.4.1.3808.20NodereturnFromDischargedINFORMATIONAL: The UPS runtime calibration completed.
1.3.6.1.4.1.3808.21NodeupsScheduleShutdownWARNING: The UPS has started its schedule shutdown sequence.
1.3.6.1.4.1.3808.22NodeupsEnterSleepWARNING: The UPS started sleep sequence.
1.3.6.1.4.1.3808.23NodeupsChargerFailureWARNING: The battery charger is abnormal.
1.3.6.1.4.1.3808.24NodereturnFromChargerFailureINFORMATIONAL: The charger returned from a failure condition.
1.3.6.1.4.1.3808.25NodeupsTurnoffStartedWARNING: The UPS started turn off sequence.
1.3.6.1.4.1.3808.26NodeupsTurnedOnWARNING: The UPS has been turned on.
1.3.6.1.4.1.3808.27NodeupsRemoteCommandFailedWARNING: The UPS remote command failed.
1.3.6.1.4.1.3808.29NodeupsSignalClientShutdownSEVERE: The UPS has signaled clients to shutdown.
1.3.6.1.4.1.3808.31NodenclBankOnINFORMATIONAL: Non-Critical bank has been turned on.
1.3.6.1.4.1.3808.32NodenclBankOffINFORMATIONAL: Non-Critical bank has been turned off.
1.3.6.1.4.1.3808.33NodeupsCommandCancelINFORMATION: The cancel command has been executed.
1.3.6.1.4.1.3808.34NodeupsStartBatteryTestINFORMATION: The UPS has started a battery test process.
1.3.6.1.4.1.3808.35NodeupsRemainRuntimeLowThanThresholdWARNING: The UPS remaining runtime is lower than threshold.
1.3.6.1.4.1.3808.36NodenclBankStartScheduleOffINFORMATION: Non-Critial bank has started its schedule off sequence.
1.3.6.1.4.1.3808.37NodeupsCalibrationAbortWARNING: The UPS runtime calibration aborted.
1.3.6.1.4.1.3808.38NodeupsHardwareFaultWARNING: The UPS hardware fault.
1.3.6.1.4.1.3808.39NodeupsBatteryNotPresentWARNING: Battery is not present.
1.3.6.1.4.1.3808.40NodeupsWiringFaultWARNING: The UPS wiring fault has been detected.
1.3.6.1.4.1.3808.41NodeupsWiringFaultClearedINFORMATION: The UPS wiring fault has been cleared.
1.3.6.1.4.1.3808.42NodeupsEnterBypassModeWARNING: The UPS enters bypass mode.
1.3.6.1.4.1.3808.43NodeupsReturnFromBypassModeINFORMATION: The UPS leaves bypass mode.
1.3.6.1.4.1.3808.44NodeupsBypassOverloadWARNING: The UPS bypass overload.
1.3.6.1.4.1.3808.45NodeupsBypassOverloadClearedINFORMATION: The UPS bypass overload has been cleared.
1.3.6.1.4.1.3808.46NodeupsEnterECOModeWARNING: The UPS enters ECO mode.
1.3.6.1.4.1.3808.47NodeupsReturnFromECOModeWARNING: The UPS leaves ECO mode.
1.3.6.1.4.1.3808.48NodeupsBatteryOverThreeYearWARNING: Battery has been 3 years from last Replacement.
1.3.6.1.4.1.3808.61NodefailAuthViaHTTPWARNING: Login authorization failure via HTTP.
1.3.6.1.4.1.3808.62NodepasswordChangeINFORMATION: The password has been changed.
1.3.6.1.4.1.3808.63NodefailAuthViaConsoleWARNING: Login authorization failure via Console.
1.3.6.1.4.1.3808.64NodeconfigFileUploadINFORMATION: Configuration file uploaded.
1.3.6.1.4.1.3808.65NodeadminLoginInfoINFORMATION: Administrator login.
1.3.6.1.4.1.3808.66NodeadminLogoutInfoINFORMATION: Administrator logout.
1.3.6.1.4.1.3808.67NodedeviceLoginInfoINFORMATION: Device login.
1.3.6.1.4.1.3808.68NodedeviceLogoutInfoINFORMATION: Device logout.
1.3.6.1.4.1.3808.69NodeconfigurationChangedINFORMATION: Configuration has been changed.
1.3.6.1.4.1.3808.70NodeclientRegisteredInformation: PowerPanel client has been registered.
1.3.6.1.4.1.3808.71NodeclientRemovedInformation: PowerPanel client has been removed.
1.3.6.1.4.1.3808.72NodetestEventInformation: Test Event.
1.3.6.1.4.1.3808.73NodeoutletUserLoginInfoInformation: Outlet User login.
1.3.6.1.4.1.3808.74NodeoutletUserLogoutInfoInformation: Outlet User logout.
1.3.6.1.4.1.3808.100NodeePDUCommunicationEstablishedINFORMATIONAL: Communication with a Rack PDU has been established. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.3808.101NodeePDUCommunicationLostSEVERE: Communication with a Rack PDU has been lost. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.3808.102NodeePDUOutletOnINFORMATIONAL: An outlet on a Switched Rack PDU has turned on. The first argument is the serial number. The second argument is the device name. The third argum…
1.3.6.1.4.1.3808.103NodeePDUOutletOffINFORMATIONAL: An outlet on a Switched Rack PDU has turned off. The first argument is the serial number. The second argument is the device name. The third argu…
1.3.6.1.4.1.3808.104NodeePDUDeviceConfigChangeINFORMATIONAL: A device configuration change has been made on a Rack PDU. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.3808.105NodeePDUOutletConfigChangeINFORMATIONAL: An outlet configuration change has been made on a Switched Rack PDU. The first argument is the serial number. The second argument is the device …
1.3.6.1.4.1.3808.106NodeePDULowLoadWARNING: A Rack PDU has violated the low load threshold. The first argument is the serial number. The second argument is the device name. The third argument is…
1.3.6.1.4.1.3808.107NodeePDULowLoadClearedINFORMATIONAL: The low load condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The thir…
1.3.6.1.4.1.3808.108NodeePDUNearOverloadWARNING: A Rack PDU is near an overload condition. The first argument is the serial number. The second argument is the device name. The third argument is the p…
1.3.6.1.4.1.3808.109NodeePDUNearOverloadClearedINFORMATIONAL: The near overload condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The…
1.3.6.1.4.1.3808.110NodeePDUOverloadSEVERE: A Rack PDU is in an overload condition. The first argument is the serial number. The second argument is the device name. The third argument is the phas…
1.3.6.1.4.1.3808.111NodeePDUOverloadClearedINFORMATIONAL: The overload condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The thir…
1.3.6.1.4.1.3808.112NodeePDUDelayOutletOnCommandINFORMATIONAL: An outlet on a Switched Rack PDU has been assigned to turn on. The first argument is the serial number. The second argument is the device name. …
1.3.6.1.4.1.3808.113NodeePDUDelayOutletOffCommandINFORMATIONAL: An outlet on a Switched Rack PDU has been assigned to turn off. The first argument is the serial number. The second argument is the device name.…
1.3.6.1.4.1.3808.114NodeePDUDelayOutletRebootCommandINFORMATIONAL: An outlet on a Switched Rack PDU has been assigned to reboot. The first argument is the serial number. The second argument is the device name. T…
1.3.6.1.4.1.3808.115NodeePDUCancelPendingCommandINFORMATIONAL: A cancel pending command has been made on a Switched Rack PDU. The first argument is the serial number. The second argument is the device name. …
1.3.6.1.4.1.3808.116NodeePDULineUndervoltageSEVERE: Utility Line Undervoltage The first argument is the serial number. The second argument is the device name. The third argument is the phase number.
1.3.6.1.4.1.3808.117NodeePDULineUndervoltageClearedINFORMATIONAL: Utility Line Undervoltage Cleared. The first argument is the serial number. The second argument is the device name. The third argument is the ph…
1.3.6.1.4.1.3808.118NodeePDULineOvervoltageSEVERE: Utility Line Overvoltage. The first argument is the serial number. The second argument is the device name. The third argument is the phase number.
1.3.6.1.4.1.3808.119NodeePDULineOvervoltageClearedINFORMATIONAL: Utility Line Overvoltage Cleared. The first argument is the serial number. The second argument is the device name. The third argument is the pha…
1.3.6.1.4.1.3808.120NodeePDUPowerSupply1FailSEVERE: Power Supply 1 on Rack PDU is in FAIL state. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.3808.121NodeePDUPowerSupply1OkINFORMATIONAL: Power Supply 1 on Rack PDU is operating normally. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.3808.122NodeePDUPowerSupply2FailSEVERE: Power Supply 2 on Rack PDU is in FAIL state. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.3808.123NodeePDUPowerSupply2OkINFORMATIONAL: Power Supply 2 on Rack PDU is operating normally. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.3808.124NodeePDUBankLowLoadWARNING: A Rack PDU bank has violated the low load threshold. The first argument is the serial number. The second argument is the device name. The third argume…
1.3.6.1.4.1.3808.125NodeePDUBankLowLoadClearedINFORMATIONAL: The low load condition on a Rack PDU bank has been cleared. The first argument is the serial number. The second argument is the device name. The…
1.3.6.1.4.1.3808.126NodeePDUBankNearOverloadWARNING: A Rack PDU bank is near an overload condition. The first argument is the serial number. The second argument is the device name. The third argument is …
1.3.6.1.4.1.3808.127NodeePDUBankNearOverloadClearedINFORMATIONAL: The near overload condition on a Rack PDU bank has been cleared. The first argument is the serial number. The second argument is the device name…
1.3.6.1.4.1.3808.128NodeePDUBankOverloadSEVERE: A Rack PDU bank is in an overload condition. The first argument is the serial number. The second argument is the device name. The third argument is the…
1.3.6.1.4.1.3808.129NodeePDUBankOverloadClearedINFORMATIONAL: The overload condition on a Rack PDU bank has been cleared. The first argument is the serial number. The second argument is the device name. The…
1.3.6.1.4.1.3808.130NodeePDUComponentCommunicationEstablishedINFORMATIONAL: Component communication lost has been cleared. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.3808.131NodeePDUComponentCommunicationLostSEVERE: Component communication lost. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.3808.132NodeePDUOutletLowLoadWARNING: A Rack PDU has violated the outlet low load threshold. The first argument is the serial number. The second argument is the device name. The third argu…
1.3.6.1.4.1.3808.133NodeePDUOutletLowLoadClearedINFORMATIONAL: The outlet low load condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. T…
1.3.6.1.4.1.3808.134NodeePDUOutletNearOverloadWARNING: A Rack PDU is near an outlet overload condition. The first argument is the serial number. The second argument is the device name. The third argument i…
1.3.6.1.4.1.3808.135NodeePDUOutletNearOverloadClearedINFORMATIONAL: The outlet near overload condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device na…
1.3.6.1.4.1.3808.136NodeePDUOutletOverloadSEVERE: A Rack PDU is in an overload condition. The first argument is the serial number. The second argument is the device name. The third argument is the outl…
1.3.6.1.4.1.3808.137NodeePDUOutletOverloadClearedINFORMATIONAL: The outlet overload condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. T…
1.3.6.1.4.1.3808.200NodeenvHighTemperatureViolationWARNING: The environment high temperature threshold has been violated.
1.3.6.1.4.1.3808.201NodeenvHighTemperatureBackINFORMATION: The environment temperature returned from high value.
1.3.6.1.4.1.3808.202NodeenvLowTemperatureViolationWARNING: The environment low temperature threshold has been violated.
1.3.6.1.4.1.3808.203NodeenvLowTempBackINFORMATION: The environment temperature returned from low value.
1.3.6.1.4.1.3808.204NodeenvHighHumidityViolationWARNING: The environment high humidity threshold has been violated.
1.3.6.1.4.1.3808.205NodeenvHighHumidityBackINFORMATION: The environment humidity return from high value.
1.3.6.1.4.1.3808.206NodeenvLowHumidityViolationWARNING: The environment low humidity threshold has been violated.
1.3.6.1.4.1.3808.207NodeenvLowHumdBackINFORMATION: The environment humidity return from low value.
1.3.6.1.4.1.3808.208NodeenvDryContactAbnormalINFORMATION: The Contact is abnormal.
1.3.6.1.4.1.3808.209NodeenvDryContactNormalINFORMATION: The Contact has returned from abnormal.
1.3.6.1.4.1.3808.210NodeenvConntectedINFORMATION: The Environment Sensor has been connected.
1.3.6.1.4.1.3808.211NodeenvDisconntectedINFORMATION: The Environment Sensor has been disconnected.
1.3.6.1.4.1.3808.212NodeenvRateOfTemperatureChangeAbnormalINFORMATION: The rate of temperature change is abnormal.
1.3.6.1.4.1.3808.213NodeenvRateOfHumdChangeAbnormalINFORMATION: The rate of humidity change is abnormal.
1.3.6.1.4.1.3808.301NodeatsSwitchSourceINFORMATIONAL: ATS has switched source. The first argument is the device name. The second argument is the serial number. The third argument is the selected sou…
1.3.6.1.4.1.3808.302NodeatsSourceFaultWARNING: Source fault occurs. The first argument is the device name. The second argument is the serial number. The third argument is the source name.
1.3.6.1.4.1.3808.303NodeatsSourceFaultClearedINFORMATIONAL: Source fault has been cleared. The first argument is the device name. The second argument is the serial number. The third argument is the source…
1.3.6.1.4.1.3808.304NodeatsRedundancyFailWARNING: Redundancy fails. The first argument is the device name. The second argument is the serial number. The third argument is the source name.
1.3.6.1.4.1.3808.305NodeatsRedundancyRestoredINFORMATIONAL: Redundancy has been restored. The first argument is the device name. The second argument is the serial number. The third argument is the source …
1.3.6.1.4.1.3808.306NodeatsInputHighVoltageWARNING: The upper voltage limit has been crossed. The first argument is the device name. The second argument is the serial number. The third argument is the s…
1.3.6.1.4.1.3808.307NodeatsInputHighVoltageClearedINFORMATIONAL: The upper voltage condition has been cleared. The first argument is the device name. The second argument is the serial number. The third argumen…
1.3.6.1.4.1.3808.308NodeatsInputLowVoltageWARNING: The lower voltage limit has been crossed. The first argument is the device name. The second argument is the serial number. The third argument is the s…
1.3.6.1.4.1.3808.309NodeatsInputLowVoltageClearedINFORMATIONAL: The lower voltage condition has been cleared. The first argument is the device name. The second argument is the serial number. The third argumen…
1.3.6.1.4.1.3808.310NodeatsInputHighFrequencyWARNING: The upper frequency limit has been crossed. The first argument is the device name. The second argument is the serial number. The third argument is the…
1.3.6.1.4.1.3808.311NodeatsInputHighFrequencyClearedINFORMATIONAL: The upper frequency condition has been cleared. The first argument is the device name. The second argument is the serial number. The third argum…
1.3.6.1.4.1.3808.312NodeatsInputLowFrequencyWARNING: The lower frequency limit has been crossed. The first argument is the device name. The second argument is the serial number. The third argument is the…
1.3.6.1.4.1.3808.313NodeatsInputLowFrequencyClearedINFORMATIONAL: The lower frequency condition has been cleared. The first argument is the device name. The second argument is the serial number. The third argum…
1.3.6.1.4.1.3808.314NodeatsCommunicationLostMAJOR: ATS communication lost. The first argument is the device name. The second argument is the serial number.
1.3.6.1.4.1.3808.315NodeatsCommunicationEstablishedINFORMATIONAL: ATS communication has been established. The first argument is the device name. The second argument is the serial number.
1.3.6.1.4.1.3808.316NodeatsLCDCommunicationLostWARNING: LCD communication lost. The first argument is the device name. The second argument is the serial number.
1.3.6.1.4.1.3808.317NodeatsLCDCommunicationLostClearedINFORMATIONAL: LCD communication lost has been cleared. The first argument is the device name. The second argument is the serial number.
1.3.6.1.4.1.3808.318NodeatsDB9CommunicationLostWARNING: DB9 communication lost. The first argument is the device name. The second argument is the serial number.
1.3.6.1.4.1.3808.319NodeatsDB9CommunicationLostClearedINFORMATIONAL: DB9 communication lost has been cleared. The first argument is the device name. The second argument is the serial number.
1.3.6.1.4.1.3808.320NodeatsPowerSupplyFaultCRITICAL: Power supply failure. The first argument is the device name. The second argument is the serial number. The third argument is the input source of the …
1.3.6.1.4.1.3808.321NodeatsPowerSupplyFaultClearedCRITICAL: Power supply failure. The first argument is the device name. The second argument is the serial number. The third argument is the input source of the …
1.3.6.1.4.1.3808.322NodeatsDevHardwareFaultCRITICAL: Device hardware failure. The first argument is the device name. The second argument is the serial number.
1.3.6.1.4.1.3808.323NodeatsDevHardwareFaultClearedINFORMATIONAL: Device hardware failure has been cleared. The first argument is the device name. The second argument is the serial number.
1.3.6.1.4.1.3808.324NodeatsSourceConfigChangedINFORMATIONAL: A source configuration change has been made. The first argument is the device name. The second argument is the serial number.
1.3.6.1.4.1.3808.325NodeatsDeviceConfigChangedINFORMATIONAL: A device configuration change has been made. The first argument is the device name. The second argument is the serial number.
1.3.6.1.4.1.3808.326NodeatsOutletConfigChangedINFORMATIONAL: A outlet configuration change has been made. The first argument is the device name. The second argument is the serial number.
1.3.6.1.4.1.3808.327NodeatsEventCountsClearedINFORMATIONAL: Event counts has been cleared. The first argument is the device name. The second argument is the serial number.
1.3.6.1.4.1.3808.328NodeatsOverloadWARNING: The load has exceeded overload threshold. The first argument is the device name. The second argument is the serial number. The third argument is the b…
1.3.6.1.4.1.3808.329NodeatsOverloadClearedINFORMATIONAL: The overload condition has been cleared. The first argument is the device name. The second argument is the serial number. The third argument is …
1.3.6.1.4.1.3808.330NodeatsNearOverloadWARNING: The load has exceeded near overload threshold. The first argument is the device name. The second argument is the serial number. The third argument is …
1.3.6.1.4.1.3808.331NodeatsNearOverloadClearedINFORMATIONAL: The near overload condition has beed cleared. The first argument is the device name. The second argument is the serial number. The third argumen…
1.3.6.1.4.1.3808.332NodeatsLowLoadWARNING: The load has been lower than low load threshold. The first argument is the device name. The second argument is the serial number. The third argument i…
1.3.6.1.4.1.3808.333NodeatsLowLoadClearedINFORMATIONAL: The low load condition has been cleared. The first argument is the device name. The second argument is the serial number. The third argument is …
1.3.6.1.4.1.3808.334NodeatsOutletOnCommandINFORMATIONAL: An outlet on ATS has been assigned to turn on. The first argument is the device name. The second argument is the serial number. The third argume…
1.3.6.1.4.1.3808.335NodeatsOutletOffCommandINFORMATIONAL: An outlet on ATS has been assigned to turn off. The first argument is the serial number. The second argument is the device name. The third argum…
1.3.6.1.4.1.3808.336NodeatsOutletRebootCommandINFORMATIONAL: An outlet on ATS has been assigned to reboot. The first argument is the serial number. The second argument is the device name. The third argumen…
1.3.6.1.4.1.3808.337NodeatsCancelPendingCommandINFORMATIONAL: A cancel pending command has been made on ATS. The first argument is the serial number. The second argument is the device name. The third argume…
1.3.6.1.4.1.3808.338NodeatsOutletOnINFORMATIONAL: An outlet on ATS has turned on. The first argument is the serial number. The second argument is the device name. The third argument is the outle…
1.3.6.1.4.1.3808.339NodeatsOutletOffINFORMATIONAL: An outlet on ATS has turned off. The first argument is the serial number. The second argument is the device name. The third argument is the outl…
1.3.6.1.4.1.3808.400NodepduDeviceEventINFORMATIONAL: A PDU device event has been happened. The first argument is the serial number. The second argument is the device name. The third argument is the…
1.3.6.1.4.1.3808.401NodepduDeviceAlarmAlarm: A PDU device alarm has been detected. The first argument is the serial number. The second argument is the device name. The third argument is the device …
1.3.6.1.4.1.3808.402NodepduDeviceAlarmClearINFORMATIONAL: A PDU device alarm has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the …
1.3.6.1.4.1.3808.403NodepduPhaseEventINFORMATIONAL: A PDU phase event has been happened. The first argument is the serial number. The second argument is the device name. The third argument is the …
1.3.6.1.4.1.3808.404NodepduPhaseAlarmAlarm: A PDU phase alarm has been detected. The first argument is the serial number. The second argument is the device name. The third argument is the phase ta…
1.3.6.1.4.1.3808.405NodepduPhaseAlarmClearINFORMATIONAL: A PDU phase alarm has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the p…
1.3.6.1.4.1.3808.406NodepduBankEventINFORMATIONAL: A PDU bank event has been happened. The first argument is the serial number. The second argument is the device name. The third argument is the b…
1.3.6.1.4.1.3808.407NodepduBankAlarmAlarm: A PDU bank alarm has been detected. The first argument is the serial number. The second argument is the device name. The third argument is the bank tabl…
1.3.6.1.4.1.3808.408NodepduBankAlarmClearINFORMATIONAL: A PDU bank alarm has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the ba…
1.3.6.1.4.1.3808.409NodepduOutletSwitchedEventINFORMATIONAL: A PDU switched outlet event has been happened. The first argument is the serial number. The second argument is the device name. The third argume…
1.3.6.1.4.1.3808.410NodepduOutletSwitchedAlarmAlarm: A PDU switched outlet alarm has been detected. The first argument is the serial number. The second argument is the device name. The third argument is th…
1.3.6.1.4.1.3808.411NodepduOutletSwitchedAlarmClearINFORMATIONAL: A PDU switched outlet alarm has been cleared. The first argument is the serial number. The second argument is the device name. The third argumen…
1.3.6.1.4.1.3808.412NodepduOutletMeteredEventINFORMATIONAL: A PDU metered outlet event has been happened. The first argument is the serial number. The second argument is the device name. The third argumen…
1.3.6.1.4.1.3808.413NodepduOutletMeteredAlarmAlarm: A PDU metered outlet alarm has been detected. The first argument is the serial number. The second argument is the device name. The third argument is the…
1.3.6.1.4.1.3808.414NodepduOutletMeteredAlarmClearINFORMATIONAL: A PDU metered outlet alarm has been cleared. The first argument is the serial number. The second argument is the device name. The third argument…
1.3.6.1.4.1.3808.415NodepduDaisyChainEventINFORMATIONAL: A PDU daisy-chain event has been happened. The first argument is the host serial number. The second argument is the host device name. The third …
1.3.6.1.4.1.3808.416NodepduDaisyChainAlarmAlarm: A PDU daisy-chain alarm has been detected. The first argument is the host serial number. The second argument is the host device name. The third argument…
1.3.6.1.4.1.3808.417NodepduDaisyChainAlarmClearINFORMATIONAL: A PDU daisy-chain alarm has been cleared. The first argument is the host serial number. The second argument is the host device name. The third a…
1.3.6.1.4.1.3808.600NodebmSystemAlarmALARM: System alarm occurance. The first argument is the bm device serial number. The second argument is the bm system identification name. The third argument …
1.3.6.1.4.1.3808.601NodebmSystemWarningWARNING: System warning occurance. The first argument is the bm device serial number. The second argument is the bm system identification name. The third argum…
1.3.6.1.4.1.3808.602NodebmSystemInfoINFO: System information. The first argument is the bm device serial number. The second argument is the bm system identification name. The third argument is th…
1.3.6.1.4.1.3808.603NodebmProbesAlarmALARM: Probe alarm event. The first argument is the bm device serial number. The second argument is the bm system identification name. The third argument is th…
1.3.6.1.4.1.3808.604NodebmSProbesWarningWARNING: Probe warning event. The first argument is the bm device serial number. The second argument is the bm system identification name. The third argument i…
1.3.6.1.4.1.3808.605NodebmProbesInfoINFO: Probe information. The first argument is the bm device serial number. The second argument is the bm system identification name. The third argument is the…