MIB Viewer

CYCLADES-ACS5K-PM-MIB

114 objects
This module defines objects of the Proxy for PM
OIDNameAccessStatusDescription
1.3.6.1.4.1.2925.8.5IdentitycyACS5KPMThis module defines objects of the Proxy for PM
1.3.6.1.4.1.2925.8.5.1ScalarcyNumberOfPMread-onlycurrentThe total number of PM's connected on the unit
1.3.6.1.4.1.2925.8.5.2TablecyPMTablenot-accessiblecurrentAllows to read information about each connected PM
1.3.6.1.4.1.2925.8.5.2.1RowcyPMEntrynot-accessiblecurrentInformation about the connected PM
1.3.6.1.4.1.2925.8.5.2.1.1ColumncyPMSerialPortNumberread-onlycurrentThe number of the serial port when the PM is connected.
1.3.6.1.4.1.2925.8.5.2.1.2ColumncyPMNumberOutletsread-onlycurrentNumber of outlets.
1.3.6.1.4.1.2925.8.5.2.1.3ColumncyPMNumberUnitsread-onlycurrentTotal number of PM unists that are accessed by this serial port.
1.3.6.1.4.1.2925.8.5.2.1.4ColumncyPMCurrentread-onlycurrentCurrent reading for the PM.
1.3.6.1.4.1.2925.8.5.2.1.5ColumncyPMVersionread-onlycurrentThe software version of the PM.
1.3.6.1.4.1.2925.8.5.2.1.7ColumncyPMCommandread-writecurrentA character string for the user to send commands to PM. He can use it to does the save command. Or to list the outlets that need to be turned off, or turned on…
1.3.6.1.4.1.2925.8.5.3TablecyPMUnitTablenot-accessiblecurrentAllow operations on specific PM unit connected
1.3.6.1.4.1.2925.8.5.3.1RowcyPMUnitEntrynot-accessiblecurrentAllow operations on outlet
1.3.6.1.4.1.2925.8.5.3.1.1ColumncyPMUnitNumbernot-accessiblecurrentThe number of the PM unit in the daisy-chained mode.
1.3.6.1.4.1.2925.8.5.3.1.2ColumncyPMUnitVersionread-onlycurrentThe software version of this PM unit.
1.3.6.1.4.1.2925.8.5.3.1.3ColumncyPMUnitOutletsread-onlycurrentNumber of outlets of this PM unit.
1.3.6.1.4.1.2925.8.5.3.1.4ColumncyPMUnitFirstOutletread-onlycurrentNumber of the first outlet of this PM unit.
1.3.6.1.4.1.2925.8.5.3.1.5ColumncyPMUnitCurrentread-onlycurrentCurrent of this PM unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the curre…
1.3.6.1.4.1.2925.8.5.3.1.6ColumncyPMUnitMaxCurrentread-onlycurrentMaximum current of this PM unit in AMP. The value of this object is the maximum current in AMP * 10. You need to translate the readed value (Ex. : value is 5, …
1.3.6.1.4.1.2925.8.5.3.1.9ColumncyPMUnitSequenceIntervalread-onlycurrentSequence interval delay. Valid values are 2 to 15 (seconds).
1.3.6.1.4.1.2925.8.5.3.1.10ColumncyPMUnitCycleIntervalread-onlycurrentNumber of seconds that a socket stays off before turning it back on.
1.3.6.1.4.1.2925.8.5.3.1.11ColumncyPMUnitIDread-onlycurrentPDU identification.
1.3.6.1.4.1.2925.8.5.3.1.12ColumncyPMUnitPhasesread-onlycurrentNumber of phases of this PDU unit.
1.3.6.1.4.1.2925.8.5.3.1.13ColumncyPMUnitBanksread-onlycurrentNumber of banks of this PDU unit.
1.3.6.1.4.1.2925.8.5.3.1.14ColumncyPMUnitNominalVoltageread-onlycurrentNominal Voltage configured for this PDU unit, when it does not have voltage sensor
1.3.6.1.4.1.2925.8.5.3.1.15ColumncyPMUnitPowerread-onlycurrentPower Consumption of this PDU unit (it is estimated when PDU does not have voltage sensor).
1.3.6.1.4.1.2925.8.5.4TablecyOutletTablenot-accessiblecurrentAllow operations on outlet
1.3.6.1.4.1.2925.8.5.4.1RowcyOutletEntrynot-accessiblecurrentAllow operations on outlet
1.3.6.1.4.1.2925.8.5.4.1.1ColumncyOutletNumbernot-accessiblecurrentThe outlet number on the PM. Zero is ALL outlets.
1.3.6.1.4.1.2925.8.5.4.1.2ColumncyOutletNameread-writecurrentThe name given to a particular outlet Maximum size is 8 characters.
1.3.6.1.4.1.2925.8.5.4.1.3ColumncyOutletServerread-onlycurrentAlias of the Server connected to this outlet .
1.3.6.1.4.1.2925.8.5.4.1.4ColumncyOutletPowerread-writecurrentGetting this object will return the power state of the outlet. Valid return states are UNKNOW, OFF and ON. Setting this object will change the power state of t…
1.3.6.1.4.1.2925.8.5.4.1.5ColumncyOutletLockread-writecurrentGetting this object will return the lock state of the outlet. Setting this object will change the lock state of the outlet.
1.3.6.1.4.1.2925.8.5.4.1.6ColumncyOutletPUIntervalread-writecurrentThe power unit interval of this outlet in seconds. The value of this object is the actual interval in seconds * 10. You need to translate the readed value (Ex.…
1.3.6.1.4.1.2925.8.5.4.1.7ColumncyOutletMinimumOnIntervalread-onlycurrentMinimum time in seconds an outlet will stay on before turning it off.
1.3.6.1.4.1.2925.8.5.4.1.8ColumncyOutletMinimumOffIntervalread-onlycurrentMinimum time in seconds an outlet will stay off before turning it on.
1.3.6.1.4.1.2925.8.5.4.1.9ColumncyOutletWakeupStateread-onlycurrentOutlet state after a cold boot. It can be set to on or off.
1.3.6.1.4.1.2925.8.5.4.1.10ColumncyOutletPduIDread-onlycurrentPDU identification.
1.3.6.1.4.1.2925.8.5.4.1.11ColumncyOutletPduNumbernot-accessiblecurrentThe number of the PDU unit in the daisy-chained mode.
1.3.6.1.4.1.2925.8.5.5TablecyPMElecPduTablenot-accessiblecurrentAllow operations on elecmon element of the PDUs
1.3.6.1.4.1.2925.8.5.5.1RowcyPMElecPduTableEntrynot-accessiblecurrenteach entry has the information about the elecmon element of the PDUs.
1.3.6.1.4.1.2925.8.5.5.1.1ColumncyPMElecPduTablePortNumberread-onlycurrentSerial Port number where the PDU is connected.
1.3.6.1.4.1.2925.8.5.5.1.2ColumncyPMElecPduTablePduNumberread-onlycurrentThe number of the PDU unit in the daisy-chained mode
1.3.6.1.4.1.2925.8.5.5.1.3ColumncyPMElecPduTableCurrentValueread-onlycurrentActual value of current in the element (A x 10).
1.3.6.1.4.1.2925.8.5.5.1.4ColumncyPMElecPduTableCurrentMaxread-writecurrentMaximum detected value of current in the element (A x 10). Write operation accepts only 0 for reset action.
1.3.6.1.4.1.2925.8.5.5.1.5ColumncyPMElecPduTablePowerValueread-onlycurrentActual value of power in the element (W x 10).
1.3.6.1.4.1.2925.8.5.5.1.6ColumncyPMElecPduTablePowerMaxread-writecurrentMaximum value of power in the element (W x 10). Write operation accepts only 0 for reset action.
1.3.6.1.4.1.2925.8.5.5.1.7ColumncyPMElecPduTableVoltageValueread-onlycurrentActual value of voltage in the element (V).When element does not have voltage sensor, it returns 0.
1.3.6.1.4.1.2925.8.5.5.1.8ColumncyPMElecPduTableVoltageMaxread-writecurrentMaximum value of voltage in the element (V). When element does not have voltage sensor, it returns 0. Write operation accepts only 0 for reset action.
1.3.6.1.4.1.2925.8.5.5.1.9ColumncyPMElecPduTablePowerFactorValueread-onlycurrentActual value of power factor in the element (Pf x 10). When element does not have power factor sensor, returns 0.
1.3.6.1.4.1.2925.8.5.5.1.10ColumncyPMElecPduTablePowerFactorMaxread-writecurrentMaximum value of power factor in the element (Pf x 10). When element does not have power factor sensor, returns 0. Write operation accepts only 0 for reset act…
1.3.6.1.4.1.2925.8.5.5.1.11ColumncyPMElecPduTablePowerTyperead-onlycurrentThis PDU unit's Power sensor type.
1.3.6.1.4.1.2925.8.5.5.1.12ColumncyPMElecPduTableVoltageTyperead-onlycurrentThis PDU unit's has voltage sensor type.
1.3.6.1.4.1.2925.8.5.5.1.13ColumncyPMElecPduTablePowerFactorTyperead-onlycurrentThis PDU unit's Power Factor sensor type.
1.3.6.1.4.1.2925.8.5.6TablecyPMElecPhaseTablenot-accessiblecurrentAllow operations on elecmon element for phases
1.3.6.1.4.1.2925.8.5.6.1RowcyPMElecPhaseTableEntrynot-accessiblecurrenteach entry has the information about the elecmon for phase.
1.3.6.1.4.1.2925.8.5.6.1.1ColumncyPMElecPhaseTablePortNumberread-onlycurrentSerial Port number where the PDU is connected.
1.3.6.1.4.1.2925.8.5.6.1.2ColumncyPMElecPhaseTablePduNumberread-onlycurrentThe number of the PDU unit in the daisy-chained mode
1.3.6.1.4.1.2925.8.5.6.1.3ColumncyPMElecPhaseTableIndexread-onlycurrentindex of the phase in the PDU. Index can be 1,2 or 3.
1.3.6.1.4.1.2925.8.5.6.1.4ColumncyPMElecPhaseTableNameread-onlycurrentSys-name of the phase.
1.3.6.1.4.1.2925.8.5.6.1.5ColumncyPMElecPhaseTableCurrentValueread-onlycurrentActual value of current in the phase (A x 10).
1.3.6.1.4.1.2925.8.5.6.1.6ColumncyPMElecPhaseTableCurrentMaxread-writecurrentMaximum detected value of current in the phase (A x 10). Write operation accepts only 0 for reset action.
1.3.6.1.4.1.2925.8.5.6.1.7ColumncyPMElecPhaseTablePowerValueread-onlycurrentActual value of power in the phase (W x 10).
1.3.6.1.4.1.2925.8.5.6.1.8ColumncyPMElecPhaseTablePowerMaxread-writecurrentMaximum value of power in the phase (W x 10).Write operation accepts only 0 for reset action.
1.3.6.1.4.1.2925.8.5.6.1.9ColumncyPMElecPhaseTableVoltageValueread-onlycurrentActual value of voltage in the phase (V).When phase does not have voltage sensor, it returns 0.
1.3.6.1.4.1.2925.8.5.6.1.10ColumncyPMElecPhaseTableVoltageMaxread-writecurrentMaximum value of voltage in the phase (V). When phase does not have voltage sensor, it returns 0. Write operation accepts only 0 for reset action.
1.3.6.1.4.1.2925.8.5.6.1.11ColumncyPMElecPhaseTablePowerFactorValueread-onlycurrentActual value of power factor in the phase (Pf x 10). When phase does not have power factor sensor, returns 0.
1.3.6.1.4.1.2925.8.5.6.1.12ColumncyPMElecPhaseTablePowerFactorMaxread-writecurrentMaximum value of power factor in the phase (Pf x 10). When phase does not have power factor sensor, returns 0.Write operation accepts only 0 for reset action.
1.3.6.1.4.1.2925.8.5.6.1.13ColumncyPMElecPhaseTablePowerTyperead-onlycurrentThe type of Power sensor for this elecmon
1.3.6.1.4.1.2925.8.5.6.1.14ColumncyPMElecPhaseTableVoltageTyperead-onlycurrentThe type of Voltage sensor for this elecmon
1.3.6.1.4.1.2925.8.5.6.1.15ColumncyPMElecPhaseTablePowerFactorTyperead-onlycurrentThe type of Power Factor sensor for this elecmon
1.3.6.1.4.1.2925.8.5.7TablecyPMElecBankTablenot-accessiblecurrentAllow operations on elecmon element for banks
1.3.6.1.4.1.2925.8.5.7.1RowcyPMElecBankTableEntrynot-accessiblecurrenteach entry has the information about the elecmon for Bank.
1.3.6.1.4.1.2925.8.5.7.1.1ColumncyPMElecBankTablePortNumberread-onlycurrentSerial Port number where the PDU is connected.
1.3.6.1.4.1.2925.8.5.7.1.2ColumncyPMElecBankTablePduNumberread-onlycurrentThe number of the PDU unit in the daisy-chained mode
1.3.6.1.4.1.2925.8.5.7.1.3ColumncyPMElecBankTableIndexread-onlycurrentindex of the Bank in the PDU. Index can be 1,2, ... number of banks of the PDU.
1.3.6.1.4.1.2925.8.5.7.1.4ColumncyPMElecBankTableNameread-onlycurrentSys-name of the Bank.
1.3.6.1.4.1.2925.8.5.7.1.5ColumncyPMElecBankTableCurrentValueread-onlycurrentActual value of current in the Bank (A x 10).
1.3.6.1.4.1.2925.8.5.7.1.6ColumncyPMElecBankTableCurrentMaxread-writecurrentMaximum detected value of current in the Bank (A x 10). Write operation accepts only 0 for reset action.
1.3.6.1.4.1.2925.8.5.7.1.7ColumncyPMElecBankTablePowerValueread-onlycurrentActual value of power in the Bank (W x 10).
1.3.6.1.4.1.2925.8.5.7.1.8ColumncyPMElecBankTablePowerMaxread-writecurrentMaximum value of power in the Bank (W x 10).Write operation accepts only 0 for reset action.
1.3.6.1.4.1.2925.8.5.7.1.9ColumncyPMElecBankTableVoltageValueread-onlycurrentActual value of voltage in the Bank (V).When Bank does not have voltage sensor, it returns 0.
1.3.6.1.4.1.2925.8.5.7.1.10ColumncyPMElecBankTableVoltageMaxread-writecurrentMaximum value of voltage in the Bank (V). When Bank does not have voltage sensor, it returns 0. Write operation accepts only 0 for reset action.
1.3.6.1.4.1.2925.8.5.7.1.11ColumncyPMElecBankTablePowerFactorValueread-onlycurrentActual value of power factor in the Bank (Pf x 10). When Bank does not have power factor sensor, returns 0.
1.3.6.1.4.1.2925.8.5.7.1.12ColumncyPMElecBankTablePowerFactorMaxread-writecurrentMaximum value of power factor in the Bank (Pf x 10). When Bank does not have power factor sensor, returns 0.Write operation accepts only 0 for reset action.
1.3.6.1.4.1.2925.8.5.7.1.13ColumncyPMElecBankTablePowerTyperead-onlycurrentThe type of Power sensor for this elecmon
1.3.6.1.4.1.2925.8.5.7.1.14ColumncyPMElecBankTableVoltageTyperead-onlycurrentThe type of Voltage sensor for this elecmon
1.3.6.1.4.1.2925.8.5.7.1.15ColumncyPMElecBankTablePowerFactorTyperead-onlycurrentThe type of Power Factor sensor for this elecmon
1.3.6.1.4.1.2925.8.5.8TablecyPMElecOutletTablenot-accessiblecurrentAllow operations on elecmon element for outlets
1.3.6.1.4.1.2925.8.5.8.1RowcyPMElecOutletTableEntrynot-accessiblecurrenteach entry has the information about the elecmon for Outlet.
1.3.6.1.4.1.2925.8.5.8.1.1ColumncyPMElecOutletTablePortNumberread-onlycurrentSerial Port number where the PDU is connected.
1.3.6.1.4.1.2925.8.5.8.1.2ColumncyPMElecOutletTablePduNumberread-onlycurrentThe number of the PDU unit in the daisy-chained mode
1.3.6.1.4.1.2925.8.5.8.1.3ColumncyPMElecOutletTableNumberread-onlycurrentoutlet number in the PDU
1.3.6.1.4.1.2925.8.5.8.1.4ColumncyPMElecOutletTableNameread-onlycurrentname of the Outlet.
1.3.6.1.4.1.2925.8.5.8.1.5ColumncyPMElecOutletTableCurrentValueread-onlycurrentActual value of current in the Outlet (A x 10).
1.3.6.1.4.1.2925.8.5.8.1.6ColumncyPMElecOutletTableCurrentMaxread-writecurrentMaximum detected value of current in the Outlet (A x 10). Write operation accepts only 0 for reset action.
1.3.6.1.4.1.2925.8.5.8.1.7ColumncyPMElecOutletTablePowerValueread-onlycurrentActual value of power in the Outlet (W x 10).
1.3.6.1.4.1.2925.8.5.8.1.8ColumncyPMElecOutletTablePowerMaxread-writecurrentMaximum value of power in the Outlet (W x 10).Write operation accepts only 0 for reset action.
1.3.6.1.4.1.2925.8.5.8.1.9ColumncyPMElecOutletTableVoltageValueread-onlycurrentActual value of voltage in the Outlet (V).When Outlet does not have voltage sensor, it returns 0.
1.3.6.1.4.1.2925.8.5.8.1.10ColumncyPMElecOutletTableVoltageMaxread-writecurrentMaximum value of voltage in the Outlet (V). When Outlet does not have voltage sensor, it returns 0. Write operation accepts only 0 for reset action.
1.3.6.1.4.1.2925.8.5.8.1.11ColumncyPMElecOutletTablePowerFactorValueread-onlycurrentActual value of power factor in the Outlet (Pf x 10). When Outlet does not have power factor sensor, returns 0.
1.3.6.1.4.1.2925.8.5.8.1.12ColumncyPMElecOutletTablePowerFactorMaxread-writecurrentMaximum value of power factor in the Outlet (Pf x 10). When Outlet does not have power factor sensor, returns 0.Write operation accepts only 0 for reset action.
1.3.6.1.4.1.2925.8.5.8.1.13ColumncyPMElecOutletTablePowerTyperead-onlycurrentThe type of Power sensor for this elecmon
1.3.6.1.4.1.2925.8.5.8.1.14ColumncyPMElecOutletTableVoltageTyperead-onlycurrentThe type of Voltage sensor for this elecmon
1.3.6.1.4.1.2925.8.5.8.1.15ColumncyPMElecOutletTablePowerFactorTyperead-onlycurrentThe type of Power Factor sensor for this elecmon
1.3.6.1.4.1.2925.8.5.9TablecyPMEnvMonTablenot-accessiblecurrentAllow operations on environmental monitors
1.3.6.1.4.1.2925.8.5.9.1RowcyPMEnvMonTableEntrynot-accessiblecurrenteach entry has the information about the environmental monitors.
1.3.6.1.4.1.2925.8.5.9.1.1ColumncyPMEnvMonTablePortNumberread-onlycurrentSerial Port number where the PDU is connected.
1.3.6.1.4.1.2925.8.5.9.1.2ColumncyPMEnvMonTablePduNumberread-onlycurrentThe number of the PDU unit in the daisy-chained mode
1.3.6.1.4.1.2925.8.5.9.1.3ColumncyPMEnvMonTableIndexread-onlycurrentindex of the environmental monitor in the PDU.
1.3.6.1.4.1.2925.8.5.9.1.4ColumncyPMEnvMonTableNameread-onlycurrentName of the environmental monitor.
1.3.6.1.4.1.2925.8.5.9.1.5ColumncyPMEnvMonTableTyperead-onlycurrentThe type of environmental monitor.
1.3.6.1.4.1.2925.8.5.9.1.6ColumncyPMEnvMonTableStatusread-onlycurrentThe status of Dry-Contact/Water-level/Smoke/Motion monitors. Dry-Contact sensor: Opened(1), closed(2). Water level: Normal (1), Triggered(2). Smoke sensor: not…
1.3.6.1.4.1.2925.8.5.9.1.7ColumncyPMEnvMonTableValueread-onlycurrentActual value of Temperature/Humidity/Air-flow monitors (x 10).
1.3.6.1.4.1.2925.8.5.9.1.8ColumncyPMEnvMonTableMaxValueread-writecurrentMaximum detected value of Temperature/Humidity/Air-flow monitor (x 10). Write operation accepts only 0 for reset action.