DCMCU3000-MIB
165 objects
The MIB module to describe DC-Power Systems.
Imported Objects
| SNMPv2-CONF | MODULE-COMPLIANCE NOTIFICATION-GROUP OBJECT-GROUP |
| SNMPv2-SMI | enterprises Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-IDENTITY OBJECT-TYPE |
| SNMPv2-TC | AutonomousType DisplayString TEXTUAL-CONVENTION TimeStamp |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.27383 | Nodebenning | |||
| 1.3.6.1.4.1.27383.6 | Identitydcmcu3000-MIB | The MIB module to describe DC-Power Systems. | ||
| 1.3.6.1.4.1.27383.6.1 | NodedcObjects | |||
| 1.3.6.1.4.1.27383.6.1.1 | NodedcIdent | |||
| 1.3.6.1.4.1.27383.6.1.1.1 | ScalardcIdentManufacturer | read-only | current | The name of the DC-power system manufacturer. |
| 1.3.6.1.4.1.27383.6.1.1.2 | ScalardcIdentModel | read-only | current | The DC-power system model description. |
| 1.3.6.1.4.1.27383.6.1.1.3 | ScalardcIdentSerialNumber | read-only | current | The serial number of the DC-power system. |
| 1.3.6.1.4.1.27383.6.1.1.4 | ScalardcIdentName | read-write | current | A string identifying the DC-power system. This object should be set by the administrator. |
| 1.3.6.1.4.1.27383.6.1.1.5 | ScalardcIdentDescription | read-write | current | A possibility for the administrator to describe the power system. |
| 1.3.6.1.4.1.27383.6.1.1.6 | ScalardcIdentSystemInstallationDate | read-write | current | A string containing either the date of system installation or acceptance date (YYYY-MM-DD). This string can be set by the administrator. |
| 1.3.6.1.4.1.27383.6.1.1.7 | ScalardcIdentNominalVoltage | read-only | current | Nominal output voltage of the system. |
| 1.3.6.1.4.1.27383.6.1.1.8 | ScalardcIdentNominalCurrent | read-only | current | Nominal output current of the system. |
| 1.3.6.1.4.1.27383.6.1.1.9 | ScalardcIdentNominalValues | read-write | current | A string containing nominal output power values of the system, e.g. 48 Volts / 3000 Amps / 3000 Ah. This string can be set by the administrator. |
| 1.3.6.1.4.1.27383.6.1.2 | NodedcPowerSystem | |||
| 1.3.6.1.4.1.27383.6.1.2.1 | ScalardcPowerSystemBusbarVoltage | read-only | current | The magnitude of the busbar voltage. |
| 1.3.6.1.4.1.27383.6.1.2.2 | ScalardcPowerSystemTotalRectCurrent | read-only | current | The magnitude of the total rectifier current. |
| 1.3.6.1.4.1.27383.6.1.2.3 | ScalardcPowerSystemTotalBatteryCurrent | read-only | current | The magnitude of the total battery current. |
| 1.3.6.1.4.1.27383.6.1.2.4 | ScalardcPowerSystemTotalLoadCurrent | read-only | current | The magnitude of the total system load current. |
| 1.3.6.1.4.1.27383.6.1.2.5 | ScalardcPowerSystemTotalOutputPower | read-only | current | The magnitude of the present total system output true power. |
| 1.3.6.1.4.1.27383.6.1.2.6 | ScalardcPowerSystemRelativeOutputPower | read-only | current | The magnitude of the present relative system output true power. |
| 1.3.6.1.4.1.27383.6.1.2.7 | ScalardcPowerSystemStatus | read-only | current | The status of the power system describing the rectifiers and the batteries. Bit 1: Float Bit 2: Boost Bit 3: Client specific operation Bit 4: Battery Test Bit … |
| 1.3.6.1.4.1.27383.6.1.2.8 | ScalardcPowerSystemFault | read-only | current | The fault of the power system. The most important fault level is displayed. Bit 1: Normal Bit 2: Minor Bit 3: Major Bit 4: Information |
| 1.3.6.1.4.1.27383.6.1.2.9 | ScalardcPowerSystemTemperature | read-only | current | The magnitude of the system ambient temperature. |
| 1.3.6.1.4.1.27383.6.1.2.10 | ScalardcPowerSystemNumRectifiers | read-only | current | The number of rectifers or rectifier-shelfs utilized in this system. |
| 1.3.6.1.4.1.27383.6.1.2.11 | ScalardcPowerSystemNumRectifiersOuputPowerAvailable | read-only | current | The number of rectifers with available output power. |
| 1.3.6.1.4.1.27383.6.1.2.12 | TabledcPowerSystemClientSpecificMeasurementTable | not-accessible | current | A list of client specific measurement entries. |
| 1.3.6.1.4.1.27383.6.1.2.12.1 | RowdcPowerSystemClientSpecificMeasurementEntry | not-accessible | current | An entry containing information applicable to a particular client specific measurement entry. |
| 1.3.6.1.4.1.27383.6.1.2.12.1.1 | ColumndcPowerSystemClientSpecificMeasurementId | not-accessible | current | A unique identifier for a client specific measurement value. This value must remain constant. |
| 1.3.6.1.4.1.27383.6.1.2.12.1.2 | ColumndcPowerSystemClientSpecificMeasurementDescription | read-only | current | The client specific measurement decscription. |
| 1.3.6.1.4.1.27383.6.1.2.12.1.3 | ColumndcPowerSystemClientSpecificMeasurementValue | read-only | current | This value shows the current client specifc measurement value. |
| 1.3.6.1.4.1.27383.6.1.2.12.1.4 | ColumndcPowerSystemClientSpecificMeasurementUnit | read-only | current | A description of the client specific measurement unit. |
| 1.3.6.1.4.1.27383.6.1.3 | NodedcController | |||
| 1.3.6.1.4.1.27383.6.1.3.1 | ScalardcControllerSerialNumber | read-only | current | The DC-power system's controller serial number. |
| 1.3.6.1.4.1.27383.6.1.3.2 | ScalardcControllerSoftwareVersion | read-only | current | The DC-power system software version(s). This variable can be different from the dcControllerFirmwareVersion. This variable may or may not have the same value … |
| 1.3.6.1.4.1.27383.6.1.3.3 | ScalardcControllerAgentSoftwareVersion | read-only | current | The DC-power system agent software version. This variable can be different from the dcControllerAgentFirmwareVersion. This variable may or may not have the sam… |
| 1.3.6.1.4.1.27383.6.1.4 | NodedcRectifier | |||
| 1.3.6.1.4.1.27383.6.1.4.1 | ScalardcRectifierNumRectifiers | read-only | current | The number of rectifers or rectifier-shelfs utilized in this system. This variable indicates the number of rows in the rectifier table. |
| 1.3.6.1.4.1.27383.6.1.4.2 | TabledcRectifierTable | not-accessible | current | A list of rectifier table entries. The number of entries is given by the value of dcRectifierNumRectifiers. |
| 1.3.6.1.4.1.27383.6.1.4.2.1 | RowdcRectifierEntry | not-accessible | current | An entry containing information applicable to a particular rectifier. |
| 1.3.6.1.4.1.27383.6.1.4.2.1.1 | ColumndcRectifierIndex | not-accessible | current | The rectifier identifier. |
| 1.3.6.1.4.1.27383.6.1.4.2.1.2 | ColumndcRectifierFirmwareVersion | read-only | current | The rectifier's firmware version. |
| 1.3.6.1.4.1.27383.6.1.4.2.1.3 | ColumndcRectifierStatus | read-only | current | The current state of the rectifier. Rectifiers can be on or off. |
| 1.3.6.1.4.1.27383.6.1.4.2.1.4 | ColumndcRectifierModuleFault | read-only | current | The current state of the retifier module fault. |
| 1.3.6.1.4.1.27383.6.1.4.2.1.5 | ColumndcRectifierFanFault | read-only | current | The current state of the retifier fan fault. |
| 1.3.6.1.4.1.27383.6.1.4.2.1.6 | ColumndcRectifierMainsFault | read-only | current | The current state of the retifier mains fault. |
| 1.3.6.1.4.1.27383.6.1.4.2.1.7 | ColumndcRectifierVoltage | read-only | current | The magnitude of the rectifier voltage. |
| 1.3.6.1.4.1.27383.6.1.4.2.1.8 | ColumndcRectifierCurrent | read-only | current | The magnitude of the present rectifier current. |
| 1.3.6.1.4.1.27383.6.1.4.2.1.9 | ColumndcRectifierAddress | read-only | current | The address of the rectifier in the system. |
| 1.3.6.1.4.1.27383.6.1.4.2.1.10 | ColumndcRectifierSerialNumber | read-only | current | The rectifier's serial number. |
| 1.3.6.1.4.1.27383.6.1.4.2.1.11 | ColumndcRectifierOperatingHours | read-only | current | The operating hours of the rectifier. |
| 1.3.6.1.4.1.27383.6.1.5 | NodedcBattery | |||
| 1.3.6.1.4.1.27383.6.1.5.1 | ScalardcBatteryFault | read-only | current | This object indicates a fault of the components affecting more than one battery string, e.g. deep discharge contactor. Bit 0: Battery circuit test failed Bit 1… |
| 1.3.6.1.4.1.27383.6.1.5.2 | ScalardcBatteryVoltage1 | read-only | current | The magnitude of the battery 1 voltage. |
| 1.3.6.1.4.1.27383.6.1.5.3 | ScalardcBatteryCurrent1 | read-only | current | The magnitude of the present battery 1 current. |
| 1.3.6.1.4.1.27383.6.1.5.4 | ScalardcBatteryCapacity1 | read-only | current | The battery 1 capacity. |
| 1.3.6.1.4.1.27383.6.1.5.5 | ScalardcBatteryVoltage2 | read-only | current | The magnitude of the battery 2 voltage. |
| 1.3.6.1.4.1.27383.6.1.5.6 | ScalardcBatteryCurrent2 | read-only | current | The magnitude of the present battery 2 current. |
| 1.3.6.1.4.1.27383.6.1.5.7 | ScalardcBatteryCapacity2 | read-only | current | The battery 2 capacity. |
| 1.3.6.1.4.1.27383.6.1.5.8 | ScalardcBatteryTemperature | read-only | current | The battery temperature. |
| 1.3.6.1.4.1.27383.6.1.5.9 | ScalardcBatteryAutomaticBoostCharge | read-only | current | This object indicates if automatic boost charge is enabled or not. |
| 1.3.6.1.4.1.27383.6.1.5.10 | ScalardcBatteryTemperatureControlledCharging | read-only | current | This object indicates if temperature controlled charging is enabled or not. |
| 1.3.6.1.4.1.27383.6.1.5.11 | ScalardcBatteryCurrentLimitation | read-only | current | This object indicates if battery current limitation is enabled or not. |
| 1.3.6.1.4.1.27383.6.1.5.12 | ScalardcBatterySensorCompensation | read-only | current | This object indicates if battery sensor compensation is enabled or not. |
| 1.3.6.1.4.1.27383.6.1.5.13 | ScalardcBatteryAutomaticBatteryTest | read-only | current | This object indicates if automatic battery test is enabled or not. |
| 1.3.6.1.4.1.27383.6.1.5.14 | ScalardcBatteryAutomaticBatteryCircuitTest | read-only | current | This object indicates if automatic battery circuit test is enabled or not. |
| 1.3.6.1.4.1.27383.6.1.6 | NodedcLoadDistribution | |||
| 1.3.6.1.4.1.27383.6.1.6.1 | ScalardcLoadDistributionTotalCurrent | read-only | current | The magnitude of the total load current. |
| 1.3.6.1.4.1.27383.6.1.7 | NodedcBatteryTest | |||
| 1.3.6.1.4.1.27383.6.1.7.1 | ScalardcBatteryTestEndVoltage | read-only | current | The battery voltage at the end of the battery test. |
| 1.3.6.1.4.1.27383.6.1.7.2 | ScalardcBatteryTestDuration | read-only | current | The duration of the last battery test in minutes. |
| 1.3.6.1.4.1.27383.6.1.7.3 | ScalardcBatteryTestDischargedAh | read-only | current | This discharged Ah during the last battery test. |
| 1.3.6.1.4.1.27383.6.1.7.4 | ScalardcBatteryTestDefaultSuccessCriterion | read-only | current | The type of success criterion of the last battery test. |
| 1.3.6.1.4.1.27383.6.1.7.5 | ScalardcBatteryTestResult | read-only | current | The result of the last battery test. |
| 1.3.6.1.4.1.27383.6.1.7.6 | ScalardcBatteryTestDate | read-only | current | A string containing the date of battery test start (YYYY-MM-DD). |
| 1.3.6.1.4.1.27383.6.1.7.7 | ScalardcBatteryTestTime | read-only | current | A string containing the time of battery test start (HH:MM). |
| 1.3.6.1.4.1.27383.6.1.8 | NodedcBatteryCircuitTest | |||
| 1.3.6.1.4.1.27383.6.1.8.1 | ScalardcBatteryCircuitTestResult | read-only | current | The result of the last battery circuit test. |
| 1.3.6.1.4.1.27383.6.1.8.2 | ScalardcBatteryCircuitTestDate | read-only | current | A string containing the date of battery circuit test start (YYYY-MM-DD). |
| 1.3.6.1.4.1.27383.6.1.8.3 | ScalardcBatteryCircuitTestTime | read-only | current | A string containing the time of battery circuit test start (HH:MM). |
| 1.3.6.1.4.1.27383.6.1.9 | NodedcControl | |||
| 1.3.6.1.4.1.27383.6.1.9.1 | ScalardcControlMode | read-write | current | This object controls the system mode. batteryTest(3) starts a battery test and setting the mode to float(1), boost(2), directFeed(4), off(5), clientSpecificOpe… |
| 1.3.6.1.4.1.27383.6.1.9.2 | ScalardcControlRestartFaultyUnits | read-write | current | This object restarts all faulty units in the system. After setting this object (1), the agent responses with 0 if executed. |
| 1.3.6.1.4.1.27383.6.1.10 | NodedcConfig | |||
| 1.3.6.1.4.1.27383.6.1.10.1 | ScalardcConfigFloatVoltage | read-write | current | The float voltage of the system. |
| 1.3.6.1.4.1.27383.6.1.10.2 | ScalardcConfigBoostVoltage | read-write | current | The boost voltage of the system. |
| 1.3.6.1.4.1.27383.6.1.10.3 | ScalardcConfigBatteryTestVoltage | read-write | current | The battery test-voltage of the system. |
| 1.3.6.1.4.1.27383.6.1.10.4 | ScalardcConfigDirectFeedVoltage | read-write | current | The direct feed voltage of the system. |
| 1.3.6.1.4.1.27383.6.1.11 | NodedcAlarm | |||
| 1.3.6.1.4.1.27383.6.1.11.1 | ScalardcAlarmsNumberOfActiveAlarms | read-only | current | The present number of active alarm conditions. |
| 1.3.6.1.4.1.27383.6.1.11.2 | TabledcAlarmTable | not-accessible | current | A list of alarm entries. |
| 1.3.6.1.4.1.27383.6.1.11.2.1 | RowdcAlarmEntry | not-accessible | current | An entry containing information applicable to a particular alarm. |
| 1.3.6.1.4.1.27383.6.1.11.2.1.1 | ColumndcAlarmId | read-only | current | A unique identifier for an alarm condition. This value must remain constant. |
| 1.3.6.1.4.1.27383.6.1.11.2.1.2 | ColumndcAlarmWellKnownDescription | read-only | current | A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con… |
| 1.3.6.1.4.1.27383.6.1.11.2.1.3 | ColumndcAlarmTime | read-only | current | The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before ag… |
| 1.3.6.1.4.1.27383.6.1.11.2.1.4 | ColumndcAlarmState | read-only | current | This value shows the current alarm state. |
| 1.3.6.1.4.1.27383.6.1.11.2.1.5 | ColumndcAlarmDescription | read-only | current | A description of the alarm condition. |
| 1.3.6.1.4.1.27383.6.1.11.3 | NodedcWellKnownAlarms | |||
| 1.3.6.1.4.1.27383.6.1.11.3.1 | IdentitydcAlarmAgentCommunication | current | This object indicates a communication problem from the agent to the DC-power system. | |
| 1.3.6.1.4.1.27383.6.1.11.3.2 | IdentitydcAlarmGeneral | current | This object indicates a general alarm. | |
| 1.3.6.1.4.1.27383.6.1.11.3.3 | IdentitydcAlarmNonUrgentError | current | This object indicates a non urgent error. | |
| 1.3.6.1.4.1.27383.6.1.11.3.4 | IdentitydcAlarmUrgentError | current | This object indicates an urgent error. | |
| 1.3.6.1.4.1.27383.6.1.11.3.5 | IdentitydcAlarmBattDischarge | current | This object indicates that the battery is in discharge mode. | |
| 1.3.6.1.4.1.27383.6.1.11.3.6 | IdentitydcAlarmBoost | current | This object indicates that the system is in boost mode. | |
| 1.3.6.1.4.1.27383.6.1.11.3.7 | IdentitydcAlarmAddressRedundancyWarning | current | This object indicates a rectifier address redundancy warning. | |
| 1.3.6.1.4.1.27383.6.1.11.3.8 | IdentitydcAlarmAddressRedundancyFault | current | This object indicates a rectifier address redundancy fault. | |
| 1.3.6.1.4.1.27383.6.1.11.3.9 | IdentitydcAlarmCurrentRedundancyFault | current | This object indicates a rectifier current redundancy fault. | |
| 1.3.6.1.4.1.27383.6.1.11.3.10 | IdentitydcAlarmBatteryFault | current | This object indicates an alarm of batteries, e.g. fuse blown, symmetry or temperature. | |
| 1.3.6.1.4.1.27383.6.1.11.3.11 | IdentitydcAlarmBatteryTestInProgress | current | This object indicates that the system is in battery test mode. | |
| 1.3.6.1.4.1.27383.6.1.11.3.12 | IdentitydcAlarmBatteryTestFailed | current | This object indicates that the battery test has failed. | |
| 1.3.6.1.4.1.27383.6.1.11.3.13 | IdentitydcAlarmBatteryTestInvalid | current | This object indicates an invalid battery test result. | |
| 1.3.6.1.4.1.27383.6.1.11.3.14 | IdentitydcAlarmBatteryCircuittestFailed | current | This object indicates that the battery circuittest has failed. | |
| 1.3.6.1.4.1.27383.6.1.11.3.15 | IdentitydcAlarmAllRectifierOff | current | This object indicates that all rectifiers are off. | |
| 1.3.6.1.4.1.27383.6.1.11.3.16 | IdentitydcAlarmRectifierOutputCurrentHigh | current | This object indicates that the rectifier output current is high. | |
| 1.3.6.1.4.1.27383.6.1.11.3.17 | IdentitydcAlarmRectifierOutputVoltageOutOfRange | current | This object indicates that the rectifier output voltage is out of range. | |
| 1.3.6.1.4.1.27383.6.1.11.3.18 | IdentitydcAlarmRectifierOvervoltage | current | This object indicates a rectifier overvoltage. | |
| 1.3.6.1.4.1.27383.6.1.11.3.19 | IdentitydcAlarmRectifierACInputFault | current | This object indicates an alarm in the AC-input, e.g. ac input fuse blown, ac input breaker tripped or mains failure. | |
| 1.3.6.1.4.1.27383.6.1.11.3.20 | IdentitydcAlarmRectifierFault | current | This object indicates an alarm of rectifiers, e.g. broken rectifier, fan or temperature alarm. | |
| 1.3.6.1.4.1.27383.6.1.11.3.21 | IdentitydcAlarmRectifierFanFault | current | This object indicates that a rectifier fan failed. The device id is given in the dcAlarmDevice field. | |
| 1.3.6.1.4.1.27383.6.1.11.3.22 | IdentitydcAlarmRectifierOff | current | This object indicates that the rectifier given as dcAlarmDevice is off. | |
| 1.3.6.1.4.1.27383.6.1.11.3.23 | IdentitydcAlarmRectifierTemperatureHighWarning | current | This object indicates a high rectifier temperature warning. | |
| 1.3.6.1.4.1.27383.6.1.11.3.24 | IdentitydcAlarmRectifierTemperatureHighFault | current | This object indicates a high rectifier temperature fault. | |
| 1.3.6.1.4.1.27383.6.1.11.3.25 | IdentitydcAlarmRectifierTemperatureSensorFault | current | This object indicates a rectifier temperature sensor fault. | |
| 1.3.6.1.4.1.27383.6.1.11.3.26 | IdentitydcAlarmRectifierShortCircuitFault | current | This object indicates a rectifier short circuit fault. | |
| 1.3.6.1.4.1.27383.6.1.11.3.27 | IdentitydcAlarmBatterySymmetryFault | current | This object indicates a battery symmetry fault. | |
| 1.3.6.1.4.1.27383.6.1.11.3.28 | IdentitydcAlarmBatteryTemperatureSensorFault | current | This object indicates a battery temperature sensor fault. | |
| 1.3.6.1.4.1.27383.6.1.11.3.50 | IdentitydcAlarmClientSpecificAlarm1 | current | This object indicates a client specific alarm. | |
| 1.3.6.1.4.1.27383.6.1.11.3.51 | IdentitydcAlarmClientSpecificAlarm2 | current | This object indicates a client specific alarm. | |
| 1.3.6.1.4.1.27383.6.1.11.3.52 | IdentitydcAlarmClientSpecificAlarm3 | current | This object indicates a client specific alarm. | |
| 1.3.6.1.4.1.27383.6.1.11.3.53 | IdentitydcAlarmClientSpecificAlarm4 | current | This object indicates a client specific alarm. | |
| 1.3.6.1.4.1.27383.6.1.11.3.54 | IdentitydcAlarmClientSpecificAlarm5 | current | This object indicates a client specific alarm. | |
| 1.3.6.1.4.1.27383.6.1.11.3.55 | IdentitydcAlarmClientSpecificAlarm6 | current | This object indicates a client specific alarm. | |
| 1.3.6.1.4.1.27383.6.1.11.3.56 | IdentitydcAlarmClientSpecificAlarm7 | current | This object indicates a client specific alarm. | |
| 1.3.6.1.4.1.27383.6.1.11.3.57 | IdentitydcAlarmClientSpecificAlarm8 | current | This object indicates a client specific alarm. | |
| 1.3.6.1.4.1.27383.6.1.11.3.58 | IdentitydcAlarmClientSpecificAlarm9 | current | This object indicates a client specific alarm. | |
| 1.3.6.1.4.1.27383.6.1.11.3.59 | IdentitydcAlarmClientSpecificAlarm10 | current | This object indicates a client specific alarm. | |
| 1.3.6.1.4.1.27383.6.1.12 | NodedcPowermanagement | |||
| 1.3.6.1.4.1.27383.6.1.12.1 | ScalardcPowermanagementMode | read-only | current | The current state of the powermanagement. |
| 1.3.6.1.4.1.27383.6.1.12.2 | ScalardcPowermanagementNumModulesInStandby | read-only | current | The number of modules in standby. |
| 1.3.6.1.4.1.27383.6.1.12.3 | ScalardcPowermanagementMinNumModulesSwitchedOn | read-only | current | The minimum number of switched on modules. |
| 1.3.6.1.4.1.27383.6.2 | NodedcMCU3000Traps | |||
| 1.3.6.1.4.1.27383.6.2.0 | NodedcTraps | |||
| 1.3.6.1.4.1.27383.6.2.0.1 | NotificationdcTrapAlarmEntryAdded | current | This trap is sent upon a alarm in the system appears. Bindings in the trap are descriptions of the alarm. Additionally binding snmpTrapEnterprise identifies th… | |
| 1.3.6.1.4.1.27383.6.2.0.2 | NotificationdcTrapAlarmEntryRemoved | current | This trap is sent upon a alarm in the system disappears. Binding in the trap are descriptions of the alarm. Additionally binding snmpTrapEnterprise identifies … | |
| 1.3.6.1.4.1.27383.6.2.0.3 | NotificationdcTrapSystemCheckInTrap | current | This trap occurs every 7 days to acknowledge that the system is running. Additionally binding snmpTrapEnterprise identifies the dc power system (oid). | |
| 1.3.6.1.4.1.27383.6.3 | Nodedcmcu3000MIBConformance | |||
| 1.3.6.1.4.1.27383.6.3.1 | Nodedcmcu3000MIBCompliances | |||
| 1.3.6.1.4.1.27383.6.3.1.1 | Compliancedcmcu3000MIBCompliance | current | The compliance statement for SNMPv2 entities which implement the Benning DC MCU MIB 2. | |
| 1.3.6.1.4.1.27383.6.3.2 | Nodedcmcu3000MIBGroups | |||
| 1.3.6.1.4.1.27383.6.3.2.1 | GroupdcIdentGroup | current | A collection of objects provided for the dc mcu ident group. | |
| 1.3.6.1.4.1.27383.6.3.2.2 | GroupdcPowerSystemGroup | current | A collection of objects provided for the dc mcu system group. | |
| 1.3.6.1.4.1.27383.6.3.2.3 | GroupdcControllerGroup | current | A collection of objects provided for the dc mcu controller group. | |
| 1.3.6.1.4.1.27383.6.3.2.4 | GroupdcRectifierGroup | current | A collection of objects provided for the dc mcu rectifier group. | |
| 1.3.6.1.4.1.27383.6.3.2.5 | GroupdcBatteryGroup | current | A collection of objects provided for the dc mcu battery group. | |
| 1.3.6.1.4.1.27383.6.3.2.6 | GroupdcLoadDistributionGroup | current | A collection of objects provided for the dc mcu load distribution group. | |
| 1.3.6.1.4.1.27383.6.3.2.7 | GroupdcBatteryTestGroup | current | A collection of objects provided for the dc mcu battery test group. | |
| 1.3.6.1.4.1.27383.6.3.2.8 | GroupdcBatteryCircuitTestGroup | current | A collection of objects provided for the dc mcu battery circuittest group. | |
| 1.3.6.1.4.1.27383.6.3.2.9 | GroupdcControlGroup | current | A collection of objects provided for the dc mcu control group. | |
| 1.3.6.1.4.1.27383.6.3.2.10 | GroupdcConfigGroup | current | A collection of objects provided for the dc mcu config group. | |
| 1.3.6.1.4.1.27383.6.3.2.11 | GroupdcAlarmGroup | current | A collection of objects provided for the dc mcu alarm group. | |
| 1.3.6.1.4.1.27383.6.3.2.12 | GroupdcPowermanagementGroup | current | A collection of objects provided for the dc mcu auxiliary group. | |
| 1.3.6.1.4.1.27383.6.3.2.13 | GroupdcTrapsGroup | current | A collection of objects provided for the dc mcu traps group. |
Type Definitions
| Name | Syntax | Status | Description |
|---|---|---|---|
| AlarmState | INTEGER { notActive(1), active(2) } | current | This data type indicates the state of an alarm. |
| FixedPointNumber | Integer32 (-2147483648..2147483647) | current | This data type is a fixed point value with two decimal places. |
| NonNegativeInteger | Integer32 (0..2147483647) | current | This data type is a non-negative value. |
| PositiveInteger | Integer32 (1..2147483647) | current | This data type is a non-zero and non-negative value. |