MIB Viewer

DGPUPS-MIB

215 objects
No module-level DESCRIPTION found.
Imported Objects
RFC-1212OBJECT-TYPE
RFC-1215TRAP-TYPE
RFC1155-SMIenterprises IpAddress
RFC1213-MIBDisplayString
OIDNameAccessStatusDescription
1.3.6.1.4.1.17420Nodedgp
1.3.6.1.4.1.17420.1NodecommunicationLostSEVERE: Communication to the UPS has been lost. Steps to reestablish communication are in progress.
1.3.6.1.4.1.17420.1Nodeproducts
1.3.6.1.4.1.17420.1.1Nodehardware
1.3.6.1.4.1.17420.1.1.1Scalarprotocolread-writemandatoryselect protocol
1.3.6.1.4.1.17420.1.1.2Nodeups
1.3.6.1.4.1.17420.1.1.2.1NodeupsIdentp
1.3.6.1.4.1.17420.1.1.2.1.1NodeupsBaseIdent
1.3.6.1.4.1.17420.1.1.2.1.1.1ScalarupsBaseIdentModelread-onlymandatoryThe UPS model name (e.g. 'Intelligent 8000E 900VA').
1.3.6.1.4.1.17420.1.1.2.1.1.2ScalarupsBaseIdentUpsNameread-writemandatoryAn 8 byte ID string identifying the UPS. This object can be set by the administrator.
1.3.6.1.4.1.17420.1.1.2.1.2NodeupsSmartIdent
1.3.6.1.4.1.17420.1.1.2.1.2.1ScalarupsSmartIdentFirmwareRevisionread-onlymandatoryThe firmware revision of the UPS system.
1.3.6.1.4.1.17420.1.1.2.1.2.2ScalarupsSmartIdentDateOfManufactureread-onlymandatoryThe date when the UPS was manufactured in mm/dd/yy format.
1.3.6.1.4.1.17420.1.1.2.1.2.3ScalarupsSmartIdentUpsSerialNumberread-onlymandatoryAn 8-character string identifying the serial number of the UPS internal microprocessor. This number is set at the factory. NOTE: This number does NOT correspon…
1.3.6.1.4.1.17420.1.1.2.1.2.4ScalarupsSmartIdentAgentFirmwareRevisionread-onlymandatoryThe firmware revision of the UPS SNMP Proxy agent.
1.3.6.1.4.1.17420.1.1.2.2NodeupsBatteryp
1.3.6.1.4.1.17420.1.1.2.2.1NodeupsBaseBattery
1.3.6.1.4.1.17420.1.1.2.2.1.1ScalarupsBaseBatteryStatusread-onlymandatoryThe status of the UPS batteries. A batteryLow(3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is …
1.3.6.1.4.1.17420.1.1.2.2.1.2ScalarupsBaseBatteryTimeOnBatteryread-onlymandatoryThe elapsed time in seconds since the UPS has switched to battery power.
1.3.6.1.4.1.17420.1.1.2.2.1.3ScalarupsBaseBatteryLastReplaceDateread-writemandatoryThe date when the UPS system's batteries were last replaced in mm/dd/yy format. For UPS models, this value is originally set in the factory. When the UPS batte…
1.3.6.1.4.1.17420.1.1.2.2.2NodeupsSmartBattery
1.3.6.1.4.1.17420.1.1.2.2.2.1ScalarupsSmartBatteryCapacityread-onlymandatoryThe remaining battery capacity expressed in percent of full capacity.
1.3.6.1.4.1.17420.1.1.2.2.2.2ScalarupsSmartBatteryVoltageread-onlymandatoryThe current battery voltage expressed in 1/10 VDC.
1.3.6.1.4.1.17420.1.1.2.2.2.3ScalarupsSmartBatteryTemperatureread-onlymandatoryThe current internal UPS temperature expressed in tenths of a Celsius degree.
1.3.6.1.4.1.17420.1.1.2.2.2.4ScalarupsSmartBatteryRunTimeRemainingread-onlymandatoryThe UPS battery run time remaining before battery exhaustion, in seconds.
1.3.6.1.4.1.17420.1.1.2.2.2.5ScalarupsSmartBatteryReplaceIndicatorread-onlymandatoryIndicates whether the UPS batteries need replacing.
1.3.6.1.4.1.17420.1.1.2.2.2.6ScalarupsSmartBatteryFullChargeVoltageread-onlymandatoryThe fully charged battery voltage of the battery system used in the UPS, expressed in tenths of a volt.
1.3.6.1.4.1.17420.1.1.2.2.2.7ScalarupsSmartBatteryCurrentread-onlymandatoryThe current battery current expressed in percent of maximum current.
1.3.6.1.4.1.17420.1.1.2.3NodeupsInputp
1.3.6.1.4.1.17420.1.1.2.3.1NodeupsBaseInput
1.3.6.1.4.1.17420.1.1.2.3.1.1ScalarupsBaseInputPhaseread-onlymandatoryThe current AC input phase.
1.3.6.1.4.1.17420.1.1.2.3.2NodeupsSmartInput
1.3.6.1.4.1.17420.1.1.2.3.2.1ScalarupsSmartInputLineVoltageread-onlymandatoryThe current utility line voltage in 1/10 VAC.
1.3.6.1.4.1.17420.1.1.2.3.2.2ScalarupsSmartInputMaxLineVoltageread-onlymandatoryThe maximum utility line voltage in 1/10 VAC over the previous 1 minute period.
1.3.6.1.4.1.17420.1.1.2.3.2.3ScalarupsSmartInputMinLineVoltageread-onlymandatoryThe minimum utility line voltage in 1/10 VAC over the previous 1 minute period.
1.3.6.1.4.1.17420.1.1.2.3.2.4ScalarupsSmartInputFrequencyread-onlymandatoryThe current input frequency to the UPS system in 1/10 Hz.
1.3.6.1.4.1.17420.1.1.2.3.2.5ScalarupsSmartInputLineFailCauseread-onlymandatoryThe reason for the occurrence of the last transfer to UPS battery power. The variable is set to noTransfer(1) if there is no transfer yet. The variable is set …
1.3.6.1.4.1.17420.1.1.2.4NodeupsOutputp
1.3.6.1.4.1.17420.1.1.2.4.1NodeupsBaseOutput
1.3.6.1.4.1.17420.1.1.2.4.1.1ScalarupsBaseOutputStatusread-onlymandatoryThe current state of the UPS. If the UPS is unable to determine the state of the UPS this variable is set to unknown(1).
1.3.6.1.4.1.17420.1.1.2.4.1.2ScalarupsBaseOutputPhaseread-onlymandatoryThe current output phase.
1.3.6.1.4.1.17420.1.1.2.4.2NodeupsSmartOutput
1.3.6.1.4.1.17420.1.1.2.4.2.1ScalarupsSmartOutputVoltageread-onlymandatoryThe output voltage of the UPS system in 1/10 VAC.
1.3.6.1.4.1.17420.1.1.2.4.2.2ScalarupsSmartOutputFrequencyread-onlymandatoryThe current output frequency of the UPS system in 1/10 Hz.
1.3.6.1.4.1.17420.1.1.2.4.2.3ScalarupsSmartOutputLoadread-onlymandatoryThe current UPS load expressed in percent of rated capacity.
1.3.6.1.4.1.17420.1.1.2.5NodeupsConfigp
1.3.6.1.4.1.17420.1.1.2.5.1NodeupsBaseConfig
1.3.6.1.4.1.17420.1.1.2.5.1.1ScalarupsBaseConfigNumDevicesread-onlymandatoryThe number of devices that are plugged into the UPS.
1.3.6.1.4.1.17420.1.1.2.5.1.2TableupsBaseConfigDeviceTablenot-accessiblemandatoryA list of devices that are plugged into the UPS. The number of entries is given by the value of upsBaseConfigNumDevices.
1.3.6.1.4.1.17420.1.1.2.5.1.2.1RowupsBaseConfigDeviceEntrynot-accessiblemandatoryThe devices plugged in to the UPS.
1.3.6.1.4.1.17420.1.1.2.5.1.2.1.1ColumnindexOfDeviceread-onlymandatoryThe index of the device that is plugged into the UPS.
1.3.6.1.4.1.17420.1.1.2.5.1.2.1.2ColumnnameOfDeviceread-writemandatoryThe name/description of the device plugged into the UPS.
1.3.6.1.4.1.17420.1.1.2.5.1.2.1.3ColumnvaRatingOfDeviceread-writemandatoryThe volt-amp rating of the device plugged into the UPS.
1.3.6.1.4.1.17420.1.1.2.5.1.2.1.4ColumndeviceAcceptread-writemandatoryAn entry is added if yes, the entry is deleted if no.
1.3.6.1.4.1.17420.1.1.2.5.2NodeupsSmartConfig
1.3.6.1.4.1.17420.1.1.2.5.2.1ScalarupsSmartConfigRatedOutputVoltageread-writemandatoryThe nominal output voltage from the UPS in 1/10 VAC. Possible values are 1000, 1200, 2080, 2200, 2250, 2300 and 2400. NOTE: Only units that are 2200, 2250, 230…
1.3.6.1.4.1.17420.1.1.2.5.2.2ScalarupsSmartConfigHighTransferVoltread-writemandatoryThe maximum line voltage in 1/10 VAC allowed before the UPS system transfers to battery backup. Allowed value depend on the UPS used: 120 Volt units allow sett…
1.3.6.1.4.1.17420.1.1.2.5.2.3ScalarupsSmartConfigLowTransferVoltread-writemandatoryThe minimum line voltage in 1/10 VAC allowed before the UPS system transfers to battery backup. Allowable values depend on the UPS used: 120 Volt units allow s…
1.3.6.1.4.1.17420.1.1.2.5.2.4ScalarupsSmartConfigAlarmread-writemandatoryA flag indicating how the UPS should handle audible line fail alarms.
1.3.6.1.4.1.17420.1.1.2.5.2.5ScalarupsSmartConfigAlarmTimerread-writemandatoryThe time in seconds after initial line failure at which the UPS begins emitting audible alarms (beeping). This timer is observerd only if the value of extContr…
1.3.6.1.4.1.17420.1.1.2.5.2.6ScalarupsSmartConfigMinReturnCapacityread-writemandatoryThe minimum battery capacity as a percent of full capacity required before the UPS will return from a low battery shutdown condition. In other words, the UPS w…
1.3.6.1.4.1.17420.1.1.2.5.2.7ScalarupsSmartConfigSensitivityread-writemandatoryThe sensitivity of the UPS to utility line abnormalities or noises.
1.3.6.1.4.1.17420.1.1.2.5.2.8ScalarupsSmartConfigLowBatteryRunTimeread-writemandatoryThe desired run time in seconds once the low battery condition is reached. Allowed values are 120, 300, 420, or 600 seconds. During this time the UPS will prod…
1.3.6.1.4.1.17420.1.1.2.5.2.9ScalarupsSmartConfigReturnDelayread-writemandatoryThe delay in seconds after utility line power returns before the UPS will turn on. This value is also used when the UPS comes out of a reboot and before the UP…
1.3.6.1.4.1.17420.1.1.2.5.2.10ScalarupsSmartConfigShutoffDelayread-writemandatoryThe delay in seconds the UPS remains on after being told to turn off. Allowed values are 12, 18, 24, 30, 36, 42, 48, 54, 60, 120, 180, 240, 300, 360, 420, 480,…
1.3.6.1.4.1.17420.1.1.2.5.2.11ScalarupsSmartConfigUpsSleepTimeread-writemandatoryThe time in minutes for the UPS to go to 'sleep' when instructed. When in sleep mode, the UPS will not provide output power regardless of the input line state.…
1.3.6.1.4.1.17420.1.1.2.5.2.12ScalarupsSmartConfigSetEEPROMDefaultsread-writemandatoryWRITE: Resets the UPS EEPROM variables to default values. READ: returns 0
1.3.6.1.4.1.17420.1.1.2.6NodeupsControlp
1.3.6.1.4.1.17420.1.1.2.6.1NodeupsBaseControl
1.3.6.1.4.1.17420.1.1.2.6.1.1ScalarupsBaseControlConserveBatteryread-writemandatorySetting this variable to turnUpsOffToConserveBattery(2) causes a UPS on battery to be put into 'sleep' mode immediately. The (10) means suspending time(10 minu…
1.3.6.1.4.1.17420.1.1.2.6.2NodeupsSmartControl
1.3.6.1.4.1.17420.1.1.2.6.2.1ScalarupsSmartControlUpsOffread-writemandatorySetting this variable to turnUpsOff(2) causes the UPS to shut off. When in this state, the UPS will not provide output power regardless of the input line state…
1.3.6.1.4.1.17420.1.1.2.6.2.2ScalarupsSmartControlRebootUpsread-writemandatorySetting this variable to rebootUps(2) causes the UPS to shut off and turn back on. Setting this value to noRebootUps(1) has no effect. The value noRebootUps(1)…
1.3.6.1.4.1.17420.1.1.2.6.2.3ScalarupsSmartControlUpsSleepread-writemandatorySetting this variable to putUpsToSleep(2) causes the UPS to go to sleep for the time specified by upsSmartConfigUpsSleepTime. When in sleep mode, the UPS will …
1.3.6.1.4.1.17420.1.1.2.6.2.4ScalarupsSmartControlSimulatePowerFailread-writemandatorySetting this variable to simulatePowerFailure(2) causes the UPS switch to battery power. Setting this value to noSimulatePowerFailure(1) has no effect. The val…
1.3.6.1.4.1.17420.1.1.2.6.2.5ScalarupsSmartControlFlashAndBeepread-writemandatoryUPS to identify itself by lighting all indicators and beeping. Setting this variable to FlashAndBeep(2) causes the UPS lights all panel indicators and beeps. S…
1.3.6.1.4.1.17420.1.1.2.6.2.6ScalarupsSmartControlTurnOnUpsLoadread-writemandatorySetting this variable to upsSmartControlTurnOnUpsLoad(2) causes the UPS switch back to utility power if utility power is present. Setting this value to noUpsSm…
1.3.6.1.4.1.17420.1.1.2.7NodeupsTestp
1.3.6.1.4.1.17420.1.1.2.7.1NodeupsBaseTest
1.3.6.1.4.1.17420.1.1.2.7.2NodeupsSmartTest
1.3.6.1.4.1.17420.1.1.2.7.2.1ScalarupsSmartTestDiagnosticScheduleread-writemandatoryThe UPS system's automatic battery test schedule.
1.3.6.1.4.1.17420.1.1.2.7.2.2ScalarupsSmartTestDiagnosticsread-writemandatorySetting this variable to testDiagnostics(2) causes the UPS to perform a diagnostic self test. Setting this value to noTestDiagnostics(1) has no effect. The val…
1.3.6.1.4.1.17420.1.1.2.7.2.3ScalarupsSmartTestDiagnosticsResultsread-onlymandatoryThe results of the last UPS diagnostics test performed.
1.3.6.1.4.1.17420.1.1.2.7.2.4ScalarupsSmartTestLastDiagnosticsDateread-onlymandatoryThe date the last UPS diagnostics test was performed in mm/dd/yy format.
1.3.6.1.4.1.17420.1.1.2.7.2.5ScalarupsSmartTestIndicatorsread-writemandatorySetting this variable to testIndicators(2) causes the UPS to perform a front panel indicator (lights) test. Setting this value to noTestIndicators(1) has no ef…
1.3.6.1.4.1.17420.1.1.2.7.2.6ScalarupsSmartTestRuntimeCalibrationread-writemandatorySetting this variable to performCalibration(2) causes the UPS to discharge to calibrate the UPS. The test will only start if the battery capacity is 100 percen…
1.3.6.1.4.1.17420.1.1.2.7.2.7ScalarupsSmartTestCalibrationResultsread-onlymandatoryThe results of the last runtime calibration. Value ok(1) means a successful runtime calibration. Value invalidTest(2) indicates last calibration did not take p…
1.3.6.1.4.1.17420.1.1.2.7.2.8ScalarupsSmartTestCalibrationDateread-onlymandatoryThe date the last UPS runtime calibration was performed in mm/dd/yy format.
1.3.6.1.4.1.17420.1.1.2.8NodeupsThreePhase
1.3.6.1.4.1.17420.1.1.2.8.1NodeupsThreePhaseBatteryGrp
1.3.6.1.4.1.17420.1.1.2.8.1.1ScalarupsThreePhaseBatteryVoltageread-onlymandatoryBattery Voltage
1.3.6.1.4.1.17420.1.1.2.8.1.2ScalarupsThreePhaseBatteryCapacityPercentageread-onlymandatoryBattery Capacity Percentage
1.3.6.1.4.1.17420.1.1.2.8.1.3ScalarupsThreePhaseBatteryTimeRemainread-onlymandatoryBattery Time Remain (unit is Minute)
1.3.6.1.4.1.17420.1.1.2.8.1.4ScalarupsThreePhaseBatteryCurrentread-onlymandatoryBattery Electric Current
1.3.6.1.4.1.17420.1.1.2.8.1.5ScalarupsThreePhaseBatteryTemperatureread-onlymandatoryBattery Temperature
1.3.6.1.4.1.17420.1.1.2.8.2NodeupsThreePhaseInputGrp
1.3.6.1.4.1.17420.1.1.2.8.2.1ScalarupsThreePhaseInputFrequencyread-onlymandatoryInput Frequency
1.3.6.1.4.1.17420.1.1.2.8.2.2ScalarupsThreePhaseInputVoltageRread-onlymandatoryInput VoltageR
1.3.6.1.4.1.17420.1.1.2.8.2.3ScalarupsThreePhaseInputVoltageSread-onlymandatoryInput VoltageS
1.3.6.1.4.1.17420.1.1.2.8.2.4ScalarupsThreePhaseInputVoltageTread-onlymandatoryInput VoltageT
1.3.6.1.4.1.17420.1.1.2.8.3NodeupsThreePhaseOutputGrp
1.3.6.1.4.1.17420.1.1.2.8.3.1ScalarupsThreePhaseOutputFrequencyread-onlymandatoryOutput Frequency
1.3.6.1.4.1.17420.1.1.2.8.3.2ScalarupsThreePhaseOutputVoltageRread-onlymandatoryOutput VoltageR
1.3.6.1.4.1.17420.1.1.2.8.3.3ScalarupsThreePhaseOutputVoltageSread-onlymandatoryOutput VoltageS
1.3.6.1.4.1.17420.1.1.2.8.3.4ScalarupsThreePhaseOutputVoltageTread-onlymandatoryOutput VoltageT
1.3.6.1.4.1.17420.1.1.2.8.3.5ScalarupsThreePhaseOutputLoadPercentageRread-onlymandatoryLoad PercentageR
1.3.6.1.4.1.17420.1.1.2.8.3.6ScalarupsThreePhaseOutputLoadPercentageSread-onlymandatoryLoad PercentageS
1.3.6.1.4.1.17420.1.1.2.8.3.7ScalarupsThreePhaseOutputLoadPercentageTread-onlymandatoryLoad PercentageT
1.3.6.1.4.1.17420.1.1.2.8.4NodeupsThreePhaseBypassGrp
1.3.6.1.4.1.17420.1.1.2.8.4.1ScalarupsThreePhaseBypassSourceFrequencyread-onlymandatoryBypass Frequency
1.3.6.1.4.1.17420.1.1.2.8.4.2ScalarupsThreePhaseBypssSourceVoltageRread-onlymandatoryBypass VoltageR
1.3.6.1.4.1.17420.1.1.2.8.4.3ScalarupsThreePhaseBypssSourceVoltageSread-onlymandatoryBypass VoltageS
1.3.6.1.4.1.17420.1.1.2.8.4.4ScalarupsThreePhaseBypssSourceVoltageTread-onlymandatoryBypass VoltageT
1.3.6.1.4.1.17420.1.1.2.8.5NodeupsThreePhaseDCandRectifierStatusGrp
1.3.6.1.4.1.17420.1.1.2.8.5.1ScalarupsThreePhaseDCandRectifierStatusRecRotErrorread-onlymandatoryRectifier Rotation Error
1.3.6.1.4.1.17420.1.1.2.8.5.2ScalarupsThreePhaseDCandRectifierStatusLowBatteryShutdownread-onlymandatoryLow Battery Shutdown
1.3.6.1.4.1.17420.1.1.2.8.5.3ScalarupsThreePhaseDCandRectifierStatusLowBatteryread-onlymandatoryLow Battery
1.3.6.1.4.1.17420.1.1.2.8.5.4ScalarupsThreePhaseDCandRectifierStatusInAndOutread-onlymandatoryIn And Put
1.3.6.1.4.1.17420.1.1.2.8.5.5ScalarupsThreePhaseDCandRectifierStatusBatteryStatusread-onlymandatoryBack Status
1.3.6.1.4.1.17420.1.1.2.8.5.6ScalarupsThreePhaseDCandRectifierStatusChargeStatusread-onlymandatoryCharge Status
1.3.6.1.4.1.17420.1.1.2.8.5.7ScalarupsThreePhaseDCandRectifierStatusRecOperatingread-onlymandatoryRectifier Operating
1.3.6.1.4.1.17420.1.1.2.8.6NodeupsThreePhaseUPSStatusGrp
1.3.6.1.4.1.17420.1.1.2.8.6.1ScalarupsThreePhaseUPSStatusBypassFreqFailread-onlymandatoryBypass Status
1.3.6.1.4.1.17420.1.1.2.8.6.2ScalarupsThreePhaseUPSStatusManualBypassBreakerread-onlymandatoryBreaker Status
1.3.6.1.4.1.17420.1.1.2.8.6.3ScalarupsThreePhaseUPSStatusACStatusread-onlymandatoryAC Status
1.3.6.1.4.1.17420.1.1.2.8.6.4ScalarupsThreePhaseUPSStaticSwitchModeread-onlymandatorySwitch Mode
1.3.6.1.4.1.17420.1.1.2.8.6.5ScalarupsThreePhaseUPSStatusInverterOperatingread-onlymandatoryOperating
1.3.6.1.4.1.17420.1.1.2.8.7NodeupsThreePhaseFaultStatusGrp
1.3.6.1.4.1.17420.1.1.2.8.7.1ScalarupsThreePhaseFaultStatusEmergencyStopread-onlymandatoryEmergency Stop
1.3.6.1.4.1.17420.1.1.2.8.7.2ScalarupsThreePhaseFaultStatusHighDCShutdownread-onlymandatoryHigh DC Shutdown
1.3.6.1.4.1.17420.1.1.2.8.7.3ScalarupsThreePhaseFaultStatusBypassBreakerread-onlymandatoryBypass Breaker
1.3.6.1.4.1.17420.1.1.2.8.7.4ScalarupsThreePhaseFaultStatusOverLoadread-onlymandatoryOver Load
1.3.6.1.4.1.17420.1.1.2.8.7.5ScalarupsThreePhaseFaultStatusInverterOutputFailread-onlymandatoryOutput Fail
1.3.6.1.4.1.17420.1.1.2.8.7.6ScalarupsThreePhaseFaultStatusOverTemperatureread-onlymandatoryOver Temperature
1.3.6.1.4.1.17420.1.1.2.8.7.7ScalarupsThreePhaseFaultStatusShortCircuitread-onlymandatoryShort Circuit
1.3.6.1.4.1.17420.1.1.2.8.8NodeupsThreePhaseRatingGrp
1.3.6.1.4.1.17420.1.1.2.8.8.1ScalarupsThreePhaseRatingRectifierVoltageread-onlymandatoryRectifier Voltage
1.3.6.1.4.1.17420.1.1.2.8.8.2ScalarupsThreePhaseRatingRectifierFrequencyread-onlymandatoryRectifier Frequency
1.3.6.1.4.1.17420.1.1.2.8.8.3ScalarupsThreePhaseRatingBypassVoltageread-onlymandatoryBypass Voltage
1.3.6.1.4.1.17420.1.1.2.8.8.4ScalarupsThreePhaseRatingBypassFrequencyread-onlymandatoryBypass Frequency
1.3.6.1.4.1.17420.1.1.2.8.8.5ScalarupsThreePhaseRatingOutputVoltageread-onlymandatoryOutput Voltage
1.3.6.1.4.1.17420.1.1.2.8.8.6ScalarupsThreePhaseRatingOutputFrequencyread-onlymandatoryOutput Frequency
1.3.6.1.4.1.17420.1.1.2.8.8.7ScalarupsThreePhaseRatingBatteryVoltageread-onlymandatoryBattery Voltage
1.3.6.1.4.1.17420.1.1.2.8.8.8ScalarupsThreePhaseRatingPowerread-onlymandatoryPower Rating
1.3.6.1.4.1.17420.1.1.2.9NodeupsEnvironment
1.3.6.1.4.1.17420.1.1.2.9.1NodeupsEnvStatus
1.3.6.1.4.1.17420.1.1.2.9.1.1ScalarupsEnvTemperatureread-onlymandatoryThe ambient environment temperature.
1.3.6.1.4.1.17420.1.1.2.9.1.2ScalarupsEnvHumidityread-onlymandatoryThe environment humidity.
1.3.6.1.4.1.17420.1.1.2.9.1.3ScalarupsEnvWaterread-onlymandatoryWater status
1.3.6.1.4.1.17420.1.1.2.9.1.4ScalarupsEnvSmokeread-onlymandatorySmoke status
1.3.6.1.4.1.17420.1.1.2.9.1.5ScalarupsEnvSecurity1read-onlymandatorySecurity status
1.3.6.1.4.1.17420.1.1.2.9.1.6ScalarupsEnvSecurity2read-onlymandatorySecurity status
1.3.6.1.4.1.17420.1.1.2.9.1.7ScalarupsEnvSecurity3read-onlymandatorySecurity status
1.3.6.1.4.1.17420.1.1.2.9.1.8ScalarupsEnvSecurity4read-onlymandatorySecurity status
1.3.6.1.4.1.17420.1.1.2.9.1.9ScalarupsEnvSecurity5read-onlymandatorySecurity status
1.3.6.1.4.1.17420.1.1.2.9.1.10ScalarupsEnvSecurity6read-onlymandatorySecurity status
1.3.6.1.4.1.17420.1.1.2.9.1.11ScalarupsEnvSecurity7read-onlymandatorySecurity status
1.3.6.1.4.1.17420.1.1.2.9.2NodeupsEnvSetting
1.3.6.1.4.1.17420.1.1.2.9.2.1ScalarupsEnvOverTemperatureread-writemandatoryAlarm dupsAlarmOverTemperature on when the environment temperature over the value.
1.3.6.1.4.1.17420.1.1.2.9.2.2ScalarupsEnvUnderTemperatureread-writemandatoryAlarm dupsAlarmUnderTemperature on when the environment temperature below the value.
1.3.6.1.4.1.17420.1.1.2.9.2.3ScalarupsEnvOverHumidityread-writemandatoryAlarm dupsAlarmOverHumidity on when the environment humidity over the value.
1.3.6.1.4.1.17420.1.1.2.9.2.4ScalarupsEnvUnderHumidityread-writemandatoryAlarm dupsAlarmUnderHumidity on when the environment humidity below the value.
1.3.6.1.4.1.17420.2Nodeppcmgmt
1.3.6.1.4.1.17420.2NodeupsOverLoadSEVERE: The UPS has sensed a load greater than 100 percent of its rated capacity.
1.3.6.1.4.1.17420.2.1Nodemconfig
1.3.6.1.4.1.17420.2.1.1ScalarmconfigTrapsReceiversNumread-onlymandatoryThe number of managers to send traps to.
1.3.6.1.4.1.17420.2.1.2TablemconfigTrapsReceiversTablenot-accessiblemandatoryA list of managers to send traps to. The number of entries is given by the value of mconfigNumTrapReceivers
1.3.6.1.4.1.17420.2.1.2.1RowmconfigTrapsReceiversEntrynot-accessiblemandatoryThe managers to send traps to.
1.3.6.1.4.1.17420.2.1.2.1.1ColumntrapsIndexread-onlymandatoryThe index to a trap receiver entry.
1.3.6.1.4.1.17420.2.1.2.1.2ColumntrapsReceiverAddrread-writemandatoryThe IP address of the manager to send a trap to.
1.3.6.1.4.1.17420.2.1.2.1.3ColumnreceiverCommunityStringread-writemandatoryThe community name to use in the trap when sent to the manager.
1.3.6.1.4.1.17420.2.1.2.1.4ColumnseverityLevelread-writemandatoryThe severity threshold of traps to send to the manager. traps are labeled in severity as informational(1), warning(2), severe(3). Only traps of equal or greate…
1.3.6.1.4.1.17420.2.1.2.1.5ColumnreceiverAcceptread-writemandatoryAn entry will become active if yes, and will be deleted if no.
1.3.6.1.4.1.17420.3NodeupsDiagnosticsFailedSEVERE: The UPS failed its internal diagnostic self-test.
1.3.6.1.4.1.17420.4NodeupsDischargedSEVERE: The UPS just started a runtime calibration discharge. The UPS batteries are being discharged.
1.3.6.1.4.1.17420.5NodeupsOnBatteryWARNING: The UPS has switched to battery backup power.
1.3.6.1.4.1.17420.6NodeboostOnWARNING: The UPS has enabled Boost.
1.3.6.1.4.1.17420.7NodelowBatterySEVERE: The UPS batteries are low and will soon be exhausted. If utility power is not restored the UPS will put itself to 'sleep' and immediately cut power to …
1.3.6.1.4.1.17420.8NodecommunicationEstablishedINFORMATION: Communication with the UPS has been established.
1.3.6.1.4.1.17420.9NodepowerRestoredINFORMATION: Utility power has been restored.
1.3.6.1.4.1.17420.10NodeupsDiagnosticsPassedINFORMATION: The UPS passed its internal self-test.
1.3.6.1.4.1.17420.11NodereturnFromLowBatteryINFORMATION: The UPS has returned from a low battery condition.
1.3.6.1.4.1.17420.12NodeupsTurnedOffWARNING: The UPS has been turned 'off' by the management station.
1.3.6.1.4.1.17420.13NodeupsSleepingWARNING: The UPS is entering 'sleep' mode. Power to the load will be cut off.
1.3.6.1.4.1.17420.14NodeupsWokeUpINFORMATION: The UPS woke up from 'sleep' mode. Power to the load has been restored.
1.3.6.1.4.1.17420.15NodeupsRebootStartedWARNING: The UPS has started its reboot sequence. After the specified delay the UPS will perform a reboot.
1.3.6.1.4.1.17420.16NodeenvOverTemperatureWARNING: The environment temperature exceed the normal value.
1.3.6.1.4.1.17420.17NodeenvTemperatureNormalINFORMATION: The environment temperature is normal.
1.3.6.1.4.1.17420.18NodeenvOverHumidityWARNING: The environment humidity exceed the normal value.
1.3.6.1.4.1.17420.19NodeenvHumidityNormalINFORMATION: The environment humidity is normal.
1.3.6.1.4.1.17420.20NodeenvSmokeAbnormalWARNING: Smoke is abnormal.
1.3.6.1.4.1.17420.21NodeenvWaterAbnormalWARNING: Water is abnormal.
1.3.6.1.4.1.17420.22NodeenvSecurityAbnormalWARNING: Security is abnormal.
1.3.6.1.4.1.17420.24NodeenvWaterNormalINFORMATION: Water is normal.
1.3.6.1.4.1.17420.26NodeenvGasAbnormalWARNING: Gas Alarm
1.3.6.1.4.1.17420.27NodeupsTempWARNING: UPS Temperature Overrun
1.3.6.1.4.1.17420.28NodeupsLoadNormalWARNING: UPS Load Normal
1.3.6.1.4.1.17420.29NodeupsTempNormalWARNING: UPS temperature Normal
1.3.6.1.4.1.17420.30NodeenvUnderTemperatureWARNING: The environment temperature below the normal value.
1.3.6.1.4.1.17420.31NodeenvUnderHumidityWARNING: The environment humidity below the normal value.
1.3.6.1.4.1.17420.32NodeupsBypassWARNING: The UPS is entering 'bypass' mode.
1.3.6.1.4.1.17420.33NodeenvSecurity1WARNING: Security1 Alarm.
1.3.6.1.4.1.17420.34NodeenvSecurity2WARNING: Security2 Alarm.
1.3.6.1.4.1.17420.35NodeenvSecurity3WARNING: Security3 Alarm.
1.3.6.1.4.1.17420.36NodeenvSecurity4WARNING: Security4 Alarm.
1.3.6.1.4.1.17420.37NodeenvSecurity5WARNING: Security5 Alarm.
1.3.6.1.4.1.17420.38NodeenvSecurity6WARNING: Security6 Alarm.
1.3.6.1.4.1.17420.39NodeenvSecurity7WARNING: Security7 Alarm.
1.3.6.1.4.1.17420.47NodeupsRecroterrorWARNING: Rectifier Rotation Error
1.3.6.1.4.1.17420.48NodeupsBypassFreFailWARNING: Bypass Frequency Fail
1.3.6.1.4.1.17420.49NodeupsBypassacnormalWARNING: Bypass AC Normal
1.3.6.1.4.1.17420.50NodeupsBypassacabnormalWARNING: Bypass AC Abnormal
1.3.6.1.4.1.17420.51NodeupsTestWARNING: UPS Test
1.3.6.1.4.1.17420.52NodeupsScheduleShutdownWARNING: UPS Schedule Shutdown
1.3.6.1.4.1.17420.53NodeupsBypassReturnThe UPS return from Bypass Mode