34 objects
MIB for NetPing remote sensing and control
Imported Objects
OIDNameAccessStatusDescription
1.3.6.1.4.1.25728Nodelightcom
1.3.6.1.4.1.25728.253IdentitynetPingMIB for NetPing remote sensing and control
1.3.6.1.4.1.25728.911NodenpReboot
1.3.6.1.4.1.25728.911.1ScalarnpSoftRebootread-writecurrentWrite 1 to reboot device after current operations completition
1.3.6.1.4.1.25728.911.2ScalarnpResetStackread-writecurrentWrite 1 to re-initialize network stack
1.3.6.1.4.1.25728.911.3ScalarnpForcedRebootread-writecurrentWrite 1 to immediate forced reboot
1.3.6.1.4.1.25728.8900NodenpIo
1.3.6.1.4.1.25728.8900.1TablenpIoTablenot-accessiblecurrentDigital Input/output Table
1.3.6.1.4.1.25728.8900.1.1RownpIoEntrynot-accessiblecurrentDigital Input/output Table Row
1.3.6.1.4.1.25728.8900.1.1.1ColumnnpIoLineNread-onlycurrentNumber of IO line, from 1 to max supported
1.3.6.1.4.1.25728.8900.1.1.2ColumnnpIoLevelInread-onlycurrentInput level, 0 or 1
1.3.6.1.4.1.25728.8900.1.1.3ColumnnpIoLevelOutread-writecurrentOutput level, 0 or 1. Write -1 to flip output.
1.3.6.1.4.1.25728.8900.1.1.6ColumnnpIoMemoread-onlycurrentIO line memo
1.3.6.1.4.1.25728.8900.1.1.9ColumnnpIoPulseCounterread-writecurrentPulse Counter (counts positive fronts) Write 0 to reset.
1.3.6.1.4.1.25728.8900.1.1.12ColumnnpIoSinglePulseDurationread-writecurrentSet duration of single pulse on IO output line, 100ms to 25500ms, min. step is 100ms
1.3.6.1.4.1.25728.8900.1.1.13ColumnnpIoSinglePulseStartread-writecurrentWrite 1 to start single pulse on IO output. Output will be inverted for time, specified by npIoSinglePulseDuration
1.3.6.1.4.1.25728.8900.2NodenpIoTraps
1.3.6.1.4.1.25728.8900.2.0NodenpIoTrapPrefix
1.3.6.1.4.1.25728.8900.2.0.1NotificationnpIoTrapcurrentInput state of IO line is changed
1.3.6.1.4.1.25728.8900.2.1ScalarnpIoTrapLineNread-onlycurrentTrap data, Number of IO line
1.3.6.1.4.1.25728.8900.2.2ScalarnpIoTrapLevelInread-onlycurrentTrap data, new Input level, 0 or 1
1.3.6.1.4.1.25728.8900.2.6ScalarnpIoTrapMemoread-onlycurrentTrap data, IO line memo
1.3.6.1.4.1.25728.8900.2.21ScalarnpIoTrapLevelIn1read-onlycurrentTrap data, current Input level Line 1, value 0 or 1
1.3.6.1.4.1.25728.8900.2.22ScalarnpIoTrapLevelIn2read-onlycurrentTrap data, current Input level Line 2, value 0 or 1
1.3.6.1.4.1.25728.8900.2.23ScalarnpIoTrapLevelIn3read-onlycurrentTrap data, current Input level Line 3, value 0 or 1
1.3.6.1.4.1.25728.8900.2.24ScalarnpIoTrapLevelIn4read-onlycurrentTrap data, current Input level Line 4, value 0 or 1
1.3.6.1.4.1.25728.9700NodenpElecMeter
1.3.6.1.4.1.25728.9700.1TablenpElecTablenot-accessiblecurrentElectricity Meter Table
1.3.6.1.4.1.25728.9700.1.1RownpElecEntrynot-accessiblecurrentElectricity Meter Table Table Row
1.3.6.1.4.1.25728.9700.1.1.1ColumnnpElecIndexread-onlycurrentNumber of elec.meter, associated with IO line
1.3.6.1.4.1.25728.9700.1.1.2ColumnnpElecPulsesPerKwhread-writecurrentPulses on IO line input per 1 kWh of consumed energy
1.3.6.1.4.1.25728.9700.1.1.3ColumnnpElecPowerread-onlycurrentPower, Watts, based on pulse rate/interval, 5 minute average
1.3.6.1.4.1.25728.9700.1.1.4ColumnnpElecEnergyread-writecurrentEnergy counter, kWh, based on pulse count
1.3.6.1.4.1.25728.9700.1.1.5ColumnnpElecEnergy100read-writecurrentEnergy counter, kWh*100, based on pulse count