DataAire-dap4-al-MIB
200 objects
This is the MIB module for the dap4_al device.
Imported Objects
| SNMPv2-CONF | OBJECT-GROUP |
| SNMPv2-MIB | sysContact sysLocation sysName |
| SNMPv2-SMI | enterprises Integer32 MODULE-IDENTITY OBJECT-TYPE |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.9839 | Nodecarel | |||
| 1.3.6.1.4.1.9839.1 | Nodesystm | |||
| 1.3.6.1.4.1.9839.1.1 | ScalaragentRelease | read-only | current | Release of the Agent. |
| 1.3.6.1.4.1.9839.1.2 | ScalaragentCode | read-only | current | Code of the Agent. 2=pCOWeb. |
| 1.3.6.1.4.1.9839.2 | Nodeinstruments | |||
| 1.3.6.1.4.1.9839.2.0 | NodepCOWebInfo | |||
| 1.3.6.1.4.1.9839.2.0.10 | NodepCOStatusgroup | |||
| 1.3.6.1.4.1.9839.2.0.10.1 | ScalarpCOId1-Status | read-only | current | Status of pCOId1. 0=Offline, 1=Init, 2=Online |
| 1.3.6.1.4.1.9839.2.0.11 | NodepCOErrorsNumbergroup | |||
| 1.3.6.1.4.1.9839.2.0.11.1 | ScalarpCOId1-ErrorsNumber | read-only | current | Number of Communication Errors from pCOId1 to pCOWeb. |
| 1.3.6.1.4.1.9839.2.1 | Identitydap4-alMIB | This is the MIB module for the dap4_al device. | ||
| 1.3.6.1.4.1.9839.2.1.1 | NodedigitalObjects | |||
| 1.3.6.1.4.1.9839.2.1.1.1 | Scalardehum-on | read-only | current | Dehumidify mode is running |
| 1.3.6.1.4.1.9839.2.1.1.2 | Scalarhum-on | read-only | current | Humidifier is running |
| 1.3.6.1.4.1.9839.2.1.1.3 | Scalarengy-on | read-only | current | Energy saver is running |
| 1.3.6.1.4.1.9839.2.1.1.4 | Scalarcool-inhibit | read-only | current | Cooling inhibit from Zone Master |
| 1.3.6.1.4.1.9839.2.1.1.5 | Scalarheat-held | read-only | current | Heat inhibited due to alarm condition |
| 1.3.6.1.4.1.9839.2.1.1.6 | Scalarhumidifier-inhibit | read-only | current | Humidifier stopped due to alarm |
| 1.3.6.1.4.1.9839.2.1.1.7 | Scalardehum-inhibit | read-only | current | Dehum is inhibited |
| 1.3.6.1.4.1.9839.2.1.1.8 | Scalarrht-during-dehum | read-only | current | reheat during dehum |
| 1.3.6.1.4.1.9839.2.1.1.9 | Scalarfloor-wtr-alm | read-only | current | Water under floor alarm |
| 1.3.6.1.4.1.9839.2.1.1.10 | Scalarair-flow-alm | read-only | current | No air flow alarm |
| 1.3.6.1.4.1.9839.2.1.1.11 | Scalarfilter-alm | read-only | current | Dirty filter from digital input |
| 1.3.6.1.4.1.9839.2.1.1.12 | Scalarhumidifier-alm | read-only | current | Alarm from humidifier digital input |
| 1.3.6.1.4.1.9839.2.1.1.13 | Scalarfirestat-alm | read-only | current | Temperature of return air above firestat alarm set point |
| 1.3.6.1.4.1.9839.2.1.1.14 | Scalarshortcycle-alm | read-only | current | One or more comps has short cycled |
| 1.3.6.1.4.1.9839.2.1.1.15 | Scalarhumidity-fail | read-only | current | Sensor is out of range |
| 1.3.6.1.4.1.9839.2.1.1.16 | Scalarret-air-fail | read-only | current | Sensor is out of range |
| 1.3.6.1.4.1.9839.2.1.1.17 | Scalarmaint-alm | read-only | current | Maintenance Schedule Due alarm |
| 1.3.6.1.4.1.9839.2.1.1.18 | Scalarc1-hp-alm | read-only | current | High pressure alarm |
| 1.3.6.1.4.1.9839.2.1.1.19 | Scalarc1-lp-alm | read-only | current | Low pressure alarm |
| 1.3.6.1.4.1.9839.2.1.1.20 | Scalarc2-hp-alm | read-only | current | High pressure alarm |
| 1.3.6.1.4.1.9839.2.1.1.21 | Scalarc2-lp-alm | read-only | current | Low pressure alarm |
| 1.3.6.1.4.1.9839.2.1.1.22 | Scalarsmoke-alm | read-only | current | Smoke detected from digital input |
| 1.3.6.1.4.1.9839.2.1.1.23 | Scalarwtr-flow-alm | read-only | current | No water flow alarm |
| 1.3.6.1.4.1.9839.2.1.1.24 | Scalardisch-air-fail | read-only | current | Sensor is out of range |
| 1.3.6.1.4.1.9839.2.1.1.25 | Scalarra-tmp-hi-alm | read-only | current | Temperature of return air above alarm set point |
| 1.3.6.1.4.1.9839.2.1.1.26 | Scalarra-tmp-lo-alm | read-only | current | Temperature of return air below alarm set point |
| 1.3.6.1.4.1.9839.2.1.1.27 | Scalarhum-hi-alm | read-only | current | Humidity above alarm set point |
| 1.3.6.1.4.1.9839.2.1.1.28 | Scalarhum-lo-alm | read-only | current | Humidity below alarm set point |
| 1.3.6.1.4.1.9839.2.1.1.29 | Scalarfan-overload | read-only | current | Fan overload |
| 1.3.6.1.4.1.9839.2.1.1.30 | Scalarstdby-pump-on | read-only | current | Standby pump on: Check primary pump -Optional alarm. Pump failure input signal required |
| 1.3.6.1.4.1.9839.2.1.1.31 | Scalarcust-msg-sw1 | read-only | current | Custom alarm #1 -Optional alarm. External alarm input required. Factory programmed custom message required |
| 1.3.6.1.4.1.9839.2.1.1.32 | Scalarcust-msg-sw2 | read-only | current | Custom alarm #2 -Optional alarm. External alarm input required. Factory programmed custom message required |
| 1.3.6.1.4.1.9839.2.1.1.33 | Scalarcust-msg-sw3 | read-only | current | Custom alarm #3 -Optional alarm. External alarm input required. Factory programmed custom message required |
| 1.3.6.1.4.1.9839.2.1.1.34 | Scalarcust-msg-sw4 | read-only | current | Custom alarm #4 -Optional alarm. External alarm input required. Factory programmed custom message required |
| 1.3.6.1.4.1.9839.2.1.1.35 | Scalarhumsw-inhibit | read-only | current | Humidifier stopped due to custom alarm switch |
| 1.3.6.1.4.1.9839.2.1.1.36 | Scalarheat-inhibit | read-only | current | Heat inhibited due to custom switch alarm condition |
| 1.3.6.1.4.1.9839.2.1.1.37 | Scalarrht-hum-inhibit | read-only | current | Reheat and humidification inhibited from operation |
| 1.3.6.1.4.1.9839.2.1.1.38 | Scalardisch-tmp-lo-alm | read-only | current | Temperature of discharge air below alarm set point |
| 1.3.6.1.4.1.9839.2.1.1.39 | Scalaroverride-alm | read-only | current | Manual override: Check bypass switches - Standard alarm. Manual override switch is on |
| 1.3.6.1.4.1.9839.2.1.1.40 | Scalarcondensation-alm | read-only | current | High condensation from digital input |
| 1.3.6.1.4.1.9839.2.1.1.41 | Scalarunit-in-standby | read-only | current | Unit in standby, all functions held off - Optional alarm. Control input signal required Factory setting required |
| 1.3.6.1.4.1.9839.2.1.1.42 | Scalarcw-sns-fail | read-only | current | Sensor is out of range |
| 1.3.6.1.4.1.9839.2.1.1.43 | Scalarhumsw-chk-cyl | read-only | current | Humidifier stopped due to custom alarm switch |
| 1.3.6.1.4.1.9839.2.1.1.44 | Scalarbms-cooling-inhibit | read-write | current | Cooling operation inhibited by BMS |
| 1.3.6.1.4.1.9839.2.1.1.45 | Scalarbms-heat-inhibit | read-write | current | Heat inhibited due to bms |
| 1.3.6.1.4.1.9839.2.1.1.46 | Scalarbms-humidifier-inhibit | read-write | current | Humidifier operation inhibited by BMS |
| 1.3.6.1.4.1.9839.2.1.1.47 | Scalarbms-dehum-inhibit | read-write | current | Dehumidify mode inhibited by bms |
| 1.3.6.1.4.1.9839.2.1.1.48 | Scalarfan-inhibit-bms | read-write | current | Inhibit fan by bms |
| 1.3.6.1.4.1.9839.2.1.1.49 | Scalarhum-expect | read-only | current | Reduces control humidity cycling |
| 1.3.6.1.4.1.9839.2.1.1.50 | Scalarusashr-f-c | read-write | current | Temperature Mode 0=_C 1=_F |
| 1.3.6.1.4.1.9839.2.1.1.52 | Scalarlead-comp | read-only | current | Lead compressor select 0= C1, 1= C2 |
| 1.3.6.1.4.1.9839.2.1.1.53 | Scalarwtrvlv-dir | read-only | current | Water valve direct or reverse acting |
| 1.3.6.1.4.1.9839.2.1.1.54 | Scalarups-on-alm | read-only | current | Alarm: UPS power on: Check main power -Optional alarm. External alarm input required |
| 1.3.6.1.4.1.9839.2.1.1.55 | Scalarpwrup-alm | read-only | current | Loss of power requires manual reset of alarm |
| 1.3.6.1.4.1.9839.2.1.1.56 | Scalarseetag-cust-alm1 | read-only | current | Local alarm #1: See tag inside door =Optional alarm. External alarm input required |
| 1.3.6.1.4.1.9839.2.1.1.57 | Scalarseetag-cust-alm2 | read-only | current | Local alarm #2: See tag inside door =Optional alarm. External alarm input required |
| 1.3.6.1.4.1.9839.2.1.1.58 | Scalarseetag-cust-alm3 | read-only | current | Local alarm #3: See tag inside door =Optional alarm. External alarm input required |
| 1.3.6.1.4.1.9839.2.1.1.59 | Scalarseetag-cust-alm4 | read-only | current | Local alarm #4: See tag inside door =Optional alarm. External alarm input required |
| 1.3.6.1.4.1.9839.2.1.1.60 | Scalarshortcycle-alm-en | read-only | current | Enable short cycle alarm of the compressors |
| 1.3.6.1.4.1.9839.2.1.1.61 | Scalarsuperv-off | read-only | current | Supervisor (BMS) On-Off. Show the state OFFbyBMS in main mask (1: Off; 0: On |
| 1.3.6.1.4.1.9839.2.1.1.62 | ScalarBMS-heartbeat | read-only | current | Bms heartbeat - pCO looks for update every 10 minutes |
| 1.3.6.1.4.1.9839.2.1.2 | NodeanalogObjects | |||
| 1.3.6.1.4.1.9839.2.1.2.1 | Scalarret-air-tmp | read-only | current | Temperature of return air |
| 1.3.6.1.4.1.9839.2.1.2.2 | Scalarminmax-24hr-retair-maximum | read-only | current | Maximum Return air temp in last 24hrs |
| 1.3.6.1.4.1.9839.2.1.2.3 | Scalarminmax-24hr-retair-minumum | read-only | current | Minimum Return air temp in last 24hrs |
| 1.3.6.1.4.1.9839.2.1.2.4 | Scalartemp-setpoint | read-write | current | Temperature setpoint |
| 1.3.6.1.4.1.9839.2.1.2.5 | Scalartemp-deadband | read-write | current | Amount from setpoint before a comp is staged on |
| 1.3.6.1.4.1.9839.2.1.2.6 | Scalarhumidity-ain-offs | read-only | current | Humidity Sensor Calibration |
| 1.3.6.1.4.1.9839.2.1.2.7 | Scalarreturn-ain-offs | read-only | current | Return Temperature Sensor Calibration |
| 1.3.6.1.4.1.9839.2.1.2.8 | Scalarcw-tmp | read-only | current | Temperature of chilled water |
| 1.3.6.1.4.1.9839.2.1.2.9 | Scalardisch-air-tmp | read-only | current | Temperature of discharge air |
| 1.3.6.1.4.1.9839.2.1.2.10 | Scalardischarge-ain-offs | read-only | current | Discharge Temperature Sensor Calibration - Optional discharge air temperature sensor required (B9) |
| 1.3.6.1.4.1.9839.2.1.2.11 | Scalarcw-ain-offs | read-only | current | Chilled Water Temperature Sensor Calibration - Optional chilled water temperature sensor required (B10) |
| 1.3.6.1.4.1.9839.2.1.2.12 | Scalarengsaver-setpoint | read-write | current | Temperature setpoint where chilled water will is requested |
| 1.3.6.1.4.1.9839.2.1.2.13 | Scalaropt1-analog | read-only | current | Value of the analog input |
| 1.3.6.1.4.1.9839.2.1.2.14 | Scalaropt2-analog | read-only | current | Value of the analog input |
| 1.3.6.1.4.1.9839.2.1.2.15 | Scalaropt3-analog | read-only | current | Value of the analog input |
| 1.3.6.1.4.1.9839.2.1.2.16 | Scalaropt4-analog | read-only | current | Value of the analog input |
| 1.3.6.1.4.1.9839.2.1.2.17 | Scalaropt-sns-1-y1 | read-only | current | Analog Sensor 1 Minimum Value |
| 1.3.6.1.4.1.9839.2.1.2.18 | Scalaropt-sns-1-y2 | read-only | current | Analog Sensor 1 Maximum Value |
| 1.3.6.1.4.1.9839.2.1.2.19 | Scalaropt-sns-1-ain-offs | read-only | current | Analog Sensor 1 Calibration |
| 1.3.6.1.4.1.9839.2.1.2.20 | Scalaropt-sns-2-y1 | read-only | current | Analog Sensor 2 Minimum Value |
| 1.3.6.1.4.1.9839.2.1.2.21 | Scalaropt-sns-2-y2 | read-only | current | Analog Sensor 2 Maximum Value |
| 1.3.6.1.4.1.9839.2.1.2.22 | Scalaropt-sns-2-ain-offs | read-only | current | Analog Sensor 2 Calibration |
| 1.3.6.1.4.1.9839.2.1.2.23 | Scalaropt-sns-3-y1 | read-only | current | Analog Sensor 3 Minimum Value |
| 1.3.6.1.4.1.9839.2.1.2.24 | Scalaropt-sns-3-y2 | read-only | current | Analog Sensor 3 Maximum Value |
| 1.3.6.1.4.1.9839.2.1.2.25 | Scalaropt-sns-3-ain-offs | read-only | current | Analog Sensor 3 Calibration |
| 1.3.6.1.4.1.9839.2.1.2.26 | Scalaropt-sns-4-y1 | read-only | current | Analog Sensor 4 Minimum Value |
| 1.3.6.1.4.1.9839.2.1.2.27 | Scalaropt-sns-4-y2 | read-only | current | Analog Sensor 4 Maximum Value |
| 1.3.6.1.4.1.9839.2.1.2.28 | Scalaropt-sns-4-ain-offs | read-only | current | Analog Sensor 4 Calibration |
| 1.3.6.1.4.1.9839.2.1.3 | NodeintegerObjects | |||
| 1.3.6.1.4.1.9839.2.1.3.1 | Scalardisch-air-lo-sp | read-write | current | Lower Limit alarm of discharge air temp |
| 1.3.6.1.4.1.9839.2.1.3.2 | Scalarhumidity-dis | read-only | current | Relative humidity displayed as xx% |
| 1.3.6.1.4.1.9839.2.1.3.3 | Scalarstages-on | read-only | current | Cooling Stages On, DX only |
| 1.3.6.1.4.1.9839.2.1.3.4 | Scalarheaters-on | read-only | current | Number of heat stages running |
| 1.3.6.1.4.1.9839.2.1.3.5 | Scalarminmax-24hr-hum-maximum | read-only | current | Maximum humidity in last 24hrs |
| 1.3.6.1.4.1.9839.2.1.3.6 | Scalarminmax-24hr-hum-minumum | read-only | current | Minimum humidity in last 24hrs |
| 1.3.6.1.4.1.9839.2.1.3.7 | Scalarcomp-duty | read-only | current | Cooling Utilization Over Last Hour -Percentage of cooling is used in the last hour of operation; this point applies to DX unit. |
| 1.3.6.1.4.1.9839.2.1.3.8 | Scalarheat-duty | read-only | current | Heating Utilization Over Last Hour -Percentage of heating is used in the last hour of operation |
| 1.3.6.1.4.1.9839.2.1.3.9 | Scalarhum-duty | read-only | current | Humidifier Utilization Over Last Hour -Percentage of humidifier is used in the last hour of operation |
| 1.3.6.1.4.1.9839.2.1.3.10 | Scalarc1-hours-h | read-only | current | Compressor 1 Runtime -This point applies to DX unit with one compressor -high |
| 1.3.6.1.4.1.9839.2.1.3.11 | Scalarc1-hours-l | read-only | current | Compressor 1 Runtime -This point applies to DX unit with one compressor -low |
| 1.3.6.1.4.1.9839.2.1.3.12 | Scalarc2-hours-h | read-only | current | Compressor 2 Runtime -This point applies to DX unit with dual compressor - high |
| 1.3.6.1.4.1.9839.2.1.3.13 | Scalarc2-hours-l | read-only | current | Compressor 2 Runtime -This point applies to DX unit with dual compressor - low |
| 1.3.6.1.4.1.9839.2.1.3.14 | Scalarht1-hours-h | read-only | current | Heater 1 Runtime - high |
| 1.3.6.1.4.1.9839.2.1.3.15 | Scalarht1-hours-l | read-only | current | Heater 1 Runtime - low |
| 1.3.6.1.4.1.9839.2.1.3.16 | Scalarcurrent-second | read-only | current | Current second |
| 1.3.6.1.4.1.9839.2.1.3.17 | Scalarcurrent-minute | read-only | current | Current minute |
| 1.3.6.1.4.1.9839.2.1.3.18 | Scalarcurrent-hour | read-only | current | Current hour |
| 1.3.6.1.4.1.9839.2.1.3.19 | Scalarcurrent-day | read-only | current | Current day |
| 1.3.6.1.4.1.9839.2.1.3.20 | Scalarcurrent-month | read-only | current | Current month |
| 1.3.6.1.4.1.9839.2.1.3.21 | Scalarcurrent-year | read-only | current | Current year |
| 1.3.6.1.4.1.9839.2.1.3.22 | Scalarfirestat-sp | read-write | current | Alarm settting of return air temp to determine there is a fire |
| 1.3.6.1.4.1.9839.2.1.3.23 | Scalarhum-hi-sp | read-write | current | Humidity upper limit alarm |
| 1.3.6.1.4.1.9839.2.1.3.24 | Scalarret-air-hi-sp | read-write | current | Upper limit alarm of return air temp |
| 1.3.6.1.4.1.9839.2.1.3.25 | Scalarhum-lo-sp | read-write | current | Humidity lower limit alarm |
| 1.3.6.1.4.1.9839.2.1.3.26 | Scalarret-air-lo-sp | read-write | current | Lower limit alarm of return air temp |
| 1.3.6.1.4.1.9839.2.1.3.27 | Scalarhum-deadband | read-write | current | amount hum must change from setpoint before acting |
| 1.3.6.1.4.1.9839.2.1.3.28 | Scalarhum-setpoint | read-write | current | humidity setpoint |
| 1.3.6.1.4.1.9839.2.1.3.29 | Scalarstart-dly | read-write | current | Time before the system starts up |
| 1.3.6.1.4.1.9839.2.1.3.30 | Scalaralm1-del | read-only | current | Optional Alarm 1 Delay |
| 1.3.6.1.4.1.9839.2.1.3.31 | Scalaralm2-del | read-only | current | Optional Alarm 2 Delay |
| 1.3.6.1.4.1.9839.2.1.3.32 | Scalaralm3-del | read-only | current | Optional Alarm 3 Delay |
| 1.3.6.1.4.1.9839.2.1.3.33 | Scalaralarm1-txt | read-only | current | Message on optional alarm screen, some also add function |
| 1.3.6.1.4.1.9839.2.1.3.34 | Scalaralarm2-txt | read-only | current | Message on optional alarm screen, some also add function |
| 1.3.6.1.4.1.9839.2.1.3.35 | Scalaralarm3-txt | read-only | current | Message on optional alarm screen, some also add function |
| 1.3.6.1.4.1.9839.2.1.3.36 | Scalaralarm4-txt | read-only | current | Message on optional alarm screen, some also add function |
| 1.3.6.1.4.1.9839.2.1.3.37 | Scalarcomp-sel | read-only | current | Comps 0=none, 1=one, 2=one+UL, 3=two, 4=two+UL, 5=Four/two circuit |
| 1.3.6.1.4.1.9839.2.1.3.38 | Scalardehum-mode | read-only | current | 0=none, 1= comp limited, 2=twocomp limited, 3= comp unlimited, 4=twocomp unlimited |
| 1.3.6.1.4.1.9839.2.1.3.39 | Scalarreheat-sel | read-only | current | Number of heat stages |
| 1.3.6.1.4.1.9839.2.1.3.40 | Scalarhum-sel | read-only | current | 0=none, 1=comp mod, 2=comp non, 3= comf mod, 4= conf non mod |
| 1.3.6.1.4.1.9839.2.1.3.41 | Scalaralm-contact-msg | read-only | current | Text displayed on all alarm screens |
| 1.3.6.1.4.1.9839.2.1.3.42 | Scalarpowerup-sel | read-only | current | 0= start wo/alarm, 1= start w/alarm, 2= requires reset of alarm |
| 1.3.6.1.4.1.9839.2.1.3.43 | Scalarbuzzer-select | read-only | current | 0=None, 1=short beeps, 2=long beep, 3=Constant |
| 1.3.6.1.4.1.9839.2.1.3.44 | Scalarcw-disp | read-only | current | % of 10volts of analog output #1 |
| 1.3.6.1.4.1.9839.2.1.3.45 | Scalarwtrvlv-duty | read-only | current | Chilled Water Utilization Over Last Hour - This applies to Chilled water or Energy saver units. |
| 1.3.6.1.4.1.9839.2.1.3.46 | Scalarhum-hours-h | read-only | current | Humidifier Runtime - high |
| 1.3.6.1.4.1.9839.2.1.3.47 | Scalarhum-hours-l | read-only | current | Humidifier Runtime - low |
| 1.3.6.1.4.1.9839.2.1.3.48 | Scalarblower-hours-h | read-only | current | Blower Runtime - high |
| 1.3.6.1.4.1.9839.2.1.3.49 | Scalarblower-hours-l | read-only | current | Blower Runtime - low |
| 1.3.6.1.4.1.9839.2.1.3.50 | Scalaralm4-del | read-only | current | Optional Alarm 4 Delay |
| 1.3.6.1.4.1.9839.2.1.3.51 | Scalarassist-sel | read-only | current | 0= no comp assist, 1=one comp assist, 2= two comp assist, 3... 4... |
| 1.3.6.1.4.1.9839.2.1.3.52 | Scalarwtrvlv-sel | read-only | current | Water valve type 0=none, 1=chill, 2=Engy, 3=Aux chill, 4=Disc Reg |
| 1.3.6.1.4.1.9839.2.1.3.53 | Scalarwtrvlv-volts-sel | read-only | current | Water valve voltage 0= 0-10, 1=2-10, 2=7-10, 3=6-9, 4=4-7 |
| 1.3.6.1.4.1.9839.2.1.3.54 | Scalarhum-volts | read-only | current | % of 10volts of analog output #2 |
| 1.3.6.1.4.1.9839.2.1.3.55 | Scalardehum-hours-h | read-only | current | Dehumidifier Runtime - High |
| 1.3.6.1.4.1.9839.2.1.3.56 | Scalardehum-hours-l | read-only | current | Dehumidifier Runtime - Low |
| 1.3.6.1.4.1.9839.2.1.3.58 | Scalarautoflush-dly | read-only | current | Time between drain cycles 0=12hr, 1=24hr, 2=48hr, 3=96hr, 4=None |
| 1.3.6.1.4.1.9839.2.1.3.59 | Scalary4-out | read-only | current | Value sent to optional analog output#1 |
| 1.3.6.1.4.1.9839.2.1.3.60 | Scalary5-out | read-only | current | Value sent to optional analog output#2 |
| 1.3.6.1.4.1.9839.2.1.3.61 | Scalarair-flow | read-only | current | Current Fan Airflow - Based on calculated Pressure Diff formula |
| 1.3.6.1.4.1.9839.2.1.3.62 | Scalaropt-snsr1-name | read-only | current | Name of the sensor |
| 1.3.6.1.4.1.9839.2.1.3.63 | Scalaropt-sns-1-ain-type | read-only | current | Analog Sensor 1 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170} |
| 1.3.6.1.4.1.9839.2.1.3.64 | Scalaropt-snsr2-name | read-only | current | Name of the sensor |
| 1.3.6.1.4.1.9839.2.1.3.65 | Scalaropt-sns-2-ain-type | read-only | current | Analog Sensor 2 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170} |
| 1.3.6.1.4.1.9839.2.1.3.66 | Scalaropt-snsr3-name | read-only | current | Name of the sensor |
| 1.3.6.1.4.1.9839.2.1.3.67 | Scalaropt-sns-3-ain-type | read-only | current | Analog Sensor 3 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170} |
| 1.3.6.1.4.1.9839.2.1.3.68 | Scalaropt-snsr4-name | read-only | current | Name of the sensor |
| 1.3.6.1.4.1.9839.2.1.3.69 | Scalaropt-sns-4-ain-type | read-only | current | Analog Sensor 4 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170} |
| 1.3.6.1.4.1.9839.2.1.3.70 | Scalarcw-fan-speed-bms | read-write | current | CW Fan speed (%) sent via BMS |
| 1.3.6.1.4.1.9839.2.1.3.71 | Scalardx-fan-speed-bms | read-write | current | DX Fan speed (%) sent via BMS |
| 1.3.6.1.4.1.9839.2.1.3.72 | Scalarfan-speed-max | read-write | current | Maximum Fan speed (% of output) modulation. |
| 1.3.6.1.4.1.9839.2.1.3.73 | Scalarfan-speed-min | read-write | current | Minimum Fan speed (% of output) modulation from pressure. |
| 1.3.6.1.4.1.9839.2.1.3.74 | Scalarfan-pr-sp | read-write | current | Fan pressure setpoint (0.01 inches of water) |
| 1.3.6.1.4.1.9839.2.1.3.75 | Scalarfan-pr-band | read-write | current | Fan pressure band (0.01 inches of water) |
| 1.3.6.1.4.1.9839.2.1.3.76 | Scalarfan-af-max | read-write | current | Maximum air flow limit of setpoint from BMS or valve modulation. |
| 1.3.6.1.4.1.9839.2.1.3.77 | Scalarfan-af-min | read-write | current | Minimum air flow limit of setpoint from BMS or valve modulation. |
| 1.3.6.1.4.1.9839.2.1.3.78 | Scalarfan-kfactor | read-write | current | Fan K Factor |
| 1.3.6.1.4.1.9839.2.1.3.79 | Scalarnum-fans | read-write | current | Number of fans installed in this unit |
| 1.3.6.1.4.1.9839.2.1.3.81 | Scalarht2-hours-h | read-only | current | Heater 2 Runtime - high |
| 1.3.6.1.4.1.9839.2.1.3.82 | Scalarht2-hours-l | read-only | current | Heater 2 Runtime - low |
| 1.3.6.1.4.1.9839.2.1.3.83 | Scalarht3-hours-h | read-only | current | Heater 3 Runtime - high |
| 1.3.6.1.4.1.9839.2.1.3.84 | Scalarht3-hours-l | read-only | current | Heater 3 Runtime - low |
| 1.3.6.1.4.1.9839.2.1.3.85 | Scalarengy-hours-h | read-only | current | Energy Saver Runtime - This optional point applies to energy saver units only -high |
| 1.3.6.1.4.1.9839.2.1.3.86 | Scalarengy-hours-l | read-only | current | Energy Saver Runtime - This optional point applies to energy saver units only - low |
| 1.3.6.1.4.1.9839.2.1.3.87 | Scalarcw-hours-h | read-only | current | Chilled Water Runtime - This applies to chilled water units only - high |
| 1.3.6.1.4.1.9839.2.1.3.88 | Scalarcw-hours-l | read-only | current | Chilled Water Runtime - This applies to chilled water units only - low |
| 1.3.6.1.4.1.9839.2.1.3.89 | Scalarc3-hours-h | read-only | current | Compressor 3 Runtime - This applies when unit has four stages tandem compressors - high |
| 1.3.6.1.4.1.9839.2.1.3.90 | Scalarc3-hours-l | read-only | current | Compressor 3 Runtime - This applies when unit has four stages tandem compressors - low |
| 1.3.6.1.4.1.9839.2.1.3.91 | Scalarc4-hours-l | read-only | current | Compressor 4 Runtime - This applies when unit has four stages tandem compressors. - high |
| 1.3.6.1.4.1.9839.2.1.3.92 | Scalarc4-hours-h | read-only | current | Compressor 4 Runtime - This applies when unit has four stages tandem compressors. - low |
| 1.3.6.1.4.1.9839.2.1.3.93 | Scalarcond-hours-h | read-only | current | Condenser Runtime - high |
| 1.3.6.1.4.1.9839.2.1.3.94 | Scalarcond-hours-l | read-only | current | Condenser Runtime - low |
| 1.3.6.1.4.1.9839.2.1.3.95 | Scalardx-fan-speed | read-only | current | Fan speed (% of output) when compressor cooling. |
| 1.3.6.1.4.1.9839.2.1.3.96 | Scalarcw-fan-speed | read-only | current | Fan speed (% of output) when cold water cooling. |
| 1.3.6.1.4.1.9839.2.1.3.97 | Scalarfan-af-dx-sp | read-only | current | Fan air flow setpoint for DX unit (cfm) |
| 1.3.6.1.4.1.9839.2.1.3.98 | Scalarfan-af-cw-sp | read-only | current | Fan air flow setpoint for CW unit (cfm) |
| 1.3.6.1.4.1.9839.2.1.3.99 | Scalarzm-airflow-sp | read-write | current | Zone Airflow Setpoint kcfm |