DataAire-dap4-al-MIB

200 objects
This is the MIB module for the dap4_al device.
Imported Objects
SNMPv2-CONFOBJECT-GROUP
SNMPv2-MIBsysContact sysLocation sysName
SNMPv2-SMIenterprises Integer32 MODULE-IDENTITY OBJECT-TYPE
OIDNameAccessStatusDescription
1.3.6.1.4.1.9839Nodecarel
1.3.6.1.4.1.9839.1Nodesystm
1.3.6.1.4.1.9839.1.1ScalaragentReleaseread-onlycurrentRelease of the Agent.
1.3.6.1.4.1.9839.1.2ScalaragentCoderead-onlycurrentCode of the Agent. 2=pCOWeb.
1.3.6.1.4.1.9839.2Nodeinstruments
1.3.6.1.4.1.9839.2.0NodepCOWebInfo
1.3.6.1.4.1.9839.2.0.10NodepCOStatusgroup
1.3.6.1.4.1.9839.2.0.10.1ScalarpCOId1-Statusread-onlycurrentStatus of pCOId1. 0=Offline, 1=Init, 2=Online
1.3.6.1.4.1.9839.2.0.11NodepCOErrorsNumbergroup
1.3.6.1.4.1.9839.2.0.11.1ScalarpCOId1-ErrorsNumberread-onlycurrentNumber of Communication Errors from pCOId1 to pCOWeb.
1.3.6.1.4.1.9839.2.1Identitydap4-alMIBThis is the MIB module for the dap4_al device.
1.3.6.1.4.1.9839.2.1.1NodedigitalObjects
1.3.6.1.4.1.9839.2.1.1.1Scalardehum-onread-onlycurrentDehumidify mode is running
1.3.6.1.4.1.9839.2.1.1.2Scalarhum-onread-onlycurrentHumidifier is running
1.3.6.1.4.1.9839.2.1.1.3Scalarengy-onread-onlycurrentEnergy saver is running
1.3.6.1.4.1.9839.2.1.1.4Scalarcool-inhibitread-onlycurrentCooling inhibit from Zone Master
1.3.6.1.4.1.9839.2.1.1.5Scalarheat-heldread-onlycurrentHeat inhibited due to alarm condition
1.3.6.1.4.1.9839.2.1.1.6Scalarhumidifier-inhibitread-onlycurrentHumidifier stopped due to alarm
1.3.6.1.4.1.9839.2.1.1.7Scalardehum-inhibitread-onlycurrentDehum is inhibited
1.3.6.1.4.1.9839.2.1.1.8Scalarrht-during-dehumread-onlycurrentreheat during dehum
1.3.6.1.4.1.9839.2.1.1.9Scalarfloor-wtr-almread-onlycurrentWater under floor alarm
1.3.6.1.4.1.9839.2.1.1.10Scalarair-flow-almread-onlycurrentNo air flow alarm
1.3.6.1.4.1.9839.2.1.1.11Scalarfilter-almread-onlycurrentDirty filter from digital input
1.3.6.1.4.1.9839.2.1.1.12Scalarhumidifier-almread-onlycurrentAlarm from humidifier digital input
1.3.6.1.4.1.9839.2.1.1.13Scalarfirestat-almread-onlycurrentTemperature of return air above firestat alarm set point
1.3.6.1.4.1.9839.2.1.1.14Scalarshortcycle-almread-onlycurrentOne or more comps has short cycled
1.3.6.1.4.1.9839.2.1.1.15Scalarhumidity-failread-onlycurrentSensor is out of range
1.3.6.1.4.1.9839.2.1.1.16Scalarret-air-failread-onlycurrentSensor is out of range
1.3.6.1.4.1.9839.2.1.1.17Scalarmaint-almread-onlycurrentMaintenance Schedule Due alarm
1.3.6.1.4.1.9839.2.1.1.18Scalarc1-hp-almread-onlycurrentHigh pressure alarm
1.3.6.1.4.1.9839.2.1.1.19Scalarc1-lp-almread-onlycurrentLow pressure alarm
1.3.6.1.4.1.9839.2.1.1.20Scalarc2-hp-almread-onlycurrentHigh pressure alarm
1.3.6.1.4.1.9839.2.1.1.21Scalarc2-lp-almread-onlycurrentLow pressure alarm
1.3.6.1.4.1.9839.2.1.1.22Scalarsmoke-almread-onlycurrentSmoke detected from digital input
1.3.6.1.4.1.9839.2.1.1.23Scalarwtr-flow-almread-onlycurrentNo water flow alarm
1.3.6.1.4.1.9839.2.1.1.24Scalardisch-air-failread-onlycurrentSensor is out of range
1.3.6.1.4.1.9839.2.1.1.25Scalarra-tmp-hi-almread-onlycurrentTemperature of return air above alarm set point
1.3.6.1.4.1.9839.2.1.1.26Scalarra-tmp-lo-almread-onlycurrentTemperature of return air below alarm set point
1.3.6.1.4.1.9839.2.1.1.27Scalarhum-hi-almread-onlycurrentHumidity above alarm set point
1.3.6.1.4.1.9839.2.1.1.28Scalarhum-lo-almread-onlycurrentHumidity below alarm set point
1.3.6.1.4.1.9839.2.1.1.29Scalarfan-overloadread-onlycurrentFan overload
1.3.6.1.4.1.9839.2.1.1.30Scalarstdby-pump-onread-onlycurrentStandby pump on: Check primary pump -Optional alarm. Pump failure input signal required
1.3.6.1.4.1.9839.2.1.1.31Scalarcust-msg-sw1read-onlycurrentCustom alarm #1 -Optional alarm. External alarm input required. Factory programmed custom message required
1.3.6.1.4.1.9839.2.1.1.32Scalarcust-msg-sw2read-onlycurrentCustom alarm #2 -Optional alarm. External alarm input required. Factory programmed custom message required
1.3.6.1.4.1.9839.2.1.1.33Scalarcust-msg-sw3read-onlycurrentCustom alarm #3 -Optional alarm. External alarm input required. Factory programmed custom message required
1.3.6.1.4.1.9839.2.1.1.34Scalarcust-msg-sw4read-onlycurrentCustom alarm #4 -Optional alarm. External alarm input required. Factory programmed custom message required
1.3.6.1.4.1.9839.2.1.1.35Scalarhumsw-inhibitread-onlycurrentHumidifier stopped due to custom alarm switch
1.3.6.1.4.1.9839.2.1.1.36Scalarheat-inhibitread-onlycurrentHeat inhibited due to custom switch alarm condition
1.3.6.1.4.1.9839.2.1.1.37Scalarrht-hum-inhibitread-onlycurrentReheat and humidification inhibited from operation
1.3.6.1.4.1.9839.2.1.1.38Scalardisch-tmp-lo-almread-onlycurrentTemperature of discharge air below alarm set point
1.3.6.1.4.1.9839.2.1.1.39Scalaroverride-almread-onlycurrentManual override: Check bypass switches - Standard alarm. Manual override switch is on
1.3.6.1.4.1.9839.2.1.1.40Scalarcondensation-almread-onlycurrentHigh condensation from digital input
1.3.6.1.4.1.9839.2.1.1.41Scalarunit-in-standbyread-onlycurrentUnit in standby, all functions held off - Optional alarm. Control input signal required Factory setting required
1.3.6.1.4.1.9839.2.1.1.42Scalarcw-sns-failread-onlycurrentSensor is out of range
1.3.6.1.4.1.9839.2.1.1.43Scalarhumsw-chk-cylread-onlycurrentHumidifier stopped due to custom alarm switch
1.3.6.1.4.1.9839.2.1.1.44Scalarbms-cooling-inhibitread-writecurrentCooling operation inhibited by BMS
1.3.6.1.4.1.9839.2.1.1.45Scalarbms-heat-inhibitread-writecurrentHeat inhibited due to bms
1.3.6.1.4.1.9839.2.1.1.46Scalarbms-humidifier-inhibitread-writecurrentHumidifier operation inhibited by BMS
1.3.6.1.4.1.9839.2.1.1.47Scalarbms-dehum-inhibitread-writecurrentDehumidify mode inhibited by bms
1.3.6.1.4.1.9839.2.1.1.48Scalarfan-inhibit-bmsread-writecurrentInhibit fan by bms
1.3.6.1.4.1.9839.2.1.1.49Scalarhum-expectread-onlycurrentReduces control humidity cycling
1.3.6.1.4.1.9839.2.1.1.50Scalarusashr-f-cread-writecurrentTemperature Mode 0=_C 1=_F
1.3.6.1.4.1.9839.2.1.1.52Scalarlead-compread-onlycurrentLead compressor select 0= C1, 1= C2
1.3.6.1.4.1.9839.2.1.1.53Scalarwtrvlv-dirread-onlycurrentWater valve direct or reverse acting
1.3.6.1.4.1.9839.2.1.1.54Scalarups-on-almread-onlycurrentAlarm: UPS power on: Check main power -Optional alarm. External alarm input required
1.3.6.1.4.1.9839.2.1.1.55Scalarpwrup-almread-onlycurrentLoss of power requires manual reset of alarm
1.3.6.1.4.1.9839.2.1.1.56Scalarseetag-cust-alm1read-onlycurrentLocal alarm #1: See tag inside door =Optional alarm. External alarm input required
1.3.6.1.4.1.9839.2.1.1.57Scalarseetag-cust-alm2read-onlycurrentLocal alarm #2: See tag inside door =Optional alarm. External alarm input required
1.3.6.1.4.1.9839.2.1.1.58Scalarseetag-cust-alm3read-onlycurrentLocal alarm #3: See tag inside door =Optional alarm. External alarm input required
1.3.6.1.4.1.9839.2.1.1.59Scalarseetag-cust-alm4read-onlycurrentLocal alarm #4: See tag inside door =Optional alarm. External alarm input required
1.3.6.1.4.1.9839.2.1.1.60Scalarshortcycle-alm-enread-onlycurrentEnable short cycle alarm of the compressors
1.3.6.1.4.1.9839.2.1.1.61Scalarsuperv-offread-onlycurrentSupervisor (BMS) On-Off. Show the state OFFbyBMS in main mask (1: Off; 0: On
1.3.6.1.4.1.9839.2.1.1.62ScalarBMS-heartbeatread-onlycurrentBms heartbeat - pCO looks for update every 10 minutes
1.3.6.1.4.1.9839.2.1.2NodeanalogObjects
1.3.6.1.4.1.9839.2.1.2.1Scalarret-air-tmpread-onlycurrentTemperature of return air
1.3.6.1.4.1.9839.2.1.2.2Scalarminmax-24hr-retair-maximumread-onlycurrentMaximum Return air temp in last 24hrs
1.3.6.1.4.1.9839.2.1.2.3Scalarminmax-24hr-retair-minumumread-onlycurrentMinimum Return air temp in last 24hrs
1.3.6.1.4.1.9839.2.1.2.4Scalartemp-setpointread-writecurrentTemperature setpoint
1.3.6.1.4.1.9839.2.1.2.5Scalartemp-deadbandread-writecurrentAmount from setpoint before a comp is staged on
1.3.6.1.4.1.9839.2.1.2.6Scalarhumidity-ain-offsread-onlycurrentHumidity Sensor Calibration
1.3.6.1.4.1.9839.2.1.2.7Scalarreturn-ain-offsread-onlycurrentReturn Temperature Sensor Calibration
1.3.6.1.4.1.9839.2.1.2.8Scalarcw-tmpread-onlycurrentTemperature of chilled water
1.3.6.1.4.1.9839.2.1.2.9Scalardisch-air-tmpread-onlycurrentTemperature of discharge air
1.3.6.1.4.1.9839.2.1.2.10Scalardischarge-ain-offsread-onlycurrentDischarge Temperature Sensor Calibration - Optional discharge air temperature sensor required (B9)
1.3.6.1.4.1.9839.2.1.2.11Scalarcw-ain-offsread-onlycurrentChilled Water Temperature Sensor Calibration - Optional chilled water temperature sensor required (B10)
1.3.6.1.4.1.9839.2.1.2.12Scalarengsaver-setpointread-writecurrentTemperature setpoint where chilled water will is requested
1.3.6.1.4.1.9839.2.1.2.13Scalaropt1-analogread-onlycurrentValue of the analog input
1.3.6.1.4.1.9839.2.1.2.14Scalaropt2-analogread-onlycurrentValue of the analog input
1.3.6.1.4.1.9839.2.1.2.15Scalaropt3-analogread-onlycurrentValue of the analog input
1.3.6.1.4.1.9839.2.1.2.16Scalaropt4-analogread-onlycurrentValue of the analog input
1.3.6.1.4.1.9839.2.1.2.17Scalaropt-sns-1-y1read-onlycurrentAnalog Sensor 1 Minimum Value
1.3.6.1.4.1.9839.2.1.2.18Scalaropt-sns-1-y2read-onlycurrentAnalog Sensor 1 Maximum Value
1.3.6.1.4.1.9839.2.1.2.19Scalaropt-sns-1-ain-offsread-onlycurrentAnalog Sensor 1 Calibration
1.3.6.1.4.1.9839.2.1.2.20Scalaropt-sns-2-y1read-onlycurrentAnalog Sensor 2 Minimum Value
1.3.6.1.4.1.9839.2.1.2.21Scalaropt-sns-2-y2read-onlycurrentAnalog Sensor 2 Maximum Value
1.3.6.1.4.1.9839.2.1.2.22Scalaropt-sns-2-ain-offsread-onlycurrentAnalog Sensor 2 Calibration
1.3.6.1.4.1.9839.2.1.2.23Scalaropt-sns-3-y1read-onlycurrentAnalog Sensor 3 Minimum Value
1.3.6.1.4.1.9839.2.1.2.24Scalaropt-sns-3-y2read-onlycurrentAnalog Sensor 3 Maximum Value
1.3.6.1.4.1.9839.2.1.2.25Scalaropt-sns-3-ain-offsread-onlycurrentAnalog Sensor 3 Calibration
1.3.6.1.4.1.9839.2.1.2.26Scalaropt-sns-4-y1read-onlycurrentAnalog Sensor 4 Minimum Value
1.3.6.1.4.1.9839.2.1.2.27Scalaropt-sns-4-y2read-onlycurrentAnalog Sensor 4 Maximum Value
1.3.6.1.4.1.9839.2.1.2.28Scalaropt-sns-4-ain-offsread-onlycurrentAnalog Sensor 4 Calibration
1.3.6.1.4.1.9839.2.1.3NodeintegerObjects
1.3.6.1.4.1.9839.2.1.3.1Scalardisch-air-lo-spread-writecurrentLower Limit alarm of discharge air temp
1.3.6.1.4.1.9839.2.1.3.2Scalarhumidity-disread-onlycurrentRelative humidity displayed as xx%
1.3.6.1.4.1.9839.2.1.3.3Scalarstages-onread-onlycurrentCooling Stages On, DX only
1.3.6.1.4.1.9839.2.1.3.4Scalarheaters-onread-onlycurrentNumber of heat stages running
1.3.6.1.4.1.9839.2.1.3.5Scalarminmax-24hr-hum-maximumread-onlycurrentMaximum humidity in last 24hrs
1.3.6.1.4.1.9839.2.1.3.6Scalarminmax-24hr-hum-minumumread-onlycurrentMinimum humidity in last 24hrs
1.3.6.1.4.1.9839.2.1.3.7Scalarcomp-dutyread-onlycurrentCooling Utilization Over Last Hour -Percentage of cooling is used in the last hour of operation; this point applies to DX unit.
1.3.6.1.4.1.9839.2.1.3.8Scalarheat-dutyread-onlycurrentHeating Utilization Over Last Hour -Percentage of heating is used in the last hour of operation
1.3.6.1.4.1.9839.2.1.3.9Scalarhum-dutyread-onlycurrentHumidifier Utilization Over Last Hour -Percentage of humidifier is used in the last hour of operation
1.3.6.1.4.1.9839.2.1.3.10Scalarc1-hours-hread-onlycurrentCompressor 1 Runtime -This point applies to DX unit with one compressor -high
1.3.6.1.4.1.9839.2.1.3.11Scalarc1-hours-lread-onlycurrentCompressor 1 Runtime -This point applies to DX unit with one compressor -low
1.3.6.1.4.1.9839.2.1.3.12Scalarc2-hours-hread-onlycurrentCompressor 2 Runtime -This point applies to DX unit with dual compressor - high
1.3.6.1.4.1.9839.2.1.3.13Scalarc2-hours-lread-onlycurrentCompressor 2 Runtime -This point applies to DX unit with dual compressor - low
1.3.6.1.4.1.9839.2.1.3.14Scalarht1-hours-hread-onlycurrentHeater 1 Runtime - high
1.3.6.1.4.1.9839.2.1.3.15Scalarht1-hours-lread-onlycurrentHeater 1 Runtime - low
1.3.6.1.4.1.9839.2.1.3.16Scalarcurrent-secondread-onlycurrentCurrent second
1.3.6.1.4.1.9839.2.1.3.17Scalarcurrent-minuteread-onlycurrentCurrent minute
1.3.6.1.4.1.9839.2.1.3.18Scalarcurrent-hourread-onlycurrentCurrent hour
1.3.6.1.4.1.9839.2.1.3.19Scalarcurrent-dayread-onlycurrentCurrent day
1.3.6.1.4.1.9839.2.1.3.20Scalarcurrent-monthread-onlycurrentCurrent month
1.3.6.1.4.1.9839.2.1.3.21Scalarcurrent-yearread-onlycurrentCurrent year
1.3.6.1.4.1.9839.2.1.3.22Scalarfirestat-spread-writecurrentAlarm settting of return air temp to determine there is a fire
1.3.6.1.4.1.9839.2.1.3.23Scalarhum-hi-spread-writecurrentHumidity upper limit alarm
1.3.6.1.4.1.9839.2.1.3.24Scalarret-air-hi-spread-writecurrentUpper limit alarm of return air temp
1.3.6.1.4.1.9839.2.1.3.25Scalarhum-lo-spread-writecurrentHumidity lower limit alarm
1.3.6.1.4.1.9839.2.1.3.26Scalarret-air-lo-spread-writecurrentLower limit alarm of return air temp
1.3.6.1.4.1.9839.2.1.3.27Scalarhum-deadbandread-writecurrentamount hum must change from setpoint before acting
1.3.6.1.4.1.9839.2.1.3.28Scalarhum-setpointread-writecurrenthumidity setpoint
1.3.6.1.4.1.9839.2.1.3.29Scalarstart-dlyread-writecurrentTime before the system starts up
1.3.6.1.4.1.9839.2.1.3.30Scalaralm1-delread-onlycurrentOptional Alarm 1 Delay
1.3.6.1.4.1.9839.2.1.3.31Scalaralm2-delread-onlycurrentOptional Alarm 2 Delay
1.3.6.1.4.1.9839.2.1.3.32Scalaralm3-delread-onlycurrentOptional Alarm 3 Delay
1.3.6.1.4.1.9839.2.1.3.33Scalaralarm1-txtread-onlycurrentMessage on optional alarm screen, some also add function
1.3.6.1.4.1.9839.2.1.3.34Scalaralarm2-txtread-onlycurrentMessage on optional alarm screen, some also add function
1.3.6.1.4.1.9839.2.1.3.35Scalaralarm3-txtread-onlycurrentMessage on optional alarm screen, some also add function
1.3.6.1.4.1.9839.2.1.3.36Scalaralarm4-txtread-onlycurrentMessage on optional alarm screen, some also add function
1.3.6.1.4.1.9839.2.1.3.37Scalarcomp-selread-onlycurrentComps 0=none, 1=one, 2=one+UL, 3=two, 4=two+UL, 5=Four/two circuit
1.3.6.1.4.1.9839.2.1.3.38Scalardehum-moderead-onlycurrent0=none, 1= comp limited, 2=twocomp limited, 3= comp unlimited, 4=twocomp unlimited
1.3.6.1.4.1.9839.2.1.3.39Scalarreheat-selread-onlycurrentNumber of heat stages
1.3.6.1.4.1.9839.2.1.3.40Scalarhum-selread-onlycurrent0=none, 1=comp mod, 2=comp non, 3= comf mod, 4= conf non mod
1.3.6.1.4.1.9839.2.1.3.41Scalaralm-contact-msgread-onlycurrentText displayed on all alarm screens
1.3.6.1.4.1.9839.2.1.3.42Scalarpowerup-selread-onlycurrent0= start wo/alarm, 1= start w/alarm, 2= requires reset of alarm
1.3.6.1.4.1.9839.2.1.3.43Scalarbuzzer-selectread-onlycurrent0=None, 1=short beeps, 2=long beep, 3=Constant
1.3.6.1.4.1.9839.2.1.3.44Scalarcw-dispread-onlycurrent% of 10volts of analog output #1
1.3.6.1.4.1.9839.2.1.3.45Scalarwtrvlv-dutyread-onlycurrentChilled Water Utilization Over Last Hour - This applies to Chilled water or Energy saver units.
1.3.6.1.4.1.9839.2.1.3.46Scalarhum-hours-hread-onlycurrentHumidifier Runtime - high
1.3.6.1.4.1.9839.2.1.3.47Scalarhum-hours-lread-onlycurrentHumidifier Runtime - low
1.3.6.1.4.1.9839.2.1.3.48Scalarblower-hours-hread-onlycurrentBlower Runtime - high
1.3.6.1.4.1.9839.2.1.3.49Scalarblower-hours-lread-onlycurrentBlower Runtime - low
1.3.6.1.4.1.9839.2.1.3.50Scalaralm4-delread-onlycurrentOptional Alarm 4 Delay
1.3.6.1.4.1.9839.2.1.3.51Scalarassist-selread-onlycurrent0= no comp assist, 1=one comp assist, 2= two comp assist, 3... 4...
1.3.6.1.4.1.9839.2.1.3.52Scalarwtrvlv-selread-onlycurrentWater valve type 0=none, 1=chill, 2=Engy, 3=Aux chill, 4=Disc Reg
1.3.6.1.4.1.9839.2.1.3.53Scalarwtrvlv-volts-selread-onlycurrentWater valve voltage 0= 0-10, 1=2-10, 2=7-10, 3=6-9, 4=4-7
1.3.6.1.4.1.9839.2.1.3.54Scalarhum-voltsread-onlycurrent% of 10volts of analog output #2
1.3.6.1.4.1.9839.2.1.3.55Scalardehum-hours-hread-onlycurrentDehumidifier Runtime - High
1.3.6.1.4.1.9839.2.1.3.56Scalardehum-hours-lread-onlycurrentDehumidifier Runtime - Low
1.3.6.1.4.1.9839.2.1.3.58Scalarautoflush-dlyread-onlycurrentTime between drain cycles 0=12hr, 1=24hr, 2=48hr, 3=96hr, 4=None
1.3.6.1.4.1.9839.2.1.3.59Scalary4-outread-onlycurrentValue sent to optional analog output#1
1.3.6.1.4.1.9839.2.1.3.60Scalary5-outread-onlycurrentValue sent to optional analog output#2
1.3.6.1.4.1.9839.2.1.3.61Scalarair-flowread-onlycurrentCurrent Fan Airflow - Based on calculated Pressure Diff formula
1.3.6.1.4.1.9839.2.1.3.62Scalaropt-snsr1-nameread-onlycurrentName of the sensor
1.3.6.1.4.1.9839.2.1.3.63Scalaropt-sns-1-ain-typeread-onlycurrentAnalog Sensor 1 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170}
1.3.6.1.4.1.9839.2.1.3.64Scalaropt-snsr2-nameread-onlycurrentName of the sensor
1.3.6.1.4.1.9839.2.1.3.65Scalaropt-sns-2-ain-typeread-onlycurrentAnalog Sensor 2 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170}
1.3.6.1.4.1.9839.2.1.3.66Scalaropt-snsr3-nameread-onlycurrentName of the sensor
1.3.6.1.4.1.9839.2.1.3.67Scalaropt-sns-3-ain-typeread-onlycurrentAnalog Sensor 3 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170}
1.3.6.1.4.1.9839.2.1.3.68Scalaropt-snsr4-nameread-onlycurrentName of the sensor
1.3.6.1.4.1.9839.2.1.3.69Scalaropt-sns-4-ain-typeread-onlycurrentAnalog Sensor 4 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170}
1.3.6.1.4.1.9839.2.1.3.70Scalarcw-fan-speed-bmsread-writecurrentCW Fan speed (%) sent via BMS
1.3.6.1.4.1.9839.2.1.3.71Scalardx-fan-speed-bmsread-writecurrentDX Fan speed (%) sent via BMS
1.3.6.1.4.1.9839.2.1.3.72Scalarfan-speed-maxread-writecurrentMaximum Fan speed (% of output) modulation.
1.3.6.1.4.1.9839.2.1.3.73Scalarfan-speed-minread-writecurrentMinimum Fan speed (% of output) modulation from pressure.
1.3.6.1.4.1.9839.2.1.3.74Scalarfan-pr-spread-writecurrentFan pressure setpoint (0.01 inches of water)
1.3.6.1.4.1.9839.2.1.3.75Scalarfan-pr-bandread-writecurrentFan pressure band (0.01 inches of water)
1.3.6.1.4.1.9839.2.1.3.76Scalarfan-af-maxread-writecurrentMaximum air flow limit of setpoint from BMS or valve modulation.
1.3.6.1.4.1.9839.2.1.3.77Scalarfan-af-minread-writecurrentMinimum air flow limit of setpoint from BMS or valve modulation.
1.3.6.1.4.1.9839.2.1.3.78Scalarfan-kfactorread-writecurrentFan K Factor
1.3.6.1.4.1.9839.2.1.3.79Scalarnum-fansread-writecurrentNumber of fans installed in this unit
1.3.6.1.4.1.9839.2.1.3.81Scalarht2-hours-hread-onlycurrentHeater 2 Runtime - high
1.3.6.1.4.1.9839.2.1.3.82Scalarht2-hours-lread-onlycurrentHeater 2 Runtime - low
1.3.6.1.4.1.9839.2.1.3.83Scalarht3-hours-hread-onlycurrentHeater 3 Runtime - high
1.3.6.1.4.1.9839.2.1.3.84Scalarht3-hours-lread-onlycurrentHeater 3 Runtime - low
1.3.6.1.4.1.9839.2.1.3.85Scalarengy-hours-hread-onlycurrentEnergy Saver Runtime - This optional point applies to energy saver units only -high
1.3.6.1.4.1.9839.2.1.3.86Scalarengy-hours-lread-onlycurrentEnergy Saver Runtime - This optional point applies to energy saver units only - low
1.3.6.1.4.1.9839.2.1.3.87Scalarcw-hours-hread-onlycurrentChilled Water Runtime - This applies to chilled water units only - high
1.3.6.1.4.1.9839.2.1.3.88Scalarcw-hours-lread-onlycurrentChilled Water Runtime - This applies to chilled water units only - low
1.3.6.1.4.1.9839.2.1.3.89Scalarc3-hours-hread-onlycurrentCompressor 3 Runtime - This applies when unit has four stages tandem compressors - high
1.3.6.1.4.1.9839.2.1.3.90Scalarc3-hours-lread-onlycurrentCompressor 3 Runtime - This applies when unit has four stages tandem compressors - low
1.3.6.1.4.1.9839.2.1.3.91Scalarc4-hours-lread-onlycurrentCompressor 4 Runtime - This applies when unit has four stages tandem compressors. - high
1.3.6.1.4.1.9839.2.1.3.92Scalarc4-hours-hread-onlycurrentCompressor 4 Runtime - This applies when unit has four stages tandem compressors. - low
1.3.6.1.4.1.9839.2.1.3.93Scalarcond-hours-hread-onlycurrentCondenser Runtime - high
1.3.6.1.4.1.9839.2.1.3.94Scalarcond-hours-lread-onlycurrentCondenser Runtime - low
1.3.6.1.4.1.9839.2.1.3.95Scalardx-fan-speedread-onlycurrentFan speed (% of output) when compressor cooling.
1.3.6.1.4.1.9839.2.1.3.96Scalarcw-fan-speedread-onlycurrentFan speed (% of output) when cold water cooling.
1.3.6.1.4.1.9839.2.1.3.97Scalarfan-af-dx-spread-onlycurrentFan air flow setpoint for DX unit (cfm)
1.3.6.1.4.1.9839.2.1.3.98Scalarfan-af-cw-spread-onlycurrentFan air flow setpoint for CW unit (cfm)
1.3.6.1.4.1.9839.2.1.3.99Scalarzm-airflow-spread-writecurrentZone Airflow Setpoint kcfm