DellrPDU-MIB
281 objects
No module-level DESCRIPTION found.
Imported Objects
| RFC-1212 | OBJECT-TYPE |
| RFC-1215 | TRAP-TYPE |
| RFC1155-SMI | enterprises Gauge IpAddress TimeTicks |
| RFC1213-MIB | DisplayString |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.674 | Nodedell | |||
| 1.3.6.1.4.1.674.10903 | Nodepdu | |||
| 1.3.6.1.4.1.674.10903.200 | Nodepdusub | |||
| 1.3.6.1.4.1.674.10903.200.1 | Nodesoftware | |||
| 1.3.6.1.4.1.674.10903.200.2 | Nodehardware | |||
| 1.3.6.1.4.1.674.10903.200.2.100 | NodeproductID | |||
| 1.3.6.1.4.1.674.10903.200.2.100.1 | ScalarproductIDDisplayName | read-write | mandatory | Name of this product for display purposes. |
| 1.3.6.1.4.1.674.10903.200.2.100.2 | ScalarproductIDDescription | read-write | mandatory | A short description of this product. |
| 1.3.6.1.4.1.674.10903.200.2.100.3 | ScalarproductIDVendor | read-only | mandatory | The name of the product manufacturer. |
| 1.3.6.1.4.1.674.10903.200.2.100.4 | ScalarproductIDVersion | read-only | mandatory | The hardware version of this product. |
| 1.3.6.1.4.1.674.10903.200.2.100.5 | ScalarproductIDBuildNumber | read-only | mandatory | The software build number of the product populating the MIB. |
| 1.3.6.1.4.1.674.10903.200.2.100.6 | ScalarproductIDURL | read-only | mandatory | The URL of the Web-based application to manage this device, should the device provide one. |
| 1.3.6.1.4.1.674.10903.200.2.100.7 | ScalarproductIDDeviceNetworkName | read-write | mandatory | Operating system-specific computer name if product SNMP service is hosted. |
| 1.3.6.1.4.1.674.10903.200.2.110 | NodeproductStatus | |||
| 1.3.6.1.4.1.674.10903.200.2.110.1 | ScalarproductStatusGlobalStatus | read-only | mandatory | The current status of the product. This is a summary of the status for the entire product including any metered devices. The SNMP monitor performs a get to ret… |
| 1.3.6.1.4.1.674.10903.200.2.110.2 | ScalarproductStatusLastGlobalStatus | read-only | mandatory | The status before the current status which induced an initiative to issue a global status change trap. |
| 1.3.6.1.4.1.674.10903.200.2.110.3 | ScalarproductStatusTimeStamp | read-only | mandatory | The last time that the SNMP table geometries changed or attribute data was significantly updated. Management applications use this OID to trigger a refresh of … |
| 1.3.6.1.4.1.674.10903.200.2.110.4 | ScalarproductStatusRESERVED1 | read-only | mandatory | RESERVED |
| 1.3.6.1.4.1.674.10903.200.2.110.5 | ScalarproductStatusRESERVED2 | read-only | mandatory | RESERVED |
| 1.3.6.1.4.1.674.10903.200.2.110.6 | ScalarproductStatusRESERVED3 | read-only | mandatory | RESERVED |
| 1.3.6.1.4.1.674.10903.200.2.200 | NoderPDU | |||
| 1.3.6.1.4.1.674.10903.200.2.200.100 | NoderPDUIdentD | |||
| 1.3.6.1.4.1.674.10903.200.2.200.100.1 | ScalarrPDUIdentTableSize | read-only | mandatory | The number of connected Rack PDUs. |
| 1.3.6.1.4.1.674.10903.200.2.200.100.2 | TablerPDUIdentTable | not-accessible | mandatory | A table of Rack PDU identification data. |
| 1.3.6.1.4.1.674.10903.200.2.200.100.2.1 | RowrPDUIdentEntry | not-accessible | mandatory | Identification data from the Rack PDU being queried. |
| 1.3.6.1.4.1.674.10903.200.2.200.100.2.1.1 | ColumnrPDUIdentIndex | read-only | mandatory | The index to the Rack PDU identification table entry. |
| 1.3.6.1.4.1.674.10903.200.2.200.100.2.1.2 | ColumnrPDUIdentNameD | read-write | mandatory | A user-defined string identifying the Rack PDU. |
| 1.3.6.1.4.1.674.10903.200.2.200.100.2.1.3 | ColumnrPDUIdentLocation | read-write | mandatory | A user-defined string identifying the location of the Rack PDU. |
| 1.3.6.1.4.1.674.10903.200.2.200.100.2.1.4 | ColumnrPDUIdentHardwareRevD | read-only | mandatory | The Rack PDU hardware version. |
| 1.3.6.1.4.1.674.10903.200.2.200.100.2.1.5 | ColumnrPDUIdentFirmwareRevD | read-only | mandatory | The Rack PDU firmware version. |
| 1.3.6.1.4.1.674.10903.200.2.200.100.2.1.6 | ColumnrPDUIdentDateOfManufactureD | read-only | mandatory | The date the Rack PDU was manufactured in mm/dd/yyyy format. |
| 1.3.6.1.4.1.674.10903.200.2.200.100.2.1.7 | ColumnrPDUIdentModelNumberD | read-only | mandatory | The Rack PDU model number. |
| 1.3.6.1.4.1.674.10903.200.2.200.100.2.1.8 | ColumnrPDUIdentSerialNumberD | read-only | mandatory | The Rack PDU serial number. |
| 1.3.6.1.4.1.674.10903.200.2.200.110 | NoderPDUDevice | |||
| 1.3.6.1.4.1.674.10903.200.2.200.110.1 | ScalarrPDUDeviceTableSize | read-only | mandatory | The number of connected Rack PDUs. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.2 | TablerPDUDeviceStatusTable | not-accessible | mandatory | A table of Rack PDU status information. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.2.1 | RowrPDUDeviceStatusEntry | not-accessible | mandatory | Status information from the Rack PDU being queried. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.2.1.1 | ColumnrPDUDeviceStatusIndex | read-only | mandatory | The index to the Rack PDU status table entry. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.2.1.2 | ColumnrPDUDeviceStatusName | read-write | mandatory | A user-defined string identifying the Rack PDU. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.2.1.3 | ColumnrPDUDeviceStatusPower | read-only | mandatory | The power consumption of the Rack PDU load in 1/100 of KWatts. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.2.1.4 | ColumnrPDUDeviceStatusEnergy | read-only | mandatory | A user resettable energy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.2.1.5 | ColumnrPDUDeviceStatusCommandPending | read-only | mandatory | Indicates whether the device is processing a pending command. If the commandPendingUnknown (3) value is returned, all devices receiving power from the Rack PDU… |
| 1.3.6.1.4.1.674.10903.200.2.200.110.2.1.6 | ColumnrPDUDeviceStatusLoadState | read-only | mandatory | Indicates the present load status of the Rack PDU Device being queried. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.3 | TablerPDUDeviceConfigTable | not-accessible | mandatory | A table of Rack PDU configuration data. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.3.1 | RowrPDUDeviceConfigEntry | not-accessible | mandatory | Configuration data from the Rack PDU being queried. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.1 | ColumnrPDUDeviceConfigIndex | read-only | mandatory | The index to the Rack PDU table entry. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.2 | ColumnrPDUDeviceConfigName | read-write | mandatory | A user-defined string identifying the Rack PDU. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.3 | ColumnrPDUDeviceConfigLocation | read-write | mandatory | The Location of the Rack PDU. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.4 | ColumnrPDUDeviceConfigColdstartDelay | read-write | mandatory | The amount of delay, measured in seconds, between when power is provided to the Rack PDU and when the Rack PDU provides basic master power to the outlets. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.5 | ColumnrPDUDeviceCfgLowLoadPwrThresh | read-write | mandatory | The user-defined low power draw alarm threshold, measured in tenths of kilowatts. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.6 | ColumnrPDUDeviceCfgNerOvloadPwrThresh | read-write | mandatory | The user-defined near power overload threshold, measured in tenths of kilowatts. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.7 | ColumnrPDUDeviceCfgOverloadPwrThresh | read-write | mandatory | The user-defined power overload threshold, measured in tenths of kilowatts. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.8 | ColumnrPDUDeviceConfigPowerHeadroom | read-only | mandatory | The amount of input power that is available to the connected devices in hundredths of kilowatt-hours. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.9 | ColumnrPDUDeviceConfigPeakPower | read-only | mandatory | The highest input power level recorded by the connected devices in hundredths of kilowatt-hours. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.10 | ColumnrPDUDeviceCfgPeakPwrStartTime | read-only | mandatory | The time, in hh:mm:ss, when the device started recording the highest input power level. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.11 | ColumnrPDUDeviceConfigPeakPwrCapTime | read-only | mandatory | The time, in hh:mm:ss, when the highest input power level was recorded by the device. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.12 | ColumnrPDUDeviceCfgPeakPowerHeadroom | read-only | mandatory | The highest level of input power that is available to the connected devices in hundredths of kilowatt-hours. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.13 | ColumnrPDUDeviceCfgEnergyStartTime | read-only | mandatory | The time, in hh:mm:ss, when the device started recording the input energy level. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.4 | TablerPDUDevicePropertiesTable | not-accessible | mandatory | A table of Rack PDU properties. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.4.1 | RowrPDUDevicePropertiesEntry | not-accessible | mandatory | Properties of the Rack PDU being queried. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.1 | ColumnrPDUDevicePropertiesIndex | read-only | mandatory | The index to the Rack PDU properties table entry. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.2 | ColumnrPDUDevicePropertiesName | read-write | mandatory | A user-defined string identifying the Rack PDU. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.3 | ColumnrPDUDevicePropertiesNumOutlets | read-only | mandatory | The number of outlets on the Rack PDU. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.4 | ColumnrPDUDevicePropertiesNumSwdOuts | read-only | mandatory | The number of switched outlets on the Rack PDU. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.5 | ColumnrPDUDevicePropertiesNumMtrdOuts | read-only | mandatory | The number of metered outlets on the Rack PDU. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.6 | ColumnrPDUDevicePropertiesNumPhases | read-only | mandatory | The number of phases present in the Rack PDU. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.7 | ColumnrPDUDevicePropertiesNumBreakers | read-only | mandatory | The number of breakers present in the Rack PDU. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.8 | ColumnrPDUDevicePropertiesMaxCurntRtg | read-only | mandatory | The maximum current rating, measured in Amps, for the Rack PDU. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.9 | ColumnrPDUDevicePropertiesOutlayout | read-only | mandatory | The phase wiring for the Rack PDU outlets. PhaseToNeutral and PhaseToPhase: outlets wired consecutively; PhaseToNeutralGrouped and PhaseToPhaseGrouped: groups … |
| 1.3.6.1.4.1.674.10903.200.2.200.110.5 | TablerPDUDeviceControlTable | not-accessible | mandatory | A table of Rack PDU control data. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.5.1 | RowrPDUDeviceControlEntry | not-accessible | mandatory | Control data from the Rack PDU being queried. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.5.1.1 | ColumnrPDUDeviceControlIndex | read-only | mandatory | The index to the Rack PDU control table entry. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.5.1.2 | ColumnrPDUDeviceControlName | read-write | mandatory | A user-defined string identifying the Rack PDU. |
| 1.3.6.1.4.1.674.10903.200.2.200.110.5.1.3 | ColumnrPDUDeviceControlCommand | read-write | mandatory | Setting this OID to turnAllOnNow (1) will turn all outlets on immediately. Setting this OID to turnAllOnSequence (2) will turn all outlets on as defined by eac… |
| 1.3.6.1.4.1.674.10903.200.2.200.120 | NoderPDUPhase | |||
| 1.3.6.1.4.1.674.10903.200.2.200.120.1 | ScalarrPDUPhaseTableSize | read-only | mandatory | The number of connected Rack PDU phases. |
| 1.3.6.1.4.1.674.10903.200.2.200.120.2 | TablerPDUPhaseStatusTable | not-accessible | mandatory | A table of Rack PDU phase status data. |
| 1.3.6.1.4.1.674.10903.200.2.200.120.2.1 | RowrPDUPhaseStatusEntry | not-accessible | mandatory | Status data from the currently queried Rack PDU phase. |
| 1.3.6.1.4.1.674.10903.200.2.200.120.2.1.1 | ColumnrPDUPhaseStatusIndex | read-only | mandatory | The index to the Rack PDU phase status table entry. |
| 1.3.6.1.4.1.674.10903.200.2.200.120.2.1.2 | ColumnrPDUPhaseStatusNumber | read-only | mandatory | The numeric phase ID. |
| 1.3.6.1.4.1.674.10903.200.2.200.120.2.1.3 | ColumnrPDUPhaseStatusLoadState | read-only | mandatory | Indicates the present load status of the Rack PDU phase being queried. |
| 1.3.6.1.4.1.674.10903.200.2.200.120.2.1.4 | ColumnrPDUPhaseStatusCurrent | read-only | mandatory | Indicates the current draw, in tenths of Amps, of the load on the Rack PDU phase being queried. |
| 1.3.6.1.4.1.674.10903.200.2.200.120.2.1.5 | ColumnrPDUPhaseStatusVoltage | read-only | mandatory | Indicates the Voltage, in Volts, of the Rack PDU phase being queried. |
| 1.3.6.1.4.1.674.10903.200.2.200.120.2.1.6 | ColumnrPDUPhaseStatusPower | read-only | mandatory | Indicates the load power, in hundredths of kilowatts, consumed on the Rack PDU phase being queried. |
| 1.3.6.1.4.1.674.10903.200.2.200.120.3 | TablerPDUPhaseConfigTable | not-accessible | mandatory | A table of Rack PDU phase configuration data. |
| 1.3.6.1.4.1.674.10903.200.2.200.120.3.1 | RowrPDUPhaseConfigEntry | not-accessible | mandatory | Configuration data from the currently queried Rack PDU phase. |
| 1.3.6.1.4.1.674.10903.200.2.200.120.3.1.1 | ColumnrPDUPhaseConfigIndex | read-only | mandatory | The index to the Rack PDU phase configuration table entry. |
| 1.3.6.1.4.1.674.10903.200.2.200.120.3.1.2 | ColumnrPDUPhaseConfigNumber | read-only | mandatory | The numeric phase ID. |
| 1.3.6.1.4.1.674.10903.200.2.200.120.3.1.3 | ColumnrPDUPhaseCfgOverloadRestriction | read-write | mandatory | This OID controls the behavior of a Switched Rack PDU phase when an overload condition is possible and additional outlets are requested to be turned on. Settin… |
| 1.3.6.1.4.1.674.10903.200.2.200.120.3.1.4 | ColumnrPDUPhCfgLowLoadCurntThreshold | read-write | mandatory | The user-defined threshold for low phase current load, in Amps. |
| 1.3.6.1.4.1.674.10903.200.2.200.120.3.1.5 | ColumnrPDUPhCfgNerOverloadCurntThresh | read-write | mandatory | The user-defined near phase overload warning threshold in Amps. |
| 1.3.6.1.4.1.674.10903.200.2.200.120.3.1.6 | ColumnrPDUPhCfgOverloadCurntThreshold | read-write | mandatory | The user-defined phase overload current threshold in Amps. |
| 1.3.6.1.4.1.674.10903.200.2.200.130 | NoderPDUOutlet | |||
| 1.3.6.1.4.1.674.10903.200.2.200.130.1 | NoderPDUOutletSwitched | |||
| 1.3.6.1.4.1.674.10903.200.2.200.130.1.1 | ScalarrPDUOutletSwitchedTableSize | read-only | mandatory | The number of switched outlets on connected Rack PDUs. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.1.2 | TablerPDUOutletSwitchedStatusTable | not-accessible | mandatory | A table of Rack PDU switched outlet status information. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1 | RowrPDUOutletSwitchedStatusEntry | not-accessible | mandatory | Status information for the currently-queried Rack PDU switched outlet. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1.1 | ColumnrPDUOutletSwitchedStatusIndex | read-only | mandatory | The index to the Rack PDU switched outlet status information table entry. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1.2 | ColumnrPDUOutletSwitchedStatusNumber | read-only | mandatory | The numeric switched outlet ID. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1.3 | ColumnrPDUOutletSwitchedStatusName | read-write | mandatory | The user-defined switched outlet ID string. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1.4 | ColumnrPDUOutletSwitchedStatusState | read-only | mandatory | Indicates the present status of the Rack PDU switched outlet being queried. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1.5 | ColumnrPDUOutletSwitchedStatCmdPnding | read-only | mandatory | Indicates whether the device is processing a command for this outlet. If the commandPendingUnknown (3) value is returned, all devices receiving power from the … |
| 1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1.6 | ColumnrPDUOutletSwitchedStatPhLayout | read-only | mandatory | Phase description of the currently-queried Rack PDU switched outlet. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.1.3 | TablerPDUOutletSwitchedConfigTable | not-accessible | mandatory | A table of Rack PDU switched outlet configuration data. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1 | RowrPDUOutletSwitchedConfigEntry | not-accessible | mandatory | Configuration data from the currently-queried Rack PDU switched outlet. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1.1 | ColumnrPDUOutletSwitchedConfigIndex | read-only | mandatory | The index to the Rack PDU switched outlet configuration table entry. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1.2 | ColumnrPDUOutletSwitchedConfigNumber | read-only | mandatory | The numeric switched outlet ID. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1.3 | ColumnrPDUOutletSwitchedConfigName | read-write | mandatory | The user-defined switched outlet ID string. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1.4 | ColumnrPDUOutSwitchedCfgPowerOnTime | read-write | mandatory | The amount of time, in seconds, between when power is provided to the Rack PDU and when this switched outlet starts providing power. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1.5 | ColumnrPDUOutSwitchedCfgPowerOffTime | read-write | mandatory | The amount of time, in seconds, this outlet will delay turning off. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1.6 | ColumnrPDUOutSwtchedCfgRebootDuration | read-write | mandatory | After turning off power during a reboot sequence, the amount of time, in seconds, to wait before turning on power to this outlet again. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.1.4 | TablerPDUOutletSwitchedControlTable | not-accessible | mandatory | A table of Rack PDU switched outlet control data. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.1.4.1 | RowrPDUOutletSwitchedControlEntry | not-accessible | mandatory | Control data for the currently-queried Rack PDU switched outlet. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.1.4.1.1 | ColumnrPDUOutletSwitchedControlIndex | read-only | mandatory | The index to the Rack PDU switched outlet control data table entry. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.1.4.1.2 | ColumnrPDUOutletSwitchedControlNumber | read-only | mandatory | The numeric switched outlet ID. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.1.4.1.3 | ColumnrPDUOutletSwitchedControlName | read-write | mandatory | The user-defined switched outlet ID string. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.1.4.1.4 | ColumnrPDUOutletSwitchedControlCmd | read-write | mandatory | Getting this variable will return the outlet state. If the outlet is on, the outletOn (1) value will be returned. If the outlet is off, the outletOff (2) value… |
| 1.3.6.1.4.1.674.10903.200.2.200.130.2 | NoderPDUOutletMetered | |||
| 1.3.6.1.4.1.674.10903.200.2.200.130.2.1 | ScalarrPDUOutletMeteredTableSize | read-only | mandatory | The number of metered outlets on connected Rack PDUs. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.2.2 | TablerPDUOutletMeteredStatusTable | not-accessible | mandatory | A table of Rack PDU metered outlet status data. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1 | RowrPDUOutletMeteredStatusEntry | not-accessible | mandatory | Status data from the currently-queried Rack PDU metered outlet. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.1 | ColumnrPDUOutletMeteredStatusIndex | read-only | mandatory | The index to the Rack PDU metered status table entry. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.2 | ColumnrPDUOutletMeteredStatusNumber | read-only | mandatory | The numeric metered outlet ID. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.3 | ColumnrPDUOutletMeteredStatusName | read-write | mandatory | The user-defined metered outlet ID string. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.4 | ColumnrPDUOutletMeteredStatusLayout | read-only | mandatory | Phase description of currently queried Rack PDU metered outlet. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.5 | ColumnrPDUOutMeteredStatPowerRating | read-only | mandatory | The power rating for the currently queried Rack PDU metered outlet. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.6 | ColumnrPDUOutletMeteredStatusCurrent | read-only | mandatory | Indicates the current draw, in Amps, of the load on the Rack PDU outlet being queried. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.7 | ColumnrPDUOutletMeteredStatusEnergy | read-only | mandatory | A user resettable energy meter measuring Rack PDU load energy consumption in kilowatt-hours. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.8 | ColumnrPDUOutletMeteredStatusPower | read-only | mandatory | Indicates the power draw of the load on the Rack PDU outlet being queried. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.9 | ColumnrPDUOutletMeteredStatPeakPower | read-only | mandatory | The highest power level recorded by the currently queried Rack PDU metered outlet, in kilowatts. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.10 | ColumnrPDUOutMeteredStatPeakPwrTime | read-only | mandatory | Indicates the date and time that peak power consumption occured |
| 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.11 | ColumnrPDUOutMeteredStatusLoadState | read-only | mandatory | Indicates the present load status of the Rack PDU Outlet being queried. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.2.4 | TablerPDUOutletMeteredConfigTable | not-accessible | mandatory | A table of Rack PDU metered outlet configuration data. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1 | RowrPDUOutletMeteredConfigEntry | not-accessible | mandatory | Configuration data from the currently queried Rack PDU metered outlet. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1.1 | ColumnrPDUOutletMeteredConfigIndex | read-only | mandatory | The index to the Rack PDU metered outlet configuration table entry. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1.2 | ColumnrPDUOutletMeteredConfigNumber | read-only | mandatory | The numeric switched outlet ID. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1.3 | ColumnrPDUOutletMeteredConfigName | read-write | mandatory | The user-defined metered outlet ID string. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1.4 | ColumnrPDUOutMtredCfgLowLdCurntThresh | read-write | mandatory | The user-defined low load outlet current threshold, in Amps. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1.5 | ColumnrPDUOutMtrdCfgNrOvdCurntThresh | read-write | mandatory | The user-defined near outlet overload warning threshold, in Amps. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1.6 | ColumnrPDUOutMtredCfgOvrldCurntThresh | read-write | mandatory | The user-defined outlet overload current threshold, in Amps. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.2.5 | ScalarrPDUOutMeteredEnergyStartTime | read-only | mandatory | The time, in hh:mm:ss, when the currently queried Rack PDU metered outlet started recording the input energy level. |
| 1.3.6.1.4.1.674.10903.200.2.200.130.2.6 | ScalarrPDUOutMeteredPeakPwrStartTime | read-only | mandatory | The time, in hh:mm:ss, when the currently queried Rack PDU metered outlet started recording the highest level of input power that is available to the connected… |
| 1.3.6.1.4.1.674.10903.200.2.200.140 | NoderPDUPowerSupply | |||
| 1.3.6.1.4.1.674.10903.200.2.200.140.1 | ScalarrPDUPowerSupplyAlarmD | read-only | mandatory | Getting this OID will return the status of the power supply alarm. |
| 1.3.6.1.4.1.674.10903.200.2.200.140.2 | ScalarrPDUPowerSupplyVoltage | read-only | mandatory | The voltage provided by the power supply in tenths of volts. |
| 1.3.6.1.4.1.674.10903.200.2.200.150 | NoderPDUSensor | |||
| 1.3.6.1.4.1.674.10903.200.2.200.150.1 | NoderPDUSensorStatus | |||
| 1.3.6.1.4.1.674.10903.200.2.200.150.1.1 | ScalarrPDUSensorStatusTableSize | read-only | mandatory | The number of connected temperature sensors. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.1.2 | TablerPDUSensorStatusTable | not-accessible | mandatory | A table of temperature sensor status data. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.1.2.1 | RowrPDUSensorStatusEntry | not-accessible | mandatory | Status information from the temperature sensor being queried. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.1.2.1.1 | ColumnrPDUSensorStatusIndex | read-only | mandatory | The index to the status data table entry. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.1.2.1.2 | ColumnrPDUSensorStatusName | read-write | mandatory | The user-defined sensor ID string. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.1.2.1.3 | ColumnrPDUSensorStatusType | read-only | mandatory | The type of the sensor. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.2 | NoderPDUSensorTemp | |||
| 1.3.6.1.4.1.674.10903.200.2.200.150.2.1 | ScalarrPDUSensorTempTableSize | read-only | mandatory | The number of connected temperature sensors. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.2.2 | TablerPDUSensorTempStatusTable | not-accessible | mandatory | A table of temperature sensor status data. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1 | RowrPDUSensorTempStatusEntry | not-accessible | mandatory | Status information from the temperature sensor being queried. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1.1 | ColumnrPDUSensorTempStatusIndex | read-only | mandatory | The index to the temperature status data table entry. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1.2 | ColumnrPDUSensorTempStatusName | read-write | mandatory | The user-defined temperature-humidity sensor ID string. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1.3 | ColumnrPDUSensorTempStatusCommStatus | read-only | mandatory | The communications status of the sensor. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1.4 | ColumnrPDUSensorTempStatusTempF | read-only | mandatory | The sensor temperature reading in tenths of degrees Fahrenheit. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1.5 | ColumnrPDUSensorTempStatusTempC | read-only | mandatory | The sensor temperature reading in tenths of degrees Celsius. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1.6 | ColumnrPDUSensorTempStatusAlarmStatus | read-only | mandatory | The alarm status of the sensor. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.2.3 | TablerPDUSensorTempConfigTable | not-accessible | mandatory | A table of temperature-humidity sensor configuration data. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1 | RowrPDUSensorTempConfigEntry | not-accessible | mandatory | Configuration data from the temperature-humidity sensor being queried. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.1 | ColumnrPDUSensorTempConfigIndex | read-only | mandatory | The index to the temperature-humidity sensor configuration data table entry. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.2 | ColumnrPDUSensorTempConfigName | read-write | mandatory | The user-defined temperature-humidity sensor ID string. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.3 | ColumnrPDUSensorTempCfgTempMaxThreshF | read-write | mandatory | The sensor maximum temperature alarm threshold in Fahrenheit. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.4 | ColumnrPDUSnsorTempCfgTempHighThreshF | read-write | mandatory | The sensor high temperature warning alarm threshold in Fahrenheit. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.5 | ColumnrPDUSnsorTempCfgTempHysteresisF | read-write | mandatory | The sensor temperature hysteresis setting in Fahrenheit. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.6 | ColumnrPDUSensorTempCfgTempMaxThreshC | read-write | mandatory | The sensor maximum temperature alarm threshold in Celsius. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.7 | ColumnrPDUSnsorTempCfgTempHighThreshC | read-write | mandatory | The sensor high temperature warning alarm threshold in Celsius. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.8 | ColumnrPDUSnsorTempCfgTempHysteresisC | read-write | mandatory | The sensor temperature hysteresis setting in Celsius. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.9 | ColumnrPDUSnsorTempCfgAlarmGeneration | read-write | mandatory | Indicates whether the Temp Alarm Generation is enabled. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.3 | NoderPDUSensorHumidity | |||
| 1.3.6.1.4.1.674.10903.200.2.200.150.3.1 | ScalarrPDUSensorHumidityTableSize | read-only | mandatory | The number of connected temperature-humidity sensors. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.3.2 | TablerPDUSensorHumidityStatusTable | not-accessible | mandatory | A table of temperature-humidity sensor status data. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.3.2.1 | RowrPDUSensorHumidityStatusEntry | not-accessible | mandatory | Status information from the temperature-humidity sensor being queried. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.3.2.1.1 | ColumnrPDUSensorHumidityStatusIndex | read-only | mandatory | The index to the temperature-humidity status data table entry. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.3.2.1.2 | ColumnrPDUSensorHumidityStatusName | read-write | mandatory | The user-defined temperature-humidity sensor ID string. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.3.2.1.3 | ColumnrPDUSnsorHumidityStatCommStatus | read-only | mandatory | The communications status of the sensor. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.3.2.1.4 | ColumnrPDUSnsorHumStatRelativeHumdity | read-only | mandatory | The sensor humidity reading in percent relative humidity. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.3.2.1.5 | ColumnrPDUSnsorHumStatusAlarmStatus | read-only | mandatory | The alarm status of the sensor. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.3.3 | TablerPDUSensorHumidityConfigTable | not-accessible | mandatory | A table of temperature-humidity sensor configuration data. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1 | RowrPDUSensorHumidityConfigEntry | not-accessible | mandatory | Configuration data from the temperature-humidity sensor being queried. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1.1 | ColumnrPDUSensorHumidityConfigIndex | read-only | mandatory | The index to the temperature-humidity sensor configuration data table entry. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1.2 | ColumnrPDUSensorHumidityConfigName | read-write | mandatory | The user-defined temperature-humidity sensor ID string. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1.3 | ColumnrPDUSnsorHumCfgHumdityLowThresh | read-write | mandatory | The sensor low humidity warning alarm threshold in percent relative humidity. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1.4 | ColumnrPDUSnsorHumCfgHumdityMinThresh | read-write | mandatory | The sensor minimum humidity alarm threshold in percent relative humidity. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1.5 | ColumnrPDUSnsorHumCfgHumdtyHysteresis | read-write | mandatory | The sensor humidity hysteresis setting in percent relative humidity. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1.6 | ColumnrPDUSnsorHumCfgAlarmGeneration | read-write | mandatory | Indicates whether the Humidity Alarm Generation is enabled. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.4 | NoderPDUSensorDiscrete | |||
| 1.3.6.1.4.1.674.10903.200.2.200.150.4.1 | ScalarrPDUSensorDiscreteTableSize | read-only | mandatory | The number of connected discrete sensors. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.4.2 | TablerPDUSensorDiscreteStatusTable | not-accessible | mandatory | A table of discrete sensor status data. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.4.2.1 | RowrPDUSensorDiscreteStatusEntry | not-accessible | mandatory | Status information from the discrete sensor being queried. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.4.2.1.1 | ColumnrPDUSensorDiscreteStatusIndex | read-only | mandatory | The index to the discrete sensor status data table entry. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.4.2.1.2 | ColumnrPDUSensorDiscreteStatusName | read-write | mandatory | The user-defined discrete sensor ID string. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.4.2.1.3 | ColumnrPDUSnsorDiscreteStatCurntState | read-only | mandatory | The current state of the discrete sensor, open, closed, or unknown. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.4.2.1.4 | ColumnrPDUSnsorDiscreteStatAlarmState | read-only | mandatory | Indicates the alarm status of the discrete sensor input. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.4.3 | TablerPDUSensorDiscreteConfigTable | not-accessible | mandatory | A table of discrete sensor configuration data. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.4.3.1 | RowrPDUSensorDiscreteConfigEntry | not-accessible | mandatory | Configuration data from the discrete sensor being queried. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.4.3.1.1 | ColumnrPDUSensorDiscreteConfigIndex | read-only | mandatory | The index to the discrete sensor configuration data table entry. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.4.3.1.2 | ColumnrPDUSensorDiscreteConfigName | read-write | mandatory | The user-defined discrete sensor ID string. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.4.3.1.3 | ColumnrPDUSnsorDiscreteCfgNormalState | read-write | mandatory | Indicates the normal state of the discrete input contact. |
| 1.3.6.1.4.1.674.10903.200.2.200.150.4.3.1.4 | ColumnrPDUSnsorDiscrteAlarmGeneration | read-write | mandatory | Indicates whether Discrete Alarm Generation is enabled. |
| 1.3.6.1.4.1.674.10903.200.2.200.160 | NodemtrapargsD | |||
| 1.3.6.1.4.1.674.10903.200.2.200.160.1 | ScalarcontactNumber | read-only | mandatory | This OID allows traps to be sent with an integer argument that may not be defined in the MIB. A get of this OID will return 0. |
| 1.3.6.1.4.1.674.10903.200.2.200.160.2 | ScalaroutletNumber | read-only | mandatory | This OID allows traps to be sent with an integer argument that may not be defined in the MIB. A get of this OID will return 0. |
| 1.3.6.1.4.1.674.10903.200.2.200.160.3 | ScalarmtrapargsString | read-only | mandatory | This OID allows traps to be sent with an octet string argument that may not be defined in the MIB. A get of this OID will return a NULL string. |
| 1.3.6.1.4.1.674.10903.200.2.200.160.4 | ScalarphaseNumber | read-only | mandatory | This OID allows traps to be sent with an integer argument that may not be defined in the MIB. A get of this OID will return 0. |
| 1.3.6.1.4.1.674.10903.200.2.200.160.5 | ScalarsensorNumber | read-only | mandatory | This OID allows traps to be sent with an integer argument that may not be defined in the MIB. A get of this OID will return 0. |
| 1.3.6.1.4.1.674.10903.200.2.200.160.6 | ScalardeviceNameD | read-only | mandatory | This OID allows traps to be sent with an octet string argument that may not be defined in the MIB. A get of this OID will return a NULL string. |
| 1.3.6.1.4.1.674.10903.200.2.200.160.7 | ScalarserialNumber | read-only | mandatory | This OID allows traps to be sent with an octet string argument that may not be defined in the MIB. A get of this OID will return a NULL string. |
| 1.3.6.1.4.1.674.10903.200.2.200.160.8 | ScalartestTrapargsInteger | read-only | mandatory | This OID allows traps to be sent with an integer argument that may not be defined in the MIB. A get of this OID will return 0. |
| 1.3.6.1.4.1.674.10903.200.2.200.500 | Nodeevents | |||
| 1.3.6.1.4.1.674.10903.200.2.200.500.1 | NodedeviceCommunicationLostCleared | INFORMATIONAL: Lost communication with device has been re-established. The first argument is the serial number. The second argument is the device name. | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.2 | NodedeviceCommunicationLostSet | CRITICAL: Lost communication with device. The first argument is the serial number. The second argument is the device name. | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.3 | NodecomponentCommLostCleared | INFORMATIONAL: Lost communication with an on board component has been re-established. The first argument is the serial number. The second argument is the devic… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.4 | NodecomponentCommLostSet | CRITICAL: Lost communication with an on board component. The first argument is the serial number. The second argument is the device name. | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.5 | NodecANBusOffCleared | INFORMATIONAL: CAN bus off condition was cleared. The first argument is the serial number. The second argument is the device name. | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.6 | NodecanBusOffSet | MINOR: CAN bus off condition was set. The first argument is the serial number. The second argument is the device name. | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.7 | NodepowerSupplyFailureCleared | INFORMATIONAL: Unit's power supply voltage is no longer out of tolerance. The first argument is the serial number. The second argument is the device name. | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.8 | NodepowerSupplyFailureSet | CRITICAL: Unit's power supply voltage is out of tolerance. The first argument is the serial number. The second argument is the device name. | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.9 | NodekeypadButtonStuckCleared | INFORMATIONAL: Keypad button stuck has been cleared. The first argument is the serial number. The second argument is the device name. | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.10 | NodekeypadButtonStuckSet | MINOR: Keypad button stuck has been set. The first argument is the serial number. The second argument is the device name. | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.11 | NodedryContactAbnormalCleared | INFORMATIONAL: Dry Contact is no longer in an abnormal state. The first argument is the serial number. The second argument is the device name. The third argume… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.12 | NodedryContactAbnormalSet | CRITICAL: Dry Contact has moved to an abnormal state. The first argument is the serial number. The second argument is the device name. The third argument is th… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.13 | NodedeviceLowLoadCleared | INFORMATIONAL: Device load is no longer below the 'Low Load' threshold value. The first argument is the serial number. The second argument is the device name. | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.14 | NodedeviceLowLoadSet | MINOR: Device load has fallen below the 'Low Load' threshold value. The first argument is the serial number. The second argument is the device name. | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.15 | NodedeviceNearOverLoadCleared | INFORMATIONAL: Device load no longer exceeds the 'Near Over Load' threshold value. The first argument is the serial number. The second argument is the device n… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.16 | NodedeviceNearOverLoadSet | MINOR: Device load has exceeded the 'Near Over Load' threshold value. The first argument is the serial number. The second argument is the device name. | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.17 | NodedeviceOverLoadCleared | INFORMATIONAL: Device load no longer exceeds the 'Over Load' threshold value. The first argument is the serial number. The second argument is the device name. | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.18 | NodedeviceOverLoadSet | CRITICAL: Device load has exceeded the 'Over Load' threshold value. The first argument is the serial number. The second argument is the device name. | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.19 | NodephaseLowLoadCleared | INFORMATIONAL: Phase load is no longer below the 'Low Load' threshold value. The first argument is the serial number. The second argument is the device name. T… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.20 | NodephaseLowLoadSet | MINOR: Phase load has fallen below the 'Low Load' threshold value. The first argument is the serial number. The second argument is the device name. The third a… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.21 | NodephaseNearOverLoadCleared | INFORMATIONAL: Phase load no longer exceeds the 'Near Over Load' threshold value. The first argument is the serial number. The second argument is the device na… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.22 | NodephaseNearOverLoadSet | MINOR: Phase load has exceeded the 'Near Over Load' threshold value. The first argument is the serial number. The second argument is the device name. The third… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.23 | NodephaseOverLoadCleared | INFORMATIONAL: Phase load no longer exceeds the 'Over Load' threshold value. The first argument is the serial number. The second argument is the device name. T… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.24 | NodephaseOverLoadSet | CRITICAL: Phase load has exceeded the 'Over Load' threshold value. The first argument is the serial number. The second argument is the device name. The third a… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.25 | NodeoutletLowLoadCleared | INFORMATIONAL: Outlet load is no longer below the 'Low Load' threshold value. The first argument is the serial number. The second argument is the device name. … | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.26 | NodeoutletLowLoadSet | MINOR: Outlet load had fallen below the 'Low Load' threshold value. The first argument is the serial number. The second argument is the device name. The third … | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.27 | NodeoutletNearOverLoadCleared | INFORMATIONAL: Outlet load no longer exceeds the 'Near Over Load' threshold value. The first argument is the serial number. The second argument is the device n… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.28 | NodeoutletNearOverLoadSet | MINOR: Outlet load has exceeded the 'Near Over Load' threshold value. The first argument is the serial number. The second argument is the device name. The thir… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.29 | NodeoutletOverLoadCleared | INFORMATIONAL: Outlet load no longer exceeds the 'Over Load' threshold value. The first argument is the serial number. The second argument is the device name. … | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.30 | NodeoutletOverLoadSet | CRITICAL: Outlet load has exceeded the 'Over Load' threshold value. The first argument is the serial number. The second argument is the device name. The third … | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.31 | NodesensorDisconnectedCleared | INFORMATIONAL: Sensor disconnected condition cleared. The first argument is the serial number. The second argument is the device name. The third argument is th… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.32 | NodesensorDisconnectedSet | MINOR: Sensor disconnected condition set. The first argument is the serial number. The second argument is the device name. The third argument is the sensor num… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.33 | NodesensorTypeIndeterminateCleared | INFORMATIONAL: Sensor type indeterminate condition cleared. The first argument is the serial number. The second argument is the device name. The third argument… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.34 | NodesensorTypeIndeterminateSet | MINOR: Sensor type indeterminate condition set. The first argument is the serial number. The second argument is the device name. The third argument is the sens… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.35 | NodesensorTypeUnsupportedCleared | INFORMATIONAL: Sensor type unsupported condition cleared. The first argument is the serial number. The second argument is the device name. The third argument i… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.36 | NodesensorTypeUnsupportedSet | MINOR: Sensor type unsupported condition set. The first argument is the serial number. The second argument is the device name. The third argument is the sensor… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.37 | NodemaxTemperatureExceededCleared | INFORMATIONAL: Sensor Temperature no longer exceeds the 'Max Temperature' threshold value. The first argument is the serial number. The second argument is the … | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.38 | NodemaxTemperatureExceededSet | CRITICAL: Sensor Temperature has exceeded the 'Max Temperature' threshold value. The first argument is the serial number. The second argument is the device nam… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.39 | NodehighTemperatureExceededCleared | INFORMATIONAL: Sensor Temperature no longer exceeds the 'High Temperature' threshold value. The first argument is the serial number. The second argument is the… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.40 | NodehighTemperatureExceededSet | MINOR: Sensor Temperature has exceeded the 'High Temperature' threshold value. The first argument is the serial number. The second argument is the device name.… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.41 | NodelowHumidityExceededCleared | INFORMATIONAL: Sensor Humidity is no longer below the 'Low Humidity' threshold value. The first argument is the serial number. The second argument is the devic… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.42 | NodelowHumidityExceededSet | MINOR: Sensor Humidity has fallen below the 'Low Humidity' threshold value. The first argument is the serial number. The second argument is the device name. Th… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.43 | NodeminHumidityExceededCleared | INFORMATIONAL: Sensor Humidity is no longer below the 'Min Humidity' threshold value. The first argument is the serial number. The second argument is the devic… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.44 | NodeminHumidityExceededSet | CRITICAL: Sensor Humidity has fallen below the 'Min Humidity' threshold value. The first argument is the serial number. The second argument is the device name.… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.45 | NodeoutletTurnOn | INFORMATIONAL: An outlet has turned on. The first argument is the serial number. The second argument is the device name. The third argument is the outlet numbe… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.46 | NodeoutletTurnOff | INFORMATIONAL: An outlet has turned off. The first argument is the serial number. The second argument is the device name. The third argument is the outlet numb… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.47 | NodeactionCancelled | INFORMATIONAL: An outlet action has been cancelled. The first argument is the serial number. The second argument is the device name. The third argument is the … | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.48 | NodedeviceConfigurationChange | INFORMATIONAL: A device configuration has been changed. The first argument is the serial number. The second argument is the device name. | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.49 | NodesensorConfigurationChange | INFORMATIONAL: A sensor configuration has been changed. The first argument is the serial number. The second argument is the device name. The third argument is … | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.50 | NodeoutletConfigurationChange | INFORMATIONAL: An outlet configuration has been changed. The first argument is the serial number. The second argument is the device name. The third argument is… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.51 | NodephaseConfigurationChange | INFORMATIONAL: A phase configuration has been changed. The first argument is the serial number. The second argument is the device name. The third argument is t… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.52 | NodedryContactConfigurationChange | INFORMATIONAL: A dry contact configuration has been changed. The first argument is the serial number. The second argument is the device name. The third argumen… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.53 | NodeactionInit | INFORMATIONAL: An outlet action has been initialized. The first argument is the serial number. The second argument is the device name. The third argument is th… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.54 | NodeactionFailed | MINOR: An outlet action has failed to complete. The first argument is the serial number. The second argument is the device name. The third argument is the outl… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.55 | NodeactionDeleted | INFORMATIONAL: An outlet action has been deleted. The first argument is the serial number. The second argument is the device name. The third argument is the ou… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.56 | NodesyncCommandFailed | MINOR: An outlet sync command to another unit has failed. The first argument is the serial number. The second argument is the device name. The third argument i… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.57 | NodemPOPicFwDownloadStarted | INFORMATIONAL: MPO pic fw download started. The first argument is the serial number. The second argument is the device name. | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.58 | NodemPOPicFwDownloadComplete | INFORMATIONAL: MPO pic fw download complete. The first argument is the serial number. The second argument is the device name. | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.59 | NodemPOPicFwDownloadAborted | INFORMATIONAL: MPO pic fw download aborted. The first argument is the serial number. The second argument is the device name. | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.60 | NodesensorCommEstablished | INFORMATIONAL: Sensor comm established. The first argument is the serial number. The second argument is the device name. The third argument is the sensor numbe… | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.1000 | NodeconfigChangeSNMP | MINOR: The SNMP configuration has been changed. | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.1001 | NodeaccessViolationConsole | MINOR: Someone attempted console login with incorrect password three times. | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.1002 | NodeaccessViolationHTTP | MINOR: Someone attempted login via HTTP with incorrect password. | ||
| 1.3.6.1.4.1.674.10903.200.2.200.500.1003 | NodedellTestTrap | INFORMATIONAL: Trap used to test SNMP trap functionality. The first argument is a place holder for test variables. | ||
| 1.3.6.1.4.1.674.10903.200.3 | Nodesystem | |||
| 1.3.6.1.4.1.674.10903.200.3.1 | NodesysRPDUV1 |