DeltaUPS-MIB
206 objects
No module-level DESCRIPTION found.
Imported Objects
| RFC-1212 | OBJECT-TYPE |
| RFC-1215 | TRAP-TYPE |
| RFC1155-SMI | enterprises IpAddress |
| RFC1213-MIB | DisplayString |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.2254 | Nodedelta | |||
| 1.3.6.1.4.1.2254.2 | Nodeups | |||
| 1.3.6.1.4.1.2254.2.4 | Nodeupsv4 | |||
| 1.3.6.1.4.1.2254.2.4.1 | NodedupsIdent | |||
| 1.3.6.1.4.1.2254.2.4.1.1 | ScalardupsIdentManufacturer | read-only | mandatory | The name of the UPS manufacturer. |
| 1.3.6.1.4.1.2254.2.4.1.2 | ScalardupsIdentModel | read-only | mandatory | The UPS Model designation. |
| 1.3.6.1.4.1.2254.2.4.1.3 | ScalardupsIdentUPSSoftwareVersion | read-only | mandatory | The UPS firmware/software version(s). This variable may or may not has the same value as upsIdentAgentSoftwareVersion in some implementations. |
| 1.3.6.1.4.1.2254.2.4.1.4 | ScalardupsIdentAgentSoftwareVersion | read-only | mandatory | The UPS agent software version. This variable may or may not has the same value as upsIdentUPSSoftwareVersion in some implementations. |
| 1.3.6.1.4.1.2254.2.4.1.5 | ScalardupsIdentName | read-write | mandatory | A string identifying the UPS. This object should be set by the administrator. |
| 1.3.6.1.4.1.2254.2.4.1.6 | ScalardupsAttachedDevices | read-write | mandatory | A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator. |
| 1.3.6.1.4.1.2254.2.4.1.7 | ScalardupsRatingOutputVA | read-only | mandatory | The magnitude of the nominal output VA rating. |
| 1.3.6.1.4.1.2254.2.4.1.8 | ScalardupsRatingOutputVoltage | read-only | mandatory | The magnitude of the nominal output voltage rating. |
| 1.3.6.1.4.1.2254.2.4.1.9 | ScalardupsRatingOutputFrequency | read-only | mandatory | The magnitude of the nominal output frequency rating. |
| 1.3.6.1.4.1.2254.2.4.1.10 | ScalardupsRatingInputVoltage | read-only | mandatory | The magnitude of the nominal input voltage rating. |
| 1.3.6.1.4.1.2254.2.4.1.11 | ScalardupsRatingInputFrequency | read-only | mandatory | The magnitude of the nominal input frequency rating. |
| 1.3.6.1.4.1.2254.2.4.1.12 | ScalardupsRatingBatteryVoltage | read-only | mandatory | The magnitude of the nominal battery voltage rating. |
| 1.3.6.1.4.1.2254.2.4.1.13 | ScalardupsLowTransferVoltUpBound | read-only | mandatory | The minimum input line voltage upper bound allowed before the UPS system transfers to battery backup. |
| 1.3.6.1.4.1.2254.2.4.1.14 | ScalardupsLowTransferVoltLowBound | read-only | mandatory | The minimum input line voltage lower bound allowed before the UPS system transfers to battery backup. |
| 1.3.6.1.4.1.2254.2.4.1.15 | ScalardupsHighTransferVoltUpBound | read-only | mandatory | The maximum input line voltage upper bound allowed before the UPS system transfers to battery backup. |
| 1.3.6.1.4.1.2254.2.4.1.16 | ScalardupsHighTransferVoltLowBound | read-only | mandatory | The maximum input line voltage lower bound allowed before the UPS system transfers to battery backup. |
| 1.3.6.1.4.1.2254.2.4.1.17 | ScalardupsLowBattTime | read-only | mandatory | Minutes, time from low battery to low battery shutdown. |
| 1.3.6.1.4.1.2254.2.4.1.18 | ScalardupsOutletRelays | read-only | mandatory | Number of outlet relay. If it is 0, the function is not available for the UPS. |
| 1.3.6.1.4.1.2254.2.4.1.19 | ScalardupsType | read-only | mandatory | Indicate the UPS type. |
| 1.3.6.1.4.1.2254.2.4.2 | NodedupsControl | |||
| 1.3.6.1.4.1.2254.2.4.2.1 | ScalardupsShutdownType | read-write | mandatory | This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reach… |
| 1.3.6.1.4.1.2254.2.4.2.2 | ScalardupsAutoReboot | read-write | mandatory | In backup mode, the UPS may shutdown normally by SDA command, dry-contact remote shutdown signal or low battery shutdown. This command is used to determine the… |
| 1.3.6.1.4.1.2254.2.4.2.3 | ScalardupsShutdownAction | read-write | mandatory | If the value is greater than 0 the UPS performs shutdown action that defined by ShutdownType after the seconds. 0, aborted. |
| 1.3.6.1.4.1.2254.2.4.2.4 | ScalardupsRestartAction | read-write | mandatory | UPS will restart after the indicated number of minutes. -1, aborted. |
| 1.3.6.1.4.1.2254.2.4.2.5 | ScalardupsSetOutletRelay | read-write | mandatory | Indicate which outlet relay, from 1,2,3... . |
| 1.3.6.1.4.1.2254.2.4.2.6 | ScalardupsRelayOffDelay | read-write | mandatory | Turn the relay off after the seconds. The relay was indicated by SetOutletRelay. |
| 1.3.6.1.4.1.2254.2.4.2.7 | ScalardupsRelayOnDelay | read-write | mandatory | Turn the relay on after the minutes. The relay was indicated by SetOutletRelay. |
| 1.3.6.1.4.1.2254.2.4.3 | NodedupsConfig | |||
| 1.3.6.1.4.1.2254.2.4.3.1 | ScalardupsConfigBuzzerAlarm | read-write | mandatory | UPS will keep silence but will alarm again when next power event is occurred |
| 1.3.6.1.4.1.2254.2.4.3.2 | ScalardupsConfigBuzzerState | read-write | mandatory | If it is disabled then the UPS is always muted. |
| 1.3.6.1.4.1.2254.2.4.3.3 | ScalardupsConfigSensitivity | read-write | mandatory | The seneitivity of the UPS to utility line abnormalities or noises. |
| 1.3.6.1.4.1.2254.2.4.3.4 | ScalardupsConfigLowVoltageTransferPoint | read-write | mandatory | The minimum input line voltage allowed before the UPS system transfers to battery backup. |
| 1.3.6.1.4.1.2254.2.4.3.5 | ScalardupsConfigHighVoltageTransferPoint | read-write | mandatory | The maximum line voltage allowed before the UPS system transfers to battery backup. |
| 1.3.6.1.4.1.2254.2.4.3.6 | ScalardupsConfigShutdownOSDelay | read-write | mandatory | The operating system shutdown delay time when the input power fail. -1 will disable this option. |
| 1.3.6.1.4.1.2254.2.4.3.7 | ScalardupsConfigUPSBootDelay | read-write | mandatory | Delay the UPS startup after power restores. The power quality may not stable when power restores, this feature let the UPS wait a period of time to startup the… |
| 1.3.6.1.4.1.2254.2.4.3.8 | ScalardupsConfigExternalBatteryPack | read-write | mandatory | Indicate the number of external battery pack. |
| 1.3.6.1.4.1.2254.2.4.4 | NodedupsInput | |||
| 1.3.6.1.4.1.2254.2.4.4.1 | ScalardupsInputNumLines | read-only | mandatory | The number of input lines utilized in this device. |
| 1.3.6.1.4.1.2254.2.4.4.2 | ScalardupsInputFrequency1 | read-only | mandatory | The current input line 1 frequency to the UPS system in 1/10 Hz. |
| 1.3.6.1.4.1.2254.2.4.4.3 | ScalardupsInputVoltage1 | read-only | mandatory | The Input line 1 voltage of the UPS system in 1/10 V. |
| 1.3.6.1.4.1.2254.2.4.4.4 | ScalardupsInputCurrent1 | read-only | mandatory | The Input line 1 current to the UPS system in 1/10 A. |
| 1.3.6.1.4.1.2254.2.4.4.5 | ScalardupsInputFrequency2 | read-only | mandatory | The current input line 2 frequency to the UPS system in 1/10 Hz. |
| 1.3.6.1.4.1.2254.2.4.4.6 | ScalardupsInputVoltage2 | read-only | mandatory | The Input line 2 voltage of the UPS system in 1/10 V. |
| 1.3.6.1.4.1.2254.2.4.4.7 | ScalardupsInputCurrent2 | read-only | mandatory | The Input line 2 current to the UPS system in 1/10 A. |
| 1.3.6.1.4.1.2254.2.4.4.8 | ScalardupsInputFrequency3 | read-only | mandatory | The current input line 3 frequency to the UPS system in 1/10 Hz. |
| 1.3.6.1.4.1.2254.2.4.4.9 | ScalardupsInputVoltage3 | read-only | mandatory | The Input line 3 voltage of the UPS system in 1/10 V. |
| 1.3.6.1.4.1.2254.2.4.4.10 | ScalardupsInputCurrent3 | read-only | mandatory | The Input line 3 current to the UPS system in 1/10 A. |
| 1.3.6.1.4.1.2254.2.4.5 | NodedupsOutput | |||
| 1.3.6.1.4.1.2254.2.4.5.1 | ScalardupsOutputSource | read-only | mandatory | The present source of output power. The enumeration none(7) indicates that there is no source of output power (and therefore no output power), for example, the… |
| 1.3.6.1.4.1.2254.2.4.5.2 | ScalardupsOutputFrequency | read-only | mandatory | The present output frequency in 1/10 Hz. |
| 1.3.6.1.4.1.2254.2.4.5.3 | ScalardupsOutputNumLines | read-only | mandatory | The number of output lines utilized in this device. |
| 1.3.6.1.4.1.2254.2.4.5.4 | ScalardupsOutputVoltage1 | read-only | mandatory | The Output line 1 voltage of the UPS system in 1/10 V. |
| 1.3.6.1.4.1.2254.2.4.5.5 | ScalardupsOutputCurrent1 | read-only | mandatory | The Output line 1 current of the UPS system in 1/10 A. |
| 1.3.6.1.4.1.2254.2.4.5.6 | ScalardupsOutputPower1 | read-only | mandatory | The Output line 1 real power of the UPS system in watts. |
| 1.3.6.1.4.1.2254.2.4.5.7 | ScalardupsOutputLoad1 | read-only | mandatory | The current UPS output line 1 load expressed in percent of rated capacity. |
| 1.3.6.1.4.1.2254.2.4.5.8 | ScalardupsOutputVoltage2 | read-only | mandatory | The Output line 2 voltage of the UPS system in 1/10 V. |
| 1.3.6.1.4.1.2254.2.4.5.9 | ScalardupsOutputCurrent2 | read-only | mandatory | The Output line 2 current of the UPS system in 1/10 A. |
| 1.3.6.1.4.1.2254.2.4.5.10 | ScalardupsOutputPower2 | read-only | mandatory | The Output line 2 real power of the UPS system in watts. |
| 1.3.6.1.4.1.2254.2.4.5.11 | ScalardupsOutputLoad2 | read-only | mandatory | The current UPS output line 2 load expressed in percent of rated capacity. |
| 1.3.6.1.4.1.2254.2.4.5.12 | ScalardupsOutputVoltage3 | read-only | mandatory | The Output line 3 voltage of the UPS system in 1/10 V. |
| 1.3.6.1.4.1.2254.2.4.5.13 | ScalardupsOutputCurrent3 | read-only | mandatory | The Output line 3 current of the UPS system in 1/10 A. |
| 1.3.6.1.4.1.2254.2.4.5.14 | ScalardupsOutputPower3 | read-only | mandatory | The Output line 3 real power of the UPS system in watts. |
| 1.3.6.1.4.1.2254.2.4.5.15 | ScalardupsOutputLoad3 | read-only | mandatory | The current UPS output line 3 load expressed in percent of rated capacity. |
| 1.3.6.1.4.1.2254.2.4.6 | NodedupsBypass | |||
| 1.3.6.1.4.1.2254.2.4.6.1 | ScalardupsBypassFrequency | read-only | mandatory | The present bypass frequency in 1/10 Hz. |
| 1.3.6.1.4.1.2254.2.4.6.2 | ScalardupsBypassNumLines | read-only | mandatory | The number of bypass lines utilized in this device. |
| 1.3.6.1.4.1.2254.2.4.6.3 | ScalardupsBypassVoltage1 | read-only | mandatory | The bypass line 1 voltage of the UPS system in 1/10 V. |
| 1.3.6.1.4.1.2254.2.4.6.4 | ScalardupsBypassCurrent1 | read-only | mandatory | The bypass line 1 current of the UPS system in 1/10 A. |
| 1.3.6.1.4.1.2254.2.4.6.5 | ScalardupsBypassPower1 | read-only | mandatory | The bypass line 1 real power of the UPS system in watts. |
| 1.3.6.1.4.1.2254.2.4.6.6 | ScalardupsBypassVoltage2 | read-only | mandatory | The bypass line 2 voltage of the UPS system in 1/10 V. |
| 1.3.6.1.4.1.2254.2.4.6.7 | ScalardupsBypassCurrent2 | read-only | mandatory | The bypass line 2 current of the UPS system in 1/10 A. |
| 1.3.6.1.4.1.2254.2.4.6.8 | ScalardupsBypassPower2 | read-only | mandatory | The bypass line 2 real power of the UPS system in watts. |
| 1.3.6.1.4.1.2254.2.4.6.9 | ScalardupsBypassVoltage3 | read-only | mandatory | The bypass line 3 voltage of the UPS system in 1/10 V. |
| 1.3.6.1.4.1.2254.2.4.6.10 | ScalardupsBypassCurrent3 | read-only | mandatory | The bypass line 3 current of the UPS system in 1/10 A. |
| 1.3.6.1.4.1.2254.2.4.6.11 | ScalardupsBypassPower3 | read-only | mandatory | The bypass line 3 real power of the UPS system in watts. |
| 1.3.6.1.4.1.2254.2.4.7 | NodedupsBattery | |||
| 1.3.6.1.4.1.2254.2.4.7.1 | ScalardupsBatteryCondition | read-only | mandatory | The indication of the capacity remaining in the UPS system's batteries when AC normal. |
| 1.3.6.1.4.1.2254.2.4.7.2 | ScalardupsBatteryStatus | read-only | mandatory | The indication of the capacity remaining in the UPS system's batteries when AC failed. A value of ok indicates that the remaining run-time is greater than upsC… |
| 1.3.6.1.4.1.2254.2.4.7.3 | ScalardupsBatteryCharge | read-only | mandatory | Representing the battery charge status. |
| 1.3.6.1.4.1.2254.2.4.7.4 | ScalardupsSecondsOnBattery | read-only | mandatory | If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res… |
| 1.3.6.1.4.1.2254.2.4.7.5 | ScalardupsBatteryEstimatedTime | read-only | mandatory | Estimated time from backup to low battery shutdown. |
| 1.3.6.1.4.1.2254.2.4.7.6 | ScalardupsBatteryVoltage | read-only | mandatory | The magnitude of the present battery voltage in 1/10 V. |
| 1.3.6.1.4.1.2254.2.4.7.7 | ScalardupsBatteryCurrent | read-only | mandatory | The present battery current in 1/10 A. |
| 1.3.6.1.4.1.2254.2.4.7.8 | ScalardupsBatteryCapacity | read-only | mandatory | An estimate of the battery charge remaining expressed as a percent of full charge. |
| 1.3.6.1.4.1.2254.2.4.7.9 | ScalardupsTemperature | read-only | mandatory | The ambient temperature at or near the UPS Battery casing. |
| 1.3.6.1.4.1.2254.2.4.7.10 | ScalardupsLastReplaceDate | read-only | mandatory | The last battery replacement date. The format is YYYYMMDD. |
| 1.3.6.1.4.1.2254.2.4.7.11 | ScalardupsNextReplaceDate | read-only | mandatory | The next battery replacement date. The format is YYYYMMDD. |
| 1.3.6.1.4.1.2254.2.4.8 | NodedupsTest | |||
| 1.3.6.1.4.1.2254.2.4.8.1 | ScalardupsTestType | read-write | mandatory | Perform the UPS Test procedure. |
| 1.3.6.1.4.1.2254.2.4.8.2 | ScalardupsTestResultsSummary | read-only | mandatory | The results of the current or last UPS diagnostics test performed. The values for donePass(1), generalTestFail(3), and batteryTestFail(4) indicate that the tes… |
| 1.3.6.1.4.1.2254.2.4.8.3 | ScalardupsTestResultsDetail | read-only | mandatory | Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned. |
| 1.3.6.1.4.1.2254.2.4.9 | NodedupsAlarm | |||
| 1.3.6.1.4.1.2254.2.4.9.1 | ScalardupsAlarmDisconnect | read-only | mandatory | Does the UPS disconnect? |
| 1.3.6.1.4.1.2254.2.4.9.2 | ScalardupsAlarmPowerFail | read-only | mandatory | Does the input power fail? |
| 1.3.6.1.4.1.2254.2.4.9.3 | ScalardupsAlarmBatteryLow | read-only | mandatory | Are the UPS batteries low? |
| 1.3.6.1.4.1.2254.2.4.9.4 | ScalardupsAlarmLoadWarning | read-only | mandatory | Does the UPS load percent over the load warning value? |
| 1.3.6.1.4.1.2254.2.4.9.5 | ScalardupsAlarmLoadSeverity | read-only | mandatory | Does the UPS load percent over the load severity value? |
| 1.3.6.1.4.1.2254.2.4.9.6 | ScalardupsAlarmLoadOnBypass | read-only | mandatory | Does the UPS load on bypass? |
| 1.3.6.1.4.1.2254.2.4.9.7 | ScalardupsAlarmUPSFault | read-only | mandatory | Does the UPS general fail? |
| 1.3.6.1.4.1.2254.2.4.9.8 | ScalardupsAlarmBatteryGroundFault | read-only | mandatory | Does the UPS battery ground fault? |
| 1.3.6.1.4.1.2254.2.4.9.9 | ScalardupsAlarmTestInProgress | read-only | mandatory | Does the UPS test in progress? |
| 1.3.6.1.4.1.2254.2.4.9.10 | ScalardupsAlarmBatteryTestFail | read-only | mandatory | Does the UPS test fail? |
| 1.3.6.1.4.1.2254.2.4.9.11 | ScalardupsAlarmFuseFailure | read-only | mandatory | Does the UPS fuse failure? |
| 1.3.6.1.4.1.2254.2.4.9.12 | ScalardupsAlarmOutputOverload | read-only | mandatory | Does the UPS output overload? |
| 1.3.6.1.4.1.2254.2.4.9.13 | ScalardupsAlarmOutputOverCurrent | read-only | mandatory | Does the UPS output overcurrent? |
| 1.3.6.1.4.1.2254.2.4.9.14 | ScalardupsAlarmInverterAbnormal | read-only | mandatory | Does the UPS inverter abnormal? |
| 1.3.6.1.4.1.2254.2.4.9.15 | ScalardupsAlarmRectifierAbnormal | read-only | mandatory | Does the UPS rectifier abnormal? |
| 1.3.6.1.4.1.2254.2.4.9.16 | ScalardupsAlarmReserveAbnormal | read-only | mandatory | Does the UPS reserve abnormal? |
| 1.3.6.1.4.1.2254.2.4.9.17 | ScalardupsAlarmLoadOnReserve | read-only | mandatory | Does the UPS load on reserve? |
| 1.3.6.1.4.1.2254.2.4.9.18 | ScalardupsAlarmTemperature | read-only | mandatory | Does the UPS temperature out of range? |
| 1.3.6.1.4.1.2254.2.4.9.19 | ScalardupsAlarmOutputBad | read-only | mandatory | Is the UPS output abnormal? |
| 1.3.6.1.4.1.2254.2.4.9.20 | ScalardupsAlarmBypassBad | read-only | mandatory | Is the UPS bypass bad? |
| 1.3.6.1.4.1.2254.2.4.9.21 | ScalardupsAlarmUPSOff | read-only | mandatory | Is the UPS in standby mode? |
| 1.3.6.1.4.1.2254.2.4.9.22 | ScalardupsAlarmChargerFail | read-only | mandatory | Does the UPS charger fail? |
| 1.3.6.1.4.1.2254.2.4.9.23 | ScalardupsAlarmFanFail | read-only | mandatory | Does the UPS fan fail? |
| 1.3.6.1.4.1.2254.2.4.9.24 | ScalardupsAlarmEconomicMode | read-only | mandatory | Indicates whether the UPS is in the economic mode. |
| 1.3.6.1.4.1.2254.2.4.9.25 | ScalardupsAlarmOutputOff | read-only | mandatory | Indicates whether the UPS output is turned off or not. |
| 1.3.6.1.4.1.2254.2.4.9.26 | ScalardupsAlarmSmartShutdown | read-only | mandatory | Indicates whether the Smart Shutdown is in progress. |
| 1.3.6.1.4.1.2254.2.4.9.27 | ScalardupsAlarmEmergencyPowerOff | read-only | mandatory | UPS emergency power off. |
| 1.3.6.1.4.1.2254.2.4.9.28 | ScalardupsAlarmUPSShutdown | read-only | mandatory | UPS shutdown. |
| 1.3.6.1.4.1.2254.2.4.9.29 | ScalardupsAlarmOutputBreaker | read-only | mandatory | Indicates the state of output breaker. |
| 1.3.6.1.4.1.2254.2.4.9.30 | ScalardupsAlarmRedundancyLoss | read-only | mandatory | To indicate the capacity of redundancy lost in a modular UPS. |
| 1.3.6.1.4.1.2254.2.4.10 | NodedupsEnvironment | |||
| 1.3.6.1.4.1.2254.2.4.10.1 | ScalardupsEnvTemperature | read-only | mandatory | The ambient environmental temperature. |
| 1.3.6.1.4.1.2254.2.4.10.2 | ScalardupsEnvHumidity | read-only | mandatory | The environmental humidity. |
| 1.3.6.1.4.1.2254.2.4.10.3 | ScalardupsEnvSetTemperatureAlarmLimit | read-write | mandatory | Alarm dupsEnvOverAlarmTemperature on when the environmental temperature over the value. |
| 1.3.6.1.4.1.2254.2.4.10.4 | ScalardupsEnvSetHumidityAlarmLimit | read-write | mandatory | Alarm dupsEnvOverAlarmHumidity on when the environmental humidity over the value. |
| 1.3.6.1.4.1.2254.2.4.10.5 | ScalardupsEnvSetEnvRelay1 | read-write | mandatory | |
| 1.3.6.1.4.1.2254.2.4.10.6 | ScalardupsEnvSetEnvRelay2 | read-write | mandatory | |
| 1.3.6.1.4.1.2254.2.4.10.7 | ScalardupsEnvSetEnvRelay3 | read-write | mandatory | |
| 1.3.6.1.4.1.2254.2.4.10.8 | ScalardupsEnvSetEnvRelay4 | read-write | mandatory | |
| 1.3.6.1.4.1.2254.2.4.10.9 | ScalardupsAlarmOverEnvTemperature | read-only | mandatory | Does the environment over alarm temperature? |
| 1.3.6.1.4.1.2254.2.4.10.10 | ScalardupsAlarmOverEnvHumidity | read-only | mandatory | Does the environment over alarm humidity? |
| 1.3.6.1.4.1.2254.2.4.10.11 | ScalardupsAlarmEnvRelay1 | read-only | mandatory | |
| 1.3.6.1.4.1.2254.2.4.10.12 | ScalardupsAlarmEnvRelay2 | read-only | mandatory | |
| 1.3.6.1.4.1.2254.2.4.10.13 | ScalardupsAlarmEnvRelay3 | read-only | mandatory | |
| 1.3.6.1.4.1.2254.2.4.10.14 | ScalardupsAlarmEnvRelay4 | read-only | mandatory | |
| 1.3.6.1.4.1.2254.2.4.10.15 | ScalardupsEnvSetTemperatureWarnLimit | read-write | mandatory | Alarm dupsEnvOverWarnTemperature on when the environmental temperature over the value. |
| 1.3.6.1.4.1.2254.2.4.10.16 | ScalardupsEnvSetHumidityWarnLimit | read-write | mandatory | Alarm dupsEnvOverWarnHumidity on when the environmental humidity over the value. |
| 1.3.6.1.4.1.2254.2.4.10.17 | ScalardupsWarnOverEnvTemperature | read-only | mandatory | Does the environment over warning temperature? |
| 1.3.6.1.4.1.2254.2.4.10.18 | ScalardupsWarnOverEnvHumidity | read-only | mandatory | Does the environment over warning humidity? |
| 1.3.6.1.4.1.2254.2.4.20 | NodedupsTraps | |||
| 1.3.6.1.4.1.2254.2.4.20.1 | NodedupsCommunicationLost | SEVER: Communication with the UPS failed. | ||
| 1.3.6.1.4.1.2254.2.4.20.2 | NodedupsCommunicationEstablished | INFORMATION: Communication with the UPS reestablished. | ||
| 1.3.6.1.4.1.2254.2.4.20.3 | NodedupsPowerFail | WARNING: Power failed! The UPS is operating on battery power. | ||
| 1.3.6.1.4.1.2254.2.4.20.4 | NodedupsPowerRestored | INFORMATION: Power restored! The utility power restored. | ||
| 1.3.6.1.4.1.2254.2.4.20.5 | NodedupsLowBattery | SEVER: The UPS batteries are low and will soon be exhausted. | ||
| 1.3.6.1.4.1.2254.2.4.20.6 | NodedupsReturnFromLowBattery | INFORMATION: The UPS has returned from a low battery condition. | ||
| 1.3.6.1.4.1.2254.2.4.20.7 | NodedupsLoadWarning | INFORMATION: Loading percent of the UPS over the Load Warning value. | ||
| 1.3.6.1.4.1.2254.2.4.20.8 | NodedupsNoLongerLoadWarning | INFORMATION: Returnd from Load Warning condition. | ||
| 1.3.6.1.4.1.2254.2.4.20.9 | NodedupsLoadSeverity | Warning: Loading percent of the UPS over the Load Severity value. | ||
| 1.3.6.1.4.1.2254.2.4.20.10 | NodedupsNoLongerLoadSeverity | INFORMATION: Returned from Load Severity condition. | ||
| 1.3.6.1.4.1.2254.2.4.20.11 | NodedupsLoadOnBypass | SEVER: The UPS loads on bypass. | ||
| 1.3.6.1.4.1.2254.2.4.20.12 | NodedupsNoLongerLoadOnBypass | INFORMATION: The UPS is not on bypass mode. | ||
| 1.3.6.1.4.1.2254.2.4.20.13 | NodedupsUPSFault | SEVER: A general fault caused in the UPS. | ||
| 1.3.6.1.4.1.2254.2.4.20.14 | NodedupsReturnFromUPSFault | INFORMATION: The UPS is returned from general fault. | ||
| 1.3.6.1.4.1.2254.2.4.20.15 | NodedupsBatteryGroundFault | SEVER: The UPS battery ground fault. | ||
| 1.3.6.1.4.1.2254.2.4.20.16 | NodedupsNoLongerBatteryFault | INFORMATION: The UPS recovered from battery ground fault. | ||
| 1.3.6.1.4.1.2254.2.4.20.17 | NodedupsTestInProgress | INFORMATION: The UPS test in progress. | ||
| 1.3.6.1.4.1.2254.2.4.20.18 | NodedupsBatteryTestFail | SEVER: The UPS test fail. | ||
| 1.3.6.1.4.1.2254.2.4.20.19 | NodedupsFuseFailure | SEVER: The UPS fuse failed. | ||
| 1.3.6.1.4.1.2254.2.4.20.20 | NodedupsFuseRecovered | INFORMATION: The UPS fuse recovered. | ||
| 1.3.6.1.4.1.2254.2.4.20.21 | NodedupsOutputOverload | SEVER: The UPS overload!. | ||
| 1.3.6.1.4.1.2254.2.4.20.22 | NodedupsNoLongerOverload | INFORMATION: Recovered from UPS overload. | ||
| 1.3.6.1.4.1.2254.2.4.20.23 | NodedupsOutputOverCurrent | SEVER: The UPS output overcurrent. | ||
| 1.3.6.1.4.1.2254.2.4.20.24 | NodedupsNoLongerOutputOverCurrent | INFORMATION: Recovered from UPS overcurrent. | ||
| 1.3.6.1.4.1.2254.2.4.20.25 | NodedupsInverterAbnormal | SEVER: The UPS inverter abnormal. | ||
| 1.3.6.1.4.1.2254.2.4.20.26 | NodedupsInverterRecovered | INFORMATION: Recovered from UPS inverter abnormal. | ||
| 1.3.6.1.4.1.2254.2.4.20.27 | NodedupsRectifierAbnormal | SEVER: The UPS rectifier abnormal. | ||
| 1.3.6.1.4.1.2254.2.4.20.28 | NodedupsRectifierRecovered | INFORMATION: The UPS recovered from rectifier abnormal. | ||
| 1.3.6.1.4.1.2254.2.4.20.29 | NodedupsReserveAbnormal | SEVER: The UPS rectifier abnormal. | ||
| 1.3.6.1.4.1.2254.2.4.20.30 | NodedupsReserveRecovered | INFORMATION: The UPS rectifier abnormal. | ||
| 1.3.6.1.4.1.2254.2.4.20.31 | NodedupsLoadOnReserve | SEVER: The UPS load on reserve. | ||
| 1.3.6.1.4.1.2254.2.4.20.32 | NodedupsNoLongerLoadOnReserve | INFORMATION: The UPS no longer load on reserve. | ||
| 1.3.6.1.4.1.2254.2.4.20.33 | NodedupsEnvOverAlarmTemperature | SEVER: The environment over alarm temperature. | ||
| 1.3.6.1.4.1.2254.2.4.20.34 | NodedupsNoLongerEnvOverAlarmTemperature | INFORMATION: The environment recovered from over alarm temperature. | ||
| 1.3.6.1.4.1.2254.2.4.20.35 | NodedupsEnvOverAlarmHumidity | SEVER: The environment over alarm humidity. | ||
| 1.3.6.1.4.1.2254.2.4.20.36 | NodedupsNoLongerEnvOverAlarmHumidity | INFORMATION: The environment recovered from over alarm humidity. | ||
| 1.3.6.1.4.1.2254.2.4.20.37 | NodedupsEnvRelay1Alarm | INFORMATION: The environment relay1 is not in normal state. | ||
| 1.3.6.1.4.1.2254.2.4.20.38 | NodedupsEnvRelay1Normal | INFORMATION: The environment relay1 is in normal state. | ||
| 1.3.6.1.4.1.2254.2.4.20.39 | NodedupsEnvRelay2Alarm | INFORMATION: The environment relay2 is not in normal state. | ||
| 1.3.6.1.4.1.2254.2.4.20.40 | NodedupsEnvRelay2Normal | INFORMATION: The environment relay2 is in normal state. | ||
| 1.3.6.1.4.1.2254.2.4.20.41 | NodedupsEnvRelay3Alarm | INFORMATION: The environment relay3 is not in normal state. | ||
| 1.3.6.1.4.1.2254.2.4.20.42 | NodedupsEnvRelay3Normal | INFORMATION: The environment relay3 is in normal state. | ||
| 1.3.6.1.4.1.2254.2.4.20.43 | NodedupsEnvRelay4Alarm | INFORMATION: The environment relay4 is not in normal state. | ||
| 1.3.6.1.4.1.2254.2.4.20.44 | NodedupsEnvRelay4Normal | INFORMATION: The environment relay4 is in normal state. | ||
| 1.3.6.1.4.1.2254.2.4.20.45 | NodedupsSmartShutdown | SEVER: Smart Shutdown is initiated. | ||
| 1.3.6.1.4.1.2254.2.4.20.46 | NodedupsCancelShutdown | INFORMATION: Cancel UPS Shutdown. | ||
| 1.3.6.1.4.1.2254.2.4.20.47 | NodedupsTestCompleted | INFORMATION: This trap is sent upon completion of a UPS diagnostic test. | ||
| 1.3.6.1.4.1.2254.2.4.20.48 | NodedupsEPOON | INFORMATION: This trap is sent when emergency power off is on. | ||
| 1.3.6.1.4.1.2254.2.4.20.49 | NodedupsEPOOFF | INFORMATION: This trap is sent when UPS recover from emergency power off. | ||
| 1.3.6.1.4.1.2254.2.4.20.51 | NodedupsNormalTemperature | INFORMATION: This trap is sent when UPS temperature back to normal. | ||
| 1.3.6.1.4.1.2254.2.4.20.52 | NodedupsBattReplace | WARNING: The battery needs to be replaced. | ||
| 1.3.6.1.4.1.2254.2.4.20.53 | NodedupsReturnFromBattReplace | INFORMATION: The UPS recovered from battery replacement. | ||
| 1.3.6.1.4.1.2254.2.4.20.54 | NodedupsEnvCommunicationLost | WARNING: Communication with the environmental sensor failed. | ||
| 1.3.6.1.4.1.2254.2.4.20.55 | NodedupsEnvCommunicationEstablished | INFORMATION: Communication with the environmental sensor reestablished. | ||
| 1.3.6.1.4.1.2254.2.4.20.56 | NodedupsEnvOverWarnTemperature | WARNING: The environment over warning temperature. | ||
| 1.3.6.1.4.1.2254.2.4.20.57 | NodedupsNoLongerEnvOverWarnTemperature | INFORMATION: The environment recovered from over warning temperature. | ||
| 1.3.6.1.4.1.2254.2.4.20.58 | NodedupsEnvOverWarnHumidity | WARNING: The environment over warning humidity. | ||
| 1.3.6.1.4.1.2254.2.4.20.59 | NodedupsNoLongerEnvOverWarnHumidity | INFORMATION: The environment recovered from over warning humidity. | ||
| 1.3.6.1.4.1.2254.2.4.20.60 | NodedupsEconomyModeEnabled | INFORMATION: The economy mode is enabled. | ||
| 1.3.6.1.4.1.2254.2.4.20.61 | NodedupsEconomyModeDisabled | INFORMATION: The economy mode is disabled. |