DeltaUPSv5-MIB

323 objects
No module-level DESCRIPTION found.
Imported Objects
RFC-1212OBJECT-TYPE
RFC-1215TRAP-TYPE
RFC1155-SMIenterprises IpAddress TimeTicks
RFC1213-MIBDisplayString
OIDNameAccessStatusDescription
1.3.6.1.4.1.2254Nodedelta
1.3.6.1.4.1.2254.2Nodeups
1.3.6.1.4.1.2254.2.5Nodeupsv5
1.3.6.1.4.1.2254.2.5.1NodedupsIdent
1.3.6.1.4.1.2254.2.5.1.1ScalardupsIdentManufacturerread-onlymandatoryThe name of the UPS manufacturer.
1.3.6.1.4.1.2254.2.5.1.2ScalardupsIdentModelread-onlymandatoryThe UPS Model designation.
1.3.6.1.4.1.2254.2.5.1.3ScalardupsIdentUPSSoftwareVersionread-onlymandatoryThe UPS firmware/software version(s). This variable may or may not has the same value as upsIdentAgentSoftwareVersion in some implementations.
1.3.6.1.4.1.2254.2.5.1.4ScalardupsIdentAgentSoftwareVersionread-onlymandatoryThe UPS agent software version. This variable may or may not has the same value as upsIdentUPSSoftwareVersion in some implementations.
1.3.6.1.4.1.2254.2.5.1.5ScalardupsIdentNameread-writemandatoryA string identifying the UPS. This object should be set by the administrator.
1.3.6.1.4.1.2254.2.5.1.6ScalardupsAttachedDevicesread-writemandatoryA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.
1.3.6.1.4.1.2254.2.5.1.7ScalardupsRatingOutputVAread-onlymandatoryThe magnitude of the nominal output VA rating. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.1.8ScalardupsRatingOutputVoltageread-onlymandatoryThe magnitude of the nominal output voltage rating. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.1.9ScalardupsRatingOutputFrequencyread-onlymandatoryThe magnitude of the nominal output frequency rating. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.1.10ScalardupsRatingInputVoltageread-onlymandatoryThe magnitude of the nominal input voltage rating. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.1.11ScalardupsRatingInputFrequencyread-onlymandatoryThe magnitude of the nominal input frequency rating. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.1.12ScalardupsRatingBatteryVoltageread-onlymandatoryThe magnitude of the nominal battery voltage rating. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.1.13ScalardupsLowTransferVoltUpBoundread-onlymandatoryThe minimum input line voltage upper bound allowed before the UPS system transfers to battery backup. The value -1 indicates this UPS does not support this ite…
1.3.6.1.4.1.2254.2.5.1.14ScalardupsLowTransferVoltLowBoundread-onlymandatoryThe minimum input line voltage lower bound allowed before the UPS system transfers to battery backup. The value -1 indicates this UPS does not support this ite…
1.3.6.1.4.1.2254.2.5.1.15ScalardupsHighTransferVoltUpBoundread-onlymandatoryThe maximum input line voltage upper bound allowed before the UPS system transfers to battery backup. The value -1 indicates this UPS does not support this ite…
1.3.6.1.4.1.2254.2.5.1.16ScalardupsHighTransferVoltLowBoundread-onlymandatoryThe maximum input line voltage lower bound allowed before the UPS system transfers to battery backup. The value -1 indicates this UPS does not support this ite…
1.3.6.1.4.1.2254.2.5.1.17ScalardupsLowBattTimeread-onlymandatoryMinutes, time from low battery to low battery shutdown. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.1.18ScalardupsOutletRelaysread-onlymandatoryNumber of outlet relay. If it is 0, the function is not available for the UPS.
1.3.6.1.4.1.2254.2.5.1.19ScalardupsTyperead-onlymandatoryIndicate the UPS type.
1.3.6.1.4.1.2254.2.5.2NodedupsControl
1.3.6.1.4.1.2254.2.5.2.1ScalardupsShutdownTyperead-writemandatoryThis object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reach…
1.3.6.1.4.1.2254.2.5.2.2ScalardupsAutoRebootread-writemandatoryIn backup mode, the UPS may shutdown normally by SDA command, dry-contact remote shutdown signal or low battery shutdown. This command is used to determine the…
1.3.6.1.4.1.2254.2.5.2.3ScalardupsShutdownActionread-writemandatoryIf the value is greater than 0 the UPS performs shutdown action that defined by ShutdownType after the seconds. 0, aborted.
1.3.6.1.4.1.2254.2.5.2.4ScalardupsRestartActionread-writemandatoryUPS will restart after the indicated number of minutes. -1, aborted.
1.3.6.1.4.1.2254.2.5.2.5ScalardupsSetOutletRelayread-writemandatoryIndicate which outlet relay, from 1,2,3... .
1.3.6.1.4.1.2254.2.5.2.6ScalardupsRelayOffDelayread-writemandatoryTurn the relay off after the seconds. The relay was indicated by SetOutletRelay.
1.3.6.1.4.1.2254.2.5.2.7ScalardupsRelayOnDelayread-writemandatoryTurn the relay on after the minutes. The relay was indicated by SetOutletRelay.
1.3.6.1.4.1.2254.2.5.2.8ScalardupsSmartShutdownread-writemandatoryAny value to initiate the Smart Shutdown for the UPS.
1.3.6.1.4.1.2254.2.5.2.9ScalardupsClearEnergyread-writemandatoryAny value to clear the energy record in the UPS.
1.3.6.1.4.1.2254.2.5.3NodedupsConfig
1.3.6.1.4.1.2254.2.5.3.1ScalardupsConfigBuzzerAlarmread-writemandatoryUPS will keep silence but will alarm again when next power event is occurred
1.3.6.1.4.1.2254.2.5.3.2ScalardupsConfigBuzzerStateread-writemandatoryIf it is disabled then the UPS is always muted.
1.3.6.1.4.1.2254.2.5.3.3ScalardupsConfigSensitivityread-writemandatoryThe seneitivity of the UPS to utility line abnormalities or noises.
1.3.6.1.4.1.2254.2.5.3.4ScalardupsConfigLowVoltageTransferPointread-writemandatoryThe minimum input line voltage allowed before the UPS system transfers to battery backup.
1.3.6.1.4.1.2254.2.5.3.5ScalardupsConfigHighVoltageTransferPointread-writemandatoryThe maximum line voltage allowed before the UPS system transfers to battery backup.
1.3.6.1.4.1.2254.2.5.3.6ScalardupsConfigUPSBootDelayread-writemandatoryDelay the UPS startup after power restores. The power quality may not stable when power restores, this feature let the UPS wait a period of time to startup the…
1.3.6.1.4.1.2254.2.5.3.7ScalardupsConfigExternalBatteryPackread-writemandatoryIndicate the number of external battery pack.
1.3.6.1.4.1.2254.2.5.3.8ScalardupsConfigSmartShutdownOSDelayread-writemandatoryThe estimated operating system shutdown delay time for Smart Shutdown.
1.3.6.1.4.1.2254.2.5.3.9ScalardupsConfigSmartShutdownUPSDelayread-writemandatoryThe estimated UPS shutdown delay time for Smart Shutdown.
1.3.6.1.4.1.2254.2.5.3.10ScalardupsConfigEconomicModeread-writemandatoryUsed to enable or disable the economic mode.
1.3.6.1.4.1.2254.2.5.4NodedupsInput
1.3.6.1.4.1.2254.2.5.4.1ScalardupsInputNumLinesread-onlymandatoryThe number of input lines utilized in this device.
1.3.6.1.4.1.2254.2.5.4.2ScalardupsInputFrequency1read-onlymandatoryThe current input line 1 frequency to the UPS system in 1/10 Hz. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.4.3ScalardupsInputVoltage1read-onlymandatoryThe Input phase 1 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.4.4ScalardupsInputVoltage12read-onlymandatoryThe Input line 1-2 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.4.5ScalardupsInputCurrent1read-onlymandatoryThe Input line 1 current to the UPS system in 1/10 A. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.4.6ScalardupsInputPower1read-onlymandatoryThe Input line 1 power to the UPS system in 1 Watt. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.4.7ScalardupsInputFrequency2read-onlymandatoryThe current input line 2 frequency to the UPS system in 1/10 Hz. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.4.8ScalardupsInputVoltage2read-onlymandatoryThe Input phase 2 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.4.9ScalardupsInputVoltage23read-onlymandatoryThe Input line 2-3 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.4.10ScalardupsInputCurrent2read-onlymandatoryThe Input line 2 current to the UPS system in 1/10 A. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.4.11ScalardupsInputPower2read-onlymandatoryThe Input line 2 power to the UPS system in 1 Watt. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.4.12ScalardupsInputFrequency3read-onlymandatoryThe current input line 3 frequency to the UPS system in 1/10 Hz. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.4.13ScalardupsInputVoltage3read-onlymandatoryThe Input phase 3 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.4.14ScalardupsInputVoltage31read-onlymandatoryThe Input line 3-1 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.4.15ScalardupsInputCurrent3read-onlymandatoryThe Input line 3 current to the UPS system in 1/10 A. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.4.16ScalardupsInputPower3read-onlymandatoryThe Input line 3 power to the UPS system in 1 Watt. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.4.17ScalardupsInputEnergy1read-onlymandatoryThe Input line 1 energy to the UPS system in 1 kWh. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.4.18ScalardupsInputEnergy2read-onlymandatoryThe Input line 2 energy to the UPS system in 1 kWh. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.4.19ScalardupsInputEnergy3read-onlymandatoryThe Input line 3 energy to the UPS system in 1 kWh. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.4.20ScalardupsInputEnergyTotalread-onlymandatoryThe total Input energy to the UPS system in 1 kWh. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.4.21ScalardupsInputLineFailCauseread-onlymandatoryCause of input outage.
1.3.6.1.4.1.2254.2.5.4.22ScalardupsInputBadStatusread-onlymandatoryIncorrect input voltage or frequency.
1.3.6.1.4.1.2254.2.5.5NodedupsOutput
1.3.6.1.4.1.2254.2.5.5.1ScalardupsOutputSourceread-onlymandatoryThe present source of output power. The enumeration noOutput(8) indicates that there is no source of output power (and therefore no output power), for example,…
1.3.6.1.4.1.2254.2.5.5.2ScalardupsOutputFrequencyread-onlymandatoryThe present output frequency in 1/10 Hz. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.5.3ScalardupsOutputNumLinesread-onlymandatoryThe number of output lines utilized in this device.
1.3.6.1.4.1.2254.2.5.5.4ScalardupsOutputVoltage1read-onlymandatoryThe Output phase 1 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.5.5ScalardupsOutputVoltage12read-onlymandatoryThe Output line 1-2 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.5.6ScalardupsOutputCurrent1read-onlymandatoryThe Output line 1 current of the UPS system in 1/10 A. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.5.7ScalardupsOutputPower1read-onlymandatoryThe Output line 1 active power of the UPS system in watts. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.5.8ScalardupsOutputLoad1read-onlymandatoryThe current UPS output line 1 load expressed in percent of rated capacity. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.5.9ScalardupsOutputVoltage2read-onlymandatoryThe Output phase 2 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.5.10ScalardupsOutputVoltage23read-onlymandatoryThe Output line 2-3 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.5.11ScalardupsOutputCurrent2read-onlymandatoryThe Output line 2 current of the UPS system in 1/10 A. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.5.12ScalardupsOutputPower2read-onlymandatoryThe Output line 2 active power of the UPS system in watts. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.5.13ScalardupsOutputLoad2read-onlymandatoryThe current UPS output line 2 load expressed in percent of rated capacity. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.5.14ScalardupsOutputVoltage3read-onlymandatoryThe Output phase 3 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.5.15ScalardupsOutputVoltage31read-onlymandatoryThe Output line 3-1 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.5.16ScalardupsOutputCurrent3read-onlymandatoryThe Output line 3 current of the UPS system in 1/10 A. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.5.17ScalardupsOutputPower3read-onlymandatoryThe Output line 3 active power of the UPS system in watts. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.5.18ScalardupsOutputLoad3read-onlymandatoryThe current UPS output line 3 load expressed in percent of rated capacity. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.5.19ScalardupsOutputTotalActivePowerread-onlymandatoryThe total output active power of the UPS system in 0.1 kW. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.5.20ScalardupsOutputTotalApparentPowerread-onlymandatoryThe total output apparent power of the UPS system in 0.1 kVA. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.5.21ScalardupsOutputTotalPowerFactorread-onlymandatoryThe total output power factor of the UPS system. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.5.22ScalardupsOutputEnergy1read-onlymandatoryThe UPS output line 1 energy in kWh. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.5.23ScalardupsOutputEnergy2read-onlymandatoryThe UPS output line 2 energy in kWh. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.5.24ScalardupsOutputEnergy3read-onlymandatoryThe UPS output line 3 energy in kWh. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.5.25ScalardupsOutputEnergyTotalread-onlymandatoryThe UPS total output energy in kWh. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.6NodedupsBypass
1.3.6.1.4.1.2254.2.5.6.1ScalardupsBypassFrequencyread-onlymandatoryThe present bypass frequency in 1/10 Hz. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.6.2ScalardupsBypassNumLinesread-onlymandatoryThe number of bypass lines utilized in this device.
1.3.6.1.4.1.2254.2.5.6.3ScalardupsBypassVoltage1read-onlymandatoryThe bypass phase 1 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.6.4ScalardupsBypassVoltage12read-onlymandatoryThe bypass line 1-2 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.6.5ScalardupsBypassCurrent1read-onlymandatoryThe bypass line 1 current of the UPS system in 1/10 A. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.6.6ScalardupsBypassPower1read-onlymandatoryThe bypass line 1 real power of the UPS system in watts. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.6.7ScalardupsBypassVoltage2read-onlymandatoryThe bypass phase 2 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.6.8ScalardupsBypassVoltage23read-onlymandatoryThe bypass line 2-3 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.6.9ScalardupsBypassCurrent2read-onlymandatoryThe bypass line 2 current of the UPS system in 1/10 A. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.6.10ScalardupsBypassPower2read-onlymandatoryThe bypass line 2 real power of the UPS system in watts. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.6.11ScalardupsBypassVoltage3read-onlymandatoryThe bypass phase 3 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.6.12ScalardupsBypassVoltage31read-onlymandatoryThe bypass line 3-1 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.6.13ScalardupsBypassCurrent3read-onlymandatoryThe bypass line 3 current of the UPS system in 1/10 A. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.6.14ScalardupsBypassPower3read-onlymandatoryThe bypass line 3 real power of the UPS system in watts. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.6.15ScalardupsBypassSTSTemperatureread-onlymandatoryThe measurement of bypass STS temperature. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.7NodedupsBattery
1.3.6.1.4.1.2254.2.5.7.1ScalardupsBatteryConditionread-onlymandatoryThe indication of the capacity remaining in the UPS system's batteries when AC normal.
1.3.6.1.4.1.2254.2.5.7.2ScalardupsBatteryStatusread-onlymandatoryThe indication of the capacity remaining in the UPS system's batteries when AC failed. A value of ok indicates that the remaining run-time is greater than upsC…
1.3.6.1.4.1.2254.2.5.7.3ScalardupsBatteryChargeread-onlymandatoryRepresenting the battery charge status.
1.3.6.1.4.1.2254.2.5.7.4ScalardupsSecondsOnBatteryread-onlymandatoryIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res…
1.3.6.1.4.1.2254.2.5.7.5ScalardupsBatteryEstimatedTimeread-onlymandatoryEstimated time from backup to low battery shutdown.
1.3.6.1.4.1.2254.2.5.7.6ScalardupsBatteryPosVoltageread-onlymandatoryThe magnitude of the present positive battery voltage in 1/10 V.
1.3.6.1.4.1.2254.2.5.7.7ScalardupsBatteryNegVoltageread-onlymandatoryThe magnitude of the present negative battery voltage in -1/10 V.
1.3.6.1.4.1.2254.2.5.7.8ScalardupsBatteryPosCurrentread-onlymandatoryThe present positive battery current in 1/10 A.
1.3.6.1.4.1.2254.2.5.7.9ScalardupsBatteryNegCurrentread-onlymandatoryThe present negative battery current in 1/10 A.
1.3.6.1.4.1.2254.2.5.7.10ScalardupsBatteryPosCapacityread-onlymandatoryAn estimate of the positive battery charge remaining expressed as a percent of full charge.
1.3.6.1.4.1.2254.2.5.7.11ScalardupsBatteryNegCapacityread-onlymandatoryAn estimate of the negative battery charge remaining expressed as a percent of full charge.
1.3.6.1.4.1.2254.2.5.7.12ScalardupsTemperatureread-onlymandatoryThe measurement of internal temperature in the UPS.
1.3.6.1.4.1.2254.2.5.7.13ScalardupsLastReplaceDateread-onlymandatoryThe last battery replacement date. The format is YYYYMMDD.
1.3.6.1.4.1.2254.2.5.7.14ScalardupsNextReplaceDateread-onlymandatoryThe next battery replacement date. The format is YYYYMMDD.
1.3.6.1.4.1.2254.2.5.7.15ScalardupsBatteryBreakerread-onlymandatoryIndicate the battery breaker status.
1.3.6.1.4.1.2254.2.5.7.16ScalardupsBatteryCab1Tempuratureread-onlymandatoryTemperature of battery cabnet 1.
1.3.6.1.4.1.2254.2.5.7.17ScalardupsBatteryCab2Tempuratureread-onlymandatoryTemperature of battery cabnet 2.
1.3.6.1.4.1.2254.2.5.7.18ScalardupsBatteryCab3Tempuratureread-onlymandatoryTemperature of battery cabnet 3.
1.3.6.1.4.1.2254.2.5.7.19ScalardupsBatteryCab4Tempuratureread-onlymandatoryTemperature of battery cabnet 4.
1.3.6.1.4.1.2254.2.5.8NodedupsTest
1.3.6.1.4.1.2254.2.5.8.1ScalardupsTestTyperead-writemandatoryPerform the UPS Test procedure.
1.3.6.1.4.1.2254.2.5.8.2ScalardupsTestResultsSummaryread-onlymandatoryThe results of the current or last UPS diagnostics test performed. The values for donePass(1), generalTestFail(3), and batteryTestFail(4) indicate that the tes…
1.3.6.1.4.1.2254.2.5.8.3ScalardupsTestResultsDetailread-onlymandatoryAdditional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.
1.3.6.1.4.1.2254.2.5.8.4ScalardupsGeneratorTestread-writemandatoryPerform the Generator Test procedure.
1.3.6.1.4.1.2254.2.5.8.5ScalardupsGeneratorTestStatusread-onlymandatoryThe results of the current or last generator diagnostics test performed.The values for None(2), InhibitTest(3), AbnormallyTerminate(4), ByInstruction(5), and B…
1.3.6.1.4.1.2254.2.5.9NodedupsAlarm
1.3.6.1.4.1.2254.2.5.9.1ScalardupsAlarmDisconnectread-onlymandatoryIndicate the communication of the UPS is connected or disconnect?
1.3.6.1.4.1.2254.2.5.9.2ScalardupsAlarmInputOutOfRangeread-onlymandatoryRepresenting the input power is out of tolerance. This item is used to indicate the input power fail, a test condition should not set this item on.
1.3.6.1.4.1.2254.2.5.9.3ScalardupsAlarmBatteryLowread-onlymandatoryAre the UPS batteries low?
1.3.6.1.4.1.2254.2.5.9.4ScalardupsAlarmLoadOnBypassread-onlymandatoryDoes the UPS load on bypass?
1.3.6.1.4.1.2254.2.5.9.5ScalardupsAlarmOtherread-onlymandatoryIndicate there is an alarm detected but which is not defined here.
1.3.6.1.4.1.2254.2.5.9.6ScalardupsAlarmBatteryGroundFaultread-onlymandatoryTo indicate the battery ground fault has been detected.
1.3.6.1.4.1.2254.2.5.9.7ScalardupsAlarmTestInProgressread-onlymandatoryDoes the UPS test in progress?
1.3.6.1.4.1.2254.2.5.9.8ScalardupsAlarmBatteryTestFailread-onlymandatoryDoes the UPS test fail?
1.3.6.1.4.1.2254.2.5.9.9ScalardupsAlarmFuseFailureread-onlymandatoryThe failure of one or more fuses has been detected.
1.3.6.1.4.1.2254.2.5.9.10ScalardupsAlarmOutputOverloadread-onlymandatoryThe output load exceeds the UPS output capacity.
1.3.6.1.4.1.2254.2.5.9.11ScalardupsAlarmInverterAbnormalread-onlymandatoryRepresenting the inverter fail alarm.
1.3.6.1.4.1.2254.2.5.9.12ScalardupsAlarmLoadOnReserveread-onlymandatoryDoes the UPS load on reserve?
1.3.6.1.4.1.2254.2.5.9.13ScalardupsAlarmTemperatureread-onlymandatoryRepresenting one of the temperature sensors has been determined its value is out of the limits.
1.3.6.1.4.1.2254.2.5.9.14ScalardupsAlarmBypassOutOfRangeread-onlymandatoryThe bypass power is out of range.
1.3.6.1.4.1.2254.2.5.9.15ScalardupsAlarmStandbyread-onlymandatoryThe UPS system is in the standby state.
1.3.6.1.4.1.2254.2.5.9.16ScalardupsAlarmChargerFailread-onlymandatoryAn incorrected problem has been detected within the UPS charger subsystem
1.3.6.1.4.1.2254.2.5.9.17ScalardupsAlarmFanFailread-onlymandatoryThe failure of one or more fans in the UPS has been detected.
1.3.6.1.4.1.2254.2.5.9.18ScalardupsAlarmEconomicModeread-onlymandatoryThe UPS is working in the economic mode (act like an off-line UPS).
1.3.6.1.4.1.2254.2.5.9.19ScalardupsAlarmOutputOffread-onlymandatoryUPS output is turned off.
1.3.6.1.4.1.2254.2.5.9.20ScalardupsAlarmSmartShutdownread-onlymandatoryIndicates whether the Smart Shutdown is in progress.
1.3.6.1.4.1.2254.2.5.9.21ScalardupsAlarmEmergencyPowerOffread-onlymandatoryRepresenting the UPS is shutdown due to the Emergency Power Off button is pressed.
1.3.6.1.4.1.2254.2.5.9.22ScalardupsAlarmUPSShutdownread-onlymandatoryThe UPS has been shutdown including remote and fault shutdown.
1.3.6.1.4.1.2254.2.5.9.23ScalardupsAlarmEPOread-onlymandatoryRepresenting the UPS is shutdown due to the Emergency Power Off button is pressed.
1.3.6.1.4.1.2254.2.5.9.24ScalardupsAlarmOutVoltOverLimitread-onlymandatoryTo indicate the output voltage is over limit.
1.3.6.1.4.1.2254.2.5.9.25ScalardupsAlarmOutVoltUnderLimitread-onlymandatoryTo indicate the output voltage is under limit.
1.3.6.1.4.1.2254.2.5.9.26ScalardupsAlarmPowerModuleread-onlymandatoryTo indicate there is at least one alarm from power module.
1.3.6.1.4.1.2254.2.5.9.27ScalardupsAlarmOutputBreakerread-onlymandatoryTo indicate the output breaker is detected open or close.
1.3.6.1.4.1.2254.2.5.9.28ScalardupsAlarmOutletBank1Breakerread-onlymandatoryTo indicate the outlet bank-1 breaker is detected open or close.
1.3.6.1.4.1.2254.2.5.9.29ScalardupsAlarmOutletBank2Breakerread-onlymandatoryTo indicate the outlet bank-2 breaker is detected open or close.
1.3.6.1.4.1.2254.2.5.9.30ScalardupsAlarmOutletBank3Breakerread-onlymandatoryTo indicate the outlet bank-3 breaker is detected open or close.
1.3.6.1.4.1.2254.2.5.9.31ScalardupsAlarmOutletBank4Breakerread-onlymandatoryTo indicate the outlet bank-4 breaker is detected open or close.
1.3.6.1.4.1.2254.2.5.9.32ScalardupsAlarmSummaryread-onlymandatoryTo indicate the alarm level for the UPS.
1.3.6.1.4.1.2254.2.5.9.33ScalardupsAlarmRedundancyLossread-onlymandatoryTo indicate the capacity of redundancy lost in a modular UPS.
1.3.6.1.4.1.2254.2.5.9.34ScalardupsAlarmPhaseAsynchronousread-onlymandatoryTo indicate the Phase is detected asynchronous or synchronous.
1.3.6.1.4.1.2254.2.5.9.35ScalardupsAlarmRectifierAbnormalread-onlymandatoryTo indicate the Rectifier is detected alarm or normal.
1.3.6.1.4.1.2254.2.5.9.36ScalardupsAlarmBypassBreakerOpenread-onlymandatoryTo indicate the bypass breaker is detected open or close.
1.3.6.1.4.1.2254.2.5.9.37ScalardupsAlarmMainInputBreakerOpenread-onlymandatoryTo indicate the main input breaker is detected open or close.
1.3.6.1.4.1.2254.2.5.9.38ScalardupsAlarmManualBypassBreakerread-onlymandatoryTo indicate the manual bypass breaker is detected open or close.
1.3.6.1.4.1.2254.2.5.10NodedupsPowerModule
1.3.6.1.4.1.2254.2.5.10.1ScalardupsPMBypassInputAlarmread-onlymandatoryIndicates the bypass voltage/frequency is abnormal.
1.3.6.1.4.1.2254.2.5.10.2ScalardupsPMBypassPhaseAlarmread-onlymandatoryIndicates the bypass phase sequence is abnormal.
1.3.6.1.4.1.2254.2.5.10.3ScalardupsPMBypassSTSOverloadAlarmread-onlymandatoryIndicates the bypass STS overload.
1.3.6.1.4.1.2254.2.5.10.4ScalardupsPMBypassSTSOverTempAlarmread-onlymandatoryIndicates the bypass STS over temperature.
1.3.6.1.4.1.2254.2.5.10.5ScalardupsPMBypassSTSFailAlarmread-onlymandatoryIndicates the bypass STS fail.
1.3.6.1.4.1.2254.2.5.10.6TabledupsPMTablenot-accessiblemandatoryA list of power module table entries.
1.3.6.1.4.1.2254.2.5.10.6.1RowdupsPMEntrynot-accessiblemandatoryAn entry containing information applicable to a particular power module.
1.3.6.1.4.1.2254.2.5.10.6.1.1ColumndupsPMIDnot-accessiblemandatoryThe power module identifier.
1.3.6.1.4.1.2254.2.5.10.6.1.2ColumndupsPMPFCTempread-onlymandatoryThe power module PFC temperature.
1.3.6.1.4.1.2254.2.5.10.6.1.3ColumndupsPMINVTempread-onlymandatoryThe power module inverter temperature.
1.3.6.1.4.1.2254.2.5.10.6.1.4ColumndupsPMINVTempRread-onlymandatoryThe power module inverter-R temperature.
1.3.6.1.4.1.2254.2.5.10.6.1.5ColumndupsPMINVTempSread-onlymandatoryThe power module inverter-S temperature.
1.3.6.1.4.1.2254.2.5.10.6.1.6ColumndupsPMINVTempTread-onlymandatoryThe power module inverter-T temperature.
1.3.6.1.4.1.2254.2.5.10.6.1.7ColumndupsPMINVVolt1read-onlymandatoryThe inverter line 1 voltage of the power module in 1/10 V.
1.3.6.1.4.1.2254.2.5.10.6.1.8ColumndupsPMINVVolt2read-onlymandatoryThe inverter line 2 voltage of the power module in 1/10 V.
1.3.6.1.4.1.2254.2.5.10.6.1.9ColumndupsPMINVVolt3read-onlymandatoryThe inverter line 3 voltage of the power module in 1/10 V.
1.3.6.1.4.1.2254.2.5.10.6.1.10ColumndupsPMStsNotExistread-onlymandatoryIndicates the power module is existed or not?
1.3.6.1.4.1.2254.2.5.10.6.1.11ColumndupsPMStsOffread-onlymandatoryIndicates the power module is on or off?
1.3.6.1.4.1.2254.2.5.10.6.1.12ColumndupsPMStsRepairread-onlymandatoryIndicates the power module is in repair mode or not?
1.3.6.1.4.1.2254.2.5.10.6.1.13ColumndupsPMStsFaultShutdownread-onlymandatoryIndicates the power module status of fault shutdown.
1.3.6.1.4.1.2254.2.5.10.6.1.14ColumndupsPMStsPFCFuseFailread-onlymandatoryIndicates the power module PFC fuse open or close?
1.3.6.1.4.1.2254.2.5.10.6.1.15ColumndupsPMStsPFCOverTempWarningread-onlymandatoryIndicates the power module PFC over temperature warning.
1.3.6.1.4.1.2254.2.5.10.6.1.16ColumndupsPMStsPFCOverTempShutdownread-onlymandatoryIndicates the power module PFC over temperature shutdown.
1.3.6.1.4.1.2254.2.5.10.6.1.17ColumndupsPMStsPFCOverVoltWarningread-onlymandatoryIndicates the power module PFC over voltage warning.
1.3.6.1.4.1.2254.2.5.10.6.1.18ColumndupsPMStsPFCOverVoltShutdownread-onlymandatoryIndicates the power module PFC over voltage shutdown.
1.3.6.1.4.1.2254.2.5.10.6.1.19ColumndupsPMStsPFCUnderVoltWarningread-onlymandatoryIndicates the power module PFC under voltage warning.
1.3.6.1.4.1.2254.2.5.10.6.1.20ColumndupsPMStsPFCUnderVoltShutdownread-onlymandatoryIndicates the power module PFC under voltage shutdown.
1.3.6.1.4.1.2254.2.5.10.6.1.21ColumndupsPMStsPFCGeneralFaultread-onlymandatoryIndicates the power module PFC genreal fault.
1.3.6.1.4.1.2254.2.5.10.6.1.22ColumndupsPMStsPFCFanFailread-onlymandatoryIndicates the power module PFC fan fail.
1.3.6.1.4.1.2254.2.5.10.6.1.23ColumndupsPMStsPFCCurrentLimitread-onlymandatoryIndicates the power module PFC output current limit.
1.3.6.1.4.1.2254.2.5.10.6.1.24ColumndupsPMStsPFCOffread-onlymandatoryIndicates the power module PFC off.
1.3.6.1.4.1.2254.2.5.10.6.1.25ColumndupsPMStsPFCInnerCommFailread-onlymandatoryIndicates the power module PFC inner communication fail.
1.3.6.1.4.1.2254.2.5.10.6.1.26ColumndupsPMStsPFCNotCalibratedread-onlymandatoryIndicates the power module PFC is not calibrated.
1.3.6.1.4.1.2254.2.5.10.6.1.27ColumndupsPMStsINVFuseFailread-onlymandatoryIndicates the power module Inverter fuse open or close?
1.3.6.1.4.1.2254.2.5.10.6.1.28ColumndupsPMStsINVOverTempWarningread-onlymandatoryIndicates the power module Inverter over temperature warning.
1.3.6.1.4.1.2254.2.5.10.6.1.29ColumndupsPMStsINVOverTempShutdownread-onlymandatoryIndicates the power module Inverter over temperature shutdown.
1.3.6.1.4.1.2254.2.5.10.6.1.30ColumndupsPMStsINVFanFailread-onlymandatoryIndicates the power module Inverter fan fail.
1.3.6.1.4.1.2254.2.5.10.6.1.31ColumndupsPMStsINVShortCircuitread-onlymandatoryIndicates the power module Inverter short circuit.
1.3.6.1.4.1.2254.2.5.10.6.1.32ColumndupsPMStsINVSTSFailread-onlymandatoryIndicates the power module Inverter STS fail.
1.3.6.1.4.1.2254.2.5.10.6.1.33ColumndupsPMStsINVCircuitFailread-onlymandatoryIndicates the power module Inverter circuit fail shutdown.
1.3.6.1.4.1.2254.2.5.10.6.1.34ColumndupsPMStsINVOverVoltread-onlymandatoryIndicates the power module Inverter over voltage shutdown.
1.3.6.1.4.1.2254.2.5.10.6.1.35ColumndupsPMStsINVOverloadread-onlymandatoryIndicates the power module Inverter overload.
1.3.6.1.4.1.2254.2.5.10.6.1.36ColumndupsPMStsINVInnerCommFailread-onlymandatoryIndicates the power module Inverter inner communication fail.
1.3.6.1.4.1.2254.2.5.10.6.1.37ColumndupsPMStsINVEPOread-onlymandatoryIndicates the power module Inverter EPO shutdown.
1.3.6.1.4.1.2254.2.5.10.6.1.38ColumndupsPMStsINVParallelCommFailread-onlymandatoryIndicates the power module Inverter parallel communication fail.
1.3.6.1.4.1.2254.2.5.10.6.1.39ColumndupsPMStsINVParallelFailread-onlymandatoryIndicates the power module Inverter parallel fail.
1.3.6.1.4.1.2254.2.5.10.6.1.40ColumndupsPMStsINVSTSOnread-onlymandatoryIndicates the status of power module Inverter state.
1.3.6.1.4.1.2254.2.5.10.6.1.41ColumndupsPMStsINVNotCalibratedread-onlymandatoryIndicates the power module Inverter is not calibrated.
1.3.6.1.4.1.2254.2.5.10.6.1.42ColumndupsPMStsChargerFailread-onlymandatoryIndicates the power module Charger fail.
1.3.6.1.4.1.2254.2.5.10.6.1.43ColumndupsPMSummaryStatusread-onlymandatoryThe power module summary status.
1.3.6.1.4.1.2254.2.5.10.6.1.44ColumndupsPMPFCTempRread-onlymandatoryThe power module pfc-R temperature.
1.3.6.1.4.1.2254.2.5.10.6.1.45ColumndupsPMPFCTempSread-onlymandatoryThe power module pfc-S temperature.
1.3.6.1.4.1.2254.2.5.10.6.1.46ColumndupsPMPFCTempTread-onlymandatoryThe power module pfc-T temperature.
1.3.6.1.4.1.2254.2.5.11NodedupsTrapArgs
1.3.6.1.4.1.2254.2.5.11.1ScalardupsDescriptionread-onlymandatoryThis OID is used for traps to send with a string argument. A get of this OID will return an empty string.
1.3.6.1.4.1.2254.2.5.11.2ScalardupsTimeTicksread-onlymandatoryThis OID is used for traps to send with a TimeTicks argument. A get of this OID will return 0.
1.3.6.1.4.1.2254.2.5.12NodedupsParallel
1.3.6.1.4.1.2254.2.5.12.1ScalardupsParallelRatingVAread-onlymandatoryThe summary rating VA to the parallel UPSs system.
1.3.6.1.4.1.2254.2.5.12.2ScalardupsParallelRatingPowerread-onlymandatoryThe summary rating power to the parallel UPSs system.
1.3.6.1.4.1.2254.2.5.12.3ScalardupsParallelInCurrent1read-onlymandatoryThe summary input line 1 current to the parallel UPSs system in 1/10 A. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.12.4ScalardupsParallelInCurrent2read-onlymandatoryThe summary input line 2 current to the parallel UPSs system in 1/!0 A. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.12.5ScalardupsParallelInCurrent3read-onlymandatoryThe summary input line 3 current to the parallel UPSs system in 1/!0 A. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.12.6ScalardupsParallelOutCurrent1read-onlymandatoryThe summary output line 1 current to the parallel UPSs system in 1/10 A. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.12.7ScalardupsParallelOutCurrent2read-onlymandatoryThe summary output line 2 current to the parallel UPSs system in 1/10 A. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.12.8ScalardupsParallelOutCurrent3read-onlymandatoryThe summary output line 3 current to the parallel UPSs system in 1/10 A. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.12.9ScalardupsParallelOutPower1read-onlymandatoryThe summary output line 1 power to the parallel UPSs system. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.12.10ScalardupsParallelOutPower2read-onlymandatoryThe summary output line 2 power to the parallel UPSs system. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.12.11ScalardupsParallelOutPower3read-onlymandatoryThe summary output line 3 power to the parallel UPSs system. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.12.12ScalardupsParallelInEnergy1read-onlymandatoryThe summary input line 1 energy to the parallel UPSs system. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.12.13ScalardupsParallelInEnergy2read-onlymandatoryThe summary input line 2 energy to the parallel UPSs system. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.12.14ScalardupsParallelInEnergy3read-onlymandatoryThe summary input line 3 energy to the parallel UPSs system. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.12.15ScalardupsParallelInEnergyTotalread-onlymandatoryThe summary total input energy to the parallel UPSs system. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.12.16ScalardupsParallelOutEnergy1read-onlymandatoryThe summary output line 1 energy to the parallel UPSs system. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.12.17ScalardupsParallelOutEnergy2read-onlymandatoryThe summary output line 2 energy to the parallel UPSs system. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.12.18ScalardupsParallelOutEnergy3read-onlymandatoryThe summary output line 3 energy to the parallel UPSs system. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.12.19ScalardupsParallelOutEnergyTotalread-onlymandatoryThe summary total output energy to the parallel UPSs system. The value -1 indicates this UPS does not support this item.
1.3.6.1.4.1.2254.2.5.13NodedupsIntegrated
1.3.6.1.4.1.2254.2.5.13.1ScalardupsIntegratedParallelread-onlymandatoryMultiple frame with the same group present.
1.3.6.1.4.1.2254.2.5.13.2ScalardupsIntegratedDryInput1read-onlymandatoryDry1 Input state.
1.3.6.1.4.1.2254.2.5.13.3ScalardupsIntegratedDryInput2read-onlymandatoryDry2 Input state.
1.3.6.1.4.1.2254.2.5.13.4ScalardupsIntegratedDryInput3read-onlymandatoryDry3 Input state.
1.3.6.1.4.1.2254.2.5.13.5ScalardupsIntegratedDryInput4read-onlymandatoryDry4 Input state.
1.3.6.1.4.1.2254.2.5.20NodedupsTraps
1.3.6.1.4.1.2254.2.5.20.1NodedupsCommunicationLostSEVER: Communication with the UPS failed.
1.3.6.1.4.1.2254.2.5.20.2NodedupsCommunicationEstablishedINFORMATION: Communication with the UPS reestablished.
1.3.6.1.4.1.2254.2.5.20.3NodedupsPowerFailWARNING: Power failed! The UPS is operating on battery power.
1.3.6.1.4.1.2254.2.5.20.4NodedupsPowerRestoredINFORMATION: Power restored! The utility power restored.
1.3.6.1.4.1.2254.2.5.20.5NodedupsLowBatterySEVER: The UPS batteries are low and will soon be exhausted.
1.3.6.1.4.1.2254.2.5.20.6NodedupsReturnFromLowBatteryINFORMATION: The UPS has returned from a low battery condition.
1.3.6.1.4.1.2254.2.5.20.7NodedupsLoadOnBypassSEVER: The UPS loads on bypass.
1.3.6.1.4.1.2254.2.5.20.8NodedupsNoLongerLoadOnBypassINFORMATION: The UPS is not on bypass mode.
1.3.6.1.4.1.2254.2.5.20.9NodedupsUPSFaultSEVER: A general fault caused in the UPS.
1.3.6.1.4.1.2254.2.5.20.10NodedupsReturnFromUPSFaultINFORMATION: The UPS is returned from general fault.
1.3.6.1.4.1.2254.2.5.20.11NodedupsBatteryGroundFaultSEVER: The UPS battery ground fault.
1.3.6.1.4.1.2254.2.5.20.12NodedupsNoLongerBatteryFaultINFORMATION: The UPS recovered from battery ground fault.
1.3.6.1.4.1.2254.2.5.20.13NodedupsTestInProgressINFORMATION: The UPS test in progress.
1.3.6.1.4.1.2254.2.5.20.14NodedupsBatteryTestFailSEVER: The UPS test fail.
1.3.6.1.4.1.2254.2.5.20.15NodedupsFuseFailureSEVER: The UPS fuse failed.
1.3.6.1.4.1.2254.2.5.20.16NodedupsFuseRecoveredINFORMATION: The UPS fuse recovered.
1.3.6.1.4.1.2254.2.5.20.17NodedupsOutputOverloadSEVER: The UPS overload!.
1.3.6.1.4.1.2254.2.5.20.18NodedupsNoLongerOverloadINFORMATION: Recovered from UPS overload.
1.3.6.1.4.1.2254.2.5.20.19NodedupsInverterAbnormalSEVER: The UPS inverter abnormal.
1.3.6.1.4.1.2254.2.5.20.20NodedupsInverterRecoveredINFORMATION: Recovered from UPS inverter abnormal.
1.3.6.1.4.1.2254.2.5.20.21NodedupsSmartShutdownInitSEVER: Smart Shutdown is initiated.
1.3.6.1.4.1.2254.2.5.20.22NodedupsCancelShutdownINFORMATION: Cancel UPS Shutdown.
1.3.6.1.4.1.2254.2.5.20.23NodedupsTestCompletedINFORMATION: This trap is sent upon completion of a UPS diagnostic test.
1.3.6.1.4.1.2254.2.5.20.24NodedupsEPOONINFORMATION: This trap is sent when emergency power off is on.
1.3.6.1.4.1.2254.2.5.20.25NodedupsEPOOFFINFORMATION: This trap is sent when UPS recover from emergency power off.
1.3.6.1.4.1.2254.2.5.20.26NodedupsTemperatureAlarmSEVER: This trap is sent when the UPS temperature out of range.
1.3.6.1.4.1.2254.2.5.20.27NodedupsTemperatureNormalINFORMATION: This trap is sent when UPS temperature back to normal.
1.3.6.1.4.1.2254.2.5.20.28NodedupsBattReplaceWARNING: The battery needs to be replaced.
1.3.6.1.4.1.2254.2.5.20.29NodedupsReturnFromBattReplaceINFORMATION: The UPS recovered from battery replacement.
1.3.6.1.4.1.2254.2.5.20.30NodedupsOutputOffSEVER: Indicate the UPS output is turned off.
1.3.6.1.4.1.2254.2.5.20.31NodedupsReturnFromOutputOffINFORMATION: The UPS recovered from output off.
1.3.6.1.4.1.2254.2.5.20.32NodedupsShutdownSEVER: The UPS has been shutdown including remote and fault shutdown.
1.3.6.1.4.1.2254.2.5.20.33NodedupsReturnFromShutdownINFORMATION: The UPS recovered from shutdown.
1.3.6.1.4.1.2254.2.5.20.34NodedupsChargerFailSEVER: An incorrected problem has been detected within the UPS charger subsystem.
1.3.6.1.4.1.2254.2.5.20.35NodedupsReturnFromChargerFailINFORMATION: The UPS recovered from charger fail.
1.3.6.1.4.1.2254.2.5.20.36NodedupsOnStandbySEVER: The UPS system is in the standby state.
1.3.6.1.4.1.2254.2.5.20.37NodedupsReturnFromStandbyINFORMATION: The UPS no longer on standby mode.
1.3.6.1.4.1.2254.2.5.20.38NodedupsFanFailSEVER: The failure of one or more fans in the UPS has been detected.
1.3.6.1.4.1.2254.2.5.20.39NodedupsReturnFromFanFailINFORMATION: The UPS recover from fan fail.
1.3.6.1.4.1.2254.2.5.20.40NodedupsOnEconomicINFORMATION: The UPS is working in the economic mode (act like an off-line UPS).
1.3.6.1.4.1.2254.2.5.20.41NodedupsReturnFromEconomicINFORMATION: The UPS no longer on economic mode.
1.3.6.1.4.1.2254.2.5.20.42NodedupsPowerModuleFailINFORMATION: One of the power modules is detected failed.
1.3.6.1.4.1.2254.2.5.20.43NodedupsReturnFromPowerModuleFailINFORMATION: The power module is back to normal.
1.3.6.1.4.1.2254.2.5.20.44NodedupsOutputBreakerOffINFORMATION: The output breaker is detected off.
1.3.6.1.4.1.2254.2.5.20.45NodedupsReturnFromOutputBreakerOffINFORMATION: The output breaker is back to on.
1.3.6.1.4.1.2254.2.5.20.46NodedupsBatteryDepletedSEVER: The UPS batteries are depleted and will soon be exhausted.
1.3.6.1.4.1.2254.2.5.20.47NodedupsReturnFromBatteryDepletedINFORMATION: The UPS has returned from a battery depleted condition.
1.3.6.1.4.1.2254.2.5.20.48NodedupsLoadOnManualBypassSEVER: The UPS loads on manual bypass.
1.3.6.1.4.1.2254.2.5.20.49NodedupsNoLongerLoadOnManualBypassINFORMATION: The UPS is not on manual bypass mode.
1.3.6.1.4.1.2254.2.5.20.50NodedupsBatteryBreakerOpenSEVER: The battery breaker is detected open.
1.3.6.1.4.1.2254.2.5.20.51NodedupsReturnFromBatteryBreakerOpenINFORMATION: The battery breaker is returned from open.
1.3.6.1.4.1.2254.2.5.20.52NodedupsOutletBankOnSEVER: The outlet bank was turned on.
1.3.6.1.4.1.2254.2.5.20.53NodedupsOutletBankOffINFORMATION: The outlet bank was turned off.
1.3.6.1.4.1.2254.2.5.20.54NodedupsRedundancyLossWARNING: The redundancy capacity lost in a modular UPS.
1.3.6.1.4.1.2254.2.5.20.55NodedupsReturnFromRedundancyLossINFORMATION: The redundancy capacity recoverd in a modular UPS.
1.3.6.1.4.1.2254.2.5.20.56NodedupsPhaseAsynchronousSEVER: The phase is detected asynchronous.
1.3.6.1.4.1.2254.2.5.20.57NodedupsReturnFromPhaseAsynchronousINFORMATION: The phase is returned from asynchronous.
1.3.6.1.4.1.2254.2.5.20.58NodedupsRectifierAbnormalSEVER: The rectifier is detected abnormal.
1.3.6.1.4.1.2254.2.5.20.59NodedupsReturnFromRectifierAbnormalINFORMATION: The rectifier is returned from abnormal.
1.3.6.1.4.1.2254.2.5.20.60NodedupsBypassBreakerOpenSEVER: The bypass breaker is detected open.
1.3.6.1.4.1.2254.2.5.20.61NodedupsReturnFromBypassBreakerOpenINFORMATION: The bypass breaker is returned from open.
1.3.6.1.4.1.2254.2.5.20.62NodedupsMainInputBreakerOpenSEVER: The main inputs breaker is detected open.
1.3.6.1.4.1.2254.2.5.20.63NodedupsReturnFromMainInputBreakerOpenINFORMATION: The main input breaker is returned from open.
1.3.6.1.4.1.2254.2.5.20.64NodedupsManualBypassBreakerOpenSEVER: The manual bypass breaker is detected open.
1.3.6.1.4.1.2254.2.5.20.65NodedupsReturnFromManualBypassBreakerOpenINFORMATION: The manual bypass breaker is returned from open.