DeltaUPSv5-MIB
323 objects
No module-level DESCRIPTION found.
Imported Objects
| RFC-1212 | OBJECT-TYPE |
| RFC-1215 | TRAP-TYPE |
| RFC1155-SMI | enterprises IpAddress TimeTicks |
| RFC1213-MIB | DisplayString |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.2254 | Nodedelta | |||
| 1.3.6.1.4.1.2254.2 | Nodeups | |||
| 1.3.6.1.4.1.2254.2.5 | Nodeupsv5 | |||
| 1.3.6.1.4.1.2254.2.5.1 | NodedupsIdent | |||
| 1.3.6.1.4.1.2254.2.5.1.1 | ScalardupsIdentManufacturer | read-only | mandatory | The name of the UPS manufacturer. |
| 1.3.6.1.4.1.2254.2.5.1.2 | ScalardupsIdentModel | read-only | mandatory | The UPS Model designation. |
| 1.3.6.1.4.1.2254.2.5.1.3 | ScalardupsIdentUPSSoftwareVersion | read-only | mandatory | The UPS firmware/software version(s). This variable may or may not has the same value as upsIdentAgentSoftwareVersion in some implementations. |
| 1.3.6.1.4.1.2254.2.5.1.4 | ScalardupsIdentAgentSoftwareVersion | read-only | mandatory | The UPS agent software version. This variable may or may not has the same value as upsIdentUPSSoftwareVersion in some implementations. |
| 1.3.6.1.4.1.2254.2.5.1.5 | ScalardupsIdentName | read-write | mandatory | A string identifying the UPS. This object should be set by the administrator. |
| 1.3.6.1.4.1.2254.2.5.1.6 | ScalardupsAttachedDevices | read-write | mandatory | A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator. |
| 1.3.6.1.4.1.2254.2.5.1.7 | ScalardupsRatingOutputVA | read-only | mandatory | The magnitude of the nominal output VA rating. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.1.8 | ScalardupsRatingOutputVoltage | read-only | mandatory | The magnitude of the nominal output voltage rating. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.1.9 | ScalardupsRatingOutputFrequency | read-only | mandatory | The magnitude of the nominal output frequency rating. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.1.10 | ScalardupsRatingInputVoltage | read-only | mandatory | The magnitude of the nominal input voltage rating. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.1.11 | ScalardupsRatingInputFrequency | read-only | mandatory | The magnitude of the nominal input frequency rating. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.1.12 | ScalardupsRatingBatteryVoltage | read-only | mandatory | The magnitude of the nominal battery voltage rating. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.1.13 | ScalardupsLowTransferVoltUpBound | read-only | mandatory | The minimum input line voltage upper bound allowed before the UPS system transfers to battery backup. The value -1 indicates this UPS does not support this ite… |
| 1.3.6.1.4.1.2254.2.5.1.14 | ScalardupsLowTransferVoltLowBound | read-only | mandatory | The minimum input line voltage lower bound allowed before the UPS system transfers to battery backup. The value -1 indicates this UPS does not support this ite… |
| 1.3.6.1.4.1.2254.2.5.1.15 | ScalardupsHighTransferVoltUpBound | read-only | mandatory | The maximum input line voltage upper bound allowed before the UPS system transfers to battery backup. The value -1 indicates this UPS does not support this ite… |
| 1.3.6.1.4.1.2254.2.5.1.16 | ScalardupsHighTransferVoltLowBound | read-only | mandatory | The maximum input line voltage lower bound allowed before the UPS system transfers to battery backup. The value -1 indicates this UPS does not support this ite… |
| 1.3.6.1.4.1.2254.2.5.1.17 | ScalardupsLowBattTime | read-only | mandatory | Minutes, time from low battery to low battery shutdown. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.1.18 | ScalardupsOutletRelays | read-only | mandatory | Number of outlet relay. If it is 0, the function is not available for the UPS. |
| 1.3.6.1.4.1.2254.2.5.1.19 | ScalardupsType | read-only | mandatory | Indicate the UPS type. |
| 1.3.6.1.4.1.2254.2.5.2 | NodedupsControl | |||
| 1.3.6.1.4.1.2254.2.5.2.1 | ScalardupsShutdownType | read-write | mandatory | This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reach… |
| 1.3.6.1.4.1.2254.2.5.2.2 | ScalardupsAutoReboot | read-write | mandatory | In backup mode, the UPS may shutdown normally by SDA command, dry-contact remote shutdown signal or low battery shutdown. This command is used to determine the… |
| 1.3.6.1.4.1.2254.2.5.2.3 | ScalardupsShutdownAction | read-write | mandatory | If the value is greater than 0 the UPS performs shutdown action that defined by ShutdownType after the seconds. 0, aborted. |
| 1.3.6.1.4.1.2254.2.5.2.4 | ScalardupsRestartAction | read-write | mandatory | UPS will restart after the indicated number of minutes. -1, aborted. |
| 1.3.6.1.4.1.2254.2.5.2.5 | ScalardupsSetOutletRelay | read-write | mandatory | Indicate which outlet relay, from 1,2,3... . |
| 1.3.6.1.4.1.2254.2.5.2.6 | ScalardupsRelayOffDelay | read-write | mandatory | Turn the relay off after the seconds. The relay was indicated by SetOutletRelay. |
| 1.3.6.1.4.1.2254.2.5.2.7 | ScalardupsRelayOnDelay | read-write | mandatory | Turn the relay on after the minutes. The relay was indicated by SetOutletRelay. |
| 1.3.6.1.4.1.2254.2.5.2.8 | ScalardupsSmartShutdown | read-write | mandatory | Any value to initiate the Smart Shutdown for the UPS. |
| 1.3.6.1.4.1.2254.2.5.2.9 | ScalardupsClearEnergy | read-write | mandatory | Any value to clear the energy record in the UPS. |
| 1.3.6.1.4.1.2254.2.5.3 | NodedupsConfig | |||
| 1.3.6.1.4.1.2254.2.5.3.1 | ScalardupsConfigBuzzerAlarm | read-write | mandatory | UPS will keep silence but will alarm again when next power event is occurred |
| 1.3.6.1.4.1.2254.2.5.3.2 | ScalardupsConfigBuzzerState | read-write | mandatory | If it is disabled then the UPS is always muted. |
| 1.3.6.1.4.1.2254.2.5.3.3 | ScalardupsConfigSensitivity | read-write | mandatory | The seneitivity of the UPS to utility line abnormalities or noises. |
| 1.3.6.1.4.1.2254.2.5.3.4 | ScalardupsConfigLowVoltageTransferPoint | read-write | mandatory | The minimum input line voltage allowed before the UPS system transfers to battery backup. |
| 1.3.6.1.4.1.2254.2.5.3.5 | ScalardupsConfigHighVoltageTransferPoint | read-write | mandatory | The maximum line voltage allowed before the UPS system transfers to battery backup. |
| 1.3.6.1.4.1.2254.2.5.3.6 | ScalardupsConfigUPSBootDelay | read-write | mandatory | Delay the UPS startup after power restores. The power quality may not stable when power restores, this feature let the UPS wait a period of time to startup the… |
| 1.3.6.1.4.1.2254.2.5.3.7 | ScalardupsConfigExternalBatteryPack | read-write | mandatory | Indicate the number of external battery pack. |
| 1.3.6.1.4.1.2254.2.5.3.8 | ScalardupsConfigSmartShutdownOSDelay | read-write | mandatory | The estimated operating system shutdown delay time for Smart Shutdown. |
| 1.3.6.1.4.1.2254.2.5.3.9 | ScalardupsConfigSmartShutdownUPSDelay | read-write | mandatory | The estimated UPS shutdown delay time for Smart Shutdown. |
| 1.3.6.1.4.1.2254.2.5.3.10 | ScalardupsConfigEconomicMode | read-write | mandatory | Used to enable or disable the economic mode. |
| 1.3.6.1.4.1.2254.2.5.4 | NodedupsInput | |||
| 1.3.6.1.4.1.2254.2.5.4.1 | ScalardupsInputNumLines | read-only | mandatory | The number of input lines utilized in this device. |
| 1.3.6.1.4.1.2254.2.5.4.2 | ScalardupsInputFrequency1 | read-only | mandatory | The current input line 1 frequency to the UPS system in 1/10 Hz. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.4.3 | ScalardupsInputVoltage1 | read-only | mandatory | The Input phase 1 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.4.4 | ScalardupsInputVoltage12 | read-only | mandatory | The Input line 1-2 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.4.5 | ScalardupsInputCurrent1 | read-only | mandatory | The Input line 1 current to the UPS system in 1/10 A. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.4.6 | ScalardupsInputPower1 | read-only | mandatory | The Input line 1 power to the UPS system in 1 Watt. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.4.7 | ScalardupsInputFrequency2 | read-only | mandatory | The current input line 2 frequency to the UPS system in 1/10 Hz. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.4.8 | ScalardupsInputVoltage2 | read-only | mandatory | The Input phase 2 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.4.9 | ScalardupsInputVoltage23 | read-only | mandatory | The Input line 2-3 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.4.10 | ScalardupsInputCurrent2 | read-only | mandatory | The Input line 2 current to the UPS system in 1/10 A. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.4.11 | ScalardupsInputPower2 | read-only | mandatory | The Input line 2 power to the UPS system in 1 Watt. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.4.12 | ScalardupsInputFrequency3 | read-only | mandatory | The current input line 3 frequency to the UPS system in 1/10 Hz. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.4.13 | ScalardupsInputVoltage3 | read-only | mandatory | The Input phase 3 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.4.14 | ScalardupsInputVoltage31 | read-only | mandatory | The Input line 3-1 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.4.15 | ScalardupsInputCurrent3 | read-only | mandatory | The Input line 3 current to the UPS system in 1/10 A. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.4.16 | ScalardupsInputPower3 | read-only | mandatory | The Input line 3 power to the UPS system in 1 Watt. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.4.17 | ScalardupsInputEnergy1 | read-only | mandatory | The Input line 1 energy to the UPS system in 1 kWh. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.4.18 | ScalardupsInputEnergy2 | read-only | mandatory | The Input line 2 energy to the UPS system in 1 kWh. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.4.19 | ScalardupsInputEnergy3 | read-only | mandatory | The Input line 3 energy to the UPS system in 1 kWh. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.4.20 | ScalardupsInputEnergyTotal | read-only | mandatory | The total Input energy to the UPS system in 1 kWh. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.4.21 | ScalardupsInputLineFailCause | read-only | mandatory | Cause of input outage. |
| 1.3.6.1.4.1.2254.2.5.4.22 | ScalardupsInputBadStatus | read-only | mandatory | Incorrect input voltage or frequency. |
| 1.3.6.1.4.1.2254.2.5.5 | NodedupsOutput | |||
| 1.3.6.1.4.1.2254.2.5.5.1 | ScalardupsOutputSource | read-only | mandatory | The present source of output power. The enumeration noOutput(8) indicates that there is no source of output power (and therefore no output power), for example,… |
| 1.3.6.1.4.1.2254.2.5.5.2 | ScalardupsOutputFrequency | read-only | mandatory | The present output frequency in 1/10 Hz. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.5.3 | ScalardupsOutputNumLines | read-only | mandatory | The number of output lines utilized in this device. |
| 1.3.6.1.4.1.2254.2.5.5.4 | ScalardupsOutputVoltage1 | read-only | mandatory | The Output phase 1 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.5.5 | ScalardupsOutputVoltage12 | read-only | mandatory | The Output line 1-2 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.5.6 | ScalardupsOutputCurrent1 | read-only | mandatory | The Output line 1 current of the UPS system in 1/10 A. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.5.7 | ScalardupsOutputPower1 | read-only | mandatory | The Output line 1 active power of the UPS system in watts. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.5.8 | ScalardupsOutputLoad1 | read-only | mandatory | The current UPS output line 1 load expressed in percent of rated capacity. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.5.9 | ScalardupsOutputVoltage2 | read-only | mandatory | The Output phase 2 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.5.10 | ScalardupsOutputVoltage23 | read-only | mandatory | The Output line 2-3 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.5.11 | ScalardupsOutputCurrent2 | read-only | mandatory | The Output line 2 current of the UPS system in 1/10 A. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.5.12 | ScalardupsOutputPower2 | read-only | mandatory | The Output line 2 active power of the UPS system in watts. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.5.13 | ScalardupsOutputLoad2 | read-only | mandatory | The current UPS output line 2 load expressed in percent of rated capacity. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.5.14 | ScalardupsOutputVoltage3 | read-only | mandatory | The Output phase 3 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.5.15 | ScalardupsOutputVoltage31 | read-only | mandatory | The Output line 3-1 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.5.16 | ScalardupsOutputCurrent3 | read-only | mandatory | The Output line 3 current of the UPS system in 1/10 A. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.5.17 | ScalardupsOutputPower3 | read-only | mandatory | The Output line 3 active power of the UPS system in watts. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.5.18 | ScalardupsOutputLoad3 | read-only | mandatory | The current UPS output line 3 load expressed in percent of rated capacity. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.5.19 | ScalardupsOutputTotalActivePower | read-only | mandatory | The total output active power of the UPS system in 0.1 kW. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.5.20 | ScalardupsOutputTotalApparentPower | read-only | mandatory | The total output apparent power of the UPS system in 0.1 kVA. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.5.21 | ScalardupsOutputTotalPowerFactor | read-only | mandatory | The total output power factor of the UPS system. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.5.22 | ScalardupsOutputEnergy1 | read-only | mandatory | The UPS output line 1 energy in kWh. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.5.23 | ScalardupsOutputEnergy2 | read-only | mandatory | The UPS output line 2 energy in kWh. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.5.24 | ScalardupsOutputEnergy3 | read-only | mandatory | The UPS output line 3 energy in kWh. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.5.25 | ScalardupsOutputEnergyTotal | read-only | mandatory | The UPS total output energy in kWh. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.6 | NodedupsBypass | |||
| 1.3.6.1.4.1.2254.2.5.6.1 | ScalardupsBypassFrequency | read-only | mandatory | The present bypass frequency in 1/10 Hz. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.6.2 | ScalardupsBypassNumLines | read-only | mandatory | The number of bypass lines utilized in this device. |
| 1.3.6.1.4.1.2254.2.5.6.3 | ScalardupsBypassVoltage1 | read-only | mandatory | The bypass phase 1 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.6.4 | ScalardupsBypassVoltage12 | read-only | mandatory | The bypass line 1-2 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.6.5 | ScalardupsBypassCurrent1 | read-only | mandatory | The bypass line 1 current of the UPS system in 1/10 A. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.6.6 | ScalardupsBypassPower1 | read-only | mandatory | The bypass line 1 real power of the UPS system in watts. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.6.7 | ScalardupsBypassVoltage2 | read-only | mandatory | The bypass phase 2 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.6.8 | ScalardupsBypassVoltage23 | read-only | mandatory | The bypass line 2-3 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.6.9 | ScalardupsBypassCurrent2 | read-only | mandatory | The bypass line 2 current of the UPS system in 1/10 A. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.6.10 | ScalardupsBypassPower2 | read-only | mandatory | The bypass line 2 real power of the UPS system in watts. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.6.11 | ScalardupsBypassVoltage3 | read-only | mandatory | The bypass phase 3 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.6.12 | ScalardupsBypassVoltage31 | read-only | mandatory | The bypass line 3-1 voltage of the UPS system in 1/10 V. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.6.13 | ScalardupsBypassCurrent3 | read-only | mandatory | The bypass line 3 current of the UPS system in 1/10 A. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.6.14 | ScalardupsBypassPower3 | read-only | mandatory | The bypass line 3 real power of the UPS system in watts. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.6.15 | ScalardupsBypassSTSTemperature | read-only | mandatory | The measurement of bypass STS temperature. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.7 | NodedupsBattery | |||
| 1.3.6.1.4.1.2254.2.5.7.1 | ScalardupsBatteryCondition | read-only | mandatory | The indication of the capacity remaining in the UPS system's batteries when AC normal. |
| 1.3.6.1.4.1.2254.2.5.7.2 | ScalardupsBatteryStatus | read-only | mandatory | The indication of the capacity remaining in the UPS system's batteries when AC failed. A value of ok indicates that the remaining run-time is greater than upsC… |
| 1.3.6.1.4.1.2254.2.5.7.3 | ScalardupsBatteryCharge | read-only | mandatory | Representing the battery charge status. |
| 1.3.6.1.4.1.2254.2.5.7.4 | ScalardupsSecondsOnBattery | read-only | mandatory | If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res… |
| 1.3.6.1.4.1.2254.2.5.7.5 | ScalardupsBatteryEstimatedTime | read-only | mandatory | Estimated time from backup to low battery shutdown. |
| 1.3.6.1.4.1.2254.2.5.7.6 | ScalardupsBatteryPosVoltage | read-only | mandatory | The magnitude of the present positive battery voltage in 1/10 V. |
| 1.3.6.1.4.1.2254.2.5.7.7 | ScalardupsBatteryNegVoltage | read-only | mandatory | The magnitude of the present negative battery voltage in -1/10 V. |
| 1.3.6.1.4.1.2254.2.5.7.8 | ScalardupsBatteryPosCurrent | read-only | mandatory | The present positive battery current in 1/10 A. |
| 1.3.6.1.4.1.2254.2.5.7.9 | ScalardupsBatteryNegCurrent | read-only | mandatory | The present negative battery current in 1/10 A. |
| 1.3.6.1.4.1.2254.2.5.7.10 | ScalardupsBatteryPosCapacity | read-only | mandatory | An estimate of the positive battery charge remaining expressed as a percent of full charge. |
| 1.3.6.1.4.1.2254.2.5.7.11 | ScalardupsBatteryNegCapacity | read-only | mandatory | An estimate of the negative battery charge remaining expressed as a percent of full charge. |
| 1.3.6.1.4.1.2254.2.5.7.12 | ScalardupsTemperature | read-only | mandatory | The measurement of internal temperature in the UPS. |
| 1.3.6.1.4.1.2254.2.5.7.13 | ScalardupsLastReplaceDate | read-only | mandatory | The last battery replacement date. The format is YYYYMMDD. |
| 1.3.6.1.4.1.2254.2.5.7.14 | ScalardupsNextReplaceDate | read-only | mandatory | The next battery replacement date. The format is YYYYMMDD. |
| 1.3.6.1.4.1.2254.2.5.7.15 | ScalardupsBatteryBreaker | read-only | mandatory | Indicate the battery breaker status. |
| 1.3.6.1.4.1.2254.2.5.7.16 | ScalardupsBatteryCab1Tempurature | read-only | mandatory | Temperature of battery cabnet 1. |
| 1.3.6.1.4.1.2254.2.5.7.17 | ScalardupsBatteryCab2Tempurature | read-only | mandatory | Temperature of battery cabnet 2. |
| 1.3.6.1.4.1.2254.2.5.7.18 | ScalardupsBatteryCab3Tempurature | read-only | mandatory | Temperature of battery cabnet 3. |
| 1.3.6.1.4.1.2254.2.5.7.19 | ScalardupsBatteryCab4Tempurature | read-only | mandatory | Temperature of battery cabnet 4. |
| 1.3.6.1.4.1.2254.2.5.8 | NodedupsTest | |||
| 1.3.6.1.4.1.2254.2.5.8.1 | ScalardupsTestType | read-write | mandatory | Perform the UPS Test procedure. |
| 1.3.6.1.4.1.2254.2.5.8.2 | ScalardupsTestResultsSummary | read-only | mandatory | The results of the current or last UPS diagnostics test performed. The values for donePass(1), generalTestFail(3), and batteryTestFail(4) indicate that the tes… |
| 1.3.6.1.4.1.2254.2.5.8.3 | ScalardupsTestResultsDetail | read-only | mandatory | Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned. |
| 1.3.6.1.4.1.2254.2.5.8.4 | ScalardupsGeneratorTest | read-write | mandatory | Perform the Generator Test procedure. |
| 1.3.6.1.4.1.2254.2.5.8.5 | ScalardupsGeneratorTestStatus | read-only | mandatory | The results of the current or last generator diagnostics test performed.The values for None(2), InhibitTest(3), AbnormallyTerminate(4), ByInstruction(5), and B… |
| 1.3.6.1.4.1.2254.2.5.9 | NodedupsAlarm | |||
| 1.3.6.1.4.1.2254.2.5.9.1 | ScalardupsAlarmDisconnect | read-only | mandatory | Indicate the communication of the UPS is connected or disconnect? |
| 1.3.6.1.4.1.2254.2.5.9.2 | ScalardupsAlarmInputOutOfRange | read-only | mandatory | Representing the input power is out of tolerance. This item is used to indicate the input power fail, a test condition should not set this item on. |
| 1.3.6.1.4.1.2254.2.5.9.3 | ScalardupsAlarmBatteryLow | read-only | mandatory | Are the UPS batteries low? |
| 1.3.6.1.4.1.2254.2.5.9.4 | ScalardupsAlarmLoadOnBypass | read-only | mandatory | Does the UPS load on bypass? |
| 1.3.6.1.4.1.2254.2.5.9.5 | ScalardupsAlarmOther | read-only | mandatory | Indicate there is an alarm detected but which is not defined here. |
| 1.3.6.1.4.1.2254.2.5.9.6 | ScalardupsAlarmBatteryGroundFault | read-only | mandatory | To indicate the battery ground fault has been detected. |
| 1.3.6.1.4.1.2254.2.5.9.7 | ScalardupsAlarmTestInProgress | read-only | mandatory | Does the UPS test in progress? |
| 1.3.6.1.4.1.2254.2.5.9.8 | ScalardupsAlarmBatteryTestFail | read-only | mandatory | Does the UPS test fail? |
| 1.3.6.1.4.1.2254.2.5.9.9 | ScalardupsAlarmFuseFailure | read-only | mandatory | The failure of one or more fuses has been detected. |
| 1.3.6.1.4.1.2254.2.5.9.10 | ScalardupsAlarmOutputOverload | read-only | mandatory | The output load exceeds the UPS output capacity. |
| 1.3.6.1.4.1.2254.2.5.9.11 | ScalardupsAlarmInverterAbnormal | read-only | mandatory | Representing the inverter fail alarm. |
| 1.3.6.1.4.1.2254.2.5.9.12 | ScalardupsAlarmLoadOnReserve | read-only | mandatory | Does the UPS load on reserve? |
| 1.3.6.1.4.1.2254.2.5.9.13 | ScalardupsAlarmTemperature | read-only | mandatory | Representing one of the temperature sensors has been determined its value is out of the limits. |
| 1.3.6.1.4.1.2254.2.5.9.14 | ScalardupsAlarmBypassOutOfRange | read-only | mandatory | The bypass power is out of range. |
| 1.3.6.1.4.1.2254.2.5.9.15 | ScalardupsAlarmStandby | read-only | mandatory | The UPS system is in the standby state. |
| 1.3.6.1.4.1.2254.2.5.9.16 | ScalardupsAlarmChargerFail | read-only | mandatory | An incorrected problem has been detected within the UPS charger subsystem |
| 1.3.6.1.4.1.2254.2.5.9.17 | ScalardupsAlarmFanFail | read-only | mandatory | The failure of one or more fans in the UPS has been detected. |
| 1.3.6.1.4.1.2254.2.5.9.18 | ScalardupsAlarmEconomicMode | read-only | mandatory | The UPS is working in the economic mode (act like an off-line UPS). |
| 1.3.6.1.4.1.2254.2.5.9.19 | ScalardupsAlarmOutputOff | read-only | mandatory | UPS output is turned off. |
| 1.3.6.1.4.1.2254.2.5.9.20 | ScalardupsAlarmSmartShutdown | read-only | mandatory | Indicates whether the Smart Shutdown is in progress. |
| 1.3.6.1.4.1.2254.2.5.9.21 | ScalardupsAlarmEmergencyPowerOff | read-only | mandatory | Representing the UPS is shutdown due to the Emergency Power Off button is pressed. |
| 1.3.6.1.4.1.2254.2.5.9.22 | ScalardupsAlarmUPSShutdown | read-only | mandatory | The UPS has been shutdown including remote and fault shutdown. |
| 1.3.6.1.4.1.2254.2.5.9.23 | ScalardupsAlarmEPO | read-only | mandatory | Representing the UPS is shutdown due to the Emergency Power Off button is pressed. |
| 1.3.6.1.4.1.2254.2.5.9.24 | ScalardupsAlarmOutVoltOverLimit | read-only | mandatory | To indicate the output voltage is over limit. |
| 1.3.6.1.4.1.2254.2.5.9.25 | ScalardupsAlarmOutVoltUnderLimit | read-only | mandatory | To indicate the output voltage is under limit. |
| 1.3.6.1.4.1.2254.2.5.9.26 | ScalardupsAlarmPowerModule | read-only | mandatory | To indicate there is at least one alarm from power module. |
| 1.3.6.1.4.1.2254.2.5.9.27 | ScalardupsAlarmOutputBreaker | read-only | mandatory | To indicate the output breaker is detected open or close. |
| 1.3.6.1.4.1.2254.2.5.9.28 | ScalardupsAlarmOutletBank1Breaker | read-only | mandatory | To indicate the outlet bank-1 breaker is detected open or close. |
| 1.3.6.1.4.1.2254.2.5.9.29 | ScalardupsAlarmOutletBank2Breaker | read-only | mandatory | To indicate the outlet bank-2 breaker is detected open or close. |
| 1.3.6.1.4.1.2254.2.5.9.30 | ScalardupsAlarmOutletBank3Breaker | read-only | mandatory | To indicate the outlet bank-3 breaker is detected open or close. |
| 1.3.6.1.4.1.2254.2.5.9.31 | ScalardupsAlarmOutletBank4Breaker | read-only | mandatory | To indicate the outlet bank-4 breaker is detected open or close. |
| 1.3.6.1.4.1.2254.2.5.9.32 | ScalardupsAlarmSummary | read-only | mandatory | To indicate the alarm level for the UPS. |
| 1.3.6.1.4.1.2254.2.5.9.33 | ScalardupsAlarmRedundancyLoss | read-only | mandatory | To indicate the capacity of redundancy lost in a modular UPS. |
| 1.3.6.1.4.1.2254.2.5.9.34 | ScalardupsAlarmPhaseAsynchronous | read-only | mandatory | To indicate the Phase is detected asynchronous or synchronous. |
| 1.3.6.1.4.1.2254.2.5.9.35 | ScalardupsAlarmRectifierAbnormal | read-only | mandatory | To indicate the Rectifier is detected alarm or normal. |
| 1.3.6.1.4.1.2254.2.5.9.36 | ScalardupsAlarmBypassBreakerOpen | read-only | mandatory | To indicate the bypass breaker is detected open or close. |
| 1.3.6.1.4.1.2254.2.5.9.37 | ScalardupsAlarmMainInputBreakerOpen | read-only | mandatory | To indicate the main input breaker is detected open or close. |
| 1.3.6.1.4.1.2254.2.5.9.38 | ScalardupsAlarmManualBypassBreaker | read-only | mandatory | To indicate the manual bypass breaker is detected open or close. |
| 1.3.6.1.4.1.2254.2.5.10 | NodedupsPowerModule | |||
| 1.3.6.1.4.1.2254.2.5.10.1 | ScalardupsPMBypassInputAlarm | read-only | mandatory | Indicates the bypass voltage/frequency is abnormal. |
| 1.3.6.1.4.1.2254.2.5.10.2 | ScalardupsPMBypassPhaseAlarm | read-only | mandatory | Indicates the bypass phase sequence is abnormal. |
| 1.3.6.1.4.1.2254.2.5.10.3 | ScalardupsPMBypassSTSOverloadAlarm | read-only | mandatory | Indicates the bypass STS overload. |
| 1.3.6.1.4.1.2254.2.5.10.4 | ScalardupsPMBypassSTSOverTempAlarm | read-only | mandatory | Indicates the bypass STS over temperature. |
| 1.3.6.1.4.1.2254.2.5.10.5 | ScalardupsPMBypassSTSFailAlarm | read-only | mandatory | Indicates the bypass STS fail. |
| 1.3.6.1.4.1.2254.2.5.10.6 | TabledupsPMTable | not-accessible | mandatory | A list of power module table entries. |
| 1.3.6.1.4.1.2254.2.5.10.6.1 | RowdupsPMEntry | not-accessible | mandatory | An entry containing information applicable to a particular power module. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.1 | ColumndupsPMID | not-accessible | mandatory | The power module identifier. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.2 | ColumndupsPMPFCTemp | read-only | mandatory | The power module PFC temperature. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.3 | ColumndupsPMINVTemp | read-only | mandatory | The power module inverter temperature. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.4 | ColumndupsPMINVTempR | read-only | mandatory | The power module inverter-R temperature. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.5 | ColumndupsPMINVTempS | read-only | mandatory | The power module inverter-S temperature. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.6 | ColumndupsPMINVTempT | read-only | mandatory | The power module inverter-T temperature. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.7 | ColumndupsPMINVVolt1 | read-only | mandatory | The inverter line 1 voltage of the power module in 1/10 V. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.8 | ColumndupsPMINVVolt2 | read-only | mandatory | The inverter line 2 voltage of the power module in 1/10 V. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.9 | ColumndupsPMINVVolt3 | read-only | mandatory | The inverter line 3 voltage of the power module in 1/10 V. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.10 | ColumndupsPMStsNotExist | read-only | mandatory | Indicates the power module is existed or not? |
| 1.3.6.1.4.1.2254.2.5.10.6.1.11 | ColumndupsPMStsOff | read-only | mandatory | Indicates the power module is on or off? |
| 1.3.6.1.4.1.2254.2.5.10.6.1.12 | ColumndupsPMStsRepair | read-only | mandatory | Indicates the power module is in repair mode or not? |
| 1.3.6.1.4.1.2254.2.5.10.6.1.13 | ColumndupsPMStsFaultShutdown | read-only | mandatory | Indicates the power module status of fault shutdown. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.14 | ColumndupsPMStsPFCFuseFail | read-only | mandatory | Indicates the power module PFC fuse open or close? |
| 1.3.6.1.4.1.2254.2.5.10.6.1.15 | ColumndupsPMStsPFCOverTempWarning | read-only | mandatory | Indicates the power module PFC over temperature warning. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.16 | ColumndupsPMStsPFCOverTempShutdown | read-only | mandatory | Indicates the power module PFC over temperature shutdown. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.17 | ColumndupsPMStsPFCOverVoltWarning | read-only | mandatory | Indicates the power module PFC over voltage warning. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.18 | ColumndupsPMStsPFCOverVoltShutdown | read-only | mandatory | Indicates the power module PFC over voltage shutdown. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.19 | ColumndupsPMStsPFCUnderVoltWarning | read-only | mandatory | Indicates the power module PFC under voltage warning. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.20 | ColumndupsPMStsPFCUnderVoltShutdown | read-only | mandatory | Indicates the power module PFC under voltage shutdown. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.21 | ColumndupsPMStsPFCGeneralFault | read-only | mandatory | Indicates the power module PFC genreal fault. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.22 | ColumndupsPMStsPFCFanFail | read-only | mandatory | Indicates the power module PFC fan fail. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.23 | ColumndupsPMStsPFCCurrentLimit | read-only | mandatory | Indicates the power module PFC output current limit. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.24 | ColumndupsPMStsPFCOff | read-only | mandatory | Indicates the power module PFC off. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.25 | ColumndupsPMStsPFCInnerCommFail | read-only | mandatory | Indicates the power module PFC inner communication fail. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.26 | ColumndupsPMStsPFCNotCalibrated | read-only | mandatory | Indicates the power module PFC is not calibrated. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.27 | ColumndupsPMStsINVFuseFail | read-only | mandatory | Indicates the power module Inverter fuse open or close? |
| 1.3.6.1.4.1.2254.2.5.10.6.1.28 | ColumndupsPMStsINVOverTempWarning | read-only | mandatory | Indicates the power module Inverter over temperature warning. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.29 | ColumndupsPMStsINVOverTempShutdown | read-only | mandatory | Indicates the power module Inverter over temperature shutdown. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.30 | ColumndupsPMStsINVFanFail | read-only | mandatory | Indicates the power module Inverter fan fail. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.31 | ColumndupsPMStsINVShortCircuit | read-only | mandatory | Indicates the power module Inverter short circuit. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.32 | ColumndupsPMStsINVSTSFail | read-only | mandatory | Indicates the power module Inverter STS fail. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.33 | ColumndupsPMStsINVCircuitFail | read-only | mandatory | Indicates the power module Inverter circuit fail shutdown. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.34 | ColumndupsPMStsINVOverVolt | read-only | mandatory | Indicates the power module Inverter over voltage shutdown. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.35 | ColumndupsPMStsINVOverload | read-only | mandatory | Indicates the power module Inverter overload. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.36 | ColumndupsPMStsINVInnerCommFail | read-only | mandatory | Indicates the power module Inverter inner communication fail. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.37 | ColumndupsPMStsINVEPO | read-only | mandatory | Indicates the power module Inverter EPO shutdown. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.38 | ColumndupsPMStsINVParallelCommFail | read-only | mandatory | Indicates the power module Inverter parallel communication fail. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.39 | ColumndupsPMStsINVParallelFail | read-only | mandatory | Indicates the power module Inverter parallel fail. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.40 | ColumndupsPMStsINVSTSOn | read-only | mandatory | Indicates the status of power module Inverter state. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.41 | ColumndupsPMStsINVNotCalibrated | read-only | mandatory | Indicates the power module Inverter is not calibrated. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.42 | ColumndupsPMStsChargerFail | read-only | mandatory | Indicates the power module Charger fail. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.43 | ColumndupsPMSummaryStatus | read-only | mandatory | The power module summary status. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.44 | ColumndupsPMPFCTempR | read-only | mandatory | The power module pfc-R temperature. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.45 | ColumndupsPMPFCTempS | read-only | mandatory | The power module pfc-S temperature. |
| 1.3.6.1.4.1.2254.2.5.10.6.1.46 | ColumndupsPMPFCTempT | read-only | mandatory | The power module pfc-T temperature. |
| 1.3.6.1.4.1.2254.2.5.11 | NodedupsTrapArgs | |||
| 1.3.6.1.4.1.2254.2.5.11.1 | ScalardupsDescription | read-only | mandatory | This OID is used for traps to send with a string argument. A get of this OID will return an empty string. |
| 1.3.6.1.4.1.2254.2.5.11.2 | ScalardupsTimeTicks | read-only | mandatory | This OID is used for traps to send with a TimeTicks argument. A get of this OID will return 0. |
| 1.3.6.1.4.1.2254.2.5.12 | NodedupsParallel | |||
| 1.3.6.1.4.1.2254.2.5.12.1 | ScalardupsParallelRatingVA | read-only | mandatory | The summary rating VA to the parallel UPSs system. |
| 1.3.6.1.4.1.2254.2.5.12.2 | ScalardupsParallelRatingPower | read-only | mandatory | The summary rating power to the parallel UPSs system. |
| 1.3.6.1.4.1.2254.2.5.12.3 | ScalardupsParallelInCurrent1 | read-only | mandatory | The summary input line 1 current to the parallel UPSs system in 1/10 A. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.12.4 | ScalardupsParallelInCurrent2 | read-only | mandatory | The summary input line 2 current to the parallel UPSs system in 1/!0 A. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.12.5 | ScalardupsParallelInCurrent3 | read-only | mandatory | The summary input line 3 current to the parallel UPSs system in 1/!0 A. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.12.6 | ScalardupsParallelOutCurrent1 | read-only | mandatory | The summary output line 1 current to the parallel UPSs system in 1/10 A. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.12.7 | ScalardupsParallelOutCurrent2 | read-only | mandatory | The summary output line 2 current to the parallel UPSs system in 1/10 A. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.12.8 | ScalardupsParallelOutCurrent3 | read-only | mandatory | The summary output line 3 current to the parallel UPSs system in 1/10 A. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.12.9 | ScalardupsParallelOutPower1 | read-only | mandatory | The summary output line 1 power to the parallel UPSs system. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.12.10 | ScalardupsParallelOutPower2 | read-only | mandatory | The summary output line 2 power to the parallel UPSs system. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.12.11 | ScalardupsParallelOutPower3 | read-only | mandatory | The summary output line 3 power to the parallel UPSs system. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.12.12 | ScalardupsParallelInEnergy1 | read-only | mandatory | The summary input line 1 energy to the parallel UPSs system. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.12.13 | ScalardupsParallelInEnergy2 | read-only | mandatory | The summary input line 2 energy to the parallel UPSs system. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.12.14 | ScalardupsParallelInEnergy3 | read-only | mandatory | The summary input line 3 energy to the parallel UPSs system. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.12.15 | ScalardupsParallelInEnergyTotal | read-only | mandatory | The summary total input energy to the parallel UPSs system. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.12.16 | ScalardupsParallelOutEnergy1 | read-only | mandatory | The summary output line 1 energy to the parallel UPSs system. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.12.17 | ScalardupsParallelOutEnergy2 | read-only | mandatory | The summary output line 2 energy to the parallel UPSs system. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.12.18 | ScalardupsParallelOutEnergy3 | read-only | mandatory | The summary output line 3 energy to the parallel UPSs system. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.12.19 | ScalardupsParallelOutEnergyTotal | read-only | mandatory | The summary total output energy to the parallel UPSs system. The value -1 indicates this UPS does not support this item. |
| 1.3.6.1.4.1.2254.2.5.13 | NodedupsIntegrated | |||
| 1.3.6.1.4.1.2254.2.5.13.1 | ScalardupsIntegratedParallel | read-only | mandatory | Multiple frame with the same group present. |
| 1.3.6.1.4.1.2254.2.5.13.2 | ScalardupsIntegratedDryInput1 | read-only | mandatory | Dry1 Input state. |
| 1.3.6.1.4.1.2254.2.5.13.3 | ScalardupsIntegratedDryInput2 | read-only | mandatory | Dry2 Input state. |
| 1.3.6.1.4.1.2254.2.5.13.4 | ScalardupsIntegratedDryInput3 | read-only | mandatory | Dry3 Input state. |
| 1.3.6.1.4.1.2254.2.5.13.5 | ScalardupsIntegratedDryInput4 | read-only | mandatory | Dry4 Input state. |
| 1.3.6.1.4.1.2254.2.5.20 | NodedupsTraps | |||
| 1.3.6.1.4.1.2254.2.5.20.1 | NodedupsCommunicationLost | SEVER: Communication with the UPS failed. | ||
| 1.3.6.1.4.1.2254.2.5.20.2 | NodedupsCommunicationEstablished | INFORMATION: Communication with the UPS reestablished. | ||
| 1.3.6.1.4.1.2254.2.5.20.3 | NodedupsPowerFail | WARNING: Power failed! The UPS is operating on battery power. | ||
| 1.3.6.1.4.1.2254.2.5.20.4 | NodedupsPowerRestored | INFORMATION: Power restored! The utility power restored. | ||
| 1.3.6.1.4.1.2254.2.5.20.5 | NodedupsLowBattery | SEVER: The UPS batteries are low and will soon be exhausted. | ||
| 1.3.6.1.4.1.2254.2.5.20.6 | NodedupsReturnFromLowBattery | INFORMATION: The UPS has returned from a low battery condition. | ||
| 1.3.6.1.4.1.2254.2.5.20.7 | NodedupsLoadOnBypass | SEVER: The UPS loads on bypass. | ||
| 1.3.6.1.4.1.2254.2.5.20.8 | NodedupsNoLongerLoadOnBypass | INFORMATION: The UPS is not on bypass mode. | ||
| 1.3.6.1.4.1.2254.2.5.20.9 | NodedupsUPSFault | SEVER: A general fault caused in the UPS. | ||
| 1.3.6.1.4.1.2254.2.5.20.10 | NodedupsReturnFromUPSFault | INFORMATION: The UPS is returned from general fault. | ||
| 1.3.6.1.4.1.2254.2.5.20.11 | NodedupsBatteryGroundFault | SEVER: The UPS battery ground fault. | ||
| 1.3.6.1.4.1.2254.2.5.20.12 | NodedupsNoLongerBatteryFault | INFORMATION: The UPS recovered from battery ground fault. | ||
| 1.3.6.1.4.1.2254.2.5.20.13 | NodedupsTestInProgress | INFORMATION: The UPS test in progress. | ||
| 1.3.6.1.4.1.2254.2.5.20.14 | NodedupsBatteryTestFail | SEVER: The UPS test fail. | ||
| 1.3.6.1.4.1.2254.2.5.20.15 | NodedupsFuseFailure | SEVER: The UPS fuse failed. | ||
| 1.3.6.1.4.1.2254.2.5.20.16 | NodedupsFuseRecovered | INFORMATION: The UPS fuse recovered. | ||
| 1.3.6.1.4.1.2254.2.5.20.17 | NodedupsOutputOverload | SEVER: The UPS overload!. | ||
| 1.3.6.1.4.1.2254.2.5.20.18 | NodedupsNoLongerOverload | INFORMATION: Recovered from UPS overload. | ||
| 1.3.6.1.4.1.2254.2.5.20.19 | NodedupsInverterAbnormal | SEVER: The UPS inverter abnormal. | ||
| 1.3.6.1.4.1.2254.2.5.20.20 | NodedupsInverterRecovered | INFORMATION: Recovered from UPS inverter abnormal. | ||
| 1.3.6.1.4.1.2254.2.5.20.21 | NodedupsSmartShutdownInit | SEVER: Smart Shutdown is initiated. | ||
| 1.3.6.1.4.1.2254.2.5.20.22 | NodedupsCancelShutdown | INFORMATION: Cancel UPS Shutdown. | ||
| 1.3.6.1.4.1.2254.2.5.20.23 | NodedupsTestCompleted | INFORMATION: This trap is sent upon completion of a UPS diagnostic test. | ||
| 1.3.6.1.4.1.2254.2.5.20.24 | NodedupsEPOON | INFORMATION: This trap is sent when emergency power off is on. | ||
| 1.3.6.1.4.1.2254.2.5.20.25 | NodedupsEPOOFF | INFORMATION: This trap is sent when UPS recover from emergency power off. | ||
| 1.3.6.1.4.1.2254.2.5.20.26 | NodedupsTemperatureAlarm | SEVER: This trap is sent when the UPS temperature out of range. | ||
| 1.3.6.1.4.1.2254.2.5.20.27 | NodedupsTemperatureNormal | INFORMATION: This trap is sent when UPS temperature back to normal. | ||
| 1.3.6.1.4.1.2254.2.5.20.28 | NodedupsBattReplace | WARNING: The battery needs to be replaced. | ||
| 1.3.6.1.4.1.2254.2.5.20.29 | NodedupsReturnFromBattReplace | INFORMATION: The UPS recovered from battery replacement. | ||
| 1.3.6.1.4.1.2254.2.5.20.30 | NodedupsOutputOff | SEVER: Indicate the UPS output is turned off. | ||
| 1.3.6.1.4.1.2254.2.5.20.31 | NodedupsReturnFromOutputOff | INFORMATION: The UPS recovered from output off. | ||
| 1.3.6.1.4.1.2254.2.5.20.32 | NodedupsShutdown | SEVER: The UPS has been shutdown including remote and fault shutdown. | ||
| 1.3.6.1.4.1.2254.2.5.20.33 | NodedupsReturnFromShutdown | INFORMATION: The UPS recovered from shutdown. | ||
| 1.3.6.1.4.1.2254.2.5.20.34 | NodedupsChargerFail | SEVER: An incorrected problem has been detected within the UPS charger subsystem. | ||
| 1.3.6.1.4.1.2254.2.5.20.35 | NodedupsReturnFromChargerFail | INFORMATION: The UPS recovered from charger fail. | ||
| 1.3.6.1.4.1.2254.2.5.20.36 | NodedupsOnStandby | SEVER: The UPS system is in the standby state. | ||
| 1.3.6.1.4.1.2254.2.5.20.37 | NodedupsReturnFromStandby | INFORMATION: The UPS no longer on standby mode. | ||
| 1.3.6.1.4.1.2254.2.5.20.38 | NodedupsFanFail | SEVER: The failure of one or more fans in the UPS has been detected. | ||
| 1.3.6.1.4.1.2254.2.5.20.39 | NodedupsReturnFromFanFail | INFORMATION: The UPS recover from fan fail. | ||
| 1.3.6.1.4.1.2254.2.5.20.40 | NodedupsOnEconomic | INFORMATION: The UPS is working in the economic mode (act like an off-line UPS). | ||
| 1.3.6.1.4.1.2254.2.5.20.41 | NodedupsReturnFromEconomic | INFORMATION: The UPS no longer on economic mode. | ||
| 1.3.6.1.4.1.2254.2.5.20.42 | NodedupsPowerModuleFail | INFORMATION: One of the power modules is detected failed. | ||
| 1.3.6.1.4.1.2254.2.5.20.43 | NodedupsReturnFromPowerModuleFail | INFORMATION: The power module is back to normal. | ||
| 1.3.6.1.4.1.2254.2.5.20.44 | NodedupsOutputBreakerOff | INFORMATION: The output breaker is detected off. | ||
| 1.3.6.1.4.1.2254.2.5.20.45 | NodedupsReturnFromOutputBreakerOff | INFORMATION: The output breaker is back to on. | ||
| 1.3.6.1.4.1.2254.2.5.20.46 | NodedupsBatteryDepleted | SEVER: The UPS batteries are depleted and will soon be exhausted. | ||
| 1.3.6.1.4.1.2254.2.5.20.47 | NodedupsReturnFromBatteryDepleted | INFORMATION: The UPS has returned from a battery depleted condition. | ||
| 1.3.6.1.4.1.2254.2.5.20.48 | NodedupsLoadOnManualBypass | SEVER: The UPS loads on manual bypass. | ||
| 1.3.6.1.4.1.2254.2.5.20.49 | NodedupsNoLongerLoadOnManualBypass | INFORMATION: The UPS is not on manual bypass mode. | ||
| 1.3.6.1.4.1.2254.2.5.20.50 | NodedupsBatteryBreakerOpen | SEVER: The battery breaker is detected open. | ||
| 1.3.6.1.4.1.2254.2.5.20.51 | NodedupsReturnFromBatteryBreakerOpen | INFORMATION: The battery breaker is returned from open. | ||
| 1.3.6.1.4.1.2254.2.5.20.52 | NodedupsOutletBankOn | SEVER: The outlet bank was turned on. | ||
| 1.3.6.1.4.1.2254.2.5.20.53 | NodedupsOutletBankOff | INFORMATION: The outlet bank was turned off. | ||
| 1.3.6.1.4.1.2254.2.5.20.54 | NodedupsRedundancyLoss | WARNING: The redundancy capacity lost in a modular UPS. | ||
| 1.3.6.1.4.1.2254.2.5.20.55 | NodedupsReturnFromRedundancyLoss | INFORMATION: The redundancy capacity recoverd in a modular UPS. | ||
| 1.3.6.1.4.1.2254.2.5.20.56 | NodedupsPhaseAsynchronous | SEVER: The phase is detected asynchronous. | ||
| 1.3.6.1.4.1.2254.2.5.20.57 | NodedupsReturnFromPhaseAsynchronous | INFORMATION: The phase is returned from asynchronous. | ||
| 1.3.6.1.4.1.2254.2.5.20.58 | NodedupsRectifierAbnormal | SEVER: The rectifier is detected abnormal. | ||
| 1.3.6.1.4.1.2254.2.5.20.59 | NodedupsReturnFromRectifierAbnormal | INFORMATION: The rectifier is returned from abnormal. | ||
| 1.3.6.1.4.1.2254.2.5.20.60 | NodedupsBypassBreakerOpen | SEVER: The bypass breaker is detected open. | ||
| 1.3.6.1.4.1.2254.2.5.20.61 | NodedupsReturnFromBypassBreakerOpen | INFORMATION: The bypass breaker is returned from open. | ||
| 1.3.6.1.4.1.2254.2.5.20.62 | NodedupsMainInputBreakerOpen | SEVER: The main inputs breaker is detected open. | ||
| 1.3.6.1.4.1.2254.2.5.20.63 | NodedupsReturnFromMainInputBreakerOpen | INFORMATION: The main input breaker is returned from open. | ||
| 1.3.6.1.4.1.2254.2.5.20.64 | NodedupsManualBypassBreakerOpen | SEVER: The manual bypass breaker is detected open. | ||
| 1.3.6.1.4.1.2254.2.5.20.65 | NodedupsReturnFromManualBypassBreakerOpen | INFORMATION: The manual bypass breaker is returned from open. |