DigiPower-PDU-MIB
371 objects
No module-level DESCRIPTION found.
Imported Objects
| RFC-1212 | OBJECT-TYPE |
| RFC-1215 | TRAP-TYPE |
| RFC1155-SMI | enterprises |
| RFC1213-MIB | DisplayString |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.17420 | Nodedigipower | |||
| 1.3.6.1.4.1.17420.1 | Nodeproducts | |||
| 1.3.6.1.4.1.17420.1.2 | NodedevTable | |||
| 1.3.6.1.4.1.17420.1.2.1 | ScalardevID | read-only | mandatory | The ID number of dev. |
| 1.3.6.1.4.1.17420.1.2.2 | ScalardevIP | read-write | mandatory | Indicate current IP address, netmask, default gateway, and DNS server. |
| 1.3.6.1.4.1.17420.1.2.3 | ScalardevMAC | read-only | mandatory | Indicate current MAC address. |
| 1.3.6.1.4.1.17420.1.2.4 | ScalardevVersion | read-only | mandatory | Indicate current firmware version. |
| 1.3.6.1.4.1.17420.1.2.5 | ScalardevInfo | read-only | mandatory | Indicate the count of attached PDUs and their id. |
| 1.3.6.1.4.1.17420.1.2.6 | ScalardevValues | read-only | mandatory | Indicate the PDU values (currents) from PDU1 to PDU16 |
| 1.3.6.1.4.1.17420.1.2.7 | ScalardevTemperature | read-only | mandatory | Indicate the PDU temperature in Celsius degree |
| 1.3.6.1.4.1.17420.1.2.8 | ScalardevHumidity | read-only | mandatory | Indicate the PDU humidity in percentage (%) |
| 1.3.6.1.4.1.17420.1.2.9 | NodepduTable | |||
| 1.3.6.1.4.1.17420.1.2.9.1 | Nodepdu01Entry | |||
| 1.3.6.1.4.1.17420.1.2.9.1.11 | Scalarpdu01Value | read-only | mandatory | Indicate the current of PDU-01 detect. |
| 1.3.6.1.4.1.17420.1.2.9.1.12 | Scalarpdu01SubValues | read-only | mandatory | Indicate the outlet values (currents) from Outlet1 to Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.1.13 | Scalarpdu01OutletStatus | read-write | mandatory | Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8 1: Outlet ON 0: Outlet OFF -1: Outlet is not available -2: Outlet powr lost or Breaker trigger… |
| 1.3.6.1.4.1.17420.1.2.9.1.14 | Nodepdu01OutletConfigs | |||
| 1.3.6.1.4.1.17420.1.2.9.1.14.1 | Scalarpdu01Outlet1Config | read-write | mandatory | Indicate the configuration of Outlet1 |
| 1.3.6.1.4.1.17420.1.2.9.1.14.2 | Scalarpdu01Outlet2Config | read-write | mandatory | Indicate the configuration of Outlet2 |
| 1.3.6.1.4.1.17420.1.2.9.1.14.3 | Scalarpdu01Outlet3Config | read-write | mandatory | Indicate the configuration of Outlet3 |
| 1.3.6.1.4.1.17420.1.2.9.1.14.4 | Scalarpdu01Outlet4Config | read-write | mandatory | Indicate the configuration of Outlet4 |
| 1.3.6.1.4.1.17420.1.2.9.1.14.5 | Scalarpdu01Outlet5Config | read-write | mandatory | Indicate the configuration of Outlet5 |
| 1.3.6.1.4.1.17420.1.2.9.1.14.6 | Scalarpdu01Outlet6Config | read-write | mandatory | Indicate the configuration of Outlet6 |
| 1.3.6.1.4.1.17420.1.2.9.1.14.7 | Scalarpdu01Outlet7Config | read-write | mandatory | Indicate the configuration of Outlet7 |
| 1.3.6.1.4.1.17420.1.2.9.1.14.8 | Scalarpdu01Outlet8Config | read-write | mandatory | Indicate the configuration of Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.1.14.9 | Scalarpdu01Outlet9Config | read-write | mandatory | Indicate the configuration of Outlet9 |
| 1.3.6.1.4.1.17420.1.2.9.1.14.10 | Scalarpdu01Outlet10Config | read-write | mandatory | Indicate the configuration of Outlet10 |
| 1.3.6.1.4.1.17420.1.2.9.1.14.11 | Scalarpdu01Outlet11Config | read-write | mandatory | Indicate the configuration of Outlet11 |
| 1.3.6.1.4.1.17420.1.2.9.1.14.12 | Scalarpdu01Outlet12Config | read-write | mandatory | Indicate the configuration of Outlet12 |
| 1.3.6.1.4.1.17420.1.2.9.1.14.13 | Scalarpdu01Outlet13Config | read-write | mandatory | Indicate the configuration of Outlet13 |
| 1.3.6.1.4.1.17420.1.2.9.1.14.14 | Scalarpdu01Outlet14Config | read-write | mandatory | Indicate the configuration of Outlet14 |
| 1.3.6.1.4.1.17420.1.2.9.1.14.15 | Scalarpdu01Outlet15Config | read-write | mandatory | Indicate the configuration of Outlet15 |
| 1.3.6.1.4.1.17420.1.2.9.1.14.16 | Scalarpdu01Outlet16Config | read-write | mandatory | Indicate the configuration of Outlet16 |
| 1.3.6.1.4.1.17420.1.2.9.1.14.17 | Scalarpdu01Outlet17Config | read-write | mandatory | Indicate the configuration of Outlet17 |
| 1.3.6.1.4.1.17420.1.2.9.1.14.18 | Scalarpdu01Outlet18Config | read-write | mandatory | Indicate the configuration of Outlet18 |
| 1.3.6.1.4.1.17420.1.2.9.1.14.19 | Scalarpdu01Outlet19Config | read-write | mandatory | Indicate the configuration of Outlet19 |
| 1.3.6.1.4.1.17420.1.2.9.1.14.20 | Scalarpdu01Outlet20Config | read-write | mandatory | Indicate the configuration of Outlet20 |
| 1.3.6.1.4.1.17420.1.2.9.1.14.21 | Scalarpdu01Outlet21Config | read-write | mandatory | Indicate the configuration of Outlet21 |
| 1.3.6.1.4.1.17420.1.2.9.1.14.22 | Scalarpdu01Outlet22Config | read-write | mandatory | Indicate the configuration of Outlet22 |
| 1.3.6.1.4.1.17420.1.2.9.1.14.23 | Scalarpdu01Outlet23Config | read-write | mandatory | Indicate the configuration of Outlet23 |
| 1.3.6.1.4.1.17420.1.2.9.1.14.24 | Scalarpdu01Outlet24Config | read-write | mandatory | Indicate the configuration of Outlet24 |
| 1.3.6.1.4.1.17420.1.2.9.1.15 | Scalarpdu01Threshold1 | read-write | mandatory | Indicate current threshold 1 (warning current). |
| 1.3.6.1.4.1.17420.1.2.9.1.16 | Scalarpdu01Threshold2 | read-write | mandatory | Indicate current threshold 2 (critical current). |
| 1.3.6.1.4.1.17420.1.2.9.1.17 | Scalarpdu01Voltage | read-only | mandatory | Indicate voltage of PDU. |
| 1.3.6.1.4.1.17420.1.2.9.1.18 | Scalarpdu01ModelName | read-only | mandatory | Indicate PDU model name. |
| 1.3.6.1.4.1.17420.1.2.9.1.19 | Scalarpdu01ModelNo | read-only | mandatory | Indicate PDU model number. |
| 1.3.6.1.4.1.17420.1.2.9.1.20 | Scalarpdu01Identify | read-write | mandatory | Indicate PDU identify. |
| 1.3.6.1.4.1.17420.1.2.9.1.21 | Scalarpdu01DelayOn | read-write | mandatory | Indicate PDU Outlet On delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.1.22 | Scalarpdu01DelayOff | read-write | mandatory | Indicate PDU Outlet Off delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.2 | Nodepdu02Entry | |||
| 1.3.6.1.4.1.17420.1.2.9.2.11 | Scalarpdu02Value | read-only | mandatory | Indicate the current of PDU-02 detect. |
| 1.3.6.1.4.1.17420.1.2.9.2.12 | Scalarpdu02SubValues | read-only | mandatory | Indicate the outlet values (currents) from Outlet1 to Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.2.13 | Scalarpdu02OutletStatus | read-write | mandatory | Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8 1: Outlet ON 0: Outlet OFF -1: Outlet is not available -2: Outlet powr lost or Breaker trigger… |
| 1.3.6.1.4.1.17420.1.2.9.2.14 | Nodepdu02OutletConfigs | |||
| 1.3.6.1.4.1.17420.1.2.9.2.14.1 | Scalarpdu02Outlet1Config | read-write | mandatory | Indicate the configuration of Outlet1 |
| 1.3.6.1.4.1.17420.1.2.9.2.14.2 | Scalarpdu02Outlet2Config | read-write | mandatory | Indicate the configuration of Outlet2 |
| 1.3.6.1.4.1.17420.1.2.9.2.14.3 | Scalarpdu02Outlet3Config | read-write | mandatory | Indicate the configuration of Outlet3 |
| 1.3.6.1.4.1.17420.1.2.9.2.14.4 | Scalarpdu02Outlet4Config | read-write | mandatory | Indicate the configuration of Outlet4 |
| 1.3.6.1.4.1.17420.1.2.9.2.14.5 | Scalarpdu02Outlet5Config | read-write | mandatory | Indicate the configuration of Outlet5 |
| 1.3.6.1.4.1.17420.1.2.9.2.14.6 | Scalarpdu02Outlet6Config | read-write | mandatory | Indicate the configuration of Outlet6 |
| 1.3.6.1.4.1.17420.1.2.9.2.14.7 | Scalarpdu02Outlet7Config | read-write | mandatory | Indicate the configuration of Outlet7 |
| 1.3.6.1.4.1.17420.1.2.9.2.14.8 | Scalarpdu02Outlet8Config | read-write | mandatory | Indicate the configuration of Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.2.15 | Scalarpdu02Threshold1 | read-write | mandatory | Indicate current threshold 1 (warning current). |
| 1.3.6.1.4.1.17420.1.2.9.2.16 | Scalarpdu02Threshold2 | read-write | mandatory | Indicate current threshold 2 (critical current). |
| 1.3.6.1.4.1.17420.1.2.9.2.17 | Scalarpdu02Voltage | read-only | mandatory | Indicate voltage of PDU. |
| 1.3.6.1.4.1.17420.1.2.9.2.18 | Scalarpdu02ModelName | read-only | mandatory | Indicate PDU model name. |
| 1.3.6.1.4.1.17420.1.2.9.2.19 | Scalarpdu02ModelNo | read-only | mandatory | Indicate PDU model number. |
| 1.3.6.1.4.1.17420.1.2.9.2.20 | Scalarpdu02Identify | read-write | mandatory | Indicate PDU identify. |
| 1.3.6.1.4.1.17420.1.2.9.2.21 | Scalarpdu02DelayOn | read-write | mandatory | Indicate PDU Outlet On delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.2.22 | Scalarpdu02DelayOff | read-write | mandatory | Indicate PDU Outlet Off delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.3 | Nodepdu03Entry | |||
| 1.3.6.1.4.1.17420.1.2.9.3.11 | Scalarpdu03Value | read-only | mandatory | Indicate the current of PDU-03 detect. |
| 1.3.6.1.4.1.17420.1.2.9.3.12 | Scalarpdu03SubValues | read-only | mandatory | Indicate the outlet values (currents) from Outlet1 to Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.3.13 | Scalarpdu03OutletStatus | read-write | mandatory | Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8 1: Outlet ON 0: Outlet OFF -1: Outlet is not available -2: Outlet powr lost or Breaker trigger… |
| 1.3.6.1.4.1.17420.1.2.9.3.14 | Nodepdu03OutletConfigs | |||
| 1.3.6.1.4.1.17420.1.2.9.3.14.1 | Scalarpdu03Outlet1Config | read-write | mandatory | Indicate the configuration of Outlet1 |
| 1.3.6.1.4.1.17420.1.2.9.3.14.2 | Scalarpdu03Outlet2Config | read-write | mandatory | Indicate the configuration of Outlet2 |
| 1.3.6.1.4.1.17420.1.2.9.3.14.3 | Scalarpdu03Outlet3Config | read-write | mandatory | Indicate the configuration of Outlet3 |
| 1.3.6.1.4.1.17420.1.2.9.3.14.4 | Scalarpdu03Outlet4Config | read-write | mandatory | Indicate the configuration of Outlet4 |
| 1.3.6.1.4.1.17420.1.2.9.3.14.5 | Scalarpdu03Outlet5Config | read-write | mandatory | Indicate the configuration of Outlet5 |
| 1.3.6.1.4.1.17420.1.2.9.3.14.6 | Scalarpdu03Outlet6Config | read-write | mandatory | Indicate the configuration of Outlet6 |
| 1.3.6.1.4.1.17420.1.2.9.3.14.7 | Scalarpdu03Outlet7Config | read-write | mandatory | Indicate the configuration of Outlet7 |
| 1.3.6.1.4.1.17420.1.2.9.3.14.8 | Scalarpdu03Outlet8Config | read-write | mandatory | Indicate the configuration of Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.3.15 | Scalarpdu03Threshold1 | read-write | mandatory | Indicate current threshold 1 (warning current). |
| 1.3.6.1.4.1.17420.1.2.9.3.16 | Scalarpdu03Threshold2 | read-write | mandatory | Indicate current threshold 2 (critical current). |
| 1.3.6.1.4.1.17420.1.2.9.3.17 | Scalarpdu03Voltage | read-only | mandatory | Indicate voltage of PDU. |
| 1.3.6.1.4.1.17420.1.2.9.3.18 | Scalarpdu03ModelName | read-only | mandatory | Indicate PDU model name. |
| 1.3.6.1.4.1.17420.1.2.9.3.19 | Scalarpdu03ModelNo | read-only | mandatory | Indicate PDU model number. |
| 1.3.6.1.4.1.17420.1.2.9.3.20 | Scalarpdu03Identify | read-write | mandatory | Indicate PDU identify. |
| 1.3.6.1.4.1.17420.1.2.9.3.21 | Scalarpdu03DelayOn | read-write | mandatory | Indicate PDU Outlet On delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.3.22 | Scalarpdu03DelayOff | read-write | mandatory | Indicate PDU Outlet Off delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.4 | Nodepdu04Entry | |||
| 1.3.6.1.4.1.17420.1.2.9.4.11 | Scalarpdu04Value | read-only | mandatory | Indicate the current of PDU-04 detect. |
| 1.3.6.1.4.1.17420.1.2.9.4.12 | Scalarpdu04SubValues | read-only | mandatory | Indicate the outlet values (currents) from Outlet1 to Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.4.13 | Scalarpdu04OutletStatus | read-write | mandatory | Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8 1: Outlet ON 0: Outlet OFF -1: Outlet is not available -2: Outlet powr lost or Breaker trigger… |
| 1.3.6.1.4.1.17420.1.2.9.4.14 | Nodepdu04OutletConfigs | |||
| 1.3.6.1.4.1.17420.1.2.9.4.14.1 | Scalarpdu04Outlet1Config | read-write | mandatory | Indicate the configuration of Outlet1 |
| 1.3.6.1.4.1.17420.1.2.9.4.14.2 | Scalarpdu04Outlet2Config | read-write | mandatory | Indicate the configuration of Outlet2 |
| 1.3.6.1.4.1.17420.1.2.9.4.14.3 | Scalarpdu04Outlet3Config | read-write | mandatory | Indicate the configuration of Outlet3 |
| 1.3.6.1.4.1.17420.1.2.9.4.14.4 | Scalarpdu04Outlet4Config | read-write | mandatory | Indicate the configuration of Outlet4 |
| 1.3.6.1.4.1.17420.1.2.9.4.14.5 | Scalarpdu04Outlet5Config | read-write | mandatory | Indicate the configuration of Outlet5 |
| 1.3.6.1.4.1.17420.1.2.9.4.14.6 | Scalarpdu04Outlet6Config | read-write | mandatory | Indicate the configuration of Outlet6 |
| 1.3.6.1.4.1.17420.1.2.9.4.14.7 | Scalarpdu04Outlet7Config | read-write | mandatory | Indicate the configuration of Outlet7 |
| 1.3.6.1.4.1.17420.1.2.9.4.14.8 | Scalarpdu04Outlet8Config | read-write | mandatory | Indicate the configuration of Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.4.15 | Scalarpdu04Threshold1 | read-write | mandatory | Indicate current threshold 1 (warning current). |
| 1.3.6.1.4.1.17420.1.2.9.4.16 | Scalarpdu04Threshold2 | read-write | mandatory | Indicate current threshold 2 (critical current). |
| 1.3.6.1.4.1.17420.1.2.9.4.17 | Scalarpdu04Voltage | read-only | mandatory | Indicate voltage of PDU. |
| 1.3.6.1.4.1.17420.1.2.9.4.18 | Scalarpdu04ModelName | read-only | mandatory | Indicate PDU model name. |
| 1.3.6.1.4.1.17420.1.2.9.4.19 | Scalarpdu04ModelNo | read-only | mandatory | Indicate PDU model number. |
| 1.3.6.1.4.1.17420.1.2.9.4.20 | Scalarpdu04Identify | read-write | mandatory | Indicate PDU identify. |
| 1.3.6.1.4.1.17420.1.2.9.4.21 | Scalarpdu04DelayOn | read-write | mandatory | Indicate PDU Outlet On delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.4.22 | Scalarpdu04DelayOff | read-write | mandatory | Indicate PDU Outlet Off delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.5 | Nodepdu05Entry | |||
| 1.3.6.1.4.1.17420.1.2.9.5.11 | Scalarpdu05Value | read-only | mandatory | Indicate the current of PDU-05 detect. |
| 1.3.6.1.4.1.17420.1.2.9.5.12 | Scalarpdu05SubValues | read-only | mandatory | Indicate the outlet values (currents) from Outlet1 to Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.5.13 | Scalarpdu05OutletStatus | read-write | mandatory | Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8 1: Outlet ON 0: Outlet OFF -1: Outlet is not available -2: Outlet powr lost or Breaker trigger… |
| 1.3.6.1.4.1.17420.1.2.9.5.14 | Nodepdu05OutletConfigs | |||
| 1.3.6.1.4.1.17420.1.2.9.5.14.1 | Scalarpdu05Outlet1Config | read-write | mandatory | Indicate the configuration of Outlet1 |
| 1.3.6.1.4.1.17420.1.2.9.5.14.2 | Scalarpdu05Outlet2Config | read-write | mandatory | Indicate the configuration of Outlet2 |
| 1.3.6.1.4.1.17420.1.2.9.5.14.3 | Scalarpdu05Outlet3Config | read-write | mandatory | Indicate the configuration of Outlet3 |
| 1.3.6.1.4.1.17420.1.2.9.5.14.4 | Scalarpdu05Outlet4Config | read-write | mandatory | Indicate the configuration of Outlet4 |
| 1.3.6.1.4.1.17420.1.2.9.5.14.5 | Scalarpdu05Outlet5Config | read-write | mandatory | Indicate the configuration of Outlet5 |
| 1.3.6.1.4.1.17420.1.2.9.5.14.6 | Scalarpdu05Outlet6Config | read-write | mandatory | Indicate the configuration of Outlet6 |
| 1.3.6.1.4.1.17420.1.2.9.5.14.7 | Scalarpdu05Outlet7Config | read-write | mandatory | Indicate the configuration of Outlet7 |
| 1.3.6.1.4.1.17420.1.2.9.5.14.8 | Scalarpdu05Outlet8Config | read-write | mandatory | Indicate the configuration of Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.5.15 | Scalarpdu05Threshold1 | read-write | mandatory | Indicate current threshold 1 (warning current). |
| 1.3.6.1.4.1.17420.1.2.9.5.16 | Scalarpdu05Threshold2 | read-write | mandatory | Indicate current threshold 2 (critical current). |
| 1.3.6.1.4.1.17420.1.2.9.5.17 | Scalarpdu05Voltage | read-only | mandatory | Indicate voltage of PDU. |
| 1.3.6.1.4.1.17420.1.2.9.5.18 | Scalarpdu05ModelName | read-only | mandatory | Indicate PDU model name. |
| 1.3.6.1.4.1.17420.1.2.9.5.19 | Scalarpdu05ModelNo | read-only | mandatory | Indicate PDU model number. |
| 1.3.6.1.4.1.17420.1.2.9.5.20 | Scalarpdu05Identify | read-write | mandatory | Indicate PDU identify. |
| 1.3.6.1.4.1.17420.1.2.9.5.21 | Scalarpdu05DelayOn | read-write | mandatory | Indicate PDU Outlet On delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.5.22 | Scalarpdu05DelayOff | read-write | mandatory | Indicate PDU Outlet Off delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.6 | Nodepdu06Entry | |||
| 1.3.6.1.4.1.17420.1.2.9.6.11 | Scalarpdu06Value | read-only | mandatory | Indicate the current of PDU-06 detect. |
| 1.3.6.1.4.1.17420.1.2.9.6.12 | Scalarpdu06SubValues | read-only | mandatory | Indicate the outlet values (currents) from Outlet1 to Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.6.13 | Scalarpdu06OutletStatus | read-write | mandatory | Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8 1: Outlet ON 0: Outlet OFF -1: Outlet is not available -2: Outlet powr lost or Breaker trigger… |
| 1.3.6.1.4.1.17420.1.2.9.6.14 | Nodepdu06OutletConfigs | |||
| 1.3.6.1.4.1.17420.1.2.9.6.14.1 | Scalarpdu06Outlet1Config | read-write | mandatory | Indicate the configuration of Outlet1 |
| 1.3.6.1.4.1.17420.1.2.9.6.14.2 | Scalarpdu06Outlet2Config | read-write | mandatory | Indicate the configuration of Outlet2 |
| 1.3.6.1.4.1.17420.1.2.9.6.14.3 | Scalarpdu06Outlet3Config | read-write | mandatory | Indicate the configuration of Outlet3 |
| 1.3.6.1.4.1.17420.1.2.9.6.14.4 | Scalarpdu06Outlet4Config | read-write | mandatory | Indicate the configuration of Outlet4 |
| 1.3.6.1.4.1.17420.1.2.9.6.14.5 | Scalarpdu06Outlet5Config | read-write | mandatory | Indicate the configuration of Outlet5 |
| 1.3.6.1.4.1.17420.1.2.9.6.14.6 | Scalarpdu06Outlet6Config | read-write | mandatory | Indicate the configuration of Outlet6 |
| 1.3.6.1.4.1.17420.1.2.9.6.14.7 | Scalarpdu06Outlet7Config | read-write | mandatory | Indicate the configuration of Outlet7 |
| 1.3.6.1.4.1.17420.1.2.9.6.14.8 | Scalarpdu06Outlet8Config | read-write | mandatory | Indicate the configuration of Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.6.15 | Scalarpdu06Threshold1 | read-write | mandatory | Indicate current threshold 1 (warning current). |
| 1.3.6.1.4.1.17420.1.2.9.6.16 | Scalarpdu06Threshold2 | read-write | mandatory | Indicate current threshold 2 (critical current). |
| 1.3.6.1.4.1.17420.1.2.9.6.17 | Scalarpdu06Voltage | read-only | mandatory | Indicate voltage of PDU. |
| 1.3.6.1.4.1.17420.1.2.9.6.18 | Scalarpdu06ModelName | read-only | mandatory | Indicate PDU model name. |
| 1.3.6.1.4.1.17420.1.2.9.6.19 | Scalarpdu06ModelNo | read-only | mandatory | Indicate PDU model number. |
| 1.3.6.1.4.1.17420.1.2.9.6.20 | Scalarpdu06Identify | read-write | mandatory | Indicate PDU identify. |
| 1.3.6.1.4.1.17420.1.2.9.6.21 | Scalarpdu06DelayOn | read-write | mandatory | Indicate PDU Outlet On delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.6.22 | Scalarpdu06DelayOff | read-write | mandatory | Indicate PDU Outlet Off delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.7 | Nodepdu07Entry | |||
| 1.3.6.1.4.1.17420.1.2.9.7.11 | Scalarpdu07Value | read-only | mandatory | Indicate the current of PDU-07 detect. |
| 1.3.6.1.4.1.17420.1.2.9.7.12 | Scalarpdu07SubValues | read-only | mandatory | Indicate the outlet values (currents) from Outlet1 to Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.7.13 | Scalarpdu07OutletStatus | read-write | mandatory | Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8 1: Outlet ON 0: Outlet OFF -1: Outlet is not available -2: Outlet powr lost or Breaker trigger… |
| 1.3.6.1.4.1.17420.1.2.9.7.14 | Nodepdu07OutletConfigs | |||
| 1.3.6.1.4.1.17420.1.2.9.7.14.1 | Scalarpdu07Outlet1Config | read-write | mandatory | Indicate the configuration of Outlet1 |
| 1.3.6.1.4.1.17420.1.2.9.7.14.2 | Scalarpdu07Outlet2Config | read-write | mandatory | Indicate the configuration of Outlet2 |
| 1.3.6.1.4.1.17420.1.2.9.7.14.3 | Scalarpdu07Outlet3Config | read-write | mandatory | Indicate the configuration of Outlet3 |
| 1.3.6.1.4.1.17420.1.2.9.7.14.4 | Scalarpdu07Outlet4Config | read-write | mandatory | Indicate the configuration of Outlet4 |
| 1.3.6.1.4.1.17420.1.2.9.7.14.5 | Scalarpdu07Outlet5Config | read-write | mandatory | Indicate the configuration of Outlet5 |
| 1.3.6.1.4.1.17420.1.2.9.7.14.6 | Scalarpdu07Outlet6Config | read-write | mandatory | Indicate the configuration of Outlet6 |
| 1.3.6.1.4.1.17420.1.2.9.7.14.7 | Scalarpdu07Outlet7Config | read-write | mandatory | Indicate the configuration of Outlet7 |
| 1.3.6.1.4.1.17420.1.2.9.7.14.8 | Scalarpdu07Outlet8Config | read-write | mandatory | Indicate the configuration of Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.7.15 | Scalarpdu07Threshold1 | read-write | mandatory | Indicate current threshold 1 (warning current). |
| 1.3.6.1.4.1.17420.1.2.9.7.16 | Scalarpdu07Threshold2 | read-write | mandatory | Indicate current threshold 2 (critical current). |
| 1.3.6.1.4.1.17420.1.2.9.7.17 | Scalarpdu07Voltage | read-only | mandatory | Indicate voltage of PDU. |
| 1.3.6.1.4.1.17420.1.2.9.7.18 | Scalarpdu07ModelName | read-only | mandatory | Indicate PDU model name. |
| 1.3.6.1.4.1.17420.1.2.9.7.19 | Scalarpdu07ModelNo | read-only | mandatory | Indicate PDU model number. |
| 1.3.6.1.4.1.17420.1.2.9.7.20 | Scalarpdu07Identify | read-write | mandatory | Indicate PDU identify. |
| 1.3.6.1.4.1.17420.1.2.9.7.21 | Scalarpdu07DelayOn | read-write | mandatory | Indicate PDU Outlet On delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.7.22 | Scalarpdu07DelayOff | read-write | mandatory | Indicate PDU Outlet Off delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.8 | Nodepdu08Entry | |||
| 1.3.6.1.4.1.17420.1.2.9.8.11 | Scalarpdu08Value | read-only | mandatory | Indicate the current of PDU-08 detect. |
| 1.3.6.1.4.1.17420.1.2.9.8.12 | Scalarpdu08SubValues | read-only | mandatory | Indicate the outlet values (currents) from Outlet1 to Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.8.13 | Scalarpdu08OutletStatus | read-write | mandatory | Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8 1: Outlet ON 0: Outlet OFF -1: Outlet is not available -2: Outlet powr lost or Breaker trigger… |
| 1.3.6.1.4.1.17420.1.2.9.8.14 | Nodepdu08OutletConfigs | |||
| 1.3.6.1.4.1.17420.1.2.9.8.14.1 | Scalarpdu08Outlet1Config | read-write | mandatory | Indicate the configuration of Outlet1 |
| 1.3.6.1.4.1.17420.1.2.9.8.14.2 | Scalarpdu08Outlet2Config | read-write | mandatory | Indicate the configuration of Outlet2 |
| 1.3.6.1.4.1.17420.1.2.9.8.14.3 | Scalarpdu08Outlet3Config | read-write | mandatory | Indicate the configuration of Outlet3 |
| 1.3.6.1.4.1.17420.1.2.9.8.14.4 | Scalarpdu08Outlet4Config | read-write | mandatory | Indicate the configuration of Outlet4 |
| 1.3.6.1.4.1.17420.1.2.9.8.14.5 | Scalarpdu08Outlet5Config | read-write | mandatory | Indicate the configuration of Outlet5 |
| 1.3.6.1.4.1.17420.1.2.9.8.14.6 | Scalarpdu08Outlet6Config | read-write | mandatory | Indicate the configuration of Outlet6 |
| 1.3.6.1.4.1.17420.1.2.9.8.14.7 | Scalarpdu08Outlet7Config | read-write | mandatory | Indicate the configuration of Outlet7 |
| 1.3.6.1.4.1.17420.1.2.9.8.14.8 | Scalarpdu08Outlet8Config | read-write | mandatory | Indicate the configuration of Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.8.15 | Scalarpdu08Threshold1 | read-write | mandatory | Indicate current threshold 1 (warning current). |
| 1.3.6.1.4.1.17420.1.2.9.8.16 | Scalarpdu08Threshold2 | read-write | mandatory | Indicate current threshold 2 (critical current). |
| 1.3.6.1.4.1.17420.1.2.9.8.17 | Scalarpdu08Voltage | read-only | mandatory | Indicate voltage of PDU. |
| 1.3.6.1.4.1.17420.1.2.9.8.18 | Scalarpdu08ModelName | read-only | mandatory | Indicate PDU model name. |
| 1.3.6.1.4.1.17420.1.2.9.8.19 | Scalarpdu08ModelNo | read-only | mandatory | Indicate PDU model number. |
| 1.3.6.1.4.1.17420.1.2.9.8.20 | Scalarpdu08Identify | read-write | mandatory | Indicate PDU identify. |
| 1.3.6.1.4.1.17420.1.2.9.8.21 | Scalarpdu08DelayOn | read-write | mandatory | Indicate PDU Outlet On delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.8.22 | Scalarpdu08DelayOff | read-write | mandatory | Indicate PDU Outlet Off delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.9 | Nodepdu09Entry | |||
| 1.3.6.1.4.1.17420.1.2.9.9.11 | Scalarpdu09Value | read-only | mandatory | Indicate the current of PDU-09 detect. |
| 1.3.6.1.4.1.17420.1.2.9.9.12 | Scalarpdu09SubValues | read-only | mandatory | Indicate the outlet values (currents) from Outlet1 to Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.9.13 | Scalarpdu09OutletStatus | read-write | mandatory | Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8 1: Outlet ON 0: Outlet OFF -1: Outlet is not available -2: Outlet powr lost or Breaker trigger… |
| 1.3.6.1.4.1.17420.1.2.9.9.14 | Nodepdu09OutletConfigs | |||
| 1.3.6.1.4.1.17420.1.2.9.9.14.1 | Scalarpdu09Outlet1Config | read-write | mandatory | Indicate the configuration of Outlet1 |
| 1.3.6.1.4.1.17420.1.2.9.9.14.2 | Scalarpdu09Outlet2Config | read-write | mandatory | Indicate the configuration of Outlet2 |
| 1.3.6.1.4.1.17420.1.2.9.9.14.3 | Scalarpdu09Outlet3Config | read-write | mandatory | Indicate the configuration of Outlet3 |
| 1.3.6.1.4.1.17420.1.2.9.9.14.4 | Scalarpdu09Outlet4Config | read-write | mandatory | Indicate the configuration of Outlet4 |
| 1.3.6.1.4.1.17420.1.2.9.9.14.5 | Scalarpdu09Outlet5Config | read-write | mandatory | Indicate the configuration of Outlet5 |
| 1.3.6.1.4.1.17420.1.2.9.9.14.6 | Scalarpdu09Outlet6Config | read-write | mandatory | Indicate the configuration of Outlet6 |
| 1.3.6.1.4.1.17420.1.2.9.9.14.7 | Scalarpdu09Outlet7Config | read-write | mandatory | Indicate the configuration of Outlet7 |
| 1.3.6.1.4.1.17420.1.2.9.9.14.8 | Scalarpdu09Outlet8Config | read-write | mandatory | Indicate the configuration of Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.9.15 | Scalarpdu09Threshold1 | read-write | mandatory | Indicate current threshold 1 (warning current). |
| 1.3.6.1.4.1.17420.1.2.9.9.16 | Scalarpdu09Threshold2 | read-write | mandatory | Indicate current threshold 2 (critical current). |
| 1.3.6.1.4.1.17420.1.2.9.9.17 | Scalarpdu09Voltage | read-only | mandatory | Indicate voltage of PDU. |
| 1.3.6.1.4.1.17420.1.2.9.9.18 | Scalarpdu09ModelName | read-only | mandatory | Indicate PDU model name. |
| 1.3.6.1.4.1.17420.1.2.9.9.19 | Scalarpdu09ModelNo | read-only | mandatory | Indicate PDU model number. |
| 1.3.6.1.4.1.17420.1.2.9.9.20 | Scalarpdu09Identify | read-write | mandatory | Indicate PDU identify. |
| 1.3.6.1.4.1.17420.1.2.9.9.21 | Scalarpdu09DelayOn | read-write | mandatory | Indicate PDU Outlet On delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.9.22 | Scalarpdu09DelayOff | read-write | mandatory | Indicate PDU Outlet Off delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.10 | Nodepdu10Entry | |||
| 1.3.6.1.4.1.17420.1.2.9.10.11 | Scalarpdu10Value | read-only | mandatory | Indicate the current of PDU-10 detect. |
| 1.3.6.1.4.1.17420.1.2.9.10.12 | Scalarpdu10SubValues | read-only | mandatory | Indicate the outlet values (currents) from Outlet1 to Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.10.13 | Scalarpdu10OutletStatus | read-write | mandatory | Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8 1: Outlet ON 0: Outlet OFF -1: Outlet is not available -2: Outlet powr lost or Breaker trigger… |
| 1.3.6.1.4.1.17420.1.2.9.10.14 | Nodepdu10OutletConfigs | |||
| 1.3.6.1.4.1.17420.1.2.9.10.14.1 | Scalarpdu10Outlet1Config | read-write | mandatory | Indicate the configuration of Outlet1 |
| 1.3.6.1.4.1.17420.1.2.9.10.14.2 | Scalarpdu10Outlet2Config | read-write | mandatory | Indicate the configuration of Outlet2 |
| 1.3.6.1.4.1.17420.1.2.9.10.14.3 | Scalarpdu10Outlet3Config | read-write | mandatory | Indicate the configuration of Outlet3 |
| 1.3.6.1.4.1.17420.1.2.9.10.14.4 | Scalarpdu10Outlet4Config | read-write | mandatory | Indicate the configuration of Outlet4 |
| 1.3.6.1.4.1.17420.1.2.9.10.14.5 | Scalarpdu10Outlet5Config | read-write | mandatory | Indicate the configuration of Outlet5 |
| 1.3.6.1.4.1.17420.1.2.9.10.14.6 | Scalarpdu10Outlet6Config | read-write | mandatory | Indicate the configuration of Outlet6 |
| 1.3.6.1.4.1.17420.1.2.9.10.14.7 | Scalarpdu10Outlet7Config | read-write | mandatory | Indicate the configuration of Outlet7 |
| 1.3.6.1.4.1.17420.1.2.9.10.14.8 | Scalarpdu10Outlet8Config | read-write | mandatory | Indicate the configuration of Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.10.15 | Scalarpdu10Threshold1 | read-write | mandatory | Indicate current threshold 1 (warning current). |
| 1.3.6.1.4.1.17420.1.2.9.10.16 | Scalarpdu10Threshold2 | read-write | mandatory | Indicate current threshold 2 (critical current). |
| 1.3.6.1.4.1.17420.1.2.9.10.17 | Scalarpdu10Voltage | read-only | mandatory | Indicate voltage of PDU. |
| 1.3.6.1.4.1.17420.1.2.9.10.18 | Scalarpdu10ModelName | read-only | mandatory | Indicate PDU model name. |
| 1.3.6.1.4.1.17420.1.2.9.10.19 | Scalarpdu10ModelNo | read-only | mandatory | Indicate PDU model number. |
| 1.3.6.1.4.1.17420.1.2.9.10.20 | Scalarpdu10Identify | read-write | mandatory | Indicate PDU identify. |
| 1.3.6.1.4.1.17420.1.2.9.10.21 | Scalarpdu10DelayOn | read-write | mandatory | Indicate PDU Outlet On delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.10.22 | Scalarpdu10DelayOff | read-write | mandatory | Indicate PDU Outlet Off delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.11 | Nodepdu11Entry | |||
| 1.3.6.1.4.1.17420.1.2.9.11.11 | Scalarpdu11Value | read-only | mandatory | Indicate the current of PDU-11 detect. |
| 1.3.6.1.4.1.17420.1.2.9.11.12 | Scalarpdu11SubValues | read-only | mandatory | Indicate the outlet values (currents) from Outlet1 to Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.11.13 | Scalarpdu11OutletStatus | read-write | mandatory | Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8 1: Outlet ON 0: Outlet OFF -1: Outlet is not available -2: Outlet powr lost or Breaker trigger… |
| 1.3.6.1.4.1.17420.1.2.9.11.14 | Nodepdu11OutletConfigs | |||
| 1.3.6.1.4.1.17420.1.2.9.11.14.1 | Scalarpdu11Outlet1Config | read-write | mandatory | Indicate the configuration of Outlet1 |
| 1.3.6.1.4.1.17420.1.2.9.11.14.2 | Scalarpdu11Outlet2Config | read-write | mandatory | Indicate the configuration of Outlet2 |
| 1.3.6.1.4.1.17420.1.2.9.11.14.3 | Scalarpdu11Outlet3Config | read-write | mandatory | Indicate the configuration of Outlet3 |
| 1.3.6.1.4.1.17420.1.2.9.11.14.4 | Scalarpdu11Outlet4Config | read-write | mandatory | Indicate the configuration of Outlet4 |
| 1.3.6.1.4.1.17420.1.2.9.11.14.5 | Scalarpdu11Outlet5Config | read-write | mandatory | Indicate the configuration of Outlet5 |
| 1.3.6.1.4.1.17420.1.2.9.11.14.6 | Scalarpdu11Outlet6Config | read-write | mandatory | Indicate the configuration of Outlet6 |
| 1.3.6.1.4.1.17420.1.2.9.11.14.7 | Scalarpdu11Outlet7Config | read-write | mandatory | Indicate the configuration of Outlet7 |
| 1.3.6.1.4.1.17420.1.2.9.11.14.8 | Scalarpdu11Outlet8Config | read-write | mandatory | Indicate the configuration of Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.11.15 | Scalarpdu11Threshold1 | read-write | mandatory | Indicate current threshold 1 (warning current). |
| 1.3.6.1.4.1.17420.1.2.9.11.16 | Scalarpdu11Threshold2 | read-write | mandatory | Indicate current threshold 2 (critical current). |
| 1.3.6.1.4.1.17420.1.2.9.11.17 | Scalarpdu11Voltage | read-only | mandatory | Indicate voltage of PDU. |
| 1.3.6.1.4.1.17420.1.2.9.11.18 | Scalarpdu11ModelName | read-only | mandatory | Indicate PDU model name. |
| 1.3.6.1.4.1.17420.1.2.9.11.19 | Scalarpdu11ModelNo | read-only | mandatory | Indicate PDU model number. |
| 1.3.6.1.4.1.17420.1.2.9.11.20 | Scalarpdu11Identify | read-write | mandatory | Indicate PDU identify. |
| 1.3.6.1.4.1.17420.1.2.9.11.21 | Scalarpdu11DelayOn | read-write | mandatory | Indicate PDU Outlet On delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.11.22 | Scalarpdu11DelayOff | read-write | mandatory | Indicate PDU Outlet Off delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.12 | Nodepdu12Entry | |||
| 1.3.6.1.4.1.17420.1.2.9.12.11 | Scalarpdu12Value | read-only | mandatory | Indicate the current of PDU-12 detect. |
| 1.3.6.1.4.1.17420.1.2.9.12.12 | Scalarpdu12SubValues | read-only | mandatory | Indicate the outlet values (currents) from Outlet1 to Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.12.13 | Scalarpdu12OutletStatus | read-write | mandatory | Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8 1: Outlet ON 0: Outlet OFF -1: Outlet is not available -2: Outlet powr lost or Breaker trigger… |
| 1.3.6.1.4.1.17420.1.2.9.12.14 | Nodepdu12OutletConfigs | |||
| 1.3.6.1.4.1.17420.1.2.9.12.14.1 | Scalarpdu12Outlet1Config | read-write | mandatory | Indicate the configuration of Outlet1 |
| 1.3.6.1.4.1.17420.1.2.9.12.14.2 | Scalarpdu12Outlet2Config | read-write | mandatory | Indicate the configuration of Outlet2 |
| 1.3.6.1.4.1.17420.1.2.9.12.14.3 | Scalarpdu12Outlet3Config | read-write | mandatory | Indicate the configuration of Outlet3 |
| 1.3.6.1.4.1.17420.1.2.9.12.14.4 | Scalarpdu12Outlet4Config | read-write | mandatory | Indicate the configuration of Outlet4 |
| 1.3.6.1.4.1.17420.1.2.9.12.14.5 | Scalarpdu12Outlet5Config | read-write | mandatory | Indicate the configuration of Outlet5 |
| 1.3.6.1.4.1.17420.1.2.9.12.14.6 | Scalarpdu12Outlet6Config | read-write | mandatory | Indicate the configuration of Outlet6 |
| 1.3.6.1.4.1.17420.1.2.9.12.14.7 | Scalarpdu12Outlet7Config | read-write | mandatory | Indicate the configuration of Outlet7 |
| 1.3.6.1.4.1.17420.1.2.9.12.14.8 | Scalarpdu12Outlet8Config | read-write | mandatory | Indicate the configuration of Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.12.15 | Scalarpdu12Threshold1 | read-write | mandatory | Indicate current threshold 1 (warning current). |
| 1.3.6.1.4.1.17420.1.2.9.12.16 | Scalarpdu12Threshold2 | read-write | mandatory | Indicate current threshold 2 (critical current). |
| 1.3.6.1.4.1.17420.1.2.9.12.17 | Scalarpdu12Voltage | read-only | mandatory | Indicate voltage of PDU. |
| 1.3.6.1.4.1.17420.1.2.9.12.18 | Scalarpdu12ModelName | read-only | mandatory | Indicate PDU model name. |
| 1.3.6.1.4.1.17420.1.2.9.12.19 | Scalarpdu12ModelNo | read-only | mandatory | Indicate PDU model number. |
| 1.3.6.1.4.1.17420.1.2.9.12.20 | Scalarpdu12Identify | read-write | mandatory | Indicate PDU identify. |
| 1.3.6.1.4.1.17420.1.2.9.12.21 | Scalarpdu12DelayOn | read-write | mandatory | Indicate PDU Outlet On delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.12.22 | Scalarpdu12DelayOff | read-write | mandatory | Indicate PDU Outlet Off delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.13 | Nodepdu13Entry | |||
| 1.3.6.1.4.1.17420.1.2.9.13.11 | Scalarpdu13Value | read-only | mandatory | Indicate the current of PDU-13 detect. |
| 1.3.6.1.4.1.17420.1.2.9.13.12 | Scalarpdu13SubValues | read-only | mandatory | Indicate the outlet values (currents) from Outlet1 to Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.13.13 | Scalarpdu13OutletStatus | read-write | mandatory | Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8 1: Outlet ON 0: Outlet OFF -1: Outlet is not available -2: Outlet powr lost or Breaker trigger… |
| 1.3.6.1.4.1.17420.1.2.9.13.14 | Nodepdu13OutletConfigs | |||
| 1.3.6.1.4.1.17420.1.2.9.13.14.1 | Scalarpdu13Outlet1Config | read-write | mandatory | Indicate the configuration of Outlet1 |
| 1.3.6.1.4.1.17420.1.2.9.13.14.2 | Scalarpdu13Outlet2Config | read-write | mandatory | Indicate the configuration of Outlet2 |
| 1.3.6.1.4.1.17420.1.2.9.13.14.3 | Scalarpdu13Outlet3Config | read-write | mandatory | Indicate the configuration of Outlet3 |
| 1.3.6.1.4.1.17420.1.2.9.13.14.4 | Scalarpdu13Outlet4Config | read-write | mandatory | Indicate the configuration of Outlet4 |
| 1.3.6.1.4.1.17420.1.2.9.13.14.5 | Scalarpdu13Outlet5Config | read-write | mandatory | Indicate the configuration of Outlet5 |
| 1.3.6.1.4.1.17420.1.2.9.13.14.6 | Scalarpdu13Outlet6Config | read-write | mandatory | Indicate the configuration of Outlet6 |
| 1.3.6.1.4.1.17420.1.2.9.13.14.7 | Scalarpdu13Outlet7Config | read-write | mandatory | Indicate the configuration of Outlet7 |
| 1.3.6.1.4.1.17420.1.2.9.13.14.8 | Scalarpdu13Outlet8Config | read-write | mandatory | Indicate the configuration of Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.13.15 | Scalarpdu13Threshold1 | read-write | mandatory | Indicate current threshold 1 (warning current). |
| 1.3.6.1.4.1.17420.1.2.9.13.16 | Scalarpdu13Threshold2 | read-write | mandatory | Indicate current threshold 2 (critical current). |
| 1.3.6.1.4.1.17420.1.2.9.13.17 | Scalarpdu13Voltage | read-only | mandatory | Indicate voltage of PDU. |
| 1.3.6.1.4.1.17420.1.2.9.13.18 | Scalarpdu13ModelName | read-only | mandatory | Indicate PDU model name. |
| 1.3.6.1.4.1.17420.1.2.9.13.19 | Scalarpdu13ModelNo | read-only | mandatory | Indicate PDU model number. |
| 1.3.6.1.4.1.17420.1.2.9.13.20 | Scalarpdu13Identify | read-write | mandatory | Indicate PDU identify. |
| 1.3.6.1.4.1.17420.1.2.9.13.21 | Scalarpdu13DelayOn | read-write | mandatory | Indicate PDU Outlet On delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.13.22 | Scalarpdu13DelayOff | read-write | mandatory | Indicate PDU Outlet Off delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.14 | Nodepdu14Entry | |||
| 1.3.6.1.4.1.17420.1.2.9.14.11 | Scalarpdu14Value | read-only | mandatory | Indicate the current of PDU-14 detect. |
| 1.3.6.1.4.1.17420.1.2.9.14.12 | Scalarpdu14SubValues | read-only | mandatory | Indicate the outlet values (currents) from Outlet1 to Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.14.13 | Scalarpdu14OutletStatus | read-write | mandatory | Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8 1: Outlet ON 0: Outlet OFF -1: Outlet is not available -2: Outlet powr lost or Breaker trigger… |
| 1.3.6.1.4.1.17420.1.2.9.14.14 | Nodepdu14OutletConfigs | |||
| 1.3.6.1.4.1.17420.1.2.9.14.14.1 | Scalarpdu14Outlet1Config | read-write | mandatory | Indicate the configuration of Outlet1 |
| 1.3.6.1.4.1.17420.1.2.9.14.14.2 | Scalarpdu14Outlet2Config | read-write | mandatory | Indicate the configuration of Outlet2 |
| 1.3.6.1.4.1.17420.1.2.9.14.14.3 | Scalarpdu14Outlet3Config | read-write | mandatory | Indicate the configuration of Outlet3 |
| 1.3.6.1.4.1.17420.1.2.9.14.14.4 | Scalarpdu14Outlet4Config | read-write | mandatory | Indicate the configuration of Outlet4 |
| 1.3.6.1.4.1.17420.1.2.9.14.14.5 | Scalarpdu14Outlet5Config | read-write | mandatory | Indicate the configuration of Outlet5 |
| 1.3.6.1.4.1.17420.1.2.9.14.14.6 | Scalarpdu14Outlet6Config | read-write | mandatory | Indicate the configuration of Outlet6 |
| 1.3.6.1.4.1.17420.1.2.9.14.14.7 | Scalarpdu14Outlet7Config | read-write | mandatory | Indicate the configuration of Outlet7 |
| 1.3.6.1.4.1.17420.1.2.9.14.14.8 | Scalarpdu14Outlet8Config | read-write | mandatory | Indicate the configuration of Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.14.15 | Scalarpdu14Threshold1 | read-write | mandatory | Indicate current threshold 1 (warning current). |
| 1.3.6.1.4.1.17420.1.2.9.14.16 | Scalarpdu14Threshold2 | read-write | mandatory | Indicate current threshold 2 (critical current). |
| 1.3.6.1.4.1.17420.1.2.9.14.17 | Scalarpdu14Voltage | read-only | mandatory | Indicate voltage of PDU. |
| 1.3.6.1.4.1.17420.1.2.9.14.18 | Scalarpdu14ModelName | read-only | mandatory | Indicate PDU model name. |
| 1.3.6.1.4.1.17420.1.2.9.14.19 | Scalarpdu14ModelNo | read-only | mandatory | Indicate PDU model number. |
| 1.3.6.1.4.1.17420.1.2.9.14.20 | Scalarpdu14Identify | read-write | mandatory | Indicate PDU identify. |
| 1.3.6.1.4.1.17420.1.2.9.14.21 | Scalarpdu14DelayOn | read-write | mandatory | Indicate PDU Outlet On delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.14.22 | Scalarpdu14DelayOff | read-write | mandatory | Indicate PDU Outlet Off delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.15 | Nodepdu15Entry | |||
| 1.3.6.1.4.1.17420.1.2.9.15.11 | Scalarpdu15Value | read-only | mandatory | Indicate the current of PDU-15 detect. |
| 1.3.6.1.4.1.17420.1.2.9.15.12 | Scalarpdu15SubValues | read-only | mandatory | Indicate the outlet values (currents) from Outlet1 to Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.15.13 | Scalarpdu15OutletStatus | read-write | mandatory | Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8 1: Outlet ON 0: Outlet OFF -1: Outlet is not available -2: Outlet powr lost or Breaker trigger… |
| 1.3.6.1.4.1.17420.1.2.9.15.14 | Nodepdu15OutletConfigs | |||
| 1.3.6.1.4.1.17420.1.2.9.15.14.1 | Scalarpdu15Outlet1Config | read-write | mandatory | Indicate the configuration of Outlet1 |
| 1.3.6.1.4.1.17420.1.2.9.15.14.2 | Scalarpdu15Outlet2Config | read-write | mandatory | Indicate the configuration of Outlet2 |
| 1.3.6.1.4.1.17420.1.2.9.15.14.3 | Scalarpdu15Outlet3Config | read-write | mandatory | Indicate the configuration of Outlet3 |
| 1.3.6.1.4.1.17420.1.2.9.15.14.4 | Scalarpdu15Outlet4Config | read-write | mandatory | Indicate the configuration of Outlet4 |
| 1.3.6.1.4.1.17420.1.2.9.15.14.5 | Scalarpdu15Outlet5Config | read-write | mandatory | Indicate the configuration of Outlet5 |
| 1.3.6.1.4.1.17420.1.2.9.15.14.6 | Scalarpdu15Outlet6Config | read-write | mandatory | Indicate the configuration of Outlet6 |
| 1.3.6.1.4.1.17420.1.2.9.15.14.7 | Scalarpdu15Outlet7Config | read-write | mandatory | Indicate the configuration of Outlet7 |
| 1.3.6.1.4.1.17420.1.2.9.15.14.8 | Scalarpdu15Outlet8Config | read-write | mandatory | Indicate the configuration of Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.15.15 | Scalarpdu15Threshold1 | read-write | mandatory | Indicate current threshold 1 (warning current). |
| 1.3.6.1.4.1.17420.1.2.9.15.16 | Scalarpdu15Threshold2 | read-write | mandatory | Indicate current threshold 2 (critical current). |
| 1.3.6.1.4.1.17420.1.2.9.15.17 | Scalarpdu15Voltage | read-only | mandatory | Indicate voltage of PDU. |
| 1.3.6.1.4.1.17420.1.2.9.15.18 | Scalarpdu15ModelName | read-only | mandatory | Indicate PDU model name. |
| 1.3.6.1.4.1.17420.1.2.9.15.19 | Scalarpdu15ModelNo | read-only | mandatory | Indicate PDU model number. |
| 1.3.6.1.4.1.17420.1.2.9.15.20 | Scalarpdu15Identify | read-write | mandatory | Indicate PDU identify. |
| 1.3.6.1.4.1.17420.1.2.9.15.21 | Scalarpdu15DelayOn | read-write | mandatory | Indicate PDU Outlet On delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.15.22 | Scalarpdu15DelayOff | read-write | mandatory | Indicate PDU Outlet Off delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.16 | Nodepdu16Entry | |||
| 1.3.6.1.4.1.17420.1.2.9.16.11 | Scalarpdu16Value | read-only | mandatory | Indicate the current of PDU-16 detect. |
| 1.3.6.1.4.1.17420.1.2.9.16.12 | Scalarpdu16SubValues | read-only | mandatory | Indicate the outlet values (currents) from Outlet1 to Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.16.13 | Scalarpdu16OutletStatus | read-write | mandatory | Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8 1: Outlet ON 0: Outlet OFF -1: Outlet is not available -2: Outlet powr lost or Breaker trigger… |
| 1.3.6.1.4.1.17420.1.2.9.16.14 | Nodepdu16OutletConfigs | |||
| 1.3.6.1.4.1.17420.1.2.9.16.14.1 | Scalarpdu16Outlet1Config | read-write | mandatory | Indicate the configuration of Outlet1 |
| 1.3.6.1.4.1.17420.1.2.9.16.14.2 | Scalarpdu16Outlet2Config | read-write | mandatory | Indicate the configuration of Outlet2 |
| 1.3.6.1.4.1.17420.1.2.9.16.14.3 | Scalarpdu16Outlet3Config | read-write | mandatory | Indicate the configuration of Outlet3 |
| 1.3.6.1.4.1.17420.1.2.9.16.14.4 | Scalarpdu16Outlet4Config | read-write | mandatory | Indicate the configuration of Outlet4 |
| 1.3.6.1.4.1.17420.1.2.9.16.14.5 | Scalarpdu16Outlet5Config | read-write | mandatory | Indicate the configuration of Outlet5 |
| 1.3.6.1.4.1.17420.1.2.9.16.14.6 | Scalarpdu16Outlet6Config | read-write | mandatory | Indicate the configuration of Outlet6 |
| 1.3.6.1.4.1.17420.1.2.9.16.14.7 | Scalarpdu16Outlet7Config | read-write | mandatory | Indicate the configuration of Outlet7 |
| 1.3.6.1.4.1.17420.1.2.9.16.14.8 | Scalarpdu16Outlet8Config | read-write | mandatory | Indicate the configuration of Outlet8 |
| 1.3.6.1.4.1.17420.1.2.9.16.15 | Scalarpdu16Threshold1 | read-write | mandatory | Indicate current threshold 1 (warning current). |
| 1.3.6.1.4.1.17420.1.2.9.16.16 | Scalarpdu16Threshold2 | read-write | mandatory | Indicate current threshold 2 (critical current). |
| 1.3.6.1.4.1.17420.1.2.9.16.17 | Scalarpdu16Voltage | read-only | mandatory | Indicate voltage of PDU. |
| 1.3.6.1.4.1.17420.1.2.9.16.18 | Scalarpdu16ModelName | read-only | mandatory | Indicate PDU model name. |
| 1.3.6.1.4.1.17420.1.2.9.16.19 | Scalarpdu16ModelNo | read-only | mandatory | Indicate PDU model number. |
| 1.3.6.1.4.1.17420.1.2.9.16.20 | Scalarpdu16Identify | read-write | mandatory | Indicate PDU identify. |
| 1.3.6.1.4.1.17420.1.2.9.16.21 | Scalarpdu16DelayOn | read-write | mandatory | Indicate PDU Outlet On delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.2.9.16.22 | Scalarpdu16DelayOff | read-write | mandatory | Indicate PDU Outlet Off delay time. Unit is second |
| 1.3.6.1.4.1.17420.1.4 | Nodeenvthreshold | |||
| 1.3.6.1.4.1.17420.1.4.42 | ScalartempLower | read-write | mandatory | Indicate temperature lower threshold |
| 1.3.6.1.4.1.17420.1.4.43 | ScalartempUpper | read-write | mandatory | Indicate temperature upper threshold |
| 1.3.6.1.4.1.17420.1.4.45 | ScalarhumidityLower | read-write | mandatory | Indicate humidity upper threshold |
| 1.3.6.1.4.1.17420.105 | NodedevOutOfThreshold1 | WARNING: DEV current out of threshold 1. | ||
| 1.3.6.1.4.1.17420.106 | NodedevOutOfThreshold2 | CRITICAL: DEV current out of threshold 2. | ||
| 1.3.6.1.4.1.17420.108 | NodedevBackToNormal | NORMAL: DEV back to normal states |