EATON-EPDU-MA-MIB

130 objects
The MIB module for Eaton ePDUs (Enclosed Power Distribution Units) -Managed Model.
Imported Objects
EATON-OIDSpduAgent
SNMPv2-CONFMODULE-COMPLIANCE NOTIFICATION-GROUP OBJECT-GROUP
SNMPv2-SMIInteger32 IpAddress MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE Unsigned32
SNMPv2-TCDisplayString MacAddress TEXTUAL-CONVENTION
OIDNameAccessStatusDescription
1.3.6.1.4.1.534.6.6.6IdentityeatonEpduMaThe MIB module for Eaton ePDUs (Enclosed Power Distribution Units) -Managed Model.
1.3.6.1.4.1.534.6.6.6.0Nodetraps
1.3.6.1.4.1.534.6.6.6.0.1NotificationrebootStartedcurrentThe reboot process has started
1.3.6.1.4.1.534.6.6.6.0.2NotificationrebootCompletedcurrentThe reboot process is complete
1.3.6.1.4.1.534.6.6.6.0.3NotificationuserLogincurrentA user logged in
1.3.6.1.4.1.534.6.6.6.0.4NotificationuserLogoutcurrentA user logged out
1.3.6.1.4.1.534.6.6.6.0.5NotificationuserAuthenticationFailurecurrentA user authentication attempt failed
1.3.6.1.4.1.534.6.6.6.0.8NotificationuserSessionTimeoutcurrentA user timed out from the device
1.3.6.1.4.1.534.6.6.6.0.11NotificationuserAddedcurrentA user was added to the system
1.3.6.1.4.1.534.6.6.6.0.12NotificationuserModifiedcurrentA user account was modified
1.3.6.1.4.1.534.6.6.6.0.13NotificationuserDeletedcurrentA user was deleted from the system
1.3.6.1.4.1.534.6.6.6.0.14NotificationgroupAddedcurrentA group was added to the system
1.3.6.1.4.1.534.6.6.6.0.15NotificationgroupModifiedcurrentA group was modified
1.3.6.1.4.1.534.6.6.6.0.16NotificationgroupDeletedcurrentA group was deleted from the system
1.3.6.1.4.1.534.6.6.6.0.20NotificationdeviceUpdateStartedcurrentThe device update has started
1.3.6.1.4.1.534.6.6.6.0.22NotificationuserBlockedcurrentA blocked user tried to log in
1.3.6.1.4.1.534.6.6.6.0.23NotificationpowerControlcurrentAn outlet has been switched
1.3.6.1.4.1.534.6.6.6.0.24NotificationuserPasswordChangedcurrentA user password was changed
1.3.6.1.4.1.534.6.6.6.0.28NotificationpasswordSettingsChangedcurrentStrong password settings changed
1.3.6.1.4.1.534.6.6.6.0.36NotificationfirmwareFileDiscardedcurrentA firmware file discarded
1.3.6.1.4.1.534.6.6.6.0.38NotificationfirmwareValidationFailedcurrentA firmware validation failed
1.3.6.1.4.1.534.6.6.6.0.39NotificationsecurityViolationcurrentSecurity violation.
1.3.6.1.4.1.534.6.6.6.0.41NotificationlogFileClearedcurrentThe log file has been cleared.
1.3.6.1.4.1.534.6.6.6.0.45NotificationthresholdAlarmcurrentConfigured sensor theshold event. The 'thresholdType' variable will indicate whether or not the threshold triggered or cleared
1.3.6.1.4.1.534.6.6.6.0.50NotificationoutletGroupingConnectivityLostcurrentMaster PDU lost contact with the slave PDU in an outlet grouping configuration.
1.3.6.1.4.1.534.6.6.6.1Nodeboard
1.3.6.1.4.1.534.6.6.6.1.1Nodeinfo
1.3.6.1.4.1.534.6.6.6.1.1.1ScalarfirmwareVersionread-onlycurrentThe current firmware version
1.3.6.1.4.1.534.6.6.6.1.1.2ScalarserialNumberread-onlycurrentThe serial number.
1.3.6.1.4.1.534.6.6.6.1.1.3ScalaripAddressread-onlycurrentThe current IP address. A value of 0.0.0.0 indicates an error or an unset option.
1.3.6.1.4.1.534.6.6.6.1.1.4Scalarnetmaskread-onlycurrentThe current Netmask. A value of 0.0.0.0 indicates an error or an unset option.
1.3.6.1.4.1.534.6.6.6.1.1.5Scalargatewayread-onlycurrentThe current Gateway. A value of 0.0.0.0 indicates an error or an unset option.
1.3.6.1.4.1.534.6.6.6.1.1.6Scalarmacread-onlycurrentThe current MAC address.
1.3.6.1.4.1.534.6.6.6.1.1.7ScalarhardwareRevread-onlycurrentThe hardware revision number.
1.3.6.1.4.1.534.6.6.6.1.1.10ScalaruserNameaccessible-for-notifycurrentThe login of a user.
1.3.6.1.4.1.534.6.6.6.1.1.12ScalarobjectNameaccessible-for-notifycurrentThe model type of the device
1.3.6.1.4.1.534.6.6.6.1.1.13ScalarobjectInstanceaccessible-for-notifycurrentThe device name
1.3.6.1.4.1.534.6.6.6.1.1.14ScalartargetUseraccessible-for-notifycurrentThe user record being operated on
1.3.6.1.4.1.534.6.6.6.1.1.15ScalargroupNameaccessible-for-notifycurrentThe group record being operated on
1.3.6.1.4.1.534.6.6.6.1.1.18ScalarimageVersionaccessible-for-notifycurrentThe version of the Upgrade image
1.3.6.1.4.1.534.6.6.6.1.1.19ScalarsensorDescraccessible-for-notifycurrentSensor description indicating which sensor experienced a threshold exceeded event. When applicable the description will indicate the sensor number.
1.3.6.1.4.1.534.6.6.6.1.1.20ScalarthresholdDescraccessible-for-notifycurrentThreshold description indicating which configured threshold has been triggered (or cleared).
1.3.6.1.4.1.534.6.6.6.1.1.21ScalarthresholdSeverityaccessible-for-notifycurrentString (Warning, Critical, etc...) indicating the severity of the threshold which has been triggered (or cleared).
1.3.6.1.4.1.534.6.6.6.1.1.22ScalarthresholdEventTypeaccessible-for-notifycurrentString (triggered, cleared) indicating if the threshold event indicates that a configured threshold has been triggered or cleared.
1.3.6.1.4.1.534.6.6.6.1.1.23Scalarstatusaccessible-for-notifycurrentThe success status of an operation
1.3.6.1.4.1.534.6.6.6.1.1.24ScalarslaveIpAddressread-onlycurrentIn a shepherding configuration, this is the IP address of slave PDU. A value of 0.0.0.0 indicates an error or an unset option.
1.3.6.1.4.1.534.6.6.6.1.2Nodeoutlets
1.3.6.1.4.1.534.6.6.6.1.2.1ScalaroutletCountread-onlycurrentThe number of outlets (regardless of their current state) present on this pdu.
1.3.6.1.4.1.534.6.6.6.1.2.2TableoutletTablenot-accessiblecurrentA list of outlet entries. The number of entries is given by the value of outletCount.
1.3.6.1.4.1.534.6.6.6.1.2.2.1RowoutletEntrynot-accessiblecurrentAn outlet entry containing objects at the for a particular outlet.
1.3.6.1.4.1.534.6.6.6.1.2.2.1.1ColumnoutletIndexnot-accessiblecurrentA unique value for each outlet. Its value ranges between 1 and the value of outletCount.
1.3.6.1.4.1.534.6.6.6.1.2.2.1.2ColumnoutletLabelread-writecurrentA textual string containing information about the outlet.
1.3.6.1.4.1.534.6.6.6.1.2.2.1.3ColumnoutletOperationalStateread-writecurrentA value for each outlet which describes the operational state of the outlet. It is also used to set the operational state of the outlet
1.3.6.1.4.1.534.6.6.6.1.2.2.1.4ColumnoutletCurrentread-onlycurrentA unique value for the current sensor attached to the outlet. This value is reported in milliamps (1/1000th of an amp)
1.3.6.1.4.1.534.6.6.6.1.2.2.1.5ColumnoutletMaxCurrentread-onlycurrentA unique value for the max. current sensor attached to the outlet. This value is reported in milliamps (1/1000th of an amp)
1.3.6.1.4.1.534.6.6.6.1.2.2.1.6ColumnoutletVoltageread-onlycurrentA unique value for the voltage sensor attached to the outlet.This value is reported in millivolts (1/1000th of a volt)
1.3.6.1.4.1.534.6.6.6.1.2.2.1.7ColumnoutletActivePowerread-onlycurrentA unique value for the active power sensor attached to the outlet. This value is reported in Watts.
1.3.6.1.4.1.534.6.6.6.1.2.2.1.8ColumnoutletApparentPowerread-onlycurrentA unique value for the apparent power sensor attached to the outlet. This value is reported in Volt-Amps
1.3.6.1.4.1.534.6.6.6.1.2.2.1.9ColumnoutletPowerFactorread-onlycurrentA unique value for the power factor of the outlet. The reading represents a percentage in the range of 0% to 100%.
1.3.6.1.4.1.534.6.6.6.1.2.2.1.21ColumnoutletCurrentUpperWarningread-writecurrentThe value of the upper warning (non-critical) current threshold for the outlet. This value is reported in milliamps (1/1000th of an amp)
1.3.6.1.4.1.534.6.6.6.1.2.2.1.23ColumnoutletCurrentUpperCriticalread-writecurrentThe value of the upper critical current threshold for the outlet. This value is reported in milliamps (1/1000th of an amp)
1.3.6.1.4.1.534.6.6.6.1.3Nodeunit
1.3.6.1.4.1.534.6.6.6.1.3.1NodeunitReadings
1.3.6.1.4.1.534.6.6.6.1.3.1.1ScalarunitCurrentread-onlycurrentThe value for the unit's current sensor in millamps.
1.3.6.1.4.1.534.6.6.6.1.3.1.2ScalarunitVoltageread-onlycurrentThe value for the unit's voltage sensor in millivolts.
1.3.6.1.4.1.534.6.6.6.1.3.1.3ScalarunitActivePowerread-onlycurrentThe value for the unit's voltage sensor in volt-amps.
1.3.6.1.4.1.534.6.6.6.1.3.1.4ScalarunitApparentPowerread-onlycurrentThe value for the unit's voltage sensor in volt-amps.
1.3.6.1.4.1.534.6.6.6.1.3.1.5ScalarunitCpuTempread-onlycurrentThe value for the unit's CPU temperature sensor in degrees Celsius.
1.3.6.1.4.1.534.6.6.6.1.3.1.20ScalarunitCircuitBreak0Stateread-onlycurrentThe value for the unit's circuit breaker state sensor 0.
1.3.6.1.4.1.534.6.6.6.1.3.1.21ScalarunitCircuitBreak1Stateread-onlycurrentThe value for the unit's circuit breaker state sensor 1.
1.3.6.1.4.1.534.6.6.6.1.3.1.22ScalarunitCircuitBreak2Stateread-onlycurrentThe value for the unit's circuit breaker state sensor 2.
1.3.6.1.4.1.534.6.6.6.1.3.1.40ScalarunitCircuitBreak0Currentread-onlycurrentThe value for the unit's circuit breaker current sensor 0.
1.3.6.1.4.1.534.6.6.6.1.3.1.41ScalarunitCircuitBreak1Currentread-onlycurrentThe value for the unit's circuit breaker current sensor 1.
1.3.6.1.4.1.534.6.6.6.1.3.1.42ScalarunitCircuitBreak2Currentread-onlycurrentThe value for the unit's circuit breaker current sensor 2.
1.3.6.1.4.1.534.6.6.6.1.3.1.60ScalarunitVoltageLowerWarningread-writecurrentThe value of the lower warning (non-critical) unit level voltage threshold.
1.3.6.1.4.1.534.6.6.6.1.3.1.61ScalarunitVoltageLowerCriticalread-writecurrentThe value of the lower critical unit level voltage threshold.
1.3.6.1.4.1.534.6.6.6.1.3.1.62ScalarunitVoltageUpperWarningread-writecurrentThe value of the upper warning (non-critical) unit level voltage threshold.
1.3.6.1.4.1.534.6.6.6.1.3.1.63ScalarunitVoltageUpperCriticalread-writecurrentThe value of the upper critical unit level voltage threshold.
1.3.6.1.4.1.534.6.6.6.1.3.1.70ScalarunitCurrentUpperWarningread-writecurrentThe value of the upper warning (non-critical) unit level current threshold.
1.3.6.1.4.1.534.6.6.6.1.3.1.71ScalarunitCurrentUpperCriticalread-onlycurrentThe value of the upper critical unit level current threshold. NOTE: This particular threshold is NOT settable
1.3.6.1.4.1.534.6.6.6.1.3.1.80ScalarunitTempLowerWarningread-writecurrentThe value of the lower warning (non-critical) unit level temperature threshold.
1.3.6.1.4.1.534.6.6.6.1.3.1.81ScalarunitTempLowerCriticalread-writecurrentThe value of the lower critical unit level temperature threshold.
1.3.6.1.4.1.534.6.6.6.1.3.1.82ScalarunitTempUpperWarningread-writecurrentThe value of the upper warning (non-critical) unit level temperature threshold.
1.3.6.1.4.1.534.6.6.6.1.3.1.83ScalarunitTempUpperCriticalread-writecurrentThe value of the upper critical unit level temperature threshold.
1.3.6.1.4.1.534.6.6.6.2Nodeenvironmental
1.3.6.1.4.1.534.6.6.6.2.1ScalartempSensorCountread-onlycurrentThe number of external temperature sensors (regardless of their current state) present on this pdu.
1.3.6.1.4.1.534.6.6.6.2.2TabletempSensorTablenot-accessiblecurrentA list of temperature sensor entries. The number of entries is given by the value of tempSensorCount.
1.3.6.1.4.1.534.6.6.6.2.2.1RowtempSensorEntrynot-accessiblecurrentAn entry containing sensor reading and threshold settings for a particular temperature sensor.
1.3.6.1.4.1.534.6.6.6.2.2.1.1ColumntempSensorIndexnot-accessiblecurrentA unique value for each temperature sensor. Its value ranges between 1 and tempSensorCount.
1.3.6.1.4.1.534.6.6.6.2.2.1.2ColumntempSensorLabelread-writecurrentA settable human-readable label for the external temperature sensor. One possible use for this label is to convey sensor location.
1.3.6.1.4.1.534.6.6.6.2.2.1.3Columntemperatureread-onlycurrentThe value of the external temperature sensor reported in degrees celsius.
1.3.6.1.4.1.534.6.6.6.2.2.1.4ColumntempLowerWarningread-writecurrentThe value of the lower warning (non-critical) threshold.
1.3.6.1.4.1.534.6.6.6.2.2.1.5ColumntempUpperWarningread-writecurrentThe value of the upper warning (non-critical) threshold.
1.3.6.1.4.1.534.6.6.6.2.2.1.6ColumntempLowerCriticalread-writecurrentThe value of the lower critical threshold.
1.3.6.1.4.1.534.6.6.6.2.2.1.7ColumntempUpperCriticalread-writecurrentThe value of the upper critical threshold.
1.3.6.1.4.1.534.6.6.6.2.2.1.8ColumntempLowerWarningResetread-writecurrentThe value of the lower warning (non-critical) reset/hysteresis value.
1.3.6.1.4.1.534.6.6.6.2.2.1.9ColumntempUpperWarningResetread-writecurrentThe value of the upper warning (non-critical) reset/hysteresis value.
1.3.6.1.4.1.534.6.6.6.2.2.1.10ColumntempLowerCriticalResetread-writecurrentThe value of the lower critical reset/hysteresis value.
1.3.6.1.4.1.534.6.6.6.2.2.1.11ColumntempUpperCriticalResetread-writecurrentThe value of the upper critical reset/hysteresis value.
1.3.6.1.4.1.534.6.6.6.2.3ScalarhumiditySensorCountread-onlycurrentThe number of external humidity sensors (regardless of their current state) present on this pdu.
1.3.6.1.4.1.534.6.6.6.2.4TablehumiditySensorTablenot-accessiblecurrentA list of humidity sensor entries. The number of entries is given by the value of humiditySensorCount.
1.3.6.1.4.1.534.6.6.6.2.4.1RowhumiditySensorEntrynot-accessiblecurrentAn entry containing sensor reading and threshold settings for a particular humidity sensor.
1.3.6.1.4.1.534.6.6.6.2.4.1.1ColumnhumiditySensorIndexnot-accessiblecurrentA unique value for each humidity sensor. Its value ranges between 1 and humiditySensorCount.
1.3.6.1.4.1.534.6.6.6.2.4.1.2ColumnhumiditySensorLabelread-writecurrentA settable human-readable label for the external humidity sensor. One possible use for this label is to convey sensor location.
1.3.6.1.4.1.534.6.6.6.2.4.1.3Columnhumidityread-onlycurrentThe value of the external humidity sensor reported as relative humidity (a percentage).
1.3.6.1.4.1.534.6.6.6.2.4.1.4ColumnhumidityLowerWarningread-writecurrentThe value of the lower warning (non-critical) threshold.
1.3.6.1.4.1.534.6.6.6.2.4.1.5ColumnhumidityUpperWarningread-writecurrentThe value of the upper warning (non-critical) threshold.
1.3.6.1.4.1.534.6.6.6.2.4.1.6ColumnhumidityLowerCriticalread-writecurrentThe value of the lower critical threshold.
1.3.6.1.4.1.534.6.6.6.2.4.1.7ColumnhumidityUpperCriticalread-writecurrentThe value of the upper critical threshold.
1.3.6.1.4.1.534.6.6.6.2.4.1.8ColumnhumidityLowerWarningResetread-writecurrentThe value of the lower warning (non-critical) reset/hysteresis value.
1.3.6.1.4.1.534.6.6.6.2.4.1.9ColumnhumidityUpperWarningResetread-writecurrentThe value of the upper warning (non-critical) reset/hysteresis value.
1.3.6.1.4.1.534.6.6.6.2.4.1.10ColumnhumidityLowerCriticalResetread-writecurrentThe value of the lower critical reset/hysteresis value.
1.3.6.1.4.1.534.6.6.6.2.4.1.11ColumnhumidityUpperCriticalResetread-writecurrentThe value of the upper critical reset/hysteresis value.
1.3.6.1.4.1.534.6.6.6.9Nodeconformance
1.3.6.1.4.1.534.6.6.6.9.1Nodecompliances
1.3.6.1.4.1.534.6.6.6.9.1.1CompliancecompliancecurrentThe requirements for conformance to the PDU-MIB.
1.3.6.1.4.1.534.6.6.6.9.2Nodegroups
1.3.6.1.4.1.534.6.6.6.9.2.1GroupinfoGroupcurrentA collection of objects providing basic information about the pdu.
1.3.6.1.4.1.534.6.6.6.9.2.2GroupoutletsGroupcurrentA collection of objects providing basic information about the outlets, including sensor readings.
1.3.6.1.4.1.534.6.6.6.9.2.4GroupunitSensorsGroupcurrentA collection of objects providing unit level sensor readings.
1.3.6.1.4.1.534.6.6.6.9.2.6GroupexternalTemperatureGroupcurrentA collection of objects providing external temperature sensor readings and threshold settings.
1.3.6.1.4.1.534.6.6.6.9.2.7GroupexternalHumidityGroupcurrentA collection of objects providing external humidity sensor readings and threshold settings.
1.3.6.1.4.1.534.6.6.6.9.2.9GrouptrapsGroupcurrentA collection of traps.
Type Definitions
NameSyntaxStatusDescription
DegreesCelsiusUnsigned32currentData type for reporting sensor readings and thresholds associated with temperature sensors. If the underlying hardware sensor indicates 1 degree Celsius, then the SNMP agent will report a value of 1 degree Celsius. No s…
MilliAmpsUnsigned32currentData type for reporting sensor readings and thresholds associated with current sensors. If the underlying hardware sensor indicates 1 amp, then the SNMP agent will report a value of 1000 milliamps. The value is scaled i…
MilliVoltsUnsigned32currentData type for reporting sensor readings and thresholds associated with voltage sensors. If the underlying hardware sensor indicates 1 volts, then the SNMP agent will report a value of 1000 millivolts. The value is scale…
PowerFactorPercentageUnsigned32 (0..100)currentData type for reporting sensor readings and thresholds associated with power factor sensors. The power factor of an AC power system is defined as the ratio of the real or active power to the apparent power and is a numb…
RelativeHumidityUnsigned32 (0..100)currentData type for reporting sensor readings and thresholds associated with humidity sensors. Relative humidity is expressed as percentage and is defined as the ratio of the partial pressure of water vapor in a gaseous mixtu…
VoltAmpsUnsigned32currentData type for reporting sensor readings and thresholds associated with apparent power sensors. If the underlying hardware sensor indicates 1 volt-amp, then the SNMP agent will report a value of 1 volt-amp. No scaling is…
WattsUnsigned32currentData type for reporting sensor readings and thresholds associated with active power sensors. If the underlying hardware sensor indicates 1 watt, then the SNMP agent will report a value of 1 watt. No scaling is performed…