EATON-EPDU-MIB
255 objects
The MIB module for Eaton ePDUs (Enclosure Power Distribution Units).
Imported Objects
| EATON-OIDS | pduAgent |
| SNMPv2-CONF | MODULE-COMPLIANCE NOTIFICATION-GROUP OBJECT-GROUP |
| SNMPv2-SMI | Counter32 enterprises Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE Unsigned32 |
| SNMPv2-TC | DateAndTime DisplayString TEXTUAL-CONVENTION |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.534 | Nodeeaton | |||
| 1.3.6.1.4.1.534.6 | Nodeproducts | |||
| 1.3.6.1.4.1.534.6.6 | NodepduAgent | |||
| 1.3.6.1.4.1.534.6.6.7 | IdentityeatonEpdu | The MIB module for Eaton ePDUs (Enclosure Power Distribution Units). | ||
| 1.3.6.1.4.1.534.6.6.7.0 | Nodenotifications | |||
| 1.3.6.1.4.1.534.6.6.7.0.1 | NotificationnotifyUserLogin | current | Sent whenever a user logs in. | |
| 1.3.6.1.4.1.534.6.6.7.0.2 | NotificationnotifyUserLogout | current | Sent whenever a user logs out. | |
| 1.3.6.1.4.1.534.6.6.7.0.3 | NotificationnotifyFailedLogin | current | Sent when someone attempts to log in and fails. On some models, may be sent after three failed login attempts. | |
| 1.3.6.1.4.1.534.6.6.7.0.4 | NotificationnotifyBootUp | current | Sent whenever an ePDU finishes booting up (hard or soft reboot). | |
| 1.3.6.1.4.1.534.6.6.7.0.11 | NotificationnotifyInputVoltageThStatus | current | Sent whenever an input voltage threshold status changes. | |
| 1.3.6.1.4.1.534.6.6.7.0.12 | NotificationnotifyInputCurrentThStatus | current | Sent whenever an input current threshold status changes. | |
| 1.3.6.1.4.1.534.6.6.7.0.13 | NotificationnotifyInputFrequencyStatus | current | Sent whenever the input frequency status changes. | |
| 1.3.6.1.4.1.534.6.6.7.0.21 | NotificationnotifyGroupVoltageThStatus | current | Sent whenever a group voltage threshold status changes. | |
| 1.3.6.1.4.1.534.6.6.7.0.22 | NotificationnotifyGroupCurrentThStatus | current | Sent whenever a group current threshold status changes. | |
| 1.3.6.1.4.1.534.6.6.7.0.23 | NotificationnotifyGroupBreakerStatus | current | Sent whenever a group status changes to indicate whether the circuit breaker is on or off. | |
| 1.3.6.1.4.1.534.6.6.7.0.31 | NotificationnotifyOutletVoltageThStatus | current | Sent whenever an outlet voltage threshold status changes. | |
| 1.3.6.1.4.1.534.6.6.7.0.32 | NotificationnotifyOutletCurrentThStatus | current | Sent whenever an outlet current threshold status changes. | |
| 1.3.6.1.4.1.534.6.6.7.0.33 | NotificationnotifyOutletControlStatus | current | Sent whenever an outlet state On / Off changes. | |
| 1.3.6.1.4.1.534.6.6.7.0.41 | NotificationnotifyTemperatureThStatus | current | Sent whenever a temperature threshold status changes. | |
| 1.3.6.1.4.1.534.6.6.7.0.42 | NotificationnotifyHumidityThStatus | current | Sent whenever a humidity threshold status changes. | |
| 1.3.6.1.4.1.534.6.6.7.0.43 | NotificationnotifyContactState | current | Sent whenever a contact sensor state changes. | |
| 1.3.6.1.4.1.534.6.6.7.0.44 | NotificationnotifyProbeStatus | current | Sent whenever the environment probe status changes. | |
| 1.3.6.1.4.1.534.6.6.7.0.51 | NotificationnotifyCommunicationStatus | current | Sent whenever the PDU communication status changes. | |
| 1.3.6.1.4.1.534.6.6.7.0.52 | NotificationnotifyInternalStatus | current | Sent whenever the PDU internal status changes. | |
| 1.3.6.1.4.1.534.6.6.7.0.53 | NotificationnotifyTest | current | Sent whenever the trap test feature is used by the communication card. | |
| 1.3.6.1.4.1.534.6.6.7.0.54 | NotificationnotifyStrappingStatus | current | Sent whenever the strapping communication status changes. | |
| 1.3.6.1.4.1.534.6.6.7.1 | Nodeunits | |||
| 1.3.6.1.4.1.534.6.6.7.1.1 | ScalarunitsPresent | read-only | current | Each unit is identified by a Strapping Index. This object returns a comma-delimited list of the Strapping Indexes of all units present in the strapping group. … |
| 1.3.6.1.4.1.534.6.6.7.1.2 | TableunitTable | not-accessible | current | A list of units. In most cases this list will only contain one entry. However, some units have a 'strapping' feature which allow units to be daisy-chained toge… |
| 1.3.6.1.4.1.534.6.6.7.1.2.1 | RowunitEntry | not-accessible | current | An entry for a PDU. |
| 1.3.6.1.4.1.534.6.6.7.1.2.1.1 | ColumnstrappingIndex | accessible-for-notify | current | For units that support 'strapping' functionality, this will be a unique value for each unit. If units do not support 'strapping', this will always be '0'. |
| 1.3.6.1.4.1.534.6.6.7.1.2.1.2 | ColumnproductName | read-only | current | Name of the product. |
| 1.3.6.1.4.1.534.6.6.7.1.2.1.3 | ColumnpartNumber | read-only | current | Part number of the unit. |
| 1.3.6.1.4.1.534.6.6.7.1.2.1.4 | ColumnserialNumber | read-only | current | Serial number of the unit. |
| 1.3.6.1.4.1.534.6.6.7.1.2.1.5 | ColumnfirmwareVersion | read-only | current | Firmware version. |
| 1.3.6.1.4.1.534.6.6.7.1.2.1.6 | ColumnunitName | read-write | current | Descriptive name for the unit. |
| 1.3.6.1.4.1.534.6.6.7.1.2.1.7 | ColumnlcdControl | read-write | current | Control the local LCD. |
| 1.3.6.1.4.1.534.6.6.7.1.2.1.8 | ColumnclockValue | read-write | current | Clock value. This could be from either a real-time clock (in which case it is likely writeable) or from a time server via NTP (probably read-only). |
| 1.3.6.1.4.1.534.6.6.7.1.2.1.9 | ColumntemperatureScale | read-write | current | Scale used to return temperature objects. |
| 1.3.6.1.4.1.534.6.6.7.1.2.1.10 | ColumnunitType | read-only | current | Technical capabilities of the PDU. Functionality is as follows: Monitored (MI) - input and usually section/group monitoring. Advanced Monitored (AM) - input, s… |
| 1.3.6.1.4.1.534.6.6.7.1.2.1.11 | ColumnsystemType | read-only | current | Architecture of the ePDU electronic. |
| 1.3.6.1.4.1.534.6.6.7.1.2.1.20 | ColumninputCount | read-only | current | Number of inputs on this ePDU. |
| 1.3.6.1.4.1.534.6.6.7.1.2.1.21 | ColumngroupCount | read-only | current | Number of groups on this ePDU. Groups include breakers, outlet sections, and user-defined groups. |
| 1.3.6.1.4.1.534.6.6.7.1.2.1.22 | ColumnoutletCount | read-only | current | Number of outlets on this ePDU. |
| 1.3.6.1.4.1.534.6.6.7.1.2.1.23 | ColumntemperatureCount | read-only | current | Max number of temperature measurements on this ePDU. |
| 1.3.6.1.4.1.534.6.6.7.1.2.1.24 | ColumnhumidityCount | read-only | current | Max number of humidity measurements on this ePDU. |
| 1.3.6.1.4.1.534.6.6.7.1.2.1.25 | ColumncontactCount | read-only | current | Max number of contact sensors on this ePDU. |
| 1.3.6.1.4.1.534.6.6.7.1.2.1.30 | ColumncommunicationStatus | read-only | current | Status of the internal communication with the PDU. |
| 1.3.6.1.4.1.534.6.6.7.1.2.1.31 | ColumninternalStatus | read-only | current | Status of the internal failure inside the PDU. |
| 1.3.6.1.4.1.534.6.6.7.1.2.1.32 | ColumnstrappingStatus | read-only | current | Status of the external communication with a strapping unit. |
| 1.3.6.1.4.1.534.6.6.7.1.2.1.40 | ColumnuserName | accessible-for-notify | current | Username used to log into the PDU. |
| 1.3.6.1.4.1.534.6.6.7.1.2.1.41 | ColumncommInterface | accessible-for-notify | current | Communications interface used to log into the PDU. |
| 1.3.6.1.4.1.534.6.6.7.1.3 | TableunitControlTable | not-accessible | current | A list of units that have controllable outlets. |
| 1.3.6.1.4.1.534.6.6.7.1.3.1 | RowunitControlEntry | not-accessible | current | An entry for a PDU which has controllable outlets. |
| 1.3.6.1.4.1.534.6.6.7.1.3.1.2 | ColumnunitControlOffCmd | read-write | current | Unit-level outlet control command. Once the command is issued, outlets will turn Off. 0-n : Time in seconds until the outlet Sequence Off command is issued -1 … |
| 1.3.6.1.4.1.534.6.6.7.1.3.1.3 | ColumnunitControlOnCmd | read-write | current | Unit-level outlet control command. Once the command is issued, outlets will turn On according to their outletControlSequenceDelay value. 0-n : Time in seconds … |
| 1.3.6.1.4.1.534.6.6.7.3 | Nodeinputs | |||
| 1.3.6.1.4.1.534.6.6.7.3.1 | TableinputTable | not-accessible | current | List of inputs to the PDU. |
| 1.3.6.1.4.1.534.6.6.7.3.1.1 | RowinputEntry | not-accessible | current | An entry for a particular input. |
| 1.3.6.1.4.1.534.6.6.7.3.1.1.1 | ColumninputIndex | accessible-for-notify | current | A unique value for each input. Its value ranges from 1 to inputCount. |
| 1.3.6.1.4.1.534.6.6.7.3.1.1.2 | ColumninputType | read-only | current | Type of input - single phase, split phase, three phase delta, or three phase wye. |
| 1.3.6.1.4.1.534.6.6.7.3.1.1.3 | ColumninputFrequency | read-only | current | Units are 0.1 Hz; divide by ten to get Hz. |
| 1.3.6.1.4.1.534.6.6.7.3.1.1.4 | ColumninputFrequencyStatus | read-only | current | Status of the measured input frequency relative to the nominal frequency and the admitted tolerance. |
| 1.3.6.1.4.1.534.6.6.7.3.1.1.5 | ColumninputVoltageCount | read-only | current | Number of input voltage measurements on this ePDU. |
| 1.3.6.1.4.1.534.6.6.7.3.1.1.6 | ColumninputCurrentCount | read-only | current | Number of input current measurements on this ePDU. |
| 1.3.6.1.4.1.534.6.6.7.3.1.1.7 | ColumninputPowerCount | read-only | current | Number of rows in the inputPowerTable. |
| 1.3.6.1.4.1.534.6.6.7.3.1.1.8 | ColumninputPlugType | read-only | current | Identifies which plug is on the input. |
| 1.3.6.1.4.1.534.6.6.7.3.1.1.9 | ColumninputFeedColor | read-write | current | Color code of the input feed. |
| 1.3.6.1.4.1.534.6.6.7.3.1.1.10 | ColumninputFeedName | read-write | current | A descriptive name for the input. |
| 1.3.6.1.4.1.534.6.6.7.3.2 | TableinputVoltageTable | not-accessible | current | A list of input voltage measurements. The number of entries is given by inputVoltageCount. |
| 1.3.6.1.4.1.534.6.6.7.3.2.1 | RowinputVoltageEntry | not-accessible | current | An entry for a particular input voltage measurement. |
| 1.3.6.1.4.1.534.6.6.7.3.2.1.1 | ColumninputVoltageIndex | accessible-for-notify | current | A unique value for each input voltage measurement. Its value ranges from 1 to inputVoltageCount. |
| 1.3.6.1.4.1.534.6.6.7.3.2.1.2 | ColumninputVoltageMeasType | read-only | current | Value indicates what input voltage is being measured in this table row - single phase voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phas… |
| 1.3.6.1.4.1.534.6.6.7.3.2.1.3 | ColumninputVoltage | read-only | current | An input voltage measurement value. Units are millivolts. |
| 1.3.6.1.4.1.534.6.6.7.3.2.1.4 | ColumninputVoltageThStatus | read-only | current | Status of the measured input voltage relative to the configured thresholds. |
| 1.3.6.1.4.1.534.6.6.7.3.2.1.5 | ColumninputVoltageThLowerWarning | read-write | current | Lower warning threshold. Units are millivolts. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.3.2.1.6 | ColumninputVoltageThLowerCritical | read-write | current | Lower critical threshold. Units are millivolts. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.3.2.1.7 | ColumninputVoltageThUpperWarning | read-write | current | Upper warning threshold. Units are millivolts. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.3.2.1.8 | ColumninputVoltageThUpperCritical | read-write | current | Upper critical threshold. Units are millivolts. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.3.3 | TableinputCurrentTable | not-accessible | current | A list of input current measurements. The number of entries is given by inputCurrentCount. |
| 1.3.6.1.4.1.534.6.6.7.3.3.1 | RowinputCurrentEntry | not-accessible | current | An entry for a particular input current measurement. |
| 1.3.6.1.4.1.534.6.6.7.3.3.1.1 | ColumninputCurrentIndex | accessible-for-notify | current | A unique value for each input current measurement. Its value ranges from 1 to inputCurrentCount. |
| 1.3.6.1.4.1.534.6.6.7.3.3.1.2 | ColumninputCurrentMeasType | read-only | current | Which input wire is being measured in this table row - single phase, neutral, phase 1, phase 2, or phase 3. |
| 1.3.6.1.4.1.534.6.6.7.3.3.1.3 | ColumninputCurrentCapacity | read-only | current | Rated current capacity of the input. A negative value indicates that the hardware current capacity is unknown. Units are milliamps. |
| 1.3.6.1.4.1.534.6.6.7.3.3.1.4 | ColumninputCurrent | read-only | current | An input current measurement value. Units are milliamps. |
| 1.3.6.1.4.1.534.6.6.7.3.3.1.5 | ColumninputCurrentThStatus | read-only | current | Status of the measured input current relative to the configured thresholds. |
| 1.3.6.1.4.1.534.6.6.7.3.3.1.6 | ColumninputCurrentThLowerWarning | read-write | current | Lower warning threshold. Units are milliamps. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.3.3.1.7 | ColumninputCurrentThLowerCritical | read-write | current | Lower critical threshold. Units are milliamps. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.3.3.1.8 | ColumninputCurrentThUpperWarning | read-write | current | Upper warning threshold. Units are milliamps. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.3.3.1.9 | ColumninputCurrentThUpperCritical | read-write | current | Upper critical threshold. Units are milliamps. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.3.3.1.10 | ColumninputCurrentCrestFactor | read-only | current | Current crest factor. Units are in milli, for example a crest factor of 1.414 will be returned as 1414. A negative value indicates that this object is not avai… |
| 1.3.6.1.4.1.534.6.6.7.3.3.1.11 | ColumninputCurrentPercentLoad | read-only | current | Current percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this o… |
| 1.3.6.1.4.1.534.6.6.7.3.3.1.12 | ColumninputPhaseDesignator | read-only | current | Alphanumeric physical name for the input. |
| 1.3.6.1.4.1.534.6.6.7.3.4 | TableinputPowerTable | not-accessible | current | A list of input power measurements. The number of entries is given by inputPowerCount. |
| 1.3.6.1.4.1.534.6.6.7.3.4.1 | RowinputPowerEntry | not-accessible | current | An entry for an input power measurement. |
| 1.3.6.1.4.1.534.6.6.7.3.4.1.1 | ColumninputPowerIndex | not-accessible | current | A unique value for each input power measurement. Its value ranges from 1 to inputPowerCount. |
| 1.3.6.1.4.1.534.6.6.7.3.4.1.2 | ColumninputPowerMeasType | read-only | current | Value indicates what is being measured in this table row. |
| 1.3.6.1.4.1.534.6.6.7.3.4.1.3 | ColumninputVA | read-only | current | An input VA value. Units are VA. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.3.4.1.4 | ColumninputWatts | read-only | current | An input Watts value. Units are Watts. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.3.4.1.5 | ColumninputWh | read-write | current | Units are Watt-hours. This object is writable so that it can be reset to 0. When it is written to, the inputWhTimer will be reset updated as well. |
| 1.3.6.1.4.1.534.6.6.7.3.4.1.6 | ColumninputWhTimer | read-only | current | Timestamp of when input Watt-hours (inputWh) was last reset. |
| 1.3.6.1.4.1.534.6.6.7.3.4.1.7 | ColumninputPowerFactor | read-only | current | An input PF value. Units are in thousandths, for example a power factor of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value … |
| 1.3.6.1.4.1.534.6.6.7.3.4.1.8 | ColumninputVAR | read-only | current | An input VAR value. Units are VAR. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.3.5 | TableinputTotalPowerTable | not-accessible | current | A list of total input power measurements. |
| 1.3.6.1.4.1.534.6.6.7.3.5.1 | RowinputTotalPowerEntry | not-accessible | current | An entry for a total input power measurement. |
| 1.3.6.1.4.1.534.6.6.7.3.5.1.3 | ColumninputTotalVA | read-only | current | An input VA value. Units are VA. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.3.5.1.4 | ColumninputTotalWatts | read-only | current | An input Watts value. Units are Watts. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.3.5.1.5 | ColumninputTotalWh | read-write | current | Units are Watt-hours. This object is writable so that it can be reset to 0. When it is written to, the inputWhTimer will be reset updated as well. |
| 1.3.6.1.4.1.534.6.6.7.3.5.1.6 | ColumninputTotalWhTimer | read-only | current | Timestamp of when input Watt-hours (inputWh) was last reset. |
| 1.3.6.1.4.1.534.6.6.7.3.5.1.7 | ColumninputTotalPowerFactor | read-only | current | An input PF value. Units are in thousandths, for example a power factor of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value … |
| 1.3.6.1.4.1.534.6.6.7.3.5.1.8 | ColumninputTotalVAR | read-only | current | An input VAR value. Units are VAR. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.3.5.1.9 | ColumninputPowerCapacity | read-only | current | Typical power capacity of the input. A negative value indicates that the hardware current capacity is unknown. |
| 1.3.6.1.4.1.534.6.6.7.5 | Nodegroups | |||
| 1.3.6.1.4.1.534.6.6.7.5.1 | TablegroupTable | not-accessible | current | A list of groups. The number of entries is given by groupCount. |
| 1.3.6.1.4.1.534.6.6.7.5.1.1 | RowgroupEntry | not-accessible | current | An entry for a particular group. |
| 1.3.6.1.4.1.534.6.6.7.5.1.1.1 | ColumngroupIndex | accessible-for-notify | current | A unique value for each group. Its value ranges from 1 to groupCount. |
| 1.3.6.1.4.1.534.6.6.7.5.1.1.2 | ColumngroupID | read-only | current | Alphanumeric designator for the group. This value may be written on the face of the unit. |
| 1.3.6.1.4.1.534.6.6.7.5.1.1.3 | ColumngroupName | read-write | current | A descriptive name for the group. |
| 1.3.6.1.4.1.534.6.6.7.5.1.1.4 | ColumngroupType | read-only | current | The type of the group. |
| 1.3.6.1.4.1.534.6.6.7.5.1.1.5 | ColumngroupBreakerStatus | read-only | current | Only applicable to breaker-groups. Indicates whether a breaker is turned off or on. |
| 1.3.6.1.4.1.534.6.6.7.5.1.1.6 | ColumngroupChildCount | read-only | current | Number of children for this group. |
| 1.3.6.1.4.1.534.6.6.7.5.1.1.7 | ColumngroupColor | read-only | current | Background color code of the group. Color codes are decimal values. |
| 1.3.6.1.4.1.534.6.6.7.5.1.1.8 | ColumngroupDesignator | read-only | current | Alphanumeric physical name for the group. This value may be written on the face of the unit. |
| 1.3.6.1.4.1.534.6.6.7.5.1.1.9 | ColumngroupInputIndex | read-only | current | Identifies the input on which the group is connected. |
| 1.3.6.1.4.1.534.6.6.7.5.2 | TablegroupChildTable | not-accessible | current | A list of children for this group. For example, this table will link to all of the outlets that are contained in a particular group. |
| 1.3.6.1.4.1.534.6.6.7.5.2.1 | RowgroupChildEntry | not-accessible | current | An entry for a particular child. |
| 1.3.6.1.4.1.534.6.6.7.5.2.1.1 | ColumngroupChildIndex | not-accessible | current | A unique value for each child. Its value ranges from 1 to groupChildCount. |
| 1.3.6.1.4.1.534.6.6.7.5.2.1.2 | ColumngroupChildType | read-only | current | The type of the child. |
| 1.3.6.1.4.1.534.6.6.7.5.2.1.3 | ColumngroupChildOID | read-only | current | Object ID of a child object. |
| 1.3.6.1.4.1.534.6.6.7.5.3 | TablegroupVoltageTable | not-accessible | current | A list of group voltage measurements. There can be only one voltage measurement for each group. |
| 1.3.6.1.4.1.534.6.6.7.5.3.1 | RowgroupVoltageEntry | not-accessible | current | An entry for a group voltage measurement. |
| 1.3.6.1.4.1.534.6.6.7.5.3.1.2 | ColumngroupVoltageMeasType | read-only | current | Value indicates what voltage is being measured in this table row. |
| 1.3.6.1.4.1.534.6.6.7.5.3.1.3 | ColumngroupVoltage | read-only | current | Units are millivolts. |
| 1.3.6.1.4.1.534.6.6.7.5.3.1.4 | ColumngroupVoltageThStatus | read-only | current | Status of the measured group voltage relative to the configured thresholds. |
| 1.3.6.1.4.1.534.6.6.7.5.3.1.5 | ColumngroupVoltageThLowerWarning | read-write | current | Lower warning threshold. Units are millivolts. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.5.3.1.6 | ColumngroupVoltageThLowerCritical | read-write | current | Lower critical threshold. Units are millivolts. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.5.3.1.7 | ColumngroupVoltageThUpperWarning | read-write | current | Upper warning threshold. Units are millivolts. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.5.3.1.8 | ColumngroupVoltageThUpperCritical | read-write | current | Upper critical threshold. Units are millivolts. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.5.4 | TablegroupCurrentTable | not-accessible | current | A list of group current measurements. There can be only one current measurement for each group. |
| 1.3.6.1.4.1.534.6.6.7.5.4.1 | RowgroupCurrentEntry | not-accessible | current | An entry for a group current measurement. |
| 1.3.6.1.4.1.534.6.6.7.5.4.1.2 | ColumngroupCurrentCapacity | read-only | current | Rated current capacity of the group. Units are milliamps. A negative value indicates that the hardware current capacity is unknown (it will always be unknown f… |
| 1.3.6.1.4.1.534.6.6.7.5.4.1.3 | ColumngroupCurrent | read-only | current | A group current measurement value. Units are milliamps. |
| 1.3.6.1.4.1.534.6.6.7.5.4.1.4 | ColumngroupCurrentThStatus | read-only | current | Status of the measured group current relative to the configured thresholds. |
| 1.3.6.1.4.1.534.6.6.7.5.4.1.5 | ColumngroupCurrentThLowerWarning | read-write | current | Lower warning threshold. Units are milliamps. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.5.4.1.6 | ColumngroupCurrentThLowerCritical | read-write | current | Lower critical threshold. Units are milliamps. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.5.4.1.7 | ColumngroupCurrentThUpperWarning | read-write | current | Upper warning threshold. Units are milliamps. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.5.4.1.8 | ColumngroupCurrentThUpperCritical | read-write | current | Upper critical threshold. Units are milliamps. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.5.4.1.9 | ColumngroupCurrentCrestFactor | read-only | current | Current crest factor. Units are in milli, for example a crest factor of 1.414 will be returned as 1414. A negative value indicates that this object is not avai… |
| 1.3.6.1.4.1.534.6.6.7.5.4.1.10 | ColumngroupCurrentPercentLoad | read-only | current | Current percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this o… |
| 1.3.6.1.4.1.534.6.6.7.5.5 | TablegroupPowerTable | not-accessible | current | A list of group power measurements. There can be only one power measurement for each group. |
| 1.3.6.1.4.1.534.6.6.7.5.5.1 | RowgroupPowerEntry | not-accessible | current | An entry for a group power measurement. |
| 1.3.6.1.4.1.534.6.6.7.5.5.1.2 | ColumngroupVA | read-only | current | A group VA value. Units are VA. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.5.5.1.3 | ColumngroupWatts | read-only | current | A group Watts value. Units are Watts. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.5.5.1.4 | ColumngroupWh | read-write | current | Units are Watt-hours. This object is writable so that it can be reset to 0. When it is written to, the inputWhTotalTimer will be reset to 0 as well. |
| 1.3.6.1.4.1.534.6.6.7.5.5.1.5 | ColumngroupWhTimer | read-only | current | Timestamp of when group Watt-hours (groupWh) was last reset. |
| 1.3.6.1.4.1.534.6.6.7.5.5.1.6 | ColumngroupPowerFactor | read-only | current | A group PF value. Units are in thousandths, for example a power factor of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value i… |
| 1.3.6.1.4.1.534.6.6.7.5.5.1.7 | ColumngroupVAR | read-only | current | A group VAR value. Units are VAR. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.5.6 | TablegroupControlTable | not-accessible | current | A list of controllable groups. |
| 1.3.6.1.4.1.534.6.6.7.5.6.1 | RowgroupControlEntry | not-accessible | current | An entry for a controllable group. |
| 1.3.6.1.4.1.534.6.6.7.5.6.1.2 | ColumngroupControlStatus | read-only | current | Current state of a controlled group. A value of 'mixed' means that that the outlets within the group have differing states. |
| 1.3.6.1.4.1.534.6.6.7.5.6.1.3 | ColumngroupControlOffCmd | read-write | current | Group-level outlet control command. Once the command is issued, the outlets in the group will turn Off immediately. 0-n : Time in seconds until the group comma… |
| 1.3.6.1.4.1.534.6.6.7.5.6.1.4 | ColumngroupControlOnCmd | read-write | current | Group-level outlet control command. Once the command is issued, the outlets in the group will turn On immediately. 0-n : Time in seconds until the group comman… |
| 1.3.6.1.4.1.534.6.6.7.5.6.1.5 | ColumngroupControlRebootCmd | read-write | current | Group-level outlet control command. For outlets that are On prior to the Reboot command, they will switch Off immediately when the command is issued, remain Of… |
| 1.3.6.1.4.1.534.6.6.7.6 | Nodeoutlets | |||
| 1.3.6.1.4.1.534.6.6.7.6.1 | TableoutletTable | not-accessible | current | A list of outlets. The number of entries is given by outletCount. |
| 1.3.6.1.4.1.534.6.6.7.6.1.1 | RowoutletEntry | not-accessible | current | An entry for a particular outlet. |
| 1.3.6.1.4.1.534.6.6.7.6.1.1.1 | ColumnoutletIndex | accessible-for-notify | current | A unique value for each outlet. its value ranges from 1 to outletCount. |
| 1.3.6.1.4.1.534.6.6.7.6.1.1.2 | ColumnoutletID | read-only | current | Alphanumeric designator for the outlet. |
| 1.3.6.1.4.1.534.6.6.7.6.1.1.3 | ColumnoutletName | read-write | current | A descriptive name for the outlet. |
| 1.3.6.1.4.1.534.6.6.7.6.1.1.4 | ColumnoutletParentCount | read-only | current | Number of parents for this outlet. |
| 1.3.6.1.4.1.534.6.6.7.6.1.1.5 | ColumnoutletType | read-only | current | The physical type of outlet. |
| 1.3.6.1.4.1.534.6.6.7.6.1.1.6 | ColumnoutletDesignator | read-only | current | Alphanumeric physical name for the outlet. |
| 1.3.6.1.4.1.534.6.6.7.6.1.1.7 | ColumnoutletPhaseID | read-only | current | Value indicates which phases are connected to each outlet in this table row - single phase voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral,… |
| 1.3.6.1.4.1.534.6.6.7.6.2 | TableoutletParentTable | not-accessible | current | A list of parents for this outlet. For example, this table will link to all of the groups that have this outlet as a child. |
| 1.3.6.1.4.1.534.6.6.7.6.2.1 | RowoutletParentEntry | not-accessible | current | An entry for a particular parent. |
| 1.3.6.1.4.1.534.6.6.7.6.2.1.1 | ColumnoutletParentIndex | not-accessible | current | A unique value for each parent. Its value ranges from 1 to outletParentCount. |
| 1.3.6.1.4.1.534.6.6.7.6.2.1.2 | ColumnoutletParentType | read-only | current | The type of the parent. |
| 1.3.6.1.4.1.534.6.6.7.6.2.1.3 | ColumnoutletParentOID | read-only | current | Object ID of a parent object. |
| 1.3.6.1.4.1.534.6.6.7.6.3 | TableoutletVoltageTable | not-accessible | current | A list of outlet voltage measurements. |
| 1.3.6.1.4.1.534.6.6.7.6.3.1 | RowoutletVoltageEntry | not-accessible | current | An entry for an outlet voltage measurement. |
| 1.3.6.1.4.1.534.6.6.7.6.3.1.2 | ColumnoutletVoltage | read-only | current | Units are millivolts. |
| 1.3.6.1.4.1.534.6.6.7.6.3.1.3 | ColumnoutletVoltageThStatus | read-only | current | Status of the measured outlet voltage relative to the configured thresholds. |
| 1.3.6.1.4.1.534.6.6.7.6.3.1.4 | ColumnoutletVoltageThLowerWarning | read-write | current | Lower warning threshold. Units are millivolts. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.6.3.1.5 | ColumnoutletVoltageThLowerCritical | read-write | current | Lower critical threshold. Units are millivolts. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.6.3.1.6 | ColumnoutletVoltageThUpperWarning | read-write | current | Upper warning threshold. Units are millivolts. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.6.3.1.7 | ColumnoutletVoltageThUpperCritical | read-write | current | Upper critical threshold. Units are millivolts. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.6.4 | TableoutletCurrentTable | not-accessible | current | A list of outlet current measurements. |
| 1.3.6.1.4.1.534.6.6.7.6.4.1 | RowoutletCurrentEntry | not-accessible | current | An entry for an outlet current measurement. |
| 1.3.6.1.4.1.534.6.6.7.6.4.1.2 | ColumnoutletCurrentCapacity | read-only | current | Rated current capacity of the outlet. Units are milliamps. A negative value indicates that the hardware current capacity is unknown. |
| 1.3.6.1.4.1.534.6.6.7.6.4.1.3 | ColumnoutletCurrent | read-only | current | An outlet current measurement value. Units are milliamps. |
| 1.3.6.1.4.1.534.6.6.7.6.4.1.4 | ColumnoutletCurrentThStatus | read-only | current | Status of the measured outlet current relative to the configured thresholds. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.6.4.1.5 | ColumnoutletCurrentThLowerWarning | read-write | current | Lower warning threshold. Units are milliamps. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.6.4.1.6 | ColumnoutletCurrentThLowerCritical | read-write | current | Lower critical threshold. Units are milliamps. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.6.4.1.7 | ColumnoutletCurrentThUpperWarning | read-write | current | Upper warning threshold. Units are milliamps. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.6.4.1.8 | ColumnoutletCurrentThUpperCritical | read-write | current | Upper critical threshold. Units are milliamps. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.6.4.1.9 | ColumnoutletCurrentCrestFactor | read-only | current | Current crest factor. Units are in milli, for example a crest factor of 1.414 will be returned as 1414. A negative value indicates that this object is not avai… |
| 1.3.6.1.4.1.534.6.6.7.6.4.1.10 | ColumnoutletCurrentPercentLoad | read-only | current | Current percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this o… |
| 1.3.6.1.4.1.534.6.6.7.6.5 | TableoutletPowerTable | not-accessible | current | A list of outlet power measurements. |
| 1.3.6.1.4.1.534.6.6.7.6.5.1 | RowoutletPowerEntry | not-accessible | current | An entry for an outlet power measurement. |
| 1.3.6.1.4.1.534.6.6.7.6.5.1.2 | ColumnoutletVA | read-only | current | An outlet VA value. Units are VA. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.6.5.1.3 | ColumnoutletWatts | read-only | current | An outlet Watts value. Units are Watts. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.6.5.1.4 | ColumnoutletWh | read-write | current | Units are Watt-hours. This object is writable so that it can be reset to 0. When it is written to, the inputWhTotalTimer will be reset to 0 as well. |
| 1.3.6.1.4.1.534.6.6.7.6.5.1.5 | ColumnoutletWhTimer | read-only | current | Timestamp of when outlet Watt-hours (outletWh) was last reset. |
| 1.3.6.1.4.1.534.6.6.7.6.5.1.6 | ColumnoutletPowerFactor | read-only | current | An outlet PF value. Units are in thousandths, for example a power factor of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value… |
| 1.3.6.1.4.1.534.6.6.7.6.5.1.7 | ColumnoutletVAR | read-only | current | An outlet VAR value. Units are VAR. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.6.6 | TableoutletControlTable | not-accessible | current | A list of controllable outlets. |
| 1.3.6.1.4.1.534.6.6.7.6.6.1 | RowoutletControlEntry | not-accessible | current | An entry for a controllable outlet. |
| 1.3.6.1.4.1.534.6.6.7.6.6.1.2 | ColumnoutletControlStatus | read-only | current | Current state of a controlled outlet. |
| 1.3.6.1.4.1.534.6.6.7.6.6.1.3 | ColumnoutletControlOffCmd | read-write | current | Outlet control command. Once the command is issued, the outlet will turn Off immediately. 0-n : Time in seconds until the outlet command is issued -1 : Cancel … |
| 1.3.6.1.4.1.534.6.6.7.6.6.1.4 | ColumnoutletControlOnCmd | read-write | current | Outlet control command. Once the command is issued, the outlet will turn On immediately. 0-n : Time in seconds until the outlet command is issued -1 : Cancel a… |
| 1.3.6.1.4.1.534.6.6.7.6.6.1.5 | ColumnoutletControlRebootCmd | read-write | current | Outlet control command. For outlets that are On prior to this Reboot command, they will switch Off immediately when the command is issued, remain Off for outle… |
| 1.3.6.1.4.1.534.6.6.7.6.6.1.6 | ColumnoutletControlPowerOnState | read-write | current | Determines the outlet state when power is applied to the unit. 0 : not restart at device startup 1 : should sequence back ON in line with outletControlSequence… |
| 1.3.6.1.4.1.534.6.6.7.6.6.1.7 | ColumnoutletControlSequenceDelay | read-write | current | Time delay in seconds from when a Global Sequence On command is issued to when the command is executed on this outlet. This delay is also used as a power-on de… |
| 1.3.6.1.4.1.534.6.6.7.6.6.1.8 | ColumnoutletControlRebootOffTime | read-write | current | Time delay in seconds that the outlet should remain in the Off state when executing a Reboot command. |
| 1.3.6.1.4.1.534.6.6.7.6.6.1.9 | ColumnoutletControlSwitchable | read-write | current | Determines the outlet capability to be controlled On/Off from the communication channels. 1 : control On/Off enabled 2 : control On/Off disabled. |
| 1.3.6.1.4.1.534.6.6.7.6.6.1.10 | ColumnoutletControlShutoffDelay | read-write | current | Time delay in seconds that could be taken in account before shutting of the outlet. An application which need to shutoff properly an outlet will read this para… |
| 1.3.6.1.4.1.534.6.6.7.6.7 | TableoutletGlobalTable | not-accessible | current | A list of globlal configuration on all outlets. |
| 1.3.6.1.4.1.534.6.6.7.6.7.1 | RowoutletGlobalEntry | not-accessible | current | An entry for a global variable on all outlets. |
| 1.3.6.1.4.1.534.6.6.7.6.7.1.2 | ColumnoutletAutomaticShutoff | read-write | current | Determines the state of all outlets when the unit is power off: 0 : not applicable (read only) 1 : Keep the outlet relays in the current position when the PDU … |
| 1.3.6.1.4.1.534.6.6.7.7 | Nodeenvironmental | |||
| 1.3.6.1.4.1.534.6.6.7.7.1 | TabletemperatureTable | not-accessible | current | A list of temperature probe measurements. The number of entries is given by temperatureCount. |
| 1.3.6.1.4.1.534.6.6.7.7.1.1 | RowtemperatureEntry | not-accessible | current | An entry for a temperature measurement. |
| 1.3.6.1.4.1.534.6.6.7.7.1.1.1 | ColumntemperatureIndex | accessible-for-notify | current | A unique value for each temperature probe measurement. Its value ranges from 1 to temperatureCount. |
| 1.3.6.1.4.1.534.6.6.7.7.1.1.2 | ColumntemperatureName | read-write | current | A descriptive name for the temperature probe. |
| 1.3.6.1.4.1.534.6.6.7.7.1.1.3 | ColumntemperatureProbeStatus | read-only | current | Indicates whether a probe is connected or not. |
| 1.3.6.1.4.1.534.6.6.7.7.1.1.4 | ColumntemperatureValue | read-only | current | Units are in tenths of a degree according to the scale specified by temperatureScale (either Fahrenheit or Celsius). Divide by ten to get degrees. |
| 1.3.6.1.4.1.534.6.6.7.7.1.1.5 | ColumntemperatureThStatus | read-only | current | Status of the measured temperature relative to the configured thresholds. |
| 1.3.6.1.4.1.534.6.6.7.7.1.1.6 | ColumntemperatureThLowerWarning | read-write | current | Lower warning threshold. Units are tenths of a degree. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.7.1.1.7 | ColumntemperatureThLowerCritical | read-write | current | Lower critical threshold. Units are tenths of a degree. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.7.1.1.8 | ColumntemperatureThUpperWarning | read-write | current | Upper warning threshold. Units are tenths of a degree. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.7.1.1.9 | ColumntemperatureThUpperCritical | read-write | current | Upper critical threshold. Units are tenths of a degree. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.7.2 | TablehumidityTable | not-accessible | current | A list of humidity probe measurements. The number of entries is given by humidityCount. |
| 1.3.6.1.4.1.534.6.6.7.7.2.1 | RowhumidityEntry | not-accessible | current | An entry for a humidity measurement. |
| 1.3.6.1.4.1.534.6.6.7.7.2.1.1 | ColumnhumidityIndex | accessible-for-notify | current | A unique value for each humidity probe measurement. Its value ranges from 1 to humidityCount. |
| 1.3.6.1.4.1.534.6.6.7.7.2.1.2 | ColumnhumidityName | read-write | current | A descriptive name for the humidity probe. |
| 1.3.6.1.4.1.534.6.6.7.7.2.1.3 | ColumnhumidityProbeStatus | read-only | current | Indicates whether a probe is connected or not. |
| 1.3.6.1.4.1.534.6.6.7.7.2.1.4 | ColumnhumidityValue | read-only | current | Units are tenths of a percent relative humidity. Divide the value by 10 to get %RH. |
| 1.3.6.1.4.1.534.6.6.7.7.2.1.5 | ColumnhumidityThStatus | read-only | current | Status of the measured humidity relative to the configured thresholds. |
| 1.3.6.1.4.1.534.6.6.7.7.2.1.6 | ColumnhumidityThLowerWarning | read-write | current | Lower warning threshold. Units are 0.1 %RH. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.7.2.1.7 | ColumnhumidityThLowerCritical | read-write | current | Lower critical threshold. Units are 0.1 %RH. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.7.2.1.8 | ColumnhumidityThUpperWarning | read-write | current | Upper warning threshold. Units are 0.1 %RH. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.7.2.1.9 | ColumnhumidityThUpperCritical | read-write | current | Upper critical threshold. Units are 0.1 %RH. A negative value indicates that this object is not available. |
| 1.3.6.1.4.1.534.6.6.7.7.3 | TablecontactTable | not-accessible | current | A list of contact sensors. The number of entries is given by contactCount. |
| 1.3.6.1.4.1.534.6.6.7.7.3.1 | RowcontactEntry | not-accessible | current | An entry for a contact sensor |
| 1.3.6.1.4.1.534.6.6.7.7.3.1.1 | ColumncontactIndex | accessible-for-notify | current | A unique value for each contact sensor. Its value ranges from 1 to contactCount. |
| 1.3.6.1.4.1.534.6.6.7.7.3.1.2 | ColumncontactName | read-write | current | A descriptive name for the contact sensor. |
| 1.3.6.1.4.1.534.6.6.7.7.3.1.3 | ColumncontactProbeStatus | read-only | current | Indicates whether a probe is connected or not. Will not be returned if the contact sensor is internal to the ePDU, in that case only contactState should be rea… |
| 1.3.6.1.4.1.534.6.6.7.7.3.1.4 | ColumncontactState | read-only | current | The state of the contact sensor. |
| 1.3.6.1.4.1.534.6.6.7.25 | Nodeconformance | |||
| 1.3.6.1.4.1.534.6.6.7.25.1 | ComplianceeatonEpduCompliances | current | The requirements for conforming to the ePDU MIB. | |
| 1.3.6.1.4.1.534.6.6.7.25.5 | NodeobjectGroups | |||
| 1.3.6.1.4.1.534.6.6.7.25.5.1 | GroupepduRequiredGroup | current | Minimal objects are required to conform to this MIB. | |
| 1.3.6.1.4.1.534.6.6.7.25.5.2 | GroupepduOptionalGroup | current | Most objects in this MIB are optional. | |
| 1.3.6.1.4.1.534.6.6.7.25.5.3 | GroupepduNotifyGroup | current | These notifications will be supported depending on the features of the ePDU. Check the web interface for options to turn these notifications on/off. If an opti… |
Type Definitions
| Name | Syntax | Status | Description |
|---|---|---|---|
| UnixTimeStamp | Counter32 | current | Unix time stamp. Measured in seconds since January 1, 1970. |