EATON-EPDU-MIB

255 objects
The MIB module for Eaton ePDUs (Enclosure Power Distribution Units).
Imported Objects
EATON-OIDSpduAgent
SNMPv2-CONFMODULE-COMPLIANCE NOTIFICATION-GROUP OBJECT-GROUP
SNMPv2-SMICounter32 enterprises Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE Unsigned32
SNMPv2-TCDateAndTime DisplayString TEXTUAL-CONVENTION
OIDNameAccessStatusDescription
1.3.6.1.4.1.534Nodeeaton
1.3.6.1.4.1.534.6Nodeproducts
1.3.6.1.4.1.534.6.6NodepduAgent
1.3.6.1.4.1.534.6.6.7IdentityeatonEpduThe MIB module for Eaton ePDUs (Enclosure Power Distribution Units).
1.3.6.1.4.1.534.6.6.7.0Nodenotifications
1.3.6.1.4.1.534.6.6.7.0.1NotificationnotifyUserLogincurrentSent whenever a user logs in.
1.3.6.1.4.1.534.6.6.7.0.2NotificationnotifyUserLogoutcurrentSent whenever a user logs out.
1.3.6.1.4.1.534.6.6.7.0.3NotificationnotifyFailedLogincurrentSent when someone attempts to log in and fails. On some models, may be sent after three failed login attempts.
1.3.6.1.4.1.534.6.6.7.0.4NotificationnotifyBootUpcurrentSent whenever an ePDU finishes booting up (hard or soft reboot).
1.3.6.1.4.1.534.6.6.7.0.11NotificationnotifyInputVoltageThStatuscurrentSent whenever an input voltage threshold status changes.
1.3.6.1.4.1.534.6.6.7.0.12NotificationnotifyInputCurrentThStatuscurrentSent whenever an input current threshold status changes.
1.3.6.1.4.1.534.6.6.7.0.13NotificationnotifyInputFrequencyStatuscurrentSent whenever the input frequency status changes.
1.3.6.1.4.1.534.6.6.7.0.21NotificationnotifyGroupVoltageThStatuscurrentSent whenever a group voltage threshold status changes.
1.3.6.1.4.1.534.6.6.7.0.22NotificationnotifyGroupCurrentThStatuscurrentSent whenever a group current threshold status changes.
1.3.6.1.4.1.534.6.6.7.0.23NotificationnotifyGroupBreakerStatuscurrentSent whenever a group status changes to indicate whether the circuit breaker is on or off.
1.3.6.1.4.1.534.6.6.7.0.31NotificationnotifyOutletVoltageThStatuscurrentSent whenever an outlet voltage threshold status changes.
1.3.6.1.4.1.534.6.6.7.0.32NotificationnotifyOutletCurrentThStatuscurrentSent whenever an outlet current threshold status changes.
1.3.6.1.4.1.534.6.6.7.0.33NotificationnotifyOutletControlStatuscurrentSent whenever an outlet state On / Off changes.
1.3.6.1.4.1.534.6.6.7.0.41NotificationnotifyTemperatureThStatuscurrentSent whenever a temperature threshold status changes.
1.3.6.1.4.1.534.6.6.7.0.42NotificationnotifyHumidityThStatuscurrentSent whenever a humidity threshold status changes.
1.3.6.1.4.1.534.6.6.7.0.43NotificationnotifyContactStatecurrentSent whenever a contact sensor state changes.
1.3.6.1.4.1.534.6.6.7.0.44NotificationnotifyProbeStatuscurrentSent whenever the environment probe status changes.
1.3.6.1.4.1.534.6.6.7.0.51NotificationnotifyCommunicationStatuscurrentSent whenever the PDU communication status changes.
1.3.6.1.4.1.534.6.6.7.0.52NotificationnotifyInternalStatuscurrentSent whenever the PDU internal status changes.
1.3.6.1.4.1.534.6.6.7.0.53NotificationnotifyTestcurrentSent whenever the trap test feature is used by the communication card.
1.3.6.1.4.1.534.6.6.7.0.54NotificationnotifyStrappingStatuscurrentSent whenever the strapping communication status changes.
1.3.6.1.4.1.534.6.6.7.1Nodeunits
1.3.6.1.4.1.534.6.6.7.1.1ScalarunitsPresentread-onlycurrentEach unit is identified by a Strapping Index. This object returns a comma-delimited list of the Strapping Indexes of all units present in the strapping group. …
1.3.6.1.4.1.534.6.6.7.1.2TableunitTablenot-accessiblecurrentA list of units. In most cases this list will only contain one entry. However, some units have a 'strapping' feature which allow units to be daisy-chained toge…
1.3.6.1.4.1.534.6.6.7.1.2.1RowunitEntrynot-accessiblecurrentAn entry for a PDU.
1.3.6.1.4.1.534.6.6.7.1.2.1.1ColumnstrappingIndexaccessible-for-notifycurrentFor units that support 'strapping' functionality, this will be a unique value for each unit. If units do not support 'strapping', this will always be '0'.
1.3.6.1.4.1.534.6.6.7.1.2.1.2ColumnproductNameread-onlycurrentName of the product.
1.3.6.1.4.1.534.6.6.7.1.2.1.3ColumnpartNumberread-onlycurrentPart number of the unit.
1.3.6.1.4.1.534.6.6.7.1.2.1.4ColumnserialNumberread-onlycurrentSerial number of the unit.
1.3.6.1.4.1.534.6.6.7.1.2.1.5ColumnfirmwareVersionread-onlycurrentFirmware version.
1.3.6.1.4.1.534.6.6.7.1.2.1.6ColumnunitNameread-writecurrentDescriptive name for the unit.
1.3.6.1.4.1.534.6.6.7.1.2.1.7ColumnlcdControlread-writecurrentControl the local LCD.
1.3.6.1.4.1.534.6.6.7.1.2.1.8ColumnclockValueread-writecurrentClock value. This could be from either a real-time clock (in which case it is likely writeable) or from a time server via NTP (probably read-only).
1.3.6.1.4.1.534.6.6.7.1.2.1.9ColumntemperatureScaleread-writecurrentScale used to return temperature objects.
1.3.6.1.4.1.534.6.6.7.1.2.1.10ColumnunitTyperead-onlycurrentTechnical capabilities of the PDU. Functionality is as follows: Monitored (MI) - input and usually section/group monitoring. Advanced Monitored (AM) - input, s…
1.3.6.1.4.1.534.6.6.7.1.2.1.11ColumnsystemTyperead-onlycurrentArchitecture of the ePDU electronic.
1.3.6.1.4.1.534.6.6.7.1.2.1.20ColumninputCountread-onlycurrentNumber of inputs on this ePDU.
1.3.6.1.4.1.534.6.6.7.1.2.1.21ColumngroupCountread-onlycurrentNumber of groups on this ePDU. Groups include breakers, outlet sections, and user-defined groups.
1.3.6.1.4.1.534.6.6.7.1.2.1.22ColumnoutletCountread-onlycurrentNumber of outlets on this ePDU.
1.3.6.1.4.1.534.6.6.7.1.2.1.23ColumntemperatureCountread-onlycurrentMax number of temperature measurements on this ePDU.
1.3.6.1.4.1.534.6.6.7.1.2.1.24ColumnhumidityCountread-onlycurrentMax number of humidity measurements on this ePDU.
1.3.6.1.4.1.534.6.6.7.1.2.1.25ColumncontactCountread-onlycurrentMax number of contact sensors on this ePDU.
1.3.6.1.4.1.534.6.6.7.1.2.1.30ColumncommunicationStatusread-onlycurrentStatus of the internal communication with the PDU.
1.3.6.1.4.1.534.6.6.7.1.2.1.31ColumninternalStatusread-onlycurrentStatus of the internal failure inside the PDU.
1.3.6.1.4.1.534.6.6.7.1.2.1.32ColumnstrappingStatusread-onlycurrentStatus of the external communication with a strapping unit.
1.3.6.1.4.1.534.6.6.7.1.2.1.40ColumnuserNameaccessible-for-notifycurrentUsername used to log into the PDU.
1.3.6.1.4.1.534.6.6.7.1.2.1.41ColumncommInterfaceaccessible-for-notifycurrentCommunications interface used to log into the PDU.
1.3.6.1.4.1.534.6.6.7.1.3TableunitControlTablenot-accessiblecurrentA list of units that have controllable outlets.
1.3.6.1.4.1.534.6.6.7.1.3.1RowunitControlEntrynot-accessiblecurrentAn entry for a PDU which has controllable outlets.
1.3.6.1.4.1.534.6.6.7.1.3.1.2ColumnunitControlOffCmdread-writecurrentUnit-level outlet control command. Once the command is issued, outlets will turn Off. 0-n : Time in seconds until the outlet Sequence Off command is issued -1 …
1.3.6.1.4.1.534.6.6.7.1.3.1.3ColumnunitControlOnCmdread-writecurrentUnit-level outlet control command. Once the command is issued, outlets will turn On according to their outletControlSequenceDelay value. 0-n : Time in seconds …
1.3.6.1.4.1.534.6.6.7.3Nodeinputs
1.3.6.1.4.1.534.6.6.7.3.1TableinputTablenot-accessiblecurrentList of inputs to the PDU.
1.3.6.1.4.1.534.6.6.7.3.1.1RowinputEntrynot-accessiblecurrentAn entry for a particular input.
1.3.6.1.4.1.534.6.6.7.3.1.1.1ColumninputIndexaccessible-for-notifycurrentA unique value for each input. Its value ranges from 1 to inputCount.
1.3.6.1.4.1.534.6.6.7.3.1.1.2ColumninputTyperead-onlycurrentType of input - single phase, split phase, three phase delta, or three phase wye.
1.3.6.1.4.1.534.6.6.7.3.1.1.3ColumninputFrequencyread-onlycurrentUnits are 0.1 Hz; divide by ten to get Hz.
1.3.6.1.4.1.534.6.6.7.3.1.1.4ColumninputFrequencyStatusread-onlycurrentStatus of the measured input frequency relative to the nominal frequency and the admitted tolerance.
1.3.6.1.4.1.534.6.6.7.3.1.1.5ColumninputVoltageCountread-onlycurrentNumber of input voltage measurements on this ePDU.
1.3.6.1.4.1.534.6.6.7.3.1.1.6ColumninputCurrentCountread-onlycurrentNumber of input current measurements on this ePDU.
1.3.6.1.4.1.534.6.6.7.3.1.1.7ColumninputPowerCountread-onlycurrentNumber of rows in the inputPowerTable.
1.3.6.1.4.1.534.6.6.7.3.1.1.8ColumninputPlugTyperead-onlycurrentIdentifies which plug is on the input.
1.3.6.1.4.1.534.6.6.7.3.1.1.9ColumninputFeedColorread-writecurrentColor code of the input feed.
1.3.6.1.4.1.534.6.6.7.3.1.1.10ColumninputFeedNameread-writecurrentA descriptive name for the input.
1.3.6.1.4.1.534.6.6.7.3.2TableinputVoltageTablenot-accessiblecurrentA list of input voltage measurements. The number of entries is given by inputVoltageCount.
1.3.6.1.4.1.534.6.6.7.3.2.1RowinputVoltageEntrynot-accessiblecurrentAn entry for a particular input voltage measurement.
1.3.6.1.4.1.534.6.6.7.3.2.1.1ColumninputVoltageIndexaccessible-for-notifycurrentA unique value for each input voltage measurement. Its value ranges from 1 to inputVoltageCount.
1.3.6.1.4.1.534.6.6.7.3.2.1.2ColumninputVoltageMeasTyperead-onlycurrentValue indicates what input voltage is being measured in this table row - single phase voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phas…
1.3.6.1.4.1.534.6.6.7.3.2.1.3ColumninputVoltageread-onlycurrentAn input voltage measurement value. Units are millivolts.
1.3.6.1.4.1.534.6.6.7.3.2.1.4ColumninputVoltageThStatusread-onlycurrentStatus of the measured input voltage relative to the configured thresholds.
1.3.6.1.4.1.534.6.6.7.3.2.1.5ColumninputVoltageThLowerWarningread-writecurrentLower warning threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.2.1.6ColumninputVoltageThLowerCriticalread-writecurrentLower critical threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.2.1.7ColumninputVoltageThUpperWarningread-writecurrentUpper warning threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.2.1.8ColumninputVoltageThUpperCriticalread-writecurrentUpper critical threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.3TableinputCurrentTablenot-accessiblecurrentA list of input current measurements. The number of entries is given by inputCurrentCount.
1.3.6.1.4.1.534.6.6.7.3.3.1RowinputCurrentEntrynot-accessiblecurrentAn entry for a particular input current measurement.
1.3.6.1.4.1.534.6.6.7.3.3.1.1ColumninputCurrentIndexaccessible-for-notifycurrentA unique value for each input current measurement. Its value ranges from 1 to inputCurrentCount.
1.3.6.1.4.1.534.6.6.7.3.3.1.2ColumninputCurrentMeasTyperead-onlycurrentWhich input wire is being measured in this table row - single phase, neutral, phase 1, phase 2, or phase 3.
1.3.6.1.4.1.534.6.6.7.3.3.1.3ColumninputCurrentCapacityread-onlycurrentRated current capacity of the input. A negative value indicates that the hardware current capacity is unknown. Units are milliamps.
1.3.6.1.4.1.534.6.6.7.3.3.1.4ColumninputCurrentread-onlycurrentAn input current measurement value. Units are milliamps.
1.3.6.1.4.1.534.6.6.7.3.3.1.5ColumninputCurrentThStatusread-onlycurrentStatus of the measured input current relative to the configured thresholds.
1.3.6.1.4.1.534.6.6.7.3.3.1.6ColumninputCurrentThLowerWarningread-writecurrentLower warning threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.3.1.7ColumninputCurrentThLowerCriticalread-writecurrentLower critical threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.3.1.8ColumninputCurrentThUpperWarningread-writecurrentUpper warning threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.3.1.9ColumninputCurrentThUpperCriticalread-writecurrentUpper critical threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.3.1.10ColumninputCurrentCrestFactorread-onlycurrentCurrent crest factor. Units are in milli, for example a crest factor of 1.414 will be returned as 1414. A negative value indicates that this object is not avai…
1.3.6.1.4.1.534.6.6.7.3.3.1.11ColumninputCurrentPercentLoadread-onlycurrentCurrent percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this o…
1.3.6.1.4.1.534.6.6.7.3.3.1.12ColumninputPhaseDesignatorread-onlycurrentAlphanumeric physical name for the input.
1.3.6.1.4.1.534.6.6.7.3.4TableinputPowerTablenot-accessiblecurrentA list of input power measurements. The number of entries is given by inputPowerCount.
1.3.6.1.4.1.534.6.6.7.3.4.1RowinputPowerEntrynot-accessiblecurrentAn entry for an input power measurement.
1.3.6.1.4.1.534.6.6.7.3.4.1.1ColumninputPowerIndexnot-accessiblecurrentA unique value for each input power measurement. Its value ranges from 1 to inputPowerCount.
1.3.6.1.4.1.534.6.6.7.3.4.1.2ColumninputPowerMeasTyperead-onlycurrentValue indicates what is being measured in this table row.
1.3.6.1.4.1.534.6.6.7.3.4.1.3ColumninputVAread-onlycurrentAn input VA value. Units are VA. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.4.1.4ColumninputWattsread-onlycurrentAn input Watts value. Units are Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.4.1.5ColumninputWhread-writecurrentUnits are Watt-hours. This object is writable so that it can be reset to 0. When it is written to, the inputWhTimer will be reset updated as well.
1.3.6.1.4.1.534.6.6.7.3.4.1.6ColumninputWhTimerread-onlycurrentTimestamp of when input Watt-hours (inputWh) was last reset.
1.3.6.1.4.1.534.6.6.7.3.4.1.7ColumninputPowerFactorread-onlycurrentAn input PF value. Units are in thousandths, for example a power factor of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value …
1.3.6.1.4.1.534.6.6.7.3.4.1.8ColumninputVARread-onlycurrentAn input VAR value. Units are VAR. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.5TableinputTotalPowerTablenot-accessiblecurrentA list of total input power measurements.
1.3.6.1.4.1.534.6.6.7.3.5.1RowinputTotalPowerEntrynot-accessiblecurrentAn entry for a total input power measurement.
1.3.6.1.4.1.534.6.6.7.3.5.1.3ColumninputTotalVAread-onlycurrentAn input VA value. Units are VA. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.5.1.4ColumninputTotalWattsread-onlycurrentAn input Watts value. Units are Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.5.1.5ColumninputTotalWhread-writecurrentUnits are Watt-hours. This object is writable so that it can be reset to 0. When it is written to, the inputWhTimer will be reset updated as well.
1.3.6.1.4.1.534.6.6.7.3.5.1.6ColumninputTotalWhTimerread-onlycurrentTimestamp of when input Watt-hours (inputWh) was last reset.
1.3.6.1.4.1.534.6.6.7.3.5.1.7ColumninputTotalPowerFactorread-onlycurrentAn input PF value. Units are in thousandths, for example a power factor of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value …
1.3.6.1.4.1.534.6.6.7.3.5.1.8ColumninputTotalVARread-onlycurrentAn input VAR value. Units are VAR. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.5.1.9ColumninputPowerCapacityread-onlycurrentTypical power capacity of the input. A negative value indicates that the hardware current capacity is unknown.
1.3.6.1.4.1.534.6.6.7.5Nodegroups
1.3.6.1.4.1.534.6.6.7.5.1TablegroupTablenot-accessiblecurrentA list of groups. The number of entries is given by groupCount.
1.3.6.1.4.1.534.6.6.7.5.1.1RowgroupEntrynot-accessiblecurrentAn entry for a particular group.
1.3.6.1.4.1.534.6.6.7.5.1.1.1ColumngroupIndexaccessible-for-notifycurrentA unique value for each group. Its value ranges from 1 to groupCount.
1.3.6.1.4.1.534.6.6.7.5.1.1.2ColumngroupIDread-onlycurrentAlphanumeric designator for the group. This value may be written on the face of the unit.
1.3.6.1.4.1.534.6.6.7.5.1.1.3ColumngroupNameread-writecurrentA descriptive name for the group.
1.3.6.1.4.1.534.6.6.7.5.1.1.4ColumngroupTyperead-onlycurrentThe type of the group.
1.3.6.1.4.1.534.6.6.7.5.1.1.5ColumngroupBreakerStatusread-onlycurrentOnly applicable to breaker-groups. Indicates whether a breaker is turned off or on.
1.3.6.1.4.1.534.6.6.7.5.1.1.6ColumngroupChildCountread-onlycurrentNumber of children for this group.
1.3.6.1.4.1.534.6.6.7.5.1.1.7ColumngroupColorread-onlycurrentBackground color code of the group. Color codes are decimal values.
1.3.6.1.4.1.534.6.6.7.5.1.1.8ColumngroupDesignatorread-onlycurrentAlphanumeric physical name for the group. This value may be written on the face of the unit.
1.3.6.1.4.1.534.6.6.7.5.1.1.9ColumngroupInputIndexread-onlycurrentIdentifies the input on which the group is connected.
1.3.6.1.4.1.534.6.6.7.5.2TablegroupChildTablenot-accessiblecurrentA list of children for this group. For example, this table will link to all of the outlets that are contained in a particular group.
1.3.6.1.4.1.534.6.6.7.5.2.1RowgroupChildEntrynot-accessiblecurrentAn entry for a particular child.
1.3.6.1.4.1.534.6.6.7.5.2.1.1ColumngroupChildIndexnot-accessiblecurrentA unique value for each child. Its value ranges from 1 to groupChildCount.
1.3.6.1.4.1.534.6.6.7.5.2.1.2ColumngroupChildTyperead-onlycurrentThe type of the child.
1.3.6.1.4.1.534.6.6.7.5.2.1.3ColumngroupChildOIDread-onlycurrentObject ID of a child object.
1.3.6.1.4.1.534.6.6.7.5.3TablegroupVoltageTablenot-accessiblecurrentA list of group voltage measurements. There can be only one voltage measurement for each group.
1.3.6.1.4.1.534.6.6.7.5.3.1RowgroupVoltageEntrynot-accessiblecurrentAn entry for a group voltage measurement.
1.3.6.1.4.1.534.6.6.7.5.3.1.2ColumngroupVoltageMeasTyperead-onlycurrentValue indicates what voltage is being measured in this table row.
1.3.6.1.4.1.534.6.6.7.5.3.1.3ColumngroupVoltageread-onlycurrentUnits are millivolts.
1.3.6.1.4.1.534.6.6.7.5.3.1.4ColumngroupVoltageThStatusread-onlycurrentStatus of the measured group voltage relative to the configured thresholds.
1.3.6.1.4.1.534.6.6.7.5.3.1.5ColumngroupVoltageThLowerWarningread-writecurrentLower warning threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.5.3.1.6ColumngroupVoltageThLowerCriticalread-writecurrentLower critical threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.5.3.1.7ColumngroupVoltageThUpperWarningread-writecurrentUpper warning threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.5.3.1.8ColumngroupVoltageThUpperCriticalread-writecurrentUpper critical threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.5.4TablegroupCurrentTablenot-accessiblecurrentA list of group current measurements. There can be only one current measurement for each group.
1.3.6.1.4.1.534.6.6.7.5.4.1RowgroupCurrentEntrynot-accessiblecurrentAn entry for a group current measurement.
1.3.6.1.4.1.534.6.6.7.5.4.1.2ColumngroupCurrentCapacityread-onlycurrentRated current capacity of the group. Units are milliamps. A negative value indicates that the hardware current capacity is unknown (it will always be unknown f…
1.3.6.1.4.1.534.6.6.7.5.4.1.3ColumngroupCurrentread-onlycurrentA group current measurement value. Units are milliamps.
1.3.6.1.4.1.534.6.6.7.5.4.1.4ColumngroupCurrentThStatusread-onlycurrentStatus of the measured group current relative to the configured thresholds.
1.3.6.1.4.1.534.6.6.7.5.4.1.5ColumngroupCurrentThLowerWarningread-writecurrentLower warning threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.5.4.1.6ColumngroupCurrentThLowerCriticalread-writecurrentLower critical threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.5.4.1.7ColumngroupCurrentThUpperWarningread-writecurrentUpper warning threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.5.4.1.8ColumngroupCurrentThUpperCriticalread-writecurrentUpper critical threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.5.4.1.9ColumngroupCurrentCrestFactorread-onlycurrentCurrent crest factor. Units are in milli, for example a crest factor of 1.414 will be returned as 1414. A negative value indicates that this object is not avai…
1.3.6.1.4.1.534.6.6.7.5.4.1.10ColumngroupCurrentPercentLoadread-onlycurrentCurrent percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this o…
1.3.6.1.4.1.534.6.6.7.5.5TablegroupPowerTablenot-accessiblecurrentA list of group power measurements. There can be only one power measurement for each group.
1.3.6.1.4.1.534.6.6.7.5.5.1RowgroupPowerEntrynot-accessiblecurrentAn entry for a group power measurement.
1.3.6.1.4.1.534.6.6.7.5.5.1.2ColumngroupVAread-onlycurrentA group VA value. Units are VA. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.5.5.1.3ColumngroupWattsread-onlycurrentA group Watts value. Units are Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.5.5.1.4ColumngroupWhread-writecurrentUnits are Watt-hours. This object is writable so that it can be reset to 0. When it is written to, the inputWhTotalTimer will be reset to 0 as well.
1.3.6.1.4.1.534.6.6.7.5.5.1.5ColumngroupWhTimerread-onlycurrentTimestamp of when group Watt-hours (groupWh) was last reset.
1.3.6.1.4.1.534.6.6.7.5.5.1.6ColumngroupPowerFactorread-onlycurrentA group PF value. Units are in thousandths, for example a power factor of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value i…
1.3.6.1.4.1.534.6.6.7.5.5.1.7ColumngroupVARread-onlycurrentA group VAR value. Units are VAR. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.5.6TablegroupControlTablenot-accessiblecurrentA list of controllable groups.
1.3.6.1.4.1.534.6.6.7.5.6.1RowgroupControlEntrynot-accessiblecurrentAn entry for a controllable group.
1.3.6.1.4.1.534.6.6.7.5.6.1.2ColumngroupControlStatusread-onlycurrentCurrent state of a controlled group. A value of 'mixed' means that that the outlets within the group have differing states.
1.3.6.1.4.1.534.6.6.7.5.6.1.3ColumngroupControlOffCmdread-writecurrentGroup-level outlet control command. Once the command is issued, the outlets in the group will turn Off immediately. 0-n : Time in seconds until the group comma…
1.3.6.1.4.1.534.6.6.7.5.6.1.4ColumngroupControlOnCmdread-writecurrentGroup-level outlet control command. Once the command is issued, the outlets in the group will turn On immediately. 0-n : Time in seconds until the group comman…
1.3.6.1.4.1.534.6.6.7.5.6.1.5ColumngroupControlRebootCmdread-writecurrentGroup-level outlet control command. For outlets that are On prior to the Reboot command, they will switch Off immediately when the command is issued, remain Of…
1.3.6.1.4.1.534.6.6.7.6Nodeoutlets
1.3.6.1.4.1.534.6.6.7.6.1TableoutletTablenot-accessiblecurrentA list of outlets. The number of entries is given by outletCount.
1.3.6.1.4.1.534.6.6.7.6.1.1RowoutletEntrynot-accessiblecurrentAn entry for a particular outlet.
1.3.6.1.4.1.534.6.6.7.6.1.1.1ColumnoutletIndexaccessible-for-notifycurrentA unique value for each outlet. its value ranges from 1 to outletCount.
1.3.6.1.4.1.534.6.6.7.6.1.1.2ColumnoutletIDread-onlycurrentAlphanumeric designator for the outlet.
1.3.6.1.4.1.534.6.6.7.6.1.1.3ColumnoutletNameread-writecurrentA descriptive name for the outlet.
1.3.6.1.4.1.534.6.6.7.6.1.1.4ColumnoutletParentCountread-onlycurrentNumber of parents for this outlet.
1.3.6.1.4.1.534.6.6.7.6.1.1.5ColumnoutletTyperead-onlycurrentThe physical type of outlet.
1.3.6.1.4.1.534.6.6.7.6.1.1.6ColumnoutletDesignatorread-onlycurrentAlphanumeric physical name for the outlet.
1.3.6.1.4.1.534.6.6.7.6.1.1.7ColumnoutletPhaseIDread-onlycurrentValue indicates which phases are connected to each outlet in this table row - single phase voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral,…
1.3.6.1.4.1.534.6.6.7.6.2TableoutletParentTablenot-accessiblecurrentA list of parents for this outlet. For example, this table will link to all of the groups that have this outlet as a child.
1.3.6.1.4.1.534.6.6.7.6.2.1RowoutletParentEntrynot-accessiblecurrentAn entry for a particular parent.
1.3.6.1.4.1.534.6.6.7.6.2.1.1ColumnoutletParentIndexnot-accessiblecurrentA unique value for each parent. Its value ranges from 1 to outletParentCount.
1.3.6.1.4.1.534.6.6.7.6.2.1.2ColumnoutletParentTyperead-onlycurrentThe type of the parent.
1.3.6.1.4.1.534.6.6.7.6.2.1.3ColumnoutletParentOIDread-onlycurrentObject ID of a parent object.
1.3.6.1.4.1.534.6.6.7.6.3TableoutletVoltageTablenot-accessiblecurrentA list of outlet voltage measurements.
1.3.6.1.4.1.534.6.6.7.6.3.1RowoutletVoltageEntrynot-accessiblecurrentAn entry for an outlet voltage measurement.
1.3.6.1.4.1.534.6.6.7.6.3.1.2ColumnoutletVoltageread-onlycurrentUnits are millivolts.
1.3.6.1.4.1.534.6.6.7.6.3.1.3ColumnoutletVoltageThStatusread-onlycurrentStatus of the measured outlet voltage relative to the configured thresholds.
1.3.6.1.4.1.534.6.6.7.6.3.1.4ColumnoutletVoltageThLowerWarningread-writecurrentLower warning threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.3.1.5ColumnoutletVoltageThLowerCriticalread-writecurrentLower critical threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.3.1.6ColumnoutletVoltageThUpperWarningread-writecurrentUpper warning threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.3.1.7ColumnoutletVoltageThUpperCriticalread-writecurrentUpper critical threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.4TableoutletCurrentTablenot-accessiblecurrentA list of outlet current measurements.
1.3.6.1.4.1.534.6.6.7.6.4.1RowoutletCurrentEntrynot-accessiblecurrentAn entry for an outlet current measurement.
1.3.6.1.4.1.534.6.6.7.6.4.1.2ColumnoutletCurrentCapacityread-onlycurrentRated current capacity of the outlet. Units are milliamps. A negative value indicates that the hardware current capacity is unknown.
1.3.6.1.4.1.534.6.6.7.6.4.1.3ColumnoutletCurrentread-onlycurrentAn outlet current measurement value. Units are milliamps.
1.3.6.1.4.1.534.6.6.7.6.4.1.4ColumnoutletCurrentThStatusread-onlycurrentStatus of the measured outlet current relative to the configured thresholds. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.4.1.5ColumnoutletCurrentThLowerWarningread-writecurrentLower warning threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.4.1.6ColumnoutletCurrentThLowerCriticalread-writecurrentLower critical threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.4.1.7ColumnoutletCurrentThUpperWarningread-writecurrentUpper warning threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.4.1.8ColumnoutletCurrentThUpperCriticalread-writecurrentUpper critical threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.4.1.9ColumnoutletCurrentCrestFactorread-onlycurrentCurrent crest factor. Units are in milli, for example a crest factor of 1.414 will be returned as 1414. A negative value indicates that this object is not avai…
1.3.6.1.4.1.534.6.6.7.6.4.1.10ColumnoutletCurrentPercentLoadread-onlycurrentCurrent percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this o…
1.3.6.1.4.1.534.6.6.7.6.5TableoutletPowerTablenot-accessiblecurrentA list of outlet power measurements.
1.3.6.1.4.1.534.6.6.7.6.5.1RowoutletPowerEntrynot-accessiblecurrentAn entry for an outlet power measurement.
1.3.6.1.4.1.534.6.6.7.6.5.1.2ColumnoutletVAread-onlycurrentAn outlet VA value. Units are VA. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.5.1.3ColumnoutletWattsread-onlycurrentAn outlet Watts value. Units are Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.5.1.4ColumnoutletWhread-writecurrentUnits are Watt-hours. This object is writable so that it can be reset to 0. When it is written to, the inputWhTotalTimer will be reset to 0 as well.
1.3.6.1.4.1.534.6.6.7.6.5.1.5ColumnoutletWhTimerread-onlycurrentTimestamp of when outlet Watt-hours (outletWh) was last reset.
1.3.6.1.4.1.534.6.6.7.6.5.1.6ColumnoutletPowerFactorread-onlycurrentAn outlet PF value. Units are in thousandths, for example a power factor of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value…
1.3.6.1.4.1.534.6.6.7.6.5.1.7ColumnoutletVARread-onlycurrentAn outlet VAR value. Units are VAR. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.6TableoutletControlTablenot-accessiblecurrentA list of controllable outlets.
1.3.6.1.4.1.534.6.6.7.6.6.1RowoutletControlEntrynot-accessiblecurrentAn entry for a controllable outlet.
1.3.6.1.4.1.534.6.6.7.6.6.1.2ColumnoutletControlStatusread-onlycurrentCurrent state of a controlled outlet.
1.3.6.1.4.1.534.6.6.7.6.6.1.3ColumnoutletControlOffCmdread-writecurrentOutlet control command. Once the command is issued, the outlet will turn Off immediately. 0-n : Time in seconds until the outlet command is issued -1 : Cancel …
1.3.6.1.4.1.534.6.6.7.6.6.1.4ColumnoutletControlOnCmdread-writecurrentOutlet control command. Once the command is issued, the outlet will turn On immediately. 0-n : Time in seconds until the outlet command is issued -1 : Cancel a…
1.3.6.1.4.1.534.6.6.7.6.6.1.5ColumnoutletControlRebootCmdread-writecurrentOutlet control command. For outlets that are On prior to this Reboot command, they will switch Off immediately when the command is issued, remain Off for outle…
1.3.6.1.4.1.534.6.6.7.6.6.1.6ColumnoutletControlPowerOnStateread-writecurrentDetermines the outlet state when power is applied to the unit. 0 : not restart at device startup 1 : should sequence back ON in line with outletControlSequence…
1.3.6.1.4.1.534.6.6.7.6.6.1.7ColumnoutletControlSequenceDelayread-writecurrentTime delay in seconds from when a Global Sequence On command is issued to when the command is executed on this outlet. This delay is also used as a power-on de…
1.3.6.1.4.1.534.6.6.7.6.6.1.8ColumnoutletControlRebootOffTimeread-writecurrentTime delay in seconds that the outlet should remain in the Off state when executing a Reboot command.
1.3.6.1.4.1.534.6.6.7.6.6.1.9ColumnoutletControlSwitchableread-writecurrentDetermines the outlet capability to be controlled On/Off from the communication channels. 1 : control On/Off enabled 2 : control On/Off disabled.
1.3.6.1.4.1.534.6.6.7.6.6.1.10ColumnoutletControlShutoffDelayread-writecurrentTime delay in seconds that could be taken in account before shutting of the outlet. An application which need to shutoff properly an outlet will read this para…
1.3.6.1.4.1.534.6.6.7.6.7TableoutletGlobalTablenot-accessiblecurrentA list of globlal configuration on all outlets.
1.3.6.1.4.1.534.6.6.7.6.7.1RowoutletGlobalEntrynot-accessiblecurrentAn entry for a global variable on all outlets.
1.3.6.1.4.1.534.6.6.7.6.7.1.2ColumnoutletAutomaticShutoffread-writecurrentDetermines the state of all outlets when the unit is power off: 0 : not applicable (read only) 1 : Keep the outlet relays in the current position when the PDU …
1.3.6.1.4.1.534.6.6.7.7Nodeenvironmental
1.3.6.1.4.1.534.6.6.7.7.1TabletemperatureTablenot-accessiblecurrentA list of temperature probe measurements. The number of entries is given by temperatureCount.
1.3.6.1.4.1.534.6.6.7.7.1.1RowtemperatureEntrynot-accessiblecurrentAn entry for a temperature measurement.
1.3.6.1.4.1.534.6.6.7.7.1.1.1ColumntemperatureIndexaccessible-for-notifycurrentA unique value for each temperature probe measurement. Its value ranges from 1 to temperatureCount.
1.3.6.1.4.1.534.6.6.7.7.1.1.2ColumntemperatureNameread-writecurrentA descriptive name for the temperature probe.
1.3.6.1.4.1.534.6.6.7.7.1.1.3ColumntemperatureProbeStatusread-onlycurrentIndicates whether a probe is connected or not.
1.3.6.1.4.1.534.6.6.7.7.1.1.4ColumntemperatureValueread-onlycurrentUnits are in tenths of a degree according to the scale specified by temperatureScale (either Fahrenheit or Celsius). Divide by ten to get degrees.
1.3.6.1.4.1.534.6.6.7.7.1.1.5ColumntemperatureThStatusread-onlycurrentStatus of the measured temperature relative to the configured thresholds.
1.3.6.1.4.1.534.6.6.7.7.1.1.6ColumntemperatureThLowerWarningread-writecurrentLower warning threshold. Units are tenths of a degree. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.7.1.1.7ColumntemperatureThLowerCriticalread-writecurrentLower critical threshold. Units are tenths of a degree. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.7.1.1.8ColumntemperatureThUpperWarningread-writecurrentUpper warning threshold. Units are tenths of a degree. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.7.1.1.9ColumntemperatureThUpperCriticalread-writecurrentUpper critical threshold. Units are tenths of a degree. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.7.2TablehumidityTablenot-accessiblecurrentA list of humidity probe measurements. The number of entries is given by humidityCount.
1.3.6.1.4.1.534.6.6.7.7.2.1RowhumidityEntrynot-accessiblecurrentAn entry for a humidity measurement.
1.3.6.1.4.1.534.6.6.7.7.2.1.1ColumnhumidityIndexaccessible-for-notifycurrentA unique value for each humidity probe measurement. Its value ranges from 1 to humidityCount.
1.3.6.1.4.1.534.6.6.7.7.2.1.2ColumnhumidityNameread-writecurrentA descriptive name for the humidity probe.
1.3.6.1.4.1.534.6.6.7.7.2.1.3ColumnhumidityProbeStatusread-onlycurrentIndicates whether a probe is connected or not.
1.3.6.1.4.1.534.6.6.7.7.2.1.4ColumnhumidityValueread-onlycurrentUnits are tenths of a percent relative humidity. Divide the value by 10 to get %RH.
1.3.6.1.4.1.534.6.6.7.7.2.1.5ColumnhumidityThStatusread-onlycurrentStatus of the measured humidity relative to the configured thresholds.
1.3.6.1.4.1.534.6.6.7.7.2.1.6ColumnhumidityThLowerWarningread-writecurrentLower warning threshold. Units are 0.1 %RH. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.7.2.1.7ColumnhumidityThLowerCriticalread-writecurrentLower critical threshold. Units are 0.1 %RH. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.7.2.1.8ColumnhumidityThUpperWarningread-writecurrentUpper warning threshold. Units are 0.1 %RH. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.7.2.1.9ColumnhumidityThUpperCriticalread-writecurrentUpper critical threshold. Units are 0.1 %RH. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.7.3TablecontactTablenot-accessiblecurrentA list of contact sensors. The number of entries is given by contactCount.
1.3.6.1.4.1.534.6.6.7.7.3.1RowcontactEntrynot-accessiblecurrentAn entry for a contact sensor
1.3.6.1.4.1.534.6.6.7.7.3.1.1ColumncontactIndexaccessible-for-notifycurrentA unique value for each contact sensor. Its value ranges from 1 to contactCount.
1.3.6.1.4.1.534.6.6.7.7.3.1.2ColumncontactNameread-writecurrentA descriptive name for the contact sensor.
1.3.6.1.4.1.534.6.6.7.7.3.1.3ColumncontactProbeStatusread-onlycurrentIndicates whether a probe is connected or not. Will not be returned if the contact sensor is internal to the ePDU, in that case only contactState should be rea…
1.3.6.1.4.1.534.6.6.7.7.3.1.4ColumncontactStateread-onlycurrentThe state of the contact sensor.
1.3.6.1.4.1.534.6.6.7.25Nodeconformance
1.3.6.1.4.1.534.6.6.7.25.1ComplianceeatonEpduCompliancescurrentThe requirements for conforming to the ePDU MIB.
1.3.6.1.4.1.534.6.6.7.25.5NodeobjectGroups
1.3.6.1.4.1.534.6.6.7.25.5.1GroupepduRequiredGroupcurrentMinimal objects are required to conform to this MIB.
1.3.6.1.4.1.534.6.6.7.25.5.2GroupepduOptionalGroupcurrentMost objects in this MIB are optional.
1.3.6.1.4.1.534.6.6.7.25.5.3GroupepduNotifyGroupcurrentThese notifications will be supported depending on the features of the ePDU. Check the web interface for options to turn these notifications on/off. If an opti…
Type Definitions
NameSyntaxStatusDescription
UnixTimeStampCounter32currentUnix time stamp. Measured in seconds since January 1, 1970.