MIB Viewer

EATON-EPDU-PU-SW-MIB

517 objects
The MIB module for Eaton Switched ePDUs (Enclosed Power Distribution Units.)
Imported Objects
SNMPv2-CONFMODULE-COMPLIANCE NOTIFICATION-GROUP OBJECT-GROUP
SNMPv2-SMIenterprises Integer32 IpAddress MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE
OIDNameAccessStatusDescription
1.3.6.1.4.1.20677IdentitypulizziThe MIB module for Eaton Switched ePDUs (Enclosed Power Distribution Units.)
1.3.6.1.4.1.20677.2Nodeipv3600
1.3.6.1.4.1.20677.2.1NodeunitConfig
1.3.6.1.4.1.20677.2.1.1ScalarunitNameread-writecurrentDescriptive name of unit.
1.3.6.1.4.1.20677.2.1.2ScalarstrappingIdread-onlycurrentID of unit when connected in a strapping configuration.
1.3.6.1.4.1.20677.2.1.3ScalarunitTimeread-writecurrentTime hh:mm
1.3.6.1.4.1.20677.2.1.4ScalarunitDateread-writecurrentToday's date mm/dd/yyyy
1.3.6.1.4.1.20677.2.1.5ScalarunitDayOfWeekread-writecurrentToday's day of week. This is important when scheduling logs to be sent on a particular week day.
1.3.6.1.4.1.20677.2.1.6ScalarvaLoggingIntervalread-writecurrentInterval for updating the VA log.
1.3.6.1.4.1.20677.2.1.7ScalarloginTimeoutread-writecurrentTimeout (in seconds) for serial, telnet, and web interfaces.
1.3.6.1.4.1.20677.2.1.8ScalarinvertDisplayread-writecurrentSelect the orientation of the local 7-segment display.
1.3.6.1.4.1.20677.2.1.9ScalarfahrenheitOrCelsiusread-writecurrentUnits for temperature readings.
1.3.6.1.4.1.20677.2.2NodenetworkSettings
1.3.6.1.4.1.20677.2.2.1ScalarunitIPAddressread-onlycurrentNetwork IP address
1.3.6.1.4.1.20677.2.2.2ScalarsubnetMaskread-onlycurrentNetwork subnet mask
1.3.6.1.4.1.20677.2.2.3ScalardefaultGatewayread-onlycurrentNetwork default gateway
1.3.6.1.4.1.20677.2.2.4ScalarwebPortread-writecurrentPort number for non-secure (http) web interface.
1.3.6.1.4.1.20677.2.2.5ScalarwebEnabledread-writecurrentEnables or disables the web interface (both secure and non-secure).
1.3.6.1.4.1.20677.2.2.6ScalarmacAddressread-onlycurrentHardware network address
1.3.6.1.4.1.20677.2.2.7ScalarenablePingread-writecurrentEnables ping watchdog feature. If enabled, the IP address for each outlet (if non-zero) will be pinged periodically; the outlet will be rebooted if there is no…
1.3.6.1.4.1.20677.2.2.8ScalarpingIntervalread-writecurrentInterval (in minutes) beween attempts to ping the IP address corresponding to an outlet.
1.3.6.1.4.1.20677.2.3NodelogManagerConfig
1.3.6.1.4.1.20677.2.3.1ScalarmailServerIPAddressread-writecurrentIP address of mail server for sending logs and alerts.
1.3.6.1.4.1.20677.2.3.2ScalarsendLogFromread-writecurrentEmail address (x@y.z format) to be used as the from address for logs and alerts.
1.3.6.1.4.1.20677.2.3.3ScalarsendLogToUser1Addressread-writecurrentEmail address to which to send unit logs.
1.3.6.1.4.1.20677.2.3.4ScalarsendLogToUser2Addressread-writecurrentSecond email address to which to send unit logs.
1.3.6.1.4.1.20677.2.3.5ScalarsendAlertsToUser1Addressread-writecurrentEmail address to which to send unit alerts.
1.3.6.1.4.1.20677.2.3.6ScalarsendAlertsToUser2Addressread-writecurrentSecond email address to which to send unit alerts.
1.3.6.1.4.1.20677.2.3.7ScalarsendLogFrequencyread-writecurrentFrequency with which to send logs via email.
1.3.6.1.4.1.20677.2.3.8ScalarsendLogTimeread-writecurrentTime of day to send logs via email. Not applicable if sendLogFrequency is set to whenFull or never.
1.3.6.1.4.1.20677.2.3.9ScalaruserLogInLogOutread-writecurrentEnabled setting to log or send an alert when a user logs in or logs out of the serial, telnet, or web interfaces.
1.3.6.1.4.1.20677.2.3.10ScalaruserLogInLogOutFailedread-writecurrentEnabled setting to log or send an alert when a user attempts to log in but fails because of a username or password mismatch.
1.3.6.1.4.1.20677.2.3.11ScalaroutletActivityread-writecurrentEnabled setting to log or send an alert each time an outlet changes state.
1.3.6.1.4.1.20677.2.3.12ScalarsystemOnOffread-writecurrentEnabled setting to log or send an alert each time the unit powers up.
1.3.6.1.4.1.20677.2.3.13ScalaroutletSection1Alertread-writecurrentEnabled setting to send an email alert when section 1 thresholds are breached.
1.3.6.1.4.1.20677.2.3.14ScalaroutletSection2Alertread-writecurrentEnabled setting to send an email alert when section 2 thresholds are brached.
1.3.6.1.4.1.20677.2.3.15ScalaroutletSection3Alertread-writecurrentEnabled setting to send an email alert when section 3 thresholds are breached.
1.3.6.1.4.1.20677.2.3.16ScalartempSensor1Alertread-writecurrentEnabled setting to send an email alert when temperature sensor 1 thresholds are breached.
1.3.6.1.4.1.20677.2.3.17ScalartempSensor2Alertread-writecurrentEnabled setting to send an email alert when temperature sensor 2 thresholds are breached.
1.3.6.1.4.1.20677.2.3.18ScalarhumSensor1Alertread-writecurrentEnabled setting to send an email alert when humidity sensor thresholds are breached.
1.3.6.1.4.1.20677.2.3.19ScalarcontactClosure1Alertread-writecurrentEnabled setting to send an email alert when contact sensor 1 changes state.
1.3.6.1.4.1.20677.2.3.20ScalarcontactClosure2Alertread-writecurrentEnabled setting to send an email alert when contact sensor 2 changes state.
1.3.6.1.4.1.20677.2.3.21ScalarcontactClosure3Alertread-writecurrentEnabled setting to send an email alert when contact sensor 3 changes state.
1.3.6.1.4.1.20677.2.4NodeserialSettings
1.3.6.1.4.1.20677.2.4.1ScalarbaudRateread-writecurrentSerial baud rate, does not take effect unless unit is soft-rebooted.
1.3.6.1.4.1.20677.2.5NodetelnetSettings
1.3.6.1.4.1.20677.2.5.1ScalartelnetPortread-writecurrentTelnet interface port, default is 23.
1.3.6.1.4.1.20677.2.5.2ScalartelnetEnabledread-writecurrentEnabled setting for the telnet interface. This can be disabled for security.
1.3.6.1.4.1.20677.2.6NodeoutletMngt
1.3.6.1.4.1.20677.2.6.1NodeoutletConfig
1.3.6.1.4.1.20677.2.6.1.1Nodeoutlet1
1.3.6.1.4.1.20677.2.6.1.1.1Scalaroutlet1Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.1.2Scalaroutlet1PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.1.3Scalaroutlet1Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.1.4Scalaroutlet1SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.1.5Scalaroutlet1RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.2Nodeoutlet2
1.3.6.1.4.1.20677.2.6.1.2.1Scalaroutlet2Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.2.2Scalaroutlet2PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.2.3Scalaroutlet2Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.2.4Scalaroutlet2SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.2.5Scalaroutlet2RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.3Nodeoutlet3
1.3.6.1.4.1.20677.2.6.1.3.1Scalaroutlet3Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.3.2Scalaroutlet3PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.3.3Scalaroutlet3Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.3.4Scalaroutlet3SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.3.5Scalaroutlet3RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.4Nodeoutlet4
1.3.6.1.4.1.20677.2.6.1.4.1Scalaroutlet4Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.4.2Scalaroutlet4PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.4.3Scalaroutlet4Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.4.4Scalaroutlet4SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.4.5Scalaroutlet4RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.5Nodeoutlet5
1.3.6.1.4.1.20677.2.6.1.5.1Scalaroutlet5Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.5.2Scalaroutlet5PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.5.3Scalaroutlet5Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.5.4Scalaroutlet5SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.5.5Scalaroutlet5RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.6Nodeoutlet6
1.3.6.1.4.1.20677.2.6.1.6.1Scalaroutlet6Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.6.2Scalaroutlet6PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.6.3Scalaroutlet6Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.6.4Scalaroutlet6SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.6.5Scalaroutlet6RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.7Nodeoutlet7
1.3.6.1.4.1.20677.2.6.1.7.1Scalaroutlet7Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.7.2Scalaroutlet7PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.7.3Scalaroutlet7Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.7.4Scalaroutlet7SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.7.5Scalaroutlet7RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.8Nodeoutlet8
1.3.6.1.4.1.20677.2.6.1.8.1Scalaroutlet8Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.8.2Scalaroutlet8PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.8.3Scalaroutlet8Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.8.4Scalaroutlet8SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.8.5Scalaroutlet8RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.9Nodeoutlet9
1.3.6.1.4.1.20677.2.6.1.9.1Scalaroutlet9Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.9.2Scalaroutlet9PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.9.3Scalaroutlet9Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.9.4Scalaroutlet9SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.9.5Scalaroutlet9RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.10Nodeoutlet10
1.3.6.1.4.1.20677.2.6.1.10.1Scalaroutlet10Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.10.2Scalaroutlet10PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.10.3Scalaroutlet10Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.10.4Scalaroutlet10SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.10.5Scalaroutlet10RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.11Nodeoutlet11
1.3.6.1.4.1.20677.2.6.1.11.1Scalaroutlet11Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.11.2Scalaroutlet11PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.11.3Scalaroutlet11Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.11.4Scalaroutlet11SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.11.5Scalaroutlet11RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.12Nodeoutlet12
1.3.6.1.4.1.20677.2.6.1.12.1Scalaroutlet12Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.12.2Scalaroutlet12PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.12.3Scalaroutlet12Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.12.4Scalaroutlet12SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.12.5Scalaroutlet12RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.13Nodeoutlet13
1.3.6.1.4.1.20677.2.6.1.13.1Scalaroutlet13Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.13.2Scalaroutlet13PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.13.3Scalaroutlet13Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.13.4Scalaroutlet13SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.13.5Scalaroutlet13RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.14Nodeoutlet14
1.3.6.1.4.1.20677.2.6.1.14.1Scalaroutlet14Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.14.2Scalaroutlet14PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.14.3Scalaroutlet14Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.14.4Scalaroutlet14SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.14.5Scalaroutlet14RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.15Nodeoutlet15
1.3.6.1.4.1.20677.2.6.1.15.1Scalaroutlet15Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.15.2Scalaroutlet15PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.15.3Scalaroutlet15Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.15.4Scalaroutlet15SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.15.5Scalaroutlet15RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.16Nodeoutlet16
1.3.6.1.4.1.20677.2.6.1.16.1Scalaroutlet16Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.16.2Scalaroutlet16PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.16.3Scalaroutlet16Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.16.4Scalaroutlet16SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.16.5Scalaroutlet16RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.17Nodeoutlet17
1.3.6.1.4.1.20677.2.6.1.17.1Scalaroutlet17Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.17.2Scalaroutlet17PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.17.3Scalaroutlet17Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.17.4Scalaroutlet17SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.17.5Scalaroutlet17RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.18Nodeoutlet18
1.3.6.1.4.1.20677.2.6.1.18.1Scalaroutlet18Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.18.2Scalaroutlet18PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.18.3Scalaroutlet18Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.18.4Scalaroutlet18SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.18.5Scalaroutlet18RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.19Nodeoutlet19
1.3.6.1.4.1.20677.2.6.1.19.1Scalaroutlet19Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.19.2Scalaroutlet19PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.19.3Scalaroutlet19Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.19.4Scalaroutlet19SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.19.5Scalaroutlet19RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.20Nodeoutlet20
1.3.6.1.4.1.20677.2.6.1.20.1Scalaroutlet20Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.20.2Scalaroutlet20PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.20.3Scalaroutlet20Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.20.4Scalaroutlet20SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.20.5Scalaroutlet20RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.21Nodeoutlet21
1.3.6.1.4.1.20677.2.6.1.21.1Scalaroutlet21Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.21.2Scalaroutlet21PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.21.3Scalaroutlet21Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.21.4Scalaroutlet21SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.21.5Scalaroutlet21RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.22Nodeoutlet22
1.3.6.1.4.1.20677.2.6.1.22.1Scalaroutlet22Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.22.2Scalaroutlet22PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.22.3Scalaroutlet22Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.22.4Scalaroutlet22SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.22.5Scalaroutlet22RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.23Nodeoutlet23
1.3.6.1.4.1.20677.2.6.1.23.1Scalaroutlet23Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.23.2Scalaroutlet23PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.23.3Scalaroutlet23Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.23.4Scalaroutlet23SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.23.5Scalaroutlet23RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.24Nodeoutlet24
1.3.6.1.4.1.20677.2.6.1.24.1Scalaroutlet24Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.24.2Scalaroutlet24PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.24.3Scalaroutlet24Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.24.4Scalaroutlet24SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.24.5Scalaroutlet24RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.25Nodeoutlet25
1.3.6.1.4.1.20677.2.6.1.25.1Scalaroutlet25Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.25.2Scalaroutlet25PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.25.3Scalaroutlet25Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.25.4Scalaroutlet25SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.25.5Scalaroutlet25RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.26Nodeoutlet26
1.3.6.1.4.1.20677.2.6.1.26.1Scalaroutlet26Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.26.2Scalaroutlet26PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.26.3Scalaroutlet26Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.26.4Scalaroutlet26SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.26.5Scalaroutlet26RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.27Nodeoutlet27
1.3.6.1.4.1.20677.2.6.1.27.1Scalaroutlet27Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.27.2Scalaroutlet27PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.27.3Scalaroutlet27Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.27.4Scalaroutlet27SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.27.5Scalaroutlet27RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.28Nodeoutlet28
1.3.6.1.4.1.20677.2.6.1.28.1Scalaroutlet28Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.28.2Scalaroutlet28PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.28.3Scalaroutlet28Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.28.4Scalaroutlet28SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.28.5Scalaroutlet28RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.29Nodeoutlet29
1.3.6.1.4.1.20677.2.6.1.29.1Scalaroutlet29Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.29.2Scalaroutlet29PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.29.3Scalaroutlet29Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.29.4Scalaroutlet29SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.29.5Scalaroutlet29RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.30Nodeoutlet30
1.3.6.1.4.1.20677.2.6.1.30.1Scalaroutlet30Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.30.2Scalaroutlet30PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.30.3Scalaroutlet30Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.30.4Scalaroutlet30SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.30.5Scalaroutlet30RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.31Nodeoutlet31
1.3.6.1.4.1.20677.2.6.1.31.1Scalaroutlet31Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.31.2Scalaroutlet31PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.31.3Scalaroutlet31Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.31.4Scalaroutlet31SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.31.5Scalaroutlet31RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.32Nodeoutlet32
1.3.6.1.4.1.20677.2.6.1.32.1Scalaroutlet32Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.32.2Scalaroutlet32PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.32.3Scalaroutlet32Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.32.4Scalaroutlet32SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.32.5Scalaroutlet32RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.33Nodeoutlet33
1.3.6.1.4.1.20677.2.6.1.33.1Scalaroutlet33Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.33.2Scalaroutlet33PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.33.3Scalaroutlet33Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.33.4Scalaroutlet33SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.33.5Scalaroutlet33RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.34Nodeoutlet34
1.3.6.1.4.1.20677.2.6.1.34.1Scalaroutlet34Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.34.2Scalaroutlet34PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.34.3Scalaroutlet34Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.34.4Scalaroutlet34SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.34.5Scalaroutlet34RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.35Nodeoutlet35
1.3.6.1.4.1.20677.2.6.1.35.1Scalaroutlet35Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.35.2Scalaroutlet35PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.35.3Scalaroutlet35Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.35.4Scalaroutlet35SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.35.5Scalaroutlet35RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.1.36Nodeoutlet36
1.3.6.1.4.1.20677.2.6.1.36.1Scalaroutlet36Nameread-writecurrentDescriptive outlet name
1.3.6.1.4.1.20677.2.6.1.36.2Scalaroutlet36PingIpAddressread-writecurrentPing watchdog IP address
1.3.6.1.4.1.20677.2.6.1.36.3Scalaroutlet36Linkread-writecurrentURL of web configuration interface for the device connected to this outlet.
1.3.6.1.4.1.20677.2.6.1.36.4Scalaroutlet36SequenceTimeread-writecurrentTime in seconds for the outlet to delay turning on after a Sequence On command is issued.
1.3.6.1.4.1.20677.2.6.1.36.5Scalaroutlet36RebootTimeread-writecurrentTime in seconds for the outlet to remain off when a Reboot command is issued.
1.3.6.1.4.1.20677.2.6.2NodeoutletControl
1.3.6.1.4.1.20677.2.6.2.1ScalarglobalCommandread-writecurrentIssue a command to all outlets on this unit.
1.3.6.1.4.1.20677.2.6.2.2Scalaroutlet1Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.3Scalaroutlet2Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.4Scalaroutlet3Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.5Scalaroutlet4Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.6Scalaroutlet5Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.7Scalaroutlet6Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.8Scalaroutlet7Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.9Scalaroutlet8Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.10Scalaroutlet9Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.11Scalaroutlet10Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.12Scalaroutlet11Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.13Scalaroutlet12Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.14Scalaroutlet13Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.15Scalaroutlet14Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.16Scalaroutlet15Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.17Scalaroutlet16Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.18Scalaroutlet17Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.19Scalaroutlet18Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.20Scalaroutlet19Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.21Scalaroutlet20Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.22Scalaroutlet21Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.23Scalaroutlet22Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.24Scalaroutlet23Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.25Scalaroutlet24Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.26Scalaroutlet25Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.27Scalaroutlet26Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.28Scalaroutlet27Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.29Scalaroutlet28Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.30Scalaroutlet29Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.31Scalaroutlet30Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.32Scalaroutlet31Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.33Scalaroutlet32Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.34Scalaroutlet33Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.35Scalaroutlet34Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.36Scalaroutlet35Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.2.37Scalaroutlet36Commandread-writecurrentIssue an outlet command
1.3.6.1.4.1.20677.2.6.3NodeoutletStatus
1.3.6.1.4.1.20677.2.6.3.1Scalaroutlet1Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.2Scalaroutlet2Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.3Scalaroutlet3Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.4Scalaroutlet4Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.5Scalaroutlet5Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.6Scalaroutlet6Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.7Scalaroutlet7Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.8Scalaroutlet8Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.9Scalaroutlet9Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.10Scalaroutlet10Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.11Scalaroutlet11Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.12Scalaroutlet12Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.13Scalaroutlet13Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.14Scalaroutlet14Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.15Scalaroutlet15Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.16Scalaroutlet16Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.17Scalaroutlet17Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.18Scalaroutlet18Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.19Scalaroutlet19Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.20Scalaroutlet20Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.21Scalaroutlet21Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.22Scalaroutlet22Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.23Scalaroutlet23Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.24Scalaroutlet24Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.25Scalaroutlet25Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.26Scalaroutlet26Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.27Scalaroutlet27Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.28Scalaroutlet28Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.29Scalaroutlet29Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.30Scalaroutlet30Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.31Scalaroutlet31Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.32Scalaroutlet32Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.33Scalaroutlet33Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.34Scalaroutlet34Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.35Scalaroutlet35Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.6.3.36Scalaroutlet36Statusread-onlycurrentGet the outlet status
1.3.6.1.4.1.20677.2.7NodesnmpSettings
1.3.6.1.4.1.20677.2.7.1ScalarpublicCommunityNamenot-accessibleobsoleteEnter the read-only community name. Default public
1.3.6.1.4.1.20677.2.7.2ScalarprivateCommunityNamenot-accessibleobsoleteEnter the read-write community name. Default private
1.3.6.1.4.1.20677.2.7.3ScalartrapCommunityNamenot-accessibleobsoleteEnter the Trap community name. Default public
1.3.6.1.4.1.20677.2.7.4ScalarpublicCommunityPasswordnot-accessibleobsoleteEnter the read-only community password. Default public
1.3.6.1.4.1.20677.2.7.5ScalarprivateCommunityPasswordnot-accessibleobsoleteEnter the read-write community password. Default private
1.3.6.1.4.1.20677.2.7.6ScalartrapIpAddressread-writecurrentEnter the IP address to which to send SNMP traps.
1.3.6.1.4.1.20677.2.7.7ScalarsnmpEnablednot-accessibleobsoleteEnabled setting for SNMP interface
1.3.6.1.4.1.20677.2.7.8NodesnmpTraps
1.3.6.1.4.1.20677.2.7.8.1ScalartrapUserLoginLogoutread-writecurrentEnabled setting to send an SNMP trap when a user logs in/out of the serial, telnet, or web interfaces.
1.3.6.1.4.1.20677.2.7.8.2ScalartrapFailedLoginread-writecurrentEnabled setting to send an SNMP trap when a user fails to log into the serial, telnet, or web interfaces because of a username or password mismatch.
1.3.6.1.4.1.20677.2.7.8.3ScalartrapOutletActivityread-writecurrentEnabled setting to send an SNMP trap whenever an outlet changes state.
1.3.6.1.4.1.20677.2.7.8.4ScalartrapSystemOnOffread-writecurrentEnabled setting to send an SNMP trap when the PDU powers up.
1.3.6.1.4.1.20677.2.7.8.5ScalartrapOutletSection1Thresholdread-writecurrentEnabled setting to send an SNMP trap when the section 1 thresholds are breached.
1.3.6.1.4.1.20677.2.7.8.6ScalartrapOutletSection2Thresholdread-writecurrentEnabled setting to send an SNMP trap when the section 2 thresholds are breached.
1.3.6.1.4.1.20677.2.7.8.7ScalartrapOutletSection3Thresholdread-writecurrentEnabled setting to send an SNMP trap when the section 3 thresholds are breached.
1.3.6.1.4.1.20677.2.7.8.8ScalartrapTemperatureSensor1Thresholdread-writecurrentEnabled setting to send an SNMP trap when the temperature 1 sensor thresholds are breached.
1.3.6.1.4.1.20677.2.7.8.9ScalartrapTemperatureSensor2Thresholdread-writecurrentEnabled setting to send an SNMP trap when the temperature 2 sensor thresholds are breached.
1.3.6.1.4.1.20677.2.7.8.10ScalartrapHumiditySensorThresholdread-writecurrentEnabled setting to send an SNMP trap when the humidity sensor thresholds are breached.
1.3.6.1.4.1.20677.2.7.8.11ScalartrapContactClosure1Thresholdread-writecurrentEnabled setting to send an SNMP trap when the contact sensor 1 state changes.
1.3.6.1.4.1.20677.2.7.8.12ScalartrapContactClosure2Thresholdread-writecurrentEnabled setting to send an SNMP trap when the contact sensor 2 state changes.
1.3.6.1.4.1.20677.2.7.8.13ScalartrapContactClosure3Thresholdread-writecurrentEnabled setting to send an SNMP trap when the contact sensor 3 state changes.
1.3.6.1.4.1.20677.2.8NodeenvironmentalSettings
1.3.6.1.4.1.20677.2.8.1NodetemperatureSensorConfig
1.3.6.1.4.1.20677.2.8.1.1NodetempSensor1
1.3.6.1.4.1.20677.2.8.1.1.1ScalartempSensor1Nameread-writecurrentDescriptive sensor name
1.3.6.1.4.1.20677.2.8.1.1.2ScalartempSensor1Enableread-writecurrentWhen disabled, the sensor measurement is not displayed and the thresholds are ignored.
1.3.6.1.4.1.20677.2.8.1.1.3ScalartempSensor1HighThreshread-writecurrentSensor high threshold
1.3.6.1.4.1.20677.2.8.1.1.4ScalartempSensor1LowThreshread-writecurrentSensor low threshold
1.3.6.1.4.1.20677.2.8.1.1.5ScalartempSensor1ControlOutletread-writecurrentEnabled setting to control an outlet or group based on the sensor thresholds.
1.3.6.1.4.1.20677.2.8.1.1.6ScalartempSensor1OutletNameread-writecurrentOutlet or group name to control based on the sensor measurement.
1.3.6.1.4.1.20677.2.8.1.1.7ScalartempSensor1OutletStateread-writecurrentturnOutletOn setting will turn the outlet/group on when the thresholds are breached and off when between the thresholds. turnOutletOff setting will turn the ou…
1.3.6.1.4.1.20677.2.8.1.2NodetempSensor2
1.3.6.1.4.1.20677.2.8.1.2.1ScalartempSensor2Nameread-writecurrentDescriptive sensor name
1.3.6.1.4.1.20677.2.8.1.2.2ScalartempSensor2Enableread-writecurrentWhen disabled, the sensor measurement is not displayed and the thresholds are ignored.
1.3.6.1.4.1.20677.2.8.1.2.3ScalartempSensor2HighThreshread-writecurrentSensor high threshold
1.3.6.1.4.1.20677.2.8.1.2.4ScalartempSensor2LowThreshread-writecurrentSensor low threshold
1.3.6.1.4.1.20677.2.8.1.2.5ScalartempSensor2ControlOutletread-writecurrentEnabled setting to control an outlet or group based on the sensor thresholds.
1.3.6.1.4.1.20677.2.8.1.2.6ScalartempSensor2OutletNameread-writecurrentOutlet or group name to control based on the sensor measurement.
1.3.6.1.4.1.20677.2.8.1.2.7ScalartempSensor2OutletStateread-writecurrentturnOutletOn setting will turn the outlet/group on when the thresholds are breached and off when between the thresholds. turnOutletOff setting will turn the ou…
1.3.6.1.4.1.20677.2.8.2NodehumiditySensorConfig
1.3.6.1.4.1.20677.2.8.2.1NodehumSensor1
1.3.6.1.4.1.20677.2.8.2.1.1ScalarhumSensor1Nameread-writecurrentDescriptive sensor name
1.3.6.1.4.1.20677.2.8.2.1.2ScalarhumSensor1Enableread-writecurrentWhen disabled, the sensor measurement is not displayed and the thresholds are ignored.
1.3.6.1.4.1.20677.2.8.2.1.3ScalarhumSensor1HighThreshread-writecurrentSensor high threshold
1.3.6.1.4.1.20677.2.8.2.1.4ScalarhumSensor1LowThreshread-writecurrentSensor low threshold
1.3.6.1.4.1.20677.2.8.2.1.5ScalarhumSensor1ControlOutletread-writecurrentEnabled setting to control an outlet or group based on the sensor thresholds.
1.3.6.1.4.1.20677.2.8.2.1.6ScalarhumSensor1OutletNameread-writecurrentOutlet or group name to control based on the sensor measurement.
1.3.6.1.4.1.20677.2.8.2.1.7ScalarhumSensor1OutletStateread-writecurrentturnOutletOn setting will turn the outlet/group on when the thresholds are breached and off when between the thresholds. turnOutletOff setting will turn the ou…
1.3.6.1.4.1.20677.2.8.3NodecontactClosureConfig
1.3.6.1.4.1.20677.2.8.3.1NodecontactClosure1
1.3.6.1.4.1.20677.2.8.3.1.1ScalarcontactClosure1Nameread-writecurrentDescriptive sensor name
1.3.6.1.4.1.20677.2.8.3.1.2ScalarcontactClosure1Enableread-writecurrentWhen disabled, the sensor measurement is not displayed and the contact state is ignored.
1.3.6.1.4.1.20677.2.8.3.1.3ScalarcontactClosure1ControlOutletread-writecurrentEnabled setting to control an outlet or group based on the contact state.
1.3.6.1.4.1.20677.2.8.3.1.4ScalarcontactClosure1OutletNameread-writecurrentOutlet or group name to control based on the contact state.
1.3.6.1.4.1.20677.2.8.3.1.5ScalarcontactClosure1OutletStateread-writecurrentturnOutletOn setting will turn the outlet/group on when the contact is closed and off when the contact is open. turnOutletOff setting will turn the outlet/grou…
1.3.6.1.4.1.20677.2.8.3.2NodecontactClosure2
1.3.6.1.4.1.20677.2.8.3.2.1ScalarcontactClosure2Nameread-writecurrentDescriptive sensor name
1.3.6.1.4.1.20677.2.8.3.2.2ScalarcontactClosure2Enableread-writecurrentWhen disabled, the sensor measurement is not displayed and the contact state is ignored.
1.3.6.1.4.1.20677.2.8.3.2.3ScalarcontactClosure2ControlOutletread-writecurrentEnabled setting to control an outlet or group based on the contact state.
1.3.6.1.4.1.20677.2.8.3.2.4ScalarcontactClosure2OutletNameread-writecurrentOutlet or group name to control based on the contact state.
1.3.6.1.4.1.20677.2.8.3.2.5ScalarcontactClosure2OutletStateread-writecurrentturnOutletOn setting will turn the outlet/group on when the contact is closed and off when the contact is open. turnOutletOff setting will turn the outlet/grou…
1.3.6.1.4.1.20677.2.8.3.3NodecontactClosure3
1.3.6.1.4.1.20677.2.8.3.3.1ScalarcontactClosure3Nameread-writecurrentDescriptive sensor name
1.3.6.1.4.1.20677.2.8.3.3.2ScalarcontactClosure3Enableread-writecurrentWhen disabled, the sensor measurement is not displayed and the contact state is ignored.
1.3.6.1.4.1.20677.2.8.3.3.3ScalarcontactClosure3ControlOutletread-writecurrentEnabled setting to control an outlet or group based on the contact state.
1.3.6.1.4.1.20677.2.8.3.3.4ScalarcontactClosure3OutletNameread-writecurrentOutlet or group name to control based on the contact state.
1.3.6.1.4.1.20677.2.8.3.3.5ScalarcontactClosure3OutletStateread-writecurrentturnOutletOn setting will turn the outlet/group on when the contact is closed and off when the contact is open. turnOutletOff setting will turn the outlet/grou…
1.3.6.1.4.1.20677.2.8.4NodeoutletSectionConfig
1.3.6.1.4.1.20677.2.8.4.1NodeoutletSection1Config
1.3.6.1.4.1.20677.2.8.4.1.1ScalaroutletSection1VoltageHighThresholdread-writecurrentUpper threshold for section voltage measurement
1.3.6.1.4.1.20677.2.8.4.1.2ScalaroutletSection1VoltageLowThresholdread-writecurrentLower threshold for section voltage measurement
1.3.6.1.4.1.20677.2.8.4.1.3ScalaroutletSection1CurrentHighThresholdread-writecurrentUpper threshold for section current measurement
1.3.6.1.4.1.20677.2.8.4.1.4ScalaroutletSection1CurrentLowThresholdread-writecurrentLower threshold for section current measurement
1.3.6.1.4.1.20677.2.8.4.1.5ScalaroutletSection1ControlOutletread-writecurrentEnabled setting to control an outlet or group based on the section voltage and current thresholds.
1.3.6.1.4.1.20677.2.8.4.1.6ScalaroutletSection1OutletNameread-writecurrentOutlet or group name to control based on the section voltage and current measurement.
1.3.6.1.4.1.20677.2.8.4.2NodeoutletSection2Config
1.3.6.1.4.1.20677.2.8.4.2.1ScalaroutletSection2VoltageHighThresholdread-writecurrentUpper threshold for section voltage measurement
1.3.6.1.4.1.20677.2.8.4.2.2ScalaroutletSection2VoltageLowThresholdread-writecurrentLower threshold for section voltage measurement
1.3.6.1.4.1.20677.2.8.4.2.3ScalaroutletSection2CurrentHighThresholdread-writecurrentUpper threshold for section current measurement
1.3.6.1.4.1.20677.2.8.4.2.4ScalaroutletSection2CurrentLowThresholdread-writecurrentLower threshold for section current measurement
1.3.6.1.4.1.20677.2.8.4.2.5ScalaroutletSection2ControlOutletread-writecurrentEnabled setting to control an outlet or group based on the section voltage and current thresholds.
1.3.6.1.4.1.20677.2.8.4.2.6ScalaroutletSection2OutletNameread-writecurrentOutlet or group name to control based on the section voltage and current measurement.
1.3.6.1.4.1.20677.2.8.4.3NodeoutletSection3Config
1.3.6.1.4.1.20677.2.8.4.3.1ScalaroutletSection3VoltageHighThresholdread-writecurrentUpper threshold for section voltage measurement
1.3.6.1.4.1.20677.2.8.4.3.2ScalaroutletSection3VoltageLowThresholdread-writecurrentLower threshold for section voltage measurement
1.3.6.1.4.1.20677.2.8.4.3.3ScalaroutletSection3CurrentHighThresholdread-writecurrentUpper threshold for section current measurement
1.3.6.1.4.1.20677.2.8.4.3.4ScalaroutletSection3CurrentLowThresholdread-writecurrentLower threshold for section current measurement
1.3.6.1.4.1.20677.2.8.4.3.5ScalaroutletSection3ControlOutletread-writecurrentEnabled setting to control an outlet or group based on the section voltage and current thresholds.
1.3.6.1.4.1.20677.2.8.4.3.6ScalaroutletSection3OutletNameread-writecurrentOutlet or group name to control based on the section voltage and current measurement.
1.3.6.1.4.1.20677.2.8.4.4NodeoutletSection4Config
1.3.6.1.4.1.20677.2.8.4.4.1ScalaroutletSection4VoltageHighThresholdread-writecurrentUpper threshold for section voltage measurement
1.3.6.1.4.1.20677.2.8.4.4.2ScalaroutletSection4VoltageLowThresholdread-writecurrentLower threshold for section voltage measurement
1.3.6.1.4.1.20677.2.8.4.4.3ScalaroutletSection4CurrentHighThresholdread-writecurrentUpper threshold for section current measurement
1.3.6.1.4.1.20677.2.8.4.4.4ScalaroutletSection4CurrentLowThresholdread-writecurrentLower threshold for section current measurement
1.3.6.1.4.1.20677.2.8.4.4.5ScalaroutletSection4ControlOutletread-writecurrentEnabled setting to control an outlet or group based on the section voltage and current thresholds.
1.3.6.1.4.1.20677.2.8.4.4.6ScalaroutletSection4OutletNameread-writecurrentOutlet or group name to control based on the section voltage and current measurement.
1.3.6.1.4.1.20677.2.8.4.5NodeoutletSection5Config
1.3.6.1.4.1.20677.2.8.4.5.1ScalaroutletSection5VoltageHighThresholdread-writecurrentUpper threshold for section voltage measurement
1.3.6.1.4.1.20677.2.8.4.5.2ScalaroutletSection5VoltageLowThresholdread-writecurrentLower threshold for section voltage measurement
1.3.6.1.4.1.20677.2.8.4.5.3ScalaroutletSection5CurrentHighThresholdread-writecurrentUpper threshold for section current measurement
1.3.6.1.4.1.20677.2.8.4.5.4ScalaroutletSection5CurrentLowThresholdread-writecurrentLower threshold for section current measurement
1.3.6.1.4.1.20677.2.8.4.5.5ScalaroutletSection5ControlOutletread-writecurrentEnabled setting to control an outlet or group based on the section voltage and current thresholds.
1.3.6.1.4.1.20677.2.8.4.5.6ScalaroutletSection5OutletNameread-writecurrentOutlet or group name to control based on the section voltage and current measurement.
1.3.6.1.4.1.20677.2.8.4.6NodeoutletSection6Config
1.3.6.1.4.1.20677.2.8.4.6.1ScalaroutletSection6VoltageHighThresholdread-writecurrentUpper threshold for section voltage measurement
1.3.6.1.4.1.20677.2.8.4.6.2ScalaroutletSection6VoltageLowThresholdread-writecurrentLower threshold for section voltage measurement
1.3.6.1.4.1.20677.2.8.4.6.3ScalaroutletSection6CurrentHighThresholdread-writecurrentUpper threshold for section current measurement
1.3.6.1.4.1.20677.2.8.4.6.4ScalaroutletSection6CurrentLowThresholdread-writecurrentLower threshold for section current measurement
1.3.6.1.4.1.20677.2.8.4.6.5ScalaroutletSection6ControlOutletread-writecurrentEnabled setting to control an outlet or group based on the section voltage and current thresholds.
1.3.6.1.4.1.20677.2.8.4.6.6ScalaroutletSection6OutletNameread-writecurrentOutlet or group name to control based on the section voltage and current measurement.
1.3.6.1.4.1.20677.2.8.5NodecurrentSensorValues
1.3.6.1.4.1.20677.2.8.5.1ScalartempSensor1Tempread-onlycurrentTemperature sensor measurement (units are indicated by the fahrenheitOrCelsius leaf under the unitConfig branch)
1.3.6.1.4.1.20677.2.8.5.2ScalartempSensor2Tempread-onlycurrentTemperature sensor measurement (units are indicated by the fahrenheitOrCelsius leaf under the unitConfig branch)
1.3.6.1.4.1.20677.2.8.5.3ScalarhumSensor1Humidityread-onlycurrentHumidity sensor measurement (percent relative humidity)
1.3.6.1.4.1.20677.2.8.5.4ScalarcontactClosure1Stateread-onlycurrentContact sensor state
1.3.6.1.4.1.20677.2.8.5.5ScalarcontactClosure2Stateread-onlycurrentContact sensor state
1.3.6.1.4.1.20677.2.8.5.6ScalarcontactClosure3Stateread-onlycurrentContact sensor state
1.3.6.1.4.1.20677.2.8.6NodecurrentOutletSectionValues
1.3.6.1.4.1.20677.2.8.6.1NodeoutletSection1
1.3.6.1.4.1.20677.2.8.6.1.1ScalaroutletSection1Voltageread-onlycurrentVoltage measurement 1. This is either the section 1 voltage, the Line X-Y voltage, or the Phase X-N voltage, depending on the PDU hardware.
1.3.6.1.4.1.20677.2.8.6.1.2ScalaroutletSection1Currentread-onlycurrentCurrent measurement 1. This is either the section 1 current or the Phase X current, depending on the PDU hardware.
1.3.6.1.4.1.20677.2.8.6.1.3ScalaroutletSection1Varead-onlycurrentSection 1 VA (or phase X VA, depending on the PDU hardware).
1.3.6.1.4.1.20677.2.8.6.2NodeoutletSection2
1.3.6.1.4.1.20677.2.8.6.2.1ScalaroutletSection2Voltageread-onlycurrentVoltage measurement 2. This is either the section 2 voltage, the Line Y-Z voltage, or the Phase Y-N voltage, depending on the PDU hardware.
1.3.6.1.4.1.20677.2.8.6.2.2ScalaroutletSection2Currentread-onlycurrentCurrent measurement 2. This is either the section 2 current or the Phase Y current, depending on the PDU hardware.
1.3.6.1.4.1.20677.2.8.6.2.3ScalaroutletSection2Varead-onlycurrentSection 2 VA (or phase Y VA, depending on the PDU hardware).
1.3.6.1.4.1.20677.2.8.6.3NodeoutletSection3
1.3.6.1.4.1.20677.2.8.6.3.1ScalaroutletSection3Voltageread-onlycurrentVoltage measurement 3. This is either the section 3 voltage, the Line Z-X voltage, or the Phase Z-N voltage, depending on the PDU hardware.
1.3.6.1.4.1.20677.2.8.6.3.2ScalaroutletSection3Currentread-onlycurrentCurrent measurement 3. This is either the section 3 current or the Phase Z current, depending on the PDU hardware.
1.3.6.1.4.1.20677.2.8.6.3.3ScalaroutletSection3Varead-onlycurrentSection 3 VA (or phase Z VA, depending on the PDU hardware).
1.3.6.1.4.1.20677.2.8.6.4Nodetotal
1.3.6.1.4.1.20677.2.8.6.4.1ScalartotalVoltageread-onlyobsoleteNone
1.3.6.1.4.1.20677.2.8.6.4.2ScalartotalCurrentread-onlycurrentSum of current for all outlet sections (or phases)
1.3.6.1.4.1.20677.2.8.6.4.3ScalartotalVaread-onlycurrentTotal PDU VA
1.3.6.1.4.1.20677.2.8.6.5NodeoutletSection4
1.3.6.1.4.1.20677.2.8.6.5.1ScalaroutletSection4Voltageread-onlycurrentVoltage measurement 4 (section 4 voltage). This object will not be present if the PDU hardware measures Line-to-Line voltage or Phase voltage.
1.3.6.1.4.1.20677.2.8.6.5.2ScalaroutletSection4Currentread-onlycurrentCurrent measurement 4. This is the section 4 current.
1.3.6.1.4.1.20677.2.8.6.5.3ScalaroutletSection4Varead-onlycurrentSection 4 VA
1.3.6.1.4.1.20677.2.8.6.6NodeoutletSection5
1.3.6.1.4.1.20677.2.8.6.6.1ScalaroutletSection5Voltageread-onlycurrentVoltage measurement 5 (section 5 voltage). This object will not be present if the PDU hardware measures Line-to-Line voltage or Phase voltage.
1.3.6.1.4.1.20677.2.8.6.6.2ScalaroutletSection5Currentread-onlycurrentCurrent measurement 5. This is the section 5 current.
1.3.6.1.4.1.20677.2.8.6.6.3ScalaroutletSection5Varead-onlycurrentSection 5 VA
1.3.6.1.4.1.20677.2.8.6.7NodeoutletSection6
1.3.6.1.4.1.20677.2.8.6.7.1ScalaroutletSection6Voltageread-onlycurrentVoltage measurement 6 (section 6 voltage). This object will not be present if the PDU hardware measures Line-to-Line voltage or Phase voltage.
1.3.6.1.4.1.20677.2.8.6.7.2ScalaroutletSection6Currentread-onlycurrentCurrent measurement 6. This is the section 6 current.
1.3.6.1.4.1.20677.2.8.6.7.3ScalaroutletSection6Varead-onlycurrentSection 6 VA
1.3.6.1.4.1.20677.2.9Nodeevents
1.3.6.1.4.1.20677.2.9.1NotificationnotifyOutletStatecurrentOutlet state has changed.
1.3.6.1.4.1.20677.2.9.2NotificationnotifyCurrentThresholdcurrentCurrent measurement has exceeded a threshold or returned from crossing a threshold.
1.3.6.1.4.1.20677.2.9.3NotificationnotifyVoltageThresholdcurrentVoltage measurement has exceeded a threshold or returned from crossing a threshold.
1.3.6.1.4.1.20677.2.9.4NotificationnotifyTempSensorThresholdcurrentTemperature measurement has exceeded a threshold or returned from crossing a threshold.
1.3.6.1.4.1.20677.2.9.5NotificationnotifyHumidSensorThresholdcurrentHumidity measurement has exceeded a threshold or returned from crossing a threshold.
1.3.6.1.4.1.20677.2.9.6NotificationnotifyContactSensorThresholdcurrentContact sensor has changed state.
1.3.6.1.4.1.20677.2.9.7NotificationnotifyUserLogincurrentA user has logged in.
1.3.6.1.4.1.20677.2.9.8NotificationnotifyUserLogoutcurrentA user has logged out.
1.3.6.1.4.1.20677.2.9.9NotificationnotifyFailedLogincurrentA login failure occurred.
1.3.6.1.4.1.20677.2.9.10NotificationnotifyOutletWatchdogFailedcurrentAn outlet watchdog has failed and the corresponding outlet is being rebooted.
1.3.6.1.4.1.20677.2.10NodeeventInfo
1.3.6.1.4.1.20677.2.10.1ScalarinfoItemIdxaccessible-for-notifycurrentNumerical index of the item that caused the notification. For example, if the notification was related to the state of outlet 5, this value will be 5 no matter…
1.3.6.1.4.1.20677.2.10.2ScalarinfoItemNameaccessible-for-notifycurrentTextual name of the item that caused the notification. For example, if an outlet state change caused the notification, this will be the customized name of the …
1.3.6.1.4.1.20677.2.10.3ScalarinfoOutletStateaccessible-for-notifycurrentThe new state of an outlet.
1.3.6.1.4.1.20677.2.10.4ScalarinfoThresholdStateaccessible-for-notifycurrentThe new state of a measurement that has upper and lower thresholds.
1.3.6.1.4.1.20677.2.10.5ScalarinfoThresholdValueaccessible-for-notifycurrentThe threshold which has been crossed.
1.3.6.1.4.1.20677.2.10.6ScalarinfoMeasuredValueaccessible-for-notifycurrentThe actual measured value.
1.3.6.1.4.1.20677.2.10.7ScalarinfoContactStateaccessible-for-notifycurrentThe new state of a contact switch sensor.
1.3.6.1.4.1.20677.2.10.8ScalarinfoUserNameaccessible-for-notifycurrentLogin name of a user.
1.3.6.1.4.1.20677.2.25Nodeconformance
1.3.6.1.4.1.20677.2.25.1CompliancecompliancescurrentThe requirements for conforming to the Switched ePDU MIB.
1.3.6.1.4.1.20677.2.25.2ComplianceoldCompliancesdeprecatedDeprecated requirements for conforming to the Switched ePDU MIB.
1.3.6.1.4.1.20677.2.25.3ComplianceobsoleteCompliancesobsoleteObsoleted requirements for conforming to the Switched ePDU MIB.
1.3.6.1.4.1.20677.2.25.5Nodegroups
1.3.6.1.4.1.20677.2.25.5.1GroupallObjectscurrentThe object group.
1.3.6.1.4.1.20677.2.25.5.2GroupoldObjectsdeprecatedThe deprecated objects group.
1.3.6.1.4.1.20677.2.25.5.3GroupobsoleteObjectsobsoleteThe obsoleted objects group.
1.3.6.1.4.1.20677.2.25.5.4GroupallNotificationscurrentThe notifications group.