MIB Viewer

EATON-PDU-MIB

94 objects
The MIB module for Eaton PDUs (Power Distribution Units). Copyright (C) Eaton Corporation (2007).
Imported Objects
EATON-OIDSpduAgent
SNMPv2-CONFMODULE-COMPLIANCE OBJECT-GROUP
SNMPv2-SMIInteger32 MODULE-IDENTITY OBJECT-TYPE
SNMPv2-TCDisplayString TEXTUAL-CONVENTION
OIDNameAccessStatusDescription
1.3.6.1.4.1.534.6.6.4IdentityeatonPduMIBThe MIB module for Eaton PDUs (Power Distribution Units). Copyright (C) Eaton Corporation (2007).
1.3.6.1.4.1.534.6.6.4.1NodeeatonPduMIBObjects
1.3.6.1.4.1.534.6.6.4.1.1NodemainPdu
1.3.6.1.4.1.534.6.6.4.1.1.1NodepduNameplate
1.3.6.1.4.1.534.6.6.4.1.1.1.1ScalarpduRatingVAread-onlycurrentThe full VA rating of this PDU (for all phases).
1.3.6.1.4.1.534.6.6.4.1.1.1.2ScalarpduNominalOutputVoltageread-onlycurrentThe nominal Output Voltage of this PDU (as distributed to the panels). May differ from the nominal Input Voltage if the PDU has an input transformer. This is e…
1.3.6.1.4.1.534.6.6.4.1.1.1.3ScalarpduNumPhasesread-onlycurrentThe number of lines (phases) for this PDU. The number of Input phases must equal the number of Output phases.
1.3.6.1.4.1.534.6.6.4.1.1.1.4ScalarpduNumPanelsread-onlycurrentThe number of panels or subfeeds contained in this PDU system. This determines the number of rows found in the panel tables.
1.3.6.1.4.1.534.6.6.4.1.1.2NodepduInput
1.3.6.1.4.1.534.6.6.4.1.1.2.1ScalarpduFrequencyread-onlycurrentThe present frequency reading for the full PDU.
1.3.6.1.4.1.534.6.6.4.1.1.2.2ScalarpduInputVAread-onlycurrentThe present VA input demand of the full PDU system.
1.3.6.1.4.1.534.6.6.4.1.1.2.3ScalarpduInputPowerread-onlycurrentThe present input power demand of the full PDU system.
1.3.6.1.4.1.534.6.6.4.1.1.2.4ScalarpduInputPowerFactorread-onlycurrentThe input power factor for the full PDU system. Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf.
1.3.6.1.4.1.534.6.6.4.1.1.2.5ScalarpduGroundCurrentread-onlycurrentThe present current in the PDU's ground phase. Ideally, this value stays at 0.
1.3.6.1.4.1.534.6.6.4.1.1.2.6ScalarpduInputVoltageUnitsread-onlycurrentIndicates whether the pduInputPhaseVoltage readings are 'Vrms Line-Line' or 'Vrms Line-Neutral'.
1.3.6.1.4.1.534.6.6.4.1.1.2.7ScalarpduInputNumPhasesread-onlycurrentThe number of input phases for this PDU. This variable indicates the number of rows in the pduInputTable.
1.3.6.1.4.1.534.6.6.4.1.1.2.8TablepduInputTablenot-accessiblecurrentA list of input table entries. The number of entries is given by the value of pduInputNumPhases.
1.3.6.1.4.1.534.6.6.4.1.1.2.8.1RowpduInputEntrynot-accessiblecurrentAn entry containing information applicable to a particular input phase.
1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.1ColumnpduInputPhaseIndexnot-accessiblecurrentThe input line identifier.
1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.2ColumnpduInputPhaseVoltageread-onlycurrentThe present input voltage for this phase.
1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.3ColumnpduInputPhaseCurrentread-onlycurrentThe present input current for this phase.
1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.4ColumnpduInputPhasePercentLoadread-onlycurrentThe percentage of the pdu power capacity presently being used on this line, normally based on the ratio of pduInputPhaseCurrent to the rated input current.
1.3.6.1.4.1.534.6.6.4.1.1.3NodepduOutput
1.3.6.1.4.1.534.6.6.4.1.1.3.1ScalarpduOutputKilowattHoursread-onlycurrentThe accumulated kilowatt-hour value for the full PDU system since the last reset.
1.3.6.1.4.1.534.6.6.4.1.1.3.2ScalarpduOutputVAread-onlycurrentThe present VA output of the full PDU system.
1.3.6.1.4.1.534.6.6.4.1.1.3.3ScalarpduOutputPowerread-onlycurrentThe present output power of the full PDU system.
1.3.6.1.4.1.534.6.6.4.1.1.3.4ScalarpduOutputPowerFactorread-onlycurrentThe output power factor for the full PDU system. Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf.
1.3.6.1.4.1.534.6.6.4.1.1.3.5ScalarpduNeutralCurrentread-onlycurrentThe present current in the PDU's output neutral phase. Ideally, this value stays at 0.
1.3.6.1.4.1.534.6.6.4.1.1.3.6ScalarpduRatedOutputCurrentread-onlycurrentThe rated current value for one PDU Output phase at full load (100%).
1.3.6.1.4.1.534.6.6.4.1.1.3.7ScalarpduOutputVoltageUnitsread-onlycurrentIndicates whether the pduOutputPhaseVoltage readings are 'Vrms Line-Line' or 'Vrms Line-Neutral'.
1.3.6.1.4.1.534.6.6.4.1.1.3.8ScalarpduOutputNumPhasesread-onlycurrentThe number of output phases for this PDU. This variable indicates the number of rows in the pduOutputTable.
1.3.6.1.4.1.534.6.6.4.1.1.3.9TablepduOutputTablenot-accessiblecurrentA list of output table entries. The number of entries is given by the value of pduOutputNumPhases.
1.3.6.1.4.1.534.6.6.4.1.1.3.9.1RowpduOutputEntrynot-accessiblecurrentAn entry containing information applicable to a particular output phase.
1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.1ColumnpduOutputPhaseIndexnot-accessiblecurrentThe output line identifier.
1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.2ColumnpduOutputPhaseVoltageread-onlycurrentThe present output voltage for this phase.
1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.3ColumnpduOutputPhaseCurrentread-onlycurrentThe present output current for this phase.
1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.4ColumnpduOutputPhasePercentLoadread-onlycurrentThe percentage of the pdu power capacity presently being used on this line, normally based on the ratio of pduOutputPhaseCurrent to pduRatedOutputCurrent.
1.3.6.1.4.1.534.6.6.4.1.2NodepduPanel
1.3.6.1.4.1.534.6.6.4.1.2.1TablepanelRatingsTablenot-accessiblecurrentA sparsely populated (ie, not sequentially numbered) table of ratings for each panel. The number of entries is given by the value of pduNumPanels.
1.3.6.1.4.1.534.6.6.4.1.2.1.1RowpanelRatingsEntrynot-accessiblecurrentAn entry containing information applicable to a particular output phase.
1.3.6.1.4.1.534.6.6.4.1.2.1.1.1ColumnpanelNumbernot-accessiblecurrentIndex for the Panel Ratings and Meters tables. Corresponds to the physical panel number in the PDU system. There must be a #1. The maximum value is 16. Panels …
1.3.6.1.4.1.534.6.6.4.1.2.1.1.2ColumnpanelRatedVoltageread-onlycurrentThe nominal Voltage of this panel (as distributed to the breakers or subfeeds). This is either Line-to-Line or Line-to-Neutral, as indicated in panelVoltageUni…
1.3.6.1.4.1.534.6.6.4.1.2.1.1.3ColumnpanelRatedBreakerCurrentread-onlycurrentThe rated current value for one panel (input) phase at full load (100%). This is set by the panel's input breaker; if there is no input breaker for this panel,…
1.3.6.1.4.1.534.6.6.4.1.2.1.1.4ColumnpanelNumPhasesread-onlycurrentThe number of lines (phases) for this panel.
1.3.6.1.4.1.534.6.6.4.1.2.1.1.5ColumnpanelNumBreakersread-onlycurrentThe number of breakers contained in this panel. This determines the number of rows found in the breaker tables.
1.3.6.1.4.1.534.6.6.4.1.2.1.1.6ColumnpanelVoltageUnitsread-onlycurrentIndicates whether the panelPhaseVoltage readings are 'Vrms Line-Line' or 'Vrms Line-Neutral'.
1.3.6.1.4.1.534.6.6.4.1.2.2TablepanelMetersTablenot-accessiblecurrentA sparsely populated (ie, not sequentially numbered) table of ratings for each panel. The number of entries is given by the value of pduNumPanels.
1.3.6.1.4.1.534.6.6.4.1.2.2.1RowpanelMetersEntrynot-accessiblecurrentAn entry containing meter readings applicable to a particular panel.
1.3.6.1.4.1.534.6.6.4.1.2.2.1.1ColumnpanelTotalKilowattHoursread-onlycurrentThe accumulated kilowatt-hours for this panel since it was commissioned and put into service, or since the last reset of the system KHW measures.
1.3.6.1.4.1.534.6.6.4.1.2.2.1.2ColumnpanelMonthlyKilowattHoursread-onlycurrentThe accumulated kilowatt-hours for this panel since the beginning of this calendar month, or since the last reset of the system KHW measures.
1.3.6.1.4.1.534.6.6.4.1.2.2.1.3ColumnpanelYtdKilowattHoursread-onlycurrentThe accumulated kilowatt-hours for this panel since the beginning of this calendar year (YTD), or since the last reset of the system KHW measures.
1.3.6.1.4.1.534.6.6.4.1.2.2.1.4ColumnpanelVAread-onlycurrentThe present VA (input) demand of this panel.
1.3.6.1.4.1.534.6.6.4.1.2.2.1.5ColumnpanelPowerread-onlycurrentThe present power (input) demand of this panel.
1.3.6.1.4.1.534.6.6.4.1.2.2.1.6ColumnpanelPowerFactorread-onlycurrentThe input power factor for this panel. Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf.
1.3.6.1.4.1.534.6.6.4.1.2.2.1.7ColumnpanelNeutralCurrentread-onlycurrentThe present neutral phase current for this panel.
1.3.6.1.4.1.534.6.6.4.1.2.3TablepanelPhaseMetersTablenot-accessiblecurrentA sparsely populated (ie, not sequentially panel numbered) table of ratings for each panel. The number of entries is given by the sum of panelNumPhases for pdu…
1.3.6.1.4.1.534.6.6.4.1.2.3.1RowpanelPhaseMetersEntrynot-accessiblecurrentAn entry containing meter readings applicable to a particular phase of a particular panel.
1.3.6.1.4.1.534.6.6.4.1.2.3.1.1ColumnpanelPhaseIndexnot-accessiblecurrentThe line or phase identifier.
1.3.6.1.4.1.534.6.6.4.1.2.3.1.2ColumnpanelPhaseVoltageread-onlycurrentThe present voltage for this phase.
1.3.6.1.4.1.534.6.6.4.1.2.3.1.3ColumnpanelPhaseCurrentread-onlycurrentThe present current for this phase.
1.3.6.1.4.1.534.6.6.4.1.2.3.1.4ColumnpanelPhasePercentLoadread-onlycurrentThe percentage of the panel power capacity presently being used on this line, normally based on the ratio of panelPhaseCurrent to the rated phase current.
1.3.6.1.4.1.534.6.6.4.1.3NodepduBreaker
1.3.6.1.4.1.534.6.6.4.1.3.1TablebreakerRatingsTablenot-accessiblecurrentA sparsely populated (ie, not sequentially numbered) table of ratings and fixed values for each breaker. The number of entries is given by the value of panelNu…
1.3.6.1.4.1.534.6.6.4.1.3.1.1RowbreakerRatingsEntrynot-accessiblecurrentAn entry containing information applicable to a particular output phase.
1.3.6.1.4.1.534.6.6.4.1.3.1.1.1ColumnbreakerNumbernot-accessiblecurrentIndex for the Breaker Ratings and Meters tables. Corresponds to the physical breaker number in the PDU system. Breakers are not required to be numbered sequent…
1.3.6.1.4.1.534.6.6.4.1.3.1.1.2ColumnbreakerNameread-onlycurrentName given by the administrator to identify this breaker.
1.3.6.1.4.1.534.6.6.4.1.3.1.1.3ColumnbreakerRatedCurrentread-onlycurrentThe rated current value of this breaker (for one phase) at full load (100%).
1.3.6.1.4.1.534.6.6.4.1.3.1.1.4ColumnbreakerNumPhasesread-onlycurrentThe number of lines (phases) for this breaker.
1.3.6.1.4.1.534.6.6.4.1.3.2TablebreakerMetersTablenot-accessiblecurrentA sparsely populated (ie, not sequentially numbered) table of ratings for each breaker. The number of entries is given by the value of panelNumBreakers for thi…
1.3.6.1.4.1.534.6.6.4.1.3.2.1RowbreakerMetersEntrynot-accessiblecurrentAn entry containing meter readings applicable to a particular breaker.
1.3.6.1.4.1.534.6.6.4.1.3.2.1.1ColumnbreakerTotalKilowattHoursread-onlycurrentThe accumulated kilowatt-hours for this breaker since it was commissioned and put into service, or since the last reset of the panel KHW measures.
1.3.6.1.4.1.534.6.6.4.1.3.2.1.2ColumnbreakerMonthlyKilowattHoursread-onlycurrentThe accumulated kilowatt-hours for this breaker since the beginning of this calendar month, or since the last reset of the panel KHW measures.
1.3.6.1.4.1.534.6.6.4.1.3.2.1.3ColumnbreakerYtdKilowattHoursread-onlycurrentThe accumulated kilowatt-hours for this breaker since the beginning of this calendar year (YTD), or since the last reset of the panel KHW measures.
1.3.6.1.4.1.534.6.6.4.1.3.3TablebreakerPhaseMetersTablenot-accessiblecurrentA sparsely populated (ie, not sequentially breaker numbered) table of ratings for each breaker. The number of entries is given by the sum of breakerNumPhases f…
1.3.6.1.4.1.534.6.6.4.1.3.3.1RowbreakerPhaseMetersEntrynot-accessiblecurrentAn entry containing meter readings applicable to a particular phase of a particular breaker on a particular panel.
1.3.6.1.4.1.534.6.6.4.1.3.3.1.1ColumnbreakerPhaseIndexnot-accessiblecurrentThe line or phase identifier.
1.3.6.1.4.1.534.6.6.4.1.3.3.1.2ColumnbreakerPhaseVAread-onlycurrentThe present VA (input) demand of this phase on this breaker.
1.3.6.1.4.1.534.6.6.4.1.3.3.1.3ColumnbreakerPhasePowerread-onlycurrentThe present power (input) demand of phase on this breaker.
1.3.6.1.4.1.534.6.6.4.1.3.3.1.4ColumnbreakerPhasePowerFactorread-onlycurrentThe input power factor for this phase on this breaker. Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf.
1.3.6.1.4.1.534.6.6.4.1.3.3.1.5ColumnbreakerPhaseCurrentread-onlycurrentThe present current for this phase of this breaker.
1.3.6.1.4.1.534.6.6.4.1.3.3.1.6ColumnbreakerPhasePercentLoadread-onlycurrentThe percentage of the breaker power capacity presently being used on this line, normally based on the ratio of breakerPhaseCurrent to the breakerRatedCurrent.
1.3.6.1.4.1.534.6.6.4.2NodeeatonPduConformance
1.3.6.1.4.1.534.6.6.4.2.1GrouppduNameplateGroupcurrentThe pduNameplate subgroup objects.
1.3.6.1.4.1.534.6.6.4.2.2GrouppduInputGroupcurrentThe pduInput Meters subgroup objects.
1.3.6.1.4.1.534.6.6.4.2.3GrouppduOutputGroupcurrentThe pduOutput Meters subgroup objects.
1.3.6.1.4.1.534.6.6.4.2.4GrouppanelRatingsGroupcurrentThe panelRatings table objects.
1.3.6.1.4.1.534.6.6.4.2.5GrouppanelMetersGroupcurrentThe BreakerMeters Table objects.
1.3.6.1.4.1.534.6.6.4.2.6GrouppanelPhaseMetersGroupcurrentThe BreakerPhaseMeters Table objects.
1.3.6.1.4.1.534.6.6.4.2.7GroupbreakerRatingsGroupcurrentThe breakerRatings table objects.
1.3.6.1.4.1.534.6.6.4.2.8GroupbreakerMetersGroupcurrentThe breakerMeters table objects.
1.3.6.1.4.1.534.6.6.4.2.9GroupbreakerPhaseMetersGroupcurrentThe breakerPhaseMeters table objects.
1.3.6.1.4.1.534.6.6.4.2.10Compliancepdu3phaseCompliancecurrentThe compliance statement for a normal 3-phase PDU, which implements the full set of objects.
Type Definitions
NameSyntaxStatusDescription
NonNegativeIntegerInteger32 (0..2147483647)currentThis data type is a non-negative value.
PositiveIntegerInteger32 (1..2147483647)currentThis data type is a non-zero and non-negative value.