MIB Viewer

EATON-PWR-MTR-MIB

88 objects
The MIB module for Power Metering measures such as those supplied by Eaton Power Meters. Some other Power Chain Devices, such as Fault Protection Breakers, can support portions of this MIB. This Power Meter MIB covers five areas: - Power Quality group: PQ Index, % THD for Current and Volts, ITIC Sags and Surges - Real-time Measures: Voltage, Currents, and Power measures. - Min/Avg/Max group for Voltage, Currents, Frequency, and PF - Energy Measures group: Watt-, VAR-, and VA-hours - Power Demand group: KW, KVA, and KVAR over the meter's Demand period All objects are indexed by the meter's device number, since some agents will present data from more than one Power Meter. This powerMeterIndex is normally the same as the entPhysicalIndex for the meter as a device. Copyright (C) Eaton Corporation (2007-).
Imported Objects
OIDNameAccessStatusDescription
1.3.6.1.4.1.534.8.3IdentitypwrMeterMIBThe MIB module for Power Metering measures such as those supplied by Eaton Power Meters. Some other Power Chain Devices, such as Fault Protection Breakers, can…
1.3.6.1.4.1.534.8.3.1NodepwrMeterMIBObjects
1.3.6.1.4.1.534.8.3.1.1NodemtrPowerQualityMeasures
1.3.6.1.4.1.534.8.3.1.1.1TablemtrPowerQualityMeasuresTablenot-accessiblecurrentA table of Power Quality measures for each meter. These measures summarize the values across all phases of the meter.
1.3.6.1.4.1.534.8.3.1.1.1.1RowmtrPowerQualityMeasuresEntrynot-accessiblecurrentAn entry containing real-time measures applicable to a particular Power Meter.
1.3.6.1.4.1.534.8.3.1.1.1.1.1ColumnpowerMeterIndexnot-accessiblecurrentThe Power Meter identifier (meter number). Used to index all tables in this MIB. Normally equal to the meter's entPhysicalIndex.
1.3.6.1.4.1.534.8.3.1.1.1.1.2ColumnmtrPresentPowerQualityIndexread-onlycurrentThe current or most recent Power Quality Index determined by this meter, using a short-term interval such as the last 10 minutes as the measurement interval.
1.3.6.1.4.1.534.8.3.1.1.1.1.3Columnmtr24hourPowerQualityIndexread-onlycurrentThe longer-term Power Quality Index determined by this meter, using the past 24 hours as the measurement interval.
1.3.6.1.4.1.534.8.3.1.1.1.1.4ColumnmtrPQVoltageTHDread-onlycurrentThe Total Harmonic Distortion of the Voltage waveforms, measured by this meter for all harmonics and summarized for all phases. The percentage result is multip…
1.3.6.1.4.1.534.8.3.1.1.1.1.5ColumnmtrPQCurrentTDDread-onlycurrentThe Total Demand Distortion of the Current waveforms, measured by this meter for all harmonics and summarized for all phases. TDD is similar to THD, but applie…
1.3.6.1.4.1.534.8.3.1.1.1.1.6ColumnmtrPQLastSagSurgeResetread-onlycurrentIndicates (in text) the date and time of the last reset of the Sag and Surge counts for this meter in mtrPQSagSurgeTable. If mtrPQSagSurgeTable is not implemen…
1.3.6.1.4.1.534.8.3.1.1.2TablemtrPQSagSurgeTablenot-accessiblecurrentA table of Voltage Sag and Surge counts for each meter, separated into meter-defined levels. Some Eaton Power Meters define four levels within the ITIC curve t…
1.3.6.1.4.1.534.8.3.1.1.2.1RowmtrPQSagSurgeEntrynot-accessiblecurrentAn entry containing Sag and Surge counts at a specific level, applicable to a particular Power Meter.
1.3.6.1.4.1.534.8.3.1.1.2.1.1ColumnmtrPQSagSurgeIndexnot-accessiblecurrentThe numeric value of this entry's level. For the ITIC curve levels, this Index will be 1, 2, 4, or 8.
1.3.6.1.4.1.534.8.3.1.1.2.1.2ColumnmtrPQSagSurgeLevelread-onlycurrentIndicates (in text) what level this entry/row is measured at. Eg, for Eaton PXM meters, indicates the ITIC level 1, 2, 4, or 8, where increasing level numbers …
1.3.6.1.4.1.534.8.3.1.1.2.1.3ColumnmtrPQSagCountread-onlycurrentThe count of Sags at this mtrPQSagSurgeLevel since the last reset, mtrPQLastSagSurgeReset.
1.3.6.1.4.1.534.8.3.1.1.2.1.4ColumnmtrPQSurgeCountread-onlycurrentThe count of Surges at this mtrPQSagSurgeLevel since the last reset, mtrPQLastSagSurgeReset.
1.3.6.1.4.1.534.8.3.1.2NodepwrMeterRealTimeMeasures
1.3.6.1.4.1.534.8.3.1.2.1TablepwrMeterRtMeasuresTablenot-accessiblecurrentA table of real-time measures for each meter. Since these measures are not broken out by phase, they summarize all phases of the meter.
1.3.6.1.4.1.534.8.3.1.2.1.1RowpwrMeterRtMeasuresEntrynot-accessiblecurrentAn entry containing real-time measures applicable to a particular Power Meter.
1.3.6.1.4.1.534.8.3.1.2.1.1.2ColumnpwrMtrRtNeutralCurrentread-onlycurrentThe present Neutral line current for this meter.
1.3.6.1.4.1.534.8.3.1.2.1.1.3ColumnpwrMtrRtGroundCurrentread-onlycurrentThe present Ground line current for this meter, in mA.
1.3.6.1.4.1.534.8.3.1.2.1.1.4ColumnpwrMtrRtTotalWattsread-onlycurrentThe present value of system watts, totaled from all phases. A negative value would generally indicate that power was being generated rather than delivered.
1.3.6.1.4.1.534.8.3.1.2.1.1.5ColumnpwrMtrRtTotalVAread-onlycurrentThe present value of system Volt-Amps, totaled from all phases.
1.3.6.1.4.1.534.8.3.1.2.1.1.6ColumnpwrMtrRtTotalVARread-onlycurrentThe present value of system Volt-Amps-Reactive, totaled from all phases.
1.3.6.1.4.1.534.8.3.1.2.1.1.7ColumnpwrMtrRtPowerFactorread-onlycurrentThe present value of apparent power factor for all phases, multiplied x100.
1.3.6.1.4.1.534.8.3.1.2.1.1.8ColumnpwrMtrRtFrequencyread-onlycurrentThe present frequency reading, multiplied x100.
1.3.6.1.4.1.534.8.3.1.2.1.1.9ColumnpwrMtrRtBtuPerHourread-onlycurrentThe present value of BTU/hr, totaled from all phases. This is a potential measure of HVAC loading for the measured equipment.
1.3.6.1.4.1.534.8.3.1.2.2TablepwrMeterRtPhaseMeasuresTablenot-accessiblecurrentA table of per-phase real-time measures for each meter.
1.3.6.1.4.1.534.8.3.1.2.2.1RowpwrMeterRtPhaseMeasuresEntrynot-accessiblecurrentAn entry containing information applicable to one line of a particular Power Meter. Indexed by meter number and phase number.
1.3.6.1.4.1.534.8.3.1.2.2.1.1ColumnpwrMtrPhaseIndexnot-accessiblecurrentThe line (phase) identifier.
1.3.6.1.4.1.534.8.3.1.2.2.1.2ColumnpwrMtrRtPhaseVoltageLLread-onlycurrentThe present Line-to-Line voltage for this phase of this meter.
1.3.6.1.4.1.534.8.3.1.2.2.1.3ColumnpwrMtrRtPhaseVoltageLNread-onlycurrentThe present Line-to-Neutral voltage for this phase of this meter.
1.3.6.1.4.1.534.8.3.1.2.2.1.4ColumnpwrMtrRtPhaseCurrentread-onlycurrentThe present rms current for this phase of this meter, multiplied x10.
1.3.6.1.4.1.534.8.3.1.2.2.1.5ColumnpwrMtrRtPhaseWattsread-onlycurrentThe present value of watts for this phase.
1.3.6.1.4.1.534.8.3.1.2.2.1.6ColumnpwrMtrRtPhaseVAread-onlycurrentThe present value of Volt-Amps for this phase.
1.3.6.1.4.1.534.8.3.1.2.2.1.7ColumnpwrMtrRtPhaseVARread-onlycurrentThe present value of Volt-Amps-Reactive for this phase.
1.3.6.1.4.1.534.8.3.1.2.2.1.8ColumnpwrMtrRtPhasePowerFactorread-onlycurrentThe present value of apparent power factor for this phase, multiplied x100.
1.3.6.1.4.1.534.8.3.1.3NodepwrMeterMinAvgMax
1.3.6.1.4.1.534.8.3.1.3.1TablepwrMeterMinAvgMaxTablenot-accessiblecurrentA table of minimum, average, and maximum measures for each meter.
1.3.6.1.4.1.534.8.3.1.3.1.1RowpwrMeterMinAvgMaxEntrynot-accessiblecurrentAn entry containing minimum, average, or maximum measures of a particular Power Meter. Indexed by meter number and a short tag for 'min', 'avg', or 'max'.
1.3.6.1.4.1.534.8.3.1.3.1.1.1ColumnpwrMtrMinAvgMaxIndexTagnot-accessiblecurrentA short tag to identify this row; one of 'min', 'avg', or 'max'.
1.3.6.1.4.1.534.8.3.1.3.1.1.2ColumnpwrMtrMinAvgMaxVoltageLNread-onlycurrentThe minimum, average, or maximum Line-to-Neutral voltage recorded by this meter since the operator last reset the min/max values.
1.3.6.1.4.1.534.8.3.1.3.1.1.3ColumnpwrMtrMinAvgMaxLineCurrentread-onlycurrentThe minimum, average, or maximum current recorded by this meter for any phase (line) since the operator last reset the min/max values.
1.3.6.1.4.1.534.8.3.1.3.1.1.4ColumnpwrMtrMinAvgMaxNeutralCurrentread-onlycurrentThe minimum, average, or maximum neutral line current recorded by this meter since the operator last reset the min/max values.
1.3.6.1.4.1.534.8.3.1.3.1.1.5ColumnpwrMtrMinAvgMaxFrequencyread-onlycurrentThe minimum, average, or maximum frequency recorded by this meter since the operator last reset the min/max values. The reading is multiplied by 100 to preserv…
1.3.6.1.4.1.534.8.3.1.3.1.1.6ColumnpwrMtrMinAvgMaxPowerFactorread-onlycurrentThe minimum, average, or maximum apparent power factor recorded by this meter since the operator last reset the min/max values. The reading is multiplied by 10…
1.3.6.1.4.1.534.8.3.1.4NodepwrMeterEnergyMeasures
1.3.6.1.4.1.534.8.3.1.4.1TablepwrMeterEnergyMeasuresTablenot-accessiblecurrentA table of cumulative power x hour readings measures for each meter. Since these measures are not broken out by phase, they summarize all phases of the meter. …
1.3.6.1.4.1.534.8.3.1.4.1.1RowpwrMeterEnergyMeasuresEntrynot-accessiblecurrentAn entry containing energy measures applicable to a particular Power Meter.
1.3.6.1.4.1.534.8.3.1.4.1.1.1ColumnpwrMtrEnergyKiloWattHoursread-onlycurrentThe cumulative value of net kiloWatt-hours (kWh), totaled from all phases since the last operator reset of the energy measures.
1.3.6.1.4.1.534.8.3.1.4.1.1.2ColumnpwrMtrEnergyKiloVAHoursread-onlycurrentThe cumulative value of kiloVolt-Ampere-hours (kVAh), totaled from all phases since the last operator reset of the energy measures.
1.3.6.1.4.1.534.8.3.1.4.1.1.3ColumnpwrMtrEnergyKiloVARHoursread-onlycurrentThe cumulative value of net kiloVolt-Amps-Reactive-hours (kvarh), totaled from all phases since the last operator reset of the energy measures.
1.3.6.1.4.1.534.8.3.1.4.1.1.4ColumnpwrMtrLastEnergyResetread-onlycurrentIndicates (in text) the date and time of the last reset of the Energy measures in this pwrMeterEnergyMeasuresEntry.
1.3.6.1.4.1.534.8.3.1.5NodepwrMeterDemandMeasures
1.3.6.1.4.1.534.8.3.1.5.1TablepwrMeterDemandMeasuresTablenot-accessiblecurrentA table of power demand measures and configuration for each meter. Demand readings provide an average of the rate of energy usage over the Demand Interval. Bot…
1.3.6.1.4.1.534.8.3.1.5.1.1RowpwrMeterDemandMeasuresEntrynot-accessiblecurrentAn entry containing power demand measures applicable to a particular Power Meter. The meter should be configured to match the Demand Interval method that the u…
1.3.6.1.4.1.534.8.3.1.5.1.1.1ColumnpwrMtrDemandIntervalTyperead-onlycurrentEnumerated value that tells which type of Demand Interval the Power Meter is using, a Fixed (block), Sliding (rolling), or Sync(end-of-interval pulse) window, …
1.3.6.1.4.1.534.8.3.1.5.1.1.2ColumnpwrMtrDemandIntervalread-onlycurrentThe interval, in minutes, used as the window for the meter's Demand measures.
1.3.6.1.4.1.534.8.3.1.5.1.1.3ColumnpwrMtrDemandSubintervalread-onlycurrentThe subinterval, in minutes, used by this meter as the update interval for a Sliding Demand window. For example, a meter might have a Sliding 15 minute Demand …
1.3.6.1.4.1.534.8.3.1.5.1.1.4ColumnpwrMtrDemandKiloWattsread-onlycurrentThe average Watts Demand measured over the last Demand period, totaled from all phases.
1.3.6.1.4.1.534.8.3.1.5.1.1.5ColumnpwrMtrPeakDemandKiloWattsread-onlycurrentThe highest pwrMtrDemandKiloWatts measured since the last operator reset of the Demand measures.
1.3.6.1.4.1.534.8.3.1.5.1.1.6ColumnpwrMtrDemandKVAread-onlycurrentThe average Volt-Ampere Demand measured over the last Demand period, totaled from all phases.
1.3.6.1.4.1.534.8.3.1.5.1.1.7ColumnpwrMtrPeakDemandKVAread-onlycurrentThe highest pwrMtrDemandKVA measured since the last operator reset of the Demand measures.
1.3.6.1.4.1.534.8.3.1.5.1.1.8ColumnpwrMtrDemandKVARread-onlycurrentThe average Volt-Ampere-Reactive Demand measured over the last Demand period, totaled from all phases.
1.3.6.1.4.1.534.8.3.1.5.1.1.9ColumnpwrMtrPeakDemandKVARread-onlycurrentThe highest pwrMtrDemandKVAR measured since the last operator reset of the Demand measures.
1.3.6.1.4.1.534.8.3.1.5.1.1.10ColumnpwrMtrLastPeakDemandResetread-onlycurrentIndicates (in text) the date and time of the last reset of the Peak Demand measures in this pwrMeterDemandMeasuresEntry.
1.3.6.1.4.1.534.8.3.1.5.1.1.11ColumnpwrMtrDemandWattsread-onlycurrentThe average Watts Demand measured over the last Demand period, totaled from all phases.
1.3.6.1.4.1.534.8.3.1.5.1.1.12ColumnpwrMtrPeakDemandWattsread-onlycurrentThe highest pwrMtrDemandWatts measured since the last operator reset of the Demand measures.
1.3.6.1.4.1.534.8.3.1.5.1.1.13ColumnpwrMtrDemandVAread-onlycurrentThe average Volt-Ampere Demand measured over the last Demand period, totaled from all phases.
1.3.6.1.4.1.534.8.3.1.5.1.1.14ColumnpwrMtrPeakDemandVAread-onlycurrentThe highest pwrMtrDemandVA measured since the last operator reset of the Demand measures.
1.3.6.1.4.1.534.8.3.1.5.1.1.15ColumnpwrMtrDemandVARread-onlycurrentThe average Volt-Ampere-Reactive Demand measured over the last Demand period, totaled from all phases.
1.3.6.1.4.1.534.8.3.1.5.1.1.16ColumnpwrMtrPeakDemandVARread-onlycurrentThe highest pwrMtrDemandVAR measured since the last operator reset of the Demand measures.
1.3.6.1.4.1.534.8.3.2NodepwrMeterConformance
1.3.6.1.4.1.534.8.3.2.1GroupmtrPowerQualityMeasuresRowcurrentThe mtrPowerQualityMeasuresEntry objects that are accessible to MIB browsers.
1.3.6.1.4.1.534.8.3.2.2GroupmtrPQSagSurgeRowcurrentThe mtrPQSagSurgeEntry objects that are accessible to MIB browsers.
1.3.6.1.4.1.534.8.3.2.3GrouppwrMeterRtMeasuresRowcurrentThe pwrMeterRtMeasuresEntry objects that are accessible to MIB browsers.
1.3.6.1.4.1.534.8.3.2.4GrouppwrMeterRtPhaseMeasuresRowcurrentThe pwrMeterRtPhaseMeasuresEntry objects that are accessible to MIB browsers.
1.3.6.1.4.1.534.8.3.2.5GrouppwrMeterMinAvgMaxRowcurrentThe pwrMeterMinAvgMaxEntry objects that are accessible to MIB browsers.
1.3.6.1.4.1.534.8.3.2.6GrouppwrMeterEnergyMeasuresRowcurrentThe pwrMeterEnergyMeasuresEntry objects that are accessible to MIB browsers.
1.3.6.1.4.1.534.8.3.2.7GrouppwrMeterDemandMeasuresRowcurrentThe pwrMeterDemandMeasuresEntry objects that are accessible to MIB browsers.
1.3.6.1.4.1.534.8.3.2.11CompliancemtrPowerQualityMeasuresCompliancecurrentThe compliance statement for Power Meter implementations that support mtrPowerQualityMeasures.
1.3.6.1.4.1.534.8.3.2.12CompliancepwrMeterRtMeasuresCompliancecurrentThe compliance statement for Power Meter implementations that support pwrMeterRealTimeMeasures.
1.3.6.1.4.1.534.8.3.2.13CompliancepwrMeterMinAvgMaxCompliancecurrentThe compliance statement for Power Meter implementations that support pwrMeterMinAvgMax measures.
1.3.6.1.4.1.534.8.3.2.14CompliancepwrMeterEnergyMeasuresCompliancecurrentThe compliance statement for Power Meter implementations that support pwrMeterEnergyMeasures.
1.3.6.1.4.1.534.8.3.2.15CompliancepwrMeterDemandMeasuresCompliancecurrentThe compliance statement for Power Meter implementations that support pwrMeterDemandMeasures.
Type Definitions
NameSyntaxStatusDescription
EatonPowerQualityIndexINTEGER { normal (1), caution (2), alert (3), unknown (4) }currentA numeric value to represent the Power Quality Index, as determined by the Power Meter. The meter uses an algorithm to determine the Power Quality level, using measures of Power Quality over a specific interval as input…
PowerFactorIntegerInteger32 (-100..100)currentThis data type represents the value of a power factor reading, with a range of -1 to 1, multiplied x100 to preserve accuracy. Positive values with delivered power indicate that current lags voltage; i.e., the load is in…