MIB Viewer

EES-POWER-FERRO-MIB

192 objects
Emerson Energy Systems (EES) Power MIB, For SMDUH.
Imported Objects
SNMPv2-SMICounter32 enterprises Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE
SNMPv2-TCDateAndTime DisplayString TEXTUAL-CONVENTION
OIDNameAccessStatusDescription
1.3.6.1.4.1.6302Nodeees
1.3.6.1.4.1.6302.2Nodeglobal
1.3.6.1.4.1.6302.2.1IdentitypowerMIBEmerson Energy Systems (EES) Power MIB, For SMDUH.
1.3.6.1.4.1.6302.2.1.1Nodeident
1.3.6.1.4.1.6302.2.1.1.1ScalaridentManufacturerread-onlycurrentThe name of the equipment manufacturer.
1.3.6.1.4.1.6302.2.1.1.2ScalaridentModelread-onlycurrentThe manufacturers model designation of the power system.
1.3.6.1.4.1.6302.2.1.1.3ScalaridentControllerFirmwareVersionread-onlycurrentThe firmware (software) version of the controller.
1.3.6.1.4.1.6302.2.1.1.4ScalaridentNameread-writecurrentThe name of the power plant. This object should be set by the administrator.
1.3.6.1.4.1.6302.2.1.1.5ScalaridentSNMPCfgVerread-onlycurrentThe name of the power plant. This object should be set by the administrator.
1.3.6.1.4.1.6302.2.1.2Nodesystem
1.3.6.1.4.1.6302.2.1.2.1ScalarsystemStatusread-onlycurrentStatus of the complete plant (highest alarm). One of (1) unknown - status has not yet been defined (2) normal - there are no activated alarms (3) warning - OA,…
1.3.6.1.4.1.6302.2.1.2.2ScalarsystemVoltageread-onlycurrentSystem voltage, stored as mV, including positive or negative sign. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.3ScalarsystemCurrentread-onlycurrentSystem current, stored as mA, including positive or negative sign. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.4ScalarsystemUsedCapacityread-onlycurrentUsed capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5NodepsBattery
1.3.6.1.4.1.6302.2.1.2.5.1ScalarpsBatteryVoltageread-onlycurrentBattery voltage, stored as mV, including positive or negative sign. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.2ScalarpsTotalBatteryCurrentread-onlycurrentBattery current, stored as mA, including positive or negative sign. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.3ScalarpsBatteryCapacityread-onlycurrentCalculated capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.4ScalarpsBatteryNominalCapacityread-onlycurrentnominal installed capacity, stored as mAh. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.5TablepsBatteryTablenot-accessiblecurrentBattery Table.
1.3.6.1.4.1.6302.2.1.2.5.5.1RowpsBatteryEntrynot-accessiblecurrentBattery Measurement Table Entry.
1.3.6.1.4.1.6302.2.1.2.5.5.1.1ColumnpsBatteryIndexread-onlycurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.5.5.1.2ColumnpsBatteryCurrentread-onlycurrentBattery current in Amps.
1.3.6.1.4.1.6302.2.1.2.5.5.1.3ColumnpsBatteryNameread-onlycurrentBattery shunt name.
1.3.6.1.4.1.6302.2.1.2.6NodepsInput
1.3.6.1.4.1.6302.2.1.2.6.1ScalarpsInputLineAVoltageread-onlycurrentThe AC line A voltage, stored as mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.6.2ScalarpsInputLineBVoltageread-onlycurrentThe AC line B voltage, stored as mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.6.3ScalarpsInputLineCVoltageread-onlycurrentThe AC line C voltage, stored as mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.7NodepsTemperature
1.3.6.1.4.1.6302.2.1.2.7.1ScalarpsTemperature1read-onlycurrentThe first route temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.7.2ScalarpsTemperature2read-onlycurrentThe second route temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value..
1.3.6.1.4.1.6302.2.1.2.7.3TablepsTemperatureTablenot-accessiblecurrentTemperature Measurement Table.
1.3.6.1.4.1.6302.2.1.2.7.3.1RowpsTemperatureEntrynot-accessiblecurrentTemperature Measurement Table Entry.
1.3.6.1.4.1.6302.2.1.2.7.3.1.1ColumnpsTemperatureIndexread-onlycurrentTemperature Probe Number
1.3.6.1.4.1.6302.2.1.2.7.3.1.2ColumnpsTemperatureMeasurementread-onlycurrentTemperature Value In Centigrade.
1.3.6.1.4.1.6302.2.1.2.7.3.1.3ColumnpsTemperatureNameread-onlycurrentConfigured Temperature Probe Name.
1.3.6.1.4.1.6302.2.1.2.7.3.1.4ColumnpsTemperatureTyperead-onlycurrentTemperature Probe Type
1.3.6.1.4.1.6302.2.1.2.7.3.1.5ColumnpsTemperatureAlarmStatusread-onlycurrentTemperature Probe Alarm Status
1.3.6.1.4.1.6302.2.1.2.8ScalarpsStatusCommunicationread-onlycurrentThe status of communication with the Power System. interrupt(3) indicates some errors occurred between Power System and agent.
1.3.6.1.4.1.6302.2.1.2.9ScalarpsStatusBatteryModeread-onlycurrentThe status of battery modes, FloatCharging(2), ShortTest(3), BoostChargingForTest(4), ManualTesting(5), PlanTesting(6), ACFailTesting(7), ACFail(8), ManualBoos…
1.3.6.1.4.1.6302.2.1.2.10NodepsSMNumber
1.3.6.1.4.1.6302.2.1.2.10.1ScalarpsSMACNumberread-onlycurrentThe number of SM AC module.
1.3.6.1.4.1.6302.2.1.2.10.2ScalarpsSMBATNumberread-onlycurrentThe number of SM BAT module.
1.3.6.1.4.1.6302.2.1.2.10.3ScalarpsSMIONumberread-onlycurrentThe number of SM IO module.
1.3.6.1.4.1.6302.2.1.2.11NodepsRectifier
1.3.6.1.4.1.6302.2.1.2.11.1ScalarnumberOfInstalledRectifiersread-onlycurrentnumber of rectifiers, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.11.2ScalarnumberOfRectifiersCommunicatingread-onlycurrentnumber of rectifiers communicating, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.11.3ScalarrectifiersUsedCapacityread-onlycurrentUsed capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.11.4TablepsRectifierTablenot-accessiblecurrentTable holding information about indivual rectifiers.
1.3.6.1.4.1.6302.2.1.2.11.4.1RowpsRectifierEntrynot-accessiblecurrentAn entry (conceptual row) in the rectifierInfoTable.
1.3.6.1.4.1.6302.2.1.2.11.4.1.1ColumnpsRectifierIndexread-onlycurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.11.4.1.2ColumnpsRectifierProductNumberread-onlycurrentRectifier Product Number.
1.3.6.1.4.1.6302.2.1.2.11.4.1.3ColumnpsRectifierHWVersionread-onlycurrentRectifier Hardware Revision.
1.3.6.1.4.1.6302.2.1.2.11.4.1.4ColumnpsRectifierSWVersionread-onlycurrentRectifier Software Revision.
1.3.6.1.4.1.6302.2.1.2.11.4.1.5ColumnpsRectifierSerialNumberread-onlycurrentRectifier Serial Number.
1.3.6.1.4.1.6302.2.1.2.11.4.1.6ColumnpsRectifierCurrentread-onlycurrentRectifier Current.
1.3.6.1.4.1.6302.2.1.2.11.4.1.7ColumnpsRectifierIdentread-onlycurrentRectifier physical location identifier.
1.3.6.1.4.1.6302.2.1.2.11.4.1.8ColumnpsRectifierFailread-onlycurrentThe type of alarm change. One of (1) activated (2) deactivated
1.3.6.1.4.1.6302.2.1.2.12NodepsDistribution
1.3.6.1.4.1.6302.2.1.2.12.1ScalarpsTotalLoadCurrentread-onlycurrentTotal Load current, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.12.2TablepsDistributionLoadTablenot-accessiblecurrentDistribution Table.
1.3.6.1.4.1.6302.2.1.2.12.2.1RowpsDistributionLoadEntrynot-accessiblecurrentDistribution Measurement Table Entry.
1.3.6.1.4.1.6302.2.1.2.12.2.1.1ColumnpsDistributionLoadIndexnot-accessiblecurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.12.2.1.2ColumnpsDistributionLoadCurrentread-onlycurrentDistribution current in Amps.
1.3.6.1.4.1.6302.2.1.2.12.2.1.3ColumnpsDistributionLoadNameread-onlycurrentDistribution name.
1.3.6.1.4.1.6302.2.1.2.12.3TablepsDistributionGeneralTablenot-accessiblecurrentDistribution Table.
1.3.6.1.4.1.6302.2.1.2.12.3.1RowpsDistributionGeneralEntrynot-accessiblecurrentDistribution Measurement Table Entry.
1.3.6.1.4.1.6302.2.1.2.12.3.1.1ColumnpsDistributionGeneralIndexnot-accessiblecurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.12.3.1.2ColumnpsDistributionGeneralCurrentread-onlycurrentDistribution current in Amps.
1.3.6.1.4.1.6302.2.1.2.12.3.1.3ColumnpsDistributionGeneralNameread-onlycurrentDistribution name.
1.3.6.1.4.1.6302.2.1.2.13NodepsConverter
1.3.6.1.4.1.6302.2.1.2.13.1ScalarnumberOfInstalledConvertersread-onlycurrentnumber of converters, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.13.2ScalarnumberOfConvertersCommunicatingread-onlycurrentnumber of converters communicating, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.13.3ScalarconvertersUsedCapacityread-onlycurrentUsed capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.13.4ScalarpsConverterVoltageread-onlycurrentConverter voltage in mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.13.5ScalarpsTotalConverterCurrentread-onlycurrentTotal Converter current in Amps. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.13.6TablepsConverterTablenot-accessiblecurrentTable holding information about indivual converters.
1.3.6.1.4.1.6302.2.1.2.13.6.1RowpsConverterEntrynot-accessiblecurrentAn entry (conceptual row) in the ConverterInfoTable.
1.3.6.1.4.1.6302.2.1.2.13.6.1.1ColumnpsConverterIndexread-onlycurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.13.6.1.2ColumnpsConverterProductNumberread-onlycurrentConverter Product Number.
1.3.6.1.4.1.6302.2.1.2.13.6.1.3ColumnpsConverterHWVersionread-onlycurrentConverter Hardware Revision.
1.3.6.1.4.1.6302.2.1.2.13.6.1.4ColumnpsConverterSWVersionread-onlycurrentConverter Software Revision.
1.3.6.1.4.1.6302.2.1.2.13.6.1.5ColumnpsConverterSerialNumberread-onlycurrentConverter Serial Number.
1.3.6.1.4.1.6302.2.1.2.13.6.1.6ColumnpsConverterCurrentread-onlycurrentConverter Current.
1.3.6.1.4.1.6302.2.1.2.13.6.1.7ColumnpsConverterIdentread-onlycurrentConverter physical location identifier.
1.3.6.1.4.1.6302.2.1.2.13.6.1.8ColumnpsConverterFailread-onlycurrentThe type of alarm change. One of (1) activated (2) deactivated
1.3.6.1.4.1.6302.2.1.2.14NodepsControl
1.3.6.1.4.1.6302.2.1.2.14.1ScalarcontrolBatteryTestread-writecurrentControl battery test, start(1), stop (0).
1.3.6.1.4.1.6302.2.1.2.14.2ScalarcontrolRelay8read-writecurrentControl relay8, close(1), open(0).
1.3.6.1.4.1.6302.2.1.2.14.3ScalarcontrolRelay7read-writecurrentControl relay7, close(1), open(0).
1.3.6.1.4.1.6302.2.1.2.14.4ScalarcontrolRelay6read-writecurrentControl relay6, close(1), open(0).
1.3.6.1.4.1.6302.2.1.2.14.5ScalarcontrolRelayTestread-writecurrentControl Relay test, start(1), stop (0).
1.3.6.1.4.1.6302.2.1.2.15TablepsEquipmentSignalTablenot-accessiblecurrentTable of indexed equipment signal values.
1.3.6.1.4.1.6302.2.1.2.15.1RowequipmentSignalTableEntrynot-accessiblecurrentAn entry (conceptual row) in the psEquipment Signal Table.
1.3.6.1.4.1.6302.2.1.2.15.1.1ColumnpsEquipmentSignalTableEntryIndexread-onlycurrentThe unique sequence number of this equipment signal.
1.3.6.1.4.1.6302.2.1.2.15.1.2ColumnpsEquipmentSignalValueread-onlycurrentIndexed equipment signal value.
1.3.6.1.4.1.6302.2.1.2.16NodepsSMDUHCurrent
1.3.6.1.4.1.6302.2.1.2.16.1ScalarnumberOfInstalledSMDUHread-onlycurrentnumber of SMDHU units, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.16.2ScalarpsSMDUH1Voltageread-onlycurrentSMDUH1 Voltage.
1.3.6.1.4.1.6302.2.1.2.16.3ScalarpsSMDUH2Voltageread-onlycurrentSMDUH2 Voltage.
1.3.6.1.4.1.6302.2.1.2.16.4ScalarpsSMDUH3Voltageread-onlycurrentSMDUH3 Voltage.
1.3.6.1.4.1.6302.2.1.2.16.5ScalarpsSMDUH4Voltageread-onlycurrentSMDUH4 Voltage.
1.3.6.1.4.1.6302.2.1.2.16.6ScalarpsSMDUH5Voltageread-onlycurrentSMDUH5 Voltage.
1.3.6.1.4.1.6302.2.1.2.16.7ScalarpsSMDUH6Voltageread-onlycurrentSMDUH6 Voltage.
1.3.6.1.4.1.6302.2.1.2.16.8ScalarpsSMDUH7Voltageread-onlycurrentSMDUH7 Voltage.
1.3.6.1.4.1.6302.2.1.2.16.9ScalarpsSMDUH8Voltageread-onlycurrentSMDU8 Voltage.
1.3.6.1.4.1.6302.2.1.2.16.10TablepsSMDUHCurrentTablenot-accessiblecurrentTable holding information about SMDUH currents.
1.3.6.1.4.1.6302.2.1.2.16.10.1RowpsSMDUHCurrentEntrynot-accessiblecurrentAn entry (conceptual row) in the SMDUHTable.
1.3.6.1.4.1.6302.2.1.2.16.10.1.1ColumnpsSMDUHCurrentIndexread-onlycurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.16.10.1.2ColumnpsSMDUHCurrent1read-onlycurrentSMDUH Current 1.
1.3.6.1.4.1.6302.2.1.2.16.10.1.3ColumnpsSMDUHCurrent2read-onlycurrentSMDUH Current 2.
1.3.6.1.4.1.6302.2.1.2.16.10.1.4ColumnpsSMDUHCurrent3read-onlycurrentSMDUH Current 3.
1.3.6.1.4.1.6302.2.1.2.16.10.1.5ColumnpsSMDUHCurrent4read-onlycurrentSMDUH Current 4.
1.3.6.1.4.1.6302.2.1.2.16.10.1.6ColumnpsSMDUHCurrent5read-onlycurrentSMDUH Current 5.
1.3.6.1.4.1.6302.2.1.2.16.10.1.7ColumnpsSMDUHCurrent6read-onlycurrentSMDUH Current 6.
1.3.6.1.4.1.6302.2.1.2.16.10.1.8ColumnpsSMDUHCurrent7read-onlycurrentSMDUH Current 7.
1.3.6.1.4.1.6302.2.1.2.16.10.1.9ColumnpsSMDUHCurrent8read-onlycurrentSMDUH Current 8.
1.3.6.1.4.1.6302.2.1.2.16.10.1.10ColumnpsSMDUHCurrent9read-onlycurrentSMDUH Current 9.
1.3.6.1.4.1.6302.2.1.2.16.10.1.11ColumnpsSMDUHCurrent10read-onlycurrentSMDUH Current 10.
1.3.6.1.4.1.6302.2.1.2.16.10.1.12ColumnpsSMDUHCurrent11read-onlycurrentSMDUH Current 11.
1.3.6.1.4.1.6302.2.1.2.16.10.1.13ColumnpsSMDUHCurrent12read-onlycurrentSMDUH Current 12.
1.3.6.1.4.1.6302.2.1.2.16.10.1.14ColumnpsSMDUHCurrent13read-onlycurrentSMDUH Current 13.
1.3.6.1.4.1.6302.2.1.2.16.10.1.15ColumnpsSMDUHCurrent14read-onlycurrentSMDUH Current 14.
1.3.6.1.4.1.6302.2.1.2.16.10.1.16ColumnpsSMDUHCurrent15read-onlycurrentSMDUH Current 15.
1.3.6.1.4.1.6302.2.1.2.16.10.1.17ColumnpsSMDUHCurrent16read-onlycurrentSMDUH Current 16.
1.3.6.1.4.1.6302.2.1.2.16.10.1.18ColumnpsSMDUHCurrent17read-onlycurrentSMDUH Current 17.
1.3.6.1.4.1.6302.2.1.2.16.10.1.19ColumnpsSMDUHCurrent18read-onlycurrentSMDUH Current 18.
1.3.6.1.4.1.6302.2.1.2.16.10.1.20ColumnpsSMDUHCurrent19read-onlycurrentSMDUH Current 19.
1.3.6.1.4.1.6302.2.1.2.16.10.1.21ColumnpsSMDUHCurrent20read-onlycurrentSMDUH Current 20.
1.3.6.1.4.1.6302.2.1.2.17NodepsSMDUHPower
1.3.6.1.4.1.6302.2.1.2.17.1TablepsSMDUHPowerTablenot-accessiblecurrentTable holding information about SMDUH power.
1.3.6.1.4.1.6302.2.1.2.17.1.1RowpsSMDUHPowerEntrynot-accessiblecurrentAn entry (conceptual row) in the SMDUHPowerTable.
1.3.6.1.4.1.6302.2.1.2.17.1.1.1ColumnpsSMDUHPowerIndexread-onlycurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.17.1.1.2ColumnpsSMDUHPower1read-onlycurrentSMDUH Power 1.
1.3.6.1.4.1.6302.2.1.2.17.1.1.3ColumnpsSMDUHPower2read-onlycurrentSMDUH Power 2.
1.3.6.1.4.1.6302.2.1.2.17.1.1.4ColumnpsSMDUHPower3read-onlycurrentSMDUH Power 3.
1.3.6.1.4.1.6302.2.1.2.17.1.1.5ColumnpsSMDUHPower4read-onlycurrentSMDUH Power 4.
1.3.6.1.4.1.6302.2.1.2.17.1.1.6ColumnpsSMDUHPower5read-onlycurrentSMDUH Power 5.
1.3.6.1.4.1.6302.2.1.2.17.1.1.7ColumnpsSMDUHPower6read-onlycurrentSMDUH Power 6.
1.3.6.1.4.1.6302.2.1.2.17.1.1.8ColumnpsSMDUHPower7read-onlycurrentSMDUH Power 7.
1.3.6.1.4.1.6302.2.1.2.17.1.1.9ColumnpsSMDUHPower8read-onlycurrentSMDUH Power 8.
1.3.6.1.4.1.6302.2.1.2.17.1.1.10ColumnpsSMDUHPower9read-onlycurrentSMDUH Power 9.
1.3.6.1.4.1.6302.2.1.2.17.1.1.11ColumnpsSMDUHPower10read-onlycurrentSMDUH Power 10.
1.3.6.1.4.1.6302.2.1.2.17.1.1.12ColumnpsSMDUHPower11read-onlycurrentSMDUH Power 11.
1.3.6.1.4.1.6302.2.1.2.17.1.1.13ColumnpsSMDUHPower12read-onlycurrentSMDUH Power 12.
1.3.6.1.4.1.6302.2.1.2.17.1.1.14ColumnpsSMDUHPower13read-onlycurrentSMDUH Power 13.
1.3.6.1.4.1.6302.2.1.2.17.1.1.15ColumnpsSMDUHPower14read-onlycurrentSMDUH Power 14.
1.3.6.1.4.1.6302.2.1.2.17.1.1.16ColumnpsSMDUHPower15read-onlycurrentSMDUH Power 15.
1.3.6.1.4.1.6302.2.1.2.17.1.1.17ColumnpsSMDUHPower16read-onlycurrentSMDUH Power 16.
1.3.6.1.4.1.6302.2.1.2.17.1.1.18ColumnpsSMDUHPower17read-onlycurrentSMDUH Power 17.
1.3.6.1.4.1.6302.2.1.2.17.1.1.19ColumnpsSMDUHPower18read-onlycurrentSMDUH Power 18.
1.3.6.1.4.1.6302.2.1.2.17.1.1.20ColumnpsSMDUHPower19read-onlycurrentSMDUH Power 19.
1.3.6.1.4.1.6302.2.1.2.17.1.1.21ColumnpsSMDUHPower20read-onlycurrentSMDUH Power 20.
1.3.6.1.4.1.6302.2.1.2.18NodepsSMDUHEnergy
1.3.6.1.4.1.6302.2.1.2.18.1TablepsSMDUHEnergyTablenot-accessiblecurrentTable holding information about SMDUH energy counters.
1.3.6.1.4.1.6302.2.1.2.18.1.1RowpsSMDUHEnergyEntrynot-accessiblecurrentAn entry (conceptual row) in the SMDUHEnergyTable.
1.3.6.1.4.1.6302.2.1.2.18.1.1.1ColumnpsSMDUHEnergyIndexread-onlycurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.18.1.1.2ColumnpsSMDUHTotalEnergy1read-onlycurrentSMDUH Total Energy 1.
1.3.6.1.4.1.6302.2.1.2.18.1.1.3ColumnpsSMDUHTotalEnergy2read-onlycurrentSMDUH Total Energy 2.
1.3.6.1.4.1.6302.2.1.2.18.1.1.4ColumnpsSMDUHTotalEnergy3read-onlycurrentSMDUH Total Energy 3.
1.3.6.1.4.1.6302.2.1.2.18.1.1.5ColumnpsSMDUHTotalEnergy4read-onlycurrentSMDUH Total Energy 4.
1.3.6.1.4.1.6302.2.1.2.18.1.1.6ColumnpsSMDUHTotalEnergy5read-onlycurrentSMDUH Total Energy 5.
1.3.6.1.4.1.6302.2.1.2.18.1.1.7ColumnpsSMDUHTotalEnergy6read-onlycurrentSMDUH Total Energy 6.
1.3.6.1.4.1.6302.2.1.2.18.1.1.8ColumnpsSMDUHTotalEnergy7read-onlycurrentSMDUH Total Energy 7.
1.3.6.1.4.1.6302.2.1.2.18.1.1.9ColumnpsSMDUHTotalEnergy8read-onlycurrentSMDUH Total Energy 8.
1.3.6.1.4.1.6302.2.1.2.18.1.1.10ColumnpsSMDUHTotalEnergy9read-onlycurrentSMDUH Total Energy 9.
1.3.6.1.4.1.6302.2.1.2.18.1.1.11ColumnpsSMDUHTotalEnergy10read-onlycurrentSMDUH Total Energy 10.
1.3.6.1.4.1.6302.2.1.2.18.1.1.12ColumnpsSMDUHTotalEnergy11read-onlycurrentSMDUH Total Energy 11.
1.3.6.1.4.1.6302.2.1.2.18.1.1.13ColumnpsSMDUHTotalEnergy12read-onlycurrentSMDUH Total Energy 12.
1.3.6.1.4.1.6302.2.1.2.18.1.1.14ColumnpsSMDUHTotalEnergy13read-onlycurrentSMDUH Total Energy 13.
1.3.6.1.4.1.6302.2.1.2.18.1.1.15ColumnpsSMDUHTotalEnergy14read-onlycurrentSMDUH Total Energy 14.
1.3.6.1.4.1.6302.2.1.2.18.1.1.16ColumnpsSMDUHTotalEnergy15read-onlycurrentSMDUH Total Energy 15.
1.3.6.1.4.1.6302.2.1.2.18.1.1.17ColumnpsSMDUHTotalEnergy16read-onlycurrentSMDUH Total Energy 16.
1.3.6.1.4.1.6302.2.1.2.18.1.1.18ColumnpsSMDUHTotalEnergy17read-onlycurrentSMDUH Total Energy 17.
1.3.6.1.4.1.6302.2.1.2.18.1.1.19ColumnpsSMDUHTotalEnergy18read-onlycurrentSMDUH Total Energy 18.
1.3.6.1.4.1.6302.2.1.2.18.1.1.20ColumnpsSMDUHTotalEnergy19read-onlycurrentSMDUH Total Energy 19.
1.3.6.1.4.1.6302.2.1.2.18.1.1.21ColumnpsSMDUHTotalEnergy20read-onlycurrentSMDUH Total Energy 20.
1.3.6.1.4.1.6302.2.1.3ScalaralarmLastTrapNoread-onlycurrentThe sequence number of last submitted alarm trap, also last row in alarmTrapTable.
1.3.6.1.4.1.6302.2.1.4TablealarmActiveAlarmTablenot-accessiblecurrentTable holding information about the currently active alarms.
1.3.6.1.4.1.6302.2.1.4.1RowactiveAlarmEntrynot-accessiblecurrentAn entry (conceptual row) in the alarmTrapTable.
1.3.6.1.4.1.6302.2.1.4.1.1ColumnalarmIndexread-onlycurrentThe unique sequence number of this alarm trap.
1.3.6.1.4.1.6302.2.1.4.1.2ColumnalarmTimeread-onlycurrentDate and time when event occured (local time), including timezone if supported by controller.
1.3.6.1.4.1.6302.2.1.4.1.3ColumnalarmStatusChangeread-onlycurrentThe type of alarm change. One of (1) activated (2) deactivated
1.3.6.1.4.1.6302.2.1.4.1.4ColumnalarmSeverityread-onlycurrentThe severity of the alarm. One of (3) warning - OA, lowest level of alarm severity (4) minor - A3 (5) major - MA (6) critical - CA, highest level of alarm seve…
1.3.6.1.4.1.6302.2.1.4.1.5ColumnalarmDescriptionread-onlycurrentFree-text description of alarm.
1.3.6.1.4.1.6302.2.1.4.1.6ColumnalarmTyperead-onlycurrentAlarm type, i.e. an integer specifying the type of alarm.
1.3.6.1.4.1.6302.2.1.5NodepowerEvents
1.3.6.1.4.1.6302.2.1.5.1NotificationalarmTrapcurrentAn alarm trap is sent when an alarm occurs (activated) or returns to normal state (deactivated). Alarm traps are logged in alarmTrapTable. Variables in this tr…
1.3.6.1.4.1.6302.2.1.5.2NotificationalarmActiveTrapcurrentAn alarm trap is sent when an alarm occurs (activated) Variables in this trap * alarmTime - Date and time when event occured (local time), including timezone i…
1.3.6.1.4.1.6302.2.1.5.3NotificationalarmCeaseTrapcurrentAn alarm trap is sent when an alarm returns to normal state (clear, deactivated). Variables in this trap: * alarmTime - Date and time when event occured (local…
Type Definitions
NameSyntaxStatusDescription
StatusINTEGER { unknown(1), normal(2), warning(3), minor(4), major(5), critical(6), unmanaged(7), restricted(8), testing(9), disabled(10) }currentThis integer value represents the operational or administrative status of the system. Also used as alarm severity. Depending on situation there may be limits on allowed values. Operational values: (1) unknown - status h…
StatusChangeINTEGER { activated(1), deactivated(2) }currentIndicates 'activated' (1) or 'deactivated' (2) alarm events.