1.3.6.1.4.1.6302Nodeees
1.3.6.1.4.1.6302.2Nodeglobal
1.3.6.1.4.1.6302.2.1IdentitypowerMIBVertiv Tech Co. Ltd. Power MIB, revision E.
1.3.6.1.4.1.6302.2.1.1Nodeident
1.3.6.1.4.1.6302.2.1.1.1ScalaridentManufacturerread-onlycurrentThe name of the equipment manufacturer.
1.3.6.1.4.1.6302.2.1.1.2ScalaridentModelread-onlycurrentThe manufacturers model designation of the power system.
1.3.6.1.4.1.6302.2.1.1.3ScalaridentControllerFirmwareVersionread-onlycurrentThe firmware (software) version of the controller.
1.3.6.1.4.1.6302.2.1.1.4ScalaridentNameread-writecurrentThe name of the power plant. This object should be set by the administrator.
1.3.6.1.4.1.6302.2.1.1.5ScalaridentSNMPCfgVerread-onlycurrentThe snmp cfg version
1.3.6.1.4.1.6302.2.1.1.6ScalaridentControllerSerialNumberread-onlycurrentThe serial number of this controller
1.3.6.1.4.1.6302.2.1.2Nodesystem
1.3.6.1.4.1.6302.2.1.2.1ScalarsystemStatusread-onlycurrentStatus of the complete plant (highest alarm). One of (1) unknown - status has not yet been defined (2) normal - there are no activated alarms (3) warning - OA,…
1.3.6.1.4.1.6302.2.1.2.2ScalarsystemVoltageread-onlycurrentSystem voltage, stored as mV, including positive or negative sign. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.3ScalarsystemCurrentread-onlycurrentSystem current, stored as mA, including positive or negative sign. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.4ScalarsystemUsedCapacityread-onlycurrentUsed capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5NodepsBattery
1.3.6.1.4.1.6302.2.1.2.5.1ScalarpsBatteryVoltageread-onlycurrentBattery voltage, stored as mV, including positive or negative sign. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.2ScalarpsTotalBatteryCurrentread-onlycurrentBattery current, stored as mA, including positive or negative sign. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.3ScalarpsLowestBatteryCapacityread-onlycurrentCalculated capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.4ScalarpsBatteryNominalCapacityread-onlycurrentnominal installed capacity, stored as mAh. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.5TablepsBatteryTablenot-accessiblecurrentBattery Table.
1.3.6.1.4.1.6302.2.1.2.5.5.1RowpsBatteryEntrynot-accessiblecurrentBattery Measurement Table Entry.
1.3.6.1.4.1.6302.2.1.2.5.5.1.1ColumnpsBatteryIndexread-onlycurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.5.5.1.2ColumnpsBatteryCurrentread-onlycurrentBattery current in mA.
1.3.6.1.4.1.6302.2.1.2.5.5.1.3ColumnpsBatteryNameread-onlycurrentBattery shunt name.
1.3.6.1.4.1.6302.2.1.2.5.5.1.4ColumnpsBatteryRatedCapacityread-writecurrentBattery reted capacity.
1.3.6.1.4.1.6302.2.1.2.5.5.1.5ColumnpsBatteryCapacityread-onlycurrentBattery capacity in Ah.
1.3.6.1.4.1.6302.2.1.2.5.5.1.6ColumnpsBatteryCapacityPercentread-onlycurrentBattery capacity in percent.
1.3.6.1.4.1.6302.2.1.2.5.6ScalarnumberOfBatteryStringsread-onlycurrentNumber of battery strings, including SMDUBat and MainboardBat. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.7ScalartemperatureOfBatteryread-onlycurrentTemperature of battery. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.8ScalarmaxCurrentOfChargingread-writecurrentMaximun battery charging current. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.9NodechargingVoltage
1.3.6.1.4.1.6302.2.1.2.5.9.1ScalarfloatVoltageread-writecurrentFloat charging voltage. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.9.2ScalarboostVoltageread-writecurrentBoost charging voltage. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.10NodehighBatteryTemperature
1.3.6.1.4.1.6302.2.1.2.5.10.1ScalarpsHighBatteryTemperatureread-writecurrentHigh battery temperature. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.10.2ScalarpsVeryHighBatteryTemperatureread-writecurrentVery high battery temperature. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.11ScalartemperatureCompensationCoefficientread-writecurrentTemperature compensation coefficient. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.12ScalartemperatureCompensationread-onlycurrentTemperature compensation . The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.13Scalarbatt1RemainingCapacityread-onlycurrentRemain capacity of battery, stored as % of the total capacity. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.14Scalarbatt1ShuntFullScaleCurrentread-writecurrentBattery 1 Shunt Full Scale Current in mA. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.15Scalarbatt1ShuntFullScaleVoltageread-writecurrentBattery 1 Shunt Full Scale Voltage in thousandths of mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.16ScalarpsBatteryCurrentLimitread-writecurrentBattery charge current limit stored as thousandths of C10
1.3.6.1.4.1.6302.2.1.2.5.17ScalarpsBatteryTyperead-writecurrentBattery Type number
1.3.6.1.4.1.6302.2.1.2.5.18ScalarpsResetBatteryCapacityread-writecurrentReset Battery Capacity, Yes(1)
1.3.6.1.4.1.6302.2.1.2.5.19ScalarpsBatteryOverCurrentLimitread-writecurrentBattery over current limit stored as thousandths of C10
1.3.6.1.4.1.6302.2.1.2.5.20ScalarpsBatteryAccumDischargeNaradaread-onlycurrentNarada Battery's Cumulated Discharge.
1.3.6.1.4.1.6302.2.1.2.5.21ScalarpsBatterySOHNaradaread-onlycurrentNarada Battery's SOH.
1.3.6.1.4.1.6302.2.1.2.5.22ScalarpsBatterySOHIncellread-onlycurrentIncell Battery's SOH.
1.3.6.1.4.1.6302.2.1.2.5.23ScalarpsBatterySOHVisionread-onlycurrentVision Battery's SOH.
1.3.6.1.4.1.6302.2.1.2.5.24ScalarpsBatterySOHNokiaread-onlycurrentNokia Battery's SOH.
1.3.6.1.4.1.6302.2.1.2.6NodepsInput
1.3.6.1.4.1.6302.2.1.2.6.1ScalarpsInputLineAVoltageread-onlycurrentThe AC line A voltage, stored as mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.6.2ScalarpsInputLineBVoltageread-onlycurrentThe AC line B voltage, stored as mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.6.3ScalarpsInputLineCVoltageread-onlycurrentThe AC line C voltage, stored as mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.6.4ScalarpsInputPhaseACurrentread-onlycurrentThe AC Phase A current, stored as mA. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.6.5ScalarpsInputPhaseBCurrentread-onlycurrentThe AC Phase B current, stored as mA. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.6.6ScalarpsInputPhaseCCurrentread-onlycurrentThe AC Phase C current, stored as mA. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.6.7ScalarpsInputPowerCPread-onlycurrentRectifier Total Input Power(CP) in thousandths of watts.
1.3.6.1.4.1.6302.2.1.2.6.8ScalarpsInputPowerDGread-onlycurrentRectifier Total Input Power(DG) in thousandths of watts.
1.3.6.1.4.1.6302.2.1.2.7NodepsTemperature
1.3.6.1.4.1.6302.2.1.2.7.1ScalarpsTemperature1read-onlycurrentThe first route temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.7.2ScalarpsTemperature2read-onlycurrentThe second route temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value..
1.3.6.1.4.1.6302.2.1.2.7.3TablepsTemperatureTablenot-accessiblecurrentTemperature Measurement Table.
1.3.6.1.4.1.6302.2.1.2.7.3.1RowpsTemperatureEntrynot-accessiblecurrentTemperature Measurement Table Entry.
1.3.6.1.4.1.6302.2.1.2.7.3.1.1ColumnpsTemperatureIndexread-onlycurrentTemperature Probe Number
1.3.6.1.4.1.6302.2.1.2.7.3.1.2ColumnpsTemperatureMeasurementread-onlycurrentTemperature Value In 0.001 Celsius Degree.
1.3.6.1.4.1.6302.2.1.2.7.3.1.3ColumnpsTemperatureNameread-onlycurrentConfigured Temperature Probe Name.
1.3.6.1.4.1.6302.2.1.2.7.3.1.4ColumnpsTemperatureTyperead-onlycurrentTemperature Probe Type
1.3.6.1.4.1.6302.2.1.2.7.3.1.5ColumnpsTemperatureAlarmStatusread-onlycurrentTemperature Probe Alarm Status
1.3.6.1.4.1.6302.2.1.2.8ScalarpsStatusCommunicationread-onlycurrentThe status of communication with the Power System. interrupt(3) indicates some errors occurred between Power System and agent.
1.3.6.1.4.1.6302.2.1.2.9ScalarpsStatusBatteryModeread-onlycurrentThe status of battery modes, FloatCharging(2), ShortTest(3), BoostChargingForTest(4), ManualTesting(5), PlanTesting(6), ACFailTesting(7), ACFail(8), ManualBoos…
1.3.6.1.4.1.6302.2.1.2.10NodepsSMNumber
1.3.6.1.4.1.6302.2.1.2.10.1ScalarpsSMACNumberread-onlycurrentThe number of SM AC module.
1.3.6.1.4.1.6302.2.1.2.10.2ScalarpsSMBATNumberread-onlycurrentThe number of SM BAT module.
1.3.6.1.4.1.6302.2.1.2.10.3ScalarpsSMIONumberread-onlycurrentThe number of SM IO module.
1.3.6.1.4.1.6302.2.1.2.11NodepsRectifier
1.3.6.1.4.1.6302.2.1.2.11.1ScalarnumberOfInstalledRectifiersread-onlycurrentnumber of rectifiers, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.11.2ScalarnumberOfRectifiersCommunicatingread-onlycurrentnumber of rectifiers communicating, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.11.3ScalarrectifiersUsedCapacityread-onlycurrentUsed capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.11.4TablepsRectifierTablenot-accessiblecurrentTable holding information about indivual rectifiers.
1.3.6.1.4.1.6302.2.1.2.11.4.1RowpsRectifierEntrynot-accessiblecurrentAn entry (conceptual row) in the rectifierInfoTable.
1.3.6.1.4.1.6302.2.1.2.11.4.1.1ColumnpsRectifierIndexread-onlycurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.11.4.1.2ColumnpsRectifierProductNumberread-onlycurrentRectifier Product Number.
1.3.6.1.4.1.6302.2.1.2.11.4.1.3ColumnpsRectifierHWVersionread-onlycurrentRectifier Hardware Revision.
1.3.6.1.4.1.6302.2.1.2.11.4.1.4ColumnpsRectifierSWVersionread-onlycurrentRectifier Software Revision.
1.3.6.1.4.1.6302.2.1.2.11.4.1.5ColumnpsRectifierSerialNumberread-onlycurrentRectifier Serial Number.
1.3.6.1.4.1.6302.2.1.2.11.4.1.6ColumnpsRectifierCurrentread-onlycurrentRectifier Current.
1.3.6.1.4.1.6302.2.1.2.11.4.1.7ColumnpsRectifierIdentread-onlycurrentRectifier physical location identifier.
1.3.6.1.4.1.6302.2.1.2.11.4.1.8ColumnpsRectifierFailread-onlycurrentThe type of alarm change. One of (1) activated (2) deactivated
1.3.6.1.4.1.6302.2.1.2.11.4.1.9ColumnpsRectifierTemperatureread-onlycurrentRectifier Temperature.
1.3.6.1.4.1.6302.2.1.2.11.5ScalarpsPowerOfRectifiersread-onlycurrentTotal power of rectifiers. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.11.7ScalarpsOverOutputVoltageread-onlycurrentRectifier output over voltage protection point. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.11.8ScalarpsVeryOverOutputVoltageread-onlycurrentRectifier output very over voltage protection point. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.11.9ScalarpsSoftStartStatusread-writecurrentSoft-start functuin status. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.11.10ScalarpsSoftStartTimeread-writecurrentSoftStart Time, stored as Sec. Value range: 8~128.
1.3.6.1.4.1.6302.2.1.2.11.11ScalarpsACEnergyOfRectifiersread-onlycurrentTotal AC energy of rectifiers. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.11.12ScalarpsDCEnergyOfRectifiersread-onlycurrentTotal DC energy of rectifiers. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.11.13ScalarpsRectifierAllONOFFread-writecurrentON OFF of all rectifiers. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.12NodepsDistribution
1.3.6.1.4.1.6302.2.1.2.12.1ScalarpsTotalLoadCurrentread-onlycurrentTotal Load current, stored as mA. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.12.2TablepsDistributionLoadTablenot-accessiblecurrentDistribution Table.
1.3.6.1.4.1.6302.2.1.2.12.2.1RowpsDistributionLoadEntrynot-accessiblecurrentDistribution Measurement Table Entry.
1.3.6.1.4.1.6302.2.1.2.12.2.1.1ColumnpsDistributionLoadIndexnot-accessiblecurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.12.2.1.2ColumnpsDistributionLoadCurrentread-onlycurrentDistribution current in mA.
1.3.6.1.4.1.6302.2.1.2.12.2.1.3ColumnpsDistributionLoadNameread-onlycurrentDistribution name.
1.3.6.1.4.1.6302.2.1.2.12.3TablepsDistributionGeneralTablenot-accessiblecurrentDistribution Table.
1.3.6.1.4.1.6302.2.1.2.12.3.1RowpsDistributionGeneralEntrynot-accessiblecurrentDistribution Measurement Table Entry.
1.3.6.1.4.1.6302.2.1.2.12.3.1.1ColumnpsDistributionGeneralIndexnot-accessiblecurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.12.3.1.2ColumnpsDistributionGeneralCurrentread-onlycurrentDistribution current in mA.
1.3.6.1.4.1.6302.2.1.2.12.3.1.3ColumnpsDistributionGeneralNameread-onlycurrentDistribution name.
1.3.6.1.4.1.6302.2.1.2.13NodepsConverter
1.3.6.1.4.1.6302.2.1.2.13.1ScalarnumberOfInstalledConvertersread-onlycurrentnumber of converters, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.13.2ScalarnumberOfConvertersCommunicatingread-onlycurrentnumber of converters communicating, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.13.3ScalarconvertersUsedCapacityread-onlycurrentUsed capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.13.4ScalarpsConverterVoltageread-onlycurrentConverter voltage in mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.13.5ScalarpsTotalConverterCurrentread-onlycurrentTotal Converter current in mA. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.13.6TablepsConverterTablenot-accessiblecurrentTable holding information about indivual converters.
1.3.6.1.4.1.6302.2.1.2.13.6.1RowpsConverterEntrynot-accessiblecurrentAn entry (conceptual row) in the ConverterInfoTable.
1.3.6.1.4.1.6302.2.1.2.13.6.1.1ColumnpsConverterIndexread-onlycurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.13.6.1.2ColumnpsConverterProductNumberread-onlycurrentConverter Product Number.
1.3.6.1.4.1.6302.2.1.2.13.6.1.3ColumnpsConverterHWVersionread-onlycurrentConverter Hardware Revision.
1.3.6.1.4.1.6302.2.1.2.13.6.1.4ColumnpsConverterSWVersionread-onlycurrentConverter Software Revision.
1.3.6.1.4.1.6302.2.1.2.13.6.1.5ColumnpsConverterSerialNumberread-onlycurrentConverter Serial Number.
1.3.6.1.4.1.6302.2.1.2.13.6.1.6ColumnpsConverterCurrentread-onlycurrentConverter Current.
1.3.6.1.4.1.6302.2.1.2.13.6.1.7ColumnpsConverterIdentread-onlycurrentConverter physical location identifier.
1.3.6.1.4.1.6302.2.1.2.13.6.1.8ColumnpsConverterFailread-onlycurrentThe type of alarm change. One of (1) activated (2) deactivated
1.3.6.1.4.1.6302.2.1.2.14NodepsControl
1.3.6.1.4.1.6302.2.1.2.14.1ScalarcontrolBatteryTestread-writecurrentControl battery test, start(1), stop(0).
1.3.6.1.4.1.6302.2.1.2.14.2ScalarcontrolRelay8read-writecurrentControl relay8, close(1), open(0).
1.3.6.1.4.1.6302.2.1.2.14.3ScalarcontrolRelay7read-writecurrentControl relay7, close(1), open(0).
1.3.6.1.4.1.6302.2.1.2.14.4ScalarcontrolRelay6read-writecurrentControl relay6, close(1), open(0).
1.3.6.1.4.1.6302.2.1.2.14.5ScalarcontrolRelayTestread-writecurrentControl Relay test, auto(2), manual(1), disabled(0).
1.3.6.1.4.1.6302.2.1.2.15TablepsEquipmentSignalTablenot-accessiblecurrentTable of indexed equipment signal values.
1.3.6.1.4.1.6302.2.1.2.15.1RowequipmentSignalTableEntrynot-accessiblecurrentAn entry (conceptual row) in the psEquipment Signal Table.
1.3.6.1.4.1.6302.2.1.2.15.1.1ColumnpsEquipmentSignalTableEntryIndexread-onlycurrentThe unique sequence number of this equipment signal.
1.3.6.1.4.1.6302.2.1.2.15.1.2ColumnpsEquipmentSignalValueread-onlycurrentIndexed equipment signal value.
1.3.6.1.4.1.6302.2.1.2.16ScalarambientTemperatureread-onlycurrentAmbientTemperature. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.17ScalarautoManualModeread-writecurrentAuto/Manual Mode of system. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.18NodepsLVDVoltage
1.3.6.1.4.1.6302.2.1.2.18.1ScalarpsLVD1DisconnectVoltageread-writecurrentLVD1 Disconnect voltage, stored as mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.18.2ScalarpsLVD2DisconnectVoltageread-writecurrentLVD2 Disconnect voltage, stored as mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.18.3ScalarpsLVD1ReconnectVoltageread-writecurrentLVD1 Reconnect voltage, stored as mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.18.4ScalarpsLVD2ReconnectVoltageread-writecurrentLVD2 Reconnect voltage, stored as mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.18.5Scalarsmdu1LVD1DisconnectVoltageread-writecurrentSMDU1 LVD1 Disconnect voltage, stored as mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.18.6Scalarsmdu1LVD2DisconnectVoltageread-writecurrentSMDU1 LVD2 Disconnect voltage, stored as mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.18.7Scalarsmdu1LVD1ReconnectVoltageread-writecurrentSMDU1 LVD1 Reconnect voltage, stored as mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.18.8Scalarsmdu1LVD2ReconnectVoltageread-writecurrentSMDU1 LVD2 Reconnect voltage, stored as mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.19NodepsDCLowVoltage
1.3.6.1.4.1.6302.2.1.2.19.1ScalarpsDCLowAlarmVoltageread-writecurrentDC low voltage, stored as mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.19.2ScalarpsDCVeryLowAlarmVoltageread-writecurrentDC very low voltage, stored as mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.20NodeacLowVoltage
1.3.6.1.4.1.6302.2.1.2.20.1ScalarpsACLowAlarmVoltageread-writecurrentAC low voltage, stored as V. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.20.2ScalarpsACVeryLowAlarmVoltageread-writecurrentAC very low voltage, stored as V. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.21NodepsSMDUHCurrent
1.3.6.1.4.1.6302.2.1.2.21.1ScalarnumberOfInstalledSMDUHread-onlycurrentnumber of SMDHU units, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.21.2ScalarpsSMDUH1Voltageread-onlycurrentSMDUH1 Voltage in mV.
1.3.6.1.4.1.6302.2.1.2.21.3ScalarpsSMDUH2Voltageread-onlycurrentSMDUH2 Voltage in mV.
1.3.6.1.4.1.6302.2.1.2.21.4ScalarpsSMDUH3Voltageread-onlycurrentSMDUH3 Voltage in mV.
1.3.6.1.4.1.6302.2.1.2.21.5ScalarpsSMDUH4Voltageread-onlycurrentSMDUH4 Voltage in mV.
1.3.6.1.4.1.6302.2.1.2.21.6ScalarpsSMDUH5Voltageread-onlycurrentSMDUH5 Voltage in mV.
1.3.6.1.4.1.6302.2.1.2.21.7ScalarpsSMDUH6Voltageread-onlycurrentSMDUH6 Voltage in mV.
1.3.6.1.4.1.6302.2.1.2.21.8ScalarpsSMDUH7Voltageread-onlycurrentSMDUH7 Voltage in mV.
1.3.6.1.4.1.6302.2.1.2.21.9ScalarpsSMDUH8Voltageread-onlycurrentSMDUH8 Voltage in mV.
1.3.6.1.4.1.6302.2.1.2.21.10TablepsSMDUHCurrentTablenot-accessiblecurrentTable holding information about SMDUH currents.
1.3.6.1.4.1.6302.2.1.2.21.10.1RowpsSMDUHCurrentEntrynot-accessiblecurrentAn entry (conceptual row) in the SMDUHTable.
1.3.6.1.4.1.6302.2.1.2.21.10.1.1ColumnpsSMDUHCurrentIndexread-onlycurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.21.10.1.2ColumnpsSMDUHCurrent1read-onlycurrentSMDUH Current 1 in mA.
1.3.6.1.4.1.6302.2.1.2.21.10.1.3ColumnpsSMDUHCurrent2read-onlycurrentSMDUH Current 2 in mA.
1.3.6.1.4.1.6302.2.1.2.21.10.1.4ColumnpsSMDUHCurrent3read-onlycurrentSMDUH Current 3 in mA.
1.3.6.1.4.1.6302.2.1.2.21.10.1.5ColumnpsSMDUHCurrent4read-onlycurrentSMDUH Current 4 in mA.
1.3.6.1.4.1.6302.2.1.2.21.10.1.6ColumnpsSMDUHCurrent5read-onlycurrentSMDUH Current 5 in mA.
1.3.6.1.4.1.6302.2.1.2.21.10.1.7ColumnpsSMDUHCurrent6read-onlycurrentSMDUH Current 6 in mA.
1.3.6.1.4.1.6302.2.1.2.21.10.1.8ColumnpsSMDUHCurrent7read-onlycurrentSMDUH Current 7 in mA.
1.3.6.1.4.1.6302.2.1.2.21.10.1.9ColumnpsSMDUHCurrent8read-onlycurrentSMDUH Current 8 in mA.
1.3.6.1.4.1.6302.2.1.2.21.10.1.10ColumnpsSMDUHCurrent9read-onlycurrentSMDUH Current 9 in mA.
1.3.6.1.4.1.6302.2.1.2.21.10.1.11ColumnpsSMDUHCurrent10read-onlycurrentSMDUH Current 10 in mA.
1.3.6.1.4.1.6302.2.1.2.21.10.1.12ColumnpsSMDUHCurrent11read-onlycurrentSMDUH Current 11 in mA.
1.3.6.1.4.1.6302.2.1.2.21.10.1.13ColumnpsSMDUHCurrent12read-onlycurrentSMDUH Current 12 in mA.
1.3.6.1.4.1.6302.2.1.2.21.10.1.14ColumnpsSMDUHCurrent13read-onlycurrentSMDUH Current 13 in mA.
1.3.6.1.4.1.6302.2.1.2.21.10.1.15ColumnpsSMDUHCurrent14read-onlycurrentSMDUH Current 14 in mA.
1.3.6.1.4.1.6302.2.1.2.21.10.1.16ColumnpsSMDUHCurrent15read-onlycurrentSMDUH Current 15 in mA.
1.3.6.1.4.1.6302.2.1.2.21.10.1.17ColumnpsSMDUHCurrent16read-onlycurrentSMDUH Current 16 in mA.
1.3.6.1.4.1.6302.2.1.2.21.10.1.18ColumnpsSMDUHCurrent17read-onlycurrentSMDUH Current 17 in mA.
1.3.6.1.4.1.6302.2.1.2.21.10.1.19ColumnpsSMDUHCurrent18read-onlycurrentSMDUH Current 18 in mA.
1.3.6.1.4.1.6302.2.1.2.21.10.1.20ColumnpsSMDUHCurrent19read-onlycurrentSMDUH Current 19 in mA.
1.3.6.1.4.1.6302.2.1.2.21.10.1.21ColumnpsSMDUHCurrent20read-onlycurrentSMDUH Current 20 in mA.
1.3.6.1.4.1.6302.2.1.2.22NodepsSMDUHPower
1.3.6.1.4.1.6302.2.1.2.22.1TablepsSMDUHPowerTablenot-accessiblecurrentTable holding information about SMDUH power.
1.3.6.1.4.1.6302.2.1.2.22.1.1RowpsSMDUHPowerEntrynot-accessiblecurrentAn entry (conceptual row) in the SMDUHPowerTable.
1.3.6.1.4.1.6302.2.1.2.22.1.1.1ColumnpsSMDUHPowerIndexread-onlycurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.22.1.1.2ColumnpsSMDUHPower1read-onlycurrentSMDUH Power 1 in thousandths of kW.
1.3.6.1.4.1.6302.2.1.2.22.1.1.3ColumnpsSMDUHPower2read-onlycurrentSMDUH Power 2.
1.3.6.1.4.1.6302.2.1.2.22.1.1.4ColumnpsSMDUHPower3read-onlycurrentSMDUH Power 3.
1.3.6.1.4.1.6302.2.1.2.22.1.1.5ColumnpsSMDUHPower4read-onlycurrentSMDUH Power 4.
1.3.6.1.4.1.6302.2.1.2.22.1.1.6ColumnpsSMDUHPower5read-onlycurrentSMDUH Power 5.
1.3.6.1.4.1.6302.2.1.2.22.1.1.7ColumnpsSMDUHPower6read-onlycurrentSMDUH Power 6.
1.3.6.1.4.1.6302.2.1.2.22.1.1.8ColumnpsSMDUHPower7read-onlycurrentSMDUH Power 7.
1.3.6.1.4.1.6302.2.1.2.22.1.1.9ColumnpsSMDUHPower8read-onlycurrentSMDUH Power 8.
1.3.6.1.4.1.6302.2.1.2.22.1.1.10ColumnpsSMDUHPower9read-onlycurrentSMDUH Power 9.
1.3.6.1.4.1.6302.2.1.2.22.1.1.11ColumnpsSMDUHPower10read-onlycurrentSMDUH Power 10.
1.3.6.1.4.1.6302.2.1.2.22.1.1.12ColumnpsSMDUHPower11read-onlycurrentSMDUH Power 11.
1.3.6.1.4.1.6302.2.1.2.22.1.1.13ColumnpsSMDUHPower12read-onlycurrentSMDUH Power 12.
1.3.6.1.4.1.6302.2.1.2.22.1.1.14ColumnpsSMDUHPower13read-onlycurrentSMDUH Power 13.
1.3.6.1.4.1.6302.2.1.2.22.1.1.15ColumnpsSMDUHPower14read-onlycurrentSMDUH Power 14.
1.3.6.1.4.1.6302.2.1.2.22.1.1.16ColumnpsSMDUHPower15read-onlycurrentSMDUH Power 15.
1.3.6.1.4.1.6302.2.1.2.22.1.1.17ColumnpsSMDUHPower16read-onlycurrentSMDUH Power 16.
1.3.6.1.4.1.6302.2.1.2.22.1.1.18ColumnpsSMDUHPower17read-onlycurrentSMDUH Power 17.
1.3.6.1.4.1.6302.2.1.2.22.1.1.19ColumnpsSMDUHPower18read-onlycurrentSMDUH Power 18.
1.3.6.1.4.1.6302.2.1.2.22.1.1.20ColumnpsSMDUHPower19read-onlycurrentSMDUH Power 19.
1.3.6.1.4.1.6302.2.1.2.22.1.1.21ColumnpsSMDUHPower20read-onlycurrentSMDUH Power 20.
1.3.6.1.4.1.6302.2.1.2.23NodepsSMDUHEnergy
1.3.6.1.4.1.6302.2.1.2.23.1TablepsSMDUHEnergyTablenot-accessiblecurrentTable holding information about SMDUH energy counters.
1.3.6.1.4.1.6302.2.1.2.23.1.1RowpsSMDUHEnergyEntrynot-accessiblecurrentAn entry (conceptual row) in the SMDUHEnergyTable.
1.3.6.1.4.1.6302.2.1.2.23.1.1.1ColumnpsSMDUHEnergyIndexread-onlycurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.23.1.1.2ColumnpsSMDUHTotalEnergy1read-onlycurrentSMDUH Total Energy 1.
1.3.6.1.4.1.6302.2.1.2.23.1.1.3ColumnpsSMDUHTotalEnergy2read-onlycurrentSMDUH Total Energy 2.
1.3.6.1.4.1.6302.2.1.2.23.1.1.4ColumnpsSMDUHTotalEnergy3read-onlycurrentSMDUH Total Energy 3.
1.3.6.1.4.1.6302.2.1.2.23.1.1.5ColumnpsSMDUHTotalEnergy4read-onlycurrentSMDUH Total Energy 4.
1.3.6.1.4.1.6302.2.1.2.23.1.1.6ColumnpsSMDUHTotalEnergy5read-onlycurrentSMDUH Total Energy 5.
1.3.6.1.4.1.6302.2.1.2.23.1.1.7ColumnpsSMDUHTotalEnergy6read-onlycurrentSMDUH Total Energy 6.
1.3.6.1.4.1.6302.2.1.2.23.1.1.8ColumnpsSMDUHTotalEnergy7read-onlycurrentSMDUH Total Energy 7.
1.3.6.1.4.1.6302.2.1.2.23.1.1.9ColumnpsSMDUHTotalEnergy8read-onlycurrentSMDUH Total Energy 8.
1.3.6.1.4.1.6302.2.1.2.23.1.1.10ColumnpsSMDUHTotalEnergy9read-onlycurrentSMDUH Total Energy 9.
1.3.6.1.4.1.6302.2.1.2.23.1.1.11ColumnpsSMDUHTotalEnergy10read-onlycurrentSMDUH Total Energy 10.
1.3.6.1.4.1.6302.2.1.2.23.1.1.12ColumnpsSMDUHTotalEnergy11read-onlycurrentSMDUH Total Energy 11.
1.3.6.1.4.1.6302.2.1.2.23.1.1.13ColumnpsSMDUHTotalEnergy12read-onlycurrentSMDUH Total Energy 12.
1.3.6.1.4.1.6302.2.1.2.23.1.1.14ColumnpsSMDUHTotalEnergy13read-onlycurrentSMDUH Total Energy 13.
1.3.6.1.4.1.6302.2.1.2.23.1.1.15ColumnpsSMDUHTotalEnergy14read-onlycurrentSMDUH Total Energy 14.
1.3.6.1.4.1.6302.2.1.2.23.1.1.16ColumnpsSMDUHTotalEnergy15read-onlycurrentSMDUH Total Energy 15.
1.3.6.1.4.1.6302.2.1.2.23.1.1.17ColumnpsSMDUHTotalEnergy16read-onlycurrentSMDUH Total Energy 16.
1.3.6.1.4.1.6302.2.1.2.23.1.1.18ColumnpsSMDUHTotalEnergy17read-onlycurrentSMDUH Total Energy 17.
1.3.6.1.4.1.6302.2.1.2.23.1.1.19ColumnpsSMDUHTotalEnergy18read-onlycurrentSMDUH Total Energy 18.
1.3.6.1.4.1.6302.2.1.2.23.1.1.20ColumnpsSMDUHTotalEnergy19read-onlycurrentSMDUH Total Energy 19.
1.3.6.1.4.1.6302.2.1.2.23.1.1.21ColumnpsSMDUHTotalEnergy20read-onlycurrentSMDUH Total Energy 20.
1.3.6.1.4.1.6302.2.1.2.24NodepsSMDU
1.3.6.1.4.1.6302.2.1.2.24.1TablepsSMDUTablenot-accessiblecurrentTable holding information about SMDU.
1.3.6.1.4.1.6302.2.1.2.24.1.1RowpsSMDUEntrynot-accessiblecurrentAn entry (conceptual row) in the SMDU Table.
1.3.6.1.4.1.6302.2.1.2.24.1.1.1ColumnpsSMDUIndexread-onlycurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.24.1.1.2ColumnpsSMDULoad1Powerread-onlycurrentSMDU Load1 Power in thousandths of kW
1.3.6.1.4.1.6302.2.1.2.24.1.1.3ColumnpsSMDULoad2Powerread-onlycurrentSMDU Load2 Power in thousandths of kW
1.3.6.1.4.1.6302.2.1.2.24.1.1.4ColumnpsSMDULoad3Powerread-onlycurrentSMDU Load3 Power in thousandths of kW
1.3.6.1.4.1.6302.2.1.2.24.1.1.5ColumnpsSMDULoad4Powerread-onlycurrentSMDU Load4 Power in thousandths of kW
1.3.6.1.4.1.6302.2.1.2.24.1.1.6ColumnpsSMDULoad5Powerread-onlycurrentSMDU Load5 Power in thousandths of kW
1.3.6.1.4.1.6302.2.1.2.24.1.1.7ColumnpsSMDUShunt1FullScaleCurrentread-writecurrentSMDU Shunt1 Full Scale Current in mA.
1.3.6.1.4.1.6302.2.1.2.24.1.1.8ColumnpsSMDUShunt1FullScaleVoltageread-writecurrentSMDU Shunt1 Full Scale Voltage in thousandths of mV.
1.3.6.1.4.1.6302.2.1.2.24.1.1.9ColumnpsSMDUShunt2FullScaleCurrentread-writecurrentSMDU Shunt2 Full Scale Current in mA.
1.3.6.1.4.1.6302.2.1.2.24.1.1.10ColumnpsSMDUShunt2FullScaleVoltageread-writecurrentSMDU Shunt2 Full Scale Voltage in thousandths of mV.
1.3.6.1.4.1.6302.2.1.2.24.1.1.11ColumnpsSMDUShunt3FullScaleCurrentread-writecurrentSMDU Shunt3 Full Scale Current in mA.
1.3.6.1.4.1.6302.2.1.2.24.1.1.12ColumnpsSMDUShunt3FullScaleVoltageread-writecurrentSMDU Shunt3 Full Scale Voltage in thousandths of mV.
1.3.6.1.4.1.6302.2.1.2.24.1.1.13ColumnpsSMDUShunt4FullScaleCurrentread-writecurrentSMDU Shunt4 Full Scale Current in mA.
1.3.6.1.4.1.6302.2.1.2.24.1.1.14ColumnpsSMDUShunt4FullScaleVoltageread-writecurrentSMDU Shunt4 Full Scale Voltage in thousandths of mV.
1.3.6.1.4.1.6302.2.1.2.24.1.1.15ColumnpsSMDUShunt5FullScaleCurrentread-writecurrentSMDU Shunt5 Full Scale Current in mA.
1.3.6.1.4.1.6302.2.1.2.24.1.1.16ColumnpsSMDUShunt5FullScaleVoltageread-writecurrentSMDU Shunt5 Full Scale Voltage in thousandths of mV.
1.3.6.1.4.1.6302.2.1.2.25NodepsSolar
1.3.6.1.4.1.6302.2.1.2.25.1ScalarnumberOfInstalledSolarread-onlycurrentnumber of Solar converters, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.25.2ScalarnumberOfSolarCommunicatingread-onlycurrentnumber of Solar converters communicating, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.25.3ScalarsolarsUsedCapacityread-onlycurrentUsed capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.25.4ScalarpsSolarTotalCurrentread-onlycurrentSolar Converter Total output current in mA. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.25.5ScalarpsSolarTotalPowerread-onlycurrentSolar Converter Total Output Power in W * 1000.
1.3.6.1.4.1.6302.2.1.2.25.6ScalarpsSolarTotalInputCurrentread-onlycurrentSolar Converter Total input current in mA. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.25.7ScalarpsSolarTotalInputPowerread-onlycurrentSolar Converter Total input Power in kW * 1000.
1.3.6.1.4.1.6302.2.1.2.25.8ScalarpsSolarModeread-writecurrentSolar mode, Disabled(0), RECT-SOLAR(1), Solar(2)
1.3.6.1.4.1.6302.2.1.2.25.9ScalarpsSolarRunningWayread-writecurrentSolar mode, Disabled(0), RECT-SOLAR(1), Solar(2)
1.3.6.1.4.1.6302.2.1.2.26NodepsSetting
1.3.6.1.4.1.6302.2.1.2.26.1ScalarsettingSolarFloatVoltageread-writecurrentSolar Float voltage stored as mV
1.3.6.1.4.1.6302.2.1.2.26.2ScalarsettingSolarEQChargeVoltageread-writecurrentSolar Equalize voltage stored as mV
1.3.6.1.4.1.6302.2.1.2.26.3ScalarsettingRectifierFloatVoltageread-writecurrentRectifier Float voltage stored as mV
1.3.6.1.4.1.6302.2.1.2.26.4ScalarsettingRectifierEQChargeVoltageread-writecurrentRectifier Equalize voltage stored as mV
1.3.6.1.4.1.6302.2.1.2.26.5ScalarsettingRectifierWalkInEnableread-writecurrentRectifier walk-in Enable, Disabled(0), Active(1)
1.3.6.1.4.1.6302.2.1.2.26.6ScalarsettingRectifierWalkInTimeread-writecurrentRectifier walk-in time in seconds.
1.3.6.1.4.1.6302.2.1.2.26.7ScalarsettingRectifierCurrentLimitEnableread-writecurrentRectifier Current Limit Enable, Disabled(0), Active(1)
1.3.6.1.4.1.6302.2.1.2.26.8ScalarsettingRectifierCurrentLimitread-writecurrentRectifier current limit stored as mA
1.3.6.1.4.1.6302.2.1.2.26.9ScalarsettingRectifierInputCurrentLimitread-writecurrentRectifier input current limit stored as mA
1.3.6.1.4.1.6302.2.1.2.26.10ScalarsettingGeneratorPowerLimitEnableread-writecurrentDiesel Generator Power Limit Enable, Disabled(0), Active(1)
1.3.6.1.4.1.6302.2.1.2.26.11ScalarsettingGeneratorPowerLimitPointread-writecurrentDiesel Generator Power Limit point in percent * 1000.
1.3.6.1.4.1.6302.2.1.2.26.12ScalarsettingGeneratorStartVoltageread-writecurrentDiesel Generator Start voltage stored as mV
1.3.6.1.4.1.6302.2.1.2.26.13ScalarsettingGeneratorStopVoltageread-writecurrentDiesel Generator Stop voltage stored as mV
1.3.6.1.4.1.6302.2.1.2.26.14ScalarsettingHybridModeread-writecurrentSolar mode, Disabled(0), RECT-SOLAR(1), Solar(2)
1.3.6.1.4.1.6302.2.1.2.26.15ScalarsettingGeneratorRelayread-writecurrentDiesel Generator Relay, None(0), Relay Output 1(1), Relay Output 2(2), Relay Output 3(3), Relay Output 4(4), Relay Output 5(5), Relay Output 6(6), Relay Output…
1.3.6.1.4.1.6302.2.1.2.27NodepsCabinet
1.3.6.1.4.1.6302.2.1.2.27.1TablepsCabinetTablenot-accessiblecurrentTable holding information about Cabinet.
1.3.6.1.4.1.6302.2.1.2.27.1.1RowpsCabinetEntrynot-accessiblecurrentAn entry (conceptual row) in the Cabinet Table.
1.3.6.1.4.1.6302.2.1.2.27.1.1.1ColumnpsCabinetIndexread-onlycurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.27.1.1.2ColumnpsCabinetTotalCurrentread-onlycurrentCabinet Total Current in mA
1.3.6.1.4.1.6302.2.1.2.27.1.1.3ColumnpsCabinetTotalPowerread-onlycurrentCabinet Total Power in thousandths of W
1.3.6.1.4.1.6302.2.1.2.27.1.1.4ColumnpsCabinetTotalEnergyread-onlycurrentCabinet Total Energy in thousandths of KWh
1.3.6.1.4.1.6302.2.1.2.27.1.1.5ColumnpsCabinetAlarmStatusread-onlycurrentCabinet Alarm Status
1.3.6.1.4.1.6302.2.1.3ScalaralarmLastTrapNoread-onlycurrentThe sequence number of last submitted alarm trap, also last row in alarmTrapTable.
1.3.6.1.4.1.6302.2.1.4TablealarmActiveAlarmTablenot-accessiblecurrentTable holding information about the currently active alarms.
1.3.6.1.4.1.6302.2.1.4.1RowactiveAlarmEntrynot-accessiblecurrentAn entry (conceptual row) in the alarmTrapTable.
1.3.6.1.4.1.6302.2.1.4.1.1ColumnalarmIndexread-onlycurrentThe unique sequence number of this alarm trap.
1.3.6.1.4.1.6302.2.1.4.1.2ColumnalarmTimeread-onlycurrentDate and time when event occured (local time), including timezone if supported by controller.
1.3.6.1.4.1.6302.2.1.4.1.3ColumnalarmStatusChangeread-onlycurrentThe type of alarm change. One of (1) activated (2) deactivated
1.3.6.1.4.1.6302.2.1.4.1.4ColumnalarmSeverityread-onlycurrentThe severity of the alarm. One of (3) warning - OA, lowest level of alarm severity (4) minor - A3 (5) major - MA (6) critical - CA, highest level of alarm seve…
1.3.6.1.4.1.6302.2.1.4.1.5ColumnalarmDescriptionread-onlycurrentFree-text description of alarm.
1.3.6.1.4.1.6302.2.1.4.1.6ColumnalarmTyperead-onlycurrentAlarm type, i.e. an integer specifying the type of alarm.
1.3.6.1.4.1.6302.2.1.5NodepowerEvents
1.3.6.1.4.1.6302.2.1.5.1NotificationalarmTrapcurrentAn alarm trap is sent when an alarm occurs (activated) or returns to normal state (deactivated). Alarm traps are logged in alarmTrapTable. Variables in this tr…
1.3.6.1.4.1.6302.2.1.5.2NotificationalarmActiveTrapcurrentAn alarm trap is sent when an alarm occurs (activated) Variables in this trap * alarmTime - Date and time when event occured (local time), including timezone i…
1.3.6.1.4.1.6302.2.1.5.3NotificationalarmCeaseTrapcurrentAn alarm trap is sent when an alarm returns to normal state (clear, deactivated). Variables in this trap: * alarmTime - Date and time when event occured (local…
Type Definitions
NameSyntaxStatusDescription
StatusINTEGER { unknown(1), normal(2), warning(3), minor(4), major(5), critical(6), unmanaged(7), restricted(8), testing(9), disabled(10) }currentThis integer value represents the operational or administrative status of the system. Also used as alarm severity. Depending on situation there may be limits on allowed values. Operational values: (1) unknown - status h…
StatusChangeINTEGER { activated(1), deactivated(2) }currentIndicates 'activated' (1) or 'deactivated' (2) alarm events.