ELTEK-BC2000-DC-POWER-MIB
391 objects
SNMP access to Eltek DC Power systems through the BC2000 controller.
Imported Objects
| RFC1155-SMI | Gauge |
| RFC1213-MIB | -- sysUpTime -- |
| SNMPv2-CONF | -- MODULE-COMPLIANCE -- OBJECT-GROUP -- |
| SNMPv2-SMI | Counter32 enterprises Gauge32 Integer32 IpAddress -- MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-IDENTITY OBJECT-TYPE |
| SNMPv2-TC | AutonomousType DisplayString TestAndIncr TEXTUAL-CONVENTION TimeInterval -- TimeStamp -- |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.13858 | Identityeltek | SNMP access to Eltek DC Power systems through the BC2000 controller. | ||
| 1.3.6.1.4.1.13858.2 | NodevpwrDcPowerSystem | |||
| 1.3.6.1.4.1.13858.2.1 | NodevpwrSystemIdentGroup | |||
| 1.3.6.1.4.1.13858.2.1.1 | ScalarvpwrIdentManufacturer | read-only | current | The name of the DC Power manufacturer. |
| 1.3.6.1.4.1.13858.2.1.2 | ScalarvpwrIdentModel | read-only | current | The DC Power Model designation. |
| 1.3.6.1.4.1.13858.2.1.3 | ScalarvpwrIdentControllerVersion | read-only | current | The hardware/firmware version(s). This variable may or may not have the same value as vpwrIdentAgentSoftwareVersion. |
| 1.3.6.1.4.1.13858.2.1.4 | ScalarvpwrIdentAgentSoftwareVersion | read-only | current | The SNMP agent software version. This variable may or may not have the same value as vpwrIdentControllerVersion. |
| 1.3.6.1.4.1.13858.2.1.5 | ScalarvpwrIdentName | read-write | current | A string identifying the system. This object should be set by the administrator. |
| 1.3.6.1.4.1.13858.2.1.6 | TablevpwrSystemIdentTable | not-accessible | current | This table describes shelves and modules that make up the sysetm. |
| 1.3.6.1.4.1.13858.2.1.6.1 | RowvpwrSystemIdentEntry | not-accessible | current | An entry containing information applicable to a particular alarm. |
| 1.3.6.1.4.1.13858.2.1.6.1.1 | ColumnvpwrShelfIndex | read-only | current | Identifies shelf number that this module belongs to. The possible values are 1 through 16 limited by vpwrSystemShelfCapacity. |
| 1.3.6.1.4.1.13858.2.1.6.1.2 | ColumnvpwrModuleIndex | read-only | current | This object identifies the module by its position in the shelf. Module numbering is left to right starting with module 1. So, the module in the first slot has … |
| 1.3.6.1.4.1.13858.2.1.6.1.3 | ColumnvpwrModuleOID | read-only | current | It indicates the type of the module by specifiying its OID |
| 1.3.6.1.4.1.13858.2.1.6.1.4 | ColumnvpwrModuleCurrent | read-only | current | The meaning of this object depends upon the module type which is indicated by vpwrModuleOID as follows - Current for Rectifier module in centiamps. - Not Appli… |
| 1.3.6.1.4.1.13858.2.1.6.1.5 | ColumnvpwrModuleOperStatus | read-only | current | This object indicates current over all status of the module. |
| 1.3.6.1.4.1.13858.2.1.6.1.6 | ColumnvpwrModuleCapacity | read-only | current | The meaning of this object depends upon the module type which is indicated by vpwrModuleOID as follows - Capacity for Rectifier module. - Not Applicable for LV… |
| 1.3.6.1.4.1.13858.2.2 | NodevpwrSystemConfigGroup | |||
| 1.3.6.1.4.1.13858.2.2.1 | ScalarvpwrSystemTempCompensation | read-write | current | This parameter enables/disables temperature compensation. |
| 1.3.6.1.4.1.13858.2.2.2 | ScalarvpwrSystemTempCompStartTemperature | read-write | current | The temperature at which temperature compensation becomes active. |
| 1.3.6.1.4.1.13858.2.2.3 | ScalarvpwrSystemTempCompStopVoltage | read-write | current | When temperature compensation is active, vpwrSystemTempCompStopVoltage is the limit to which float voltage will be reduced. For example, to set this voltage to… |
| 1.3.6.1.4.1.13858.2.2.4 | ScalarvpwrSystemTempCompensationSlope | read-write | current | The rate at which float voltage is changed, within the specified limits, when temperature compensation is active. |
| 1.3.6.1.4.1.13858.2.2.5 | ScalarvpwrSystemThermalSenseType | read-write | current | This parameter selects the temperature sensing point for temperature compensation (in)activation. |
| 1.3.6.1.4.1.13858.2.2.6 | ScalarvpwrSystemHVAlarmSetpoint | read-write | current | System High voltage alarm voltage setting. |
| 1.3.6.1.4.1.13858.2.2.7 | ScalarvpwrSystemBDAlarmSetpoint | read-write | current | System Battery Discharge voltage setting. |
| 1.3.6.1.4.1.13858.2.2.8 | ScalarvpwrSystemInternalTempLThreshold | read-write | current | Temperature value at which temperature compensation inactive (clear) trap would be sent if temperature compensation was active when this value is reached. |
| 1.3.6.1.4.1.13858.2.2.9 | ScalarvpwrSystemInternalTempUThreshold | read-write | current | Temperature value at which temperature compensation active (set) trap would be sent. |
| 1.3.6.1.4.1.13858.2.3 | NodevpwrSystemParameterGroup | |||
| 1.3.6.1.4.1.13858.2.3.1 | ScalarvpwrSystemShelfCapacity | read-only | current | It describes the maximum number of shelves that can/are controlled by the controller. Each shelf is uniquely numbered in the range from 1 to vpwrShelfCapacity. |
| 1.3.6.1.4.1.13858.2.3.2 | ScalarvpwrSystemVoltage | read-only | current | The current system voltage. |
| 1.3.6.1.4.1.13858.2.3.3 | ScalarvpwrSystemCurrent | read-only | current | The current system current. |
| 1.3.6.1.4.1.13858.2.3.4 | ScalarvpwrSystemControllerState | read-only | current | Current System state as shown on the enhanced display. |
| 1.3.6.1.4.1.13858.2.3.5 | ScalarvpwrSystemInternalTemperature | read-only | current | The current controller internal temperature. |
| 1.3.6.1.4.1.13858.2.3.6 | ScalarvpwrSystemTempCompensationState | read-only | current | Active or Inactive. Applicable only if temperature compensation is enabled. This means that the controller is temperature compensating the float voltage. |
| 1.3.6.1.4.1.13858.2.3.7 | ScalarvpwrSystemType | read-only | current | This parameter describes the type of the system being managed. This object is set by Eltek Valere Inc. |
| 1.3.6.1.4.1.13858.2.3.8 | ScalarvpwrSystemCumulativeUpTime | read-only | current | This parameter describes the cumulative runtime in seconds of the Eltek Valere controller. |
| 1.3.6.1.4.1.13858.2.3.9 | ScalarvpwrSystemBatteryRemainingTime | read-only | current | This parameter describes the remaining battery capacity based upon installed battery capacity and plant load. This number would change as the SOC parameters of… |
| 1.3.6.1.4.1.13858.2.4 | NodevpwrSystemPanelIdentGroup | |||
| 1.3.6.1.4.1.13858.2.4.1 | TablevpwrPanelStatusTable | not-accessible | current | This table describes shelves and modules that make up the panels. |
| 1.3.6.1.4.1.13858.2.4.1.1 | RowvpwrPanelStatus | not-accessible | current | An entry containing information applicable to a particular panel making up the system. |
| 1.3.6.1.4.1.13858.2.4.1.1.1 | ColumnvpwrPanelStatusIndex | read-only | current | Identifies panel number that this module belongs to. The possible values are 1 through 8, starting from the top. |
| 1.3.6.1.4.1.13858.2.4.1.1.2 | ColumnvpwrPanelStatusModuleIndex | read-only | current | This object identifies the module within the panel. The orentation of modules within the panel is mappable. |
| 1.3.6.1.4.1.13858.2.4.1.1.3 | ColumnvpwrPanelStatusModuleOID | read-only | current | The module OID. |
| 1.3.6.1.4.1.13858.2.4.1.1.4 | ColumnvpwrPanelStatusModuleCurrent | read-only | current | The current measured by the device (if applicable). LVD current reported in deciAmps. |
| 1.3.6.1.4.1.13858.2.4.1.1.5 | ColumnvpwrpanelStatusModuleOperStatus | read-only | current | This object indicates current over all status of the module. |
| 1.3.6.1.4.1.13858.2.4.1.1.6 | ColumnvpwrPanelStatusModuleCapacity | read-only | current | The maximum capacity of the module (if applicable). |
| 1.3.6.1.4.1.13858.2.4.2 | TablevpwrPanelIdentTable | not-accessible | current | This table describes shelves and modules that make up the panels. |
| 1.3.6.1.4.1.13858.2.4.2.1 | RowvpwrPanelIdentEntry | not-accessible | current | An entry containing information applicable to a particular panel making up the system. |
| 1.3.6.1.4.1.13858.2.4.2.1.1 | ColumnvpwrPanelIndex | read-only | current | Identifies panel number that this module belongs to. The possible values are 1 through 8, starting from the top. |
| 1.3.6.1.4.1.13858.2.4.2.1.2 | ColumnvpwrPanelModuleIndex | read-only | current | This object identifies the module within the panel. The orentation of modules within the panel is mappable. |
| 1.3.6.1.4.1.13858.2.4.2.1.3 | ColumnvpwrPanelModuleSerNum | read-only | current | The module serial number. |
| 1.3.6.1.4.1.13858.2.4.2.1.4 | ColumnvpwrPanelModuleModelName | read-only | current | The model name of the device. |
| 1.3.6.1.4.1.13858.2.4.2.1.5 | ColumnvpwrPanelModuleFWVer | read-only | current | The module firmware version. |
| 1.3.6.1.4.1.13858.2.4.2.1.6 | ColumnvpwrPanelModuleTestDate | read-only | current | The manufacturing test date. |
| 1.3.6.1.4.1.13858.2.5 | NodevpwrSystemHistoryGroup | |||
| 1.3.6.1.4.1.13858.2.5.1 | TablevpwrSysHistAlarmTable | not-accessible | current | This table provides a list of most recent alarms. |
| 1.3.6.1.4.1.13858.2.5.1.1 | RowvpwrSysHistAlarmEntry | not-accessible | current | An entry describing an alarm. |
| 1.3.6.1.4.1.13858.2.5.1.1.1 | ColumnvpwrSysHistAlarmIndex | read-only | current | Alarm index. |
| 1.3.6.1.4.1.13858.2.5.1.1.2 | ColumnvpwrSysHistAlarmDescription | read-only | current | Alarm description including time stamp. |
| 1.3.6.1.4.1.13858.2.6 | NodevpwrSystemAlarmGroup | |||
| 1.3.6.1.4.1.13858.2.6.1 | ScalarvpwrSystemAlarmMajor | read-only | current | Indicates a Major Alarm exists on the system. |
| 1.3.6.1.4.1.13858.2.6.2 | ScalarvpwrSystemAlarmMinor | read-only | current | Indicates a Minor Alarm exists on the system. |
| 1.3.6.1.4.1.13858.2.6.3 | ScalarvpwrSystemACFailAlarm | read-only | current | One or more rectifiers have reported AC failure. If system is configured to report rectifier communication failure as AC fail this alarm will report. |
| 1.3.6.1.4.1.13858.2.6.4 | ScalarvpwrSystemHighVoltageWarningAlarm | read-only | current | System has exceeded High Voltage Warning Setpoint. Check for high voltage on system bus. |
| 1.3.6.1.4.1.13858.2.6.5 | ScalarvpwrSystemHighVoltageShutdownAlarm | read-only | current | One or more rectifiers have shut down due to high voltage present on output. Check bus voltage and reseat rectifiers that have indicated this problem. |
| 1.3.6.1.4.1.13858.2.6.6 | ScalarvpwrSystemBatteryonDischargeAlarm | read-only | current | System voltage has currently dropped below the alarm setpoint. This may be due to battery testing or AC failure. |
| 1.3.6.1.4.1.13858.2.6.7 | ScalarvpwrSystemLowVoltageWarningAlarm | read-only | current | System Voltage has dropped below setpoint for Low Voltage Alarm. This may occur during battery testing or AC failure |
| 1.3.6.1.4.1.13858.2.6.8 | ScalarvpwrSystemLVDOpenAlarm | read-only | current | One or more contactors have opened. This occurs normally during system power on. If it occurs during operation this may indicate system is operating below LVD … |
| 1.3.6.1.4.1.13858.2.6.9 | ScalarvpwrSystemDistributionAlarm | read-only | current | One or more distribution alarm inputs are reporting an error condition. Check source of alarm and correct issue. |
| 1.3.6.1.4.1.13858.2.6.10 | ScalarvpwrSystemAuxiliaryAlarm | read-only | current | One or more Auxliary alarm inputs are reporting an error condition. Check source of alarm and correct issue. |
| 1.3.6.1.4.1.13858.2.6.11 | ScalarvpwrSystemRedundantCapAlarm | read-only | current | The system load has exceeded the requirements for redundancy. This may be a temporary system overload condition or caused by a rectifier alarm. |
| 1.3.6.1.4.1.13858.2.6.12 | ScalarvpwrSystemRectIShareAlarm | read-only | current | One or more rectifiers are reporting a mismatch in current. This may be due to mismatched rectifier models or one or more rectifiers not current sharing |
| 1.3.6.1.4.1.13858.2.6.13 | ScalarvpwrSystemSnglRectAlarm | read-only | current | |
| 1.3.6.1.4.1.13858.2.6.14 | ScalarvpwrSystemMultRectAlarm | read-only | current | |
| 1.3.6.1.4.1.13858.2.6.15 | ScalarvpwrSystemModlCommAlarm | read-only | current | |
| 1.3.6.1.4.1.13858.2.6.16 | ScalarvpwrSystemOverTempAlarm | read-only | current | |
| 1.3.6.1.4.1.13858.2.6.17 | ScalarvpwrSystemThermRAAlarm | read-only | current | Thermal Runaway has occurred on system. Check temperature inputs. |
| 1.3.6.1.4.1.13858.2.6.18 | ScalarvpwrSystemBDTAlarm | read-only | current | System has entered Battery Discharge Test mode |
| 1.3.6.1.4.1.13858.2.6.19 | ScalarvpwrSystemRectUVAlarm | read-only | current | Rectifier output has dropped 1V below Low Voltage Alarm setpoint |
| 1.3.6.1.4.1.13858.2.6.20 | ScalarvpwrSystemMultRectUVAlarm | read-only | current | |
| 1.3.6.1.4.1.13858.2.6.21 | ScalarvpwrSystemSnglRngrAlarm | read-only | current | |
| 1.3.6.1.4.1.13858.2.6.22 | ScalarvpwrSystemMultRngrAlarm | read-only | current | |
| 1.3.6.1.4.1.13858.2.6.23 | ScalarvpwrSystemTempProbeAlarm | read-only | current | Temp probe input missing or failed |
| 1.3.6.1.4.1.13858.2.6.24 | ScalarvpwrSystemRngrCommAlarm | read-only | current | Ringer Module has stopped communicating with Controller. |
| 1.3.6.1.4.1.13858.2.6.25 | ScalarvpwrSystemDistPMCommAlarm | read-only | current | One or more distribution alarm modules, TRIOs, or PM modules has stopped communicating with Controller. |
| 1.3.6.1.4.1.13858.2.6.26 | ScalarvpwrSystemRectILimitAlarm | read-only | current | Rectifier has reached current limit setpoint. |
| 1.3.6.1.4.1.13858.2.6.27 | ScalarvpwrSystemMultRectILimitAlarm | read-only | current | |
| 1.3.6.1.4.1.13858.2.6.28 | ScalarvpwrSystemUnmappedI2CCANAlarm | read-only | current | Recheck all I2C and CAN dip switch settings. One or more devices in conflict. |
| 1.3.6.1.4.1.13858.2.6.29 | ScalarvpwrSystemConfigErrAlarm | read-only | current | Recheck all I2C and CAN dip switch settings. One or more devices in conflict. |
| 1.3.6.1.4.1.13858.2.6.30 | ScalarvpwrSystemDispFWAlarm | read-only | current | |
| 1.3.6.1.4.1.13858.2.6.31 | ScalarvpwrSystemUndefinedAlarm | read-only | current | |
| 1.3.6.1.4.1.13858.3 | NodevpwrDcPowerRectifier | |||
| 1.3.6.1.4.1.13858.3.1 | NodevpwrRectifierConfigGroup | |||
| 1.3.6.1.4.1.13858.3.1.1 | ScalarvpwrRectifierFVSetpoint | read-write | current | System Float Voltage setting |
| 1.3.6.1.4.1.13858.3.1.2 | ScalarvpwrRectifierHVSDSetpoint | read-write | current | System High Voltage Shutdown voltage setting |
| 1.3.6.1.4.1.13858.3.1.3 | ScalarvpwrRectifierCurrentLimitAdminState | read-write | current | This parameter allows enabling or rectifier current limit |
| 1.3.6.1.4.1.13858.3.1.4 | ScalarvpwrRectifierCurrentLimit | read-write | current | Rectifier current limit setpoint |
| 1.3.6.1.4.1.13858.3.1.5 | ScalarvpwrRectifierFallbackAdminState | read-write | current | Enables Rectifier to use Fallback Voltage when it loses communication with the controller. This applies to all rectifiers. |
| 1.3.6.1.4.1.13858.3.1.6 | ScalarvpwrRectifierFallbackVoltage | read-write | current | Fallback Voltage setpoint to use when rectifier loses communication with the controller. This applies to all rectifiers. |
| 1.3.6.1.4.1.13858.3.2 | NodevpwrRectifierAlarmGroup | |||
| 1.3.6.1.4.1.13858.3.2.1 | IdentityvpwrRectAlarmDCFail | current | ||
| 1.3.6.1.4.1.13858.3.2.2 | IdentityvpwrRectAlarmBoostFail | current | ||
| 1.3.6.1.4.1.13858.3.2.3 | IdentityvpwrRectAlarmACFail | current | ||
| 1.3.6.1.4.1.13858.3.2.4 | IdentityvpwrRectAlarmHVSD | current | ||
| 1.3.6.1.4.1.13858.3.2.5 | IdentityvpwrRectAlarmFanFail | current | ||
| 1.3.6.1.4.1.13858.3.2.6 | IdentityvpwrRectAlarmAmbTemp | current | ||
| 1.3.6.1.4.1.13858.3.2.7 | IdentityvpwrRectAlarmIntTemp | current | ||
| 1.3.6.1.4.1.13858.3.2.8 | IdentityvpwrRectAlarmIShare | current | ||
| 1.3.6.1.4.1.13858.3.2.9 | IdentityvpwrRectAlarmUV | current | ||
| 1.3.6.1.4.1.13858.3.2.10 | IdentityvpwrRectAlarmLowVoltage | current | ||
| 1.3.6.1.4.1.13858.3.2.11 | IdentityvpwrRectAlarmReserved | current | ||
| 1.3.6.1.4.1.13858.3.2.12 | IdentityvpwrRectAlarmDCEnable | current | ||
| 1.3.6.1.4.1.13858.3.2.13 | IdentityvpwrRectAlarmRemoteShutdown | current | ||
| 1.3.6.1.4.1.13858.3.2.14 | IdentityvpwrRectAlarmModDisableShutdown | current | ||
| 1.3.6.1.4.1.13858.3.2.15 | IdentityvpwrRectAlarmShortPinShutdown | current | ||
| 1.3.6.1.4.1.13858.3.2.16 | IdentityvpwrRectAlarmBoostComm | current | ||
| 1.3.6.1.4.1.13858.4 | NodevpwrDcPowerLvd | |||
| 1.3.6.1.4.1.13858.4.1 | NodevpwrLvdConfigGroup | |||
| 1.3.6.1.4.1.13858.4.1.1 | ScalarvpwrLvdWarningSetpoint | read-write | current | LVD Warning voltage setpoint. |
| 1.3.6.1.4.1.13858.4.1.2 | ScalarvpwrLvdDisconnectSetpoint | read-write | current | LVD disconnect voltage setpoint. |
| 1.3.6.1.4.1.13858.4.1.3 | ScalarvpwrLvdReconnectSetpoint | read-write | current | LVD Reconnect voltage setpoint. |
| 1.3.6.1.4.1.13858.4.1.4 | ScalarvpwrLvdReconnectDelayTimer | read-only | current | The delay time, in seconds, before LVD is reconnected |
| 1.3.6.1.4.1.13858.4.1.7 | ScalarvpwrLvd2DisconnectSetpoint | read-write | current | LVD disconnect voltage setpoint. |
| 1.3.6.1.4.1.13858.4.1.8 | ScalarvpwrLvd2ReconnectSetpoint | read-write | current | LVD Reconnect voltage setpoint. |
| 1.3.6.1.4.1.13858.4.1.9 | ScalarvpwrLvd2ReconnectDelayTimer | read-only | current | The delay time, in seconds, before LVD is reconnected |
| 1.3.6.1.4.1.13858.4.1.11 | ScalarvpwrLvd3DisconnectSetpoint | read-write | current | LVD disconnect voltage setpoint. |
| 1.3.6.1.4.1.13858.4.1.12 | ScalarvpwrLvd3ReconnectSetpoint | read-write | current | LVD Reconnect voltage setpoint. |
| 1.3.6.1.4.1.13858.4.1.13 | ScalarvpwrLvd3ReconnectDelayTimer | read-only | current | The delay time, in seconds, before LVD is reconnected |
| 1.3.6.1.4.1.13858.4.1.15 | ScalarvpwrLvd4DisconnectSetpoint | read-write | current | LVD disconnect voltage setpoint. |
| 1.3.6.1.4.1.13858.4.1.16 | ScalarvpwrLvd4ReconnectSetpoint | read-write | current | LVD Reconnect voltage setpoint. |
| 1.3.6.1.4.1.13858.4.1.17 | ScalarvpwrLvd4ReconnectDelayTimer | read-only | current | The delay time, in seconds, before LVD is reconnected |
| 1.3.6.1.4.1.13858.5 | ScalarvpwrDCPowerLampTest | read-write | current | Lamp Test for modules |
| 1.3.6.1.4.1.13858.6 | NodevpwrDcPowerModuleIdent | |||
| 1.3.6.1.4.1.13858.6.1 | TablevpwrDcPowerModuleIdentTable | not-accessible | current | This table describes power modules that make up the system. |
| 1.3.6.1.4.1.13858.6.1.1 | RowvpwrDcPowerModuleIdentEntry | not-accessible | current | An entry containing information applicable to a power module. |
| 1.3.6.1.4.1.13858.6.1.1.1 | ColumnvpwrShelfIndex1 | read-only | current | Identifies shelf number that this module belongs to. The possible values are 1 through 2, starting from the top. |
| 1.3.6.1.4.1.13858.6.1.1.2 | ColumnvpwrDCModuleIndex | read-only | current | This object identifies the module within the shelf. |
| 1.3.6.1.4.1.13858.6.1.1.3 | ColumnvpwrModuleSerialNumber | read-only | current | Serial Number of the module |
| 1.3.6.1.4.1.13858.6.1.1.4 | ColumnvpwrModuleModelNumber | read-only | current | Model Number of the module. |
| 1.3.6.1.4.1.13858.6.1.1.5 | ColumnvpwrModuleFwVersion | read-only | current | Firmware version of the module. |
| 1.3.6.1.4.1.13858.6.1.1.6 | ColumnvpwrModuleTestDate | read-only | current | Date when the module was last tested. |
| 1.3.6.1.4.1.13858.6.1.1.7 | ColumnvpwrModuleOperHours | read-only | current | Cumulative Operating Hours. |
| 1.3.6.1.4.1.13858.7 | NodevpwrDcPowerBatteryGroup | |||
| 1.3.6.1.4.1.13858.7.1 | NodevpwrBatteryTempGroup | |||
| 1.3.6.1.4.1.13858.7.1.1 | TablevpwrBatteryTempTable | not-accessible | current | This table describes battery temperature probes. |
| 1.3.6.1.4.1.13858.7.1.1.1 | RowvpwrBatteryTempEntry | not-accessible | current | An entry containing information applicable to a particular temperature probe. |
| 1.3.6.1.4.1.13858.7.1.1.1.1 | ColumnvpwrBatteryTempIndex | read-only | current | Index into temperature table |
| 1.3.6.1.4.1.13858.7.1.1.1.2 | ColumnvpwrBatteryTempName | read-write | current | A string identifying probe location. |
| 1.3.6.1.4.1.13858.7.1.1.1.3 | ColumnvpwrBatteryTemp | read-only | current | Current temperature as recorded by the probe. |
| 1.3.6.1.4.1.13858.7.1.2 | ScalarvpwrBatteryTempLThreshold | read-write | current | Temperature value at which a clear trap would be sent. All three battery temperature must be at or below this value to trigger this trap. |
| 1.3.6.1.4.1.13858.7.1.3 | ScalarvpwrBatteryTempUThreshold | read-write | current | Temperature value at which a set trap would be sent. Any one of the three battery temperatures at or exceeding this limit would trigger the trap. |
| 1.3.6.1.4.1.13858.7.1.4 | ScalarbatteryTempCompensation | read-write | current | This parameter enables/disables temperature compensation. |
| 1.3.6.1.4.1.13858.7.1.5 | ScalarbatteryTempCompHighStartTemperature | read-write | current | The temperature at which temperature compensation becomes active. |
| 1.3.6.1.4.1.13858.7.1.6 | ScalarbatteryTempCompHighStopVoltage | read-write | current | When temperature compensation is active, batteryTempCompHighStopVoltage is the limit to which float voltage will be reduced. For example, to set this voltage t… |
| 1.3.6.1.4.1.13858.7.1.7 | ScalarbatteryTempCompHighSlope | read-write | current | The rate at which float voltage is changed, within the specified limits, when temperature compensation is active. |
| 1.3.6.1.4.1.13858.7.1.8 | ScalarbatteryTempCompLowStartTemperature | read-write | current | The temperature at which temperature compensation becomes active. |
| 1.3.6.1.4.1.13858.7.1.9 | ScalarbatteryTempCompLowStopVoltage | read-write | current | When temperature compensation is active, batteryTempCompLowStopVoltage is the limit to which float voltage will be reduced. For example, to set this voltage to… |
| 1.3.6.1.4.1.13858.7.1.10 | ScalarbatteryTempCompLowSlope | read-write | current | The rate at which float voltage is changed, within the specified limits, when temperature compensation is active. |
| 1.3.6.1.4.1.13858.7.1.11 | ScalarbatteryTempCompRunawayTemperature | read-write | current | The temperature at which system voltage will be set to batteryTempCompRunawayStopVoltage. |
| 1.3.6.1.4.1.13858.7.1.12 | ScalarbatteryTempCompRunawayStopVoltage | read-write | current | When temperature compensation is enabled, float voltage will be reduced to batteryTempCompRunawayStopVoltage if temperature reaches batteryTempCompRunawayTempe… |
| 1.3.6.1.4.1.13858.7.1.13 | ScalarbatteryTempCompSenseSource | read-write | current | This parameter selects the temperature sensing point for temperature compensation (in)activation. |
| 1.3.6.1.4.1.13858.7.1.14 | ScalarbatteryTempCompRunawayState | read-only | current | This parameter selects the temperature sensing point for temperature compensation (in)activation. |
| 1.3.6.1.4.1.13858.7.2 | NodevpwrBatteryCurrentGroup | |||
| 1.3.6.1.4.1.13858.7.2.1 | ScalarvpwrBatteryCurrentLimitAdminState | read-write | current | This parameter allows enabling or disabling battery current limit. |
| 1.3.6.1.4.1.13858.7.2.2 | ScalarvpwrBatteryCurrentLimit | read-write | current | |
| 1.3.6.1.4.1.13858.7.2.3 | ScalarvpwrBatteryCurrent | read-only | current | Battery current |
| 1.3.6.1.4.1.13858.7.3 | NodevpwrBatteryBoostGroup | |||
| 1.3.6.1.4.1.13858.7.3.1 | ScalarvpwrBoostAdminState | read-write | current | This parameter allows enabling or disabling boost. |
| 1.3.6.1.4.1.13858.7.3.2 | ScalarvpwrBoostVoltage | read-write | current | |
| 1.3.6.1.4.1.13858.7.3.3 | ScalarvpwrBoostDuration | read-write | current | Number of seconds for boost. |
| 1.3.6.1.4.1.13858.7.3.4 | ScalarvpwrBoostOperState | read-write | current | This parameter allows starting or stopping boost if it is enabled. |
| 1.3.6.1.4.1.13858.7.4 | NodevpwrBatteryDischargeTestGroup | |||
| 1.3.6.1.4.1.13858.7.4.1 | ScalarvpwrBDTAdminState | read-write | current | Enable / Disable Battery Discharge Test execution. |
| 1.3.6.1.4.1.13858.7.4.2 | ScalarvpwrBDTDuration | read-only | current | BDT Duration Setpoint. |
| 1.3.6.1.4.1.13858.7.4.3 | ScalarvpwrBDTAlarmVoltage | read-write | current | BDT Alarm Voltage Setpoint. |
| 1.3.6.1.4.1.13858.7.4.4 | ScalarvpwrBDTAbortVoltage | read-write | current | BDT Abort Voltage Setpoint. |
| 1.3.6.1.4.1.13858.7.4.5 | ScalarvpwrBDTAlarmCoefficient | read-only | current | Deprecated. Always returns 1 |
| 1.3.6.1.4.1.13858.7.4.6 | ScalarvpwrBDTOperState | read-only | current | Start/Stop Battery Discharge Test execution. |
| 1.3.6.1.4.1.13858.7.4.7 | ScalarvpwrBDTClearAlarm | read-only | current | Clears any active BDT alarm. |
| 1.3.6.1.4.1.13858.7.4.8 | ScalarvpwrBDTActualTime | read-only | current | Actual BDT runtime in minutes. |
| 1.3.6.1.4.1.13858.7.4.9 | ScalarvpwrBDTAlarmDelay | read-only | current | Delay, in minutes, before checking and raising BDT alarm. Test: Plant Voltage <= BDTAlarmVoltage |
| 1.3.6.1.4.1.13858.7.4.10 | ScalarvpwrBDTResult | read-only | current | Results of BDT. |
| 1.3.6.1.4.1.13858.7.4.11 | ScalarvpwrBDTAutoAdminState | read-write | current | Enable /Disable Battery Discharge Test data collection upon detecting AC Fail condition. |
| 1.3.6.1.4.1.13858.7.4.12 | TablevpwrBDTHistTable | not-accessible | current | This table provides results of past BDT test. |
| 1.3.6.1.4.1.13858.7.4.12.1 | RowvpwrBDTHistEntry | not-accessible | current | An entry containing information applicable to a particular BDT History. |
| 1.3.6.1.4.1.13858.7.4.12.1.1 | ColumnvpwrBDTHistIndex | read-only | current | BDT History index. |
| 1.3.6.1.4.1.13858.7.4.12.1.2 | ColumnvpwrBDTHistDateTime | read-only | current | BDT run date as yr-mm-dd hh:mm |
| 1.3.6.1.4.1.13858.7.4.12.1.3 | ColumnvpwrBDTHistDuration | read-only | current | BDT duration at the time this test was run. |
| 1.3.6.1.4.1.13858.7.4.12.1.4 | ColumnvpwrBDTHistAlarmVoltage | read-write | current | BDT Alarm Voltage setpoint when this test was run. |
| 1.3.6.1.4.1.13858.7.4.12.1.5 | ColumnvpwrBDTHistAbortVoltage | read-only | current | BDT Abort Voltage setpoint when this test was run. |
| 1.3.6.1.4.1.13858.7.4.12.1.6 | ColumnvpwrBDTHistStartMethod | read-only | current | How Battery Discharge Test was started. |
| 1.3.6.1.4.1.13858.7.4.12.1.7 | ColumnvpwrBDTHistResult | read-only | current | Results of BDT. |
| 1.3.6.1.4.1.13858.7.4.12.1.8 | ColumnvpwrBDTHistActualTime | read-only | current | Actual BDT runtime in minutes. |
| 1.3.6.1.4.1.13858.7.4.12.1.9 | ColumnvpwrBDTHistStartVoltage | read-only | current | Plant Voltage at the time the BDT was started. |
| 1.3.6.1.4.1.13858.7.4.12.1.10 | ColumnvpwrBDTHistEndVoltage | read-only | current | Plant Voltage at the time the BDT was completed. |
| 1.3.6.1.4.1.13858.7.4.13 | TablevpwrBDTSchedTable | not-accessible | current | This table provides the list of the 12 BDTs that can be scheduled. Need to set date(month and day) and time (hh and minutes) when the test should be started. |
| 1.3.6.1.4.1.13858.7.4.13.1 | RowvpwrBDTSchedEntry | not-accessible | current | An entry describing an alarm. |
| 1.3.6.1.4.1.13858.7.4.13.1.1 | ColumnvpwrBDTSchedIndex | read-only | current | BDT Sched index. |
| 1.3.6.1.4.1.13858.7.4.13.1.2 | ColumnvpwrBDTSchedDay | read-write | current | 1 to 28,29,30 or 31 depending upon the month |
| 1.3.6.1.4.1.13858.7.4.13.1.3 | ColumnvpwrBDTSchedMonth | read-write | current | range 1 to 12 |
| 1.3.6.1.4.1.13858.7.4.13.1.4 | ColumnvpwrBDTSchedHour | read-write | current | range 0 to 23 |
| 1.3.6.1.4.1.13858.7.4.13.1.5 | ColumnvpwrBDTSchedMinute | read-write | current | range 0 to 59 |
| 1.3.6.1.4.1.13858.8 | NodevpwrDcPowerAlarmGroup | |||
| 1.3.6.1.4.1.13858.8.1 | ScalarvpwrAlarmsPresent | read-only | current | The present number of active alarm conditions. |
| 1.3.6.1.4.1.13858.8.2 | TablevpwrAlarmTable | not-accessible | current | A list of alarm table entries. The table contains zero, one, or multiple rows at any time depending upon the number of alarm conditions in effect. The table is… |
| 1.3.6.1.4.1.13858.8.2.1 | RowvpwrAlarmEntry | not-accessible | current | An entry containing information applicable to a particular alarm. |
| 1.3.6.1.4.1.13858.8.2.1.1 | ColumnvpwrAlarmIndex | read-only | current | Identifies the alarm associated with the module. It is unique on per module type basis. For example, multiple rectifiers can have the same alarm and therefore … |
| 1.3.6.1.4.1.13858.8.2.1.2 | ColumnvpwrAlarmDescr | read-only | current | A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con… |
| 1.3.6.1.4.1.13858.8.2.1.3 | ColumnvpwrAlarmTime | read-only | current | The value of sysUpTime when the alarm condition was detected. |
| 1.3.6.1.4.1.13858.8.3 | TablesysAlarmConfigTable | not-accessible | current | This table describes system alarm configuration and current status. |
| 1.3.6.1.4.1.13858.8.3.1 | RowsysAlarmConfigEntry | not-accessible | current | An entry containing information applicable to a particular system alarm. |
| 1.3.6.1.4.1.13858.8.3.1.1 | ColumnsysAlarmIndex | read-only | current | Index into system alarm table |
| 1.3.6.1.4.1.13858.8.3.1.2 | ColumnsysAlarmDefaultName | read-only | current | Default alarm name. |
| 1.3.6.1.4.1.13858.8.3.1.3 | ColumnsysAlarmCustomName | read-write | current | A custom alarm name. |
| 1.3.6.1.4.1.13858.8.3.1.4 | ColumnsysAlarmSeverity | read-write | current | Alarm Severity as denoted by Major and Minor Alarm Mask |
| 1.3.6.1.4.1.13858.8.3.1.5 | ColumnsysAlarmToRelayMapping | read-write | current | No additional mapping = 0 Map to Relay A = 1 Map to Relay B = 2 Map to Relay C = 4 Map to Relay D = 8 Map to Relay E = 16 Map to Relay F = 32 Map to Relay A an… |
| 1.3.6.1.4.1.13858.8.3.1.6 | ColumnsysAlarmOperStatus | read-only | current | Indicates current alarm status |
| 1.3.6.1.4.1.13858.8.4 | ScalarsysAlarmComFailState | read-write | current | Enable/Disable generation of comm fail alarm. |
| 1.3.6.1.4.1.13858.8.5 | ScalarsysAlarmIShareState | read-write | current | Enable/Disable generation of current share alarm. |
| 1.3.6.1.4.1.13858.8.6 | ScalarsysAlarmRedundancyState | read-write | current | Enable/Disable generation of redundancy alarm. |
| 1.3.6.1.4.1.13858.8.7 | ScalarsysAlarmComFailToACFailState | read-write | current | Enable/Disable generation of ACF upon Com Fail |
| 1.3.6.1.4.1.13858.9 | NodevpwrDcPowerSnmpConfig | |||
| 1.3.6.1.4.1.13858.9.1 | TablevpwrTrapTable | not-accessible | current | A list of possible trap destinations depending upon the criticality of the trap. |
| 1.3.6.1.4.1.13858.9.1.1 | RowvpwrTrapEntry | not-accessible | current | An entry containing information applicable to a particular trap destination. |
| 1.3.6.1.4.1.13858.9.1.1.1 | ColumnvpwrTrapIpIndex | read-only | current | Trap Entry Index |
| 1.3.6.1.4.1.13858.9.1.1.2 | ColumnvpwrTrapIpAddress | read-write | current | Trap destination IP Address |
| 1.3.6.1.4.1.13858.9.1.1.3 | ColumnvpwrTrapCriticality | read-write | current | Criticality of traps sent to this IP Address |
| 1.3.6.1.4.1.13858.9.2 | ScalarvpwrReadCommunityString | read-write | current | This allows setting password to be able to do Get operations |
| 1.3.6.1.4.1.13858.9.3 | ScalarvpwrWriteCommunityString | read-write | current | This allows setting password to be able to do Get and Set operations. The read-access is not allowed in the actual implementation. |
| 1.3.6.1.4.1.13858.9.4 | ScalarvpwrTrapCommunityString | read-write | current | This allows setting community string required for the trap to be accepted at the destination. |
| 1.3.6.1.4.1.13858.9.5 | ScalarvpwrTrapVersion | read-write | current | This allows setting the version of trap message sent from the system |
| 1.3.6.1.4.1.13858.10 | NodevpwrDcPowerTraps | |||
| 1.3.6.1.4.1.13858.10.1 | NotificationvpwrTrapPowerMajorAlarm | current | Major Alarm | |
| 1.3.6.1.4.1.13858.10.2 | NotificationvpwrTrapPowerMinorAlarm | current | Minor Alarm | |
| 1.3.6.1.4.1.13858.10.3 | NotificationvpwrTrapACFAlarm | current | AC Fail Alarm | |
| 1.3.6.1.4.1.13858.10.4 | NotificationvpwrTrapHVAlarm | current | High Voltage Warning Alarm | |
| 1.3.6.1.4.1.13858.10.5 | NotificationvpwrTrapHVSDAlarm | current | High Voltage Shutdown Alarm | |
| 1.3.6.1.4.1.13858.10.6 | NotificationvpwrTrapBDAlarm | current | Battery on Discharge Alarm | |
| 1.3.6.1.4.1.13858.10.7 | NotificationvpwrTrapLVDWarningAlarm | current | LVD Warning Alarm | |
| 1.3.6.1.4.1.13858.10.8 | NotificationvpwrTrapLVDOpenAlarm | current | LVD Open Alarm | |
| 1.3.6.1.4.1.13858.10.9 | NotificationvpwrTrapDistAlarm | current | Distribution Open Alarm | |
| 1.3.6.1.4.1.13858.10.10 | NotificationvpwrTrapAuxAlarm | current | Auxiliary System Alarm | |
| 1.3.6.1.4.1.13858.10.11 | NotificationvpwrTrapSystemRedundancyAlarm | current | System Redundant Capacity Alarm | |
| 1.3.6.1.4.1.13858.10.12 | NotificationvpwrTrapIShareAlarm | current | Rectifier Current Share Alarm | |
| 1.3.6.1.4.1.13858.10.13 | NotificationvpwrTrapModuleFailAlarm | current | Single Rectifier Fail Alarm | |
| 1.3.6.1.4.1.13858.10.14 | NotificationvpwrTrapMultipleModuleFailAlarm | current | Multiple Rectifier Fail Alarm | |
| 1.3.6.1.4.1.13858.10.15 | NotificationvpwrTrapModuleCommAlarm | current | Power Module Communication Alarm | |
| 1.3.6.1.4.1.13858.10.16 | NotificationvpwrTrapSystemOverTemperatureAlarm | current | System Over Temperature Alarm | |
| 1.3.6.1.4.1.13858.10.17 | NotificationvpwrTrapSystemOK | current | SYSTEM OK - No Active Alarms | |
| 1.3.6.1.4.1.13858.10.18 | NotificationvpwrTrapModuleInserted | current | A new module has been inserted into the system | |
| 1.3.6.1.4.1.13858.10.19 | NotificationvpwrTrapModuleRemoved | current | A module has been removed from the system | |
| 1.3.6.1.4.1.13858.10.20 | NotificationvpwrTrapThermalCompActive | current | Thermal compensation has become active | |
| 1.3.6.1.4.1.13858.10.21 | NotificationvpwrTrapThermalCompInactive | current | Thermal compensation has been de-activated | |
| 1.3.6.1.4.1.13858.10.22 | NotificationvpwrTrapInternalTempAlarmSet | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! Internal Temperature upper threshold exceeded | |
| 1.3.6.1.4.1.13858.10.23 | NotificationvpwrTrapInternalTempAlarmCleared | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! Internal Temperature within limits | |
| 1.3.6.1.4.1.13858.10.24 | NotificationvpwrTrapBatteryTempAlarmSet | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! At least one Battery Temperature exceeded upper threshold | |
| 1.3.6.1.4.1.13858.10.25 | NotificationvpwrTrapBatteryTempAlarmCleared | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! All Battery Temperatures within limits | |
| 1.3.6.1.4.1.13858.10.26 | NotificationvpwrTrapLoginFail | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! Admin login failed due to wrong username/password | |
| 1.3.6.1.4.1.13858.10.27 | NotificationvpwrTrapLoginSuccess | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! Admin login successful | |
| 1.3.6.1.4.1.13858.10.28 | NotificationvpwrTrapLogout | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! Admin logout | |
| 1.3.6.1.4.1.13858.10.29 | NotificationvpwrTrapAdminPwdChange | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! Config change submitted with invalid access | |
| 1.3.6.1.4.1.13858.10.30 | NotificationvpwrTrapIllegalConfigSubmit | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! Config change submitted with invalid access | |
| 1.3.6.1.4.1.13858.10.31 | NotificationvpwrTrapCfgChange | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! Config change submitted | |
| 1.3.6.1.4.1.13858.10.32 | NotificationvpwrTrapClearEventHistory | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! Clear Event history buffer clear request | |
| 1.3.6.1.4.1.13858.10.33 | NotificationvpwrTrapSwDownloadNoReboot | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! System software upgrade without reboot | |
| 1.3.6.1.4.1.13858.10.34 | NotificationvpwrTrapSwDownloadAndReboot | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! System reboot due to software upgrade | |
| 1.3.6.1.4.1.13858.10.35 | NotificationvpwrTrapSystemClockChange | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! System clock updated | |
| 1.3.6.1.4.1.13858.10.36 | NotificationvpwrTrapModuleAlarm | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! Module Alarm | |
| 1.3.6.1.4.1.13858.10.37 | NotificationvpwrTrapOIDChange | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! Change in OID | |
| 1.3.6.1.4.1.13858.10.38 | NotificationvpwrTrapThermalRunaway | current | Thermal Runaway Alarm | |
| 1.3.6.1.4.1.13858.10.39 | NotificationvpwrTrapBatteryDischargeTestAlarm | current | System Voltage dropped to BDT Alarm Setpoint | |
| 1.3.6.1.4.1.13858.10.40 | NotificationvpwrTrapBayUnnameAlarm | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! Unassigned Bay Fail Alarm | |
| 1.3.6.1.4.1.13858.10.41 | NotificationvpwrTrapPMComFailAlarm | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! PM Communication Fail Alarm | |
| 1.3.6.1.4.1.13858.10.42 | NotificationvpwrTrapFuseOverloadAlarm | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! Fuse Overload Alarm | |
| 1.3.6.1.4.1.13858.10.43 | NotificationvpwrTrapPeripheralAlarm | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! Peripheral Alarm. | |
| 1.3.6.1.4.1.13858.10.44 | NotificationvpwrTrapThermalProbeAlarm | current | Thermal Probe Missing Alarm | |
| 1.3.6.1.4.1.13858.10.45 | NotificationvpwrTrapBayCommAlarm | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! Bay Communication Alarm | |
| 1.3.6.1.4.1.13858.10.46 | NotificationvpwrTrapDistributionCommAlarm | current | Distribution Communication Alarm | |
| 1.3.6.1.4.1.13858.10.47 | NotificationvpwrTrapConverterAlarm | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! Single Converter Fail Alarm | |
| 1.3.6.1.4.1.13858.10.48 | NotificationvpwrTrapMultipleConvFailAlarm | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! Multiple Converter Fail Alarm | |
| 1.3.6.1.4.1.13858.10.49 | NotificationvpwrTrapDGUAlarm | current | !!! For Future Use. !!! DGU Alarm | |
| 1.3.6.1.4.1.13858.10.50 | NotificationvpwrTrapConfigErrorAlarm | current | Configuration Error | |
| 1.3.6.1.4.1.13858.10.51 | NotificationvpwrTrapDisplayFirmwareMismatchAlarm | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! Display Firmware Mismatch | |
| 1.3.6.1.4.1.13858.10.52 | NotificationvpwrTrapConverterInputFailAlarm | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! Converter Input Fail Alarm | |
| 1.3.6.1.4.1.13858.10.53 | NotificationvpwrTrapBatteryRechgIlimitFailAlarm | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! Battery Recharge Current Limit Fail | |
| 1.3.6.1.4.1.13858.10.54 | NotificationvpwrTrapSystemAlive | current | Periodic Keepalive trap | |
| 1.3.6.1.4.1.13858.10.55 | NotificationvpwrTrapSystemAuxAlmSource | current | Source of Auxilary Alarms. Indicates the module and the aux within the module causing alarms | |
| 1.3.6.1.4.1.13858.10.56 | NotificationvpwrTrapSystemDistAlmSource | current | Source of Distribution Alarms. Indicates the module and the dist within the module causing alarms | |
| 1.3.6.1.4.1.13858.10.58 | NotificationvpwrTrapSystemBatCapacityAlarm | current | Plant Load exceeds Plant Battery Current Capacity. Useful for batteries that limit maximum discharge current It will not be sent out for VRLA batteries, eg | |
| 1.3.6.1.4.1.13858.10.61 | NotificationvpwrTrapSystemACFClearAlarm | current | AC Fail (ACF) Conditioned Cleared Alarm. Duration is in minutes. | |
| 1.3.6.1.4.1.13858.10.62 | NotificationvpwrTrapSystemACFSetAlarm | current | ACF Conditioned detected Alarm. The duration would always be zero. Msg String: ACF Alarm Set | |
| 1.3.6.1.4.1.13858.10.64 | NotificationvpwrTrapSystemBatCapacityLeft | current | !!! For Future Use. !!! Battery Useful Capacity Remaining | |
| 1.3.6.1.4.1.13858.10.65 | NotificationvpwrTrapRectifierUVAlarm | current | Rectifier Under Voltage Alarm | |
| 1.3.6.1.4.1.13858.10.66 | NotificationvpwrTrapMultRectifierUVAlarm | current | !!! For Future Use. !!! Multiple Rectifier Under Voltage Alarm | |
| 1.3.6.1.4.1.13858.10.67 | NotificationvpwrTrapRingerAlarm | current | Ringer Alarm | |
| 1.3.6.1.4.1.13858.10.68 | NotificationvpwrTrapMultRingerAlarm | current | !!! For Future Use. !!! Multiple Ringer Alarm | |
| 1.3.6.1.4.1.13858.10.69 | NotificationvpwrTrapI2CCANAlarm | current | !!! For Future Use. !!! Unmapped I2C/CAN Address Alarm One of your I2C or CAN devices has a duplicate or invalid address and can not be mapped. Please recheck … | |
| 1.3.6.1.4.1.13858.10.70 | NotificationvpwrTrapRectifierIlimitAlarm | current | Rectifier Current Limit Alarm | |
| 1.3.6.1.4.1.13858.10.71 | NotificationvpwrTrapMultRectifierIlimitAlarm | current | !!! For Future Use. !!! Multiple Rectifier Current Limit Alarm | |
| 1.3.6.1.4.1.13858.10.72 | NotificationvpwrTrapRingerCommAlarm | current | Ringer Communication Alarm | |
| 1.3.6.1.4.1.13858.10.99 | NotificationvpwrTrapUnassignedAlarm | current | !!! NOT VALID FOR BC2000 CONTROLLER !!! Unassigned Alarm(Trap) - Check Web Page | |
| 1.3.6.1.4.1.13858.11 | NodevpwrDcPowerTrapVars | |||
| 1.3.6.1.4.1.13858.11.1 | ScalarvpwrTrapsMsgString | read-only | current | Place holder for trap notification message string |
| 1.3.6.1.4.1.13858.11.2 | ScalarvpwrTrapUserIpAddress | not-accessible | current | Place holder for IP address of the user accessing the system |
| 1.3.6.1.4.1.13858.11.3 | ScalarvpwrTrapAcfDuration | read-only | current | Place holder for duration. |
| 1.3.6.1.4.1.13858.11.4 | ScalarvpwrAlarmingSubModuleBitMap | read-only | current | indices of alarming sources are encoded as a bit-map e.g., source 1 and source 2 will be encoded as hex 3. source 1 and 3 will be encoded as hex 5. |
| 1.3.6.1.4.1.13858.11.5 | ScalarvpwrBatteryCurrentCapacity | read-only | current | Place holder for total battery capacity |
| 1.3.6.1.4.1.13858.11.6 | ScalarvpwrAlarmingModuleIndex | read-only | current | index of alarming module. |
| 1.3.6.1.4.1.13858.11.7 | ScalarvpwrAlarmingModuleOID | read-only | current | It indicates the type of the module by specifiying its OID |
| 1.3.6.1.4.1.13858.11.8 | ScalarvpwrAlarmingModuleBitMap | not-accessible | current | indices of alarming sources are encoded as a bit-map e.g., source 1 and source 2 will be encoded as hex 3. source 1 and 3 will be encoded as hex 5. |
| 1.3.6.1.4.1.13858.11.9 | ScalarvpwrBatteryRemainingTime | read-only | current | Place holder for remaining battery time at the current load |
| 1.3.6.1.4.1.13858.12 | NodevpwrDcPowerRinger | |||
| 1.3.6.1.4.1.13858.12.1 | NodevpwrRingerConfigGroup | |||
| 1.3.6.1.4.1.13858.12.1.1 | ScalarvpwrRingerIndex | read-write | current | This parameter allows selecting ringer A or Ringer B as the active ringer. |
| 1.3.6.1.4.1.13858.12.1.2 | ScalarvpwrRingerParameterAdminState | read-write | current | This parameter allows selecting ringer A or Ringer B as the active ringer. |
| 1.3.6.1.4.1.13858.12.1.3 | ScalarvpwrRingerParameterAcVoltage | read-write | current | This parameter sets the output AC voltage of the ringer. |
| 1.3.6.1.4.1.13858.12.1.4 | ScalarvpwrRingerParameterDcVoltage | read-write | current | This parameter sets the DC offset value of the ringer. |
| 1.3.6.1.4.1.13858.12.1.5 | ScalarvpwrRingerParameterFrequency | read-write | current | This parameter sets the ringer AC frequency. |
| 1.3.6.1.4.1.13858.12.1.6 | ScalarvpwrRingerNumberPresent | read-only | current | The present number of ringer modules. |
| 1.3.6.1.4.1.13858.12.2 | NodevpwrRingerAlarmGroup | |||
| 1.3.6.1.4.1.13858.12.2.1 | IdentityvpwrRingerAlarmAFailed | current | Ringer A Failed | |
| 1.3.6.1.4.1.13858.12.2.2 | IdentityvpwrRingerAlarmAOverTemp | current | Ringer A Heatsink Over-Temperature | |
| 1.3.6.1.4.1.13858.12.2.3 | IdentityvpwrRingerAlarmAOverCurrent | current | Ringer A Over-Current protection | |
| 1.3.6.1.4.1.13858.12.2.4 | IdentityvpwrRingerAlarmBFailed | current | Ringer B Failed | |
| 1.3.6.1.4.1.13858.12.2.5 | IdentityvpwrRingerAlarmBOverTemp | current | Ringer B Heatsink Over-Temperature | |
| 1.3.6.1.4.1.13858.12.2.6 | IdentityvpwrRingerAlarmBOverCurrent | current | Ringer B Over-Current protection | |
| 1.3.6.1.4.1.13858.12.3 | NodevpwrRingerTestGroup | |||
| 1.3.6.1.4.1.13858.13 | NodevpwrDcPowerDcDcConverter | |||
| 1.3.6.1.4.1.13858.13.1 | NodevpwrDcDcConverterConfigGroup | |||
| 1.3.6.1.4.1.13858.13.2 | NodevpwrDcDcConverterAlarmGroup | |||
| 1.3.6.1.4.1.13858.13.3 | NodevpwrDcDcConverterTestGroup | |||
| 1.3.6.1.4.1.13858.14 | NodevpwrDcPowerDcAcInverter | |||
| 1.3.6.1.4.1.13858.14.1 | NodevpwrDcAcInverterConfigGroup | |||
| 1.3.6.1.4.1.13858.14.2 | NodevpwrDcAcInverterAlarmGroup | |||
| 1.3.6.1.4.1.13858.14.3 | NodevpwrDcAcInverterTestGroup | |||
| 1.3.6.1.4.1.13858.15 | NodevpwrDcPowerAcLineModule | |||
| 1.3.6.1.4.1.13858.15.1 | NodevpwrAcLineModuleConfigGroup | |||
| 1.3.6.1.4.1.13858.15.2 | NodevpwrAcLineModuleAlarmGroup | |||
| 1.3.6.1.4.1.13858.15.3 | NodevpwrAcLineModuleTestGroup | |||
| 1.3.6.1.4.1.13858.16 | NodevpwrDcPowerIoModule | |||
| 1.3.6.1.4.1.13858.16.1 | NodevpwrIoModuleConfigGroup | |||
| 1.3.6.1.4.1.13858.16.2 | NodevpwrIoModuleAlarmGroup | |||
| 1.3.6.1.4.1.13858.16.3 | NodevpwrIoModuleTestGroup | |||
| 1.3.6.1.4.1.13858.17 | NodevpwrDcPowerPMModule | |||
| 1.3.6.1.4.1.13858.17.1 | TablevpwrPMCnfgTable | not-accessible | current | This table shows the current configuration of the TRIO/PM86000/Controller inputs. |
| 1.3.6.1.4.1.13858.17.1.1 | RowvpwrPMCnfgEntry | not-accessible | current | An entry containing current configuration of the TRIO/PM86000/Controller inputs. |
| 1.3.6.1.4.1.13858.17.1.1.1 | ColumnvpwrPMIndex | read-only | current | This parameter describes which TRIO/PM86000 device is being accessed. |
| 1.3.6.1.4.1.13858.17.1.1.2 | ColumnvpwrPMDescription | read-only | current | This parameter describes the configuration of the TRIO/PM86000 device. |
| 1.3.6.1.4.1.13858.17.1.1.3 | ColumnvpwrPMCnfg1 | read-write | current | This parameter gets the current configuration of the TRIO/PM86000, input 1 |
| 1.3.6.1.4.1.13858.17.1.1.4 | ColumnvpwrPMCnfg2 | read-write | current | This parameter gets the current configuration of the TRIO/PM86000, input 2 |
| 1.3.6.1.4.1.13858.17.1.1.5 | ColumnvpwrPMCnfg3 | read-write | current | This parameter gets the current configuration of the TRIO/PM86000, input 3 |
| 1.3.6.1.4.1.13858.17.1.1.6 | ColumnvpwrPMCnfg4 | read-write | current | This parameter gets the current configuration of the TRIO/PM86000, input 4 |
| 1.3.6.1.4.1.13858.17.1.1.7 | ColumnvpwrPMCnfg5 | read-write | current | This parameter gets the current configuration of the TRIO/PM86000, input 5 |
| 1.3.6.1.4.1.13858.17.1.1.8 | ColumnvpwrPMCnfg6 | read-write | current | This parameter gets the current configuration of the TRIO/PM86000, input 6 |
| 1.3.6.1.4.1.13858.17.1.1.9 | ColumnvpwrPMCnfg7 | read-write | current | This parameter gets the current configuration of the TRIO (PM86000), input 7 |
| 1.3.6.1.4.1.13858.17.1.1.10 | ColumnvpwrPMCnfg8 | read-write | current | This parameter gets the current configuration of the TRIO/PM86000, input 8 |
| 1.3.6.1.4.1.13858.17.2 | TablevpwrPMInputStatusTable | not-accessible | current | This table shows the current values of the TRIO/PM86000/Controller inputs. |
| 1.3.6.1.4.1.13858.17.2.1 | RowvpwrPMInputStatusEntry | not-accessible | current | An entry containing current state of the TRIO/PM86000/Controller inputs. |
| 1.3.6.1.4.1.13858.17.2.1.1 | ColumnvpwrPMIndex1 | read-only | current | This parameter describes which TRIO/PM86000 device is being accessed. |
| 1.3.6.1.4.1.13858.17.2.1.2 | ColumnvpwrPMDescription1 | read-only | current | This parameter describes the input values of the TRIO/PM86000 device. |
| 1.3.6.1.4.1.13858.17.2.1.3 | ColumnvpwrPMInput1State | read-only | current | This parameter gets the current state of input 1 |
| 1.3.6.1.4.1.13858.17.2.1.4 | ColumnvpwrPMInput2State | read-only | current | This parameter gets the current state of input 2 |
| 1.3.6.1.4.1.13858.17.2.1.5 | ColumnvpwrPMInput3State | read-only | current | This parameter gets the current state of input 3 |
| 1.3.6.1.4.1.13858.17.2.1.6 | ColumnvpwrPMInput4State | read-only | current | This parameter gets the current state of input 4 |
| 1.3.6.1.4.1.13858.17.2.1.7 | ColumnvpwrPMInput5State | read-only | current | This parameter gets the current state of input 5 |
| 1.3.6.1.4.1.13858.17.2.1.8 | ColumnvpwrPMInput6State | read-only | current | This parameter gets the current state of input 6 |
| 1.3.6.1.4.1.13858.17.2.1.9 | ColumnvpwrPMInput7State | read-only | current | This parameter gets the current state of input 7 |
| 1.3.6.1.4.1.13858.17.2.1.10 | ColumnvpwrPMInput8State | read-only | current | This parameter gets the current state of input 8 |
| 1.3.6.1.4.1.13858.17.3 | TablevpwrPMRelayCtrlTable | not-accessible | current | This table describes/controls system relays. |
| 1.3.6.1.4.1.13858.17.3.1 | RowvpwrPMRelayCtrlEntry | not-accessible | current | An entry containing current state of the relays. |
| 1.3.6.1.4.1.13858.17.3.1.1 | ColumnvpwrPMIndex2 | read-only | current | This parameter describes the TRIO/PM device |
| 1.3.6.1.4.1.13858.17.3.1.2 | ColumnvpwrPMDescription2 | read-only | current | This parameter describes the TRIO/PM device |
| 1.3.6.1.4.1.13858.17.3.1.3 | ColumnvpwrPMRelay1State | read-write | current | This parameter sets the current state of relay 1 |
| 1.3.6.1.4.1.13858.17.3.1.4 | ColumnvpwrPMRelay2State | read-write | current | This parameter sets the current state of relay 2 |
| 1.3.6.1.4.1.13858.17.3.1.5 | ColumnvpwrPMRelay3State | read-write | current | This parameter sets the current state of relay 3 |
| 1.3.6.1.4.1.13858.17.3.1.6 | ColumnvpwrPMRelay4State | read-write | current | This parameter sets the current state of relay 4 |
| 1.3.6.1.4.1.13858.17.3.1.7 | ColumnvpwrPMRelay5State | read-write | current | This parameter sets the current state of relay 5 |
| 1.3.6.1.4.1.13858.17.3.1.8 | ColumnvpwrPMRelay6State | read-write | current | This parameter sets the current state of relay 6 |
| 1.3.6.1.4.1.13858.17.4 | NodevpwrPMModuleAlarmGroup | |||
| 1.3.6.1.4.1.13858.17.5 | NodevpwrPMModuleTestGroup | |||
| 1.3.6.1.4.1.13858.18 | NodevpwrDcPowerDistModule | |||
| 1.3.6.1.4.1.13858.19 | NodevpwrDcPowerBattery | |||
| 1.3.6.1.4.1.13858.20 | NodevpwrDcPowerController | |||
| 1.3.6.1.4.1.13858.499 | NodevpwrDcPowerUnkModule | |||
| 1.3.6.1.4.1.13858.500 | NodethirdPartyProduct |
Type Definitions
| Name | Syntax | Status | Description |
|---|---|---|---|
| BDTResultTC | INTEGER { bdtResultCleared(0), bdtResultPassed(1), bdtResultFailed(2), bdtResultStopped(3), bdtResultAborted(4), bdtResultInProgress(5) } | current | The defines how was BDT started. |
| BDTStartSourceTC | INTEGER { bdtInactive(0), bdtManualStart(1), bdtSched01Start1(2), bdtSched02Start2(3), bdtSched03Start3(4), bdtSched04Start4(5), bdtSched05Start5(6), bdtSched06Start6(7), bdtSched07Start7(8), bdtSched08Start8(9), bdtSched09Start9(10), bdtSched10Start10(11), bdtSched11Start11(12), bdtSched12Start12(13), bdtACFailStart(14) } | current | The defines how was BDT started. |
| GenericEnableDisableTC | INTEGER { disabled(0), enabled(1) } | current | The defines how was BDT started. |
| NonNegativeInteger | Integer32 (0..2147483647) | current | This data type is a non-negative value. |
| PositiveInteger | Integer32 (1..2147483647) | current | This data type is a non-zero and non-negative value. |
| SysInputValue | INTEGER { disabled(-127), removed(-126), shorted(-125), auxAlarm(-124), auxNormal(-123), distAlarm(-122), distNormal(-121), undefined(255) } | current | These are the results of the system input value definitions. |
| VpwrPMCnfgValue | INTEGER { disabled(0), tProbe(1), auxNO(2), auxNC(3), distNO(4), distNC(5), undefined(255) } | current | These are the results of the system input value definitions. |