ELTEK-BC2000-DC-POWER-MIB

391 objects
SNMP access to Eltek DC Power systems through the BC2000 controller.
Imported Objects
RFC1155-SMIGauge
RFC1213-MIB-- sysUpTime --
SNMPv2-CONF-- MODULE-COMPLIANCE -- OBJECT-GROUP --
SNMPv2-SMICounter32 enterprises Gauge32 Integer32 IpAddress -- MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-IDENTITY OBJECT-TYPE
SNMPv2-TCAutonomousType DisplayString TestAndIncr TEXTUAL-CONVENTION TimeInterval -- TimeStamp --
OIDNameAccessStatusDescription
1.3.6.1.4.1.13858IdentityeltekSNMP access to Eltek DC Power systems through the BC2000 controller.
1.3.6.1.4.1.13858.2NodevpwrDcPowerSystem
1.3.6.1.4.1.13858.2.1NodevpwrSystemIdentGroup
1.3.6.1.4.1.13858.2.1.1ScalarvpwrIdentManufacturerread-onlycurrentThe name of the DC Power manufacturer.
1.3.6.1.4.1.13858.2.1.2ScalarvpwrIdentModelread-onlycurrentThe DC Power Model designation.
1.3.6.1.4.1.13858.2.1.3ScalarvpwrIdentControllerVersionread-onlycurrentThe hardware/firmware version(s). This variable may or may not have the same value as vpwrIdentAgentSoftwareVersion.
1.3.6.1.4.1.13858.2.1.4ScalarvpwrIdentAgentSoftwareVersionread-onlycurrentThe SNMP agent software version. This variable may or may not have the same value as vpwrIdentControllerVersion.
1.3.6.1.4.1.13858.2.1.5ScalarvpwrIdentNameread-writecurrentA string identifying the system. This object should be set by the administrator.
1.3.6.1.4.1.13858.2.1.6TablevpwrSystemIdentTablenot-accessiblecurrentThis table describes shelves and modules that make up the sysetm.
1.3.6.1.4.1.13858.2.1.6.1RowvpwrSystemIdentEntrynot-accessiblecurrentAn entry containing information applicable to a particular alarm.
1.3.6.1.4.1.13858.2.1.6.1.1ColumnvpwrShelfIndexread-onlycurrentIdentifies shelf number that this module belongs to. The possible values are 1 through 16 limited by vpwrSystemShelfCapacity.
1.3.6.1.4.1.13858.2.1.6.1.2ColumnvpwrModuleIndexread-onlycurrentThis object identifies the module by its position in the shelf. Module numbering is left to right starting with module 1. So, the module in the first slot has …
1.3.6.1.4.1.13858.2.1.6.1.3ColumnvpwrModuleOIDread-onlycurrentIt indicates the type of the module by specifiying its OID
1.3.6.1.4.1.13858.2.1.6.1.4ColumnvpwrModuleCurrentread-onlycurrentThe meaning of this object depends upon the module type which is indicated by vpwrModuleOID as follows - Current for Rectifier module in centiamps. - Not Appli…
1.3.6.1.4.1.13858.2.1.6.1.5ColumnvpwrModuleOperStatusread-onlycurrentThis object indicates current over all status of the module.
1.3.6.1.4.1.13858.2.1.6.1.6ColumnvpwrModuleCapacityread-onlycurrentThe meaning of this object depends upon the module type which is indicated by vpwrModuleOID as follows - Capacity for Rectifier module. - Not Applicable for LV…
1.3.6.1.4.1.13858.2.2NodevpwrSystemConfigGroup
1.3.6.1.4.1.13858.2.2.1ScalarvpwrSystemTempCompensationread-writecurrentThis parameter enables/disables temperature compensation.
1.3.6.1.4.1.13858.2.2.2ScalarvpwrSystemTempCompStartTemperatureread-writecurrentThe temperature at which temperature compensation becomes active.
1.3.6.1.4.1.13858.2.2.3ScalarvpwrSystemTempCompStopVoltageread-writecurrentWhen temperature compensation is active, vpwrSystemTempCompStopVoltage is the limit to which float voltage will be reduced. For example, to set this voltage to…
1.3.6.1.4.1.13858.2.2.4ScalarvpwrSystemTempCompensationSloperead-writecurrentThe rate at which float voltage is changed, within the specified limits, when temperature compensation is active.
1.3.6.1.4.1.13858.2.2.5ScalarvpwrSystemThermalSenseTyperead-writecurrentThis parameter selects the temperature sensing point for temperature compensation (in)activation.
1.3.6.1.4.1.13858.2.2.6ScalarvpwrSystemHVAlarmSetpointread-writecurrentSystem High voltage alarm voltage setting.
1.3.6.1.4.1.13858.2.2.7ScalarvpwrSystemBDAlarmSetpointread-writecurrentSystem Battery Discharge voltage setting.
1.3.6.1.4.1.13858.2.2.8ScalarvpwrSystemInternalTempLThresholdread-writecurrentTemperature value at which temperature compensation inactive (clear) trap would be sent if temperature compensation was active when this value is reached.
1.3.6.1.4.1.13858.2.2.9ScalarvpwrSystemInternalTempUThresholdread-writecurrentTemperature value at which temperature compensation active (set) trap would be sent.
1.3.6.1.4.1.13858.2.3NodevpwrSystemParameterGroup
1.3.6.1.4.1.13858.2.3.1ScalarvpwrSystemShelfCapacityread-onlycurrentIt describes the maximum number of shelves that can/are controlled by the controller. Each shelf is uniquely numbered in the range from 1 to vpwrShelfCapacity.
1.3.6.1.4.1.13858.2.3.2ScalarvpwrSystemVoltageread-onlycurrentThe current system voltage.
1.3.6.1.4.1.13858.2.3.3ScalarvpwrSystemCurrentread-onlycurrentThe current system current.
1.3.6.1.4.1.13858.2.3.4ScalarvpwrSystemControllerStateread-onlycurrentCurrent System state as shown on the enhanced display.
1.3.6.1.4.1.13858.2.3.5ScalarvpwrSystemInternalTemperatureread-onlycurrentThe current controller internal temperature.
1.3.6.1.4.1.13858.2.3.6ScalarvpwrSystemTempCompensationStateread-onlycurrentActive or Inactive. Applicable only if temperature compensation is enabled. This means that the controller is temperature compensating the float voltage.
1.3.6.1.4.1.13858.2.3.7ScalarvpwrSystemTyperead-onlycurrentThis parameter describes the type of the system being managed. This object is set by Eltek Valere Inc.
1.3.6.1.4.1.13858.2.3.8ScalarvpwrSystemCumulativeUpTimeread-onlycurrentThis parameter describes the cumulative runtime in seconds of the Eltek Valere controller.
1.3.6.1.4.1.13858.2.3.9ScalarvpwrSystemBatteryRemainingTimeread-onlycurrentThis parameter describes the remaining battery capacity based upon installed battery capacity and plant load. This number would change as the SOC parameters of…
1.3.6.1.4.1.13858.2.4NodevpwrSystemPanelIdentGroup
1.3.6.1.4.1.13858.2.4.1TablevpwrPanelStatusTablenot-accessiblecurrentThis table describes shelves and modules that make up the panels.
1.3.6.1.4.1.13858.2.4.1.1RowvpwrPanelStatusnot-accessiblecurrentAn entry containing information applicable to a particular panel making up the system.
1.3.6.1.4.1.13858.2.4.1.1.1ColumnvpwrPanelStatusIndexread-onlycurrentIdentifies panel number that this module belongs to. The possible values are 1 through 8, starting from the top.
1.3.6.1.4.1.13858.2.4.1.1.2ColumnvpwrPanelStatusModuleIndexread-onlycurrentThis object identifies the module within the panel. The orentation of modules within the panel is mappable.
1.3.6.1.4.1.13858.2.4.1.1.3ColumnvpwrPanelStatusModuleOIDread-onlycurrentThe module OID.
1.3.6.1.4.1.13858.2.4.1.1.4ColumnvpwrPanelStatusModuleCurrentread-onlycurrentThe current measured by the device (if applicable). LVD current reported in deciAmps.
1.3.6.1.4.1.13858.2.4.1.1.5ColumnvpwrpanelStatusModuleOperStatusread-onlycurrentThis object indicates current over all status of the module.
1.3.6.1.4.1.13858.2.4.1.1.6ColumnvpwrPanelStatusModuleCapacityread-onlycurrentThe maximum capacity of the module (if applicable).
1.3.6.1.4.1.13858.2.4.2TablevpwrPanelIdentTablenot-accessiblecurrentThis table describes shelves and modules that make up the panels.
1.3.6.1.4.1.13858.2.4.2.1RowvpwrPanelIdentEntrynot-accessiblecurrentAn entry containing information applicable to a particular panel making up the system.
1.3.6.1.4.1.13858.2.4.2.1.1ColumnvpwrPanelIndexread-onlycurrentIdentifies panel number that this module belongs to. The possible values are 1 through 8, starting from the top.
1.3.6.1.4.1.13858.2.4.2.1.2ColumnvpwrPanelModuleIndexread-onlycurrentThis object identifies the module within the panel. The orentation of modules within the panel is mappable.
1.3.6.1.4.1.13858.2.4.2.1.3ColumnvpwrPanelModuleSerNumread-onlycurrentThe module serial number.
1.3.6.1.4.1.13858.2.4.2.1.4ColumnvpwrPanelModuleModelNameread-onlycurrentThe model name of the device.
1.3.6.1.4.1.13858.2.4.2.1.5ColumnvpwrPanelModuleFWVerread-onlycurrentThe module firmware version.
1.3.6.1.4.1.13858.2.4.2.1.6ColumnvpwrPanelModuleTestDateread-onlycurrentThe manufacturing test date.
1.3.6.1.4.1.13858.2.5NodevpwrSystemHistoryGroup
1.3.6.1.4.1.13858.2.5.1TablevpwrSysHistAlarmTablenot-accessiblecurrentThis table provides a list of most recent alarms.
1.3.6.1.4.1.13858.2.5.1.1RowvpwrSysHistAlarmEntrynot-accessiblecurrentAn entry describing an alarm.
1.3.6.1.4.1.13858.2.5.1.1.1ColumnvpwrSysHistAlarmIndexread-onlycurrentAlarm index.
1.3.6.1.4.1.13858.2.5.1.1.2ColumnvpwrSysHistAlarmDescriptionread-onlycurrentAlarm description including time stamp.
1.3.6.1.4.1.13858.2.6NodevpwrSystemAlarmGroup
1.3.6.1.4.1.13858.2.6.1ScalarvpwrSystemAlarmMajorread-onlycurrentIndicates a Major Alarm exists on the system.
1.3.6.1.4.1.13858.2.6.2ScalarvpwrSystemAlarmMinorread-onlycurrentIndicates a Minor Alarm exists on the system.
1.3.6.1.4.1.13858.2.6.3ScalarvpwrSystemACFailAlarmread-onlycurrentOne or more rectifiers have reported AC failure. If system is configured to report rectifier communication failure as AC fail this alarm will report.
1.3.6.1.4.1.13858.2.6.4ScalarvpwrSystemHighVoltageWarningAlarmread-onlycurrentSystem has exceeded High Voltage Warning Setpoint. Check for high voltage on system bus.
1.3.6.1.4.1.13858.2.6.5ScalarvpwrSystemHighVoltageShutdownAlarmread-onlycurrentOne or more rectifiers have shut down due to high voltage present on output. Check bus voltage and reseat rectifiers that have indicated this problem.
1.3.6.1.4.1.13858.2.6.6ScalarvpwrSystemBatteryonDischargeAlarmread-onlycurrentSystem voltage has currently dropped below the alarm setpoint. This may be due to battery testing or AC failure.
1.3.6.1.4.1.13858.2.6.7ScalarvpwrSystemLowVoltageWarningAlarmread-onlycurrentSystem Voltage has dropped below setpoint for Low Voltage Alarm. This may occur during battery testing or AC failure
1.3.6.1.4.1.13858.2.6.8ScalarvpwrSystemLVDOpenAlarmread-onlycurrentOne or more contactors have opened. This occurs normally during system power on. If it occurs during operation this may indicate system is operating below LVD …
1.3.6.1.4.1.13858.2.6.9ScalarvpwrSystemDistributionAlarmread-onlycurrentOne or more distribution alarm inputs are reporting an error condition. Check source of alarm and correct issue.
1.3.6.1.4.1.13858.2.6.10ScalarvpwrSystemAuxiliaryAlarmread-onlycurrentOne or more Auxliary alarm inputs are reporting an error condition. Check source of alarm and correct issue.
1.3.6.1.4.1.13858.2.6.11ScalarvpwrSystemRedundantCapAlarmread-onlycurrentThe system load has exceeded the requirements for redundancy. This may be a temporary system overload condition or caused by a rectifier alarm.
1.3.6.1.4.1.13858.2.6.12ScalarvpwrSystemRectIShareAlarmread-onlycurrentOne or more rectifiers are reporting a mismatch in current. This may be due to mismatched rectifier models or one or more rectifiers not current sharing
1.3.6.1.4.1.13858.2.6.13ScalarvpwrSystemSnglRectAlarmread-onlycurrent
1.3.6.1.4.1.13858.2.6.14ScalarvpwrSystemMultRectAlarmread-onlycurrent
1.3.6.1.4.1.13858.2.6.15ScalarvpwrSystemModlCommAlarmread-onlycurrent
1.3.6.1.4.1.13858.2.6.16ScalarvpwrSystemOverTempAlarmread-onlycurrent
1.3.6.1.4.1.13858.2.6.17ScalarvpwrSystemThermRAAlarmread-onlycurrentThermal Runaway has occurred on system. Check temperature inputs.
1.3.6.1.4.1.13858.2.6.18ScalarvpwrSystemBDTAlarmread-onlycurrentSystem has entered Battery Discharge Test mode
1.3.6.1.4.1.13858.2.6.19ScalarvpwrSystemRectUVAlarmread-onlycurrentRectifier output has dropped 1V below Low Voltage Alarm setpoint
1.3.6.1.4.1.13858.2.6.20ScalarvpwrSystemMultRectUVAlarmread-onlycurrent
1.3.6.1.4.1.13858.2.6.21ScalarvpwrSystemSnglRngrAlarmread-onlycurrent
1.3.6.1.4.1.13858.2.6.22ScalarvpwrSystemMultRngrAlarmread-onlycurrent
1.3.6.1.4.1.13858.2.6.23ScalarvpwrSystemTempProbeAlarmread-onlycurrentTemp probe input missing or failed
1.3.6.1.4.1.13858.2.6.24ScalarvpwrSystemRngrCommAlarmread-onlycurrentRinger Module has stopped communicating with Controller.
1.3.6.1.4.1.13858.2.6.25ScalarvpwrSystemDistPMCommAlarmread-onlycurrentOne or more distribution alarm modules, TRIOs, or PM modules has stopped communicating with Controller.
1.3.6.1.4.1.13858.2.6.26ScalarvpwrSystemRectILimitAlarmread-onlycurrentRectifier has reached current limit setpoint.
1.3.6.1.4.1.13858.2.6.27ScalarvpwrSystemMultRectILimitAlarmread-onlycurrent
1.3.6.1.4.1.13858.2.6.28ScalarvpwrSystemUnmappedI2CCANAlarmread-onlycurrentRecheck all I2C and CAN dip switch settings. One or more devices in conflict.
1.3.6.1.4.1.13858.2.6.29ScalarvpwrSystemConfigErrAlarmread-onlycurrentRecheck all I2C and CAN dip switch settings. One or more devices in conflict.
1.3.6.1.4.1.13858.2.6.30ScalarvpwrSystemDispFWAlarmread-onlycurrent
1.3.6.1.4.1.13858.2.6.31ScalarvpwrSystemUndefinedAlarmread-onlycurrent
1.3.6.1.4.1.13858.3NodevpwrDcPowerRectifier
1.3.6.1.4.1.13858.3.1NodevpwrRectifierConfigGroup
1.3.6.1.4.1.13858.3.1.1ScalarvpwrRectifierFVSetpointread-writecurrentSystem Float Voltage setting
1.3.6.1.4.1.13858.3.1.2ScalarvpwrRectifierHVSDSetpointread-writecurrentSystem High Voltage Shutdown voltage setting
1.3.6.1.4.1.13858.3.1.3ScalarvpwrRectifierCurrentLimitAdminStateread-writecurrentThis parameter allows enabling or rectifier current limit
1.3.6.1.4.1.13858.3.1.4ScalarvpwrRectifierCurrentLimitread-writecurrentRectifier current limit setpoint
1.3.6.1.4.1.13858.3.1.5ScalarvpwrRectifierFallbackAdminStateread-writecurrentEnables Rectifier to use Fallback Voltage when it loses communication with the controller. This applies to all rectifiers.
1.3.6.1.4.1.13858.3.1.6ScalarvpwrRectifierFallbackVoltageread-writecurrentFallback Voltage setpoint to use when rectifier loses communication with the controller. This applies to all rectifiers.
1.3.6.1.4.1.13858.3.2NodevpwrRectifierAlarmGroup
1.3.6.1.4.1.13858.3.2.1IdentityvpwrRectAlarmDCFailcurrent
1.3.6.1.4.1.13858.3.2.2IdentityvpwrRectAlarmBoostFailcurrent
1.3.6.1.4.1.13858.3.2.3IdentityvpwrRectAlarmACFailcurrent
1.3.6.1.4.1.13858.3.2.4IdentityvpwrRectAlarmHVSDcurrent
1.3.6.1.4.1.13858.3.2.5IdentityvpwrRectAlarmFanFailcurrent
1.3.6.1.4.1.13858.3.2.6IdentityvpwrRectAlarmAmbTempcurrent
1.3.6.1.4.1.13858.3.2.7IdentityvpwrRectAlarmIntTempcurrent
1.3.6.1.4.1.13858.3.2.8IdentityvpwrRectAlarmISharecurrent
1.3.6.1.4.1.13858.3.2.9IdentityvpwrRectAlarmUVcurrent
1.3.6.1.4.1.13858.3.2.10IdentityvpwrRectAlarmLowVoltagecurrent
1.3.6.1.4.1.13858.3.2.11IdentityvpwrRectAlarmReservedcurrent
1.3.6.1.4.1.13858.3.2.12IdentityvpwrRectAlarmDCEnablecurrent
1.3.6.1.4.1.13858.3.2.13IdentityvpwrRectAlarmRemoteShutdowncurrent
1.3.6.1.4.1.13858.3.2.14IdentityvpwrRectAlarmModDisableShutdowncurrent
1.3.6.1.4.1.13858.3.2.15IdentityvpwrRectAlarmShortPinShutdowncurrent
1.3.6.1.4.1.13858.3.2.16IdentityvpwrRectAlarmBoostCommcurrent
1.3.6.1.4.1.13858.4NodevpwrDcPowerLvd
1.3.6.1.4.1.13858.4.1NodevpwrLvdConfigGroup
1.3.6.1.4.1.13858.4.1.1ScalarvpwrLvdWarningSetpointread-writecurrentLVD Warning voltage setpoint.
1.3.6.1.4.1.13858.4.1.2ScalarvpwrLvdDisconnectSetpointread-writecurrentLVD disconnect voltage setpoint.
1.3.6.1.4.1.13858.4.1.3ScalarvpwrLvdReconnectSetpointread-writecurrentLVD Reconnect voltage setpoint.
1.3.6.1.4.1.13858.4.1.4ScalarvpwrLvdReconnectDelayTimerread-onlycurrentThe delay time, in seconds, before LVD is reconnected
1.3.6.1.4.1.13858.4.1.7ScalarvpwrLvd2DisconnectSetpointread-writecurrentLVD disconnect voltage setpoint.
1.3.6.1.4.1.13858.4.1.8ScalarvpwrLvd2ReconnectSetpointread-writecurrentLVD Reconnect voltage setpoint.
1.3.6.1.4.1.13858.4.1.9ScalarvpwrLvd2ReconnectDelayTimerread-onlycurrentThe delay time, in seconds, before LVD is reconnected
1.3.6.1.4.1.13858.4.1.11ScalarvpwrLvd3DisconnectSetpointread-writecurrentLVD disconnect voltage setpoint.
1.3.6.1.4.1.13858.4.1.12ScalarvpwrLvd3ReconnectSetpointread-writecurrentLVD Reconnect voltage setpoint.
1.3.6.1.4.1.13858.4.1.13ScalarvpwrLvd3ReconnectDelayTimerread-onlycurrentThe delay time, in seconds, before LVD is reconnected
1.3.6.1.4.1.13858.4.1.15ScalarvpwrLvd4DisconnectSetpointread-writecurrentLVD disconnect voltage setpoint.
1.3.6.1.4.1.13858.4.1.16ScalarvpwrLvd4ReconnectSetpointread-writecurrentLVD Reconnect voltage setpoint.
1.3.6.1.4.1.13858.4.1.17ScalarvpwrLvd4ReconnectDelayTimerread-onlycurrentThe delay time, in seconds, before LVD is reconnected
1.3.6.1.4.1.13858.5ScalarvpwrDCPowerLampTestread-writecurrentLamp Test for modules
1.3.6.1.4.1.13858.6NodevpwrDcPowerModuleIdent
1.3.6.1.4.1.13858.6.1TablevpwrDcPowerModuleIdentTablenot-accessiblecurrentThis table describes power modules that make up the system.
1.3.6.1.4.1.13858.6.1.1RowvpwrDcPowerModuleIdentEntrynot-accessiblecurrentAn entry containing information applicable to a power module.
1.3.6.1.4.1.13858.6.1.1.1ColumnvpwrShelfIndex1read-onlycurrentIdentifies shelf number that this module belongs to. The possible values are 1 through 2, starting from the top.
1.3.6.1.4.1.13858.6.1.1.2ColumnvpwrDCModuleIndexread-onlycurrentThis object identifies the module within the shelf.
1.3.6.1.4.1.13858.6.1.1.3ColumnvpwrModuleSerialNumberread-onlycurrentSerial Number of the module
1.3.6.1.4.1.13858.6.1.1.4ColumnvpwrModuleModelNumberread-onlycurrentModel Number of the module.
1.3.6.1.4.1.13858.6.1.1.5ColumnvpwrModuleFwVersionread-onlycurrentFirmware version of the module.
1.3.6.1.4.1.13858.6.1.1.6ColumnvpwrModuleTestDateread-onlycurrentDate when the module was last tested.
1.3.6.1.4.1.13858.6.1.1.7ColumnvpwrModuleOperHoursread-onlycurrentCumulative Operating Hours.
1.3.6.1.4.1.13858.7NodevpwrDcPowerBatteryGroup
1.3.6.1.4.1.13858.7.1NodevpwrBatteryTempGroup
1.3.6.1.4.1.13858.7.1.1TablevpwrBatteryTempTablenot-accessiblecurrentThis table describes battery temperature probes.
1.3.6.1.4.1.13858.7.1.1.1RowvpwrBatteryTempEntrynot-accessiblecurrentAn entry containing information applicable to a particular temperature probe.
1.3.6.1.4.1.13858.7.1.1.1.1ColumnvpwrBatteryTempIndexread-onlycurrentIndex into temperature table
1.3.6.1.4.1.13858.7.1.1.1.2ColumnvpwrBatteryTempNameread-writecurrentA string identifying probe location.
1.3.6.1.4.1.13858.7.1.1.1.3ColumnvpwrBatteryTempread-onlycurrentCurrent temperature as recorded by the probe.
1.3.6.1.4.1.13858.7.1.2ScalarvpwrBatteryTempLThresholdread-writecurrentTemperature value at which a clear trap would be sent. All three battery temperature must be at or below this value to trigger this trap.
1.3.6.1.4.1.13858.7.1.3ScalarvpwrBatteryTempUThresholdread-writecurrentTemperature value at which a set trap would be sent. Any one of the three battery temperatures at or exceeding this limit would trigger the trap.
1.3.6.1.4.1.13858.7.1.4ScalarbatteryTempCompensationread-writecurrentThis parameter enables/disables temperature compensation.
1.3.6.1.4.1.13858.7.1.5ScalarbatteryTempCompHighStartTemperatureread-writecurrentThe temperature at which temperature compensation becomes active.
1.3.6.1.4.1.13858.7.1.6ScalarbatteryTempCompHighStopVoltageread-writecurrentWhen temperature compensation is active, batteryTempCompHighStopVoltage is the limit to which float voltage will be reduced. For example, to set this voltage t…
1.3.6.1.4.1.13858.7.1.7ScalarbatteryTempCompHighSloperead-writecurrentThe rate at which float voltage is changed, within the specified limits, when temperature compensation is active.
1.3.6.1.4.1.13858.7.1.8ScalarbatteryTempCompLowStartTemperatureread-writecurrentThe temperature at which temperature compensation becomes active.
1.3.6.1.4.1.13858.7.1.9ScalarbatteryTempCompLowStopVoltageread-writecurrentWhen temperature compensation is active, batteryTempCompLowStopVoltage is the limit to which float voltage will be reduced. For example, to set this voltage to…
1.3.6.1.4.1.13858.7.1.10ScalarbatteryTempCompLowSloperead-writecurrentThe rate at which float voltage is changed, within the specified limits, when temperature compensation is active.
1.3.6.1.4.1.13858.7.1.11ScalarbatteryTempCompRunawayTemperatureread-writecurrentThe temperature at which system voltage will be set to batteryTempCompRunawayStopVoltage.
1.3.6.1.4.1.13858.7.1.12ScalarbatteryTempCompRunawayStopVoltageread-writecurrentWhen temperature compensation is enabled, float voltage will be reduced to batteryTempCompRunawayStopVoltage if temperature reaches batteryTempCompRunawayTempe…
1.3.6.1.4.1.13858.7.1.13ScalarbatteryTempCompSenseSourceread-writecurrentThis parameter selects the temperature sensing point for temperature compensation (in)activation.
1.3.6.1.4.1.13858.7.1.14ScalarbatteryTempCompRunawayStateread-onlycurrentThis parameter selects the temperature sensing point for temperature compensation (in)activation.
1.3.6.1.4.1.13858.7.2NodevpwrBatteryCurrentGroup
1.3.6.1.4.1.13858.7.2.1ScalarvpwrBatteryCurrentLimitAdminStateread-writecurrentThis parameter allows enabling or disabling battery current limit.
1.3.6.1.4.1.13858.7.2.2ScalarvpwrBatteryCurrentLimitread-writecurrent
1.3.6.1.4.1.13858.7.2.3ScalarvpwrBatteryCurrentread-onlycurrentBattery current
1.3.6.1.4.1.13858.7.3NodevpwrBatteryBoostGroup
1.3.6.1.4.1.13858.7.3.1ScalarvpwrBoostAdminStateread-writecurrentThis parameter allows enabling or disabling boost.
1.3.6.1.4.1.13858.7.3.2ScalarvpwrBoostVoltageread-writecurrent
1.3.6.1.4.1.13858.7.3.3ScalarvpwrBoostDurationread-writecurrentNumber of seconds for boost.
1.3.6.1.4.1.13858.7.3.4ScalarvpwrBoostOperStateread-writecurrentThis parameter allows starting or stopping boost if it is enabled.
1.3.6.1.4.1.13858.7.4NodevpwrBatteryDischargeTestGroup
1.3.6.1.4.1.13858.7.4.1ScalarvpwrBDTAdminStateread-writecurrentEnable / Disable Battery Discharge Test execution.
1.3.6.1.4.1.13858.7.4.2ScalarvpwrBDTDurationread-onlycurrentBDT Duration Setpoint.
1.3.6.1.4.1.13858.7.4.3ScalarvpwrBDTAlarmVoltageread-writecurrentBDT Alarm Voltage Setpoint.
1.3.6.1.4.1.13858.7.4.4ScalarvpwrBDTAbortVoltageread-writecurrentBDT Abort Voltage Setpoint.
1.3.6.1.4.1.13858.7.4.5ScalarvpwrBDTAlarmCoefficientread-onlycurrentDeprecated. Always returns 1
1.3.6.1.4.1.13858.7.4.6ScalarvpwrBDTOperStateread-onlycurrentStart/Stop Battery Discharge Test execution.
1.3.6.1.4.1.13858.7.4.7ScalarvpwrBDTClearAlarmread-onlycurrentClears any active BDT alarm.
1.3.6.1.4.1.13858.7.4.8ScalarvpwrBDTActualTimeread-onlycurrentActual BDT runtime in minutes.
1.3.6.1.4.1.13858.7.4.9ScalarvpwrBDTAlarmDelayread-onlycurrentDelay, in minutes, before checking and raising BDT alarm. Test: Plant Voltage <= BDTAlarmVoltage
1.3.6.1.4.1.13858.7.4.10ScalarvpwrBDTResultread-onlycurrentResults of BDT.
1.3.6.1.4.1.13858.7.4.11ScalarvpwrBDTAutoAdminStateread-writecurrentEnable /Disable Battery Discharge Test data collection upon detecting AC Fail condition.
1.3.6.1.4.1.13858.7.4.12TablevpwrBDTHistTablenot-accessiblecurrentThis table provides results of past BDT test.
1.3.6.1.4.1.13858.7.4.12.1RowvpwrBDTHistEntrynot-accessiblecurrentAn entry containing information applicable to a particular BDT History.
1.3.6.1.4.1.13858.7.4.12.1.1ColumnvpwrBDTHistIndexread-onlycurrentBDT History index.
1.3.6.1.4.1.13858.7.4.12.1.2ColumnvpwrBDTHistDateTimeread-onlycurrentBDT run date as yr-mm-dd hh:mm
1.3.6.1.4.1.13858.7.4.12.1.3ColumnvpwrBDTHistDurationread-onlycurrentBDT duration at the time this test was run.
1.3.6.1.4.1.13858.7.4.12.1.4ColumnvpwrBDTHistAlarmVoltageread-writecurrentBDT Alarm Voltage setpoint when this test was run.
1.3.6.1.4.1.13858.7.4.12.1.5ColumnvpwrBDTHistAbortVoltageread-onlycurrentBDT Abort Voltage setpoint when this test was run.
1.3.6.1.4.1.13858.7.4.12.1.6ColumnvpwrBDTHistStartMethodread-onlycurrentHow Battery Discharge Test was started.
1.3.6.1.4.1.13858.7.4.12.1.7ColumnvpwrBDTHistResultread-onlycurrentResults of BDT.
1.3.6.1.4.1.13858.7.4.12.1.8ColumnvpwrBDTHistActualTimeread-onlycurrentActual BDT runtime in minutes.
1.3.6.1.4.1.13858.7.4.12.1.9ColumnvpwrBDTHistStartVoltageread-onlycurrentPlant Voltage at the time the BDT was started.
1.3.6.1.4.1.13858.7.4.12.1.10ColumnvpwrBDTHistEndVoltageread-onlycurrentPlant Voltage at the time the BDT was completed.
1.3.6.1.4.1.13858.7.4.13TablevpwrBDTSchedTablenot-accessiblecurrentThis table provides the list of the 12 BDTs that can be scheduled. Need to set date(month and day) and time (hh and minutes) when the test should be started.
1.3.6.1.4.1.13858.7.4.13.1RowvpwrBDTSchedEntrynot-accessiblecurrentAn entry describing an alarm.
1.3.6.1.4.1.13858.7.4.13.1.1ColumnvpwrBDTSchedIndexread-onlycurrentBDT Sched index.
1.3.6.1.4.1.13858.7.4.13.1.2ColumnvpwrBDTSchedDayread-writecurrent1 to 28,29,30 or 31 depending upon the month
1.3.6.1.4.1.13858.7.4.13.1.3ColumnvpwrBDTSchedMonthread-writecurrentrange 1 to 12
1.3.6.1.4.1.13858.7.4.13.1.4ColumnvpwrBDTSchedHourread-writecurrentrange 0 to 23
1.3.6.1.4.1.13858.7.4.13.1.5ColumnvpwrBDTSchedMinuteread-writecurrentrange 0 to 59
1.3.6.1.4.1.13858.8NodevpwrDcPowerAlarmGroup
1.3.6.1.4.1.13858.8.1ScalarvpwrAlarmsPresentread-onlycurrentThe present number of active alarm conditions.
1.3.6.1.4.1.13858.8.2TablevpwrAlarmTablenot-accessiblecurrentA list of alarm table entries. The table contains zero, one, or multiple rows at any time depending upon the number of alarm conditions in effect. The table is…
1.3.6.1.4.1.13858.8.2.1RowvpwrAlarmEntrynot-accessiblecurrentAn entry containing information applicable to a particular alarm.
1.3.6.1.4.1.13858.8.2.1.1ColumnvpwrAlarmIndexread-onlycurrentIdentifies the alarm associated with the module. It is unique on per module type basis. For example, multiple rectifiers can have the same alarm and therefore …
1.3.6.1.4.1.13858.8.2.1.2ColumnvpwrAlarmDescrread-onlycurrentA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con…
1.3.6.1.4.1.13858.8.2.1.3ColumnvpwrAlarmTimeread-onlycurrentThe value of sysUpTime when the alarm condition was detected.
1.3.6.1.4.1.13858.8.3TablesysAlarmConfigTablenot-accessiblecurrentThis table describes system alarm configuration and current status.
1.3.6.1.4.1.13858.8.3.1RowsysAlarmConfigEntrynot-accessiblecurrentAn entry containing information applicable to a particular system alarm.
1.3.6.1.4.1.13858.8.3.1.1ColumnsysAlarmIndexread-onlycurrentIndex into system alarm table
1.3.6.1.4.1.13858.8.3.1.2ColumnsysAlarmDefaultNameread-onlycurrentDefault alarm name.
1.3.6.1.4.1.13858.8.3.1.3ColumnsysAlarmCustomNameread-writecurrentA custom alarm name.
1.3.6.1.4.1.13858.8.3.1.4ColumnsysAlarmSeverityread-writecurrentAlarm Severity as denoted by Major and Minor Alarm Mask
1.3.6.1.4.1.13858.8.3.1.5ColumnsysAlarmToRelayMappingread-writecurrentNo additional mapping = 0 Map to Relay A = 1 Map to Relay B = 2 Map to Relay C = 4 Map to Relay D = 8 Map to Relay E = 16 Map to Relay F = 32 Map to Relay A an…
1.3.6.1.4.1.13858.8.3.1.6ColumnsysAlarmOperStatusread-onlycurrentIndicates current alarm status
1.3.6.1.4.1.13858.8.4ScalarsysAlarmComFailStateread-writecurrentEnable/Disable generation of comm fail alarm.
1.3.6.1.4.1.13858.8.5ScalarsysAlarmIShareStateread-writecurrentEnable/Disable generation of current share alarm.
1.3.6.1.4.1.13858.8.6ScalarsysAlarmRedundancyStateread-writecurrentEnable/Disable generation of redundancy alarm.
1.3.6.1.4.1.13858.8.7ScalarsysAlarmComFailToACFailStateread-writecurrentEnable/Disable generation of ACF upon Com Fail
1.3.6.1.4.1.13858.9NodevpwrDcPowerSnmpConfig
1.3.6.1.4.1.13858.9.1TablevpwrTrapTablenot-accessiblecurrentA list of possible trap destinations depending upon the criticality of the trap.
1.3.6.1.4.1.13858.9.1.1RowvpwrTrapEntrynot-accessiblecurrentAn entry containing information applicable to a particular trap destination.
1.3.6.1.4.1.13858.9.1.1.1ColumnvpwrTrapIpIndexread-onlycurrentTrap Entry Index
1.3.6.1.4.1.13858.9.1.1.2ColumnvpwrTrapIpAddressread-writecurrentTrap destination IP Address
1.3.6.1.4.1.13858.9.1.1.3ColumnvpwrTrapCriticalityread-writecurrentCriticality of traps sent to this IP Address
1.3.6.1.4.1.13858.9.2ScalarvpwrReadCommunityStringread-writecurrentThis allows setting password to be able to do Get operations
1.3.6.1.4.1.13858.9.3ScalarvpwrWriteCommunityStringread-writecurrentThis allows setting password to be able to do Get and Set operations. The read-access is not allowed in the actual implementation.
1.3.6.1.4.1.13858.9.4ScalarvpwrTrapCommunityStringread-writecurrentThis allows setting community string required for the trap to be accepted at the destination.
1.3.6.1.4.1.13858.9.5ScalarvpwrTrapVersionread-writecurrentThis allows setting the version of trap message sent from the system
1.3.6.1.4.1.13858.10NodevpwrDcPowerTraps
1.3.6.1.4.1.13858.10.1NotificationvpwrTrapPowerMajorAlarmcurrentMajor Alarm
1.3.6.1.4.1.13858.10.2NotificationvpwrTrapPowerMinorAlarmcurrentMinor Alarm
1.3.6.1.4.1.13858.10.3NotificationvpwrTrapACFAlarmcurrentAC Fail Alarm
1.3.6.1.4.1.13858.10.4NotificationvpwrTrapHVAlarmcurrentHigh Voltage Warning Alarm
1.3.6.1.4.1.13858.10.5NotificationvpwrTrapHVSDAlarmcurrentHigh Voltage Shutdown Alarm
1.3.6.1.4.1.13858.10.6NotificationvpwrTrapBDAlarmcurrentBattery on Discharge Alarm
1.3.6.1.4.1.13858.10.7NotificationvpwrTrapLVDWarningAlarmcurrentLVD Warning Alarm
1.3.6.1.4.1.13858.10.8NotificationvpwrTrapLVDOpenAlarmcurrentLVD Open Alarm
1.3.6.1.4.1.13858.10.9NotificationvpwrTrapDistAlarmcurrentDistribution Open Alarm
1.3.6.1.4.1.13858.10.10NotificationvpwrTrapAuxAlarmcurrentAuxiliary System Alarm
1.3.6.1.4.1.13858.10.11NotificationvpwrTrapSystemRedundancyAlarmcurrentSystem Redundant Capacity Alarm
1.3.6.1.4.1.13858.10.12NotificationvpwrTrapIShareAlarmcurrentRectifier Current Share Alarm
1.3.6.1.4.1.13858.10.13NotificationvpwrTrapModuleFailAlarmcurrentSingle Rectifier Fail Alarm
1.3.6.1.4.1.13858.10.14NotificationvpwrTrapMultipleModuleFailAlarmcurrentMultiple Rectifier Fail Alarm
1.3.6.1.4.1.13858.10.15NotificationvpwrTrapModuleCommAlarmcurrentPower Module Communication Alarm
1.3.6.1.4.1.13858.10.16NotificationvpwrTrapSystemOverTemperatureAlarmcurrentSystem Over Temperature Alarm
1.3.6.1.4.1.13858.10.17NotificationvpwrTrapSystemOKcurrentSYSTEM OK - No Active Alarms
1.3.6.1.4.1.13858.10.18NotificationvpwrTrapModuleInsertedcurrentA new module has been inserted into the system
1.3.6.1.4.1.13858.10.19NotificationvpwrTrapModuleRemovedcurrentA module has been removed from the system
1.3.6.1.4.1.13858.10.20NotificationvpwrTrapThermalCompActivecurrentThermal compensation has become active
1.3.6.1.4.1.13858.10.21NotificationvpwrTrapThermalCompInactivecurrentThermal compensation has been de-activated
1.3.6.1.4.1.13858.10.22NotificationvpwrTrapInternalTempAlarmSetcurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! Internal Temperature upper threshold exceeded
1.3.6.1.4.1.13858.10.23NotificationvpwrTrapInternalTempAlarmClearedcurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! Internal Temperature within limits
1.3.6.1.4.1.13858.10.24NotificationvpwrTrapBatteryTempAlarmSetcurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! At least one Battery Temperature exceeded upper threshold
1.3.6.1.4.1.13858.10.25NotificationvpwrTrapBatteryTempAlarmClearedcurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! All Battery Temperatures within limits
1.3.6.1.4.1.13858.10.26NotificationvpwrTrapLoginFailcurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! Admin login failed due to wrong username/password
1.3.6.1.4.1.13858.10.27NotificationvpwrTrapLoginSuccesscurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! Admin login successful
1.3.6.1.4.1.13858.10.28NotificationvpwrTrapLogoutcurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! Admin logout
1.3.6.1.4.1.13858.10.29NotificationvpwrTrapAdminPwdChangecurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! Config change submitted with invalid access
1.3.6.1.4.1.13858.10.30NotificationvpwrTrapIllegalConfigSubmitcurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! Config change submitted with invalid access
1.3.6.1.4.1.13858.10.31NotificationvpwrTrapCfgChangecurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! Config change submitted
1.3.6.1.4.1.13858.10.32NotificationvpwrTrapClearEventHistorycurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! Clear Event history buffer clear request
1.3.6.1.4.1.13858.10.33NotificationvpwrTrapSwDownloadNoRebootcurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! System software upgrade without reboot
1.3.6.1.4.1.13858.10.34NotificationvpwrTrapSwDownloadAndRebootcurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! System reboot due to software upgrade
1.3.6.1.4.1.13858.10.35NotificationvpwrTrapSystemClockChangecurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! System clock updated
1.3.6.1.4.1.13858.10.36NotificationvpwrTrapModuleAlarmcurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! Module Alarm
1.3.6.1.4.1.13858.10.37NotificationvpwrTrapOIDChangecurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! Change in OID
1.3.6.1.4.1.13858.10.38NotificationvpwrTrapThermalRunawaycurrentThermal Runaway Alarm
1.3.6.1.4.1.13858.10.39NotificationvpwrTrapBatteryDischargeTestAlarmcurrentSystem Voltage dropped to BDT Alarm Setpoint
1.3.6.1.4.1.13858.10.40NotificationvpwrTrapBayUnnameAlarmcurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! Unassigned Bay Fail Alarm
1.3.6.1.4.1.13858.10.41NotificationvpwrTrapPMComFailAlarmcurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! PM Communication Fail Alarm
1.3.6.1.4.1.13858.10.42NotificationvpwrTrapFuseOverloadAlarmcurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! Fuse Overload Alarm
1.3.6.1.4.1.13858.10.43NotificationvpwrTrapPeripheralAlarmcurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! Peripheral Alarm.
1.3.6.1.4.1.13858.10.44NotificationvpwrTrapThermalProbeAlarmcurrentThermal Probe Missing Alarm
1.3.6.1.4.1.13858.10.45NotificationvpwrTrapBayCommAlarmcurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! Bay Communication Alarm
1.3.6.1.4.1.13858.10.46NotificationvpwrTrapDistributionCommAlarmcurrentDistribution Communication Alarm
1.3.6.1.4.1.13858.10.47NotificationvpwrTrapConverterAlarmcurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! Single Converter Fail Alarm
1.3.6.1.4.1.13858.10.48NotificationvpwrTrapMultipleConvFailAlarmcurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! Multiple Converter Fail Alarm
1.3.6.1.4.1.13858.10.49NotificationvpwrTrapDGUAlarmcurrent!!! For Future Use. !!! DGU Alarm
1.3.6.1.4.1.13858.10.50NotificationvpwrTrapConfigErrorAlarmcurrentConfiguration Error
1.3.6.1.4.1.13858.10.51NotificationvpwrTrapDisplayFirmwareMismatchAlarmcurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! Display Firmware Mismatch
1.3.6.1.4.1.13858.10.52NotificationvpwrTrapConverterInputFailAlarmcurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! Converter Input Fail Alarm
1.3.6.1.4.1.13858.10.53NotificationvpwrTrapBatteryRechgIlimitFailAlarmcurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! Battery Recharge Current Limit Fail
1.3.6.1.4.1.13858.10.54NotificationvpwrTrapSystemAlivecurrentPeriodic Keepalive trap
1.3.6.1.4.1.13858.10.55NotificationvpwrTrapSystemAuxAlmSourcecurrentSource of Auxilary Alarms. Indicates the module and the aux within the module causing alarms
1.3.6.1.4.1.13858.10.56NotificationvpwrTrapSystemDistAlmSourcecurrentSource of Distribution Alarms. Indicates the module and the dist within the module causing alarms
1.3.6.1.4.1.13858.10.58NotificationvpwrTrapSystemBatCapacityAlarmcurrentPlant Load exceeds Plant Battery Current Capacity. Useful for batteries that limit maximum discharge current It will not be sent out for VRLA batteries, eg
1.3.6.1.4.1.13858.10.61NotificationvpwrTrapSystemACFClearAlarmcurrentAC Fail (ACF) Conditioned Cleared Alarm. Duration is in minutes.
1.3.6.1.4.1.13858.10.62NotificationvpwrTrapSystemACFSetAlarmcurrentACF Conditioned detected Alarm. The duration would always be zero. Msg String: ACF Alarm Set
1.3.6.1.4.1.13858.10.64NotificationvpwrTrapSystemBatCapacityLeftcurrent!!! For Future Use. !!! Battery Useful Capacity Remaining
1.3.6.1.4.1.13858.10.65NotificationvpwrTrapRectifierUVAlarmcurrentRectifier Under Voltage Alarm
1.3.6.1.4.1.13858.10.66NotificationvpwrTrapMultRectifierUVAlarmcurrent!!! For Future Use. !!! Multiple Rectifier Under Voltage Alarm
1.3.6.1.4.1.13858.10.67NotificationvpwrTrapRingerAlarmcurrentRinger Alarm
1.3.6.1.4.1.13858.10.68NotificationvpwrTrapMultRingerAlarmcurrent!!! For Future Use. !!! Multiple Ringer Alarm
1.3.6.1.4.1.13858.10.69NotificationvpwrTrapI2CCANAlarmcurrent!!! For Future Use. !!! Unmapped I2C/CAN Address Alarm One of your I2C or CAN devices has a duplicate or invalid address and can not be mapped. Please recheck …
1.3.6.1.4.1.13858.10.70NotificationvpwrTrapRectifierIlimitAlarmcurrentRectifier Current Limit Alarm
1.3.6.1.4.1.13858.10.71NotificationvpwrTrapMultRectifierIlimitAlarmcurrent!!! For Future Use. !!! Multiple Rectifier Current Limit Alarm
1.3.6.1.4.1.13858.10.72NotificationvpwrTrapRingerCommAlarmcurrentRinger Communication Alarm
1.3.6.1.4.1.13858.10.99NotificationvpwrTrapUnassignedAlarmcurrent!!! NOT VALID FOR BC2000 CONTROLLER !!! Unassigned Alarm(Trap) - Check Web Page
1.3.6.1.4.1.13858.11NodevpwrDcPowerTrapVars
1.3.6.1.4.1.13858.11.1ScalarvpwrTrapsMsgStringread-onlycurrentPlace holder for trap notification message string
1.3.6.1.4.1.13858.11.2ScalarvpwrTrapUserIpAddressnot-accessiblecurrentPlace holder for IP address of the user accessing the system
1.3.6.1.4.1.13858.11.3ScalarvpwrTrapAcfDurationread-onlycurrentPlace holder for duration.
1.3.6.1.4.1.13858.11.4ScalarvpwrAlarmingSubModuleBitMapread-onlycurrentindices of alarming sources are encoded as a bit-map e.g., source 1 and source 2 will be encoded as hex 3. source 1 and 3 will be encoded as hex 5.
1.3.6.1.4.1.13858.11.5ScalarvpwrBatteryCurrentCapacityread-onlycurrentPlace holder for total battery capacity
1.3.6.1.4.1.13858.11.6ScalarvpwrAlarmingModuleIndexread-onlycurrentindex of alarming module.
1.3.6.1.4.1.13858.11.7ScalarvpwrAlarmingModuleOIDread-onlycurrentIt indicates the type of the module by specifiying its OID
1.3.6.1.4.1.13858.11.8ScalarvpwrAlarmingModuleBitMapnot-accessiblecurrentindices of alarming sources are encoded as a bit-map e.g., source 1 and source 2 will be encoded as hex 3. source 1 and 3 will be encoded as hex 5.
1.3.6.1.4.1.13858.11.9ScalarvpwrBatteryRemainingTimeread-onlycurrentPlace holder for remaining battery time at the current load
1.3.6.1.4.1.13858.12NodevpwrDcPowerRinger
1.3.6.1.4.1.13858.12.1NodevpwrRingerConfigGroup
1.3.6.1.4.1.13858.12.1.1ScalarvpwrRingerIndexread-writecurrentThis parameter allows selecting ringer A or Ringer B as the active ringer.
1.3.6.1.4.1.13858.12.1.2ScalarvpwrRingerParameterAdminStateread-writecurrentThis parameter allows selecting ringer A or Ringer B as the active ringer.
1.3.6.1.4.1.13858.12.1.3ScalarvpwrRingerParameterAcVoltageread-writecurrentThis parameter sets the output AC voltage of the ringer.
1.3.6.1.4.1.13858.12.1.4ScalarvpwrRingerParameterDcVoltageread-writecurrentThis parameter sets the DC offset value of the ringer.
1.3.6.1.4.1.13858.12.1.5ScalarvpwrRingerParameterFrequencyread-writecurrentThis parameter sets the ringer AC frequency.
1.3.6.1.4.1.13858.12.1.6ScalarvpwrRingerNumberPresentread-onlycurrentThe present number of ringer modules.
1.3.6.1.4.1.13858.12.2NodevpwrRingerAlarmGroup
1.3.6.1.4.1.13858.12.2.1IdentityvpwrRingerAlarmAFailedcurrentRinger A Failed
1.3.6.1.4.1.13858.12.2.2IdentityvpwrRingerAlarmAOverTempcurrentRinger A Heatsink Over-Temperature
1.3.6.1.4.1.13858.12.2.3IdentityvpwrRingerAlarmAOverCurrentcurrentRinger A Over-Current protection
1.3.6.1.4.1.13858.12.2.4IdentityvpwrRingerAlarmBFailedcurrentRinger B Failed
1.3.6.1.4.1.13858.12.2.5IdentityvpwrRingerAlarmBOverTempcurrentRinger B Heatsink Over-Temperature
1.3.6.1.4.1.13858.12.2.6IdentityvpwrRingerAlarmBOverCurrentcurrentRinger B Over-Current protection
1.3.6.1.4.1.13858.12.3NodevpwrRingerTestGroup
1.3.6.1.4.1.13858.13NodevpwrDcPowerDcDcConverter
1.3.6.1.4.1.13858.13.1NodevpwrDcDcConverterConfigGroup
1.3.6.1.4.1.13858.13.2NodevpwrDcDcConverterAlarmGroup
1.3.6.1.4.1.13858.13.3NodevpwrDcDcConverterTestGroup
1.3.6.1.4.1.13858.14NodevpwrDcPowerDcAcInverter
1.3.6.1.4.1.13858.14.1NodevpwrDcAcInverterConfigGroup
1.3.6.1.4.1.13858.14.2NodevpwrDcAcInverterAlarmGroup
1.3.6.1.4.1.13858.14.3NodevpwrDcAcInverterTestGroup
1.3.6.1.4.1.13858.15NodevpwrDcPowerAcLineModule
1.3.6.1.4.1.13858.15.1NodevpwrAcLineModuleConfigGroup
1.3.6.1.4.1.13858.15.2NodevpwrAcLineModuleAlarmGroup
1.3.6.1.4.1.13858.15.3NodevpwrAcLineModuleTestGroup
1.3.6.1.4.1.13858.16NodevpwrDcPowerIoModule
1.3.6.1.4.1.13858.16.1NodevpwrIoModuleConfigGroup
1.3.6.1.4.1.13858.16.2NodevpwrIoModuleAlarmGroup
1.3.6.1.4.1.13858.16.3NodevpwrIoModuleTestGroup
1.3.6.1.4.1.13858.17NodevpwrDcPowerPMModule
1.3.6.1.4.1.13858.17.1TablevpwrPMCnfgTablenot-accessiblecurrentThis table shows the current configuration of the TRIO/PM86000/Controller inputs.
1.3.6.1.4.1.13858.17.1.1RowvpwrPMCnfgEntrynot-accessiblecurrentAn entry containing current configuration of the TRIO/PM86000/Controller inputs.
1.3.6.1.4.1.13858.17.1.1.1ColumnvpwrPMIndexread-onlycurrentThis parameter describes which TRIO/PM86000 device is being accessed.
1.3.6.1.4.1.13858.17.1.1.2ColumnvpwrPMDescriptionread-onlycurrentThis parameter describes the configuration of the TRIO/PM86000 device.
1.3.6.1.4.1.13858.17.1.1.3ColumnvpwrPMCnfg1read-writecurrentThis parameter gets the current configuration of the TRIO/PM86000, input 1
1.3.6.1.4.1.13858.17.1.1.4ColumnvpwrPMCnfg2read-writecurrentThis parameter gets the current configuration of the TRIO/PM86000, input 2
1.3.6.1.4.1.13858.17.1.1.5ColumnvpwrPMCnfg3read-writecurrentThis parameter gets the current configuration of the TRIO/PM86000, input 3
1.3.6.1.4.1.13858.17.1.1.6ColumnvpwrPMCnfg4read-writecurrentThis parameter gets the current configuration of the TRIO/PM86000, input 4
1.3.6.1.4.1.13858.17.1.1.7ColumnvpwrPMCnfg5read-writecurrentThis parameter gets the current configuration of the TRIO/PM86000, input 5
1.3.6.1.4.1.13858.17.1.1.8ColumnvpwrPMCnfg6read-writecurrentThis parameter gets the current configuration of the TRIO/PM86000, input 6
1.3.6.1.4.1.13858.17.1.1.9ColumnvpwrPMCnfg7read-writecurrentThis parameter gets the current configuration of the TRIO (PM86000), input 7
1.3.6.1.4.1.13858.17.1.1.10ColumnvpwrPMCnfg8read-writecurrentThis parameter gets the current configuration of the TRIO/PM86000, input 8
1.3.6.1.4.1.13858.17.2TablevpwrPMInputStatusTablenot-accessiblecurrentThis table shows the current values of the TRIO/PM86000/Controller inputs.
1.3.6.1.4.1.13858.17.2.1RowvpwrPMInputStatusEntrynot-accessiblecurrentAn entry containing current state of the TRIO/PM86000/Controller inputs.
1.3.6.1.4.1.13858.17.2.1.1ColumnvpwrPMIndex1read-onlycurrentThis parameter describes which TRIO/PM86000 device is being accessed.
1.3.6.1.4.1.13858.17.2.1.2ColumnvpwrPMDescription1read-onlycurrentThis parameter describes the input values of the TRIO/PM86000 device.
1.3.6.1.4.1.13858.17.2.1.3ColumnvpwrPMInput1Stateread-onlycurrentThis parameter gets the current state of input 1
1.3.6.1.4.1.13858.17.2.1.4ColumnvpwrPMInput2Stateread-onlycurrentThis parameter gets the current state of input 2
1.3.6.1.4.1.13858.17.2.1.5ColumnvpwrPMInput3Stateread-onlycurrentThis parameter gets the current state of input 3
1.3.6.1.4.1.13858.17.2.1.6ColumnvpwrPMInput4Stateread-onlycurrentThis parameter gets the current state of input 4
1.3.6.1.4.1.13858.17.2.1.7ColumnvpwrPMInput5Stateread-onlycurrentThis parameter gets the current state of input 5
1.3.6.1.4.1.13858.17.2.1.8ColumnvpwrPMInput6Stateread-onlycurrentThis parameter gets the current state of input 6
1.3.6.1.4.1.13858.17.2.1.9ColumnvpwrPMInput7Stateread-onlycurrentThis parameter gets the current state of input 7
1.3.6.1.4.1.13858.17.2.1.10ColumnvpwrPMInput8Stateread-onlycurrentThis parameter gets the current state of input 8
1.3.6.1.4.1.13858.17.3TablevpwrPMRelayCtrlTablenot-accessiblecurrentThis table describes/controls system relays.
1.3.6.1.4.1.13858.17.3.1RowvpwrPMRelayCtrlEntrynot-accessiblecurrentAn entry containing current state of the relays.
1.3.6.1.4.1.13858.17.3.1.1ColumnvpwrPMIndex2read-onlycurrentThis parameter describes the TRIO/PM device
1.3.6.1.4.1.13858.17.3.1.2ColumnvpwrPMDescription2read-onlycurrentThis parameter describes the TRIO/PM device
1.3.6.1.4.1.13858.17.3.1.3ColumnvpwrPMRelay1Stateread-writecurrentThis parameter sets the current state of relay 1
1.3.6.1.4.1.13858.17.3.1.4ColumnvpwrPMRelay2Stateread-writecurrentThis parameter sets the current state of relay 2
1.3.6.1.4.1.13858.17.3.1.5ColumnvpwrPMRelay3Stateread-writecurrentThis parameter sets the current state of relay 3
1.3.6.1.4.1.13858.17.3.1.6ColumnvpwrPMRelay4Stateread-writecurrentThis parameter sets the current state of relay 4
1.3.6.1.4.1.13858.17.3.1.7ColumnvpwrPMRelay5Stateread-writecurrentThis parameter sets the current state of relay 5
1.3.6.1.4.1.13858.17.3.1.8ColumnvpwrPMRelay6Stateread-writecurrentThis parameter sets the current state of relay 6
1.3.6.1.4.1.13858.17.4NodevpwrPMModuleAlarmGroup
1.3.6.1.4.1.13858.17.5NodevpwrPMModuleTestGroup
1.3.6.1.4.1.13858.18NodevpwrDcPowerDistModule
1.3.6.1.4.1.13858.19NodevpwrDcPowerBattery
1.3.6.1.4.1.13858.20NodevpwrDcPowerController
1.3.6.1.4.1.13858.499NodevpwrDcPowerUnkModule
1.3.6.1.4.1.13858.500NodethirdPartyProduct
Type Definitions
NameSyntaxStatusDescription
BDTResultTCINTEGER { bdtResultCleared(0), bdtResultPassed(1), bdtResultFailed(2), bdtResultStopped(3), bdtResultAborted(4), bdtResultInProgress(5) }currentThe defines how was BDT started.
BDTStartSourceTCINTEGER { bdtInactive(0), bdtManualStart(1), bdtSched01Start1(2), bdtSched02Start2(3), bdtSched03Start3(4), bdtSched04Start4(5), bdtSched05Start5(6), bdtSched06Start6(7), bdtSched07Start7(8), bdtSched08Start8(9), bdtSched09Start9(10), bdtSched10Start10(11), bdtSched11Start11(12), bdtSched12Start12(13), bdtACFailStart(14) }currentThe defines how was BDT started.
GenericEnableDisableTCINTEGER { disabled(0), enabled(1) }currentThe defines how was BDT started.
NonNegativeIntegerInteger32 (0..2147483647)currentThis data type is a non-negative value.
PositiveIntegerInteger32 (1..2147483647)currentThis data type is a non-zero and non-negative value.
SysInputValueINTEGER { disabled(-127), removed(-126), shorted(-125), auxAlarm(-124), auxNormal(-123), distAlarm(-122), distNormal(-121), undefined(255) }currentThese are the results of the system input value definitions.
VpwrPMCnfgValueINTEGER { disabled(0), tProbe(1), auxNO(2), auxNC(3), distNO(4), distNC(5), undefined(255) }currentThese are the results of the system input value definitions.