MIB Viewer

ELTEK-DISTRIBUTED-MIB

337 objects
No module-level DESCRIPTION found.
Imported Objects
ELTEK-COMMON-MIBeltek
SNMPv2-CONFNOTIFICATION-GROUP
SNMPv2-SMICounter32 enterprises Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE
SNMPv2-TCDisplayString
OIDNameAccessStatusDescription
1.3.6.1.4.1.12148.9NodeeltekDistributedPlantV8
1.3.6.1.4.1.12148.9.1NodecontrolSystem
1.3.6.1.4.1.12148.9.1.1NodesystemTime
1.3.6.1.4.1.12148.9.1.1.1ScalarsystemTimeTimeread-onlycurrentThe system date and time. Used for event timestamps and logging
1.3.6.1.4.1.12148.9.1.2ScalarsystemInfoRefreshread-writecurrentThis is a push button function that will rebuild all the dynamic SNMP tables. When control units are removed or added this function must be executed to make su…
1.3.6.1.4.1.12148.9.1.3ScalarsystemTrapRepeatRateread-writecurrentThis object sets the repeat rate of any active traps, in minutes. Entering 0 (zero) will prevent repeating traps - one trap only will be sent per alarm event.
1.3.6.1.4.1.12148.9.1.4ScalarsystemSendOffTrapread-writecurrentA separate off-trap will be issued when an alarm condition goes off, if this flag is set to 1. Entering 0 (zero) will prevent OFF traps from being transmitted.
1.3.6.1.4.1.12148.9.1.5ScalarsystemNumOfControlUnitsread-onlycurrentThe number of Control units in a distributed system.
1.3.6.1.4.1.12148.9.1.6ScalarsystemControlUnitIndexaccessible-for-notifycurrentIndex used for navigating in the table for configurable inputs.
1.3.6.1.4.1.12148.9.1.7TablesystemControlUnitTablenot-accessiblecurrentThis table contains the status of the programmable inputs. There is one row for each Control unit.
1.3.6.1.4.1.12148.9.1.7.1RowsystemControlUnitEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.9.1.7.1.1ColumninputControlUnitIDread-onlycurrentThe ID of which Control unit to be read.
1.3.6.1.4.1.12148.9.1.7.1.2ColumninputUserConfigurable1read-onlycurrentProgrammable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.3ColumninputUserConfigurable2read-onlycurrentProgrammable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.4ColumninputUserConfigurable3read-onlycurrentProgrammable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.5ColumninputUserConfigurable4read-onlycurrentProgrammable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.6ColumninputUserConfigurable5read-onlycurrentProgrammable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.7ColumninputUserConfigurable6read-onlycurrentProgrammable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.8ColumninputUserConfigurable7read-onlycurrentProgrammable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.9ColumninputUserConfigurable8read-onlycurrentProgrammable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.10ColumninputUserConfigurable9read-onlycurrentProgrammable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.11ColumninputUserConfigurable10read-onlycurrentProgrammable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.8ScalarsystemLinkStatusread-onlycurrentA flag showing the status of the serial port used between the HEIDI Webpower adapter or embedded WEB/SNMP card and the Smartpack Control system. If this flag s…
1.3.6.1.4.1.12148.9.1.9ScalarsystemInitiateEEPROMread-writedeprecatedPushbutton function that initiates a forced write of default data to the SB70/SB72 eeprom. This function is used for productiontest only. The 3rd party OS used…
1.3.6.1.4.1.12148.9.1.10ScalarsystemLastDigInputaccessible-for-notifycurrentThe last Prog.Input that generated a trap. Used by Traps only.
1.3.6.1.4.1.12148.9.1.11ScalarsystemTrapCounteraccessible-for-notifycurrentThe number of times a trap has been repeated.. Only acessible for Traps.
1.3.6.1.4.1.12148.9.1.12ScalarsystemHeartBeatTrapRepeatRateread-writecurrentThe repeat rate for the systemHeartBeatTrap. Setting this value to zero will disable the HeartBeatTrap.
1.3.6.1.4.1.12148.9.1.13ScalarsystemResetManualAlarmsread-writecurrentA pushutton that resets all manually resettable alarms in the controlsystem. Alarms that is not manually resettable will not be affected by this.
1.3.6.1.4.1.12148.9.1.14ScalarsystemControlUnitInputIndexaccessible-for-notifycurrentIndex used for navigating in the table for configurable inputs.
1.3.6.1.4.1.12148.9.1.15TablesystemControlUnitInputTablenot-accessiblecurrentThis table contains the description of the programmable inputs. There is one row for each Control unit. Programmable input alarms will have description attache…
1.3.6.1.4.1.12148.9.1.15.1RowsystemControlUnitInputEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.9.1.15.1.1ColumninputUnitIDread-onlycurrentThe ID of which Control unit to be read.
1.3.6.1.4.1.12148.9.1.15.1.2ColumninputUserConfigurableText1read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.1.
1.3.6.1.4.1.12148.9.1.15.1.3ColumninputUserConfigurableText2read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.2.
1.3.6.1.4.1.12148.9.1.15.1.4ColumninputUserConfigurableText3read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.3.
1.3.6.1.4.1.12148.9.1.15.1.5ColumninputUserConfigurableText4read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.4.
1.3.6.1.4.1.12148.9.1.15.1.6ColumninputUserConfigurableText5read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.5.
1.3.6.1.4.1.12148.9.1.15.1.7ColumninputUserConfigurableText6read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.6.
1.3.6.1.4.1.12148.9.1.15.1.8ColumninputUserConfigurableText7read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.7.
1.3.6.1.4.1.12148.9.1.15.1.9ColumninputUserConfigurableText8read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.8.
1.3.6.1.4.1.12148.9.1.15.1.10ColumninputUserConfigurableText9read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.9.
1.3.6.1.4.1.12148.9.1.15.1.11ColumninputUserConfigurableText10read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.10.
1.3.6.1.4.1.12148.9.1.16ScalarsystemResetCtrlSystemread-writedeprecatedA pushbutton function that resets the control system. Configuration data will be kept.
1.3.6.1.4.1.12148.9.1.17NodeioUnits
1.3.6.1.4.1.12148.9.1.17.1ScalarioUnitNumberOfUnitsread-onlycurrent
1.3.6.1.4.1.12148.9.1.17.2ScalarioUnitsIndexaccessible-for-notifycurrent
1.3.6.1.4.1.12148.9.1.17.3TableioUnitsTablenot-accessiblecurrent
1.3.6.1.4.1.12148.9.1.17.3.1RowioUnitsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.9.1.17.3.1.1ColumnioUnitIDread-onlycurrent
1.3.6.1.4.1.12148.9.1.17.3.1.2ColumnioUnitOutDoorTemp1read-onlycurrentThe measured value of the temperature input. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit.
1.3.6.1.4.1.12148.9.1.17.3.1.3ColumnioUnitOutDoorTemp2read-onlycurrentThe measured value of the temperature input. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit.
1.3.6.1.4.1.12148.9.1.17.3.1.4ColumnioUnitFanSpeed1read-onlycurrentThe speed of the cooling/ circulation fan. The speed is a percentage of max RPM.
1.3.6.1.4.1.12148.9.1.17.3.1.5ColumnioUnitFanSpeedDeltaValue1read-onlycurrentThe deviation of the cooling/circulation fans speed set value. Is a percentage of the desired value.
1.3.6.1.4.1.12148.9.1.17.3.1.6ColumnioUnitFanSpeed2read-onlycurrentThe speed of the cooling/ circulation fan. The speed is a percentage of max RPM.
1.3.6.1.4.1.12148.9.1.17.3.1.7ColumnioUnitFanSpeedDeltaValue2read-onlycurrentThe deviation of the cooling/circulation fans speed set value. Is a percentage of the desired value.
1.3.6.1.4.1.12148.9.1.17.3.1.8ColumnioUnitProgInputText1read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.1
1.3.6.1.4.1.12148.9.1.17.3.1.9ColumnioUnitProgInputStatus1read-onlycurrentProgrammable input status.
1.3.6.1.4.1.12148.9.1.17.3.1.10ColumnioUnitProgInputText2read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.2
1.3.6.1.4.1.12148.9.1.17.3.1.11ColumnioUnitProgInputStatus2read-onlycurrentProgrammable input status.
1.3.6.1.4.1.12148.9.1.17.3.1.12ColumnioUnitProgInputText3read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.3
1.3.6.1.4.1.12148.9.1.17.3.1.13ColumnioUnitProgInputStatus3read-onlycurrentProgrammable input status.
1.3.6.1.4.1.12148.9.1.17.3.1.14ColumnioUnitProgInputText4read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.4
1.3.6.1.4.1.12148.9.1.17.3.1.15ColumnioUnitProgInputStatus4read-onlycurrentProgrammable input status.
1.3.6.1.4.1.12148.9.1.17.3.1.16ColumnioUnitProgInputText5read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.5
1.3.6.1.4.1.12148.9.1.17.3.1.17ColumnioUnitProgInputStatus5read-onlycurrentProgrammable input status.
1.3.6.1.4.1.12148.9.1.17.3.1.18ColumnioUnitProgInputText6read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.6
1.3.6.1.4.1.12148.9.1.17.3.1.19ColumnioUnitProgInputStatus6read-onlycurrentProgrammable input status.
1.3.6.1.4.1.12148.9.1.17.3.1.20ColumnioUnitProgInputValue1read-onlycurrentThe value read on input.
1.3.6.1.4.1.12148.9.1.17.3.1.21ColumnioUnitProgInputValue2read-onlycurrentThe value read on input.
1.3.6.1.4.1.12148.9.1.17.3.1.22ColumnioUnitProgInputValue3read-onlycurrentThe value read on input.
1.3.6.1.4.1.12148.9.1.17.3.1.23ColumnioUnitProgInputValue4read-onlycurrentThe value read on input.
1.3.6.1.4.1.12148.9.1.17.3.1.24ColumnioUnitProgInputValue5read-onlycurrentThe value read on input.
1.3.6.1.4.1.12148.9.1.17.3.1.25ColumnioUnitProgInputValue6read-onlycurrentThe value read on input.
1.3.6.1.4.1.12148.9.1.18ScalarsystemServiceModeread-writedeprecatedThis is a switch function to activate (1) or deactivate (0) servicemode. Status can also be read. Servicemode prevent the system to operate relays or send trap…
1.3.6.1.4.1.12148.9.2NodedcSystem
1.3.6.1.4.1.12148.9.2.1NodedcPlant
1.3.6.1.4.1.12148.9.2.1.3NodesystemSiteInfo
1.3.6.1.4.1.12148.9.2.1.3.1ScalarsystemSiteInfoCustomerread-onlycurrentThe Customer name (as stored in the Control Unit).
1.3.6.1.4.1.12148.9.2.1.3.2ScalarsystemSiteInfoLocationread-onlycurrentThe system/site Location details (as stored in the Control Unit).
1.3.6.1.4.1.12148.9.2.1.3.3ScalarsystemSiteInfoMessage1read-onlycurrentThe system/site Info Message record #1 (as stored in the Control Unit). 31 Bytes.
1.3.6.1.4.1.12148.9.2.1.3.4ScalarsystemSiteInfoMessage2read-onlycurrentThe system/site Info Message record #2 (as stored in the Control Unit). 31 Bytes.
1.3.6.1.4.1.12148.9.2.1.3.5ScalarsystemSiteInfoInstalledDateread-onlycurrentThe system's Installed Date text string (as stored in the Control Unit) 16bytes.
1.3.6.1.4.1.12148.9.2.1.3.6ScalarsystemSiteInfoControllerTyperead-onlycurrentThe system Controller Module currently connected. 0 = AL175 1 = AL4000 (Aeon Gold) 2 = AL6000 3 = AL175OEM 4 = MCU 5 = SmartPack 6 = ComPack
1.3.6.1.4.1.12148.9.2.1.3.7ScalarsystemSiteInfoSystemSeriaNumread-onlycurrentThe serial number for the complete system.
1.3.6.1.4.1.12148.9.2.1.3.8ScalarsystemSiteInfoControllerSeriaNumread-onlycurrentThe serial number for Control unit 1.
1.3.6.1.4.1.12148.9.2.1.4ScalarsystemNominalVoltageread-onlycurrentThe nominal voltage rating. 24V/48V/60V systems. 0=48V 1=24V 2=Not used 3=Not used 4=60V
1.3.6.1.4.1.12148.9.2.2ScalarsystemOperationalStatusread-onlycurrentA summary status showing if the system is testing, boosting, floating etc. 0=Float, voltage regulated 1=Float, temperature comp. regulated; 2=boost 3=battery t…
1.3.6.1.4.1.12148.9.3Nodebattery
1.3.6.1.4.1.12148.9.3.1ScalarbatteryNameread-onlycurrentA descriptive name of the battery installed in the system.
1.3.6.1.4.1.12148.9.3.2ScalarbatteryVoltageread-onlycurrentThe measured battery voltage.
1.3.6.1.4.1.12148.9.3.3ScalarbatteryCurrentread-onlycurrentThe measured total battery current. This is the sum of all the enabled shunt measurements in the system. Negative battery current indicates discharging of the …
1.3.6.1.4.1.12148.9.3.4ScalarbatteryTempread-onlycurrentThe highest value of the enabled battery temperature measurements. Depending on the global setting in the Control unit, this value will be presented in Celsius…
1.3.6.1.4.1.12148.9.3.5ScalarbatteryBreakerStatusread-onlycurrentThe state of the battery fuses/breakers can be either normal(0) or alarm(1).
1.3.6.1.4.1.12148.9.3.6ScalarbatteryChargeCurrentLimitCtrlread-writecurrentEnable/disable of the battery charge current limitation feature; 0=disable, 1=enable.
1.3.6.1.4.1.12148.9.3.7ScalarbatteryChargeCurrentLimitValueread-writecurrentBattery charging current limit value. Used only when AC source is mains feed. Note that the units measured may be i Amperes or in Deciamperes depending on glob…
1.3.6.1.4.1.12148.9.3.8ScalarbatteryTempCompEnableread-writecurrentEnable (0) or Disable (1) of Battery Temperature Compensated output regulation mode
1.3.6.1.4.1.12148.9.3.9ScalarbatteryFloatVoltConfigread-writecurrentThe Voltage at which the DC System float charges. Acts as reference voltage when running temperature compensated charging.
1.3.6.1.4.1.12148.9.3.10ScalarbatteryBoostVoltConfigread-writecurrentThe Voltage at which the DC System boost charges the batteries.
1.3.6.1.4.1.12148.9.3.11ScalarbatteryHighMajorAlarmVoltageConfigread-writecurrentThe Major High Battery Voltage alarm limit set voltage
1.3.6.1.4.1.12148.9.3.12ScalarbatteryHighMinorAlarmVoltageConfigread-writecurrentThe Minor High Battery Voltage alarm limit set voltage
1.3.6.1.4.1.12148.9.3.13ScalarbatteryLowMajorAlarmVoltageConfigread-writecurrentThe Major Low Battery Voltage Alarm limit set voltage
1.3.6.1.4.1.12148.9.3.14ScalarbatteryLowMinorAlarmVoltageConfigread-writecurrentThe Minor Low Battery Voltage Alarm limit set voltage
1.3.6.1.4.1.12148.9.3.15ScalarbatteryStartManualTestread-writecurrentThis pushbutton will start or stop a manual battery test if the system allows it.
1.3.6.1.4.1.12148.9.3.16ScalarbatteryStartManualBoostread-writecurrentThis pushbutton will start or stop a manual battery boost if the system allows it.
1.3.6.1.4.1.12148.9.3.17NodebatteryLVD
1.3.6.1.4.1.12148.9.3.17.1ScalarbatteryLVDStatusread-onlycurrentThe Battery Contactor is connected(0), disconnected(1) or disabled(2)
1.3.6.1.4.1.12148.9.3.17.2ScalarbatteryLVDDisconnectVoltageread-writecurrentThe Battery Contactors Disconnect Voltage
1.3.6.1.4.1.12148.9.3.17.3ScalarbatteryLVDConnectVoltageread-writecurrentThe Battery Contactors Reconnect Voltage
1.3.6.1.4.1.12148.9.3.18ScalarbatteryBanksNumofBanksread-onlycurrentThe number of Control units that is used to measure battery parameters.
1.3.6.1.4.1.12148.9.3.19NodebatteryBanks
1.3.6.1.4.1.12148.9.3.19.1ScalarbatterySymmetryDeltaLimitVoltageread-writecurrentThe allowable deviation of the symmetry voltage from the theoretical. Exceeding this value in either direction (+/-) causes an alarm state.
1.3.6.1.4.1.12148.9.3.19.2ScalarbatteryBanksIndexaccessible-for-notifycurrentIndex used for navigating the rows 1..8 of batteryBanksTable
1.3.6.1.4.1.12148.9.3.19.3TablebatteryBanksTablenot-accessiblecurrentA table of up to 8 battery banks. Each banks may have up to 8 symmetry measuments.
1.3.6.1.4.1.12148.9.3.19.3.1RowbatteryBanksEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.9.3.19.3.1.1ColumnbatteryBankIDread-onlycurrentThe ID of the selected row in the table. i.e. the battery bank.
1.3.6.1.4.1.12148.9.3.19.3.1.2ColumnbatteryBanksSymmetry1enableread-writecurrentEnable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
1.3.6.1.4.1.12148.9.3.19.3.1.3ColumnbatteryBanksSymmetry1statusread-onlycurrentContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.19.3.1.4ColumnbatteryBanksSymmetry1deltaVoltageread-onlycurrentThe difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it wi…
1.3.6.1.4.1.12148.9.3.19.3.1.5ColumnbatteryBanksSymmetry2enableread-writecurrentEnable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
1.3.6.1.4.1.12148.9.3.19.3.1.6ColumnbatteryBanksSymmetry2statusread-onlycurrentContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.19.3.1.7ColumnbatteryBanksSymmetry2deltaVoltageread-onlycurrentThe difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it wi…
1.3.6.1.4.1.12148.9.3.19.3.1.8ColumnbatteryBanksSymmetry3enableread-writecurrentEnable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
1.3.6.1.4.1.12148.9.3.19.3.1.9ColumnbatteryBanksSymmetry3statusread-onlycurrentContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.19.3.1.10ColumnbatteryBanksSymmetry3deltaVoltageread-onlycurrentThe difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it wi…
1.3.6.1.4.1.12148.9.3.19.3.1.11ColumnbatteryBanksSymmetry4enableread-writecurrentEnable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
1.3.6.1.4.1.12148.9.3.19.3.1.12ColumnbatteryBanksSymmetry4statusread-onlycurrentContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.19.3.1.13ColumnbatteryBanksSymmetry4deltaVoltageread-onlycurrentThe difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it wi…
1.3.6.1.4.1.12148.9.3.19.3.1.14ColumnbatteryBanksSymmetry5enableread-writecurrentEnable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
1.3.6.1.4.1.12148.9.3.19.3.1.15ColumnbatteryBanksSymmetry5statusread-onlycurrentContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.19.3.1.16ColumnbatteryBanksSymmetry5deltaVoltageread-onlycurrentThe difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it wi…
1.3.6.1.4.1.12148.9.3.19.3.1.17ColumnbatteryBanksSymmetry6enableread-writecurrentEnable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
1.3.6.1.4.1.12148.9.3.19.3.1.18ColumnbatteryBanksSymmetry6statusread-onlycurrentContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.19.3.1.19ColumnbatteryBanksSymmetry6deltaVoltageread-onlycurrentThe difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it wi…
1.3.6.1.4.1.12148.9.3.19.3.1.20ColumnbatteryBanksSymmetry7enableread-writecurrentEnable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
1.3.6.1.4.1.12148.9.3.19.3.1.21ColumnbatteryBanksSymmetry7statusread-onlycurrentContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.19.3.1.22ColumnbatteryBanksSymmetry7deltaVoltageread-onlycurrentThe difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it wi…
1.3.6.1.4.1.12148.9.3.19.3.1.23ColumnbatteryBanksSymmetry8enableread-writecurrentEnable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
1.3.6.1.4.1.12148.9.3.19.3.1.24ColumnbatteryBanksSymmetry8statusread-onlycurrentContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.19.3.1.25ColumnbatteryBanksSymmetry8deltaVoltageread-onlycurrentThe difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it wi…
1.3.6.1.4.1.12148.9.3.19.4ScalarbatteryBanksNumberOfStringsread-onlycurrentNumber of strings in the power system.
1.3.6.1.4.1.12148.9.3.19.5ScalarbatteryBanksExtensionIndexaccessible-for-notifycurrentIndex used for navigating the rows 1..14 of batteryBanksExtensionTable
1.3.6.1.4.1.12148.9.3.19.6TablebatteryBanksExtensionTablenot-accessiblecurrentThis table shows the measured value on the symmetry inputs.
1.3.6.1.4.1.12148.9.3.19.6.1RowbatteryBanksExtensionEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.9.3.19.6.1.1ColumnbatteryBanksExtensionIDread-onlycurrentThe ID of the selected row in the table. i.e. the battery bank.
1.3.6.1.4.1.12148.9.3.19.6.1.2ColumnbatteryBanksExtensionSymmetryInputValue1read-onlycurrentThe measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.19.6.1.3ColumnbatteryBanksExtensionSymmetryInputValue2read-onlycurrentThe measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.19.6.1.4ColumnbatteryBanksExtensionSymmetryInputValue3read-onlycurrentThe measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.19.6.1.5ColumnbatteryBanksExtensionSymmetryInputValue4read-onlycurrentThe measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.19.6.1.6ColumnbatteryBanksExtensionSymmetryInputValue5read-onlycurrentThe measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.19.6.1.7ColumnbatteryBanksExtensionSymmetryInputValue6read-onlycurrentThe measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.19.6.1.8ColumnbatteryBanksExtensionSymmetryInputValue7read-onlycurrentThe measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.19.6.1.9ColumnbatteryBanksExtensionSymmetryInputValue8read-onlycurrentThe measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.20NodebatteryCapacityData
1.3.6.1.4.1.12148.9.3.20.1ScalarbatteryTimeToDisconnectread-onlycurrentRemaining time to low voltage battery disconnect.
1.3.6.1.4.1.12148.9.3.20.2ScalarbatteryCapacityLeftread-onlycurrentCapacity left in the battery.
1.3.6.1.4.1.12148.9.3.20.3ScalarbatteryCapacityUsedread-onlycurrentCapacity consumed.
1.3.6.1.4.1.12148.9.3.20.4ScalarbatteryCapacityTotalread-onlycurrentThis is the total Capacity of the battery. This value is the installed capacity compensated with the last battery tests quality level
1.3.6.1.4.1.12148.9.3.20.5ScalarbatteryQualityread-onlycurrentThis is the battery quality (%) of the latest battery test.
1.3.6.1.4.1.12148.9.3.21NodebatteryMonitorUnits
1.3.6.1.4.1.12148.9.3.21.1ScalarbattmonNumberOfUnitsread-onlycurrentNumber of battery monitor units in the power system.
1.3.6.1.4.1.12148.9.3.21.2ScalarbattmonUnitsIndexaccessible-for-notifycurrentIndex used for navigating the rows 1..14 of battmonUnitsTable
1.3.6.1.4.1.12148.9.3.21.3TablebattmonUnitsTablenot-accessiblecurrentA table of up to 14 battery monitor control units.
1.3.6.1.4.1.12148.9.3.21.3.1RowbattmonUnitsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.9.3.21.3.1.1ColumnbatteryMonitorIDread-onlycurrentThe ID of the selected row
1.3.6.1.4.1.12148.9.3.21.3.1.2ColumnbatteryMonitorSymmetry1statusread-onlycurrentContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.21.3.1.3ColumnbatteryMonitorSymmetry1InputValueread-onlycurrentThe measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.21.3.1.4ColumnbatteryMonitorSymmetry2statusread-onlycurrentContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.21.3.1.5ColumnbatteryMonitorSymmetry2InputValueread-onlycurrentThe measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.21.3.1.6ColumnbatteryMonitorSymmetry3statusread-onlycurrentContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.21.3.1.7ColumnbatteryMonitorSymmetry3InputValueread-onlycurrentThe measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.21.3.1.8ColumnbatteryMonitorSymmetry4statusread-onlycurrentContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.21.3.1.9ColumnbatteryMonitorSymmetry4InputValueread-onlycurrentThe measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.21.3.1.10ColumnbatteryMonitorCurrentValueread-onlycurrentThe measured current to/from the battery. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.9.3.21.3.1.11ColumnbatteryMonitorFuseStatusread-onlycurrentThe state of the battery fuse/breaker can be either normal(0) or alarm(1).
1.3.6.1.4.1.12148.9.3.21.3.1.12ColumnbatteryMonitorTemperatureread-onlycurrentThe battery temperature.
1.3.6.1.4.1.12148.9.3.22ScalarbatteryHighMajorTempAlarmLevelread-writecurrentThis is the Major High Temperature Alarm level.
1.3.6.1.4.1.12148.9.3.23ScalarbatteryHighMinorTempAlarmLevelread-writecurrentThis is the Minor High Temperature Alarm level.
1.3.6.1.4.1.12148.9.4NodeloadDistribution
1.3.6.1.4.1.12148.9.4.1ScalarloadDistributionCurrentread-onlycurrentThe total load current Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.9.4.2ScalarloadDistributionBreakerStatusread-onlycurrentThe state of the load fuses/breakers can be either normal(0) or alarm(1)
1.3.6.1.4.1.12148.9.4.3NodeloadDistributionLVDStatus
1.3.6.1.4.1.12148.9.4.3.1ScalarloadLVD1Enableread-onlycurrentThe status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use.
1.3.6.1.4.1.12148.9.4.3.2ScalarloadLVD1Statusread-onlycurrentThe load Contactor 1 is connected(0), disconnected(1) or disabled(2)
1.3.6.1.4.1.12148.9.4.3.3ScalarloadLVD1ConnectVoltageread-writecurrentLVLD1 Connect Voltage
1.3.6.1.4.1.12148.9.4.3.4ScalarloadLVD1DisconnectVoltageread-writecurrentLVLD1 Disconnect Voltage
1.3.6.1.4.1.12148.9.4.3.5ScalarloadLVD2Enableread-onlycurrentThe status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use.
1.3.6.1.4.1.12148.9.4.3.6ScalarloadLVD2Statusread-onlycurrentThe load Contactor 2 is connected(0), disconnected(1) or disabled(2)
1.3.6.1.4.1.12148.9.4.3.7ScalarloadLVD2ConnectVoltageread-writecurrentLVLD2 Connect Voltage
1.3.6.1.4.1.12148.9.4.3.8ScalarloadLVD2DisconnectVoltageread-writecurrentLVLD2 Disconnect Voltage
1.3.6.1.4.1.12148.9.4.3.9ScalarloadLVD3Enableread-onlycurrentThe status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use.
1.3.6.1.4.1.12148.9.4.3.10ScalarloadLVD3Statusread-onlycurrentThe load Contactor 3 is connected(0), disconnected(1) or disabled(2)
1.3.6.1.4.1.12148.9.4.3.11ScalarloadLVD3ConnectVoltageread-writecurrentLVLD3 Connect Voltage
1.3.6.1.4.1.12148.9.4.3.12ScalarloadLVD3DisconnectVoltageread-writecurrentLVLD3 Disconnect Voltage
1.3.6.1.4.1.12148.9.4.4NodeloadMonitorUnits
1.3.6.1.4.1.12148.9.4.4.1ScalarloadmonitorNumberOfUnitsread-onlycurrent
1.3.6.1.4.1.12148.9.4.4.2ScalarloadMonitorUnitsIndexaccessible-for-notifycurrent
1.3.6.1.4.1.12148.9.4.4.3TableloadMonitorUnitsTablenot-accessiblecurrent
1.3.6.1.4.1.12148.9.4.4.3.1RowloadMonitorUnitsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.9.4.4.3.1.1ColumnloadMonitorIDread-onlycurrent
1.3.6.1.4.1.12148.9.4.4.3.1.2ColumnloadMonitorFuseStatus1read-onlycurrentThe state of the load fuses/breakers can be either normal(0) or alarm(1)
1.3.6.1.4.1.12148.9.4.4.3.1.3ColumnloadMonitorCurrent1read-onlycurrentThe current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.9.4.4.3.1.4ColumnloadMonitorFuseStatus2read-onlycurrentThe state of the load fuses/breakers can be either normal(0) or alarm(1)
1.3.6.1.4.1.12148.9.4.4.3.1.5ColumnloadMonitorCurrent2read-onlycurrentThe current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.9.4.4.3.1.6ColumnloadMonitorFuseStatus3read-onlycurrentThe state of the load fuses/breakers can be either normal(0) or alarm(1)
1.3.6.1.4.1.12148.9.4.4.3.1.7ColumnloadMonitorCurrent3read-onlycurrentThe current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.9.4.4.3.1.8ColumnloadMonitorFuseStatus4read-onlycurrentThe state of the load fuses/breakers can be either normal(0) or alarm(1)
1.3.6.1.4.1.12148.9.4.4.3.1.9ColumnloadMonitorCurrent4read-onlycurrentThe current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.9.4.4.3.1.10ColumnloadMonitorFuseStatus5read-onlycurrentThe state of the load fuses/breakers can be either normal(0) or alarm(1)
1.3.6.1.4.1.12148.9.4.4.3.1.11ColumnloadMonitorCurrent5read-onlycurrentThe current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.9.4.4.3.1.12ColumnloadMonitorFuseStatus6read-onlycurrentThe state of the load fuses/breakers can be either normal(0) or alarm(1)
1.3.6.1.4.1.12148.9.4.4.3.1.13ColumnloadMonitorCurrent6read-onlycurrentThe current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.9.4.4.3.1.14ColumnloadMonitorFuseStatus7read-onlycurrentThe state of the load fuses/breakers can be either normal(0) or alarm(1)
1.3.6.1.4.1.12148.9.4.4.3.1.15ColumnloadMonitorCurrent7read-onlycurrentThe current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.9.4.4.3.1.16ColumnloadMonitorFuseStatus8read-onlycurrentThe state of the load fuses/breakers can be either normal(0) or alarm(1)
1.3.6.1.4.1.12148.9.4.4.3.1.17ColumnloadMonitorCurrent8read-onlycurrentThe current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.9.5Noderectifier
1.3.6.1.4.1.12148.9.5.1ScalarrectifierInstalledRectifiersread-onlycurrentThe number of installed rectifiers for this DC Power System.
1.3.6.1.4.1.12148.9.5.2ScalarrectifierRectifiersActiveread-onlycurrentNot Used!
1.3.6.1.4.1.12148.9.5.3ScalarrectifierTotalCurrentread-onlycurrentThe DC system's total delivered rectifier current
1.3.6.1.4.1.12148.9.5.4ScalarrectifierUtilizationread-onlycurrentUtilization in % of available rectifier capacity
1.3.6.1.4.1.12148.9.5.5NoderectifierStatus
1.3.6.1.4.1.12148.9.5.5.1ScalarrectifierStatusNoIndexread-writecurrentAn offset for the rectifierStatusTable array. The rectifier status table has a fixed number of 20 rows. This OID sets the offset for the rectifier in the first…
1.3.6.1.4.1.12148.9.5.5.2TablerectifierStatusTablenot-accessiblecurrentA table listing up to 20 recifiers, starting from the rectifier number specified by rectifierStatusNoIndex
1.3.6.1.4.1.12148.9.5.5.2.1RowrectifierStatusEntrynot-accessiblecurrentA row of rectifier status data corresponding to the rectifierStatusNoIndex value
1.3.6.1.4.1.12148.9.5.5.2.1.1ColumnrectifierStatusIDread-onlycurrentThe rectifier ID number of the rectifier.
1.3.6.1.4.1.12148.9.5.5.2.1.2ColumnrectifierStatusStatusread-onlycurrentThe operational status of the rectifier record. Not Present (0), normal (1), alarm (2), notUsed (3), disabled (4)
1.3.6.1.4.1.12148.9.5.5.2.1.3ColumnrectifierStatusOutputCurrentread-onlycurrentThe output current of the rectifier.
1.3.6.1.4.1.12148.9.5.5.2.1.4ColumnrectifierStatusOutputVoltageread-onlycurrentThe rectifier voltage of the rectifier record.
1.3.6.1.4.1.12148.9.5.5.2.1.5ColumnrectifierStatusTempread-onlycurrentThe input air temperature of the rectifier.
1.3.6.1.4.1.12148.9.5.5.2.1.6ColumnrectifierStatusTyperead-onlycurrentThe rectifier article number string of the rectifier record.
1.3.6.1.4.1.12148.9.5.5.2.1.7ColumnrectifierStatusSKUread-onlycurrentThe rectifier part number.
1.3.6.1.4.1.12148.9.5.5.2.1.8ColumnrectifierStatusSerialNoread-onlycurrentThe rectifier serial number string of the rectifier record.
1.3.6.1.4.1.12148.9.5.5.2.1.9ColumnrectifierStatusRevisionLevelread-onlycurrentThe rectifier HW revision number string of the rectifier record.
1.3.6.1.4.1.12148.9.6NodeacDistribution
1.3.6.1.4.1.12148.9.6.1ScalaracVoltage1read-onlycurrentThe AC Voltage of phase 1
1.3.6.1.4.1.12148.9.6.2ScalaracVoltage2read-onlycurrentThe AC Voltage of phase 2
1.3.6.1.4.1.12148.9.6.3ScalaracVoltage3read-onlycurrentThe AC Voltage of phase 3
1.3.6.1.4.1.12148.9.7NodealarmGroup
1.3.6.1.4.1.12148.9.7.1NodealarmWellknownAlarms
1.3.6.1.4.1.12148.9.7.1.1ScalaralarmMajorHighBattVoltread-onlycurrentThe Major High Battery Voltage Alarm
1.3.6.1.4.1.12148.9.7.1.2ScalaralarmMinorHighBattVoltread-onlycurrentThe Minor High Battery Voltage alarm
1.3.6.1.4.1.12148.9.7.1.3ScalaralarmMajorLowBattVoltread-onlycurrentThe Major Low Battery Voltage Alarm
1.3.6.1.4.1.12148.9.7.1.4ScalaralarmMinorLowBattVoltread-onlycurrentThe Minor Low Battery Voltage Alarm
1.3.6.1.4.1.12148.9.7.1.5ScalaralarmMajorBatteryHighTempread-onlycurrentThe Major High Battery Temperature alarm.
1.3.6.1.4.1.12148.9.7.1.6ScalaralarmMinorBatteryHighTempread-onlycurrentThe Minor High Battery Temperature alarm.
1.3.6.1.4.1.12148.9.7.1.7ScalaralarmBatteryDisconnectOpenread-onlycurrentThe Battery Disconnect Contactor alarm
1.3.6.1.4.1.12148.9.7.1.8ScalaralarmLVD1openread-onlycurrentThe load Contactor 1 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
1.3.6.1.4.1.12148.9.7.1.9ScalaralarmLVD2openread-onlycurrentThe load Contactor 2 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
1.3.6.1.4.1.12148.9.7.1.10ScalaralarmLVD3openread-onlycurrentThe load Contactor 3 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
1.3.6.1.4.1.12148.9.7.1.11ScalaralarmACmainsread-onlycurrentThe AC voltage has dropped below critical level, or one or more AC input phases was lost.
1.3.6.1.4.1.12148.9.7.1.12ScalaralarmBatteryBreakerOpenread-onlycurrentA battery breaker/fuse alarm.
1.3.6.1.4.1.12148.9.7.1.13ScalaralarmDistributionBreakerOpenread-onlycurrentA Load Distribution breaker/fuse alarm.
1.3.6.1.4.1.12148.9.7.1.14ScalaralarmMajorRectifierread-onlycurrentThis is a Major Rectifier alarm.
1.3.6.1.4.1.12148.9.7.1.15ScalaralarmMinorRectifierread-onlycurrentThis is a Minor Rectifier alarm.
1.3.6.1.4.1.12148.9.7.1.16ScalaralarmMajorBatterySymmetryread-onlycurrentBattery Symmetry Delta Voltage Major alarm.
1.3.6.1.4.1.12148.9.7.1.17ScalaralarmMinorBatterySymmetryread-onlycurrentBattery Symmetry Delta Voltage Minor alarm
1.3.6.1.4.1.12148.9.7.1.18ScalaralarmBatteryLifeEndedread-onlycurrentThe battery quality has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifec…
1.3.6.1.4.1.12148.9.7.1.19ScalaralarmBatteryTestmodeEnteredread-onlycurrentThe system has lowered the battery charge voltage in order to discharge the batteries to a predefined level. When the criteria for stopping the battery testing…
1.3.6.1.4.1.12148.9.7.1.20ScalaralarmBatteryBoostmodeEnteredread-onlycurrentThe system has increased the battery charge voltage in order to boost the battery. When the criteria for stopping the battery boost is reached, the charge volt…
1.3.6.1.4.1.12148.9.7.1.21ScalaralarmIoUnitTemp1read-onlycurrentHigh or low temperature alarm 1 from any of the IO units.
1.3.6.1.4.1.12148.9.7.1.22ScalaralarmIoUnitTemp2read-onlycurrentHigh or low temperature alarm 2 from any of the IO units.
1.3.6.1.4.1.12148.9.7.1.23ScalaralarmIoUnitDeltaFanSpeed1read-onlycurrentDelta fan speed 1 from any of the IO units.
1.3.6.1.4.1.12148.9.7.1.24ScalaralarmIoUnitDeltaFanSpeed2read-onlycurrentDelta fan speed 2 from any of the IO units.
1.3.6.1.4.1.12148.9.7.1.25ScalaralarmMajorSolarread-onlycurrentThis is a Major Solar alarm.
1.3.6.1.4.1.12148.9.7.1.26ScalaralarmMinorSolarread-onlycurrentThis is a Major Solar alarm.
1.3.6.1.4.1.12148.9.7.1.27ScalaralarmMajorRectifierCapacityread-onlycurrentThis is a Major Rectifier Capacity alarm.
1.3.6.1.4.1.12148.9.7.1.28ScalaralarmMinorRectifierCapacityread-onlycurrentThis is a Minor Rectifier Capacity alarm.
1.3.6.1.4.1.12148.9.8GroupdcSystemTrapscurrentThis branch contains the Alarm Notification Traps, which duplicate the alarmGroup OIDs. Each alarm condition is represented by a Alarm Condition Trap and an as…
1.3.6.1.4.1.12148.9.8.1NotificationalarmMajorHighBattVoltTrapcurrentThe Major High Battery Voltage alarm
1.3.6.1.4.1.12148.9.8.2NotificationalarmMinorHighBattVoltTrapcurrentThe Minor High Battery Voltage alarm
1.3.6.1.4.1.12148.9.8.3NotificationalarmMajorLowBattVoltTrapcurrentThe Major Low Battery Voltage Alarm
1.3.6.1.4.1.12148.9.8.4NotificationalarmMinorLowBattVoltTrapcurrentThe Minor Low Battery Voltage Alarm
1.3.6.1.4.1.12148.9.8.5NotificationalarmMajorBatteryHighTempTrapcurrentThe Major High Battery Temperature alarm.
1.3.6.1.4.1.12148.9.8.6NotificationalarmMinorBatteryHighTempTrapcurrentThe Minor High Battery Temperature alarm.
1.3.6.1.4.1.12148.9.8.7NotificationalarmBatteryDisconnectOpenTrapcurrentThe Battery Disconnect Contactor alarm
1.3.6.1.4.1.12148.9.8.8NotificationalarmLVD1openTrapcurrentThe load Contactor 1 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
1.3.6.1.4.1.12148.9.8.9NotificationalarmLVD2openTrapcurrentThe load Contactor 2 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
1.3.6.1.4.1.12148.9.8.10NotificationalarmLVD3openTrapcurrentThe load Contactor 3 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
1.3.6.1.4.1.12148.9.8.11NotificationalarmACmainsTrapcurrentThe AC voltage has dropped below critical level, or one or more AC input phases was lost.
1.3.6.1.4.1.12148.9.8.12NotificationalarmBatteryBreakerOpenTrapcurrentA battery breaker/fuse alarm.
1.3.6.1.4.1.12148.9.8.13NotificationalarmDistributionBreakerOpenTrapcurrentA Load Distribution breaker/fuse alarm.
1.3.6.1.4.1.12148.9.8.14NotificationalarmMajorRectifierTrapcurrentThis is a Major Rectifier alarm.
1.3.6.1.4.1.12148.9.8.15NotificationalarmMinorRectifierTrapcurrentThis is a Minor Rectifier alarm.
1.3.6.1.4.1.12148.9.8.16NotificationalarmMajorBatterySymmetryTrapcurrentBattery Symmetry Delta Voltage Major alarm
1.3.6.1.4.1.12148.9.8.17NotificationalarmMinorBatterySymmetryTrapcurrentBattery Symmetry Delta Voltage Minor alarm
1.3.6.1.4.1.12148.9.8.18NotificationalarmBatteryLifeEndedTrapcurrentThe battery quality has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifec…
1.3.6.1.4.1.12148.9.8.19NotificationalarmBatteryTestmodeEnteredTrapcurrentThe system has lowered the battery charge voltage in order to discharge the batteries to a predefined level. When the criteria for stopping the battery testing…
1.3.6.1.4.1.12148.9.8.20NotificationalarmBatteryBoostmodeEnteredTrapcurrentThe system has increased the battery charge voltage in order to boost the battery. When the criteria for stopping the battery boost is reached, the charge volt…
1.3.6.1.4.1.12148.9.8.21NotificationalarmController1proginputTrapcurrentProgrammable input alarm for Control unit 1. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInpu…
1.3.6.1.4.1.12148.9.8.22NotificationalarmController2proginputTrapcurrentProgrammable input alarm for Control unit 2. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInpu…
1.3.6.1.4.1.12148.9.8.23NotificationalarmController3proginputTrapcurrentProgrammable input alarm for Control unit 3. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInpu…
1.3.6.1.4.1.12148.9.8.24NotificationalarmController4proginputTrapcurrentProgrammable input alarm for Control unit 4. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInpu…
1.3.6.1.4.1.12148.9.8.25NotificationalarmController5proginputTrapcurrentProgrammable input alarm for Control unit 5. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInpu…
1.3.6.1.4.1.12148.9.8.26NotificationalarmController6proginputTrapcurrentProgrammable input alarm for Control unit 6. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInpu…
1.3.6.1.4.1.12148.9.8.27NotificationalarmController7proginputTrapcurrentProgrammable input alarm for Control unit 7. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInpu…
1.3.6.1.4.1.12148.9.8.28NotificationalarmController8proginputTrapcurrentProgrammable input alarm for Control unit 8. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInpu…
1.3.6.1.4.1.12148.9.8.29NotificationinfoHeartBeatTrapcurrentWhen enabled, this trap will be transmitted at regular inervals. This trap is not intended to be an alarm but more like some information that the system is ali…
1.3.6.1.4.1.12148.9.8.30NotificationalarmIoUnitTemp1TrapcurrentHigh or low temperature alarm 1 from any of the IO units.
1.3.6.1.4.1.12148.9.8.31NotificationalarmIoUnitTemp2TrapcurrentHigh or low temperature alarm 2 from any of the IO units.
1.3.6.1.4.1.12148.9.8.32NotificationalarmIoUnitDeltaFanSpeed1TrapcurrentDelta fan speed 1 from any of the IO units. Occurs if the fan speed deviation is above/below the configured level.
1.3.6.1.4.1.12148.9.8.33NotificationalarmIoUnitDeltaFanSpeed2TrapcurrentDelta fan speed 2 from any of the IO units. Occurs if the fan speed deviation is above/below the configured level.
1.3.6.1.4.1.12148.9.8.34NotificationalarmIoUnit1proginputTrapcurrentProgrammable input alarm for IO Unit 1. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO…
1.3.6.1.4.1.12148.9.8.35NotificationalarmIoUnit2proginputTrapcurrentProgrammable input alarm for IO Unit 2. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO…
1.3.6.1.4.1.12148.9.8.36NotificationalarmIoUnit3proginputTrapcurrentProgrammable input alarm for IO Unit 3. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO…
1.3.6.1.4.1.12148.9.8.37NotificationalarmIoUnit4proginputTrapcurrentProgrammable input alarm for IO Unit 4. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO…
1.3.6.1.4.1.12148.9.8.38NotificationalarmIoUnit5proginputTrapcurrentProgrammable input alarm for IO Unit 5. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO…
1.3.6.1.4.1.12148.9.8.39NotificationalarmIoUnit6proginputTrapcurrentProgrammable input alarm for IO Unit 6. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO…
1.3.6.1.4.1.12148.9.8.40NotificationalarmIoUnit7proginputTrapcurrentProgrammable input alarm for IO Unit 7. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO…
1.3.6.1.4.1.12148.9.8.41NotificationalarmIoUnit8proginputTrapcurrentProgrammable input alarm for IO Unit 8. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO…
1.3.6.1.4.1.12148.9.8.42NotificationalarmIoUnit9proginputTrapcurrentProgrammable input alarm for IO Unit 9. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO…
1.3.6.1.4.1.12148.9.8.43NotificationalarmIoUnit10proginputTrapcurrentProgrammable input alarm for IO Unit 10. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I…
1.3.6.1.4.1.12148.9.8.44NotificationalarmIoUnit11proginputTrapcurrentProgrammable input alarm for IO Unit 11. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I…
1.3.6.1.4.1.12148.9.8.45NotificationalarmIoUnit12proginputTrapcurrentProgrammable input alarm for IO Unit 12. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I…
1.3.6.1.4.1.12148.9.8.46NotificationalarmIoUnit13proginputTrapcurrentProgrammable input alarm for IO Unit 13. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I…
1.3.6.1.4.1.12148.9.8.47NotificationalarmIoUnit14proginputTrapcurrentProgrammable input alarm for IO Unit 14. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I…
1.3.6.1.4.1.12148.9.8.48NotificationalarmMajorSolarChargerTrapcurrentThe Major Solar Charger alarm
1.3.6.1.4.1.12148.9.8.49NotificationalarmMinorSolarChargerTrapcurrentThe Minor Solar Charger alarm
1.3.6.1.4.1.12148.9.8.50NotificationalarmMajorRectifierCapacityTrapcurrentThe Major Rectifier Capacity alarm
1.3.6.1.4.1.12148.9.8.51NotificationalarmMinorRectifierCapacityTrapcurrentThe Minor Rectifier Capacity alarm
1.3.6.1.4.1.12148.9.9NodesolarCharger
1.3.6.1.4.1.12148.9.9.1ScalarsolarChargerInstalledsolarChargersread-onlycurrentThe number of installed solar chargers for this DC Power System.
1.3.6.1.4.1.12148.9.9.2ScalarsolarChargersActiveread-onlycurrentNot Used!
1.3.6.1.4.1.12148.9.9.3ScalarsolarChargerTotalCurrentread-onlycurrentThe DC system's total delivered solar current
1.3.6.1.4.1.12148.9.9.4ScalarsolarChargerUtilizationread-onlycurrentUtilization in % of available solar capacity
1.3.6.1.4.1.12148.9.9.5NodesolarChargerStatus
1.3.6.1.4.1.12148.9.9.5.1ScalarsolarChargerStatusNoIndexread-writecurrentAn offset for the solarStatusTable array. The solar status table has a fixed number of 20 rows. This OID sets the offset for the solarcharger in the first row …
1.3.6.1.4.1.12148.9.9.5.2TablesolarChargerStatusTablenot-accessiblecurrentA table listing up to 20 solarchargers, starting from the solarcharger number specified by solarStatusNoIndex
1.3.6.1.4.1.12148.9.9.5.2.1RowsolarChargerStatusEntrynot-accessiblecurrentA row of rectifier status data corresponding to the rectifierStatusNoIndex value
1.3.6.1.4.1.12148.9.9.5.2.1.1ColumnsolarChargerStatusIDread-onlycurrentThe ID number of the solarcharger.
1.3.6.1.4.1.12148.9.9.5.2.1.2ColumnsolarChargerStatusStatusread-onlycurrentThe operational status of the solarcharger record. Not Present (0), normal (1), alarm (2), notUsed (3), disabled (4)
1.3.6.1.4.1.12148.9.9.5.2.1.3ColumnsolarChargerOutputCurrentread-onlycurrentThe output current of the solarcharger.
1.3.6.1.4.1.12148.9.9.5.2.1.4ColumnsolarChargerOutputVoltageread-onlycurrentThe output voltage of the solarcharger.
1.3.6.1.4.1.12148.9.9.5.2.1.5ColumnsolarChargerTempread-onlycurrentThe input air temperature of the solarcharger.
1.3.6.1.4.1.12148.9.9.5.2.1.6ColumnsolarChargerTyperead-onlycurrentThe article number string of the solarcharger.
1.3.6.1.4.1.12148.9.9.5.2.1.7ColumnsolarChargerSKUread-onlycurrentThe solarcharger part number.
1.3.6.1.4.1.12148.9.9.5.2.1.8ColumnsolarChargerSerialNoread-onlycurrentThe serial number string of the solarcharger.
1.3.6.1.4.1.12148.9.9.5.2.1.9ColumnsolarChargerRevisionLevelread-onlycurrentThe HW revision number string of the solarcharger.