MIB Viewer

ELTEK_GENERIC-MIB

162 objects
No module-level DESCRIPTION found.
Imported Objects
ELTEK-COMMON-MIBeltek
SNMPv2-CONFNOTIFICATION-GROUP
SNMPv2-SMIenterprises Integer32 mib-2 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE
SNMPv2-TCDisplayString
OIDNameAccessStatusDescription
1.3.6.1.4.1.12148.7NodeeltekPlant
1.3.6.1.4.1.12148.7.1NodecontrolSystem
1.3.6.1.4.1.12148.7.1.1NodesystemTime
1.3.6.1.4.1.12148.7.1.1.1ScalarsystemTimeTimeread-onlycurrentThe system date and time. Used for event timestamps and logging
1.3.6.1.4.1.12148.7.1.2ScalarsystemInfoRefreshread-writecurrentThis object will re-initialize the agent, updating MIB data values.
1.3.6.1.4.1.12148.7.1.3ScalarsystemTrapRepeatRateread-writecurrentThis object sets the repeat rate of any active traps, in seconds. Entering 0 (zero) will prevent repeating traps - one trap only will be sent per alarm event.
1.3.6.1.4.1.12148.7.1.4ScalarsystemSendOffTrapread-writecurrentA separate off-trap will be issued when an alarm condition goes off, if this flag is set to 1. Entering 0 (zero) will prevent OFF traps from being transmitted.
1.3.6.1.4.1.12148.7.2NodedcSystem
1.3.6.1.4.1.12148.7.2.1NodedcPlant
1.3.6.1.4.1.12148.7.2.1.3NodesystemSiteInfo
1.3.6.1.4.1.12148.7.2.1.3.1ScalarsystemSiteInfoCustomerread-onlycurrentThe Customer name (as stored in the Smartpack Control Unit)
1.3.6.1.4.1.12148.7.2.1.3.2ScalarsystemSiteInfoLocationread-onlycurrentThe system/site Location details (as stored in the Smartpack Control Unit).
1.3.6.1.4.1.12148.7.2.1.3.3ScalarsystemSiteInfoMessage1read-onlycurrentThe system/site Info Message record #1 (as stored in the Smartpack Control Unit). 31 Bytes.
1.3.6.1.4.1.12148.7.2.1.3.4ScalarsystemSiteInfoMessage2read-onlycurrentThe system/site Info Message record #2 (as stored in the Smartpack Control Unit). 31 Bytes.
1.3.6.1.4.1.12148.7.2.1.3.5ScalarsystemSiteInfoInstalledDateread-onlycurrentThe system's Installed Date text string (as stored in the Smartpack Control Unit) 16bytes.
1.3.6.1.4.1.12148.7.2.1.3.6ScalarsystemSiteInfoControllerTyperead-onlycurrentThe system Controller Module currently connected. AL175/MCU=0; AEON Gold=1; AL6000=2; Smartpack=3
1.3.6.1.4.1.12148.7.2.1.3.7ScalarsystemSiteInfoSystemSeriaNumread-onlycurrentThe serial number for the complete system
1.3.6.1.4.1.12148.7.2.1.3.8ScalarsystemSiteInfoControllerSeriaNumread-onlycurrentThe serial number for the system controller
1.3.6.1.4.1.12148.7.2.1.4ScalarsystemNominalVoltageread-onlycurrentThe nominal voltage rating. 12V/24V/48V/60V systems 0=48V 1=24V 2=12V 3=26V 4=60V
1.3.6.1.4.1.12148.7.2.2ScalarsystemOperationalStatusread-onlycurrentA summary status showing if the system is testing, boosting, floating etc. 0=Float, voltage regulated 1=Float, temperature comp. regulated; 2=equalize 3=batter…
1.3.6.1.4.1.12148.7.3Nodebattery
1.3.6.1.4.1.12148.7.3.1ScalarbatteryNameread-onlycurrentA descriptive name of the battery installed in the system
1.3.6.1.4.1.12148.7.3.2ScalarbatteryVoltageread-onlycurrentThe measured battery voltage.
1.3.6.1.4.1.12148.7.3.3ScalarbatteryCurrentread-onlycurrentThe measured battery current.
1.3.6.1.4.1.12148.7.3.4ScalarbatteryTempread-onlycurrentThe battery temperature
1.3.6.1.4.1.12148.7.3.5ScalarbatteryBreakerStatusread-onlycurrentThe state of the battery fuse/breaker can be either closed(0) or open(1)
1.3.6.1.4.1.12148.7.3.6ScalarbatteryChargeCurrentLimitCtrlread-writecurrentControl field for the battery charge limitation feature; 0=inactive, 1=active.
1.3.6.1.4.1.12148.7.3.7ScalarbatteryChargeCurrentLimitValueread-writecurrentBattery charging current limit value
1.3.6.1.4.1.12148.7.3.8ScalarbatteryTempCompEnableread-writecurrentEnable (0) or Disable (1) Battery Temperature Compensated output regulation mode
1.3.6.1.4.1.12148.7.3.9ScalarbatteryFloatVoltConfigread-writecurrentThe Voltage at which the DC System float charges.
1.3.6.1.4.1.12148.7.3.10ScalarbatteryEqualizeVoltConfigread-writecurrentThe Voltage at which the DC System boost charges the batteries.
1.3.6.1.4.1.12148.7.3.11ScalarbatteryHighMajorAlarmVoltageConfigread-writecurrentThe High Battery Voltage alarm limit set voltage
1.3.6.1.4.1.12148.7.3.12ScalarbatteryHighMinorAlarmVoltageConfigread-writecurrentThe High Battery Voltage alarm limit set voltage
1.3.6.1.4.1.12148.7.3.13ScalarbatteryLowMajorAlarmVoltageConfigread-writecurrentThe Low Battery Voltage Alarm limit set voltage
1.3.6.1.4.1.12148.7.3.14ScalarbatteryLowMinorAlarmVoltageConfigread-writecurrentThe Very Low Battery Voltage Alarm limit set voltage
1.3.6.1.4.1.12148.7.3.15ScalarbatteryStartManualTestread-writecurrentThis pushbutton will start a manual battery test if otherwise the system allows it.
1.3.6.1.4.1.12148.7.3.16ScalarbatteryStartManualBoostread-writecurrentThis pushbutton will start a manual battery boost if otherwise the system allows it.
1.3.6.1.4.1.12148.7.3.17NodebatteryLVD
1.3.6.1.4.1.12148.7.3.17.1ScalarbatteryLVDStatusread-onlycurrentContactor is closed(0) or open(1)
1.3.6.1.4.1.12148.7.3.17.2ScalarbatteryLVDDisconnectVoltageread-writecurrentThe Contactor Disconnect Voltage
1.3.6.1.4.1.12148.7.3.17.3ScalarbatteryLVDConnectVoltageread-writecurrentThe Contactor Reconnect Voltage
1.3.6.1.4.1.12148.7.3.18NodebatteryMidpoint
1.3.6.1.4.1.12148.7.3.18.1ScalarbatteryMidpointDeltaLimitVoltageread-writecurrentThe allowable deviation of the midpoint battery voltage from the theoretical. Exceeding this value in either direction (+/-) causes an alarm state
1.3.6.1.4.1.12148.7.3.18.2ScalarbatteryMidpointIndexread-onlycurrentAn index of Battery Strings, for the batteryMidpointControlTable and batteryMidpointStatusTable arrays
1.3.6.1.4.1.12148.7.3.18.3TablebatteryMidpointControlTablenot-accessiblecurrentA table of settings related to Battery Symmetry (midpoint) Monitoring
1.3.6.1.4.1.12148.7.3.18.3.1RowbatteryMidpointControlEntrynot-accessiblecurrentSettings related to Battery Symmetry (midpoint) Monitoring, corresponding to the batteryMidpointIndex value
1.3.6.1.4.1.12148.7.3.18.3.1.1ColumnmidpointEnableIDread-onlycurrentThe rectifier ID number of the rectifier record.
1.3.6.1.4.1.12148.7.3.18.3.1.2ColumnmidpointEnableread-writecurrentEnable (1) or Disable (0) the Battery Monitor channel which corresponds to the batteryMidpointIndex value
1.3.6.1.4.1.12148.7.3.18.4TablebatteryMidpointStatusTablenot-accessiblecurrentA table of values and/or measurements related to Battery Symmetry (midpoint) Monitoring
1.3.6.1.4.1.12148.7.3.18.4.1RowbatteryMidpointStatusEntrynot-accessiblecurrentValues related to Battery Symmetry (midpoint) Monitoring, corresponding to the batteryMidpointIndex value
1.3.6.1.4.1.12148.7.3.18.4.1.1ColumnmidpointStatusIDread-onlycurrentThe rectifier ID number of the rectifier record.
1.3.6.1.4.1.12148.7.3.18.4.1.2ColumnmidpointStatusread-onlycurrentStatus (0=Normal; 1=Alarm) of the Battery Monitor channel which corresponds to the batteryMidpointIndex value
1.3.6.1.4.1.12148.7.3.18.4.1.3ColumnmidpointDeltaVoltageread-onlycurrentThe measured battery voltage deviation from midpoint of the Battery Monitor channel which corresponds to the batteryMidpointIndex value.
1.3.6.1.4.1.12148.7.4NodeloadDistribution
1.3.6.1.4.1.12148.7.4.1ScalarloadDistributionCurrentread-onlycurrentThe total load current
1.3.6.1.4.1.12148.7.4.2ScalarloadDistributionBreakerStatusread-onlycurrentThe state of the load fuse/breaker can be either closed(0) or open(1)
1.3.6.1.4.1.12148.7.4.3NodeloadDistributionLVDStatus
1.3.6.1.4.1.12148.7.4.3.1ScalarloadLVD1EnableStatusread-onlycurrentThe status of contactors configuration. 'enabled' means that the contactor is i n use. 'disabled' means that the contactor is disconfigured and not in use.
1.3.6.1.4.1.12148.7.4.3.2ScalarloadLVD1Statusread-onlycurrentThe A Bus (primary loads) Contactor is closed(0) or open(1)
1.3.6.1.4.1.12148.7.4.3.3ScalarloadLVD1ConnectVoltageread-writecurrentThe A Bus (primary loads) Contactor Connect Voltage
1.3.6.1.4.1.12148.7.4.3.4ScalarloadLVD1DisconnectVoltageread-writecurrentThe A Bus (primary loads) Contactor Disconnect Voltage
1.3.6.1.4.1.12148.7.4.3.5ScalarloadLVD2EnableStatusread-onlycurrentThe status of contactors configuration. 'enabled' means that the contactor is i n use. 'disabled' means that the contactor is disconfigured and not in use.
1.3.6.1.4.1.12148.7.4.3.6ScalarloadLVD2Statusread-onlycurrentThe B Bus (secondary loads) Contactor is closed(0) or open(1)
1.3.6.1.4.1.12148.7.4.3.7ScalarloadLVD2ConnectVoltageread-writecurrentThe B Bus (secondary loads) Contactor Connect Voltage
1.3.6.1.4.1.12148.7.4.3.8ScalarloadLVD2DisconnectVoltageread-writecurrentThe B Bus (secondary loads) Contactor Disconnect Voltage
1.3.6.1.4.1.12148.7.4.3.9ScalarloadLVD3EnableStatusread-onlycurrentThe status of contactors configuration. 'enabled' means that the contactor is i n use. 'disabled' means that the contactor is disconfigured and not in use.
1.3.6.1.4.1.12148.7.4.3.10ScalarloadLVD3Statusread-onlycurrentThe C Bus (critical loads) Contactor is closed(0) or open(1)
1.3.6.1.4.1.12148.7.4.3.11ScalarloadLVD3ConnectVoltageread-writecurrentThe C Bus (critical loads) Contactor Connect Voltage
1.3.6.1.4.1.12148.7.4.3.12ScalarloadLVD3DisconnectVoltageread-writecurrentThe C Bus (critical loads) Contactor Disconnect Voltage
1.3.6.1.4.1.12148.7.5Noderectifier
1.3.6.1.4.1.12148.7.5.1ScalarrectifierInstalledRectifiersread-onlycurrentThe installed number of rectifiers for this DC Power System.
1.3.6.1.4.1.12148.7.5.2ScalarrectifierRectifiersActiveread-onlycurrentThe actual number of active rectifiers in this DC Power System.
1.3.6.1.4.1.12148.7.5.3ScalarrectifierTotalCurrentread-onlycurrentThe DC system's total available current
1.3.6.1.4.1.12148.7.5.4ScalarrectifierUtilizationread-onlycurrentUtilization in % of available rectifier capacity
1.3.6.1.4.1.12148.7.5.5NoderectifierStatus
1.3.6.1.4.1.12148.7.5.5.1ScalarrectifierStatusNoIndexread-writecurrentA starting index for the rectifierStatusTable array
1.3.6.1.4.1.12148.7.5.5.2TablerectifierStatusTablenot-accessiblecurrentA table listing up to sixteen sequential recifiers, starting from the rectifier number specified by rectifierStatusNoIndex
1.3.6.1.4.1.12148.7.5.5.2.1RowrectifierStatusEntrynot-accessiblecurrentA row of rectifier status data corresponding to the rectifierStatusNoIndex value
1.3.6.1.4.1.12148.7.5.5.2.1.1ColumnrectifierStatusIDread-onlycurrentThe rectifier ID number of the rectifier record.
1.3.6.1.4.1.12148.7.5.5.2.1.2ColumnrectifierStatusStatusread-onlycurrentThe operational status of the rectifier record. absent (0), active (1), failed (2), walkin (3), disabledbycommand (4)
1.3.6.1.4.1.12148.7.5.5.2.1.3ColumnrectifierStatusOutputCurrentread-onlycurrentThe rectifier current of the rectifier record.
1.3.6.1.4.1.12148.7.5.5.2.1.4ColumnrectifierStatusOutputVoltageread-onlycurrentThe rectifier voltage of the rectifier record.
1.3.6.1.4.1.12148.7.5.5.2.1.5ColumnrectifierStatusTempread-onlycurrentThe heatsink temperature of the rectifier record.
1.3.6.1.4.1.12148.7.5.5.2.1.6ColumnrectifierStatusTyperead-onlycurrentThe rectifier article number string of the rectifier record.
1.3.6.1.4.1.12148.7.5.5.2.1.7ColumnrectifierStatusSKUread-onlycurrentThe rectifier Stock Keeping Unit number or other user-defined ID of the rectifier record.
1.3.6.1.4.1.12148.7.5.5.2.1.8ColumnrectifierStatusSerialNoread-onlycurrentThe rectifier serial number string of the rectifier record.
1.3.6.1.4.1.12148.7.5.5.2.1.9ColumnrectifierStatusRevisionLevelread-onlycurrentThe rectifier version number string of the rectifier record.
1.3.6.1.4.1.12148.7.6NodeacDistribution
1.3.6.1.4.1.12148.7.6.1ScalaracVoltage1read-onlycurrentThe AC Voltage of phase 1
1.3.6.1.4.1.12148.7.6.2ScalaracVoltage2read-onlycurrentThe AC Voltage of phase 2
1.3.6.1.4.1.12148.7.6.3ScalaracVoltage3read-onlycurrentThe AC Voltage of phase 3
1.3.6.1.4.1.12148.7.7NodealarmGroup
1.3.6.1.4.1.12148.7.7.1NodealarmWellknownAlarms
1.3.6.1.4.1.12148.7.7.1.1ScalaralarmMajorHighBattVoltread-onlycurrentThe Very High Battery Voltage Alarm
1.3.6.1.4.1.12148.7.7.1.2ScalaralarmMinorHighBattVoltread-onlycurrentThe High Battery Voltage alarm
1.3.6.1.4.1.12148.7.7.1.3ScalaralarmMajorLowBattVoltread-onlycurrentThe Very Low Battery Voltage Alarm
1.3.6.1.4.1.12148.7.7.1.4ScalaralarmMinorLowBattVoltread-onlycurrentThe Low Battery Voltage Alarm
1.3.6.1.4.1.12148.7.7.1.5ScalaralarmMajorBatteryHighTempread-onlycurrentTemperature much too high alarm, or temperature compensation circuit / probe failure alarm
1.3.6.1.4.1.12148.7.7.1.6ScalaralarmMinorBatteryHighTempread-onlycurrentTemperature much too high alarm
1.3.6.1.4.1.12148.7.7.1.7ScalaralarmBatteryDisconnectOpenread-onlycurrentThe Battery Disconnect Contactor alarm
1.3.6.1.4.1.12148.7.7.1.8ScalaralarmLVD1openread-onlycurrentThe A Bus (primary loads) Contactor alarm. The contactor dropout voltage has been reached and the contactor will release.
1.3.6.1.4.1.12148.7.7.1.9ScalaralarmLVD2openread-onlycurrentThe B Bus (secondary loads) Contactor alarm. The contactor dropout voltage has been reached and the contactor will release.
1.3.6.1.4.1.12148.7.7.1.10ScalaralarmLVD3openread-onlycurrentThe C Bus (critical loads) Contactor alarm. The contactor dropout voltage has been reached and the contactor will release.
1.3.6.1.4.1.12148.7.7.1.11ScalaralarmACmainsread-onlycurrentThe AC voltage has dropped below critical level, or one or more AC input phases was lost.
1.3.6.1.4.1.12148.7.7.1.12ScalaralarmBatteryBreakerOpenread-onlycurrentBattery string disconnect breaker/fuse alarm
1.3.6.1.4.1.12148.7.7.1.13ScalaralarmDistributionBreakerOpenread-onlycurrentThe Load Distribution breaker/fuse alarm
1.3.6.1.4.1.12148.7.7.1.14ScalaralarmMajorRectifierread-onlycurrentThis is a 'multiple rectifiers have failed' alarm
1.3.6.1.4.1.12148.7.7.1.15ScalaralarmMinorRectifierread-onlycurrentThis is a 'one rectifier has failed' alarm
1.3.6.1.4.1.12148.7.7.1.16ScalaralarmMajorBatteryMidpointread-onlycurrentBattery Symmetry (midpoint) Delta Voltage is badly out of limits alarm
1.3.6.1.4.1.12148.7.7.1.17ScalaralarmMinorBatteryMidpointread-onlycurrentBattery Symmetry (midpoint) Delta Voltage out of limits alarm
1.3.6.1.4.1.12148.7.7.1.18ScalaralarmBatteryLifeEndedread-onlycurrentThe battery capacity has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery life…
1.3.6.1.4.1.12148.7.7.1.19ScalaralarmBatteryTestmodeEnteredread-onlycurrentThe system has lowered the battery charge voltage in order to discharge the batteries to a predefinend level. When the criteria for stopping the battery testin…
1.3.6.1.4.1.12148.7.7.1.20ScalaralarmBatteryBoostmodeEnteredread-onlycurrentThe system has increased the battery charge voltage in order to equalize the battery cells charging. When the criteria for stopping the battery equalizing is r…
1.3.6.1.4.1.12148.7.7.1.21ScalaralarmUserConfigurable1read-onlycurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.7.1.22ScalaralarmUserConfigurable2read-onlycurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.7.1.23ScalaralarmUserConfigurable3read-onlycurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.7.1.24ScalaralarmUserConfigurable4read-onlycurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.7.1.25ScalaralarmUserConfigurable5read-onlycurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.7.1.26ScalaralarmUserConfigurable6read-onlycurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.7.1.27ScalaralarmUserConfigurable7read-onlycurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.7.1.28ScalaralarmUserConfigurable8read-onlycurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.7.1.29ScalaralarmUserConfigurable9read-onlycurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.7.1.30ScalaralarmUserConfigurable10read-onlycurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.7.1.31ScalaralarmUserConfigurable11read-onlycurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.7.1.32ScalaralarmUserConfigurable12read-onlycurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.7.1.33ScalaralarmUserConfigurable13read-onlycurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.7.1.34ScalaralarmUserConfigurable14read-onlycurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.8GroupdcSystemTrapscurrentThis branch contains the Alarm Notification Traps, which duplicate the alarmGroup OIDs. Each alarm condition is represented by a Alarm Condition Trap and an as…
1.3.6.1.4.1.12148.7.8.1NotificationalarmMajorHighBattVoltTrapcurrentThe Very High Battery Voltage alarm
1.3.6.1.4.1.12148.7.8.2NotificationalarmMinorHighBattVoltTrapcurrentThe High Battery Voltage alarm
1.3.6.1.4.1.12148.7.8.3NotificationalarmMajorLowBattVoltTrapcurrentThe Very Low Battery Voltage Alarm
1.3.6.1.4.1.12148.7.8.4NotificationalarmMinorLowBattVoltTrapcurrentThe Low Battery Voltage Alarm
1.3.6.1.4.1.12148.7.8.5NotificationalarmMajorBatteryHighTempTrapcurrentHigh Battery temperature alarm or Temperature Compensation circuit / probe failure alarm
1.3.6.1.4.1.12148.7.8.6NotificationalarmMinorBatteryHighTempTrapcurrentHigh Battery temperature alarm
1.3.6.1.4.1.12148.7.8.7NotificationalarmBatteryDisconnectOpenTrapcurrentThe Battery Disconnect Contactor alarm
1.3.6.1.4.1.12148.7.8.8NotificationalarmLVD1openTrapcurrentThe A Bus (primary loads) Contactor is open alarm
1.3.6.1.4.1.12148.7.8.9NotificationalarmLVD2openTrapcurrentThe B Bus (secondary loads) Contactor is open alarm
1.3.6.1.4.1.12148.7.8.10NotificationalarmLVD3openTrapcurrentThe C Bus (critical loads) Contactor alarm. The contactor dropout voltage has been reached and the contactor is released.
1.3.6.1.4.1.12148.7.8.11NotificationalarmACmainsTrapcurrentThe AC voltage has dropped below critical level, or one or more AC input phases was lost.
1.3.6.1.4.1.12148.7.8.12NotificationalarmBatteryBreakerOpenTrapcurrentBattery string disconnect breaker/fuse alarm
1.3.6.1.4.1.12148.7.8.13NotificationalarmDistributionBreakerOpenTrapcurrentThe Load Distribution breaker/fuse alarm
1.3.6.1.4.1.12148.7.8.14NotificationalarmMajorRectifierTrapcurrentThis is a 'multiple rectifiers have failed' alarm
1.3.6.1.4.1.12148.7.8.15NotificationalarmMinorRectifierTrapcurrentThis is a 'one rectifier has failed' alarm
1.3.6.1.4.1.12148.7.8.16NotificationalarmMajorBatteryMidpointTrapcurrentBattery Symmetry (midpoint) Delta Voltage out of 'major fault' limits alarm
1.3.6.1.4.1.12148.7.8.17NotificationalarmMinorBatteryMidpointTrapcurrentBattery Symmetry (midpoint) Delta Voltage out of limits alarm
1.3.6.1.4.1.12148.7.8.18NotificationalarmBatteryLifeEndedTrapcurrentThe battery capacity has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery life…
1.3.6.1.4.1.12148.7.8.19NotificationalarmBatteryTestmodeEnteredTrapcurrentThe system has lowered the battery charge voltage in order to discharge the batteries to a predefinend level. When the criteria for stopping the battery testin…
1.3.6.1.4.1.12148.7.8.20NotificationalarmBatteryBoostmodeEnteredTrapcurrentThe system has increased the battery charge voltage in order to equalize the battery cells charging. When the criteria for stopping the battery equalizing is r…
1.3.6.1.4.1.12148.7.8.21NotificationalarmUserConfigurable1TrapcurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.8.22NotificationalarmUserConfigurable2TrapcurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.8.23NotificationalarmUserConfigurable3TrapcurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.8.24NotificationalarmUserConfigurable4TrapcurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.8.25NotificationalarmUserConfigurable5TrapcurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.8.26NotificationalarmUserConfigurable6TrapcurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.8.27NotificationalarmUserConfigurable7TrapcurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.8.28NotificationalarmUserConfigurable8TrapcurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.8.29NotificationalarmUserConfigurable9TrapcurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.8.30NotificationalarmUserConfigurable10TrapcurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.8.31NotificationalarmUserConfigurable11TrapcurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.8.32NotificationalarmUserConfigurable12TrapcurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.8.33NotificationalarmUserConfigurable13TrapcurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …
1.3.6.1.4.1.12148.7.8.34NotificationalarmUserConfigurable14TrapcurrentGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the …