ELTEK_GENERIC-MIB
162 objects
No module-level DESCRIPTION found.
Imported Objects
| ELTEK-COMMON-MIB | eltek |
| SNMPv2-CONF | NOTIFICATION-GROUP |
| SNMPv2-SMI | enterprises Integer32 mib-2 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE |
| SNMPv2-TC | DisplayString |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.12148.7 | NodeeltekPlant | |||
| 1.3.6.1.4.1.12148.7.1 | NodecontrolSystem | |||
| 1.3.6.1.4.1.12148.7.1.1 | NodesystemTime | |||
| 1.3.6.1.4.1.12148.7.1.1.1 | ScalarsystemTimeTime | read-only | current | The system date and time. Used for event timestamps and logging |
| 1.3.6.1.4.1.12148.7.1.2 | ScalarsystemInfoRefresh | read-write | current | This object will re-initialize the agent, updating MIB data values. |
| 1.3.6.1.4.1.12148.7.1.3 | ScalarsystemTrapRepeatRate | read-write | current | This object sets the repeat rate of any active traps, in seconds. Entering 0 (zero) will prevent repeating traps - one trap only will be sent per alarm event. |
| 1.3.6.1.4.1.12148.7.1.4 | ScalarsystemSendOffTrap | read-write | current | A separate off-trap will be issued when an alarm condition goes off, if this flag is set to 1. Entering 0 (zero) will prevent OFF traps from being transmitted. |
| 1.3.6.1.4.1.12148.7.2 | NodedcSystem | |||
| 1.3.6.1.4.1.12148.7.2.1 | NodedcPlant | |||
| 1.3.6.1.4.1.12148.7.2.1.3 | NodesystemSiteInfo | |||
| 1.3.6.1.4.1.12148.7.2.1.3.1 | ScalarsystemSiteInfoCustomer | read-only | current | The Customer name (as stored in the Smartpack Control Unit) |
| 1.3.6.1.4.1.12148.7.2.1.3.2 | ScalarsystemSiteInfoLocation | read-only | current | The system/site Location details (as stored in the Smartpack Control Unit). |
| 1.3.6.1.4.1.12148.7.2.1.3.3 | ScalarsystemSiteInfoMessage1 | read-only | current | The system/site Info Message record #1 (as stored in the Smartpack Control Unit). 31 Bytes. |
| 1.3.6.1.4.1.12148.7.2.1.3.4 | ScalarsystemSiteInfoMessage2 | read-only | current | The system/site Info Message record #2 (as stored in the Smartpack Control Unit). 31 Bytes. |
| 1.3.6.1.4.1.12148.7.2.1.3.5 | ScalarsystemSiteInfoInstalledDate | read-only | current | The system's Installed Date text string (as stored in the Smartpack Control Unit) 16bytes. |
| 1.3.6.1.4.1.12148.7.2.1.3.6 | ScalarsystemSiteInfoControllerType | read-only | current | The system Controller Module currently connected. AL175/MCU=0; AEON Gold=1; AL6000=2; Smartpack=3 |
| 1.3.6.1.4.1.12148.7.2.1.3.7 | ScalarsystemSiteInfoSystemSeriaNum | read-only | current | The serial number for the complete system |
| 1.3.6.1.4.1.12148.7.2.1.3.8 | ScalarsystemSiteInfoControllerSeriaNum | read-only | current | The serial number for the system controller |
| 1.3.6.1.4.1.12148.7.2.1.4 | ScalarsystemNominalVoltage | read-only | current | The nominal voltage rating. 12V/24V/48V/60V systems 0=48V 1=24V 2=12V 3=26V 4=60V |
| 1.3.6.1.4.1.12148.7.2.2 | ScalarsystemOperationalStatus | read-only | current | A summary status showing if the system is testing, boosting, floating etc. 0=Float, voltage regulated 1=Float, temperature comp. regulated; 2=equalize 3=batter… |
| 1.3.6.1.4.1.12148.7.3 | Nodebattery | |||
| 1.3.6.1.4.1.12148.7.3.1 | ScalarbatteryName | read-only | current | A descriptive name of the battery installed in the system |
| 1.3.6.1.4.1.12148.7.3.2 | ScalarbatteryVoltage | read-only | current | The measured battery voltage. |
| 1.3.6.1.4.1.12148.7.3.3 | ScalarbatteryCurrent | read-only | current | The measured battery current. |
| 1.3.6.1.4.1.12148.7.3.4 | ScalarbatteryTemp | read-only | current | The battery temperature |
| 1.3.6.1.4.1.12148.7.3.5 | ScalarbatteryBreakerStatus | read-only | current | The state of the battery fuse/breaker can be either closed(0) or open(1) |
| 1.3.6.1.4.1.12148.7.3.6 | ScalarbatteryChargeCurrentLimitCtrl | read-write | current | Control field for the battery charge limitation feature; 0=inactive, 1=active. |
| 1.3.6.1.4.1.12148.7.3.7 | ScalarbatteryChargeCurrentLimitValue | read-write | current | Battery charging current limit value |
| 1.3.6.1.4.1.12148.7.3.8 | ScalarbatteryTempCompEnable | read-write | current | Enable (0) or Disable (1) Battery Temperature Compensated output regulation mode |
| 1.3.6.1.4.1.12148.7.3.9 | ScalarbatteryFloatVoltConfig | read-write | current | The Voltage at which the DC System float charges. |
| 1.3.6.1.4.1.12148.7.3.10 | ScalarbatteryEqualizeVoltConfig | read-write | current | The Voltage at which the DC System boost charges the batteries. |
| 1.3.6.1.4.1.12148.7.3.11 | ScalarbatteryHighMajorAlarmVoltageConfig | read-write | current | The High Battery Voltage alarm limit set voltage |
| 1.3.6.1.4.1.12148.7.3.12 | ScalarbatteryHighMinorAlarmVoltageConfig | read-write | current | The High Battery Voltage alarm limit set voltage |
| 1.3.6.1.4.1.12148.7.3.13 | ScalarbatteryLowMajorAlarmVoltageConfig | read-write | current | The Low Battery Voltage Alarm limit set voltage |
| 1.3.6.1.4.1.12148.7.3.14 | ScalarbatteryLowMinorAlarmVoltageConfig | read-write | current | The Very Low Battery Voltage Alarm limit set voltage |
| 1.3.6.1.4.1.12148.7.3.15 | ScalarbatteryStartManualTest | read-write | current | This pushbutton will start a manual battery test if otherwise the system allows it. |
| 1.3.6.1.4.1.12148.7.3.16 | ScalarbatteryStartManualBoost | read-write | current | This pushbutton will start a manual battery boost if otherwise the system allows it. |
| 1.3.6.1.4.1.12148.7.3.17 | NodebatteryLVD | |||
| 1.3.6.1.4.1.12148.7.3.17.1 | ScalarbatteryLVDStatus | read-only | current | Contactor is closed(0) or open(1) |
| 1.3.6.1.4.1.12148.7.3.17.2 | ScalarbatteryLVDDisconnectVoltage | read-write | current | The Contactor Disconnect Voltage |
| 1.3.6.1.4.1.12148.7.3.17.3 | ScalarbatteryLVDConnectVoltage | read-write | current | The Contactor Reconnect Voltage |
| 1.3.6.1.4.1.12148.7.3.18 | NodebatteryMidpoint | |||
| 1.3.6.1.4.1.12148.7.3.18.1 | ScalarbatteryMidpointDeltaLimitVoltage | read-write | current | The allowable deviation of the midpoint battery voltage from the theoretical. Exceeding this value in either direction (+/-) causes an alarm state |
| 1.3.6.1.4.1.12148.7.3.18.2 | ScalarbatteryMidpointIndex | read-only | current | An index of Battery Strings, for the batteryMidpointControlTable and batteryMidpointStatusTable arrays |
| 1.3.6.1.4.1.12148.7.3.18.3 | TablebatteryMidpointControlTable | not-accessible | current | A table of settings related to Battery Symmetry (midpoint) Monitoring |
| 1.3.6.1.4.1.12148.7.3.18.3.1 | RowbatteryMidpointControlEntry | not-accessible | current | Settings related to Battery Symmetry (midpoint) Monitoring, corresponding to the batteryMidpointIndex value |
| 1.3.6.1.4.1.12148.7.3.18.3.1.1 | ColumnmidpointEnableID | read-only | current | The rectifier ID number of the rectifier record. |
| 1.3.6.1.4.1.12148.7.3.18.3.1.2 | ColumnmidpointEnable | read-write | current | Enable (1) or Disable (0) the Battery Monitor channel which corresponds to the batteryMidpointIndex value |
| 1.3.6.1.4.1.12148.7.3.18.4 | TablebatteryMidpointStatusTable | not-accessible | current | A table of values and/or measurements related to Battery Symmetry (midpoint) Monitoring |
| 1.3.6.1.4.1.12148.7.3.18.4.1 | RowbatteryMidpointStatusEntry | not-accessible | current | Values related to Battery Symmetry (midpoint) Monitoring, corresponding to the batteryMidpointIndex value |
| 1.3.6.1.4.1.12148.7.3.18.4.1.1 | ColumnmidpointStatusID | read-only | current | The rectifier ID number of the rectifier record. |
| 1.3.6.1.4.1.12148.7.3.18.4.1.2 | ColumnmidpointStatus | read-only | current | Status (0=Normal; 1=Alarm) of the Battery Monitor channel which corresponds to the batteryMidpointIndex value |
| 1.3.6.1.4.1.12148.7.3.18.4.1.3 | ColumnmidpointDeltaVoltage | read-only | current | The measured battery voltage deviation from midpoint of the Battery Monitor channel which corresponds to the batteryMidpointIndex value. |
| 1.3.6.1.4.1.12148.7.4 | NodeloadDistribution | |||
| 1.3.6.1.4.1.12148.7.4.1 | ScalarloadDistributionCurrent | read-only | current | The total load current |
| 1.3.6.1.4.1.12148.7.4.2 | ScalarloadDistributionBreakerStatus | read-only | current | The state of the load fuse/breaker can be either closed(0) or open(1) |
| 1.3.6.1.4.1.12148.7.4.3 | NodeloadDistributionLVDStatus | |||
| 1.3.6.1.4.1.12148.7.4.3.1 | ScalarloadLVD1EnableStatus | read-only | current | The status of contactors configuration. 'enabled' means that the contactor is i n use. 'disabled' means that the contactor is disconfigured and not in use. |
| 1.3.6.1.4.1.12148.7.4.3.2 | ScalarloadLVD1Status | read-only | current | The A Bus (primary loads) Contactor is closed(0) or open(1) |
| 1.3.6.1.4.1.12148.7.4.3.3 | ScalarloadLVD1ConnectVoltage | read-write | current | The A Bus (primary loads) Contactor Connect Voltage |
| 1.3.6.1.4.1.12148.7.4.3.4 | ScalarloadLVD1DisconnectVoltage | read-write | current | The A Bus (primary loads) Contactor Disconnect Voltage |
| 1.3.6.1.4.1.12148.7.4.3.5 | ScalarloadLVD2EnableStatus | read-only | current | The status of contactors configuration. 'enabled' means that the contactor is i n use. 'disabled' means that the contactor is disconfigured and not in use. |
| 1.3.6.1.4.1.12148.7.4.3.6 | ScalarloadLVD2Status | read-only | current | The B Bus (secondary loads) Contactor is closed(0) or open(1) |
| 1.3.6.1.4.1.12148.7.4.3.7 | ScalarloadLVD2ConnectVoltage | read-write | current | The B Bus (secondary loads) Contactor Connect Voltage |
| 1.3.6.1.4.1.12148.7.4.3.8 | ScalarloadLVD2DisconnectVoltage | read-write | current | The B Bus (secondary loads) Contactor Disconnect Voltage |
| 1.3.6.1.4.1.12148.7.4.3.9 | ScalarloadLVD3EnableStatus | read-only | current | The status of contactors configuration. 'enabled' means that the contactor is i n use. 'disabled' means that the contactor is disconfigured and not in use. |
| 1.3.6.1.4.1.12148.7.4.3.10 | ScalarloadLVD3Status | read-only | current | The C Bus (critical loads) Contactor is closed(0) or open(1) |
| 1.3.6.1.4.1.12148.7.4.3.11 | ScalarloadLVD3ConnectVoltage | read-write | current | The C Bus (critical loads) Contactor Connect Voltage |
| 1.3.6.1.4.1.12148.7.4.3.12 | ScalarloadLVD3DisconnectVoltage | read-write | current | The C Bus (critical loads) Contactor Disconnect Voltage |
| 1.3.6.1.4.1.12148.7.5 | Noderectifier | |||
| 1.3.6.1.4.1.12148.7.5.1 | ScalarrectifierInstalledRectifiers | read-only | current | The installed number of rectifiers for this DC Power System. |
| 1.3.6.1.4.1.12148.7.5.2 | ScalarrectifierRectifiersActive | read-only | current | The actual number of active rectifiers in this DC Power System. |
| 1.3.6.1.4.1.12148.7.5.3 | ScalarrectifierTotalCurrent | read-only | current | The DC system's total available current |
| 1.3.6.1.4.1.12148.7.5.4 | ScalarrectifierUtilization | read-only | current | Utilization in % of available rectifier capacity |
| 1.3.6.1.4.1.12148.7.5.5 | NoderectifierStatus | |||
| 1.3.6.1.4.1.12148.7.5.5.1 | ScalarrectifierStatusNoIndex | read-write | current | A starting index for the rectifierStatusTable array |
| 1.3.6.1.4.1.12148.7.5.5.2 | TablerectifierStatusTable | not-accessible | current | A table listing up to sixteen sequential recifiers, starting from the rectifier number specified by rectifierStatusNoIndex |
| 1.3.6.1.4.1.12148.7.5.5.2.1 | RowrectifierStatusEntry | not-accessible | current | A row of rectifier status data corresponding to the rectifierStatusNoIndex value |
| 1.3.6.1.4.1.12148.7.5.5.2.1.1 | ColumnrectifierStatusID | read-only | current | The rectifier ID number of the rectifier record. |
| 1.3.6.1.4.1.12148.7.5.5.2.1.2 | ColumnrectifierStatusStatus | read-only | current | The operational status of the rectifier record. absent (0), active (1), failed (2), walkin (3), disabledbycommand (4) |
| 1.3.6.1.4.1.12148.7.5.5.2.1.3 | ColumnrectifierStatusOutputCurrent | read-only | current | The rectifier current of the rectifier record. |
| 1.3.6.1.4.1.12148.7.5.5.2.1.4 | ColumnrectifierStatusOutputVoltage | read-only | current | The rectifier voltage of the rectifier record. |
| 1.3.6.1.4.1.12148.7.5.5.2.1.5 | ColumnrectifierStatusTemp | read-only | current | The heatsink temperature of the rectifier record. |
| 1.3.6.1.4.1.12148.7.5.5.2.1.6 | ColumnrectifierStatusType | read-only | current | The rectifier article number string of the rectifier record. |
| 1.3.6.1.4.1.12148.7.5.5.2.1.7 | ColumnrectifierStatusSKU | read-only | current | The rectifier Stock Keeping Unit number or other user-defined ID of the rectifier record. |
| 1.3.6.1.4.1.12148.7.5.5.2.1.8 | ColumnrectifierStatusSerialNo | read-only | current | The rectifier serial number string of the rectifier record. |
| 1.3.6.1.4.1.12148.7.5.5.2.1.9 | ColumnrectifierStatusRevisionLevel | read-only | current | The rectifier version number string of the rectifier record. |
| 1.3.6.1.4.1.12148.7.6 | NodeacDistribution | |||
| 1.3.6.1.4.1.12148.7.6.1 | ScalaracVoltage1 | read-only | current | The AC Voltage of phase 1 |
| 1.3.6.1.4.1.12148.7.6.2 | ScalaracVoltage2 | read-only | current | The AC Voltage of phase 2 |
| 1.3.6.1.4.1.12148.7.6.3 | ScalaracVoltage3 | read-only | current | The AC Voltage of phase 3 |
| 1.3.6.1.4.1.12148.7.7 | NodealarmGroup | |||
| 1.3.6.1.4.1.12148.7.7.1 | NodealarmWellknownAlarms | |||
| 1.3.6.1.4.1.12148.7.7.1.1 | ScalaralarmMajorHighBattVolt | read-only | current | The Very High Battery Voltage Alarm |
| 1.3.6.1.4.1.12148.7.7.1.2 | ScalaralarmMinorHighBattVolt | read-only | current | The High Battery Voltage alarm |
| 1.3.6.1.4.1.12148.7.7.1.3 | ScalaralarmMajorLowBattVolt | read-only | current | The Very Low Battery Voltage Alarm |
| 1.3.6.1.4.1.12148.7.7.1.4 | ScalaralarmMinorLowBattVolt | read-only | current | The Low Battery Voltage Alarm |
| 1.3.6.1.4.1.12148.7.7.1.5 | ScalaralarmMajorBatteryHighTemp | read-only | current | Temperature much too high alarm, or temperature compensation circuit / probe failure alarm |
| 1.3.6.1.4.1.12148.7.7.1.6 | ScalaralarmMinorBatteryHighTemp | read-only | current | Temperature much too high alarm |
| 1.3.6.1.4.1.12148.7.7.1.7 | ScalaralarmBatteryDisconnectOpen | read-only | current | The Battery Disconnect Contactor alarm |
| 1.3.6.1.4.1.12148.7.7.1.8 | ScalaralarmLVD1open | read-only | current | The A Bus (primary loads) Contactor alarm. The contactor dropout voltage has been reached and the contactor will release. |
| 1.3.6.1.4.1.12148.7.7.1.9 | ScalaralarmLVD2open | read-only | current | The B Bus (secondary loads) Contactor alarm. The contactor dropout voltage has been reached and the contactor will release. |
| 1.3.6.1.4.1.12148.7.7.1.10 | ScalaralarmLVD3open | read-only | current | The C Bus (critical loads) Contactor alarm. The contactor dropout voltage has been reached and the contactor will release. |
| 1.3.6.1.4.1.12148.7.7.1.11 | ScalaralarmACmains | read-only | current | The AC voltage has dropped below critical level, or one or more AC input phases was lost. |
| 1.3.6.1.4.1.12148.7.7.1.12 | ScalaralarmBatteryBreakerOpen | read-only | current | Battery string disconnect breaker/fuse alarm |
| 1.3.6.1.4.1.12148.7.7.1.13 | ScalaralarmDistributionBreakerOpen | read-only | current | The Load Distribution breaker/fuse alarm |
| 1.3.6.1.4.1.12148.7.7.1.14 | ScalaralarmMajorRectifier | read-only | current | This is a 'multiple rectifiers have failed' alarm |
| 1.3.6.1.4.1.12148.7.7.1.15 | ScalaralarmMinorRectifier | read-only | current | This is a 'one rectifier has failed' alarm |
| 1.3.6.1.4.1.12148.7.7.1.16 | ScalaralarmMajorBatteryMidpoint | read-only | current | Battery Symmetry (midpoint) Delta Voltage is badly out of limits alarm |
| 1.3.6.1.4.1.12148.7.7.1.17 | ScalaralarmMinorBatteryMidpoint | read-only | current | Battery Symmetry (midpoint) Delta Voltage out of limits alarm |
| 1.3.6.1.4.1.12148.7.7.1.18 | ScalaralarmBatteryLifeEnded | read-only | current | The battery capacity has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery life… |
| 1.3.6.1.4.1.12148.7.7.1.19 | ScalaralarmBatteryTestmodeEntered | read-only | current | The system has lowered the battery charge voltage in order to discharge the batteries to a predefinend level. When the criteria for stopping the battery testin… |
| 1.3.6.1.4.1.12148.7.7.1.20 | ScalaralarmBatteryBoostmodeEntered | read-only | current | The system has increased the battery charge voltage in order to equalize the battery cells charging. When the criteria for stopping the battery equalizing is r… |
| 1.3.6.1.4.1.12148.7.7.1.21 | ScalaralarmUserConfigurable1 | read-only | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … |
| 1.3.6.1.4.1.12148.7.7.1.22 | ScalaralarmUserConfigurable2 | read-only | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … |
| 1.3.6.1.4.1.12148.7.7.1.23 | ScalaralarmUserConfigurable3 | read-only | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … |
| 1.3.6.1.4.1.12148.7.7.1.24 | ScalaralarmUserConfigurable4 | read-only | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … |
| 1.3.6.1.4.1.12148.7.7.1.25 | ScalaralarmUserConfigurable5 | read-only | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … |
| 1.3.6.1.4.1.12148.7.7.1.26 | ScalaralarmUserConfigurable6 | read-only | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … |
| 1.3.6.1.4.1.12148.7.7.1.27 | ScalaralarmUserConfigurable7 | read-only | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … |
| 1.3.6.1.4.1.12148.7.7.1.28 | ScalaralarmUserConfigurable8 | read-only | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … |
| 1.3.6.1.4.1.12148.7.7.1.29 | ScalaralarmUserConfigurable9 | read-only | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … |
| 1.3.6.1.4.1.12148.7.7.1.30 | ScalaralarmUserConfigurable10 | read-only | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … |
| 1.3.6.1.4.1.12148.7.7.1.31 | ScalaralarmUserConfigurable11 | read-only | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … |
| 1.3.6.1.4.1.12148.7.7.1.32 | ScalaralarmUserConfigurable12 | read-only | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … |
| 1.3.6.1.4.1.12148.7.7.1.33 | ScalaralarmUserConfigurable13 | read-only | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … |
| 1.3.6.1.4.1.12148.7.7.1.34 | ScalaralarmUserConfigurable14 | read-only | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … |
| 1.3.6.1.4.1.12148.7.8 | GroupdcSystemTraps | current | This branch contains the Alarm Notification Traps, which duplicate the alarmGroup OIDs. Each alarm condition is represented by a Alarm Condition Trap and an as… | |
| 1.3.6.1.4.1.12148.7.8.1 | NotificationalarmMajorHighBattVoltTrap | current | The Very High Battery Voltage alarm | |
| 1.3.6.1.4.1.12148.7.8.2 | NotificationalarmMinorHighBattVoltTrap | current | The High Battery Voltage alarm | |
| 1.3.6.1.4.1.12148.7.8.3 | NotificationalarmMajorLowBattVoltTrap | current | The Very Low Battery Voltage Alarm | |
| 1.3.6.1.4.1.12148.7.8.4 | NotificationalarmMinorLowBattVoltTrap | current | The Low Battery Voltage Alarm | |
| 1.3.6.1.4.1.12148.7.8.5 | NotificationalarmMajorBatteryHighTempTrap | current | High Battery temperature alarm or Temperature Compensation circuit / probe failure alarm | |
| 1.3.6.1.4.1.12148.7.8.6 | NotificationalarmMinorBatteryHighTempTrap | current | High Battery temperature alarm | |
| 1.3.6.1.4.1.12148.7.8.7 | NotificationalarmBatteryDisconnectOpenTrap | current | The Battery Disconnect Contactor alarm | |
| 1.3.6.1.4.1.12148.7.8.8 | NotificationalarmLVD1openTrap | current | The A Bus (primary loads) Contactor is open alarm | |
| 1.3.6.1.4.1.12148.7.8.9 | NotificationalarmLVD2openTrap | current | The B Bus (secondary loads) Contactor is open alarm | |
| 1.3.6.1.4.1.12148.7.8.10 | NotificationalarmLVD3openTrap | current | The C Bus (critical loads) Contactor alarm. The contactor dropout voltage has been reached and the contactor is released. | |
| 1.3.6.1.4.1.12148.7.8.11 | NotificationalarmACmainsTrap | current | The AC voltage has dropped below critical level, or one or more AC input phases was lost. | |
| 1.3.6.1.4.1.12148.7.8.12 | NotificationalarmBatteryBreakerOpenTrap | current | Battery string disconnect breaker/fuse alarm | |
| 1.3.6.1.4.1.12148.7.8.13 | NotificationalarmDistributionBreakerOpenTrap | current | The Load Distribution breaker/fuse alarm | |
| 1.3.6.1.4.1.12148.7.8.14 | NotificationalarmMajorRectifierTrap | current | This is a 'multiple rectifiers have failed' alarm | |
| 1.3.6.1.4.1.12148.7.8.15 | NotificationalarmMinorRectifierTrap | current | This is a 'one rectifier has failed' alarm | |
| 1.3.6.1.4.1.12148.7.8.16 | NotificationalarmMajorBatteryMidpointTrap | current | Battery Symmetry (midpoint) Delta Voltage out of 'major fault' limits alarm | |
| 1.3.6.1.4.1.12148.7.8.17 | NotificationalarmMinorBatteryMidpointTrap | current | Battery Symmetry (midpoint) Delta Voltage out of limits alarm | |
| 1.3.6.1.4.1.12148.7.8.18 | NotificationalarmBatteryLifeEndedTrap | current | The battery capacity has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery life… | |
| 1.3.6.1.4.1.12148.7.8.19 | NotificationalarmBatteryTestmodeEnteredTrap | current | The system has lowered the battery charge voltage in order to discharge the batteries to a predefinend level. When the criteria for stopping the battery testin… | |
| 1.3.6.1.4.1.12148.7.8.20 | NotificationalarmBatteryBoostmodeEnteredTrap | current | The system has increased the battery charge voltage in order to equalize the battery cells charging. When the criteria for stopping the battery equalizing is r… | |
| 1.3.6.1.4.1.12148.7.8.21 | NotificationalarmUserConfigurable1Trap | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … | |
| 1.3.6.1.4.1.12148.7.8.22 | NotificationalarmUserConfigurable2Trap | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … | |
| 1.3.6.1.4.1.12148.7.8.23 | NotificationalarmUserConfigurable3Trap | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … | |
| 1.3.6.1.4.1.12148.7.8.24 | NotificationalarmUserConfigurable4Trap | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … | |
| 1.3.6.1.4.1.12148.7.8.25 | NotificationalarmUserConfigurable5Trap | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … | |
| 1.3.6.1.4.1.12148.7.8.26 | NotificationalarmUserConfigurable6Trap | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … | |
| 1.3.6.1.4.1.12148.7.8.27 | NotificationalarmUserConfigurable7Trap | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … | |
| 1.3.6.1.4.1.12148.7.8.28 | NotificationalarmUserConfigurable8Trap | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … | |
| 1.3.6.1.4.1.12148.7.8.29 | NotificationalarmUserConfigurable9Trap | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … | |
| 1.3.6.1.4.1.12148.7.8.30 | NotificationalarmUserConfigurable10Trap | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … | |
| 1.3.6.1.4.1.12148.7.8.31 | NotificationalarmUserConfigurable11Trap | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … | |
| 1.3.6.1.4.1.12148.7.8.32 | NotificationalarmUserConfigurable12Trap | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … | |
| 1.3.6.1.4.1.12148.7.8.33 | NotificationalarmUserConfigurable13Trap | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … | |
| 1.3.6.1.4.1.12148.7.8.34 | NotificationalarmUserConfigurable14Trap | current | Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the … |