MIB Viewer

ENERGY-OBJECT-MIB

61 objects
Copyright (c) 2015 IETF Trust and the persons identified as authors of the code. All rights reserved. Redistribution and use in source and binary forms, with or without modification, is permitted pursuant to, and subject to the license terms contained in, the Simplified BSD License set forth in Section 4.c of the IETF Trust's Legal Provisions Relating to IETF Documents (http://trustee.ietf.org/license-info). This MIB is used to monitor power and energy in devices. The tables eoMeterCapabilitiesTable and eoPowerTable are a sparse extension of the eoTable from the ENERGY-OBJECT-CONTEXT-MIB. As a requirement, [RFC7461] SHOULD be implemented. Module Compliance of ENTITY-MIB v4 with respect to entity4CRCompliance MUST be supported which requires implementation of 4 MIB objects: entPhysicalIndex, entPhysicalClass, entPhysicalName and entPhysicalUUID.
Imported Objects
ENTITY-MIBentPhysicalIndex
IANAPowerStateSet-MIBPowerStateSet
RMON-MIBOwnerString
SNMPv2-CONFMODULE-COMPLIANCE NOTIFICATION-GROUP OBJECT-GROUP
SNMPv2-SMICounter32 Integer32 mib-2 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE TimeTicks Unsigned32
SNMPv2-TCRowStatus StorageType TEXTUAL-CONVENTION TimeInterval TimeStamp TruthValue
OIDNameAccessStatusDescription
1.3.6.1.2.1.229IdentityenergyObjectMibCopyright (c) 2015 IETF Trust and the persons identified as authors of the code. All rights reserved. Redistribution and use in source and binary forms, with o…
1.3.6.1.2.1.229.0NodeenergyObjectMibNotifs
1.3.6.1.2.1.229.0.1ScalareoPowerEnableStatusNotificationread-writecurrentThis object controls whether the system produces notifications for eoPowerStateChange. A false value will prevent these notifications from being generated.
1.3.6.1.2.1.229.0.2NotificationeoPowerStateChangecurrentThe SNMP entity generates the eoPowerStateChange when the values of eoPowerAdminState or eoPowerOperState, in the context of the Power State Set, have changed …
1.3.6.1.2.1.229.1NodeenergyObjectMibObjects
1.3.6.1.2.1.229.1.1TableeoMeterCapabilitiesTablenot-accessiblecurrentThis table is useful for helping applications determine the monitoring capabilities supported by the local management agents. It is possible for applications t…
1.3.6.1.2.1.229.1.1.1RoweoMeterCapabilitiesEntrynot-accessiblecurrentAn entry describes the metering capability of an Energy Object.
1.3.6.1.2.1.229.1.1.1.1ColumneoMeterCapabilityread-onlycurrentAn indication of the energy-monitoring capabilities supported by this agent. This object use a BITS syntax and indicates the MIB groups supported by the probe.…
1.3.6.1.2.1.229.1.2TableeoPowerTablenot-accessiblecurrentThis table lists Energy Objects.
1.3.6.1.2.1.229.1.2.1RoweoPowerEntrynot-accessiblecurrentAn entry describes the power usage of an Energy Object.
1.3.6.1.2.1.229.1.2.1.1ColumneoPowerread-onlycurrentThis object indicates the power measured for the Energy Object. For alternating current, this value is obtained as an average over fixed number of AC cycles. T…
1.3.6.1.2.1.229.1.2.1.2ColumneoPowerNameplateread-onlycurrentThis object indicates the rated maximum consumption for the fully populated Energy Object. The nameplate power requirements are the maximum power numbers given…
1.3.6.1.2.1.229.1.2.1.3ColumneoPowerUnitMultiplierread-onlycurrentThe magnitude of watts for the usage value in eoPower and eoPowerNameplate.
1.3.6.1.2.1.229.1.2.1.4ColumneoPowerAccuracyread-onlycurrentThis object indicates a percentage value, in hundredths of a percent, representing the assumed accuracy of the usage reported by eoPower. For example, the valu…
1.3.6.1.2.1.229.1.2.1.5ColumneoPowerMeasurementCaliberread-onlycurrentThis object specifies how the usage value reported by eoPower was obtained: - unavailable(1): Indicates that the usage is not available. In such a case, the eo…
1.3.6.1.2.1.229.1.2.1.6ColumneoPowerCurrentTyperead-onlycurrentThis object indicates whether the eoPower for the Energy Object reports alternating current 'ac', direct current 'dc', or that the current type is unknown.
1.3.6.1.2.1.229.1.2.1.7ColumneoPowerMeasurementLocalread-onlycurrentThis object indicates the source of power measurement and can be useful when modeling the power usage of attached devices. The power measurement can be perform…
1.3.6.1.2.1.229.1.2.1.8ColumneoPowerAdminStateread-writecurrentThis object specifies the desired Power State and the Power State Set for the Energy Object. Note that other(0) is not a Power State Set and unknown(255) is no…
1.3.6.1.2.1.229.1.2.1.9ColumneoPowerOperStateread-onlycurrentThis object specifies the current operational Power State and the Power State Set for the Energy Object. other(0) is not a Power State Set and unknown(255) is …
1.3.6.1.2.1.229.1.2.1.10ColumneoPowerStateEnterReasonread-writecurrentThis string object describes the reason for the eoPowerAdminState transition. Alternatively, this string may contain with the entity that configured this Energ…
1.3.6.1.2.1.229.1.3TableeoPowerStateTablenot-accessiblecurrentThis table enumerates the maximum power usage, in watts, for every single supported Power State of each Energy Object. This table has cross-reference with the …
1.3.6.1.2.1.229.1.3.1RoweoPowerStateEntrynot-accessiblecurrentA eoPowerStateEntry extends a corresponding eoPowerEntry. This entry displays max usage values at every single possible Power State supported by the Energy Obj…
1.3.6.1.2.1.229.1.3.1.1ColumneoPowerStateIndexnot-accessiblecurrentThis object specifies the index of the Power State of the Energy Object within a Power State Set. The semantics of the specific Power State can be obtained fro…
1.3.6.1.2.1.229.1.3.1.2ColumneoPowerStateMaxPowerread-onlycurrentThis object indicates the maximum power for the Energy Object at the particular Power State. This value is specified in SI units of watts with the magnitude of…
1.3.6.1.2.1.229.1.3.1.3ColumneoPowerStatePowerUnitMultiplierread-onlycurrentThe magnitude of watts for the usage value in eoPowerStateMaxPower.
1.3.6.1.2.1.229.1.3.1.4ColumneoPowerStateTotalTimeread-onlycurrentThis object indicates the total time in hundredths of a second that the Energy Object has been in this power state since the last reset, as specified in the sy…
1.3.6.1.2.1.229.1.3.1.5ColumneoPowerStateEnterCountread-onlycurrentThis object indicates how often the Energy Object has entered this power state, since the last reset of the device as specified in the sysUpTime.
1.3.6.1.2.1.229.1.4TableeoEnergyParametersTablenot-accessiblecurrentThis table is used to configure the parameters for energy measurement collection in the table eoEnergyTable. This table allows the configuration of different m…
1.3.6.1.2.1.229.1.4.1RoweoEnergyParametersEntrynot-accessiblecurrentAn entry controls an energy measurement in eoEnergyTable.
1.3.6.1.2.1.229.1.4.1.2ColumneoEnergyParametersIndexnot-accessiblecurrentThis object specifies the index of the Energy Parameters setting for collection of energy measurements for an Energy Object. An Energy Object can have multiple…
1.3.6.1.2.1.229.1.4.1.3ColumneoEnergyParametersIntervalLengthread-createcurrentThis object indicates the length of time in hundredths of a second over which to compute the average eoEnergyConsumed measurement in the eoEnergyTable table. T…
1.3.6.1.2.1.229.1.4.1.4ColumneoEnergyParametersIntervalNumberread-createcurrentThe number of intervals maintained in the eoEnergyTable. Each interval is characterized by a specific eoEnergyCollectionStartTime, used as an index to the tabl…
1.3.6.1.2.1.229.1.4.1.5ColumneoEnergyParametersIntervalModeread-createcurrentA control object to define the mode of interval calculation for the computation of the average eoEnergyConsumed or eoEnergyProvided measurement in the eoEnergy…
1.3.6.1.2.1.229.1.4.1.6ColumneoEnergyParametersIntervalWindowread-createcurrentThe length of the duration window between the starting time of one sliding window and the next starting time in hundredths of seconds, used to compute the aver…
1.3.6.1.2.1.229.1.4.1.7ColumneoEnergyParametersSampleRateread-createcurrentThe sampling rate, in milliseconds, at which the Energy Object should poll power usage in order to compute the average eoEnergyConsumed, eoEnergyProvided measu…
1.3.6.1.2.1.229.1.4.1.8ColumneoEnergyParametersStorageTyperead-createcurrentThis variable indicates the storage type for this row.
1.3.6.1.2.1.229.1.4.1.9ColumneoEnergyParametersStatusread-createcurrentThe status of this row. The eoEnergyParametersStatus is used to start or stop energy usage logging. An entry status may not be active(1) unless all objects in …
1.3.6.1.2.1.229.1.5TableeoEnergyTablenot-accessiblecurrentThis table lists Energy Object energy measurements. Entries in this table are only created if the corresponding value of object eoPowerMeasurementCaliber is ac…
1.3.6.1.2.1.229.1.5.1RoweoEnergyEntrynot-accessiblecurrentAn entry describing energy measurements.
1.3.6.1.2.1.229.1.5.1.1ColumneoEnergyCollectionStartTimenot-accessiblecurrentThe time (in hundredths of a second) since the network management portion of the system was last re-initialized, as specified in the sysUpTime RFC 3418. This o…
1.3.6.1.2.1.229.1.5.1.2ColumneoEnergyConsumedread-onlycurrentThis object indicates the energy consumed in units of watt-hours for the Energy Object over the defined interval. This value is specified in the common billing…
1.3.6.1.2.1.229.1.5.1.3ColumneoEnergyProvidedread-onlycurrentThis object indicates the energy produced in units of watt-hours for the Energy Object over the defined interval. This value is specified in the common billing…
1.3.6.1.2.1.229.1.5.1.4ColumneoEnergyStoredread-onlycurrentThis object indicates the difference of the energy consumed and energy produced for an Energy Object in units of watt-hours for the Energy Object over the defi…
1.3.6.1.2.1.229.1.5.1.5ColumneoEnergyUnitMultiplierread-onlycurrentThis object is the magnitude of watt-hours for the energy field in eoEnergyConsumed, eoEnergyProvided, eoEnergyStored, eoEnergyMaxConsumed, and eoEnergyMaxProd…
1.3.6.1.2.1.229.1.5.1.6ColumneoEnergyAccuracyread-onlycurrentThis object indicates a percentage accuracy, in hundredths of a percent, of Energy usage reporting. eoEnergyAccuracy is applicable to all Energy measurements i…
1.3.6.1.2.1.229.1.5.1.7ColumneoEnergyMaxConsumedread-onlycurrentThis object is the maximum energy observed in eoEnergyConsumed since the monitoring started or was reinitialized. This value is specified in the common billing…
1.3.6.1.2.1.229.1.5.1.8ColumneoEnergyMaxProducedread-onlycurrentThis object is the maximum energy ever observed in eoEnergyEnergyProduced since the monitoring started. This value is specified in the units of watt-hours with…
1.3.6.1.2.1.229.1.5.1.9ColumneoEnergyDiscontinuityTimeread-onlycurrentThe value of sysUpTime RFC 3418 on the most recent occasion at which any one or more of this entity's energy counters in this table suffered a discontinuity: e…
1.3.6.1.2.1.229.2NodeenergyObjectMibConform
1.3.6.1.2.1.229.2.1NodeenergyObjectMibCompliances
1.3.6.1.2.1.229.2.1.1ComplianceenergyObjectMibFullCompliancecurrentWhen this MIB is implemented with support for read-create, then such an implementation can claim full compliance. Such devices can then be both monitored and c…
1.3.6.1.2.1.229.2.1.2ComplianceenergyObjectMibReadOnlyCompliancecurrentWhen this MIB is implemented without support for read-create (i.e., in read-only mode), then such an implementation can claim read-only compliance. Such a devi…
1.3.6.1.2.1.229.2.2NodeenergyObjectMibGroups
1.3.6.1.2.1.229.2.2.1GroupenergyObjectMibTableGroupcurrentThis group contains the collection of all the objects related to the Energy Object.
1.3.6.1.2.1.229.2.2.2GroupenergyObjectMibStateTableGroupcurrentThis group contains the collection of all the objects related to the Power State.
1.3.6.1.2.1.229.2.2.3GroupenergyObjectMibEnergyParametersTableGroupcurrentThis group contains the collection of all the objects related to the configuration of the Energy Table.
1.3.6.1.2.1.229.2.2.4GroupenergyObjectMibEnergyTableGroupcurrentThis group contains the collection of all the objects related to the Energy Table.
1.3.6.1.2.1.229.2.2.5GroupenergyObjectMibMeterCapabilitiesTableGroupcurrentThis group contains the object indicating the capability of the Energy Object
1.3.6.1.2.1.229.2.2.6GroupeoPowerEnableStatusNotificationGroupcurrentThe collection of objects that are used to enable notification.
1.3.6.1.2.1.229.2.2.7GroupenergyObjectMibNotifGroupcurrentThis group contains the notifications for the Monitoring and Control MIB for Power and Energy.
Type Definitions
NameSyntaxStatusDescription
UnitMultiplierINTEGER { yocto(-24), zepto(-21), atto(-18), femto(-15), pico(-12), nano(-9), micro(-6), milli(-3), units(0), kilo(3), mega(6), giga(9), tera(12), peta(15), exa(18), zetta(21), yotta(24) }currentThe Unit Multiplier is an integer value that represents the IEEE 61850 Annex A units multiplier associated with the integer units used to measure the power or energy. For example, when used with eoPowerUnitMultiplier, -…