The MIB module for the Racktivity Devices
Imported Objects
SNMPv2-CONFMODULE-COMPLIANCE NOTIFICATION-GROUP OBJECT-GROUP
SNMPv2-SMIenterprises Integer32 IpAddress MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE TimeTicks Unsigned32
SNMPv2-TCDisplayString MacAddress TEXTUAL-CONVENTION
OIDNameAccessStatusDescription
1.3.6.1.4.1.34097Noderacktivity
1.3.6.1.4.1.34097.9IdentityesRACKTIVITYMIBThe MIB module for the Racktivity Devices
1.3.6.1.4.1.34097.9.0NoderacktivityNotif
1.3.6.1.4.1.34097.9.0.16NotificationerrorValueTooHighRaisedcurrentThis trap is sent when an element goes above the specified error threshold indicating the maximum value for this element
1.3.6.1.4.1.34097.9.0.17NotificationerrorValueTooLowRaisedcurrentThis trap is sent when an element goes below the specified error threshold indicating the minimum value for this element
1.3.6.1.4.1.34097.9.0.18NotificationerrorRaisedcurrentThis trap is sent when an element gets into an error state
1.3.6.1.4.1.34097.9.0.19NotificationerrorValueTooHighClearedcurrentThis trap is sent when an element goes below the specified error threshold indicating the maximum value for this element
1.3.6.1.4.1.34097.9.0.20NotificationerrorValueTooLowClearedcurrentThis trap is sent when an element goes above the specified error threshold indicating the minimum value for this element
1.3.6.1.4.1.34097.9.0.21NotificationerrorClearedcurrentThis trap is sent when an element recovers from an error state
1.3.6.1.4.1.34097.9.0.48NotificationwarningValueTooHighRaisedcurrentThis trap is sent when an element goes above the specified warning threshold indicating the maximum value for this element
1.3.6.1.4.1.34097.9.0.49NotificationwarningValueTooLowRaisedcurrentThis trap is sent when an element goes below the specified warning threshold indicating the minimum value for this element
1.3.6.1.4.1.34097.9.0.50NotificationwarningRaisedcurrentThis trap is sent when an element gets into an warning state
1.3.6.1.4.1.34097.9.0.51NotificationwarningValueTooHighClearedcurrentThis trap is sent when an element goes below the specified warning threshold indicating the maximum value for this element
1.3.6.1.4.1.34097.9.0.52NotificationwarningValueTooLowClearedcurrentThis trap is sent when an element goes above the specified warning threshold indicating the minimum value for this element
1.3.6.1.4.1.34097.9.0.53NotificationwarningClearedcurrentThis trap is sent when an element recovers from an warning state
1.3.6.1.4.1.34097.9.0.54NotificationwarningMicroInterruptioncurrentThis event is raised when a micro interruption is detected above a threshold time
1.3.6.1.4.1.34097.9.0.55NotificationwarningPhaseShiftcurrentThis event is raised when a phase shift is detected above a threshold
1.3.6.1.4.1.34097.9.0.80NotificationinfoValueTooHighRaisedcurrentThis trap is sent when an element goes above a specified threshold indicating the maximum value for this element
1.3.6.1.4.1.34097.9.0.81NotificationinfoValueTooLowRaisedcurrentThis trap is sent when an element goes below a specified threshold indicating the minimum value for this element
1.3.6.1.4.1.34097.9.0.82NotificationinfoRaisedcurrentThis trap is sent when an element gets into a specific state
1.3.6.1.4.1.34097.9.0.83NotificationinfoValueTooHighClearedcurrentThis trap is sent when an element goes below a specified threshold indicating the maximum value for this element
1.3.6.1.4.1.34097.9.0.84NotificationinfoValueTooLowClearedcurrentThis trap is sent when an element goes above a specified threshold indicating the minimum value for this element
1.3.6.1.4.1.34097.9.0.85NotificationinfoClearedcurrentThis trap is sent when an element recovers from a specific state
1.3.6.1.4.1.34097.9.0.96NotificationinfoPortStateChangedcurrentThis trap is sent when a port changes state for any reason
1.3.6.1.4.1.34097.9.0.97NotificationinfoResetcurrentThis trap is sent when a module is reboot
1.3.6.1.4.1.34097.9.0.98NotificationinfoUpgradecurrentThis trap is sent when upgrade or downgrade of firmware is completed
1.3.6.1.4.1.34097.9.0.99NotificationinfoPortSchedulecurrentThis trap is sent when a port changes state because of a scheduling
1.3.6.1.4.1.34097.9.0.100NotificationinfoHeartbeatcurrentThis trap is sent when a heartbeat has occurred
1.3.6.1.4.1.34097.9.2NodeesRacktivityConformance
1.3.6.1.4.1.34097.9.2.1NodeesRacktivityMIBGroups
1.3.6.1.4.1.34097.9.2.1.1GroupesRacktivityMIBGroupcurrentAll accessible objects in a Racktivity device
1.3.6.1.4.1.34097.9.2.1.2GroupesRacktivityNotificationGroupcurrentAll notification that can be sent out by a Racktivity device
1.3.6.1.4.1.34097.9.2.2NodeesRacktivityMIBCompliances
1.3.6.1.4.1.34097.9.2.2.1ComplianceesRacktivityConpliancecurrentThe compliance statements for a Racktivity device.
1.3.6.1.4.1.34097.9.65NodeesnModule
1.3.6.1.4.1.34097.9.65.1TableeESNTablenot-accessiblecurrentTemperature Humidity Presure Airflow Waterleak
1.3.6.1.4.1.34097.9.65.1.1RoweESNEntrynot-accessiblecurrentTemperature Humidity Presure Airflow Waterleak
1.3.6.1.4.1.34097.9.65.1.1.1ColumnaGeneralModuleStatusread-onlycurrentGeneral status of a module.
1.3.6.1.4.1.34097.9.65.1.1.2ColumnaSpecificModuleStatusread-onlycurrentSpecific status of a module.
1.3.6.1.4.1.34097.9.65.1.1.3ColumnaCurrentTimeread-writecurrentGets or sets the current time (not possible when NTP is enabled). (unit: UNIX)
1.3.6.1.4.1.34097.9.65.1.1.4ColumnaVoltageread-onlycurrentGets the voltage of a power module. (unit: 0.01V)
1.3.6.1.4.1.34097.9.65.1.1.8ColumnaStatePortCurread-onlycurrentGets the current state of an outlet. To toggle an outlet use PORTSTAT (CLI) or pPortstate (SNMP) (GUID 10035) instead.
1.3.6.1.4.1.34097.9.65.1.1.11ColumnaTemperatureread-onlycurrentGets the current temperature of a temperature sensor. (unit: 0.1K)
1.3.6.1.4.1.34097.9.65.1.1.12ColumnaHumidityread-onlycurrentGets the relative humidity. (unit: 0.1RH)
1.3.6.1.4.1.34097.9.65.1.1.23ColumnaAirflowread-onlycurrentGets the current airflow level. (unit: 0.1m/s)
1.3.6.1.4.1.34097.9.65.1.1.25ColumnaDewPointread-onlycurrentGets the current dewpoint. Taking the current humidity into consideration, condensation will occur if the temperature drops below this level. (unit: 0.1K)
1.3.6.1.4.1.34097.9.65.1.1.26ColumnaPressureread-onlycurrentGets the atmospheric pressure. (unit: 0.1hPa)
1.3.6.1.4.1.34097.9.65.1.1.27ColumnaAnalogueInputread-onlycurrentGets the value of an analog input (voltage). (unit: mV)
1.3.6.1.4.1.34097.9.65.1.1.28ColumnaWaterleakread-onlycurrentGets the current state of the water leak sensor.
1.3.6.1.4.1.34097.9.65.1.1.29ColumnaMotionDetectedread-onlycurrentGets or resets whether motion has been detected.
1.3.6.1.4.1.34097.9.65.1.1.30ColumnaIOPortread-onlycurrentGets the state of a digital input.
1.3.6.1.4.1.34097.9.65.1.1.41ColumnaHighCurrentread-onlycurrentThe current for high values (unit: 0.1A)
1.3.6.1.4.1.34097.9.65.1.1.43ColumnaHighPowerread-onlycurrentThe power for high values (unit: 0.01kW)
1.3.6.1.4.1.34097.9.65.1.1.10001ColumnaModuleNameread-writecurrentGets, sets or defaults the module name.
1.3.6.1.4.1.34097.9.65.1.1.10002ColumnaFirmwareVersionread-onlycurrentGets the version of the module's firmware.
1.3.6.1.4.1.34097.9.65.1.1.10003ColumnaHardwareVersionread-onlycurrentGets the version of a module's hardware.
1.3.6.1.4.1.34097.9.65.1.1.10004ColumnaFirmwareIDread-onlycurrentGets the ID of the module's firmware.
1.3.6.1.4.1.34097.9.65.1.1.10005ColumnaHardwareIDread-onlycurrentGets the ID of a module's hardware.
1.3.6.1.4.1.34097.9.65.1.1.10032ColumnaDisplayTimeOnread-writecurrentGets, sets or defaults the display sleep timer. If the display is inactive for longer than this time, the display turns off to save power. Time is in minutes. …
1.3.6.1.4.1.34097.9.65.1.1.10047ColumnaMaxVoltageWarningread-writecurrentGets, sets or defaults the maximum voltage warning level. (unit: 0.01V)
1.3.6.1.4.1.34097.9.65.1.1.10049ColumnaMinVoltageWarningread-writecurrentGets, sets or defaults the minimum voltage warning level. (unit: 0.01V)
1.3.6.1.4.1.34097.9.65.1.1.10052ColumnaMinTemperatureWarningread-writecurrentGets, sets or defaults the minimum temperature warning level (use DEF accessor to reset). (unit: 0.1K)
1.3.6.1.4.1.34097.9.65.1.1.10053ColumnaMaxTemperatureWarningread-writecurrentGets, sets or defaults the maximum temperature warning level (use DEF accessor to reset). (unit: 0.1K)
1.3.6.1.4.1.34097.9.65.1.1.10054ColumnaMinHumidityWarningread-writecurrentGets, sets or defaults the minimum relative humidity warning level (use DEF accessor to reset). (unit: 0.1RH)
1.3.6.1.4.1.34097.9.65.1.1.10055ColumnaMaxHumidityWarningread-writecurrentGets, sets or defaults the maximum relative humidity warning level (use DEF accessor to reset). (unit: 0.1RH)
1.3.6.1.4.1.34097.9.65.1.1.10078ColumnaCurrentWarningEventread-writecurrentEnables or disables the SNMP trap if the outlet current warning level is exceeded.
1.3.6.1.4.1.34097.9.65.1.1.10080ColumnaPowerWarningEventread-writecurrentEnables or disables the SNMP trap if the power warning level is exceeded.
1.3.6.1.4.1.34097.9.65.1.1.10086ColumnaVoltageWarningEventread-writecurrentEnables or disables the SNMP trap if the voltage warning level is exceeded.
1.3.6.1.4.1.34097.9.65.1.1.10087ColumnaTemperatureWarningEventread-writecurrentEnables or disables the SNMP trap if the temperature warning level is exceeded.
1.3.6.1.4.1.34097.9.65.1.1.10088ColumnaHumidityWarningEventread-writecurrentEnables or disables the SNMP trap if the humidity warning level is exceeded.
1.3.6.1.4.1.34097.9.65.1.1.10092ColumnaDewPointWarningread-writecurrentGets, sets or defaults the dewpoint warning level. If the temperature difference between the current temperature and the dewpoint temperature drops below this …
1.3.6.1.4.1.34097.9.65.1.1.10093ColumnaDewPointWarningEventread-writecurrentEnables or disables the SNMP trap if the dewpoint warning level is exceeded.
1.3.6.1.4.1.34097.9.65.1.1.10094ColumnaDewPointViolationEventread-writecurrentEnables or disables the SNMP trap if the dewpoint temperature is reached.
1.3.6.1.4.1.34097.9.65.1.1.10095ColumnaPressureWarningEventread-writecurrentEnables or disables the SNMP trap if the atmospheric pressure warning level is exceeded.
1.3.6.1.4.1.34097.9.65.1.1.10096ColumnaMinPressureWarningread-writecurrentGets, sets or defaults the minimum atmospheric pressure warning level. (unit: 0.1hPa)
1.3.6.1.4.1.34097.9.65.1.1.10097ColumnaMaxPressureWarningread-writecurrentGets, sets or defaults the maximum atmospheric pressure warning level. (unit: 0.1hPa)
1.3.6.1.4.1.34097.9.65.1.1.10098ColumnaDisplayBrightnessread-writecurrentGets, sets or defaults the display brightness (if supported).
1.3.6.1.4.1.34097.9.65.1.1.10107ColumnaMotionSensitivityread-writecurrentGets, sets or defaults the sensitivity of a motion sensor.
1.3.6.1.4.1.34097.9.65.1.1.10109ColumnaExternalSensorLabelread-writecurrentGets, sets or defaults the external sensor label. External sensors can be connected to Energy Sensors.
1.3.6.1.4.1.34097.9.65.1.1.10110ColumnaRelayLabelread-writecurrentGets, sets or defaults an Energy Sensor relay label.
1.3.6.1.4.1.34097.9.65.1.1.10111ColumnaMinAnalogueInputWarningread-writecurrentGets, sets or defaults the lower warning level for an analog input. A warning is generated if this level is exceeded. (unit: mV)
1.3.6.1.4.1.34097.9.65.1.1.10112ColumnaMaxAnalogueInputWarningread-writecurrentGets, sets or defaults the upper warning level for an analog input. A warning is generated if this level is exceeded.
1.3.6.1.4.1.34097.9.65.1.1.10113ColumnaWaterleakWarningread-writecurrentGets, sets or defaults the water leak detection state (0 = disabled, other values = enabled).
1.3.6.1.4.1.34097.9.65.1.1.10114ColumnaMinAirflowWarningread-writecurrentGets, sets or defaults the minimum warning level for an airflow sensor. A warning is generated if this level is exceeded.
1.3.6.1.4.1.34097.9.65.1.1.10115ColumnaMaxAirflowWarningread-writecurrentGets, sets or defaults the maximum warning level for an airflow sensor. A warning is generated if this level is exceeded.
1.3.6.1.4.1.34097.9.65.1.1.10116ColumnaAnalogueInputWarningEventread-writecurrentEnables or disables the SNMP trap if the analog input warning level is exceeded.
1.3.6.1.4.1.34097.9.65.1.1.10117ColumnaWaterleakWarningEventread-writecurrentEnables or disables the SNMP trap if a water leak is detected.
1.3.6.1.4.1.34097.9.65.1.1.10118ColumnaAirflowWarningEventread-writecurrentEnables or disables the SNMP trap if the airflow warning level is exceeded.
1.3.6.1.4.1.34097.9.65.1.1.10119ColumnaRelayAssertActionEventread-writecurrentEnables or disables the SNMP trap if an Energy Sensor relay is asserted.
1.3.6.1.4.1.34097.9.65.1.1.10120ColumnaRelayDeassertActionEventread-writecurrentEnables or disables the SNMP trap if an Energy Sensor relay is deasserted.
1.3.6.1.4.1.34097.9.65.1.1.10141ColumnaMotionWarningread-writecurrentGets, sets or defaults the motion warning threshold.
1.3.6.1.4.1.34097.9.65.1.1.10149ColumnaMotionWarningEventread-writecurrentEnables or disables the SNMP trap if the motion warning threshold is exceeded.
1.3.6.1.4.1.34097.9.65.1.1.10150ColumnaDeviceIDread-onlycurrentThe ID of the device.
1.3.6.1.4.1.34097.9.65.1.1.10151ColumnaDeviceVersionread-onlycurrentThe version of the device.
1.3.6.1.4.1.34097.9.65.1.1.10152ColumnaSysNameread-onlycurrentThe full name of the device.
1.3.6.1.4.1.34097.9.65.1.1.10165ColumnaMaxHighCurrentWarningread-writecurrentGets sets or defaults the maximum high current warning level. (unit: 0.1A)
1.3.6.1.4.1.34097.9.65.1.1.10176ColumnaMinHighCurrentWarningread-writecurrentGets sets or defaults the minimum high current warning level. (unit: 0.1A)
1.3.6.1.4.1.34097.9.65.1.1.10177ColumnaMinHighPowerWarningread-writecurrentGets sets or defaults the power min high current warning level. (unit: 0.01kW)
1.3.6.1.4.1.34097.9.65.1.1.10178ColumnaMaxHighPowerWarningread-writecurrentGets sets or defaults the power max high current warning level. (unit: 0.01kW)
1.3.6.1.4.1.34097.9.65.1.1.10192ColumnaIOPortWarningEventread-writecurrentEnables or disables the SNMP trap if the IO Port change state.
1.3.6.1.4.1.34097.9.65.1.1.65537ColumnesnIndexnot-accessiblecurrentIndex for the selected ESN Module
1.3.6.1.4.1.34097.9.65.1.1.65538ColumnesnModuleIndexnot-accessiblecurrentSelected ESN Module
1.3.6.1.4.1.34097.9.66NodethreephasepowerModule
1.3.6.1.4.1.34097.9.66.1TableeThreePhasePowerTablenot-accessiblecurrentNO_INFO
1.3.6.1.4.1.34097.9.66.1.1RoweThreePhasePowerEntrynot-accessiblecurrentNO_INFO
1.3.6.1.4.1.34097.9.66.1.1.65537ColumnthreephasepowerIndexnot-accessiblecurrentIndex for the selected ThreePhasePower Module
1.3.6.1.4.1.34097.9.66.1.1.65538ColumnthreephasepowerModuleIndexnot-accessiblecurrentSelected ThreePhasePower Module
1.3.6.1.4.1.34097.9.68NodedisplaymoduleModule
1.3.6.1.4.1.34097.9.68.1TableeDisplayModuleTablenot-accessiblecurrentNO_INFO
1.3.6.1.4.1.34097.9.68.1.1RoweDisplayModuleEntrynot-accessiblecurrentNO_INFO
1.3.6.1.4.1.34097.9.68.1.1.1ColumndGeneralModuleStatusread-onlycurrentGeneral status of a module.
1.3.6.1.4.1.34097.9.68.1.1.2ColumndSpecificModuleStatusread-onlycurrentSpecific status of a module.
1.3.6.1.4.1.34097.9.68.1.1.3ColumndCurrentTimeread-writecurrentGets or sets the current time (not possible when NTP is enabled). (unit: UNIX)
1.3.6.1.4.1.34097.9.68.1.1.11ColumndTemperatureread-onlycurrentGets the current temperature of a temperature sensor. (unit: 0.1K)
1.3.6.1.4.1.34097.9.68.1.1.24ColumndTimeOnlineread-onlycurrentGets the amount of seconds since the last reset. (unit: s)
1.3.6.1.4.1.34097.9.68.1.1.10001ColumndModuleNameread-writecurrentGets, sets or defaults the module name.
1.3.6.1.4.1.34097.9.68.1.1.10002ColumndFirmwareVersionread-onlycurrentGets the version of the module's firmware.
1.3.6.1.4.1.34097.9.68.1.1.10003ColumndHardwareVersionread-onlycurrentGets the version of a module's hardware.
1.3.6.1.4.1.34097.9.68.1.1.10004ColumndFirmwareIDread-onlycurrentGets the ID of the module's firmware.
1.3.6.1.4.1.34097.9.68.1.1.10005ColumndHardwareIDread-onlycurrentGets the ID of a module's hardware.
1.3.6.1.4.1.34097.9.68.1.1.10052ColumndMinTemperatureWarningread-writecurrentGets, sets or defaults the minimum temperature warning level (use DEF accessor to reset). (unit: 0.1K)
1.3.6.1.4.1.34097.9.68.1.1.10053ColumndMaxTemperatureWarningread-writecurrentGets, sets or defaults the maximum temperature warning level (use DEF accessor to reset). (unit: 0.1K)
1.3.6.1.4.1.34097.9.68.1.1.10237ColumndDisplayAllDevicesread-writecurrentIf a display need to show all devices or just a small list
1.3.6.1.4.1.34097.9.68.1.1.65537ColumndisplaymoduleIndexnot-accessiblecurrentIndex for the selected DisplayModule Module
1.3.6.1.4.1.34097.9.68.1.1.65538ColumndisplaymoduleModuleIndexnot-accessiblecurrentSelected DisplayModule Module
1.3.6.1.4.1.34097.9.69NodeenergymonitorModule
1.3.6.1.4.1.34097.9.69.1TableeEnergyMonitorTablenot-accessiblecurrentNO_INFO
1.3.6.1.4.1.34097.9.69.1.1RoweEnergyMonitorEntrynot-accessiblecurrentNO_INFO
1.3.6.1.4.1.34097.9.69.1.1.1ColumneGeneralModuleStatusread-onlycurrentGeneral status of a module.
1.3.6.1.4.1.34097.9.69.1.1.2ColumneSpecificModuleStatusread-onlycurrentSpecific status of a module.
1.3.6.1.4.1.34097.9.69.1.1.3ColumneCurrentTimeread-writecurrentGets or sets the current time (not possible when NTP is enabled). (unit: UNIX)
1.3.6.1.4.1.34097.9.69.1.1.4ColumneVoltageread-onlycurrentGets the voltage of a power module. (unit: 0.01V)
1.3.6.1.4.1.34097.9.69.1.1.5ColumneFrequencyread-onlycurrentGets the frequency of the input voltage of a power module. (unit: 0.001Hz)
1.3.6.1.4.1.34097.9.69.1.1.6ColumneCurrentread-onlycurrentGets the current of an outlet. (unit: 0.001A)
1.3.6.1.4.1.34097.9.69.1.1.7ColumnePowerread-onlycurrentGets the power of an outlet. (unit: W)
1.3.6.1.4.1.34097.9.69.1.1.9ColumneActiveEnergyread-onlycurrentGets the energy used by an outlet. (unit: 0.001kWh)
1.3.6.1.4.1.34097.9.69.1.1.10ColumneApparentEnergyread-onlycurrentGets the apparent energy used by an outlet. (unit: 0.001kVAh)
1.3.6.1.4.1.34097.9.69.1.1.11ColumneTemperatureread-onlycurrentGets the current temperature of a temperature sensor. (unit: 0.1K)
1.3.6.1.4.1.34097.9.69.1.1.15ColumneApparentPowerread-onlycurrentGets the apparent power of an outlet. (unit: VA)
1.3.6.1.4.1.34097.9.69.1.1.16ColumnePowerFactorread-onlycurrentGets the power factor of an outlet. (unit: %)
1.3.6.1.4.1.34097.9.69.1.1.17ColumneTotalCurrentread-onlycurrentGets the total current of a power module. (unit: 0.001A)
1.3.6.1.4.1.34097.9.69.1.1.18ColumneTotalRealPowerread-onlycurrentGets the total power level of a power module. (unit: W)
1.3.6.1.4.1.34097.9.69.1.1.19ColumneTotalApparentPowerread-onlycurrentGets the total apparent power of a power module. (unit: VA)
1.3.6.1.4.1.34097.9.69.1.1.20ColumneTotalActiveEnergyread-onlycurrentGets the total energy of a power module. (unit: 0.001kWh)
1.3.6.1.4.1.34097.9.69.1.1.21ColumneTotalApparentEnergyread-onlycurrentGets the total apparent energy of a power module. (unit: 0.001kVAh)
1.3.6.1.4.1.34097.9.69.1.1.22ColumneTotalPowerFactorread-onlycurrentGets the total power factor of a power module. (unit: %)
1.3.6.1.4.1.34097.9.69.1.1.24ColumneTimeOnlineread-onlycurrentGets the amount of seconds since the last reset. (unit: s)
1.3.6.1.4.1.34097.9.69.1.1.50ColumneTotalHarmonicDistortionread-onlycurrenttotal harmonic distortion - outlet (unit: 0.1%)
1.3.6.1.4.1.34097.9.69.1.1.10001ColumneModuleNameread-writecurrentGets, sets or defaults the module name.
1.3.6.1.4.1.34097.9.69.1.1.10002ColumneFirmwareVersionread-onlycurrentGets the version of the module's firmware.
1.3.6.1.4.1.34097.9.69.1.1.10003ColumneHardwareVersionread-onlycurrentGets the version of a module's hardware.
1.3.6.1.4.1.34097.9.69.1.1.10004ColumneFirmwareIDread-onlycurrentGets the ID of the module's firmware.
1.3.6.1.4.1.34097.9.69.1.1.10005ColumneHardwareIDread-onlycurrentGets the ID of a module's hardware.
1.3.6.1.4.1.34097.9.69.1.1.10039ColumneMaxCurrentWarningread-writecurrentGets, sets or defaults the maximum current warning level of an outlet. (unit: 0.001A)
1.3.6.1.4.1.34097.9.69.1.1.10041ColumneMaxPowerWarningread-writecurrentGets, sets or defaults the maximum power warning level of an outlet. (unit: W)
1.3.6.1.4.1.34097.9.69.1.1.10043ColumneMaxTotalCurrentWarningread-writecurrentGets, sets or defaults the total maximum current warning level of a power module. (unit: 0.001A)
1.3.6.1.4.1.34097.9.69.1.1.10045ColumneMaxTotalPowerWarningread-writecurrentGets, sets or defaults the maximum total power warning level. (unit: W)
1.3.6.1.4.1.34097.9.69.1.1.10047ColumneMaxVoltageWarningread-writecurrentGets, sets or defaults the maximum voltage warning level. (unit: 0.01V)
1.3.6.1.4.1.34097.9.69.1.1.10049ColumneMinVoltageWarningread-writecurrentGets, sets or defaults the minimum voltage warning level. (unit: 0.01V)
1.3.6.1.4.1.34097.9.69.1.1.10052ColumneMinTemperatureWarningread-writecurrentGets, sets or defaults the minimum temperature warning level (use DEF accessor to reset). (unit: 0.1K)
1.3.6.1.4.1.34097.9.69.1.1.10053ColumneMaxTemperatureWarningread-writecurrentGets, sets or defaults the maximum temperature warning level (use DEF accessor to reset). (unit: 0.1K)
1.3.6.1.4.1.34097.9.69.1.1.10078ColumneCurrentWarningEventread-writecurrentEnables or disables the SNMP trap if the outlet current warning level is exceeded.
1.3.6.1.4.1.34097.9.69.1.1.10080ColumnePowerWarningEventread-writecurrentEnables or disables the SNMP trap if the power warning level is exceeded.
1.3.6.1.4.1.34097.9.69.1.1.10082ColumneTotalCurrentWarningEventread-writecurrentEnables or disables the SNMP trap if the total outlet current warning level is exceeded.
1.3.6.1.4.1.34097.9.69.1.1.10084ColumneTotalPowerWarningEventread-writecurrentEnables or disables the SNMP trap if the total power warning level is exceeded.
1.3.6.1.4.1.34097.9.69.1.1.10086ColumneVoltageWarningEventread-writecurrentEnables or disables the SNMP trap if the voltage warning level is exceeded.
1.3.6.1.4.1.34097.9.69.1.1.10087ColumneTemperatureWarningEventread-writecurrentEnables or disables the SNMP trap if the temperature warning level is exceeded.
1.3.6.1.4.1.34097.9.69.1.1.10135ColumneMicroIntTimeThresholdread-writecurrentThe minimum time the voltage must be interrupted before it is seen as a micro interruption (unit: 0.1ms)
1.3.6.1.4.1.34097.9.69.1.1.10136ColumneMicroIntEventread-writecurrentEnables or disables the SNMP trap if a microinterruption on the voltage is detected.
1.3.6.1.4.1.34097.9.69.1.1.65537ColumnenergymonitorIndexnot-accessiblecurrentIndex for the selected EnergyMonitor Module
1.3.6.1.4.1.34097.9.69.1.1.65538ColumnenergymonitorModuleIndexnot-accessiblecurrentSelected EnergyMonitor Module
1.3.6.1.4.1.34097.9.77NodemasterModule
1.3.6.1.4.1.34097.9.77.1TableeMasterTablenot-accessiblecurrentNO_INFO
1.3.6.1.4.1.34097.9.77.1.1RoweMasterEntrynot-accessiblecurrentNO_INFO
1.3.6.1.4.1.34097.9.77.1.1.1ColumnmGeneralModuleStatusread-onlycurrentGeneral status of a module.
1.3.6.1.4.1.34097.9.77.1.1.2ColumnmSpecificModuleStatusread-onlycurrentSpecific status of a module.
1.3.6.1.4.1.34097.9.77.1.1.3ColumnmCurrentTimeread-writecurrentGets or sets the current time (not possible when NTP is enabled). (unit: UNIX)
1.3.6.1.4.1.34097.9.77.1.1.4ColumnmVoltageread-onlycurrentGets the voltage of a power module. (unit: 0.01V)
1.3.6.1.4.1.34097.9.77.1.1.11ColumnmTemperatureread-onlycurrentGets the current temperature of a temperature sensor. (unit: 0.1K)
1.3.6.1.4.1.34097.9.77.1.1.14ColumnmCurrentIPread-onlycurrentGets the current IP address. To set the IP address, use IPADDR instead.
1.3.6.1.4.1.34097.9.77.1.1.17ColumnmTotalCurrentread-onlycurrentGets the total current of a power module. (unit: 0.001A)
1.3.6.1.4.1.34097.9.77.1.1.18ColumnmTotalRealPowerread-onlycurrentGets the total power level of a power module. (unit: W)
1.3.6.1.4.1.34097.9.77.1.1.20ColumnmTotalActiveEnergyread-onlycurrentGets the total energy of a power module. (unit: 0.001kWh)
1.3.6.1.4.1.34097.9.77.1.1.32ColumnmLineCurrentread-onlycurrentGets the current line current. (unit: 0.001A)
1.3.6.1.4.1.34097.9.77.1.1.33ColumnmFuseCurrentread-onlycurrentGets the current through a fuse. (unit: 0.001A)
1.3.6.1.4.1.34097.9.77.1.1.34ColumnmCurrentSubNetMaskread-onlycurrentGets the current subnet mask. To set the subnet mask use SNMSK instead.
1.3.6.1.4.1.34097.9.77.1.1.35ColumnmCurrentDNSServerread-onlycurrentGets the current DNS server. To set the DNS server use DNSSRV instead.
1.3.6.1.4.1.34097.9.77.1.1.36ColumnmCurrentStdGatewayread-onlycurrentGets the current standard gateway. To set the standard gateway use STDGW instead.
1.3.6.1.4.1.34097.9.77.1.1.37ColumnmUPSPresentread-onlycurrentChecks if a UPS is present.
1.3.6.1.4.1.34097.9.77.1.1.38ColumnmUPSStatusread-onlycurrentGets the working status of a UPS (if its working on its batteries or not).
1.3.6.1.4.1.34097.9.77.1.1.39ColumnmUPSEstimatedRunTimeread-onlycurrentGets the estimated run time of a UPS. (unit: min)
1.3.6.1.4.1.34097.9.77.1.1.40ColumnmUPSBatteryLevelread-onlycurrentThe current UPS battery level. (unit: 0.1%)
1.3.6.1.4.1.34097.9.77.1.1.41ColumnmHighCurrentread-onlycurrentThe current for high values (unit: 0.1A)
1.3.6.1.4.1.34097.9.77.1.1.42ColumnmUpsCommunicationStatusread-onlycurrentStatus information of communication with the UPS
1.3.6.1.4.1.34097.9.77.1.1.43ColumnmHighPowerread-onlycurrentThe power for high values (unit: 0.01kW)
1.3.6.1.4.1.34097.9.77.1.1.44ColumnmTotalHighCurrentread-onlycurrentThe current for high values (unit: 0.1A)
1.3.6.1.4.1.34097.9.77.1.1.45ColumnmTotalHighPowerread-onlycurrentThe power for high values (unit: 0.01kW)
1.3.6.1.4.1.34097.9.77.1.1.46ColumnmPositiveEnergyread-onlycurrentGets the positive energy used by an outlet. (unit: 0.001kWh)
1.3.6.1.4.1.34097.9.77.1.1.47ColumnmNegativeEnergyread-onlycurrentGets the negative energy used by an outlet. (unit: 0.001kWh)
1.3.6.1.4.1.34097.9.77.1.1.48ColumnmTotalPositiveEnergyread-onlycurrentGets the positive energy of the module. (unit: 0.001kWh)
1.3.6.1.4.1.34097.9.77.1.1.49ColumnmTotalNegativeEnergyread-onlycurrentGets the negative energy of the module. (unit: 0.001kWh)
1.3.6.1.4.1.34097.9.77.1.1.56ColumnmCloudStatusread-onlycurrentGets the status of the connection with the cloud. 0 = Idle state; 1 = Disabled; 2 = Initialising; 3 = Initialising - No connection; 4 = Initialising - No key; …
1.3.6.1.4.1.34097.9.77.1.1.1000ColumnmStatusread-onlycurrentstatus of a module
1.3.6.1.4.1.34097.9.77.1.1.10001ColumnmModuleNameread-writecurrentGets, sets or defaults the module name.
1.3.6.1.4.1.34097.9.77.1.1.10002ColumnmFirmwareVersionread-onlycurrentGets the version of the module's firmware.
1.3.6.1.4.1.34097.9.77.1.1.10003ColumnmHardwareVersionread-onlycurrentGets the version of a module's hardware.
1.3.6.1.4.1.34097.9.77.1.1.10004ColumnmFirmwareIDread-onlycurrentGets the ID of the module's firmware.
1.3.6.1.4.1.34097.9.77.1.1.10005ColumnmHardwareIDread-onlycurrentGets the ID of a module's hardware.
1.3.6.1.4.1.34097.9.77.1.1.10006ColumnmRackNameread-writecurrentGets, sets or defaults the name of the rack.
1.3.6.1.4.1.34097.9.77.1.1.10007ColumnmRackPositionread-writecurrentGets, sets or defaults the position in the rack.
1.3.6.1.4.1.34097.9.77.1.1.10011ColumnmIPAddressread-writecurrentGets, sets or defaults the IP address (when DHCP is disabled).
1.3.6.1.4.1.34097.9.77.1.1.10012ColumnmSubNetMaskread-writecurrentGets, sets or defaults the subnet mask (when DHCP is disabled).
1.3.6.1.4.1.34097.9.77.1.1.10013ColumnmStdGateWayread-writecurrentGets, sets or defaults the standard gateway (when DHCP is disabled).
1.3.6.1.4.1.34097.9.77.1.1.10014ColumnmDnsServerread-writecurrentGets, sets or defaults the IP address of the used DNS server (when DHCP is disabled).
1.3.6.1.4.1.34097.9.77.1.1.10015ColumnmMACread-onlycurrentGets the MAC address of a master module.
1.3.6.1.4.1.34097.9.77.1.1.10016ColumnmDHCPEnableread-writecurrentEnables, disables or defaults DHCP. Set to 1 to enable DHCP, or 0 to disable DHCP.
1.3.6.1.4.1.34097.9.77.1.1.10017ColumnmNTPServerread-writecurrentGets, sets or defaults the NTP (Network Time Protocol) server IP address.
1.3.6.1.4.1.34097.9.77.1.1.10018ColumnmUseDefaultNTPServerread-writecurrentEnables, disables or defaults the usage of the default NTP (Network Time Protocol) server (pool.ntp.org).
1.3.6.1.4.1.34097.9.77.1.1.10019ColumnmUseNTPread-writecurrentEnables, disables or defaults NTP (Network Time Protocol). Set to 1 to enable NTP, or 0 to disable NTP.
1.3.6.1.4.1.34097.9.77.1.1.10020ColumnmSNMPTrapRecvIPread-writecurrentGets, sets or defaults the SNMP trap receiver IP address.
1.3.6.1.4.1.34097.9.77.1.1.10021ColumnmSNMPTrapRecvPortread-writecurrentGets, sets or defaults the SNMP tap receiver port.
1.3.6.1.4.1.34097.9.77.1.1.10024ColumnmSNMPControlread-writecurrentEnables, disables or defaults write access over SNMP. Set to 1 to disable write access, or 0 to enable write access.
1.3.6.1.4.1.34097.9.77.1.1.10028ColumnmECSServerread-writecurrentGets, sets or defaults the ECS (Energy Cloud Sentinel) server IP address.
1.3.6.1.4.1.34097.9.77.1.1.10029ColumnmUseECSServerread-writecurrentEnables, disables or defaults the use of an ECS (Energy Cloud Sentinel) server. Set to 1 to enable or 0 to disable.
1.3.6.1.4.1.34097.9.77.1.1.10031ColumnmDisplayLockread-writecurrentGets, sets or defaults the display lock. If the display is locked, you can still view information on the display, but you are not allowed to change settings th…
1.3.6.1.4.1.34097.9.77.1.1.10032ColumnmDisplayTimeOnread-writecurrentGets, sets or defaults the display sleep timer. If the display is inactive for longer than this time, the display turns off to save power. Time is in minutes. …
1.3.6.1.4.1.34097.9.77.1.1.10047ColumnmMaxVoltageWarningread-writecurrentGets, sets or defaults the maximum voltage warning level. (unit: 0.01V)
1.3.6.1.4.1.34097.9.77.1.1.10049ColumnmMinVoltageWarningread-writecurrentGets, sets or defaults the minimum voltage warning level. (unit: 0.01V)
1.3.6.1.4.1.34097.9.77.1.1.10052ColumnmMinTemperatureWarningread-writecurrentGets, sets or defaults the minimum temperature warning level (use DEF accessor to reset). (unit: 0.1K)
1.3.6.1.4.1.34097.9.77.1.1.10053ColumnmMaxTemperatureWarningread-writecurrentGets, sets or defaults the maximum temperature warning level (use DEF accessor to reset). (unit: 0.1K)
1.3.6.1.4.1.34097.9.77.1.1.10074ColumnmGeneralEventEnableread-writecurrentGets, sets or defaults general events. If set to 0, no events will be generated. Set to 1 to generate events on media indicated by the event bitfields.
1.3.6.1.4.1.34097.9.77.1.1.10075ColumnmSNMPSysContactread-writecurrentGets, sets or defaults the SNMP contact information.
1.3.6.1.4.1.34097.9.77.1.1.10078ColumnmCurrentWarningEventread-writecurrentEnables or disables the SNMP trap if the outlet current warning level is exceeded.
1.3.6.1.4.1.34097.9.77.1.1.10080ColumnmPowerWarningEventread-writecurrentEnables or disables the SNMP trap if the power warning level is exceeded.
1.3.6.1.4.1.34097.9.77.1.1.10082ColumnmTotalCurrentWarningEventread-writecurrentEnables or disables the SNMP trap if the total outlet current warning level is exceeded.
1.3.6.1.4.1.34097.9.77.1.1.10084ColumnmTotalPowerWarningEventread-writecurrentEnables or disables the SNMP trap if the total power warning level is exceeded.
1.3.6.1.4.1.34097.9.77.1.1.10086ColumnmVoltageWarningEventread-writecurrentEnables or disables the SNMP trap if the voltage warning level is exceeded.
1.3.6.1.4.1.34097.9.77.1.1.10087ColumnmTemperatureWarningEventread-writecurrentEnables or disables the SNMP trap if the temperature warning level is exceeded.
1.3.6.1.4.1.34097.9.77.1.1.10098ColumnmDisplayBrightnessread-writecurrentGets, sets or defaults the display brightness (if supported).
1.3.6.1.4.1.34097.9.77.1.1.10106ColumnmECSServerPortread-writecurrentGets, sets or defaults the ECS (Energy Cloud Sentinel) server port.
1.3.6.1.4.1.34097.9.77.1.1.10109ColumnmExternalSensorLabelread-writecurrentGets, sets or defaults the external sensor label. External sensors can be connected to Energy Sensors.
1.3.6.1.4.1.34097.9.77.1.1.10127ColumnmHttpsOnlyread-writecurrentEnables or disables the use of HTTPS (secure HTTP). Set to 1 to enable HTTPS only, or 0 to also enable HTTP.
1.3.6.1.4.1.34097.9.77.1.1.10128ColumnmTelnetSslread-writecurrentEnables or disables the use of Telnet SSL (secure Telnet). Set to 1 to enable Telnet SSL, or 0 to disable Telnet SSL).
1.3.6.1.4.1.34097.9.77.1.1.10130ColumnmCookieTimeToLiveread-writecurrentThe TTL (Time To Live) of the website cookie. (unit: min)
1.3.6.1.4.1.34097.9.77.1.1.10131ColumnmLineCurrentWarningThresholdread-writecurrentGets, sets the warning threshold of the linecurrent. (unit: 0.001A)
1.3.6.1.4.1.34097.9.77.1.1.10132ColumnmLineCurrentOffThresholdread-writecurrentGets, sets the off threshold of the linecurrent. (unit: 0.001A)
1.3.6.1.4.1.34097.9.77.1.1.10133ColumnmLineCurrentWarningEventread-writecurrentEnables or disables the SNMP trap if the linecurrent warning level is exceeded.
1.3.6.1.4.1.34097.9.77.1.1.10134ColumnmLineCurrentOffEventread-writecurrentEnables or disables the SNMP trap if the linecurrent off level is exceeded.
1.3.6.1.4.1.34097.9.77.1.1.10142ColumnmFuseCurrentWarningThresholdread-writecurrentGets, sets or defaults the maximum current warning threshold per fuse. (unit: 0.001A)
1.3.6.1.4.1.34097.9.77.1.1.10143ColumnmFuseCurrentOffThresholdread-writecurrentGets, sets or defaults the maximum current off threshold per fuse. (unit: 0.001A)
1.3.6.1.4.1.34097.9.77.1.1.10144ColumnmFuseCurrentWarningEventread-writecurrentEnables or disables the SNMP trap if the fusecurrent warning threshold is exceeded.
1.3.6.1.4.1.34097.9.77.1.1.10145ColumnmFuseCurrentOffEventread-writecurrentEnables or disables the SNMP trap if the fusecurrent off threshold is exceeded.
1.3.6.1.4.1.34097.9.77.1.1.10150ColumnmDeviceIDread-onlycurrentThe ID of the device.
1.3.6.1.4.1.34097.9.77.1.1.10151ColumnmDeviceVersionread-onlycurrentThe version of the device.
1.3.6.1.4.1.34097.9.77.1.1.10152ColumnmSysNameread-onlycurrentThe full name of the device.
1.3.6.1.4.1.34097.9.77.1.1.10153ColumnmElectricalTopologyread-onlycurrentGets the electrical topology of the unit.
1.3.6.1.4.1.34097.9.77.1.1.10154ColumnmFusePortTopologyread-onlycurrentGets the topology between the outlets and fuses.
1.3.6.1.4.1.34097.9.77.1.1.10155ColumnmLineFuseTopologyread-onlycurrentGets the topology between the inlet (cable or connection) and the fuses.
1.3.6.1.4.1.34097.9.77.1.1.10156ColumnmSSOIPAddressread-writecurrentGets, sets the IP address of an SSO (Smart Style Office).
1.3.6.1.4.1.34097.9.77.1.1.10157ColumnmSSOLoginCredentialsread-writecurrentGets, sets the login credentials of an SSO (Smart Style Office).
1.3.6.1.4.1.34097.9.77.1.1.10158ColumnmSSOGracefullShutdownread-writecurrentGets, sets the string to send if the UPS' battery level is below the set threshold.
1.3.6.1.4.1.34097.9.77.1.1.10159ColumnmUPSWarningLevelread-writecurrentGets, sets or defaults the graceful shutdown threshold of a UPS.
1.3.6.1.4.1.34097.9.77.1.1.10160ColumnmUPSOffLevelread-writecurrentGets, sets or defaults the threshold of a UPS to set outlets off.
1.3.6.1.4.1.34097.9.77.1.1.10165ColumnmMaxHighCurrentWarningread-writecurrentGets sets or defaults the maximum high current warning level. (unit: 0.1A)
1.3.6.1.4.1.34097.9.77.1.1.10167ColumnmUpsMonitoringProtocolread-writecurrentDisables/Enables UPS monitoring and selects the protocol used for UPS monitoring. 0 = Disabled; 1 = Use old APC protocol
1.3.6.1.4.1.34097.9.77.1.1.10168ColumnmUpsEmergencyThresholdread-writecurrentWhen the UPS battery level goes below this threshold a shutdown request will be sent to all agents (unit: 0.1%)
1.3.6.1.4.1.34097.9.77.1.1.10169ColumnmUpsRecoveryThresholdread-writecurrentWhen the UPS battery level goes above this threshold a outlets will be powered on as configured by the user (unit: 0.1%)
1.3.6.1.4.1.34097.9.77.1.1.10170ColumnmUpsEventFlagsread-writecurrentEvent flags for events related to the UPS monitoring
1.3.6.1.4.1.34097.9.77.1.1.10171ColumnmRecoveryPowerThresholdread-writecurrentWhen the UPS was on battery and it went below UPSEMERGTHRES, the outlets that have a load below the RECOVPOWERTHRES will be power cycled once the UPS is back o…
1.3.6.1.4.1.34097.9.77.1.1.10176ColumnmMinHighCurrentWarningread-writecurrentGets sets or defaults the minimum high current warning level. (unit: 0.1A)
1.3.6.1.4.1.34097.9.77.1.1.10177ColumnmMinHighPowerWarningread-writecurrentGets sets or defaults the power min high current warning level. (unit: 0.01kW)
1.3.6.1.4.1.34097.9.77.1.1.10178ColumnmMaxHighPowerWarningread-writecurrentGets sets or defaults the power max high current warning level. (unit: 0.01kW)
1.3.6.1.4.1.34097.9.77.1.1.10179ColumnmHeartbeatIntervalread-writecurrentInterval (in seconds) between 2 heartbeat SNMP traps, Set to 0 to disable (unit: s)
1.3.6.1.4.1.34097.9.77.1.1.10180ColumnmMinTotalHighCurrentWarningread-writecurrentGets sets or defaults the maximum high current warning level. (unit: 0.1A)
1.3.6.1.4.1.34097.9.77.1.1.10181ColumnmMaxTotalHighCurrentWarningread-writecurrentGets sets or defaults the maximum high current warning level. (unit: 0.1A)
1.3.6.1.4.1.34097.9.77.1.1.10182ColumnmMinTotalHighPowerWarningread-writecurrentGets sets or defaults the power min high current warning level. (unit: 0.01kW)
1.3.6.1.4.1.34097.9.77.1.1.10183ColumnmMaxTotalHighPowerWarningread-writecurrentGets sets or defaults the power max high current warning level. (unit: 0.01kW)
1.3.6.1.4.1.34097.9.77.1.1.10208ColumnmCloudStateread-writecurrentSet if the device needs to push info to the init cloud (val=0) or to the normal cloud (val=1)
1.3.6.1.4.1.34097.9.77.1.1.10210ColumnmSensorBiasread-writecurrentget or set the DC sensor bias (unit: mV)
1.3.6.1.4.1.34097.9.77.1.1.10211ColumnmDaisyChainDeviceModeread-writecurrentallowed modes: 0: standalone (master without daisy chain slaves) 1: daisy chain master 2: daisy chain slave 1 3: daisy chain slave 2 4: daisy chain slave 3
1.3.6.1.4.1.34097.9.77.1.1.10212ColumnmSNMPTrapUserread-writecurrentGets, sets or defaults the SNMP tap user out of the user list.
1.3.6.1.4.1.34097.9.77.1.1.10213ColumnmUSMUserread-writecurrentGets, sets or defaults the SNMP USM security user
1.3.6.1.4.1.34097.9.77.1.1.10214ColumnmUSMAuthPassphraseread-writecurrentGets, sets or defaults the SNMP USM authentication passphrase (Always MD5)
1.3.6.1.4.1.34097.9.77.1.1.10215ColumnmUSMPrivPassphraseread-writecurrentGets, sets or defaults the SNMP USM private passphrase (Always AES)
1.3.6.1.4.1.34097.9.77.1.1.10216ColumnmSNMPV2GetSetEnableread-writecurrentGets, sets or defaults the SNMP V2 Enable for get ,set or walk but not for traps.
1.3.6.1.4.1.34097.9.77.1.1.10217ColumnmSNMPV3GetSetEnableread-writecurrentGets, sets or defaults the SNMP V3 Enable for get ,set or walk but not for traps.
1.3.6.1.4.1.34097.9.77.1.1.10218ColumnmUSMAuthPassphraseLengthread-writecurrentGets, sets or defaults the SNMP USM authentication passphrase length
1.3.6.1.4.1.34097.9.77.1.1.10219ColumnmUSMPrivPassphraseLengthread-writecurrentGets, sets or defaults the SNMP USM private passphrase length
1.3.6.1.4.1.34097.9.77.1.1.10222ColumnmSNMPTrapEnableread-writecurrentGets, sets or defaults the SNMP Trap Enable per trap account
1.3.6.1.4.1.34097.9.77.1.1.10227ColumnmLDAPAttributeread-writecurrentAttribute linked to the LDAPFilter
1.3.6.1.4.1.34097.9.77.1.1.10228ColumnmLDAPPathread-writecurrentRelative Path to be used for the LDAPFilter
1.3.6.1.4.1.34097.9.77.1.1.10229ColumnmLDAPAdminGroupNameread-writecurrentGroupName for Admin Credentials in LDAP
1.3.6.1.4.1.34097.9.77.1.1.10230ColumnmLDAPRestrictedGroupNameread-writecurrentGroupName for Restricted Credentials in LDAP
1.3.6.1.4.1.34097.9.77.1.1.10231ColumnmLDAPGuestGroupNameread-writecurrentGroupName for Guest Credentials in LDAP
1.3.6.1.4.1.34097.9.77.1.1.10232ColumnmLDAPEnableread-writecurrentEnable or disable login via LDAP credentials
1.3.6.1.4.1.34097.9.77.1.1.10233ColumnmLDAPLoginWrapperread-writecurrentWrapper for login in with LDAP
1.3.6.1.4.1.34097.9.77.1.1.10235ColumnmLDAPServerread-writecurrentNO_INFO
1.3.6.1.4.1.34097.9.77.1.1.10236ColumnmLocalAuthEnableread-writecurrentSet if local authentication is still possible if LDAP is enabled
1.3.6.1.4.1.34097.9.77.1.1.65537ColumnmasterIndexnot-accessiblecurrentIndex for the selected Master Module
1.3.6.1.4.1.34097.9.77.1.1.65538ColumnmasterModuleIndexnot-accessiblecurrentSelected Master Module
1.3.6.1.4.1.34097.9.80NodepowerModule
1.3.6.1.4.1.34097.9.80.1TableePowerTablenot-accessiblecurrentNO_INFO
1.3.6.1.4.1.34097.9.80.1.1RowePowerEntrynot-accessiblecurrentNO_INFO
1.3.6.1.4.1.34097.9.80.1.1.1ColumnpGeneralModuleStatusread-onlycurrentGeneral status of a module.
1.3.6.1.4.1.34097.9.80.1.1.2ColumnpSpecificModuleStatusread-onlycurrentSpecific status of a module.
1.3.6.1.4.1.34097.9.80.1.1.3ColumnpCurrentTimeread-writecurrentGets or sets the current time (not possible when NTP is enabled). (unit: UNIX)
1.3.6.1.4.1.34097.9.80.1.1.4ColumnpVoltageread-onlycurrentGets the voltage of a power module. (unit: 0.01V)
1.3.6.1.4.1.34097.9.80.1.1.5ColumnpFrequencyread-onlycurrentGets the frequency of the input voltage of a power module. (unit: 0.001Hz)
1.3.6.1.4.1.34097.9.80.1.1.6ColumnpCurrentread-onlycurrentGets the current of an outlet. (unit: 0.001A)
1.3.6.1.4.1.34097.9.80.1.1.7ColumnpPowerread-onlycurrentGets the power of an outlet. (unit: W)
1.3.6.1.4.1.34097.9.80.1.1.8ColumnpStatePortCurread-onlycurrentGets the current state of an outlet. To toggle an outlet use PORTSTAT (CLI) or pPortstate (SNMP) (GUID 10035) instead.
1.3.6.1.4.1.34097.9.80.1.1.9ColumnpActiveEnergyread-onlycurrentGets the energy used by an outlet. (unit: 0.001kWh)
1.3.6.1.4.1.34097.9.80.1.1.10ColumnpApparentEnergyread-onlycurrentGets the apparent energy used by an outlet. (unit: 0.001kVAh)
1.3.6.1.4.1.34097.9.80.1.1.11ColumnpTemperatureread-onlycurrentGets the current temperature of a temperature sensor. (unit: 0.1K)
1.3.6.1.4.1.34097.9.80.1.1.15ColumnpApparentPowerread-onlycurrentGets the apparent power of an outlet. (unit: VA)
1.3.6.1.4.1.34097.9.80.1.1.16ColumnpPowerFactorread-onlycurrentGets the power factor of an outlet. (unit: %)
1.3.6.1.4.1.34097.9.80.1.1.17ColumnpTotalCurrentread-onlycurrentGets the total current of a power module. (unit: 0.001A)
1.3.6.1.4.1.34097.9.80.1.1.18ColumnpTotalRealPowerread-onlycurrentGets the total power level of a power module. (unit: W)
1.3.6.1.4.1.34097.9.80.1.1.19ColumnpTotalApparentPowerread-onlycurrentGets the total apparent power of a power module. (unit: VA)
1.3.6.1.4.1.34097.9.80.1.1.20ColumnpTotalActiveEnergyread-onlycurrentGets the total energy of a power module. (unit: 0.001kWh)
1.3.6.1.4.1.34097.9.80.1.1.21ColumnpTotalApparentEnergyread-onlycurrentGets the total apparent energy of a power module. (unit: 0.001kVAh)
1.3.6.1.4.1.34097.9.80.1.1.22ColumnpTotalPowerFactorread-onlycurrentGets the total power factor of a power module. (unit: %)
1.3.6.1.4.1.34097.9.80.1.1.24ColumnpTimeOnlineread-onlycurrentGets the amount of seconds since the last reset. (unit: s)
1.3.6.1.4.1.34097.9.80.1.1.50ColumnpTotalHarmonicDistortionread-onlycurrenttotal harmonic distortion - outlet (unit: 0.1%)
1.3.6.1.4.1.34097.9.80.1.1.51ColumnpPhaseread-onlycurrentthe phase between 2 waves (unit: degr)
1.3.6.1.4.1.34097.9.80.1.1.52ColumnpBigCurrentread-onlycurrentGets the current of an outlet. (unit: 0.0001A)
1.3.6.1.4.1.34097.9.80.1.1.53ColumnpBigPowerread-onlycurrentGets the power of an outlet. (unit: 0.001W)
1.3.6.1.4.1.34097.9.80.1.1.54ColumnpBigApparentPowerread-onlycurrentGets the apparent power of an outlet. (unit: 0.001VA)
1.3.6.1.4.1.34097.9.80.1.1.55ColumnpDetectedPhaseread-onlycurrentGives the best matching Phase per currentsensor. Updated every 8s. returnes 255 if no good phaselink is found
1.3.6.1.4.1.34097.9.80.1.1.10001ColumnpModuleNameread-writecurrentGets, sets or defaults the module name.
1.3.6.1.4.1.34097.9.80.1.1.10002ColumnpFirmwareVersionread-onlycurrentGets the version of the module's firmware.
1.3.6.1.4.1.34097.9.80.1.1.10003ColumnpHardwareVersionread-onlycurrentGets the version of a module's hardware.
1.3.6.1.4.1.34097.9.80.1.1.10004ColumnpFirmwareIDread-onlycurrentGets the ID of the module's firmware.
1.3.6.1.4.1.34097.9.80.1.1.10005ColumnpHardwareIDread-onlycurrentGets the ID of a module's hardware.
1.3.6.1.4.1.34097.9.80.1.1.10034ColumnpPortNameread-writecurrentGets, sets or defaults the name of an outlet.
1.3.6.1.4.1.34097.9.80.1.1.10035ColumnpPortStateread-writecurrentSets the state of an outlet: 0=OFF, 1=ON, 2=POWER CYCLE. To get the state of an outlet use CPORTSTAT (CLI) or pStatePortCur (SNMP) (GUID 8) instead.
1.3.6.1.4.1.34097.9.80.1.1.10036ColumnpCurrentPriorOffread-writecurrentGets, sets or defaults the priority of an outlet. Priority settings are used when 1 or more outlets must be turned off because the total current of a power mod…
1.3.6.1.4.1.34097.9.80.1.1.10037ColumnpDelayOnread-writecurrentGets, sets or defaults the outlet turn-on delay. Use this to reduce inrush current when the Energy Switch boots. (unit: s)
1.3.6.1.4.1.34097.9.80.1.1.10038ColumnpMaxCurrentOffread-writecurrentGets, sets or defaults the maximum current off level of an outlet. (unit: 0.001A)
1.3.6.1.4.1.34097.9.80.1.1.10039ColumnpMaxCurrentWarningread-writecurrentGets, sets or defaults the maximum current warning level of an outlet. (unit: 0.001A)
1.3.6.1.4.1.34097.9.80.1.1.10040ColumnpMaxPowerOffread-writecurrentGets, sets or defaults the maximum power off level of an outlet. (unit: W)
1.3.6.1.4.1.34097.9.80.1.1.10041ColumnpMaxPowerWarningread-writecurrentGets, sets or defaults the maximum power warning level of an outlet. (unit: W)
1.3.6.1.4.1.34097.9.80.1.1.10042ColumnpMaxTotalCurrentOffread-writecurrentGets, sets or defaults the total maximum current off level of a power module. (unit: 0.001A)
1.3.6.1.4.1.34097.9.80.1.1.10043ColumnpMaxTotalCurrentWarningread-writecurrentGets, sets or defaults the total maximum current warning level of a power module. (unit: 0.001A)
1.3.6.1.4.1.34097.9.80.1.1.10044ColumnpMaxTotalPowerOffread-writecurrentGets, sets or defaults the maximum total power off level. (unit: W)
1.3.6.1.4.1.34097.9.80.1.1.10045ColumnpMaxTotalPowerWarningread-writecurrentGets, sets or defaults the maximum total power warning level. (unit: W)
1.3.6.1.4.1.34097.9.80.1.1.10047ColumnpMaxVoltageWarningread-writecurrentGets, sets or defaults the maximum voltage warning level. (unit: 0.01V)
1.3.6.1.4.1.34097.9.80.1.1.10049ColumnpMinVoltageWarningread-writecurrentGets, sets or defaults the minimum voltage warning level. (unit: 0.01V)
1.3.6.1.4.1.34097.9.80.1.1.10052ColumnpMinTemperatureWarningread-writecurrentGets, sets or defaults the minimum temperature warning level (use DEF accessor to reset). (unit: 0.1K)
1.3.6.1.4.1.34097.9.80.1.1.10053ColumnpMaxTemperatureWarningread-writecurrentGets, sets or defaults the maximum temperature warning level (use DEF accessor to reset). (unit: 0.1K)
1.3.6.1.4.1.34097.9.80.1.1.10076ColumnpPortStateEventread-writecurrentEnables or disables the SNMP trap if the state of an outlet is changed.
1.3.6.1.4.1.34097.9.80.1.1.10077ColumnpCurrentOffEventread-writecurrentEnables or disables the SNMP trap if the outlet current off level is exceeded.
1.3.6.1.4.1.34097.9.80.1.1.10078ColumnpCurrentWarningEventread-writecurrentEnables or disables the SNMP trap if the outlet current warning level is exceeded.
1.3.6.1.4.1.34097.9.80.1.1.10079ColumnpPowerOffEventread-writecurrentEnables or disables the SNMP trap if the power off level is exceeded.
1.3.6.1.4.1.34097.9.80.1.1.10080ColumnpPowerWarningEventread-writecurrentEnables or disables the SNMP trap if the power warning level is exceeded.
1.3.6.1.4.1.34097.9.80.1.1.10081ColumnpTotalCurrentOffEventread-writecurrentEnables or disables the SNMP trap if the total outlet current off level is exceeded.
1.3.6.1.4.1.34097.9.80.1.1.10082ColumnpTotalCurrentWarningEventread-writecurrentEnables or disables the SNMP trap if the total outlet current warning level is exceeded.
1.3.6.1.4.1.34097.9.80.1.1.10083ColumnpTotalPowerOffEventread-writecurrentEnables or disables the SNMP trap if the total power off level is exceeded.
1.3.6.1.4.1.34097.9.80.1.1.10084ColumnpTotalPowerWarningEventread-writecurrentEnables or disables the SNMP trap if the total power warning level is exceeded.
1.3.6.1.4.1.34097.9.80.1.1.10086ColumnpVoltageWarningEventread-writecurrentEnables or disables the SNMP trap if the voltage warning level is exceeded.
1.3.6.1.4.1.34097.9.80.1.1.10087ColumnpTemperatureWarningEventread-writecurrentEnables or disables the SNMP trap if the temperature warning level is exceeded.
1.3.6.1.4.1.34097.9.80.1.1.10090ColumnpMaxOverheatingOffread-writecurrentGets, sets or defaults the maximum overheat temperature off level. (unit: 0.1K)
1.3.6.1.4.1.34097.9.80.1.1.10091ColumnpOverheatingOffEventread-writecurrentEnables or disables the SNMP trap if the overtemperature off level is exceeded.
1.3.6.1.4.1.34097.9.80.1.1.10099ColumnpPowerCycleTimeread-writecurrentGets, sets or defaults the time interval that is used to do a power cycle of an outlet. (unit: s)
1.3.6.1.4.1.34097.9.80.1.1.10109ColumnpExternalSensorLabelread-writecurrentGets, sets or defaults the external sensor label. External sensors can be connected to Energy Sensors.
1.3.6.1.4.1.34097.9.80.1.1.10121ColumnpMaxOverheatingWarningread-writecurrentGets, sets or defaults the overheating temperature warning level. (unit: 0.1K)
1.3.6.1.4.1.34097.9.80.1.1.10122ColumnpOverheatingWarningEventread-writecurrentEnables or disables the SNMP trap if the overheat warning level is exceeded.
1.3.6.1.4.1.34097.9.80.1.1.10135ColumnpMicroIntTimeThresholdread-writecurrentThe minimum time the voltage must be interrupted before it is seen as a micro interruption (unit: 0.1ms)
1.3.6.1.4.1.34097.9.80.1.1.10136ColumnpMicroIntEventread-writecurrentEnables or disables the SNMP trap if a microinterruption on the voltage is detected.
1.3.6.1.4.1.34097.9.80.1.1.10137ColumnpSoftFuseCurrentThresholdread-writecurrentThe threshold of the soft fuse is a factor of the maximum nominal current off (unit: A)
1.3.6.1.4.1.34097.9.80.1.1.10138ColumnpSoftFuseDelayread-writecurrentThe minimum time the current of an outlet must be above the soft fuse current threshold to switch it off. (unit: ms)
1.3.6.1.4.1.34097.9.80.1.1.10139ColumnpSoftFuseEventread-writecurrentEnables or disables the SNMP trap if a soft fuse is triggered.
1.3.6.1.4.1.34097.9.80.1.1.10140ColumnpPhaseShiftEventread-writecurrentEnables or disables the SNMP trap if a phase shift on the voltage is detected.
1.3.6.1.4.1.34097.9.80.1.1.10146ColumnpSchedulePortOnTimeread-writecurrentGets, sets or defaults the time for the scheduler to turn on an outlet. (unit: min)
1.3.6.1.4.1.34097.9.80.1.1.10147ColumnpSchedulePortOffTimeread-writecurrentGets, sets or defaults the time for the scheduler to turn off an outlet. (unit: min)
1.3.6.1.4.1.34097.9.80.1.1.10148ColumnpEnableSchedulePortread-writecurrentEnables or disables the scheduler on an outlet. When enabled the scheduling is repeated daily.
1.3.6.1.4.1.34097.9.80.1.1.10161ColumnpBlockSetPortOffread-writecurrentPrevent outlets to be set off (only delay on and powercycle are still possible).
1.3.6.1.4.1.34097.9.80.1.1.10166ColumnpSchedulePortChangeEventread-writecurrentevent if a port has changed state because of the scheduler
1.3.6.1.4.1.34097.9.80.1.1.10172ColumnpAgentIPread-writecurrentIP address of the agent associated to this outlet
1.3.6.1.4.1.34097.9.80.1.1.10173ColumnpAgentPortread-writecurrentNetwork port on which the associated agent will listen
1.3.6.1.4.1.34097.9.80.1.1.10174ColumnpAgentCommunicationEventFlagsread-writecurrentEvent flags for events related to agent communication
1.3.6.1.4.1.34097.9.80.1.1.10175ColumnpAlwaysOnread-writecurrentOutlets marked as Always On can only be power cycled by the user
1.3.6.1.4.1.34097.9.80.1.1.10190ColumnpGenericTransducerParametersread-writecurrentsets the slope of the transducer transfer function when the generic transducer type is selected (unit: mA/V)
1.3.6.1.4.1.34097.9.80.1.1.10193ColumnpMaxBigCurrentWarningread-writecurrentGets, sets or defaults the maximum current warning level of an outlet. (unit: 0.0001A)
1.3.6.1.4.1.34097.9.80.1.1.10194ColumnpMaxBigPowerWarningread-writecurrentGets, sets or defaults the maximum power warning level of an outlet. (unit: 0.001W)
1.3.6.1.4.1.34097.9.80.1.1.10195ColumnpGroupNumberread-writecurrentGroup number per port to group ports
1.3.6.1.4.1.34097.9.80.1.1.10196ColumnpPhaseLinkread-writecurrentLink the current port with a voltage phase
1.3.6.1.4.1.34097.9.80.1.1.10197ColumnpCurrentSensorSelectorread-writecurrentSelection of the currentsensor connected to port. To enter your own value you need to use 255 and fill in guid 10190.
1.3.6.1.4.1.34097.9.80.1.1.10209ColumnpMinBigCurrentWarningread-writecurrentGets, sets or defaults the minimum current warning level of a port. (unit: 0.0001A)
1.3.6.1.4.1.34097.9.80.1.1.65537ColumnpowerIndexnot-accessiblecurrentIndex for the selected Power Module
1.3.6.1.4.1.34097.9.80.1.1.65538ColumnpowerModuleIndexnot-accessiblecurrentSelected Power Module
1.3.6.1.4.1.34097.9.81Nodemeasuring3phaseModule
1.3.6.1.4.1.34097.9.81.1TableeMeasuring3PhaseTablenot-accessiblecurrentNO_INFO
1.3.6.1.4.1.34097.9.81.1.1RoweMeasuring3PhaseEntrynot-accessiblecurrentNO_INFO
1.3.6.1.4.1.34097.9.81.1.1.1ColumnqGeneralModuleStatusread-onlycurrentGeneral status of a module.
1.3.6.1.4.1.34097.9.81.1.1.2ColumnqSpecificModuleStatusread-onlycurrentSpecific status of a module.
1.3.6.1.4.1.34097.9.81.1.1.3ColumnqCurrentTimeread-writecurrentGets or sets the current time (not possible when NTP is enabled). (unit: UNIX)
1.3.6.1.4.1.34097.9.81.1.1.4ColumnqVoltageread-onlycurrentGets the voltage of a power module. (unit: 0.01V)
1.3.6.1.4.1.34097.9.81.1.1.5ColumnqFrequencyread-onlycurrentGets the frequency of the input voltage of a power module. (unit: 0.001Hz)
1.3.6.1.4.1.34097.9.81.1.1.9ColumnqActiveEnergyread-onlycurrentGets the energy used by an outlet. (unit: 0.001kWh)
1.3.6.1.4.1.34097.9.81.1.1.10ColumnqApparentEnergyread-onlycurrentGets the apparent energy used by an outlet. (unit: 0.001kVAh)
1.3.6.1.4.1.34097.9.81.1.1.11ColumnqTemperatureread-onlycurrentGets the current temperature of a temperature sensor. (unit: 0.1K)
1.3.6.1.4.1.34097.9.81.1.1.16ColumnqPowerFactorread-onlycurrentGets the power factor of an outlet. (unit: %)
1.3.6.1.4.1.34097.9.81.1.1.24ColumnqTimeOnlineread-onlycurrentGets the amount of seconds since the last reset. (unit: s)
1.3.6.1.4.1.34097.9.81.1.1.30ColumnqIOPortread-onlycurrentGets the state of a digital input.
1.3.6.1.4.1.34097.9.81.1.1.50ColumnqTotalHarmonicDistortionread-onlycurrenttotal harmonic distortion - outlet (unit: 0.1%)
1.3.6.1.4.1.34097.9.81.1.1.51ColumnqPhaseread-onlycurrentthe phase between 2 waves (unit: degr)
1.3.6.1.4.1.34097.9.81.1.1.52ColumnqBigCurrentread-onlycurrentGets the current of an outlet. (unit: 0.0001A)
1.3.6.1.4.1.34097.9.81.1.1.53ColumnqBigPowerread-onlycurrentGets the power of an outlet. (unit: 0.001W)
1.3.6.1.4.1.34097.9.81.1.1.54ColumnqBigApparentPowerread-onlycurrentGets the apparent power of an outlet. (unit: 0.001VA)
1.3.6.1.4.1.34097.9.81.1.1.1000ColumnqStatusread-onlycurrentstatus of a module
1.3.6.1.4.1.34097.9.81.1.1.10001ColumnqModuleNameread-writecurrentGets, sets or defaults the module name.
1.3.6.1.4.1.34097.9.81.1.1.10002ColumnqFirmwareVersionread-onlycurrentGets the version of the module's firmware.
1.3.6.1.4.1.34097.9.81.1.1.10003ColumnqHardwareVersionread-onlycurrentGets the version of a module's hardware.
1.3.6.1.4.1.34097.9.81.1.1.10004ColumnqFirmwareIDread-onlycurrentGets the ID of the module's firmware.
1.3.6.1.4.1.34097.9.81.1.1.10005ColumnqHardwareIDread-onlycurrentGets the ID of a module's hardware.
1.3.6.1.4.1.34097.9.81.1.1.10035ColumnqPortStateread-writecurrentSets the state of an outlet: 0=OFF, 1=ON, 2=POWER CYCLE. To get the state of an outlet use CPORTSTAT (CLI) or pStatePortCur (SNMP) (GUID 8) instead.
1.3.6.1.4.1.34097.9.81.1.1.10047ColumnqMaxVoltageWarningread-writecurrentGets, sets or defaults the maximum voltage warning level. (unit: 0.01V)
1.3.6.1.4.1.34097.9.81.1.1.10049ColumnqMinVoltageWarningread-writecurrentGets, sets or defaults the minimum voltage warning level. (unit: 0.01V)
1.3.6.1.4.1.34097.9.81.1.1.10052ColumnqMinTemperatureWarningread-writecurrentGets, sets or defaults the minimum temperature warning level (use DEF accessor to reset). (unit: 0.1K)
1.3.6.1.4.1.34097.9.81.1.1.10053ColumnqMaxTemperatureWarningread-writecurrentGets, sets or defaults the maximum temperature warning level (use DEF accessor to reset). (unit: 0.1K)
1.3.6.1.4.1.34097.9.81.1.1.10076ColumnqPortStateEventread-writecurrentEnables or disables the SNMP trap if the state of an outlet is changed.
1.3.6.1.4.1.34097.9.81.1.1.10078ColumnqCurrentWarningEventread-writecurrentEnables or disables the SNMP trap if the outlet current warning level is exceeded.
1.3.6.1.4.1.34097.9.81.1.1.10080ColumnqPowerWarningEventread-writecurrentEnables or disables the SNMP trap if the power warning level is exceeded.
1.3.6.1.4.1.34097.9.81.1.1.10086ColumnqVoltageWarningEventread-writecurrentEnables or disables the SNMP trap if the voltage warning level is exceeded.
1.3.6.1.4.1.34097.9.81.1.1.10087ColumnqTemperatureWarningEventread-writecurrentEnables or disables the SNMP trap if the temperature warning level is exceeded.
1.3.6.1.4.1.34097.9.81.1.1.10135ColumnqMicroIntTimeThresholdread-writecurrentThe minimum time the voltage must be interrupted before it is seen as a micro interruption (unit: 0.1ms)
1.3.6.1.4.1.34097.9.81.1.1.10136ColumnqMicroIntEventread-writecurrentEnables or disables the SNMP trap if a microinterruption on the voltage is detected.
1.3.6.1.4.1.34097.9.81.1.1.10150ColumnqDeviceIDread-onlycurrentThe ID of the device.
1.3.6.1.4.1.34097.9.81.1.1.10151ColumnqDeviceVersionread-onlycurrentThe version of the device.
1.3.6.1.4.1.34097.9.81.1.1.10193ColumnqMaxBigCurrentWarningread-writecurrentGets, sets or defaults the maximum current warning level of an outlet. (unit: 0.0001A)
1.3.6.1.4.1.34097.9.81.1.1.10194ColumnqMaxBigPowerWarningread-writecurrentGets, sets or defaults the maximum power warning level of an outlet. (unit: 0.001W)
1.3.6.1.4.1.34097.9.81.1.1.10197ColumnqCurrentSensorSelectorread-writecurrentSelection of the currentsensor connected to port. To enter your own value you need to use 255 and fill in guid 10190.
1.3.6.1.4.1.34097.9.81.1.1.10209ColumnqMinBigCurrentWarningread-writecurrentGets, sets or defaults the minimum current warning level of a port. (unit: 0.0001A)
1.3.6.1.4.1.34097.9.81.1.1.10234ColumnqkWhModeread-writecurrentSet the mode when to count kWh, 0 = always, 1 = only positive, 2= only negative
1.3.6.1.4.1.34097.9.81.1.1.65537Columnmeasuring3phaseIndexnot-accessiblecurrentIndex for the selected Measuring3Phase Module
1.3.6.1.4.1.34097.9.81.1.1.65538Columnmeasuring3phaseModuleIndexnot-accessiblecurrentSelected Measuring3Phase Module
1.3.6.1.4.1.34097.9.85NodepcModule
1.3.6.1.4.1.34097.9.85.1TableePCTablenot-accessiblecurrentNO_INFO
1.3.6.1.4.1.34097.9.85.1.1RowePCEntrynot-accessiblecurrentNO_INFO
1.3.6.1.4.1.34097.9.85.1.1.1ColumnuGeneralModuleStatusread-onlycurrentGeneral status of a module.
1.3.6.1.4.1.34097.9.85.1.1.2ColumnuSpecificModuleStatusread-onlycurrentSpecific status of a module.
1.3.6.1.4.1.34097.9.85.1.1.3ColumnuCurrentTimeread-writecurrentGets or sets the current time (not possible when NTP is enabled). (unit: UNIX)
1.3.6.1.4.1.34097.9.85.1.1.4ColumnuVoltageread-onlycurrentGets the voltage of a power module. (unit: 0.01V)
1.3.6.1.4.1.34097.9.85.1.1.6ColumnuCurrentread-onlycurrentGets the current of an outlet. (unit: 0.001A)
1.3.6.1.4.1.34097.9.85.1.1.8ColumnuStatePortCurread-onlycurrentGets the current state of an outlet. To toggle an outlet use PORTSTAT (CLI) or pPortstate (SNMP) (GUID 10035) instead.
1.3.6.1.4.1.34097.9.85.1.1.11ColumnuTemperatureread-onlycurrentGets the current temperature of a temperature sensor. (unit: 0.1K)
1.3.6.1.4.1.34097.9.85.1.1.12ColumnuHumidityread-onlycurrentGets the relative humidity. (unit: 0.1RH)
1.3.6.1.4.1.34097.9.85.1.1.10001ColumnuModuleNameread-writecurrentGets, sets or defaults the module name.
1.3.6.1.4.1.34097.9.85.1.1.10002ColumnuFirmwareVersionread-onlycurrentGets the version of the module's firmware.
1.3.6.1.4.1.34097.9.85.1.1.10003ColumnuHardwareVersionread-onlycurrentGets the version of a module's hardware.
1.3.6.1.4.1.34097.9.85.1.1.10004ColumnuFirmwareIDread-onlycurrentGets the ID of the module's firmware.
1.3.6.1.4.1.34097.9.85.1.1.10005ColumnuHardwareIDread-onlycurrentGets the ID of a module's hardware.
1.3.6.1.4.1.34097.9.85.1.1.10035ColumnuPortStateread-writecurrentSets the state of an outlet: 0=OFF, 1=ON, 2=POWER CYCLE. To get the state of an outlet use CPORTSTAT (CLI) or pStatePortCur (SNMP) (GUID 8) instead.
1.3.6.1.4.1.34097.9.85.1.1.65537ColumnpcIndexnot-accessiblecurrentIndex for the selected PC Module
1.3.6.1.4.1.34097.9.85.1.1.65538ColumnpcModuleIndexnot-accessiblecurrentSelected PC Module
1.3.6.1.4.1.34097.9.89NodetestmoduleModule
1.3.6.1.4.1.34097.9.89.1TableeTestModuleTablenot-accessiblecurrentModule to test the R-bus
1.3.6.1.4.1.34097.9.89.1.1RoweTestModuleEntrynot-accessiblecurrentModule to test the R-bus
1.3.6.1.4.1.34097.9.89.1.1.1ColumnyGeneralModuleStatusread-onlycurrentGeneral status of a module.
1.3.6.1.4.1.34097.9.89.1.1.2ColumnySpecificModuleStatusread-onlycurrentSpecific status of a module.
1.3.6.1.4.1.34097.9.89.1.1.3ColumnyCurrentTimeread-writecurrentGets or sets the current time (not possible when NTP is enabled). (unit: UNIX)
1.3.6.1.4.1.34097.9.89.1.1.6ColumnyCurrentread-onlycurrentGets the current of an outlet. (unit: 0.001A)
1.3.6.1.4.1.34097.9.89.1.1.8ColumnyStatePortCurread-onlycurrentGets the current state of an outlet. To toggle an outlet use PORTSTAT (CLI) or pPortstate (SNMP) (GUID 10035) instead.
1.3.6.1.4.1.34097.9.89.1.1.27ColumnyAnalogueInputread-onlycurrentGets the value of an analog input (voltage). (unit: mV)
1.3.6.1.4.1.34097.9.89.1.1.10001ColumnyModuleNameread-writecurrentGets, sets or defaults the module name.
1.3.6.1.4.1.34097.9.89.1.1.10002ColumnyFirmwareVersionread-onlycurrentGets the version of the module's firmware.
1.3.6.1.4.1.34097.9.89.1.1.10003ColumnyHardwareVersionread-onlycurrentGets the version of a module's hardware.
1.3.6.1.4.1.34097.9.89.1.1.10004ColumnyFirmwareIDread-onlycurrentGets the ID of the module's firmware.
1.3.6.1.4.1.34097.9.89.1.1.10005ColumnyHardwareIDread-onlycurrentGets the ID of a module's hardware.
1.3.6.1.4.1.34097.9.89.1.1.65537ColumntestmoduleIndexnot-accessiblecurrentIndex for the selected TestModule Module
1.3.6.1.4.1.34097.9.89.1.1.65538ColumntestmoduleModuleIndexnot-accessiblecurrentSelected TestModule Module
Type Definitions
NameSyntaxStatusDescription
CURPORTSTATEINTEGER { portOff(0), portOnNoWarning(1), portOff1(2), portOnWithWarningCurrent(3), portOff2(4), portOnWithWarningPower(5), portOff3(6), portOnWithWarningCurrentAndPower(7), portOffWithError(8), portOnNoWarning1(9), portOffWithError1(10), portOnWithWarningCurrent1(11), portOffWithError2(12), portOnWithWarningPower1(13), portOffWithError3(14), portOnWithWarnCurrentAndPower1(15), portOffWithDelayOn(16), portOnNoWarning2(17), portOffWithDelayOn1(18), portOnWithWarningCurrent2(19), portOffWithDelayOn2(20), portOnWithWarningPower2(21), portOffWithDelayOn3(22), portOnWithWarnCurrentAndPower2(23) }currentenumeration of all port states possible
EVENTFLAGSINTEGER { sNMPTrapOff(0), sNMPTrapOn(1) }currentenumeration of all eventflags possible
ShundredthInteger32current0.01
StenthInteger32current0.1
SthousandthInteger32current0.001
UhundredthUnsigned32current0.01
UtenthUnsigned32current0.1
UthousandthUnsigned32current0.001
VersionOCTET STRING (SIZE (4))currentDisplays a version number