MIB Viewer

ETA-RCI10-MIB

229 objects
Copyright notice (c) E-T-A Elektrotechnische Apparate GmbH 2014-2015 Florian Pfanner, Michael Haerteis This MIB file was created for a RCI10. Via SNMP the slave states can be retrieved and device actions can initiated.
Imported Objects
SNMPv2-SMIenterprises Integer32 IpAddress MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE
OIDNameAccessStatusDescription
1.3.6.1.4.1.44086Nodeeta
1.3.6.1.4.1.44086.4NodeetaProp
1.3.6.1.4.1.44086.4.1Identityrci10Copyright notice (c) E-T-A Elektrotechnische Apparate GmbH 2014-2015 Florian Pfanner, Michael Haerteis This MIB file was created for a RCI10. Via SNMP the slav…
1.3.6.1.4.1.44086.4.1.1Nodesystem
1.3.6.1.4.1.44086.4.1.1.1Nodesnmp
1.3.6.1.4.1.44086.4.1.1.1.1ScalarsnmpTrapsEnableread-writecurrentIf 1 sending of SNMP traps is enabled. Else no traps will be sent
1.3.6.1.4.1.44086.4.1.1.1.2ScalarsnmpTrapTargetread-writecurrentTraps are sent to the destination given here. This could be an IP address or a host name.
1.3.6.1.4.1.44086.4.1.1.1.3ScalarsnmpProtocolread-onlycurrentSNMP protocol version currently used. The value can only be changed using the SSH configuration.
1.3.6.1.4.1.44086.4.1.1.1.10ScalarsnmpCommunityStringread-writecurrentSNMP community string used to access the values. Also the SNMP traps are sent using this community string. Only valid if SNMPv2c is used.
1.3.6.1.4.1.44086.4.1.1.1.20ScalarsnmpLoginread-writecurrentLogin name used to access the SNMP data values. Only valid if SNMPv3 is used.
1.3.6.1.4.1.44086.4.1.1.1.21ScalarsnmpPasswordread-writecurrentPassword used to access the SNMP data values. The password have to be at least eight characters long. Only valid if SNMPv3 is used.
1.3.6.1.4.1.44086.4.1.1.1.22ScalarsnmpAuthenticationread-writecurrentAuthentication method used to encrypt the SNMP data transmission. Valid entries are 'MD5' and 'SHA'. Only valid if SNMPv3 is used.
1.3.6.1.4.1.44086.4.1.1.1.23ScalarsnmpEncryptionread-writecurrentEncryption method used for the SNMP data transmission. Valid entries are 'AES', 'DES' and 'off'. Only valid if SNMPv3 is used.
1.3.6.1.4.1.44086.4.1.1.1.24ScalarsnmpEncryptionKeyread-writecurrentEncryption key used for the SNMP data transmission. Only valid if SNMPv3 is used.
1.3.6.1.4.1.44086.4.1.1.2Nodeethernet
1.3.6.1.4.1.44086.4.1.1.2.1Nodeipv4
1.3.6.1.4.1.44086.4.1.1.2.1.1Scalardhcpv4Enableread-writecurrentIf 1 the IPv4 settings are automatically obtained using DHCP.
1.3.6.1.4.1.44086.4.1.1.2.1.10Scalarip4Addressread-writecurrentIPv4 adress of the RCI10, for example 192.168.1.25.
1.3.6.1.4.1.44086.4.1.1.2.1.11Scalarip4NetMaskread-writecurrentIPv4 network mask, for example 255.255.255.0.
1.3.6.1.4.1.44086.4.1.1.2.1.12Scalarip4Gatewayread-writecurrentIPv4 gateway address, for example 192.168.1.1.
1.3.6.1.4.1.44086.4.1.1.2.2Nodeipv6
1.3.6.1.4.1.44086.4.1.1.2.2.1Scalardhcpv6Enableread-writecurrentIf 1 the IPv6 settings are automatically obtained using DHCP.
1.3.6.1.4.1.44086.4.1.1.2.2.10Scalarip6Addressread-writecurrentIPv6 adress of the RCI10, for example 2001:0db8:85a3::1000.
1.3.6.1.4.1.44086.4.1.1.2.2.11Scalarip6PrefixLengthread-writecurrentIPv6 network prefix length. Valid range is from 1 to 128.
1.3.6.1.4.1.44086.4.1.1.2.10ScalardnsServerread-writecurrentAddress of DNS server, for example 192.168.0.1. The address given here can be either an IPv4 or an IPv6 address.
1.3.6.1.4.1.44086.4.1.1.3NodedateTime
1.3.6.1.4.1.44086.4.1.1.3.1Scalartimeread-writecurrentCurrent system time. Write to this object to update the system time, use the format HH:MM:SS.
1.3.6.1.4.1.44086.4.1.1.3.2Scalardateread-writecurrentCurrent date of the RCI10. Write to this object to update the system date, use the format dd.mm.yyyy.
1.3.6.1.4.1.44086.4.1.1.3.3Scalartimezoneread-writecurrentTimezone of the RCI10. The timezone gives the difference between UTC and local time in hours.
1.3.6.1.4.1.44086.4.1.1.3.4ScalardstEnread-writecurrentIf 1 the daylight saving time is enabled.
1.3.6.1.4.1.44086.4.1.1.11ScalarhwVersionread-onlycurrentRCI10 hardware version
1.3.6.1.4.1.44086.4.1.1.12ScalarhwSerialread-onlycurrentRCI10 hardware serial number
1.3.6.1.4.1.44086.4.1.1.13ScalarswVersionread-onlycurrentRCI10 software version
1.3.6.1.4.1.44086.4.1.1.14ScalarsystemNameread-writecurrentRCI10 System Name
1.3.6.1.4.1.44086.4.1.1.15ScalarsystemContactread-writecurrentName of the person which is responsible for the system
1.3.6.1.4.1.44086.4.1.1.16ScalarsystemLocationread-writecurrentLocation of this RCI10
1.3.6.1.4.1.44086.4.1.1.50Scalarrebootread-writecurrentWrite 1 to this value will cause a reboot of the RCI10.
1.3.6.1.4.1.44086.4.1.10Nodefuses
1.3.6.1.4.1.44086.4.1.10.1NodefeedA
1.3.6.1.4.1.44086.4.1.10.1.1ScalarsumCurrentAread-onlycurrentCurrent of the whole feed in milliampere
1.3.6.1.4.1.44086.4.1.10.1.10TablefusesATablenot-accessiblecurrent
1.3.6.1.4.1.44086.4.1.10.1.10.1RowfusesAEntrynot-accessiblecurrent
1.3.6.1.4.1.44086.4.1.10.1.10.1.1ColumnindexAnot-accessiblecurrentFuse index
1.3.6.1.4.1.44086.4.1.10.1.10.1.2ColumnavailableAread-onlycurrentStatus of fuse: 0=no fuse, 1=fuse available
1.3.6.1.4.1.44086.4.1.10.1.10.1.3ColumndeviceTypeAread-onlycurrentType number of the fuse
1.3.6.1.4.1.44086.4.1.10.1.10.1.4ColumnserialAread-onlycurrentSerial number of the fuse
1.3.6.1.4.1.44086.4.1.10.1.10.1.5ColumnhwVersionAread-onlycurrentHardware version number of the fuse
1.3.6.1.4.1.44086.4.1.10.1.10.1.6ColumnswVersionAread-onlycurrentSoftware version number of the fuse
1.3.6.1.4.1.44086.4.1.10.1.10.1.7ColumnnominalCurrentAread-onlycurrentNominal current of the fuse in milliampere
1.3.6.1.4.1.44086.4.1.10.1.10.1.8ColumnerrNoSysParAread-onlycurrentNo systemparameter available fault: 0=no fault, 1=fault
1.3.6.1.4.1.44086.4.1.10.1.10.1.9ColumnerrCrcParamAread-onlycurrentParameter CRC fault: 0=no fault, 1=fault
1.3.6.1.4.1.44086.4.1.10.1.10.1.10ColumnerrCrcProgAread-onlycurrentProgram memory CRC fault: 0=no fault, 1=fault
1.3.6.1.4.1.44086.4.1.10.1.10.1.11ColumnerrIntMemAread-onlycurrentInternal memory fault: 0=no fault, 1=fault
1.3.6.1.4.1.44086.4.1.10.1.10.1.12ColumnerrControllerAread-onlycurrentController fault: 0=no fault, 1=fault
1.3.6.1.4.1.44086.4.1.10.1.10.1.13ColumnerrWatchdogAread-onlycurrentWatchdog reset fault: 0=no fault, 1=fault
1.3.6.1.4.1.44086.4.1.10.1.10.1.14ColumnvoltageAread-onlycurrentPower supply voltage in millivolt
1.3.6.1.4.1.44086.4.1.10.1.10.1.15ColumntemperatureAread-onlycurrentCurrent temperature of the fuse in millivolt
1.3.6.1.4.1.44086.4.1.10.1.10.1.16ColumnloadOutputAread-writecurrentOutput status of the fuse: 0=output off, 1=output on
1.3.6.1.4.1.44086.4.1.10.1.10.1.17ColumnstatusShortAread-onlycurrentShort is detected by this fuse: 0=no fault, 1=fault
1.3.6.1.4.1.44086.4.1.10.1.10.1.18ColumnstatusOverloadAread-onlycurrentOverload status: 0=no overload, 1=overload
1.3.6.1.4.1.44086.4.1.10.1.10.1.19ColumnstatusUvltAread-onlycurrentUndervoltage status: 0=no undervoltage, 1=undervoltage
1.3.6.1.4.1.44086.4.1.10.1.10.1.20ColumnstatusOvltAread-onlycurrentOvervoltage status: 0=no overvoltage, 1=overvoltage
1.3.6.1.4.1.44086.4.1.10.1.10.1.21ColumnstatusOtmpAread-onlycurrentOvertemperature status: 0=no overtemperature, 1=overtemperature
1.3.6.1.4.1.44086.4.1.10.1.10.1.22ColumnstatusNoVccAread-onlycurrentNo VCC status: 0=no VCC, 1=VCC ok
1.3.6.1.4.1.44086.4.1.10.1.10.1.23ColumnloadAread-onlycurrentCurrent in milliampere which flows throuth the fuse
1.3.6.1.4.1.44086.4.1.10.1.10.1.24ColumnlabelAread-writecurrentLabel given for this fuse
1.3.6.1.4.1.44086.4.1.10.1.10.1.25ColumnnominalVoltageAread-onlycurrentPolarity and nominal voltage of the fuse in volt. E.g.: -48
1.3.6.1.4.1.44086.4.1.10.1.10.1.26ColumnmultiEsxAread-onlycurrentMultiEsx: Fuses are connected in parallel to protect higher nominal loads: 0=not connected, 1=connected to a lower slot index, 2=connected as first
1.3.6.1.4.1.44086.4.1.10.2NodefeedB
1.3.6.1.4.1.44086.4.1.10.2.1ScalarsumCurrentBread-onlycurrentCurrent of the whole feed in milliampere
1.3.6.1.4.1.44086.4.1.10.2.10TablefusesBTablenot-accessiblecurrent
1.3.6.1.4.1.44086.4.1.10.2.10.1RowfusesBEntrynot-accessiblecurrent
1.3.6.1.4.1.44086.4.1.10.2.10.1.1ColumnindexBnot-accessiblecurrentFuse index
1.3.6.1.4.1.44086.4.1.10.2.10.1.2ColumnavailableBread-onlycurrentStatus of fuse: 0=no fuse, 1=fuse available
1.3.6.1.4.1.44086.4.1.10.2.10.1.3ColumndeviceTypeBread-onlycurrentType number of the fuse
1.3.6.1.4.1.44086.4.1.10.2.10.1.4ColumnserialBread-onlycurrentSerial number of the fuse
1.3.6.1.4.1.44086.4.1.10.2.10.1.5ColumnhwVersionBread-onlycurrentHardware version number of the fuse
1.3.6.1.4.1.44086.4.1.10.2.10.1.6ColumnswVersionBread-onlycurrentSoftware version number of the fuse
1.3.6.1.4.1.44086.4.1.10.2.10.1.7ColumnnominalCurrentBread-onlycurrentNominal current of the fuse in milliampere
1.3.6.1.4.1.44086.4.1.10.2.10.1.8ColumnerrNoSysParBread-onlycurrentNo systemparameter available fault: 0=no fault, 1=fault
1.3.6.1.4.1.44086.4.1.10.2.10.1.9ColumnerrCrcParamBread-onlycurrentParameter CRC fault: 0=no fault, 1=fault
1.3.6.1.4.1.44086.4.1.10.2.10.1.10ColumnerrCrcProgBread-onlycurrentProgram memory CRC fault: 0=no fault, 1=fault
1.3.6.1.4.1.44086.4.1.10.2.10.1.11ColumnerrIntMemBread-onlycurrentInternal memory fault: 0=no fault, 1=fault
1.3.6.1.4.1.44086.4.1.10.2.10.1.12ColumnerrControllerBread-onlycurrentController fault: 0=no fault, 1=fault
1.3.6.1.4.1.44086.4.1.10.2.10.1.13ColumnerrWatchdogBread-onlycurrentWatchdog reset fault: 0=no fault, 1=fault
1.3.6.1.4.1.44086.4.1.10.2.10.1.14ColumnvoltageBread-onlycurrentPower supply voltage in millivolt
1.3.6.1.4.1.44086.4.1.10.2.10.1.15ColumntemperatureBread-onlycurrentCurrent temperature of the fuse in millivolt
1.3.6.1.4.1.44086.4.1.10.2.10.1.16ColumnloadOutputBread-writecurrentOutput status of the fuse: 0=output off, 1=output on
1.3.6.1.4.1.44086.4.1.10.2.10.1.17ColumnstatusShortBread-onlycurrentShort is detected by this fuse: 0=no fault, 1=fault
1.3.6.1.4.1.44086.4.1.10.2.10.1.18ColumnstatusOverloadBread-onlycurrentOverload status: 0=no overload, 1=overload
1.3.6.1.4.1.44086.4.1.10.2.10.1.19ColumnstatusUvltBread-onlycurrentUndervoltage status: 0=no undervoltage, 1=undervoltage
1.3.6.1.4.1.44086.4.1.10.2.10.1.20ColumnstatusOvltBread-onlycurrentOvervoltage status: 0=no overvoltage, 1=overvoltage
1.3.6.1.4.1.44086.4.1.10.2.10.1.21ColumnstatusOtmpBread-onlycurrentOvertemperature status: 0=no overtemperature, 1=overtemperature
1.3.6.1.4.1.44086.4.1.10.2.10.1.22ColumnstatusNoVccBread-onlycurrentNo VCC status: 0=no VCC, 1=VCC ok
1.3.6.1.4.1.44086.4.1.10.2.10.1.23ColumnloadBread-onlycurrentLoad current in milliampere which flows throuth the fuse
1.3.6.1.4.1.44086.4.1.10.2.10.1.24ColumnlabelBread-writecurrentLabel given for this fuse
1.3.6.1.4.1.44086.4.1.10.2.10.1.25ColumnnominalVoltageBread-onlycurrentPolarity and nominal voltage of the fuse in volt. E.g.: -48
1.3.6.1.4.1.44086.4.1.10.2.10.1.26ColumnmultiEsxBread-onlycurrentMultiEsx: Fuses are connected in parallel to protect higher nominal loads: 0=not connected, 1=connected to a lower slot index, 2=connected as first
1.3.6.1.4.1.44086.4.1.10.20ScalarswitchAllFusesread-writecurrentSets the output state of all fuses: 0=output off, 1=output on
1.3.6.1.4.1.44086.4.1.10.40ScalarmonitorEnabledread-onlycurrentIf 1 is returned any automatic feed or fuse monitor is enabled.
1.3.6.1.4.1.44086.4.1.20NodeexternalAlarms
1.3.6.1.4.1.44086.4.1.20.1NodeeaFeedA
1.3.6.1.4.1.44086.4.1.20.1.1TableeaATablenot-accessiblecurrent
1.3.6.1.4.1.44086.4.1.20.1.1.1RoweaAEntrynot-accessiblecurrent
1.3.6.1.4.1.44086.4.1.20.1.1.1.1ColumneaIndexAnot-accessiblecurrentDevice index (slot number)
1.3.6.1.4.1.44086.4.1.20.1.1.1.2ColumneaAvailableAread-onlycurrentStatus of the device: 0=no EAI device, 1=EEAI device available
1.3.6.1.4.1.44086.4.1.20.1.1.1.3ColumneaDeviceTypeAread-onlycurrentType number of the device
1.3.6.1.4.1.44086.4.1.20.1.1.1.4ColumneaSerialAread-onlycurrentSerial number of the device
1.3.6.1.4.1.44086.4.1.20.1.1.1.5ColumneaHwVersionAread-onlycurrentHardware version number of the device
1.3.6.1.4.1.44086.4.1.20.1.1.1.6ColumneaSwVersionAread-onlycurrentSoftware version number of the device
1.3.6.1.4.1.44086.4.1.20.1.1.1.7ColumneaOutput1Aread-writecurrentStatus of the relay output1: 0=output off, 1=output on (contact to normaly close is closed)
1.3.6.1.4.1.44086.4.1.20.1.1.1.8ColumneaOutput2Aread-writecurrentStatus of the relay output2: 0=output off, 1=output on (contact to normaly close is closed)
1.3.6.1.4.1.44086.4.1.20.1.1.1.9ColumneaInput1Aread-onlycurrentStatus digital input1: 0=low, 1=high
1.3.6.1.4.1.44086.4.1.20.1.1.1.10ColumneaInput2Aread-onlycurrentStatus digital input2: 0=low, 1=high
1.3.6.1.4.1.44086.4.1.20.1.1.1.11ColumneaInput3Aread-onlycurrentStatus digital input3: 0=low, 1=high
1.3.6.1.4.1.44086.4.1.20.1.1.1.12ColumneaInput4Aread-onlycurrentStatus digital input4: 0=low, 1=high
1.3.6.1.4.1.44086.4.1.20.1.1.1.13ColumneaInput5Aread-onlycurrentStatus digital input5: 0=low, 1=high
1.3.6.1.4.1.44086.4.1.20.1.1.1.14ColumneaInput6Aread-onlycurrentStatus digital input6: 0=low, 1=high
1.3.6.1.4.1.44086.4.1.20.1.1.1.15ColumneaInput7Aread-onlycurrentStatus digital input7: 0=low, 1=high
1.3.6.1.4.1.44086.4.1.20.1.1.1.16ColumneaInput8Aread-onlycurrentStatus digital input8: 0=low, 1=high
1.3.6.1.4.1.44086.4.1.20.1.1.1.17ColumneaAnalogInputAread-onlycurrentAnalog current input in mA
1.3.6.1.4.1.44086.4.1.20.1.1.1.18ColumneaLabelOutput1Aread-writecurrentLabel for output1 of this EAI device
1.3.6.1.4.1.44086.4.1.20.1.1.1.19ColumneaLabelOutput2Aread-writecurrentLabel for output2 of this EAI device
1.3.6.1.4.1.44086.4.1.20.1.1.1.20ColumneaLabelInput1Aread-writecurrentLabel for input1 of this EAI device
1.3.6.1.4.1.44086.4.1.20.1.1.1.21ColumneaLabelInput2Aread-writecurrentLabel for input2 of this EAI device
1.3.6.1.4.1.44086.4.1.20.1.1.1.22ColumneaLabelInput3Aread-writecurrentLabel for input3 of this EAI device
1.3.6.1.4.1.44086.4.1.20.1.1.1.23ColumneaLabelInput4Aread-writecurrentLabel for input4 of this EAI device
1.3.6.1.4.1.44086.4.1.20.1.1.1.24ColumneaLabelInput5Aread-writecurrentLabel for input5 of this EAI device
1.3.6.1.4.1.44086.4.1.20.1.1.1.25ColumneaLabelInput6Aread-writecurrentLabel for input6 of this EAI device
1.3.6.1.4.1.44086.4.1.20.1.1.1.26ColumneaLabelInput7Aread-writecurrentLabel for input7 of this EAI device
1.3.6.1.4.1.44086.4.1.20.1.1.1.27ColumneaLabelInput8Aread-writecurrentLabel for input8 of this EAI device
1.3.6.1.4.1.44086.4.1.20.1.1.1.28ColumneaLabelAnalogInputAread-writecurrentLabel for the analog input of this EAI device
1.3.6.1.4.1.44086.4.1.20.1.1.1.29ColumneaSignallingGroupOutput1Aread-writecurrentSignalling function for output1. Syntax: 20 (for 20 slots) characters '0' or '1'. '0'= signalling not active for this slot; '0'= signalling is active for this …
1.3.6.1.4.1.44086.4.1.20.1.1.1.30ColumneaSignallingActiveOutput1Aread-onlycurrentStatus of signalling function for output1: 0=not active, 1=active
1.3.6.1.4.1.44086.4.1.20.1.1.1.31ColumneaSignallingGroupOutput2Aread-writecurrentSignalling function for output2. Syntax: 20 (for 20 slots) characters '0' or '1'. '0'= signalling not active for this slot; '0'= signalling is active for this …
1.3.6.1.4.1.44086.4.1.20.1.1.1.32ColumneaSignallingActiveOutput2Aread-onlycurrentStatus of signalling function for output2: 0=not active, 1=active
1.3.6.1.4.1.44086.4.1.20.1.1.1.33ColumneaLogicFunctionOutput1Aread-writecurrentLogic function for output1. Length: 40 characters. Syntax: Logic connections '*'=AND, '+'=OR, '!'=Negation; Signals: EAI digital input 'eai<slot address>in<inp…
1.3.6.1.4.1.44086.4.1.20.1.1.1.34ColumneaLogicFunctionActiveOutput1Aread-onlycurrentStatus of logic function for output1: 0=not active, 1=active
1.3.6.1.4.1.44086.4.1.20.1.1.1.35ColumneaLogicFunctionOutput2Aread-writecurrentLogic function for output2. Length: 40 characters. Syntax: Logic connections '*'=AND, '+'=OR, '!'=Negation; Signals: EAI digital input 'eai<slot address>in<inp…
1.3.6.1.4.1.44086.4.1.20.1.1.1.36ColumneaLogicFunctionActiveOutput2Aread-onlycurrentStatus of logic function for output2: 0=not active, 1=active
1.3.6.1.4.1.44086.4.1.20.2NodeeaFeedB
1.3.6.1.4.1.44086.4.1.20.2.1TableeaBTablenot-accessiblecurrent
1.3.6.1.4.1.44086.4.1.20.2.1.1RoweaBEntrynot-accessiblecurrent
1.3.6.1.4.1.44086.4.1.20.2.1.1.1ColumneaIndexBnot-accessiblecurrentDevice index (slot number)
1.3.6.1.4.1.44086.4.1.20.2.1.1.2ColumneaAvailableBread-onlycurrentStatus of the device: 0=no EAI device, 1=EEAI device available
1.3.6.1.4.1.44086.4.1.20.2.1.1.3ColumneaDeviceTypeBread-onlycurrentType number of the device
1.3.6.1.4.1.44086.4.1.20.2.1.1.4ColumneaSerialBread-onlycurrentSerial number of the device
1.3.6.1.4.1.44086.4.1.20.2.1.1.5ColumneaHwVersionBread-onlycurrentHardware version number of the device
1.3.6.1.4.1.44086.4.1.20.2.1.1.6ColumneaSwVersionBread-onlycurrentSoftware version number of the device
1.3.6.1.4.1.44086.4.1.20.2.1.1.7ColumneaOutput1Bread-writecurrentStatus of the relay output1: 0=output off, 1=output on (contact to normaly close is closed)
1.3.6.1.4.1.44086.4.1.20.2.1.1.8ColumneaOutput2Bread-writecurrentStatus of the relay output2: 0=output off, 1=output on (contact to normaly close is closed)
1.3.6.1.4.1.44086.4.1.20.2.1.1.9ColumneaInput1Bread-onlycurrentStatus digital input1: 0=low, 1=high
1.3.6.1.4.1.44086.4.1.20.2.1.1.10ColumneaInput2Bread-onlycurrentStatus digital input2: 0=low, 1=high
1.3.6.1.4.1.44086.4.1.20.2.1.1.11ColumneaInput3Bread-onlycurrentStatus digital input3: 0=low, 1=high
1.3.6.1.4.1.44086.4.1.20.2.1.1.12ColumneaInput4Bread-onlycurrentStatus digital input4: 0=low, 1=high
1.3.6.1.4.1.44086.4.1.20.2.1.1.13ColumneaInput5Bread-onlycurrentStatus digital input5: 0=low, 1=high
1.3.6.1.4.1.44086.4.1.20.2.1.1.14ColumneaInput6Bread-onlycurrentStatus digital input6: 0=low, 1=high
1.3.6.1.4.1.44086.4.1.20.2.1.1.15ColumneaInput7Bread-onlycurrentStatus digital input7: 0=low, 1=high
1.3.6.1.4.1.44086.4.1.20.2.1.1.16ColumneaInput8Bread-onlycurrentStatus digital input8: 0=low, 1=high
1.3.6.1.4.1.44086.4.1.20.2.1.1.17ColumneaAnalogInputBread-onlycurrentAnalog current input in mA
1.3.6.1.4.1.44086.4.1.20.2.1.1.18ColumneaLabelOutput1Bread-writecurrentLabel for output1 of this EAI device
1.3.6.1.4.1.44086.4.1.20.2.1.1.19ColumneaLabelOutput2Bread-writecurrentLabel for output2 of this EAI device
1.3.6.1.4.1.44086.4.1.20.2.1.1.20ColumneaLabelInput1Bread-writecurrentLabel for input1 of this EAI device
1.3.6.1.4.1.44086.4.1.20.2.1.1.21ColumneaLabelInput2Bread-writecurrentLabel for input2 of this EAI device
1.3.6.1.4.1.44086.4.1.20.2.1.1.22ColumneaLabelInput3Bread-writecurrentLabel for input3 of this EAI device
1.3.6.1.4.1.44086.4.1.20.2.1.1.23ColumneaLabelInput4Bread-writecurrentLabel for input4 of this EAI device
1.3.6.1.4.1.44086.4.1.20.2.1.1.24ColumneaLabelInput5Bread-writecurrentLabel for input5 of this EAI device
1.3.6.1.4.1.44086.4.1.20.2.1.1.25ColumneaLabelInput6Bread-writecurrentLabel for input6 of this EAI device
1.3.6.1.4.1.44086.4.1.20.2.1.1.26ColumneaLabelInput7Bread-writecurrentLabel for input7 of this EAI device
1.3.6.1.4.1.44086.4.1.20.2.1.1.27ColumneaLabelInput8Bread-writecurrentLabel for input8 of this EAI device
1.3.6.1.4.1.44086.4.1.20.2.1.1.28ColumneaLabelAnalogInputBread-writecurrentLabel for the analog input of this EAI device
1.3.6.1.4.1.44086.4.1.20.2.1.1.29ColumneaSignallingGroupOutput1Bread-writecurrentSignalling function for output1. Syntax: 20 (for 20 slots) characters '0' or '1'. '0'= signalling not active for this slot; '0'= signalling is active for this …
1.3.6.1.4.1.44086.4.1.20.2.1.1.30ColumneaSignallingActiveOutput1Bread-onlycurrentStatus of signalling function for output1: 0=not active, 1=active
1.3.6.1.4.1.44086.4.1.20.2.1.1.31ColumneaSignallingGroupOutput2Bread-writecurrentSignalling function for output2. Syntax: 20 (for 20 slots) characters '0' or '1'. '0'= signalling not active for this slot; '0'= signalling is active for this …
1.3.6.1.4.1.44086.4.1.20.2.1.1.32ColumneaSignallingActiveOutput2Bread-onlycurrentStatus of signalling function for output2: 0=not active, 1=active
1.3.6.1.4.1.44086.4.1.20.2.1.1.33ColumneaLogicFunctionOutput1Bread-writecurrentLogic function for output1. Length: 40 characters. Syntax: Logic connections '*'=AND, '+'=OR, '!'=Negation; Signals: EAI digital input 'eai<slot address>in<inp…
1.3.6.1.4.1.44086.4.1.20.2.1.1.34ColumneaLogicFunctionActiveOutput1Bread-onlycurrentStatus of logic function for output1: 0=not active, 1=active
1.3.6.1.4.1.44086.4.1.20.2.1.1.35ColumneaLogicFunctionOutput2Bread-writecurrentLogic function for output2. Length: 40 characters. Syntax: Logic connections '*'=AND, '+'=OR, '!'=Negation; Signals: EAI digital input 'eai<slot address>in<inp…
1.3.6.1.4.1.44086.4.1.20.2.1.1.36ColumneaLogicFunctionActiveOutput2Bread-onlycurrentStatus of logic function for output2: 0=not active, 1=active
1.3.6.1.4.1.44086.4.1.100Nodenotifications
1.3.6.1.4.1.44086.4.1.100.1Nodeprefix
1.3.6.1.4.1.44086.4.1.100.1.1NodesystemNotifications
1.3.6.1.4.1.44086.4.1.100.1.1.1NotificationpowerUpcurrentThis notification is sent after a successful power up
1.3.6.1.4.1.44086.4.1.100.1.1.2NotificationsystemFailurecurrentIf the system enters failure mode this Trap is sent
1.3.6.1.4.1.44086.4.1.100.1.10NodefusesNotifications
1.3.6.1.4.1.44086.4.1.100.1.10.1NotificationfuseNewcurrentThis Trap is sent if a new fuse was found
1.3.6.1.4.1.44086.4.1.100.1.10.2NotificationfuseGonecurrentInforms that a fuse which responds onto requests in the past does no longer respond.
1.3.6.1.4.1.44086.4.1.100.1.10.3NotificationfuseWrongcurrentA recently added fuse has a different nominal current as the fuse in the same slot had before.
1.3.6.1.4.1.44086.4.1.100.1.10.4NotificationfuseOutputStateChangedcurrentInforms that the output state of a fuse had changed his status.
1.3.6.1.4.1.44086.4.1.100.1.10.5NotificationfuseFailurecurrentIf any status or error flag changes, this trap is sent.
1.3.6.1.4.1.44086.4.1.100.1.20NodeexternalAlarmNotifications
1.3.6.1.4.1.44086.4.1.100.1.20.1NotificationeaNewcurrentThis Trap is sent if a new external alarm device was found
1.3.6.1.4.1.44086.4.1.100.1.20.2NotificationeaGonecurrentInforms that a external alarm device, which responded onto requests in the past, does no longer respond.
1.3.6.1.4.1.44086.4.1.100.1.20.3NotificationeaActiveFunctionWarningcurrentInforms that a logic- or signalling function is configured for a new plugged or pulled external alarm device.
1.3.6.1.4.1.44086.4.1.100.1.20.4NotificationeaInternalErrorcurrentInforms that a internal error of external alarm device occured
1.3.6.1.4.1.44086.4.1.100.1.20.5NotificationeaMasterWasNotAvailablecurrentInforms (one time) that a external alarm device detected, that the master device was not available for some time.
1.3.6.1.4.1.44086.4.1.100.1.20.6NotificationeaInputChangedcurrentInforms that a external alarm device input has changed its state; Summary for all inputs of one external alarm device.
1.3.6.1.4.1.44086.4.1.100.1.20.7NotificationeaOutputChangedcurrentInforms that a external alarm device output has changed its state; Summary for all outputs of one external alarm device.
1.3.6.1.4.1.44086.4.1.100.1.20.8NotificationeaSingleInputChangedcurrentInforms that a external alarm device input has changed its state; Is sent for every changed input. If input changed high: 'raise'; If input changed low: 'clear'
1.3.6.1.4.1.44086.4.1.100.1.20.9NotificationeaSingleOutputChangedcurrentInforms that a external alarm device output has changed its state; Is sent for every changed output. If output changed high: 'raise'; If output changed low: 'c…
1.3.6.1.4.1.44086.4.1.100.2Nodeobjects
1.3.6.1.4.1.44086.4.1.100.2.1NodesystemObjects
1.3.6.1.4.1.44086.4.1.100.2.1.1ScalarresetReasonaccessible-for-notifycurrentHolds a human readable text which gives the reason for reset. Possible values are coldstart, warmstart or watchdog
1.3.6.1.4.1.44086.4.1.100.2.1.2ScalarfailureReasonaccessible-for-notifycurrentHolds a human readable text which gives the reason for system failure.
1.3.6.1.4.1.44086.4.1.100.2.10NodefusesObjects
1.3.6.1.4.1.44086.4.1.100.2.10.1ScalarfuseNraccessible-for-notifycurrentGives the number of a fuse
1.3.6.1.4.1.44086.4.1.100.2.10.2ScalarfuseLabelaccessible-for-notifycurrentGives the label of a fuse
1.3.6.1.4.1.44086.4.1.100.2.10.5ScalarfuseOutputStateaccessible-for-notifycurrentDefines the output state of a fuse. 0 = Output off, 1 = Output on
1.3.6.1.4.1.44086.4.1.100.2.10.10ScalarfuseErrorRegisteraccessible-for-notifycurrentDefines the error register data type.
1.3.6.1.4.1.44086.4.1.100.2.10.20ScalarfuseStatusShortCircuitaccessible-for-notifycurrentStatus register flag for short circuit
1.3.6.1.4.1.44086.4.1.100.2.10.21ScalarfuseStatusOverloadaccessible-for-notifycurrentStatus register flag for overload
1.3.6.1.4.1.44086.4.1.100.2.10.22ScalarfuseStatusUndervoltageaccessible-for-notifycurrentStatus register flag for undervoltage
1.3.6.1.4.1.44086.4.1.100.2.10.23ScalarfuseStatusOvervoltageaccessible-for-notifycurrentStatus register flag for overvoltage
1.3.6.1.4.1.44086.4.1.100.2.10.24ScalarfuseStatusOvertemperatureaccessible-for-notifycurrentStatus register flag for overtemperature
1.3.6.1.4.1.44086.4.1.100.2.10.25ScalarfuseStatusNoPowerSupplyaccessible-for-notifycurrentStatus register flag for no power supply
1.3.6.1.4.1.44086.4.1.100.2.10.30ScalarfuseOldNominalCurrentaccessible-for-notifycurrentThe nominal current of the fuse which was located in this slot before.
1.3.6.1.4.1.44086.4.1.100.2.10.31ScalarfuseNewNominalCurrentaccessible-for-notifycurrentThe nominal current of the new fuse
1.3.6.1.4.1.44086.4.1.100.2.20NodeexternalAlarmObjects
1.3.6.1.4.1.44086.4.1.100.2.20.1ScalareaSlotNraccessible-for-notifycurrentGives the slot number of a external alarm device
1.3.6.1.4.1.44086.4.1.100.2.20.2ScalareaInputStatesaccessible-for-notifycurrentGives the input states of the external alarm device. [Left -> right: output 1 .. output n]
1.3.6.1.4.1.44086.4.1.100.2.20.3ScalareaOutputStatesaccessible-for-notifycurrentGives the output states of the external alarm device. [Left -> right: output 1 .. output n]
1.3.6.1.4.1.44086.4.1.100.2.20.4ScalareaFailureMsgaccessible-for-notifycurrentGives a human readable text for a external alarm device failure.
1.3.6.1.4.1.44086.4.1.100.2.20.5ScalareaMsgaccessible-for-notifycurrentGives a human readable text for a external alarm device notification.
1.3.6.1.4.1.44086.4.1.100.2.20.6ScalareaInputNraccessible-for-notifycurrentGives the input Nr. of a external alarm device input. [1-8]
1.3.6.1.4.1.44086.4.1.100.2.20.7ScalareaInputLabelaccessible-for-notifycurrentGives the label of a external alarm device input.
1.3.6.1.4.1.44086.4.1.100.2.20.8ScalareaInputStateaccessible-for-notifycurrentGives the state of an external alarm device input. [raise/clear]
1.3.6.1.4.1.44086.4.1.100.2.20.9ScalareaOutputNraccessible-for-notifycurrentGives the output Nr. of a external alarm device output. [1-2]
1.3.6.1.4.1.44086.4.1.100.2.20.10ScalareaOutputLabelaccessible-for-notifycurrentGives the label of a external alarm device output.
1.3.6.1.4.1.44086.4.1.100.2.20.11ScalareaOutputStateaccessible-for-notifycurrentGives the state of an external alarm device output. [raise/clear]