ETA-RCI10-MIB
229 objects
Copyright notice (c) E-T-A Elektrotechnische Apparate GmbH 2014-2015 Florian Pfanner, Michael Haerteis This MIB file was created for a RCI10. Via SNMP the slave states can be retrieved and device actions can initiated.
Imported Objects
| SNMPv2-SMI | enterprises Integer32 IpAddress MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.44086 | Nodeeta | |||
| 1.3.6.1.4.1.44086.4 | NodeetaProp | |||
| 1.3.6.1.4.1.44086.4.1 | Identityrci10 | Copyright notice (c) E-T-A Elektrotechnische Apparate GmbH 2014-2015 Florian Pfanner, Michael Haerteis This MIB file was created for a RCI10. Via SNMP the slav… | ||
| 1.3.6.1.4.1.44086.4.1.1 | Nodesystem | |||
| 1.3.6.1.4.1.44086.4.1.1.1 | Nodesnmp | |||
| 1.3.6.1.4.1.44086.4.1.1.1.1 | ScalarsnmpTrapsEnable | read-write | current | If 1 sending of SNMP traps is enabled. Else no traps will be sent |
| 1.3.6.1.4.1.44086.4.1.1.1.2 | ScalarsnmpTrapTarget | read-write | current | Traps are sent to the destination given here. This could be an IP address or a host name. |
| 1.3.6.1.4.1.44086.4.1.1.1.3 | ScalarsnmpProtocol | read-only | current | SNMP protocol version currently used. The value can only be changed using the SSH configuration. |
| 1.3.6.1.4.1.44086.4.1.1.1.10 | ScalarsnmpCommunityString | read-write | current | SNMP community string used to access the values. Also the SNMP traps are sent using this community string. Only valid if SNMPv2c is used. |
| 1.3.6.1.4.1.44086.4.1.1.1.20 | ScalarsnmpLogin | read-write | current | Login name used to access the SNMP data values. Only valid if SNMPv3 is used. |
| 1.3.6.1.4.1.44086.4.1.1.1.21 | ScalarsnmpPassword | read-write | current | Password used to access the SNMP data values. The password have to be at least eight characters long. Only valid if SNMPv3 is used. |
| 1.3.6.1.4.1.44086.4.1.1.1.22 | ScalarsnmpAuthentication | read-write | current | Authentication method used to encrypt the SNMP data transmission. Valid entries are 'MD5' and 'SHA'. Only valid if SNMPv3 is used. |
| 1.3.6.1.4.1.44086.4.1.1.1.23 | ScalarsnmpEncryption | read-write | current | Encryption method used for the SNMP data transmission. Valid entries are 'AES', 'DES' and 'off'. Only valid if SNMPv3 is used. |
| 1.3.6.1.4.1.44086.4.1.1.1.24 | ScalarsnmpEncryptionKey | read-write | current | Encryption key used for the SNMP data transmission. Only valid if SNMPv3 is used. |
| 1.3.6.1.4.1.44086.4.1.1.2 | Nodeethernet | |||
| 1.3.6.1.4.1.44086.4.1.1.2.1 | Nodeipv4 | |||
| 1.3.6.1.4.1.44086.4.1.1.2.1.1 | Scalardhcpv4Enable | read-write | current | If 1 the IPv4 settings are automatically obtained using DHCP. |
| 1.3.6.1.4.1.44086.4.1.1.2.1.10 | Scalarip4Address | read-write | current | IPv4 adress of the RCI10, for example 192.168.1.25. |
| 1.3.6.1.4.1.44086.4.1.1.2.1.11 | Scalarip4NetMask | read-write | current | IPv4 network mask, for example 255.255.255.0. |
| 1.3.6.1.4.1.44086.4.1.1.2.1.12 | Scalarip4Gateway | read-write | current | IPv4 gateway address, for example 192.168.1.1. |
| 1.3.6.1.4.1.44086.4.1.1.2.2 | Nodeipv6 | |||
| 1.3.6.1.4.1.44086.4.1.1.2.2.1 | Scalardhcpv6Enable | read-write | current | If 1 the IPv6 settings are automatically obtained using DHCP. |
| 1.3.6.1.4.1.44086.4.1.1.2.2.10 | Scalarip6Address | read-write | current | IPv6 adress of the RCI10, for example 2001:0db8:85a3::1000. |
| 1.3.6.1.4.1.44086.4.1.1.2.2.11 | Scalarip6PrefixLength | read-write | current | IPv6 network prefix length. Valid range is from 1 to 128. |
| 1.3.6.1.4.1.44086.4.1.1.2.10 | ScalardnsServer | read-write | current | Address of DNS server, for example 192.168.0.1. The address given here can be either an IPv4 or an IPv6 address. |
| 1.3.6.1.4.1.44086.4.1.1.3 | NodedateTime | |||
| 1.3.6.1.4.1.44086.4.1.1.3.1 | Scalartime | read-write | current | Current system time. Write to this object to update the system time, use the format HH:MM:SS. |
| 1.3.6.1.4.1.44086.4.1.1.3.2 | Scalardate | read-write | current | Current date of the RCI10. Write to this object to update the system date, use the format dd.mm.yyyy. |
| 1.3.6.1.4.1.44086.4.1.1.3.3 | Scalartimezone | read-write | current | Timezone of the RCI10. The timezone gives the difference between UTC and local time in hours. |
| 1.3.6.1.4.1.44086.4.1.1.3.4 | ScalardstEn | read-write | current | If 1 the daylight saving time is enabled. |
| 1.3.6.1.4.1.44086.4.1.1.11 | ScalarhwVersion | read-only | current | RCI10 hardware version |
| 1.3.6.1.4.1.44086.4.1.1.12 | ScalarhwSerial | read-only | current | RCI10 hardware serial number |
| 1.3.6.1.4.1.44086.4.1.1.13 | ScalarswVersion | read-only | current | RCI10 software version |
| 1.3.6.1.4.1.44086.4.1.1.14 | ScalarsystemName | read-write | current | RCI10 System Name |
| 1.3.6.1.4.1.44086.4.1.1.15 | ScalarsystemContact | read-write | current | Name of the person which is responsible for the system |
| 1.3.6.1.4.1.44086.4.1.1.16 | ScalarsystemLocation | read-write | current | Location of this RCI10 |
| 1.3.6.1.4.1.44086.4.1.1.50 | Scalarreboot | read-write | current | Write 1 to this value will cause a reboot of the RCI10. |
| 1.3.6.1.4.1.44086.4.1.10 | Nodefuses | |||
| 1.3.6.1.4.1.44086.4.1.10.1 | NodefeedA | |||
| 1.3.6.1.4.1.44086.4.1.10.1.1 | ScalarsumCurrentA | read-only | current | Current of the whole feed in milliampere |
| 1.3.6.1.4.1.44086.4.1.10.1.10 | TablefusesATable | not-accessible | current | |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1 | RowfusesAEntry | not-accessible | current | |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.1 | ColumnindexA | not-accessible | current | Fuse index |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.2 | ColumnavailableA | read-only | current | Status of fuse: 0=no fuse, 1=fuse available |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.3 | ColumndeviceTypeA | read-only | current | Type number of the fuse |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.4 | ColumnserialA | read-only | current | Serial number of the fuse |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.5 | ColumnhwVersionA | read-only | current | Hardware version number of the fuse |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.6 | ColumnswVersionA | read-only | current | Software version number of the fuse |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.7 | ColumnnominalCurrentA | read-only | current | Nominal current of the fuse in milliampere |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.8 | ColumnerrNoSysParA | read-only | current | No systemparameter available fault: 0=no fault, 1=fault |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.9 | ColumnerrCrcParamA | read-only | current | Parameter CRC fault: 0=no fault, 1=fault |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.10 | ColumnerrCrcProgA | read-only | current | Program memory CRC fault: 0=no fault, 1=fault |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.11 | ColumnerrIntMemA | read-only | current | Internal memory fault: 0=no fault, 1=fault |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.12 | ColumnerrControllerA | read-only | current | Controller fault: 0=no fault, 1=fault |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.13 | ColumnerrWatchdogA | read-only | current | Watchdog reset fault: 0=no fault, 1=fault |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.14 | ColumnvoltageA | read-only | current | Power supply voltage in millivolt |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.15 | ColumntemperatureA | read-only | current | Current temperature of the fuse in millivolt |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.16 | ColumnloadOutputA | read-write | current | Output status of the fuse: 0=output off, 1=output on |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.17 | ColumnstatusShortA | read-only | current | Short is detected by this fuse: 0=no fault, 1=fault |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.18 | ColumnstatusOverloadA | read-only | current | Overload status: 0=no overload, 1=overload |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.19 | ColumnstatusUvltA | read-only | current | Undervoltage status: 0=no undervoltage, 1=undervoltage |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.20 | ColumnstatusOvltA | read-only | current | Overvoltage status: 0=no overvoltage, 1=overvoltage |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.21 | ColumnstatusOtmpA | read-only | current | Overtemperature status: 0=no overtemperature, 1=overtemperature |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.22 | ColumnstatusNoVccA | read-only | current | No VCC status: 0=no VCC, 1=VCC ok |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.23 | ColumnloadA | read-only | current | Current in milliampere which flows throuth the fuse |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.24 | ColumnlabelA | read-write | current | Label given for this fuse |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.25 | ColumnnominalVoltageA | read-only | current | Polarity and nominal voltage of the fuse in volt. E.g.: -48 |
| 1.3.6.1.4.1.44086.4.1.10.1.10.1.26 | ColumnmultiEsxA | read-only | current | MultiEsx: Fuses are connected in parallel to protect higher nominal loads: 0=not connected, 1=connected to a lower slot index, 2=connected as first |
| 1.3.6.1.4.1.44086.4.1.10.2 | NodefeedB | |||
| 1.3.6.1.4.1.44086.4.1.10.2.1 | ScalarsumCurrentB | read-only | current | Current of the whole feed in milliampere |
| 1.3.6.1.4.1.44086.4.1.10.2.10 | TablefusesBTable | not-accessible | current | |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1 | RowfusesBEntry | not-accessible | current | |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.1 | ColumnindexB | not-accessible | current | Fuse index |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.2 | ColumnavailableB | read-only | current | Status of fuse: 0=no fuse, 1=fuse available |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.3 | ColumndeviceTypeB | read-only | current | Type number of the fuse |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.4 | ColumnserialB | read-only | current | Serial number of the fuse |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.5 | ColumnhwVersionB | read-only | current | Hardware version number of the fuse |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.6 | ColumnswVersionB | read-only | current | Software version number of the fuse |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.7 | ColumnnominalCurrentB | read-only | current | Nominal current of the fuse in milliampere |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.8 | ColumnerrNoSysParB | read-only | current | No systemparameter available fault: 0=no fault, 1=fault |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.9 | ColumnerrCrcParamB | read-only | current | Parameter CRC fault: 0=no fault, 1=fault |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.10 | ColumnerrCrcProgB | read-only | current | Program memory CRC fault: 0=no fault, 1=fault |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.11 | ColumnerrIntMemB | read-only | current | Internal memory fault: 0=no fault, 1=fault |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.12 | ColumnerrControllerB | read-only | current | Controller fault: 0=no fault, 1=fault |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.13 | ColumnerrWatchdogB | read-only | current | Watchdog reset fault: 0=no fault, 1=fault |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.14 | ColumnvoltageB | read-only | current | Power supply voltage in millivolt |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.15 | ColumntemperatureB | read-only | current | Current temperature of the fuse in millivolt |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.16 | ColumnloadOutputB | read-write | current | Output status of the fuse: 0=output off, 1=output on |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.17 | ColumnstatusShortB | read-only | current | Short is detected by this fuse: 0=no fault, 1=fault |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.18 | ColumnstatusOverloadB | read-only | current | Overload status: 0=no overload, 1=overload |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.19 | ColumnstatusUvltB | read-only | current | Undervoltage status: 0=no undervoltage, 1=undervoltage |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.20 | ColumnstatusOvltB | read-only | current | Overvoltage status: 0=no overvoltage, 1=overvoltage |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.21 | ColumnstatusOtmpB | read-only | current | Overtemperature status: 0=no overtemperature, 1=overtemperature |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.22 | ColumnstatusNoVccB | read-only | current | No VCC status: 0=no VCC, 1=VCC ok |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.23 | ColumnloadB | read-only | current | Load current in milliampere which flows throuth the fuse |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.24 | ColumnlabelB | read-write | current | Label given for this fuse |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.25 | ColumnnominalVoltageB | read-only | current | Polarity and nominal voltage of the fuse in volt. E.g.: -48 |
| 1.3.6.1.4.1.44086.4.1.10.2.10.1.26 | ColumnmultiEsxB | read-only | current | MultiEsx: Fuses are connected in parallel to protect higher nominal loads: 0=not connected, 1=connected to a lower slot index, 2=connected as first |
| 1.3.6.1.4.1.44086.4.1.10.20 | ScalarswitchAllFuses | read-write | current | Sets the output state of all fuses: 0=output off, 1=output on |
| 1.3.6.1.4.1.44086.4.1.10.40 | ScalarmonitorEnabled | read-only | current | If 1 is returned any automatic feed or fuse monitor is enabled. |
| 1.3.6.1.4.1.44086.4.1.20 | NodeexternalAlarms | |||
| 1.3.6.1.4.1.44086.4.1.20.1 | NodeeaFeedA | |||
| 1.3.6.1.4.1.44086.4.1.20.1.1 | TableeaATable | not-accessible | current | |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1 | RoweaAEntry | not-accessible | current | |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.1 | ColumneaIndexA | not-accessible | current | Device index (slot number) |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.2 | ColumneaAvailableA | read-only | current | Status of the device: 0=no EAI device, 1=EEAI device available |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.3 | ColumneaDeviceTypeA | read-only | current | Type number of the device |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.4 | ColumneaSerialA | read-only | current | Serial number of the device |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.5 | ColumneaHwVersionA | read-only | current | Hardware version number of the device |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.6 | ColumneaSwVersionA | read-only | current | Software version number of the device |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.7 | ColumneaOutput1A | read-write | current | Status of the relay output1: 0=output off, 1=output on (contact to normaly close is closed) |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.8 | ColumneaOutput2A | read-write | current | Status of the relay output2: 0=output off, 1=output on (contact to normaly close is closed) |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.9 | ColumneaInput1A | read-only | current | Status digital input1: 0=low, 1=high |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.10 | ColumneaInput2A | read-only | current | Status digital input2: 0=low, 1=high |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.11 | ColumneaInput3A | read-only | current | Status digital input3: 0=low, 1=high |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.12 | ColumneaInput4A | read-only | current | Status digital input4: 0=low, 1=high |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.13 | ColumneaInput5A | read-only | current | Status digital input5: 0=low, 1=high |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.14 | ColumneaInput6A | read-only | current | Status digital input6: 0=low, 1=high |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.15 | ColumneaInput7A | read-only | current | Status digital input7: 0=low, 1=high |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.16 | ColumneaInput8A | read-only | current | Status digital input8: 0=low, 1=high |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.17 | ColumneaAnalogInputA | read-only | current | Analog current input in mA |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.18 | ColumneaLabelOutput1A | read-write | current | Label for output1 of this EAI device |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.19 | ColumneaLabelOutput2A | read-write | current | Label for output2 of this EAI device |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.20 | ColumneaLabelInput1A | read-write | current | Label for input1 of this EAI device |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.21 | ColumneaLabelInput2A | read-write | current | Label for input2 of this EAI device |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.22 | ColumneaLabelInput3A | read-write | current | Label for input3 of this EAI device |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.23 | ColumneaLabelInput4A | read-write | current | Label for input4 of this EAI device |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.24 | ColumneaLabelInput5A | read-write | current | Label for input5 of this EAI device |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.25 | ColumneaLabelInput6A | read-write | current | Label for input6 of this EAI device |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.26 | ColumneaLabelInput7A | read-write | current | Label for input7 of this EAI device |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.27 | ColumneaLabelInput8A | read-write | current | Label for input8 of this EAI device |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.28 | ColumneaLabelAnalogInputA | read-write | current | Label for the analog input of this EAI device |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.29 | ColumneaSignallingGroupOutput1A | read-write | current | Signalling function for output1. Syntax: 20 (for 20 slots) characters '0' or '1'. '0'= signalling not active for this slot; '0'= signalling is active for this … |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.30 | ColumneaSignallingActiveOutput1A | read-only | current | Status of signalling function for output1: 0=not active, 1=active |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.31 | ColumneaSignallingGroupOutput2A | read-write | current | Signalling function for output2. Syntax: 20 (for 20 slots) characters '0' or '1'. '0'= signalling not active for this slot; '0'= signalling is active for this … |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.32 | ColumneaSignallingActiveOutput2A | read-only | current | Status of signalling function for output2: 0=not active, 1=active |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.33 | ColumneaLogicFunctionOutput1A | read-write | current | Logic function for output1. Length: 40 characters. Syntax: Logic connections '*'=AND, '+'=OR, '!'=Negation; Signals: EAI digital input 'eai<slot address>in<inp… |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.34 | ColumneaLogicFunctionActiveOutput1A | read-only | current | Status of logic function for output1: 0=not active, 1=active |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.35 | ColumneaLogicFunctionOutput2A | read-write | current | Logic function for output2. Length: 40 characters. Syntax: Logic connections '*'=AND, '+'=OR, '!'=Negation; Signals: EAI digital input 'eai<slot address>in<inp… |
| 1.3.6.1.4.1.44086.4.1.20.1.1.1.36 | ColumneaLogicFunctionActiveOutput2A | read-only | current | Status of logic function for output2: 0=not active, 1=active |
| 1.3.6.1.4.1.44086.4.1.20.2 | NodeeaFeedB | |||
| 1.3.6.1.4.1.44086.4.1.20.2.1 | TableeaBTable | not-accessible | current | |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1 | RoweaBEntry | not-accessible | current | |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.1 | ColumneaIndexB | not-accessible | current | Device index (slot number) |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.2 | ColumneaAvailableB | read-only | current | Status of the device: 0=no EAI device, 1=EEAI device available |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.3 | ColumneaDeviceTypeB | read-only | current | Type number of the device |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.4 | ColumneaSerialB | read-only | current | Serial number of the device |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.5 | ColumneaHwVersionB | read-only | current | Hardware version number of the device |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.6 | ColumneaSwVersionB | read-only | current | Software version number of the device |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.7 | ColumneaOutput1B | read-write | current | Status of the relay output1: 0=output off, 1=output on (contact to normaly close is closed) |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.8 | ColumneaOutput2B | read-write | current | Status of the relay output2: 0=output off, 1=output on (contact to normaly close is closed) |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.9 | ColumneaInput1B | read-only | current | Status digital input1: 0=low, 1=high |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.10 | ColumneaInput2B | read-only | current | Status digital input2: 0=low, 1=high |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.11 | ColumneaInput3B | read-only | current | Status digital input3: 0=low, 1=high |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.12 | ColumneaInput4B | read-only | current | Status digital input4: 0=low, 1=high |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.13 | ColumneaInput5B | read-only | current | Status digital input5: 0=low, 1=high |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.14 | ColumneaInput6B | read-only | current | Status digital input6: 0=low, 1=high |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.15 | ColumneaInput7B | read-only | current | Status digital input7: 0=low, 1=high |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.16 | ColumneaInput8B | read-only | current | Status digital input8: 0=low, 1=high |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.17 | ColumneaAnalogInputB | read-only | current | Analog current input in mA |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.18 | ColumneaLabelOutput1B | read-write | current | Label for output1 of this EAI device |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.19 | ColumneaLabelOutput2B | read-write | current | Label for output2 of this EAI device |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.20 | ColumneaLabelInput1B | read-write | current | Label for input1 of this EAI device |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.21 | ColumneaLabelInput2B | read-write | current | Label for input2 of this EAI device |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.22 | ColumneaLabelInput3B | read-write | current | Label for input3 of this EAI device |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.23 | ColumneaLabelInput4B | read-write | current | Label for input4 of this EAI device |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.24 | ColumneaLabelInput5B | read-write | current | Label for input5 of this EAI device |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.25 | ColumneaLabelInput6B | read-write | current | Label for input6 of this EAI device |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.26 | ColumneaLabelInput7B | read-write | current | Label for input7 of this EAI device |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.27 | ColumneaLabelInput8B | read-write | current | Label for input8 of this EAI device |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.28 | ColumneaLabelAnalogInputB | read-write | current | Label for the analog input of this EAI device |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.29 | ColumneaSignallingGroupOutput1B | read-write | current | Signalling function for output1. Syntax: 20 (for 20 slots) characters '0' or '1'. '0'= signalling not active for this slot; '0'= signalling is active for this … |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.30 | ColumneaSignallingActiveOutput1B | read-only | current | Status of signalling function for output1: 0=not active, 1=active |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.31 | ColumneaSignallingGroupOutput2B | read-write | current | Signalling function for output2. Syntax: 20 (for 20 slots) characters '0' or '1'. '0'= signalling not active for this slot; '0'= signalling is active for this … |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.32 | ColumneaSignallingActiveOutput2B | read-only | current | Status of signalling function for output2: 0=not active, 1=active |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.33 | ColumneaLogicFunctionOutput1B | read-write | current | Logic function for output1. Length: 40 characters. Syntax: Logic connections '*'=AND, '+'=OR, '!'=Negation; Signals: EAI digital input 'eai<slot address>in<inp… |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.34 | ColumneaLogicFunctionActiveOutput1B | read-only | current | Status of logic function for output1: 0=not active, 1=active |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.35 | ColumneaLogicFunctionOutput2B | read-write | current | Logic function for output2. Length: 40 characters. Syntax: Logic connections '*'=AND, '+'=OR, '!'=Negation; Signals: EAI digital input 'eai<slot address>in<inp… |
| 1.3.6.1.4.1.44086.4.1.20.2.1.1.36 | ColumneaLogicFunctionActiveOutput2B | read-only | current | Status of logic function for output2: 0=not active, 1=active |
| 1.3.6.1.4.1.44086.4.1.100 | Nodenotifications | |||
| 1.3.6.1.4.1.44086.4.1.100.1 | Nodeprefix | |||
| 1.3.6.1.4.1.44086.4.1.100.1.1 | NodesystemNotifications | |||
| 1.3.6.1.4.1.44086.4.1.100.1.1.1 | NotificationpowerUp | current | This notification is sent after a successful power up | |
| 1.3.6.1.4.1.44086.4.1.100.1.1.2 | NotificationsystemFailure | current | If the system enters failure mode this Trap is sent | |
| 1.3.6.1.4.1.44086.4.1.100.1.10 | NodefusesNotifications | |||
| 1.3.6.1.4.1.44086.4.1.100.1.10.1 | NotificationfuseNew | current | This Trap is sent if a new fuse was found | |
| 1.3.6.1.4.1.44086.4.1.100.1.10.2 | NotificationfuseGone | current | Informs that a fuse which responds onto requests in the past does no longer respond. | |
| 1.3.6.1.4.1.44086.4.1.100.1.10.3 | NotificationfuseWrong | current | A recently added fuse has a different nominal current as the fuse in the same slot had before. | |
| 1.3.6.1.4.1.44086.4.1.100.1.10.4 | NotificationfuseOutputStateChanged | current | Informs that the output state of a fuse had changed his status. | |
| 1.3.6.1.4.1.44086.4.1.100.1.10.5 | NotificationfuseFailure | current | If any status or error flag changes, this trap is sent. | |
| 1.3.6.1.4.1.44086.4.1.100.1.20 | NodeexternalAlarmNotifications | |||
| 1.3.6.1.4.1.44086.4.1.100.1.20.1 | NotificationeaNew | current | This Trap is sent if a new external alarm device was found | |
| 1.3.6.1.4.1.44086.4.1.100.1.20.2 | NotificationeaGone | current | Informs that a external alarm device, which responded onto requests in the past, does no longer respond. | |
| 1.3.6.1.4.1.44086.4.1.100.1.20.3 | NotificationeaActiveFunctionWarning | current | Informs that a logic- or signalling function is configured for a new plugged or pulled external alarm device. | |
| 1.3.6.1.4.1.44086.4.1.100.1.20.4 | NotificationeaInternalError | current | Informs that a internal error of external alarm device occured | |
| 1.3.6.1.4.1.44086.4.1.100.1.20.5 | NotificationeaMasterWasNotAvailable | current | Informs (one time) that a external alarm device detected, that the master device was not available for some time. | |
| 1.3.6.1.4.1.44086.4.1.100.1.20.6 | NotificationeaInputChanged | current | Informs that a external alarm device input has changed its state; Summary for all inputs of one external alarm device. | |
| 1.3.6.1.4.1.44086.4.1.100.1.20.7 | NotificationeaOutputChanged | current | Informs that a external alarm device output has changed its state; Summary for all outputs of one external alarm device. | |
| 1.3.6.1.4.1.44086.4.1.100.1.20.8 | NotificationeaSingleInputChanged | current | Informs that a external alarm device input has changed its state; Is sent for every changed input. If input changed high: 'raise'; If input changed low: 'clear' | |
| 1.3.6.1.4.1.44086.4.1.100.1.20.9 | NotificationeaSingleOutputChanged | current | Informs that a external alarm device output has changed its state; Is sent for every changed output. If output changed high: 'raise'; If output changed low: 'c… | |
| 1.3.6.1.4.1.44086.4.1.100.2 | Nodeobjects | |||
| 1.3.6.1.4.1.44086.4.1.100.2.1 | NodesystemObjects | |||
| 1.3.6.1.4.1.44086.4.1.100.2.1.1 | ScalarresetReason | accessible-for-notify | current | Holds a human readable text which gives the reason for reset. Possible values are coldstart, warmstart or watchdog |
| 1.3.6.1.4.1.44086.4.1.100.2.1.2 | ScalarfailureReason | accessible-for-notify | current | Holds a human readable text which gives the reason for system failure. |
| 1.3.6.1.4.1.44086.4.1.100.2.10 | NodefusesObjects | |||
| 1.3.6.1.4.1.44086.4.1.100.2.10.1 | ScalarfuseNr | accessible-for-notify | current | Gives the number of a fuse |
| 1.3.6.1.4.1.44086.4.1.100.2.10.2 | ScalarfuseLabel | accessible-for-notify | current | Gives the label of a fuse |
| 1.3.6.1.4.1.44086.4.1.100.2.10.5 | ScalarfuseOutputState | accessible-for-notify | current | Defines the output state of a fuse. 0 = Output off, 1 = Output on |
| 1.3.6.1.4.1.44086.4.1.100.2.10.10 | ScalarfuseErrorRegister | accessible-for-notify | current | Defines the error register data type. |
| 1.3.6.1.4.1.44086.4.1.100.2.10.20 | ScalarfuseStatusShortCircuit | accessible-for-notify | current | Status register flag for short circuit |
| 1.3.6.1.4.1.44086.4.1.100.2.10.21 | ScalarfuseStatusOverload | accessible-for-notify | current | Status register flag for overload |
| 1.3.6.1.4.1.44086.4.1.100.2.10.22 | ScalarfuseStatusUndervoltage | accessible-for-notify | current | Status register flag for undervoltage |
| 1.3.6.1.4.1.44086.4.1.100.2.10.23 | ScalarfuseStatusOvervoltage | accessible-for-notify | current | Status register flag for overvoltage |
| 1.3.6.1.4.1.44086.4.1.100.2.10.24 | ScalarfuseStatusOvertemperature | accessible-for-notify | current | Status register flag for overtemperature |
| 1.3.6.1.4.1.44086.4.1.100.2.10.25 | ScalarfuseStatusNoPowerSupply | accessible-for-notify | current | Status register flag for no power supply |
| 1.3.6.1.4.1.44086.4.1.100.2.10.30 | ScalarfuseOldNominalCurrent | accessible-for-notify | current | The nominal current of the fuse which was located in this slot before. |
| 1.3.6.1.4.1.44086.4.1.100.2.10.31 | ScalarfuseNewNominalCurrent | accessible-for-notify | current | The nominal current of the new fuse |
| 1.3.6.1.4.1.44086.4.1.100.2.20 | NodeexternalAlarmObjects | |||
| 1.3.6.1.4.1.44086.4.1.100.2.20.1 | ScalareaSlotNr | accessible-for-notify | current | Gives the slot number of a external alarm device |
| 1.3.6.1.4.1.44086.4.1.100.2.20.2 | ScalareaInputStates | accessible-for-notify | current | Gives the input states of the external alarm device. [Left -> right: output 1 .. output n] |
| 1.3.6.1.4.1.44086.4.1.100.2.20.3 | ScalareaOutputStates | accessible-for-notify | current | Gives the output states of the external alarm device. [Left -> right: output 1 .. output n] |
| 1.3.6.1.4.1.44086.4.1.100.2.20.4 | ScalareaFailureMsg | accessible-for-notify | current | Gives a human readable text for a external alarm device failure. |
| 1.3.6.1.4.1.44086.4.1.100.2.20.5 | ScalareaMsg | accessible-for-notify | current | Gives a human readable text for a external alarm device notification. |
| 1.3.6.1.4.1.44086.4.1.100.2.20.6 | ScalareaInputNr | accessible-for-notify | current | Gives the input Nr. of a external alarm device input. [1-8] |
| 1.3.6.1.4.1.44086.4.1.100.2.20.7 | ScalareaInputLabel | accessible-for-notify | current | Gives the label of a external alarm device input. |
| 1.3.6.1.4.1.44086.4.1.100.2.20.8 | ScalareaInputState | accessible-for-notify | current | Gives the state of an external alarm device input. [raise/clear] |
| 1.3.6.1.4.1.44086.4.1.100.2.20.9 | ScalareaOutputNr | accessible-for-notify | current | Gives the output Nr. of a external alarm device output. [1-2] |
| 1.3.6.1.4.1.44086.4.1.100.2.20.10 | ScalareaOutputLabel | accessible-for-notify | current | Gives the label of a external alarm device output. |
| 1.3.6.1.4.1.44086.4.1.100.2.20.11 | ScalareaOutputState | accessible-for-notify | current | Gives the state of an external alarm device output. [raise/clear] |