MIB Viewer

EatonSTS-MIB

101 objects
No module-level DESCRIPTION found.
Imported Objects
RFC-1212OBJECT-TYPE
RFC-1215TRAP-TYPE
RFC1155-SMIenterprises
RFC1213-MIBDisplayString
OIDNameAccessStatusDescription
1.3.6.1.4.1.534Nodeeaton
1.3.6.1.4.1.534.10Nodests
1.3.6.1.4.1.534.10.1Nodeats
1.3.6.1.4.1.534.10.1.1NodeatsAgent
1.3.6.1.4.1.534.10.1.1.1ScalaratsAgentManufacturerread-onlymandatoryThe manufacturer name of SNMP-Agent.
1.3.6.1.4.1.534.10.1.1.2ScalaratsAgentVersionread-onlymandatoryThe firmware version of SNMP-Agent.
1.3.6.1.4.1.534.10.1.1.3NodeatsAgentModbus
1.3.6.1.4.1.534.10.1.1.3.1ScalaratsAgentModbusLinkread-onlymandatoryThe link status of ModBUS communication to ATS device.
1.3.6.1.4.1.534.10.1.2NodeatsIdent
1.3.6.1.4.1.534.10.1.2.1ScalaratsIdentModelread-onlymandatoryDevice model name.
1.3.6.1.4.1.534.10.1.2.2ScalaratsIdentFWVersionread-onlymandatoryDevice F/W version.
1.3.6.1.4.1.534.10.1.2.3ScalaratsIdentReleaseread-onlymandatoryThe released date.
1.3.6.1.4.1.534.10.1.2.4ScalaratsIdentSerialNumberread-onlymandatoryDevice serial number
1.3.6.1.4.1.534.10.1.2.5ScalaratsIdentIDCodesread-writemandatoryDevice ID codes
1.3.6.1.4.1.534.10.1.3NodeatsMeasure
1.3.6.1.4.1.534.10.1.3.1TableatsInputTablenot-accessiblemandatoryThe table of input information.
1.3.6.1.4.1.534.10.1.3.1.1RowatsInputEntrynot-accessiblemandatoryThe input information of each source input: <node>.1 source-1 <node>.2 source-2
1.3.6.1.4.1.534.10.1.3.1.1.1ColumnatsInputIndexread-onlymandatoryIndex to input.
1.3.6.1.4.1.534.10.1.3.1.1.2ColumnatsInputVoltageread-onlymandatoryThe input voltage in front of relay.
1.3.6.1.4.1.534.10.1.3.1.1.3ColumnatsInputFrequencyread-onlymandatoryThe input frequency.
1.3.6.1.4.1.534.10.1.3.2NodeatsOutput
1.3.6.1.4.1.534.10.1.3.2.1ScalaratsOutputVoltageread-onlymandatoryThe output voltage.
1.3.6.1.4.1.534.10.1.3.2.2ScalaratsOutputCurrentread-onlymandatoryThe output current.
1.3.6.1.4.1.534.10.1.3.3ScalaratsMeasureTemperatureCread-onlymandatoryThe internal temperature (in Celsius).
1.3.6.1.4.1.534.10.1.3.4ScalaratsMeasureTemperatureFread-onlymandatoryThe internal temperature (in Fahrenheit).
1.3.6.1.4.1.534.10.1.3.5ScalaratsMessureRunTimeread-onlymandatoryThe ATS run time.
1.3.6.1.4.1.534.10.1.3.6ScalaratsMessureTransferedTimesread-onlymandatoryThe transfered times.
1.3.6.1.4.1.534.10.1.3.7ScalaratsMessureOperationModeread-onlymandatoryThe operation mode.
1.3.6.1.4.1.534.10.1.4NodeatsStatus
1.3.6.1.4.1.534.10.1.4.1ScalaratsInputFlowIndicatorread-onlymandatory
1.3.6.1.4.1.534.10.1.4.2TableatsInputFlowTablenot-accessiblemandatoryThe table of input flow status.
1.3.6.1.4.1.534.10.1.4.2.1RowatsInputFlowEntrynot-accessiblemandatoryThe input flow status: <node>.1 source-1 <node>.2 source-2
1.3.6.1.4.1.534.10.1.4.2.1.1ColumnatsInputFlowIndexread-onlymandatoryIndex of input entry.
1.3.6.1.4.1.534.10.1.4.2.1.2ColumnatsInputFlowRelayread-onlymandatoryThe status of input relay.
1.3.6.1.4.1.534.10.1.4.2.1.3ColumnatsInputFlowSCRread-onlymandatoryThe status of input SCR.
1.3.6.1.4.1.534.10.1.4.2.1.4ColumnatsInputFlowParallelRelayread-onlymandatoryThe status of input parallel relay.
1.3.6.1.4.1.534.10.1.4.3ScalaratsInputFailureIndicatorread-onlymandatory
1.3.6.1.4.1.534.10.1.4.4TableatsInputFailureTablenot-accessiblemandatoryThe table of input status.
1.3.6.1.4.1.534.10.1.4.4.1RowatsInputFailureEntrynot-accessiblemandatoryThe status of input failure: <node>.1 source-1 <node>.2 source-2
1.3.6.1.4.1.534.10.1.4.4.1.1ColumnatsInputFailureIndexread-onlymandatoryIndex of entry.
1.3.6.1.4.1.534.10.1.4.4.1.2ColumnatsInputFailureRelayOpenread-onlymandatoryThe status of input relay is OPEN.
1.3.6.1.4.1.534.10.1.4.4.1.3ColumnatsInputFailureRelayShortread-onlymandatoryThe status of input relay is SHORT.
1.3.6.1.4.1.534.10.1.4.4.1.4ColumnatsInputFailureSCROpenread-onlymandatoryThe status of input SCR is OPEN.
1.3.6.1.4.1.534.10.1.4.4.1.5ColumnatsInputFailureSCRShortread-onlymandatoryThe status of input SCR is SHORT.
1.3.6.1.4.1.534.10.1.4.4.1.6ColumnatsInputFailureSCRThermalread-onlymandatoryThe status of input SCR thermal is over.
1.3.6.1.4.1.534.10.1.4.4.1.7ColumnatsInputFailureAuxPowerread-onlymandatoryInternal axuiliary power is reported as failure.
1.3.6.1.4.1.534.10.1.4.4.1.8ColumnatsInputFailureDropread-onlymandatoryA voltage drop was detected.
1.3.6.1.4.1.534.10.1.4.4.1.9ColumnatsInputFailureBrownoutread-onlymandatoryA voltage brownout was detected.
1.3.6.1.4.1.534.10.1.4.4.1.10ColumnatsInputFailureFrequencyread-onlymandatoryThe input frequency is out of range.
1.3.6.1.4.1.534.10.1.4.4.1.11ColumnatsInputFailureNotOperableread-onlymandatoryThe input is not operable.
1.3.6.1.4.1.534.10.1.4.5ScalaratsFailureIndicatorread-onlymandatory
1.3.6.1.4.1.534.10.1.4.6NodeatsFailure
1.3.6.1.4.1.534.10.1.4.6.1ScalaratsFailureSwitchFaultread-onlymandatoryThe relay, SCR and thermal switch fail.
1.3.6.1.4.1.534.10.1.4.6.2ScalaratsFailureNoOutputread-onlymandatoryThere is no output.
1.3.6.1.4.1.534.10.1.4.6.3ScalaratsFailureOutputOCread-onlymandatoryThe output current is over.
1.3.6.1.4.1.534.10.1.4.6.4ScalaratsFailureOverTemperatureread-onlymandatoryThe ambient temperature is over.
1.3.6.1.4.1.534.10.1.5NodeatsLog
1.3.6.1.4.1.534.10.1.5.1ScalaratsLogNumread-onlymandatoryThe number of event logs.
1.3.6.1.4.1.534.10.1.5.2TableatsLogTablenot-accessiblemandatoryThe table of event logs.
1.3.6.1.4.1.534.10.1.5.2.1RowatsLogEntrynot-accessiblemandatoryThe recorded event log
1.3.6.1.4.1.534.10.1.5.2.1.1ColumnatsLogIndexread-onlymandatoryIndex to event log.
1.3.6.1.4.1.534.10.1.5.2.1.2ColumnatsLogTimeread-onlymandatoryThe event time (since 01/01/2000 00:00:00).
1.3.6.1.4.1.534.10.1.5.2.1.3ColumnatsLogCoderead-onlymandatoryThe event code.
1.3.6.1.4.1.534.10.1.5.2.1.4ColumnatsLogTimeTextread-onlymandatoryThe event time with form: hh:mm:ss MM/DD/YYYY.
1.3.6.1.4.1.534.10.1.6NodeatsConfig
1.3.6.1.4.1.534.10.1.6.1NodeatsConfigTime
1.3.6.1.4.1.534.10.1.6.1.1ScalaratsConfigTimeRTCread-writemandatoryThe RTC timer value (since 1/1/2000 00:00:00).
1.3.6.1.4.1.534.10.1.6.1.2ScalaratsConfigTimeTextDateread-writemandatoryThe present date in MM/DD/YYYY text format.
1.3.6.1.4.1.534.10.1.6.1.3ScalaratsConfigTimeTextTimeread-writemandatoryThe present time in hh:mm:ss text format.
1.3.6.1.4.1.534.10.1.6.2TableatsConfigInputTablenot-accessiblemandatoryThe table of input configuration.
1.3.6.1.4.1.534.10.1.6.2.1RowatsConfigInputEntrynot-accessiblemandatoryInput configuration entry
1.3.6.1.4.1.534.10.1.6.2.1.1ColumnatsConfigInputIndexread-writemandatoryIndex to input configuration.
1.3.6.1.4.1.534.10.1.6.2.1.2ColumnatsConfigInputTripread-writemandatorySetting of input trip voltage.
1.3.6.1.4.1.534.10.1.6.2.1.3ColumnatsConfigInputBrownoutLowread-writemandatorySetting of input brownout low voltage.
1.3.6.1.4.1.534.10.1.6.2.1.4ColumnatsConfigInputBrownoutHighread-writemandatorySetting of input brownout high voltage.
1.3.6.1.4.1.534.10.1.6.2.1.5ColumnatsConfigInputRecoverread-writemandatorySetting of input recovered time.
1.3.6.1.4.1.534.10.1.6.2.1.6ColumnatsConfigInputMaxVoltageread-writemandatorySet the detected delta RMS voltage of fast detected AC blackout by the comparing cycles.
1.3.6.1.4.1.534.10.1.6.2.1.7ColumnatsConfigInputMaxTimeread-writemandatorySet the detected time of fast detected AC blackout by the comparing cycles.
1.3.6.1.4.1.534.10.1.6.2.1.8ColumnatsConfigInputDelayTimeread-onlymandatoryThe delay time includes Recovered Time (atsConfigInputRecover) and Random Delay Time.
1.3.6.1.4.1.534.10.1.6.3ScalaratsConfigInputVoltageRatingread-onlymandatoryThe input voltage rating.
1.3.6.1.4.1.534.10.1.6.4ScalaratsConfigRandomTimeread-onlymandatoryDelay time is calculated by device serial numbers.
1.3.6.1.4.1.534.10.1.6.5ScalaratsConfigPreferredread-writemandatoryThe prefered source.
1.3.6.1.4.1.534.10.1.6.6ScalaratsConfigSensitivityread-writemandatoryThe AC Blackout Sensitivity.
1.3.6.1.4.1.534.10.1.6.7ScalaratsConfigTestread-writemandatoryThe activity of source test.
1.3.6.1.4.1.534.10.1.7NodeatsUpgrade
1.3.6.1.4.1.534.10.1.7.1ScalaratsUpgradeProcessread-onlymandatoryThe status of upgrade progress.
1.3.6.1.4.1.534.10.1.7.2ScalaratsUpgradeStepread-onlymandatoryThe step of ATS F/W upgrade.
1.3.6.1.4.1.534.10.1.7.3ScalaratsUpgradePercentageread-onlymandatoryThe percentage of current progress (program or read).
1.3.6.1.4.1.534.10.1.20NodeatsTraps
1.3.6.1.4.1.534.10.1.20.1NodeatsTrapCommLostCommunication with the ATS failed.
1.3.6.1.4.1.534.10.1.20.2NodeatsTrapCommEstablishedCommunication with the ATS reestablished.
1.3.6.1.4.1.534.10.1.20.3NodeatsTrapConfigChangeThe ATS configuration has been changed.
1.3.6.1.4.1.534.10.1.20.4NodeatsTrapFlowChangeThe Input flow status has been changed.
1.3.6.1.4.1.534.10.1.20.5NodeatsTrapInput1AlarmAlarm of source-1 failure(s).
1.3.6.1.4.1.534.10.1.20.6NodeatsTrapInput1AlarmRecoverRecover from source-1 failure(s).
1.3.6.1.4.1.534.10.1.20.7NodeatsTrapInput2AlarmAlarm of source-2 failure(s).
1.3.6.1.4.1.534.10.1.20.8NodeatsTrapInput2AlarmRecoverRecover from source-2 failure(s).
1.3.6.1.4.1.534.10.1.20.9NodeatsTrapAlarmAlarm of failure(s).
1.3.6.1.4.1.534.10.1.20.10NodeatsTrapAlarmRecoverRecover from failure(s).
1.3.6.1.4.1.534.10.1.20.11NodeatsTrapUpgradeBeginStart to upgrade ATS firmware.
1.3.6.1.4.1.534.10.1.20.12NodeatsTrapUpgradeEndEnd of upgrade progress.