GEIST-IMD-MIB
268 objects
The MIB for Geist Products
Imported Objects
| SNMPv2-SMI | enterprises Gauge32 Integer32 IpAddress MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE |
| SNMPv2-TC | DisplayString |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.21239 | Identitygeist | The MIB for Geist Products | ||
| 1.3.6.1.4.1.21239.5 | Nodeblackbird | |||
| 1.3.6.1.4.1.21239.5.2 | Nodeimd | |||
| 1.3.6.1.4.1.21239.5.2.1 | NodedeviceInfo | |||
| 1.3.6.1.4.1.21239.5.2.1.1 | ScalarproductTitle | read-only | current | Product name |
| 1.3.6.1.4.1.21239.5.2.1.2 | ScalarproductVersion | read-only | current | Product version |
| 1.3.6.1.4.1.21239.5.2.1.3 | ScalarproductFriendlyName | read-only | current | User-assigned name |
| 1.3.6.1.4.1.21239.5.2.1.4 | ScalarproductMacAddress | read-only | current | Product's unique MAC address |
| 1.3.6.1.4.1.21239.5.2.1.5 | ScalarproductUrl | read-only | current | Product's main URL access point |
| 1.3.6.1.4.1.21239.5.2.1.6 | ScalardeviceCount | read-only | current | Total number of devices on unit |
| 1.3.6.1.4.1.21239.5.2.1.7 | ScalartemperatureUnits | read-write | current | Current units for temperature values. 0 = Degrees Fahrenheit, 1 = Degrees Celsius |
| 1.3.6.1.4.1.21239.5.2.3 | Nodepdu | |||
| 1.3.6.1.4.1.21239.5.2.3.1 | TablepduMainTable | not-accessible | current | PDU general information |
| 1.3.6.1.4.1.21239.5.2.3.1.1 | RowpduMainEntry | not-accessible | current | Entry in the pduMainTable table: each entry contains an index and other sensor details |
| 1.3.6.1.4.1.21239.5.2.3.1.1.1 | ColumnpduMainIndex | read-only | current | Table entry index value |
| 1.3.6.1.4.1.21239.5.2.3.1.1.2 | ColumnpduMainSerial | read-only | current | Serial Number |
| 1.3.6.1.4.1.21239.5.2.3.1.1.3 | ColumnpduMainName | read-only | current | Name |
| 1.3.6.1.4.1.21239.5.2.3.1.1.4 | ColumnpduMainLabel | read-only | current | Label |
| 1.3.6.1.4.1.21239.5.2.3.1.1.5 | ColumnpduMainAvail | read-only | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable |
| 1.3.6.1.4.1.21239.5.2.3.1.1.6 | ColumnpduMeterType | read-only | current | Current meter type. 0 = Wye, 1 = Delta |
| 1.3.6.1.4.1.21239.5.2.3.1.1.7 | ColumnpduTotalName | read-only | current | Total Name |
| 1.3.6.1.4.1.21239.5.2.3.1.1.8 | ColumnpduTotalLabel | read-only | current | Total Label |
| 1.3.6.1.4.1.21239.5.2.3.1.1.9 | ColumnpduTotalRealPower | read-only | current | PDU Total Real Power |
| 1.3.6.1.4.1.21239.5.2.3.1.1.10 | ColumnpduTotalApparentPower | read-only | current | PDU Total Apparent Power |
| 1.3.6.1.4.1.21239.5.2.3.1.1.11 | ColumnpduTotalPowerFactor | read-only | current | PDU Total Power Factor |
| 1.3.6.1.4.1.21239.5.2.3.1.1.12 | ColumnpduTotalEnergy | read-only | current | PDU Total Accumulated Energy |
| 1.3.6.1.4.1.21239.5.2.3.2 | TablepduPhaseTable | not-accessible | current | PDU phases information |
| 1.3.6.1.4.1.21239.5.2.3.2.1 | RowpduPhaseEntry | not-accessible | current | Entry in the pduPhaseTable table: each entry contains an index and other sensor details |
| 1.3.6.1.4.1.21239.5.2.3.2.1.1 | ColumnpduPhaseIndex | read-only | current | Table entry index value |
| 1.3.6.1.4.1.21239.5.2.3.2.1.2 | ColumnpduPhaseName | read-only | current | PDU Phase Name |
| 1.3.6.1.4.1.21239.5.2.3.2.1.3 | ColumnpduPhaseLabel | read-only | current | PDU Phase Label |
| 1.3.6.1.4.1.21239.5.2.3.2.1.4 | ColumnpduPhaseVoltage | read-only | current | PDU Phase Voltage in tenths of a volt |
| 1.3.6.1.4.1.21239.5.2.3.2.1.5 | ColumnpduPhaseVoltageMax | read-only | current | PDU Phase Voltage (Max) in tenths of a volt |
| 1.3.6.1.4.1.21239.5.2.3.2.1.6 | ColumnpduPhaseVoltageMin | read-only | current | PDU Phase Voltage (Min) in tenths of a volt |
| 1.3.6.1.4.1.21239.5.2.3.2.1.7 | ColumnpduPhaseVoltagePeak | read-only | current | PDU Phase Voltage (Peak) in tenths of a volt |
| 1.3.6.1.4.1.21239.5.2.3.2.1.8 | ColumnpduPhaseCurrent | read-only | current | PDU Phase Current reading in hundreths of an amp |
| 1.3.6.1.4.1.21239.5.2.3.2.1.9 | ColumnpduPhaseCurrentMax | read-only | current | PDU Phase Current (Max) reading in hundreths of an amp |
| 1.3.6.1.4.1.21239.5.2.3.2.1.10 | ColumnpduPhaseCurrentMin | read-only | current | PDU Phase Current (Min) reading in hundreths of an amp |
| 1.3.6.1.4.1.21239.5.2.3.2.1.11 | ColumnpduPhaseCurrentPeak | read-only | current | PDU Phase Current (Peak) reading in hundreths of an amp |
| 1.3.6.1.4.1.21239.5.2.3.2.1.12 | ColumnpduPhaseRealPower | read-only | current | PDU Phase Real Power |
| 1.3.6.1.4.1.21239.5.2.3.2.1.13 | ColumnpduPhaseApparentPower | read-only | current | PDU Phase Apparent Power |
| 1.3.6.1.4.1.21239.5.2.3.2.1.14 | ColumnpduPhasePowerFactor | read-only | current | PDU Phase Power Factor |
| 1.3.6.1.4.1.21239.5.2.3.2.1.15 | ColumnpduPhaseEnergy | read-only | current | PDU Phase Accumulated Energy |
| 1.3.6.1.4.1.21239.5.2.3.3 | TablepduBreakerTable | not-accessible | current | PDU information |
| 1.3.6.1.4.1.21239.5.2.3.3.1 | RowpduBreakerEntry | not-accessible | current | Entry in the pduBreakerTable table: each entry contains an index and other sensor details |
| 1.3.6.1.4.1.21239.5.2.3.3.1.1 | ColumnpduBreakerIndex | read-only | current | Table entry index value |
| 1.3.6.1.4.1.21239.5.2.3.3.1.2 | ColumnpduBreakerName | read-only | current | PDU Breaker Name |
| 1.3.6.1.4.1.21239.5.2.3.3.1.3 | ColumnpduBreakerLabel | read-only | current | PDU Breaker Label |
| 1.3.6.1.4.1.21239.5.2.3.3.1.4 | ColumnpduBreakerCurrent | read-only | current | PDU Breaker Current reading in hundreths of an amp |
| 1.3.6.1.4.1.21239.5.2.3.3.1.5 | ColumnpduBreakerCurrentMax | read-only | current | PDU Breaker Current (Max) reading in hundreths of an amp |
| 1.3.6.1.4.1.21239.5.2.3.3.1.6 | ColumnpduBreakerCurrentMin | read-only | current | PDU Breaker Current (Min) reading in hundreths of an amp |
| 1.3.6.1.4.1.21239.5.2.3.3.1.7 | ColumnpduBreakerCurrentPeak | read-only | current | PDU Breaker Current (Peak) reading in hundreths of an amp |
| 1.3.6.1.4.1.21239.5.2.3.4 | TablepduLineTable | not-accessible | current | PDU line current information |
| 1.3.6.1.4.1.21239.5.2.3.4.1 | RowpduLineEntry | not-accessible | current | Entry in the pduLineTable table: each entry contains an index and other sensor details |
| 1.3.6.1.4.1.21239.5.2.3.4.1.1 | ColumnpduLineIndex | read-only | current | Table entry index value |
| 1.3.6.1.4.1.21239.5.2.3.4.1.2 | ColumnpduLineName | read-only | current | PDU Line Name |
| 1.3.6.1.4.1.21239.5.2.3.4.1.3 | ColumnpduLineLabel | read-only | current | PDU Line Label |
| 1.3.6.1.4.1.21239.5.2.3.4.1.4 | ColumnpduLineCurrent | read-only | current | PDU Line Current reading in hundreths of an amp |
| 1.3.6.1.4.1.21239.5.2.3.4.1.5 | ColumnpduLineCurrentMax | read-only | current | PDU Line Current (Max) reading in hundreths of an amp |
| 1.3.6.1.4.1.21239.5.2.3.4.1.6 | ColumnpduLineCurrentMin | read-only | current | PDU Line Current (Min) reading in hundreths of an amp |
| 1.3.6.1.4.1.21239.5.2.3.4.1.7 | ColumnpduLineCurrentPeak | read-only | current | PDU Line Current (Peak) reading in hundreths of an amp |
| 1.3.6.1.4.1.21239.5.2.4 | TabletempSensorTable | not-accessible | current | Remote Temperature Sensor |
| 1.3.6.1.4.1.21239.5.2.4.1 | RowtempSensorEntry | not-accessible | current | Entry in the tempSensorTable table: each entry contains an index and other sensor details |
| 1.3.6.1.4.1.21239.5.2.4.1.1 | ColumntempSensorIndex | read-only | current | Table entry index value |
| 1.3.6.1.4.1.21239.5.2.4.1.2 | ColumntempSensorSerial | read-only | current | Serial Number |
| 1.3.6.1.4.1.21239.5.2.4.1.3 | ColumntempSensorName | read-only | current | Friendly Name |
| 1.3.6.1.4.1.21239.5.2.4.1.4 | ColumntempSensorAvail | read-only | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable |
| 1.3.6.1.4.1.21239.5.2.4.1.5 | ColumntempSensorTemp | read-only | current | Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo |
| 1.3.6.1.4.1.21239.5.2.5 | TableairFlowSensorTable | not-accessible | current | Remote Airflow, Humidity, Temperature and Dewpoint Sensor |
| 1.3.6.1.4.1.21239.5.2.5.1 | RowairFlowSensorEntry | not-accessible | current | Entry in the airFlowSensorTable table: each entry contains an index and other sensor details |
| 1.3.6.1.4.1.21239.5.2.5.1.1 | ColumnairFlowSensorIndex | read-only | current | Table entry index value |
| 1.3.6.1.4.1.21239.5.2.5.1.2 | ColumnairFlowSensorSerial | read-only | current | Serial Number |
| 1.3.6.1.4.1.21239.5.2.5.1.3 | ColumnairFlowSensorName | read-only | current | Friendly Name |
| 1.3.6.1.4.1.21239.5.2.5.1.4 | ColumnairFlowSensorAvail | read-only | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable |
| 1.3.6.1.4.1.21239.5.2.5.1.5 | ColumnairFlowSensorTemp | read-only | current | Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo |
| 1.3.6.1.4.1.21239.5.2.5.1.6 | ColumnairFlowSensorFlow | read-only | current | AFHT3 Airflow reading |
| 1.3.6.1.4.1.21239.5.2.5.1.7 | ColumnairFlowSensorHumidity | read-only | current | AFHT3 Humidity reading |
| 1.3.6.1.4.1.21239.5.2.5.1.8 | ColumnairFlowSensorDewPoint | read-only | current | Current reading for Dew Point in tenths of degrees. Units are given by temperatureUnits field in deviceInfo |
| 1.3.6.1.4.1.21239.5.2.6 | TabledewPointSensorTable | not-accessible | current | Remote Dew Point sensor |
| 1.3.6.1.4.1.21239.5.2.6.1 | RowdewPointSensorEntry | not-accessible | current | Entry in the dewPointSensorTable table: each entry contains an index and other sensor details |
| 1.3.6.1.4.1.21239.5.2.6.1.1 | ColumndewPointSensorIndex | read-only | current | Table entry index value |
| 1.3.6.1.4.1.21239.5.2.6.1.2 | ColumndewPointSensorSerial | read-only | current | Serial Number |
| 1.3.6.1.4.1.21239.5.2.6.1.3 | ColumndewPointSensorName | read-only | current | Friendly Name |
| 1.3.6.1.4.1.21239.5.2.6.1.4 | ColumndewPointSensorAvail | read-only | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable |
| 1.3.6.1.4.1.21239.5.2.6.1.5 | ColumndewPointSensorTemp | read-only | current | Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo |
| 1.3.6.1.4.1.21239.5.2.6.1.6 | ColumndewPointSensorHumidity | read-only | current | Humidity reading |
| 1.3.6.1.4.1.21239.5.2.6.1.7 | ColumndewPointSensorDewPoint | read-only | current | Current reading for Dew-point in tenths of degrees. Units are given by temperatureUnits field in deviceInfo |
| 1.3.6.1.4.1.21239.5.2.7 | TableccatSensorTable | not-accessible | current | Remote CCAT sensor |
| 1.3.6.1.4.1.21239.5.2.7.1 | RowccatSensorEntry | not-accessible | current | Entry in the ccatSensorTable table: each entry contains an index and other sensor details |
| 1.3.6.1.4.1.21239.5.2.7.1.1 | ColumnccatSensorIndex | read-only | current | Table entry index value |
| 1.3.6.1.4.1.21239.5.2.7.1.2 | ColumnccatSensorSerial | read-only | current | Serial Number |
| 1.3.6.1.4.1.21239.5.2.7.1.3 | ColumnccatSensorName | read-only | current | Friendly Name |
| 1.3.6.1.4.1.21239.5.2.7.1.4 | ColumnccatSensorAvail | read-only | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable |
| 1.3.6.1.4.1.21239.5.2.7.1.5 | ColumnccatSensorValue | read-only | current | CCAT sensor reading |
| 1.3.6.1.4.1.21239.5.2.7.1.6 | ColumnccatSensorType | read-only | current | CCAT sensor type |
| 1.3.6.1.4.1.21239.5.2.7.1.7 | ColumnccatSensorDescription | read-only | current | CCAT sensor value description |
| 1.3.6.1.4.1.21239.5.2.8 | Tablet3hdSensorTable | not-accessible | current | Remote Temperature x 3, Humidity and Dewpoint Sensor |
| 1.3.6.1.4.1.21239.5.2.8.1 | Rowt3hdSensorEntry | not-accessible | current | Entry in the t3hdSensorTable table: each entry contains an index and other sensor details |
| 1.3.6.1.4.1.21239.5.2.8.1.1 | Columnt3hdSensorIndex | read-only | current | Table entry index value |
| 1.3.6.1.4.1.21239.5.2.8.1.2 | Columnt3hdSensorSerial | read-only | current | Serial Number |
| 1.3.6.1.4.1.21239.5.2.8.1.3 | Columnt3hdSensorName | read-only | current | Friendly Name |
| 1.3.6.1.4.1.21239.5.2.8.1.4 | Columnt3hdSensorAvail | read-only | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable |
| 1.3.6.1.4.1.21239.5.2.8.1.5 | Columnt3hdSensorIntName | read-only | current | T3HD Sensor Internal Friendly Name |
| 1.3.6.1.4.1.21239.5.2.8.1.6 | Columnt3hdSensorIntTemp | read-only | current | Current reading for Internal Temperature in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo |
| 1.3.6.1.4.1.21239.5.2.8.1.7 | Columnt3hdSensorIntHumidity | read-only | current | T3HD Sensor Internal Humidity |
| 1.3.6.1.4.1.21239.5.2.8.1.8 | Columnt3hdSensorIntDewPoint | read-only | current | Current reading for Internal DewPoint in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo |
| 1.3.6.1.4.1.21239.5.2.8.1.9 | Columnt3hdSensorExtAAvail | read-only | current | T3HD External A status: 0 = Unavailable, 1 = Available |
| 1.3.6.1.4.1.21239.5.2.8.1.10 | Columnt3hdSensorExtAName | read-only | current | T3HD External A Friendly Name |
| 1.3.6.1.4.1.21239.5.2.8.1.11 | Columnt3hdSensorExtATemp | read-only | current | Current reading for External Temperature A in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo |
| 1.3.6.1.4.1.21239.5.2.8.1.12 | Columnt3hdSensorExtBAvail | read-only | current | T3HD External B status: 0 = Unavailable, 1 = Available |
| 1.3.6.1.4.1.21239.5.2.8.1.13 | Columnt3hdSensorExtBName | read-only | current | T3HD External B Friendly Name |
| 1.3.6.1.4.1.21239.5.2.8.1.14 | Columnt3hdSensorExtBTemp | read-only | current | Current reading for External Temperature B in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo |
| 1.3.6.1.4.1.21239.5.2.9 | TablethdSensorTable | not-accessible | current | Remote Temperature, Humidity and Dewpoint Sensor |
| 1.3.6.1.4.1.21239.5.2.9.1 | RowthdSensorEntry | not-accessible | current | Entry in the thdSensorTable table: each entry contains an index and other sensor details |
| 1.3.6.1.4.1.21239.5.2.9.1.1 | ColumnthdSensorIndex | read-only | current | Table entry index value |
| 1.3.6.1.4.1.21239.5.2.9.1.2 | ColumnthdSensorSerial | read-only | current | Serial Number |
| 1.3.6.1.4.1.21239.5.2.9.1.3 | ColumnthdSensorName | read-only | current | Friendly Name |
| 1.3.6.1.4.1.21239.5.2.9.1.4 | ColumnthdSensorAvail | read-only | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable |
| 1.3.6.1.4.1.21239.5.2.9.1.5 | ColumnthdSensorTemp | read-only | current | Current reading for Temperature in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo |
| 1.3.6.1.4.1.21239.5.2.9.1.6 | ColumnthdSensorHumidity | read-only | current | THD Sensor Humidity |
| 1.3.6.1.4.1.21239.5.2.9.1.7 | ColumnthdSensorDewPoint | read-only | current | Current reading for DewPoint in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo |
| 1.3.6.1.4.1.21239.5.2.10 | TablerpmSensorTable | not-accessible | current | Remote Power Manager Sensor |
| 1.3.6.1.4.1.21239.5.2.10.1 | RowrpmSensorEntry | not-accessible | current | Entry in the rpmSensorTable table: each entry contains an index and other sensor details |
| 1.3.6.1.4.1.21239.5.2.10.1.1 | ColumnrpmSensorIndex | read-only | current | Table entry index value |
| 1.3.6.1.4.1.21239.5.2.10.1.2 | ColumnrpmSensorSerial | read-only | current | Serial Number |
| 1.3.6.1.4.1.21239.5.2.10.1.3 | ColumnrpmSensorName | read-only | current | Friendly Name |
| 1.3.6.1.4.1.21239.5.2.10.1.4 | ColumnrpmSensorAvail | read-only | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable |
| 1.3.6.1.4.1.21239.5.2.10.1.5 | ColumnrpmSensorEnergy | read-only | current | RPM Sensor Accumulated Energy |
| 1.3.6.1.4.1.21239.5.2.10.1.6 | ColumnrpmSensorVoltage | read-only | current | RPM Sensor Voltage |
| 1.3.6.1.4.1.21239.5.2.10.1.7 | ColumnrpmSensorVoltageMax | read-only | current | RPM Sensor Voltage (Max) |
| 1.3.6.1.4.1.21239.5.2.10.1.8 | ColumnrpmSensorVoltageMin | read-only | current | RPM Sensor Voltage (Min) |
| 1.3.6.1.4.1.21239.5.2.10.1.9 | ColumnrpmSensorVoltagePeak | read-only | current | RPM Sensor Voltage (Peak) |
| 1.3.6.1.4.1.21239.5.2.10.1.10 | ColumnrpmSensorCurrent | read-only | current | RPM Sensor Current reading in deciAmps |
| 1.3.6.1.4.1.21239.5.2.10.1.11 | ColumnrpmSensorRealPower | read-only | current | RPM Sensor Real Power |
| 1.3.6.1.4.1.21239.5.2.10.1.12 | ColumnrpmSensorApparentPower | read-only | current | RPM Sensor Apparent Power |
| 1.3.6.1.4.1.21239.5.2.10.1.13 | ColumnrpmSensorPowerFactor | read-only | current | RPM Sensor Power Factor |
| 1.3.6.1.4.1.21239.5.2.10.1.14 | ColumnrpmSensorOutlet1 | read-only | current | RPM Sensor Outlet 1 State: 0 = off, 1 = on |
| 1.3.6.1.4.1.21239.5.2.10.1.15 | ColumnrpmSensorOutlet2 | read-only | current | RPM Sensor Outlet 2 State: 0 = off, 1 = on |
| 1.3.6.1.4.1.21239.5.2.11 | Tablea2dSensorTable | not-accessible | current | Analog Measurement Sensor (Voltage, Current, or Dry Contact) |
| 1.3.6.1.4.1.21239.5.2.11.1 | Rowa2DSensorEntry | not-accessible | current | Entry in the a2dSensorTable table: each entry contains an index and other sensor details |
| 1.3.6.1.4.1.21239.5.2.11.1.1 | Columna2dSensorIndex | read-only | current | Table entry index value |
| 1.3.6.1.4.1.21239.5.2.11.1.2 | Columna2dSensorSerial | read-only | current | Serial Number |
| 1.3.6.1.4.1.21239.5.2.11.1.3 | Columna2dSensorName | read-only | current | Friendly Name |
| 1.3.6.1.4.1.21239.5.2.11.1.4 | Columna2dSensorAvail | read-only | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable |
| 1.3.6.1.4.1.21239.5.2.11.1.5 | Columna2dSensorValue | read-only | current | Current analog measurement reading within either a user defined or preset range depending on device mode. |
| 1.3.6.1.4.1.21239.5.2.32767 | Nodetrap | |||
| 1.3.6.1.4.1.21239.5.2.32767.0 | NodetrapPrefix | |||
| 1.3.6.1.4.1.21239.5.2.32767.0.10101 | NotificationinternalTestNOTIFY | current | Test SNMP Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10305 | NotificationpduMainAvailNOTIFY | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10309 | NotificationpduTotalRealPowerNOTIFY | current | PDU Total Real Power Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10310 | NotificationpduTotalApparentPowerNOTIFY | current | PDU Total Apparent Power Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10311 | NotificationpduTotalPowerFactorNOTIFY | current | PDU Total Power Factor Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10312 | NotificationpduTotalEnergyNOTIFY | current | PDU Total Accumulated Energy Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10324 | NotificationpduPhaseVoltageNOTIFY | current | PDU Phase Voltage in tenths of a volt Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10325 | NotificationpduPhaseVoltageMaxNOTIFY | current | PDU Phase Voltage (Max) in tenths of a volt Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10326 | NotificationpduPhaseVoltageMinNOTIFY | current | PDU Phase Voltage (Min) in tenths of a volt Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10327 | NotificationpduPhaseVoltagePeakNOTIFY | current | PDU Phase Voltage (Peak) in tenths of a volt Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10328 | NotificationpduPhaseCurrentNOTIFY | current | PDU Phase Current Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10329 | NotificationpduPhaseCurrentMaxNOTIFY | current | PDU Phase Current (Max) Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10330 | NotificationpduPhaseCurrentMinNOTIFY | current | PDU Phase Current (Min) Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10331 | NotificationpduPhaseCurrentPeakNOTIFY | current | PDU Phase Current (Peak) Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10332 | NotificationpduPhaseRealPowerNOTIFY | current | PDU Phase Real Power Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10333 | NotificationpduPhaseApparentPowerNOTIFY | current | PDU Phase Apparent Power Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10334 | NotificationpduPhasePowerFactorNOTIFY | current | PDU Phase Power Factor Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10335 | NotificationpduPhaseEnergyNOTIFY | current | PDU Phase Accumulated Energy Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10354 | NotificationpduBreakerCurrentNOTIFY | current | PDU Breaker Current Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10355 | NotificationpduBreakerCurrentMaxNOTIFY | current | PDU Breaker Current (Max) Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10356 | NotificationpduBreakerCurrentMinNOTIFY | current | PDU Breaker Current (Min) Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10357 | NotificationpduBreakerCurrentPeakNOTIFY | current | PDU Breaker Current (Peak) Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10374 | NotificationpduLineCurrentNOTIFY | current | PDU Line Current Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10375 | NotificationpduLineCurrentMaxNOTIFY | current | PDU Line Current (Max) Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10376 | NotificationpduLineCurrentMinNOTIFY | current | PDU Line Current (Min) Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10377 | NotificationpduLineCurrentPeakNOTIFY | current | PDU Line Current (Peak) Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10404 | NotificationtempSensorAvailNOTIFY | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10405 | NotificationtempSensorTempNOTIFY | current | Remote Temperature Sensor Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10504 | NotificationairFlowSensorAvailNOTIFY | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10505 | NotificationairFlowSensorTempNOTIFY | current | AFHT3 Sensor Temperature Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10506 | NotificationairFlowSensorFlowNOTIFY | current | AFHT3 Airflow reading Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10507 | NotificationairFlowSensorHumidityNOTIFY | current | AFHT3 Humidity reading Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10508 | NotificationairFlowSensorDewPointNOTIFY | current | AFHT3 Sensor Dew Point Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10604 | NotificationdewPointSensorAvailNOTIFY | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10605 | NotificationdewPointSensorTempNOTIFY | current | Remote Dew Point Sensor Temperature Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10606 | NotificationdewPointSensorHumidityNOTIFY | current | Humidity reading Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10607 | NotificationdewPointSensorDewPointNOTIFY | current | Remote Dew Point Sensor Dew Point Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10704 | NotificationccatSensorAvailNOTIFY | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10705 | NotificationccatSensorValueNOTIFY | current | CCAT sensor reading Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10804 | Notificationt3hdSensorAvailNOTIFY | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10806 | Notificationt3hdSensorIntTempNOTIFY | current | T3HD Sensor Temperature Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10807 | Notificationt3hdSensorIntHumidityNOTIFY | current | T3HD Sensor Internal Humidity Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10808 | Notificationt3hdSensorIntDewPointNOTIFY | current | T3HD Sensor Dew Point Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10811 | Notificationt3hdSensorExtATempNOTIFY | current | T3HD Sensor External A Temperature Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10814 | Notificationt3hdSensorExtBTempNOTIFY | current | T3HD Sensor External B Temperature Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10904 | NotificationthdSensorAvailNOTIFY | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10905 | NotificationthdSensorTempNOTIFY | current | THD Sensor Temperature Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10906 | NotificationthdSensorHumidityNOTIFY | current | THD Sensor Humidity Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10907 | NotificationthdSensorDewPointNOTIFY | current | THD Sensor Dew Point Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.11004 | NotificationrpmSensorAvailNOTIFY | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.11005 | NotificationrpmSensorEnergyNOTIFY | current | RPM Sensor Accumulated Energy Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.11006 | NotificationrpmSensorVoltageNOTIFY | current | RPM Sensor Voltage Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.11007 | NotificationrpmSensorVoltageMaxNOTIFY | current | RPM Sensor Voltage (Max) Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.11008 | NotificationrpmSensorVoltageMinNOTIFY | current | RPM Sensor Voltage (Min) Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.11009 | NotificationrpmSensorVoltagePeakNOTIFY | current | RPM Sensor Voltage (Peak) Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.11010 | NotificationrpmSensorCurrentNOTIFY | current | RPM Sensor Current Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.11011 | NotificationrpmSensorRealPowerNOTIFY | current | RPM Sensor Real Power Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.11012 | NotificationrpmSensorApparentPowerNOTIFY | current | RPM Sensor Apparent Power Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.11013 | NotificationrpmSensorPowerFactorNOTIFY | current | RPM Sensor Power Factor Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.11104 | Notificationa2dSensorAvailNOTIFY | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.11105 | Notificationa2dSensorValueNOTIFY | current | A2D Analog Sensor Measurement Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20305 | NotificationpduMainAvailCLEAR | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20309 | NotificationpduTotalRealPowerCLEAR | current | PDU Total Real Power Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20310 | NotificationpduTotalApparentPowerCLEAR | current | PDU Total Apparent Power Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20311 | NotificationpduTotalPowerFactorCLEAR | current | PDU Total Power Factor Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20312 | NotificationpduTotalEnergyCLEAR | current | PDU Total Accumulated Energy Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20324 | NotificationpduPhaseVoltageCLEAR | current | PDU Phase Voltage in tenths of a volt Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20325 | NotificationpduPhaseVoltageMaxCLEAR | current | PDU Phase Voltage (Max) in tenths of a volt Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20326 | NotificationpduPhaseVoltageMinCLEAR | current | PDU Phase Voltage (Min) in tenths of a volt Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20327 | NotificationpduPhaseVoltagePeakCLEAR | current | PDU Phase Voltage (Peak) in tenths of a volt Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20328 | NotificationpduPhaseCurrentCLEAR | current | PDU Phase Current Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20329 | NotificationpduPhaseCurrentMaxCLEAR | current | PDU Phase Current (Max) Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20330 | NotificationpduPhaseCurrentMinCLEAR | current | PDU Phase Current (Min) Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20331 | NotificationpduPhaseCurrentPeakCLEAR | current | PDU Phase Current (Peak) Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20332 | NotificationpduPhaseRealPowerCLEAR | current | PDU Phase Real Power Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20333 | NotificationpduPhaseApparentPowerCLEAR | current | PDU Phase Apparent Power Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20334 | NotificationpduPhasePowerFactorCLEAR | current | PDU Phase Power Factor Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20335 | NotificationpduPhaseEnergyCLEAR | current | PDU Phase Accumulated Energy Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20354 | NotificationpduBreakerCurrentCLEAR | current | PDU Breaker Current Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20355 | NotificationpduBreakerCurrentMaxCLEAR | current | PDU Breaker Current (Max) Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20356 | NotificationpduBreakerCurrentMinCLEAR | current | PDU Breaker Current (Min) Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20357 | NotificationpduBreakerCurrentPeakCLEAR | current | PDU Breaker Current (Peak) Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20374 | NotificationpduLineCurrentCLEAR | current | PDU Line Current Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20375 | NotificationpduLineCurrentMaxCLEAR | current | PDU Line Current (Max) Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20376 | NotificationpduLineCurrentMinCLEAR | current | PDU Line Current (Min) Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20377 | NotificationpduLineCurrentPeakCLEAR | current | PDU Line Current (Peak) Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20404 | NotificationtempSensorAvailCLEAR | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20405 | NotificationtempSensorTempCLEAR | current | Remote Temperature Sensor Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20504 | NotificationairFlowSensorAvailCLEAR | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20505 | NotificationairFlowSensorTempCLEAR | current | AFHT3 Sensor Temperature Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20506 | NotificationairFlowSensorFlowCLEAR | current | AFHT3 Airflow reading Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20507 | NotificationairFlowSensorHumidityCLEAR | current | AFHT3 Humidity reading Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20508 | NotificationairFlowSensorDewPointCLEAR | current | AFHT3 Sensor Dew Point Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20604 | NotificationdewPointSensorAvailCLEAR | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20605 | NotificationdewPointSensorTempCLEAR | current | Remote Dew Point Sensor Temperature Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20606 | NotificationdewPointSensorHumidityCLEAR | current | Humidity reading Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20607 | NotificationdewPointSensorDewPointCLEAR | current | Remote Dew Point Sensor Dew Point Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20704 | NotificationccatSensorAvailCLEAR | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20705 | NotificationccatSensorValueCLEAR | current | CCAT sensor reading Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20804 | Notificationt3hdSensorAvailCLEAR | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20806 | Notificationt3hdSensorIntTempCLEAR | current | T3HD Sensor Temperature Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20807 | Notificationt3hdSensorIntHumidityCLEAR | current | T3HD Sensor Internal Humidity Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20808 | Notificationt3hdSensorIntDewPointCLEAR | current | T3HD Sensor Dew Point Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20811 | Notificationt3hdSensorExtATempCLEAR | current | T3HD Sensor External A Temperature Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20814 | Notificationt3hdSensorExtBTempCLEAR | current | T3HD Sensor External B Temperature Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20904 | NotificationthdSensorAvailCLEAR | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20905 | NotificationthdSensorTempCLEAR | current | THD Sensor Temperature Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20906 | NotificationthdSensorHumidityCLEAR | current | THD Sensor Humidity Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20907 | NotificationthdSensorDewPointCLEAR | current | THD Sensor Dew Point Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.21004 | NotificationrpmSensorAvailCLEAR | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.21005 | NotificationrpmSensorEnergyCLEAR | current | RPM Sensor Accumulated Energy Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.21006 | NotificationrpmSensorVoltageCLEAR | current | RPM Sensor Voltage Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.21007 | NotificationrpmSensorVoltageMaxCLEAR | current | RPM Sensor Voltage (Max) Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.21008 | NotificationrpmSensorVoltageMinCLEAR | current | RPM Sensor Voltage (Min) Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.21009 | NotificationrpmSensorVoltagePeakCLEAR | current | RPM Sensor Voltage (Peak) Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.21010 | NotificationrpmSensorCurrentCLEAR | current | RPM Sensor Current Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.21011 | NotificationrpmSensorRealPowerCLEAR | current | RPM Sensor Real Power Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.21012 | NotificationrpmSensorApparentPowerCLEAR | current | RPM Sensor Apparent Power Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.21013 | NotificationrpmSensorPowerFactorCLEAR | current | RPM Sensor Power Factor Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.21104 | Notificationa2dSensorAvailCLEAR | current | Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.21105 | Notificationa2dSensorValueCLEAR | current | A2D Analog Sensor Measurement Clear Trap |