The MIB module to describe GE Digital Energy Uninterruptible Power Supplies.
Imported Objects
SNMPv2-SMICounter32 enterprises Gauge32 Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-IDENTITY OBJECT-TYPE Unsigned32
SNMPv2-TCAutonomousType DisplayString TestAndIncr TEXTUAL-CONVENTION TimeInterval TimeStamp
OIDNameAccessStatusDescription
1.3.6.1.4.1.818IdentityimvThe MIB module to describe GE Digital Energy Uninterruptible Power Supplies.
1.3.6.1.4.1.818.1NodegeHardware
1.3.6.1.4.1.818.1.1NodegeUPS
1.3.6.1.4.1.818.1.1.1ScalargeDiscoveredUPSsMaskread-onlycurrentReading this variable returns bit mask indicating which UPSs in a parallel system are alive. Management software should poll only these UPSs on their snmp bran…
1.3.6.1.4.1.818.1.1.2ScalargeRequestPacketread-writecurrentPut the string, formatted as a IMV/CP4 packet, directly to internally RS485 bus. This OID could be used for accede directly to the internally RS485 bus from a …
1.3.6.1.4.1.818.1.1.3ScalargeReplyPacketread-onlycurrentContain the reply of the IMV/CP4 request packet sent using the OID geRequestPacket. Every time that a write command has be made at the OID ge RequestPacket, th…
1.3.6.1.4.1.818.1.1.10NodegeGenericUPS
1.3.6.1.4.1.818.1.1.10.1NodeupsIdent
1.3.6.1.4.1.818.1.1.10.1.1ScalarupsIdentManufacturerread-onlycurrentThe name of the UPS manufacturer.(*)
1.3.6.1.4.1.818.1.1.10.1.2ScalarupsIdentModelread-onlycurrentThe UPS Model designation.(*)
1.3.6.1.4.1.818.1.1.10.1.3ScalarupsIdentUPSSoftwareVersionread-onlycurrentThe UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*)
1.3.6.1.4.1.818.1.1.10.1.4ScalarupsIdentAgentSoftwareVersionread-onlycurrentThe UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*)
1.3.6.1.4.1.818.1.1.10.1.5ScalarupsIdentNameread-writecurrentA string identifying the UPS. This object should be set by the administrator.(*)
1.3.6.1.4.1.818.1.1.10.1.6ScalarupsIdentAttachedDevicesread-writecurrentA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*)
1.3.6.1.4.1.818.1.1.10.1.7ScalarupsIdentUPSSerialNumberread-onlycurrentThe UPS serial number
1.3.6.1.4.1.818.1.1.10.1.8ScalarupsIdentComProtVersionread-onlycurrentThe IMV communication protocol version
1.3.6.1.4.1.818.1.1.10.1.9ScalarupsIdentOperatingTimeread-onlycurrentThe present value of the operating time. total 'on' time since UPS manufactured
1.3.6.1.4.1.818.1.1.10.2NodeupsBattery
1.3.6.1.4.1.818.1.1.10.2.1ScalarupsBatteryStatusread-onlycurrentThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfi…
1.3.6.1.4.1.818.1.1.10.2.2ScalarupsSecondsOnBatteryread-onlycurrentIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res…
1.3.6.1.4.1.818.1.1.10.2.3ScalarupsEstimatedMinutesRemainingread-onlycurrentAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and…
1.3.6.1.4.1.818.1.1.10.2.4ScalarupsEstimatedChargeRemainingread-onlycurrentAn estimate of the battery charge remaining expressed as a percent of full charge.(*)
1.3.6.1.4.1.818.1.1.10.2.5ScalarupsBatteryVoltageread-onlycurrentThe magnitude of the present battery voltage.(*)
1.3.6.1.4.1.818.1.1.10.2.6ScalarupsBatteryCurrentread-onlycurrentThe present battery current.(*)
1.3.6.1.4.1.818.1.1.10.2.7ScalarupsBatteryTemperatureread-onlycurrentThe ambient temperature at or near the UPS Battery casing.(*)
1.3.6.1.4.1.818.1.1.10.2.8ScalarupsBatteryRippleread-onlycurrentThe present DC link RMS voltage ripple.(*)
1.3.6.1.4.1.818.1.1.10.3NodeupsInput
1.3.6.1.4.1.818.1.1.10.3.1ScalarupsInputLineBadsread-onlycurrentA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the i…
1.3.6.1.4.1.818.1.1.10.3.2ScalarupsInputNumLinesread-onlycurrentThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*)
1.3.6.1.4.1.818.1.1.10.3.3TableupsInputTablenot-accessiblecurrentA list of input table entries. The number of entries is given by the value of upsInputNumLines.(*)
1.3.6.1.4.1.818.1.1.10.3.3.1RowupsInputEntrynot-accessiblecurrentAn entry containing information applicable to a particular input line.(*)
1.3.6.1.4.1.818.1.1.10.3.3.1.1ColumnupsInputLineIndexnot-accessiblecurrentThe input line identifier.(*)
1.3.6.1.4.1.818.1.1.10.3.3.1.2ColumnupsInputFrequencyread-onlycurrentThe present input frequency.(*)
1.3.6.1.4.1.818.1.1.10.3.3.1.3ColumnupsInputVoltageread-onlycurrentThe magnitude of the present input voltage.(*)
1.3.6.1.4.1.818.1.1.10.3.3.1.4ColumnupsInputCurrentread-onlycurrentThe magnitude of the present input current.(*)
1.3.6.1.4.1.818.1.1.10.3.3.1.5ColumnupsInputTruePowerread-onlycurrentThe magnitude of the present input true power.(*)
1.3.6.1.4.1.818.1.1.10.3.3.1.6ColumnupsInputVoltageMinread-onlycurrentThe lowest magnitude of the input voltage since last read out.
1.3.6.1.4.1.818.1.1.10.3.3.1.7ColumnupsInputVoltageMaxread-onlycurrentThe highest magnitude of the input voltage since last read out.
1.3.6.1.4.1.818.1.1.10.4NodeupsOutput
1.3.6.1.4.1.818.1.1.10.4.1ScalarupsOutputSourceread-onlycurrentThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the…
1.3.6.1.4.1.818.1.1.10.4.2ScalarupsOutputFrequencyread-onlycurrentThe present output frequency.(*)
1.3.6.1.4.1.818.1.1.10.4.3ScalarupsOutputNumLinesread-onlycurrentThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*)
1.3.6.1.4.1.818.1.1.10.4.4TableupsOutputTablenot-accessiblecurrentA list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*)
1.3.6.1.4.1.818.1.1.10.4.4.1RowupsOutputEntrynot-accessiblecurrentAn entry containing information applicable to a particular output line.(*)
1.3.6.1.4.1.818.1.1.10.4.4.1.1ColumnupsOutputLineIndexnot-accessiblecurrentThe output line identifier.(*)
1.3.6.1.4.1.818.1.1.10.4.4.1.2ColumnupsOutputVoltageread-onlycurrentThe present output voltage.(*)
1.3.6.1.4.1.818.1.1.10.4.4.1.3ColumnupsOutputCurrentread-onlycurrentThe present output current.(*)
1.3.6.1.4.1.818.1.1.10.4.4.1.4ColumnupsOutputPowerread-onlycurrentThe present output true power.(*)
1.3.6.1.4.1.818.1.1.10.4.4.1.5ColumnupsOutputPercentLoadread-onlycurrentThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent…
1.3.6.1.4.1.818.1.1.10.4.4.1.6ColumnupsOutputPowerFactorread-onlycurrentThe present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate …
1.3.6.1.4.1.818.1.1.10.4.4.1.7ColumnupsOutputPeakCurrentread-onlycurrentThe present output peak current.(*)
1.3.6.1.4.1.818.1.1.10.4.4.1.8ColumnupsOutputShareCurrentread-onlycurrentIn a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share…
1.3.6.1.4.1.818.1.1.10.5NodeupsBypass
1.3.6.1.4.1.818.1.1.10.5.1ScalarupsBypassFrequencyread-onlycurrentThe present bypass frequency.(*)
1.3.6.1.4.1.818.1.1.10.5.2ScalarupsBypassNumLinesread-onlycurrentThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*)
1.3.6.1.4.1.818.1.1.10.5.3TableupsBypassTablenot-accessiblecurrentA list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*)
1.3.6.1.4.1.818.1.1.10.5.3.1RowupsBypassEntrynot-accessiblecurrentAn entry containing information applicable to a particular bypass input.(*)
1.3.6.1.4.1.818.1.1.10.5.3.1.1ColumnupsBypassLineIndexnot-accessiblecurrentThe bypass line identifier.(*)
1.3.6.1.4.1.818.1.1.10.5.3.1.2ColumnupsBypassVoltageread-onlycurrentThe present bypass voltage.(*)
1.3.6.1.4.1.818.1.1.10.5.3.1.3ColumnupsBypassCurrentread-onlycurrentThe present bypass current.(*)
1.3.6.1.4.1.818.1.1.10.5.3.1.4ColumnupsBypassPowerread-onlycurrentThe present true power conveyed by the bypass.(*)
1.3.6.1.4.1.818.1.1.10.6NodeupsAlarm
1.3.6.1.4.1.818.1.1.10.6.1ScalarupsAlarmsPresentread-onlycurrentThe present number of active alarm conditions.(*)
1.3.6.1.4.1.818.1.1.10.6.2TableupsAlarmTablenot-accessiblecurrentA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is …
1.3.6.1.4.1.818.1.1.10.6.2.1RowupsAlarmEntrynot-accessiblecurrentAn entry containing information applicable to a particular alarm.(*)
1.3.6.1.4.1.818.1.1.10.6.2.1.1ColumnupsAlarmIdnot-accessiblecurrentA unique identifier for an alarm condition. This value must remain constant.(*)
1.3.6.1.4.1.818.1.1.10.6.2.1.2ColumnupsAlarmDescrread-onlycurrentA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con…
1.3.6.1.4.1.818.1.1.10.6.2.1.3ColumnupsAlarmTimeread-onlycurrentThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before ag…
1.3.6.1.4.1.818.1.1.10.6.3NodeupsWellKnownAlarms
1.3.6.1.4.1.818.1.1.10.6.3.1IdentityupsAlarmBatteryBadcurrentOne or more batteries have been determined to require replacement.(*)
1.3.6.1.4.1.818.1.1.10.6.3.2IdentityupsAlarmOnBatterycurrentThe UPS is drawing power from the batteries.(*)
1.3.6.1.4.1.818.1.1.10.6.3.3IdentityupsAlarmLowBatterycurrentThe remaining battery run-time is less than or equal to upsConfigLowBattTime.(*)
1.3.6.1.4.1.818.1.1.10.6.3.4IdentityupsAlarmDepletedBatterycurrentThe UPS will be unable to sustain the present load when and if the utility power is lost.(*)
1.3.6.1.4.1.818.1.1.10.6.3.5IdentityupsAlarmTempBadcurrentA temperature is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.10.6.3.6IdentityupsAlarmInputBadcurrentAn input condition is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.10.6.3.7IdentityupsAlarmOutputBadcurrentAn output condition (other than OutputOverload) is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.10.6.3.8IdentityupsAlarmOutputOverloadcurrentThe output load exceeds the UPS output capacity.(*)
1.3.6.1.4.1.818.1.1.10.6.3.9IdentityupsAlarmOnBypasscurrentThe Bypass is presently engaged on the UPS.(*)
1.3.6.1.4.1.818.1.1.10.6.3.10IdentityupsAlarmBypassBadcurrentThe Bypass is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.10.6.3.11IdentityupsAlarmOutputOffAsRequestedcurrentThe UPS has shutdown as requested, i.e., the output is off.(*)
1.3.6.1.4.1.818.1.1.10.6.3.12IdentityupsAlarmUpsOffAsRequestedcurrentThe entire UPS has shutdown as commanded.(*)
1.3.6.1.4.1.818.1.1.10.6.3.13IdentityupsAlarmChargerFailedcurrentAn uncorrected problem has been detected within the UPS charger subsystem.(*)
1.3.6.1.4.1.818.1.1.10.6.3.14IdentityupsAlarmUpsOutputOffcurrentThe output of the UPS is in the off state.(*)
1.3.6.1.4.1.818.1.1.10.6.3.15IdentityupsAlarmUpsSystemOffcurrentThe UPS system is in the off state.(*)
1.3.6.1.4.1.818.1.1.10.6.3.16IdentityupsAlarmFanFailurecurrentThe failure of one or more fans in the UPS has been detected.(*)
1.3.6.1.4.1.818.1.1.10.6.3.17IdentityupsAlarmFuseFailurecurrentThe failure of one or more fuses has been detected.(*)
1.3.6.1.4.1.818.1.1.10.6.3.18IdentityupsAlarmGeneralFaultcurrentA general fault in the UPS has been detected.(*)
1.3.6.1.4.1.818.1.1.10.6.3.19IdentityupsAlarmDiagnosticTestFailedcurrentThe result of the last diagnostic test indicates a failure.(*)
1.3.6.1.4.1.818.1.1.10.6.3.20IdentityupsAlarmCommunicationsLostcurrentA problem has been encountered in the communications between the agent and the UPS.(*)
1.3.6.1.4.1.818.1.1.10.6.3.21IdentityupsAlarmAwaitingPowercurrentThe UPS output is off and the UPS is awaiting the return of input power.(*)
1.3.6.1.4.1.818.1.1.10.6.3.22IdentityupsAlarmShutdownPendingcurrentA upsShutdownAfterDelay countdown is underway.(*)
1.3.6.1.4.1.818.1.1.10.6.3.23IdentityupsAlarmShutdownImminentcurrentThe UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.(*)
1.3.6.1.4.1.818.1.1.10.6.3.24IdentityupsAlarmTestInProgresscurrentA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of …
1.3.6.1.4.1.818.1.1.10.6.3.25IdentityupsAlarmReceptacleOffcurrentThe receptacle are switch off
1.3.6.1.4.1.818.1.1.10.6.3.26IdentityupsAlarmHighSpeedBusFailurecurrentA problem on the High Speed Bus communication is detected
1.3.6.1.4.1.818.1.1.10.6.3.27IdentityupsAlarmHighSpeedBusJACRCFailurecurrentA CRC problem on the Highspeed Bus JA is detected.
1.3.6.1.4.1.818.1.1.10.6.3.28IdentityupsAlarmConnectivityBusFailurecurrentA problem on the Connectivity Bus communication is detected
1.3.6.1.4.1.818.1.1.10.6.3.29IdentityupsAlarmHighSpeedBusJBCRCFailurecurrentA CRC problem on the Highspeed Bus JB is detected.
1.3.6.1.4.1.818.1.1.10.6.3.30IdentityupsAlarmCurrentSharingcurrentThe System detects an high current sharing on the parallel system
1.3.6.1.4.1.818.1.1.10.6.3.31IdentityupsAlarmDCRipplecurrentThe System detects an high ripple voltage on one DC link
1.3.6.1.4.1.818.1.1.10.6.4ScalarupsAlarmMaskAread-onlycurrentSpecifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' com…
1.3.6.1.4.1.818.1.1.10.7NodeupsTest
1.3.6.1.4.1.818.1.1.10.7.1ScalarupsTestIdread-writecurrentThe test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this docu…
1.3.6.1.4.1.818.1.1.10.7.2ScalarupsTestSpinLockread-writecurrentA spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress a…
1.3.6.1.4.1.818.1.1.10.7.3ScalarupsTestResultsSummaryread-onlycurrentThe results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test complete…
1.3.6.1.4.1.818.1.1.10.7.4ScalarupsTestResultsDetailread-onlycurrentAdditional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*)
1.3.6.1.4.1.818.1.1.10.7.5ScalarupsTestStartTimeread-onlycurrentThe value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of…
1.3.6.1.4.1.818.1.1.10.7.6ScalarupsTestElapsedTimeread-onlycurrentThe amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of …
1.3.6.1.4.1.818.1.1.10.7.7NodeupsWellKnownTests
1.3.6.1.4.1.818.1.1.10.7.7.1IdentityupsTestNoTestsInitiatedcurrentNo tests have been initiated and no test is in progress.(*)
1.3.6.1.4.1.818.1.1.10.7.7.2IdentityupsTestAbortTestInProgresscurrentThe test in progress is to be aborted / the test in progress was aborted.(*)
1.3.6.1.4.1.818.1.1.10.7.7.3IdentityupsTestGeneralSystemsTestcurrentThe manufacturer's standard test of UPS device systems.(*)
1.3.6.1.4.1.818.1.1.10.7.7.4IdentityupsTestQuickBatteryTestcurrentA test that is sufficient to determine if the battery needs replacement.(*)
1.3.6.1.4.1.818.1.1.10.7.7.5IdentityupsTestDeepBatteryCalibrationcurrentThe system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high deg…
1.3.6.1.4.1.818.1.1.10.8NodeupsControl
1.3.6.1.4.1.818.1.1.10.8.1ScalarupsShutdownTyperead-writecurrentThis object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reach…
1.3.6.1.4.1.818.1.1.10.8.2ScalarupsShutdownAfterDelayread-writecurrentSetting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdo…
1.3.6.1.4.1.818.1.1.10.8.3ScalarupsStartupAfterDelayread-writecurrentSetting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause …
1.3.6.1.4.1.818.1.1.10.8.4ScalarupsRebootWithDurationread-writecurrentSetting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the ti…
1.3.6.1.4.1.818.1.1.10.8.5ScalarupsAutoRestartread-writecurrentSetting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutd…
1.3.6.1.4.1.818.1.1.10.8.6ScalarupsReceptaclesNumread-onlycurrentThe number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table.
1.3.6.1.4.1.818.1.1.10.8.7TableupsReceptacleTablenot-accessiblecurrentA list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum.
1.3.6.1.4.1.818.1.1.10.8.7.1RowupsReceptacleEntrynot-accessiblecurrentAn entry containing information applicable to a particular receptacle.
1.3.6.1.4.1.818.1.1.10.8.7.1.1ColumnupsReceptacleLineIndexnot-accessiblecurrentThe receptacle line identifier.
1.3.6.1.4.1.818.1.1.10.8.7.1.2ColumnupsReceptacleOnOffread-writecurrentThe present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptac…
1.3.6.1.4.1.818.1.1.10.8.8ScalarupsUPSModeread-writecurrentThe operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transfor…
1.3.6.1.4.1.818.1.1.10.8.9ScalarupsRectifierOnOffread-writecurrentThe present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier …
1.3.6.1.4.1.818.1.1.10.8.10ScalarupsBatteryChargeMethodread-writecurrentThe present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this objec…
1.3.6.1.4.1.818.1.1.10.8.11ScalarupsInverterOnOffread-writecurrentThe present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off…
1.3.6.1.4.1.818.1.1.10.8.12ScalarupsBypassOnOffread-writecurrentThe present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If…
1.3.6.1.4.1.818.1.1.10.8.13ScalarupsLoadSourceread-writecurrentThe present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will …
1.3.6.1.4.1.818.1.1.10.9NodeupsConfig
1.3.6.1.4.1.818.1.1.10.9.1ScalarupsConfigInputVoltageread-writecurrentThe magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a v…
1.3.6.1.4.1.818.1.1.10.9.2ScalarupsConfigInputFreqread-writecurrentThe nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is no…
1.3.6.1.4.1.818.1.1.10.9.3ScalarupsConfigOutputVoltageread-writecurrentThe magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a …
1.3.6.1.4.1.818.1.1.10.9.4ScalarupsConfigOutputFreqread-writecurrentThe nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is n…
1.3.6.1.4.1.818.1.1.10.9.5ScalarupsConfigOutputVAread-onlycurrentThe magnitude of the nominal Volt-Amp rating.(*)
1.3.6.1.4.1.818.1.1.10.9.6ScalarupsConfigOutputPowerread-onlycurrentThe magnitude of the nominal true power rating.(*)
1.3.6.1.4.1.818.1.1.10.9.7ScalarupsConfigLowBattTimeread-writecurrentThe value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the …
1.3.6.1.4.1.818.1.1.10.9.8ScalarupsConfigAudibleStatusread-writecurrentThe requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this …
1.3.6.1.4.1.818.1.1.10.9.9ScalarupsConfigLowVoltageTransferPointread-writecurrentThe minimum input line voltage allowed before the UPS system transfers to battery backup.(*)
1.3.6.1.4.1.818.1.1.10.9.10ScalarupsConfigHighVoltageTransferPointread-writecurrentThe maximum line voltage allowed before the UPS system transfers to battery backup.(*)
1.3.6.1.4.1.818.1.1.10.9.11ScalarupsConfigBatteryCapacityread-writecurrentThe installed battery capacity. This value is the 'factory'-value, not the value after calibration.
1.3.6.1.4.1.818.1.1.10.9.12ScalarupsConfigBatteryChargeCurrentread-writecurrentThe maximum battery charge current, including external chargers.
1.3.6.1.4.1.818.1.1.10.9.13ScalarupsConfigNoLoadShutdownread-writecurrentDis- or enable 'no load' shutdown from the contact interface.
1.3.6.1.4.1.818.1.1.10.9.14ScalarupsConfigStartDelayread-writecurrentMinimum required autonomy time before the UPS may perform an autorestart.
1.3.6.1.4.1.818.1.1.10.10NodeupsGetSet
1.3.6.1.4.1.818.1.1.10.10.1ScalarupsEventGetNextread-writecurrentThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The val…
1.3.6.1.4.1.818.1.1.10.10.2ScalarupsEventGetPreviousread-writecurrentThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The val…
1.3.6.1.4.1.818.1.1.10.10.3ScalarupsEventSetStartingTimeStampread-writecurrentThe timestamp which is used as starting point for downloading events from the UPS event buffer
1.3.6.1.4.1.818.1.1.10.10.4ScalarupsEventRetreiveCurrentTimeStampread-onlycurrentThe current timestamp is retreived from the UPS
1.3.6.1.4.1.818.1.1.10.10.5ScalarupsEventTableSizeread-onlycurrentThe number of entries in the event table. This object indicates the number of rows in the event table.
1.3.6.1.4.1.818.1.1.10.10.6TableupsEventTablenot-accessiblecurrentA list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the…
1.3.6.1.4.1.818.1.1.10.10.6.1RowupsEventEntrynot-accessiblecurrentAn entry containing information applicable to a particular event.
1.3.6.1.4.1.818.1.1.10.10.6.1.1ColumnupsEventLineIndexnot-accessiblecurrentThe event line identifier.
1.3.6.1.4.1.818.1.1.10.10.6.1.2ColumnupsEventCoderead-onlycurrentThe event code in numerical format.
1.3.6.1.4.1.818.1.1.10.10.6.1.3ColumnupsEventStatusread-onlycurrentThe status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status …
1.3.6.1.4.1.818.1.1.10.10.6.1.4ColumnupsEventTimeread-onlycurrentThe timestamp of the moment the event was generated.
1.3.6.1.4.1.818.1.1.10.10.7ScalarupsParametersReadread-writecurrentThe number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value up…
1.3.6.1.4.1.818.1.1.10.10.8ScalarupsParametersWriteread-writecurrentThe number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be u…
1.3.6.1.4.1.818.1.1.10.10.9ScalarupsParametersStartAddressread-writecurrentThe address which is used as starting point for downloading parameters from the UPS
1.3.6.1.4.1.818.1.1.10.10.10ScalarupsParameterTableSizeread-onlycurrentThe number of entries in the parameter table. This object indicates the number of rows in the parameter table.
1.3.6.1.4.1.818.1.1.10.10.11TableupsParameterTablenot-accessiblecurrentA list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of t…
1.3.6.1.4.1.818.1.1.10.10.11.1RowupsParameterEntrynot-accessiblecurrentAn entry containing information applicable to a particular parameter.
1.3.6.1.4.1.818.1.1.10.10.11.1.1ColumnupsParameterLineIndexnot-accessiblecurrentThe parameter line identifier.
1.3.6.1.4.1.818.1.1.10.10.11.1.2ColumnupsParameterValueread-writecurrentThe parameter value in numerical format.
1.3.6.1.4.1.818.1.1.10.10.12ScalarupsStatusread-onlycurrentThe global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other comman…
1.3.6.1.4.1.818.1.1.10.10.13ScalarupsMainsStatisticsMBfailread-onlycurrentCount of main bypass failures (>200 ms), since UPS installation.
1.3.6.1.4.1.818.1.1.10.10.14ScalarupsMainsStatisticsMRfailread-onlycurrentCount of mains rectifier failures (>200 ms), since UPS installation.
1.3.6.1.4.1.818.1.1.10.10.15ScalarupsMainsStatisticsB2read-onlycurrentCount of transients on the mains bypass (0..2 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.10.10.16ScalarupsMainsStatisticsB5read-onlycurrentCount of transients on the mains bypass (2..5 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.10.10.17ScalarupsMainsStatisticsB10read-onlycurrentCount of transients on the mains bypass (5..10 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.10.10.18ScalarupsMainsStatisticsB200read-onlycurrentCount of transients on the mains bypass (10..200 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.10.10.19ScalarupsMainsStatisticsBypRelread-onlycurrentBypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'.
1.3.6.1.4.1.818.1.1.10.10.20ScalarupsTimegenread-writecurrentThe current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp for…
1.3.6.1.4.1.818.1.1.10.10.21ScalarupsRequestPermissionread-writecurrentAn encrypted code is send to enable use of restricted write objects during a limited period of time.
1.3.6.1.4.1.818.1.1.10.10.22ScalarupsEventGetCoderead-writecurrentThe code which is used as starting point to downloading the events from the UPS event buffer.
1.3.6.1.4.1.818.1.1.10.10.23ScalarupsEventSpinLockread-writecurrentA spin lock on the event subsystem.
1.3.6.1.4.1.818.1.1.10.10.24ScalarupsParameterSpinLockread-writecurrentA spin lock on the parameters subsystem.
1.3.6.1.4.1.818.1.1.10.11NodegeUPSTraps
1.3.6.1.4.1.818.1.1.10.11.1NotificationupsTrapAlarmBatteryBadcurrentOne or more batteries have been determined to require replacement.
1.3.6.1.4.1.818.1.1.10.11.2NotificationupsTrapAlarmOnBatterycurrentThe UPS is drawing power from the batteries.
1.3.6.1.4.1.818.1.1.10.11.3NotificationupsTrapAlarmLowBatterycurrentThe remaining battery run-time is less than or equal to upsConfigLowBattTime.
1.3.6.1.4.1.818.1.1.10.11.4NotificationupsTrapAlarmDepletedBatterycurrentThe UPS will be unable to sustain the present load when and if the utility power is lost)
1.3.6.1.4.1.818.1.1.10.11.5NotificationupsTrapAlarmTempBadcurrentA temperature is out of tolerance.
1.3.6.1.4.1.818.1.1.10.11.6NotificationupsTrapAlarmInputBadcurrentAn input condition is out of tolerance.
1.3.6.1.4.1.818.1.1.10.11.7NotificationupsTrapAlarmOutputBadcurrentAn output condition (other than OutputOverload) is out of tolerance.
1.3.6.1.4.1.818.1.1.10.11.8NotificationupsTrapAlarmOutputOverloadcurrentThe output load exceeds the UPS output capacity.
1.3.6.1.4.1.818.1.1.10.11.9NotificationupsTrapAlarmOnBypasscurrentThe Bypass is presently engaged on the UPS.
1.3.6.1.4.1.818.1.1.10.11.10NotificationupsTrapAlarmBypassBadcurrentThe Bypass is out of tolerance.
1.3.6.1.4.1.818.1.1.10.11.11NotificationupsTrapAlarmOutputOffAsRequestedcurrentThe UPS has shutdown as requested, i.e., the output is off.
1.3.6.1.4.1.818.1.1.10.11.12NotificationupsTrapAlarmUpsOffAsRequestedcurrentThe entire UPS has shutdown as commanded.
1.3.6.1.4.1.818.1.1.10.11.13NotificationupsTrapAlarmChargerFailedcurrentAn uncorrected problem has been detected within the UPS charger subsystem.
1.3.6.1.4.1.818.1.1.10.11.14NotificationupsTrapAlarmUpsOutputOffcurrentThe output of the UPS is in the off state.
1.3.6.1.4.1.818.1.1.10.11.15NotificationupsTrapAlarmUpsSystemOffcurrentThe UPS system is in the off state.
1.3.6.1.4.1.818.1.1.10.11.16NotificationupsTrapAlarmFanFailurecurrentThe failure of one or more fans in the UPS has been detected.
1.3.6.1.4.1.818.1.1.10.11.17NotificationupsTrapAlarmFuseFailurecurrentThe failure of one or more fuses has been detected.
1.3.6.1.4.1.818.1.1.10.11.18NotificationupsTrapAlarmGeneralFaultcurrentA general fault in the UPS has been detected.
1.3.6.1.4.1.818.1.1.10.11.19NotificationupsTrapAlarmDiagnosticTestFailedcurrentThe result of the last diagnostic test indicates a failure.
1.3.6.1.4.1.818.1.1.10.11.20NotificationupsTrapAlarmCommunicationsLostcurrentA problem has been encountered in the communication between the agent and the UPS.
1.3.6.1.4.1.818.1.1.10.11.21NotificationupsTrapAlarmAwaitingPowercurrentThe UPS output is off and the UPS is awaiting the return of the input power (*).
1.3.6.1.4.1.818.1.1.10.11.22NotificationupsTrapAlarmShutdownPendingcurrentA upsShutdownAfterDelay countdown is underway.
1.3.6.1.4.1.818.1.1.10.11.23NotificationupsTrapAlarmShutdownImminentcurrentThe UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.
1.3.6.1.4.1.818.1.1.10.11.24NotificationupsTrapAlarmTestInProgresscurrentA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of …
1.3.6.1.4.1.818.1.1.10.11.25NotificationupsTrapAlarmReceptacleOffcurrentA receptacle has been switched off.
1.3.6.1.4.1.818.1.1.10.11.26NotificationupsTrapAlarmHighspeedBusFailurecurrentA problem on the Highspeed Bus communication is detected.
1.3.6.1.4.1.818.1.1.10.11.27NotificationupsTrapAlarmHighspeedBusJACRCFailurecurrentA CRC failure on the Highspeed Bus JA is detected.
1.3.6.1.4.1.818.1.1.10.11.28NotificationupsTrapAlarmConnectivityBusFailurecurrentA problem on the Connectivity Bus is detected.
1.3.6.1.4.1.818.1.1.10.11.29NotificationupsTrapAlarmHighspeedBusJBCRCFailurecurrentA CRC failure on the Highspeed Bus JB is detected.
1.3.6.1.4.1.818.1.1.10.11.30NotificationupsTrapAlarmCurrentSharingFailurecurrentAn high current sharing on the parallel system is detected.
1.3.6.1.4.1.818.1.1.10.11.31NotificationupsTrapAlarmDCRippleFailurecurrentAn high ripple voltage on his DC link is detected.
1.3.6.1.4.1.818.1.1.10.11.33NotificationupsTrapAlarmBatteryBadRestoredcurrentA Battery bad condition is restored.
1.3.6.1.4.1.818.1.1.10.11.34NotificationupsTrapAlarmOnBatteryRestoredcurrentThe UPS is drawing power from mains again.
1.3.6.1.4.1.818.1.1.10.11.35NotificationupsTrapAlarmLowBatteryRestoredcurrentA Low Battery condition is restored.
1.3.6.1.4.1.818.1.1.10.11.36NotificationupsTrapAlarmDepletedBatteryRestoredcurrentA Depleted Battery condition is restored.
1.3.6.1.4.1.818.1.1.10.11.37NotificationupsTrapAlarmTempBadRestoredcurrentA bad temperature condition is restored.
1.3.6.1.4.1.818.1.1.10.11.38NotificationupsTrapAlarmInputBadRestoredcurrentAn input bad condition is restored.
1.3.6.1.4.1.818.1.1.10.11.39NotificationupsTrapAlarmOutputBadRestoredcurrentAn output bad condition is restored.
1.3.6.1.4.1.818.1.1.10.11.40NotificationupsTrapAlarmOutputOverloadRestoredcurrentAn output overload condition is restored.
1.3.6.1.4.1.818.1.1.10.11.41NotificationupsTrapAlarmOnBypassRestoredcurrentAn On Bypass condition is restored.
1.3.6.1.4.1.818.1.1.10.11.42NotificationupsTrapAlarmBypassBadRestoredcurrentA Bypass bad condition is restored.
1.3.6.1.4.1.818.1.1.10.11.43NotificationupsTrapAlarmOutputOffAsRequestedRestoredcurrentA request shutdown has been restored.
1.3.6.1.4.1.818.1.1.10.11.44NotificationupsTrapAlarmUpsOffAsRequestedRestoredcurrentA entire UPS command has been restored.
1.3.6.1.4.1.818.1.1.10.11.45NotificationupsTrapAlarmChargerFailedRestoredcurrentA Charger Failer condition is restored.
1.3.6.1.4.1.818.1.1.10.11.46NotificationupsTrapAlarmUpsOutputOncurrentThe output of the UPS switched in the on state.
1.3.6.1.4.1.818.1.1.10.11.47NotificationupsTrapAlarmUpsSystemOncurrentThe UPS system is switched in the on state.
1.3.6.1.4.1.818.1.1.10.11.48NotificationupsTrapAlarmFanFailureRestoredcurrentA Fan failure condition is restored.
1.3.6.1.4.1.818.1.1.10.11.49NotificationupsTrapAlarmFuseFailureRestoredcurrentA Fuse failure condition is restored.
1.3.6.1.4.1.818.1.1.10.11.50NotificationupsTrapAlarmGeneralFaultRestoredcurrentA general fault is restored.
1.3.6.1.4.1.818.1.1.10.11.51NotificationupsTrapAlarmDiagnosticTestFailedRestoredcurrentA last diagnostic test indicates a failure is restored.
1.3.6.1.4.1.818.1.1.10.11.52NotificationupsTrapAlarmCommunicationsLostRestoredcurrentA problem in the communication between the agent and the UPS is restored.
1.3.6.1.4.1.818.1.1.10.11.53NotificationupsTrapAlarmAwaitingPowerRestoredcurrentA awaiting power condition is restored (*).
1.3.6.1.4.1.818.1.1.10.11.54NotificationupsTrapAlarmShutdownPendingRestoredcurrentA upsShutdownAfterDelay countdown is restored.
1.3.6.1.4.1.818.1.1.10.11.55NotificationupsTrapAlarmShutdownImminentRestoredcurrentA shutdown imminent condition is restored.
1.3.6.1.4.1.818.1.1.10.11.56NotificationupsTrapAlarmTestInProgressRestoredcurrentThe test is in progress is terminated.
1.3.6.1.4.1.818.1.1.10.11.57NotificationupsTrapAlarmReceptacleOncurrentA receptacle has been switched on.
1.3.6.1.4.1.818.1.1.10.11.58NotificationupsTrapAlarmHighspeedBusRestoredcurrentA problem on the Highspeed Bus communication is restored.
1.3.6.1.4.1.818.1.1.10.11.59NotificationupsTrapAlarmHighspeedBusJACRCRestoredcurrentA CRC failure on the Highspeed Bus JA is restored.
1.3.6.1.4.1.818.1.1.10.11.60NotificationupsTrapAlarmConnectivityBusRestoredcurrentA problem on the Connectivity Bus communication is restored.
1.3.6.1.4.1.818.1.1.10.11.61NotificationupsTrapAlarmHighspeedBusJBCRCRestoredcurrentA CRC failure on the Highspeed Bus JB is restored.
1.3.6.1.4.1.818.1.1.10.11.62NotificationupsTrapAlarmCurrentSharingRestoredcurrentAn high current sharing on the parallel system is restored.
1.3.6.1.4.1.818.1.1.10.11.63NotificationupsTrapAlarmDCRippleRestoredcurrentAn high ripple voltage on his DC link is restored.
1.3.6.1.4.1.818.1.1.10.11.129NotificationupsTrapAlarmValueLowcurrentA measurement value reached a value below its low-level threshold.
1.3.6.1.4.1.818.1.1.10.11.130NotificationupsTrapAlarmValueHighcurrentA measurement value reached a value higher than its high-level threshold.
1.3.6.1.4.1.818.1.1.10.11.133NotificationupsTrapAlarmValueLowRestoredcurrentA ValueLow alarm condition is restored.
1.3.6.1.4.1.818.1.1.10.11.134NotificationupsTrapAlarmValueHighRestoredcurrentA ValueHigh alarm condition is restored.
1.3.6.1.4.1.818.1.1.10.12NodeupsDiagnostic
1.3.6.1.4.1.818.1.1.10.12.1ScalarupsDiagnosticBusJACommunicationStatusread-onlycurrentBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA …
1.3.6.1.4.1.818.1.1.10.12.2ScalarupsDiagnosticBusJBCommunicationStatusread-onlycurrentBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA …
1.3.6.1.4.1.818.1.1.10.12.3ScalarupsDiagnosticBatteryLifetimeread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.10.12.4ScalarupsDiagnosticFansLifetimeread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.10.12.5ScalarupsDiagnosticDCcapacitorsLifetimeread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.10.12.6ScalarupsDiagnosticACcapacitorsLifetimeread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.10.12.7ScalarupsDiagnosticGlobalServiceCheckread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.11NodegeFirstUPS
1.3.6.1.4.1.818.1.1.11.1NodeupsIdentfirst
1.3.6.1.4.1.818.1.1.11.1.1ScalarupsIdentManufacturerfirstread-onlycurrentThe name of the UPS manufacturer.(*)
1.3.6.1.4.1.818.1.1.11.1.2ScalarupsIdentModelfirstread-onlycurrentThe UPS Model designation.(*)
1.3.6.1.4.1.818.1.1.11.1.3ScalarupsIdentUPSSoftwareVersionfirstread-onlycurrentThe UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*)
1.3.6.1.4.1.818.1.1.11.1.4ScalarupsIdentAgentSoftwareVersionfirstread-onlycurrentThe UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*)
1.3.6.1.4.1.818.1.1.11.1.5ScalarupsIdentNamefirstread-writecurrentA string identifying the UPS. This object should be set by the administrator.(*)
1.3.6.1.4.1.818.1.1.11.1.6ScalarupsIdentAttachedDevicesfirstread-writecurrentA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*)
1.3.6.1.4.1.818.1.1.11.1.7ScalarupsIdentUPSSerialNumberfirstread-onlycurrentThe UPS serial number
1.3.6.1.4.1.818.1.1.11.1.8ScalarupsIdentComProtVersionfirstread-onlycurrentThe IMV communication protocol version
1.3.6.1.4.1.818.1.1.11.1.9ScalarupsIdentOperatingTimefirstread-onlycurrentThe present value of the operating time. total 'on' time since UPS manufactured
1.3.6.1.4.1.818.1.1.11.2NodeupsBatteryfirst
1.3.6.1.4.1.818.1.1.11.2.1ScalarupsBatteryStatusfirstread-onlycurrentThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfi…
1.3.6.1.4.1.818.1.1.11.2.2ScalarupsSecondsOnBatteryfirstread-onlycurrentIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res…
1.3.6.1.4.1.818.1.1.11.2.3ScalarupsEstimatedMinutesRemainingfirstread-onlycurrentAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and…
1.3.6.1.4.1.818.1.1.11.2.4ScalarupsEstimatedChargeRemainingfirstread-onlycurrentAn estimate of the battery charge remaining expressed as a percent of full charge.(*)
1.3.6.1.4.1.818.1.1.11.2.5ScalarupsBatteryVoltagefirstread-onlycurrentThe magnitude of the present battery voltage.(*)
1.3.6.1.4.1.818.1.1.11.2.6ScalarupsBatteryCurrentfirstread-onlycurrentThe present battery current.(*)
1.3.6.1.4.1.818.1.1.11.2.7ScalarupsBatteryTemperaturefirstread-onlycurrentThe ambient temperature at or near the UPS Battery casing.(*)
1.3.6.1.4.1.818.1.1.11.2.8ScalarupsBatteryRipplefirstread-onlycurrentThe present DC link RMS voltage ripple.(*)
1.3.6.1.4.1.818.1.1.11.3NodeupsInputfirst
1.3.6.1.4.1.818.1.1.11.3.1ScalarupsInputLineBadsfirstread-onlycurrentA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the i…
1.3.6.1.4.1.818.1.1.11.3.2ScalarupsInputNumLinesfirstread-onlycurrentThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*)
1.3.6.1.4.1.818.1.1.11.3.3TableupsInputFirstTablenot-accessiblecurrentA list of input table entries. The number of entries is given by the value of upsInputNumLines.(*)
1.3.6.1.4.1.818.1.1.11.3.3.1RowupsInputFirstEntrynot-accessiblecurrentAn entry containing information applicable to a particular input line.(*)
1.3.6.1.4.1.818.1.1.11.3.3.1.1ColumnupsInputLineIndexfirstnot-accessiblecurrentThe input line identifier.(*)
1.3.6.1.4.1.818.1.1.11.3.3.1.2ColumnupsInputFrequencyfirstread-onlycurrentThe present input frequency.(*)
1.3.6.1.4.1.818.1.1.11.3.3.1.3ColumnupsInputVoltagefirstread-onlycurrentThe magnitude of the present input voltage.(*)
1.3.6.1.4.1.818.1.1.11.3.3.1.4ColumnupsInputCurrentfirstread-onlycurrentThe magnitude of the present input current.(*)
1.3.6.1.4.1.818.1.1.11.3.3.1.5ColumnupsInputTruePowerfirstread-onlycurrentThe magnitude of the present input true power.(*)
1.3.6.1.4.1.818.1.1.11.3.3.1.6ColumnupsInputVoltageMinfirstread-onlycurrentThe lowest magnitude of the input voltage since last read out.
1.3.6.1.4.1.818.1.1.11.3.3.1.7ColumnupsInputVoltageMaxfirstread-onlycurrentThe highest magnitude of the input voltage since last read out.
1.3.6.1.4.1.818.1.1.11.4NodeupsOutputfirst
1.3.6.1.4.1.818.1.1.11.4.1ScalarupsOutputSourcefirstread-onlycurrentThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the…
1.3.6.1.4.1.818.1.1.11.4.2ScalarupsOutputFrequencyfirstread-onlycurrentThe present output frequency.(*)
1.3.6.1.4.1.818.1.1.11.4.3ScalarupsOutputNumLinesfirstread-onlycurrentThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*)
1.3.6.1.4.1.818.1.1.11.4.4TableupsOutputFirstTablenot-accessiblecurrentA list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*)
1.3.6.1.4.1.818.1.1.11.4.4.1RowupsOutputFirstEntrynot-accessiblecurrentAn entry containing information applicable to a particular output line.(*)
1.3.6.1.4.1.818.1.1.11.4.4.1.1ColumnupsOutputLineIndexfirstnot-accessiblecurrentThe output line identifier.(*)
1.3.6.1.4.1.818.1.1.11.4.4.1.2ColumnupsOutputVoltagefirstread-onlycurrentThe present output voltage.(*)
1.3.6.1.4.1.818.1.1.11.4.4.1.3ColumnupsOutputCurrentfirstread-onlycurrentThe present output current.(*)
1.3.6.1.4.1.818.1.1.11.4.4.1.4ColumnupsOutputPowerfirstread-onlycurrentThe present output true power.(*)
1.3.6.1.4.1.818.1.1.11.4.4.1.5ColumnupsOutputPercentLoadfirstread-onlycurrentThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent…
1.3.6.1.4.1.818.1.1.11.4.4.1.6ColumnupsOutputPowerFactorfirstread-onlycurrentThe present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate …
1.3.6.1.4.1.818.1.1.11.4.4.1.7ColumnupsOutputPeakCurrentfirstread-onlycurrentThe present output peak current.(*)
1.3.6.1.4.1.818.1.1.11.4.4.1.8ColumnupsOutputShareCurrentfirstread-onlycurrentIn a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share…
1.3.6.1.4.1.818.1.1.11.5NodeupsBypassfirst
1.3.6.1.4.1.818.1.1.11.5.1ScalarupsBypassFrequencyfirstread-onlycurrentThe present bypass frequency.(*)
1.3.6.1.4.1.818.1.1.11.5.2ScalarupsBypassNumLinesfirstread-onlycurrentThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*)
1.3.6.1.4.1.818.1.1.11.5.3TableupsBypassFirstTablenot-accessiblecurrentA list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*)
1.3.6.1.4.1.818.1.1.11.5.3.1RowupsBypassFirstEntrynot-accessiblecurrentAn entry containing information applicable to a particular bypass input.(*)
1.3.6.1.4.1.818.1.1.11.5.3.1.1ColumnupsBypassLineIndexfirstnot-accessiblecurrentThe bypass line identifier.(*)
1.3.6.1.4.1.818.1.1.11.5.3.1.2ColumnupsBypassVoltagefirstread-onlycurrentThe present bypass voltage.(*)
1.3.6.1.4.1.818.1.1.11.5.3.1.3ColumnupsBypassCurrentfirstread-onlycurrentThe present bypass current.(*)
1.3.6.1.4.1.818.1.1.11.5.3.1.4ColumnupsBypassPowerfirstread-onlycurrentThe present true power conveyed by the bypass.(*)
1.3.6.1.4.1.818.1.1.11.6NodeupsAlarmfirst
1.3.6.1.4.1.818.1.1.11.6.1ScalarupsAlarmsPresentfirstread-onlycurrentThe present number of active alarm conditions.(*)
1.3.6.1.4.1.818.1.1.11.6.2TableupsAlarmFirstTablenot-accessiblecurrentA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is …
1.3.6.1.4.1.818.1.1.11.6.2.1RowupsAlarmFirstEntrynot-accessiblecurrentAn entry containing information applicable to a particular alarm.(*)
1.3.6.1.4.1.818.1.1.11.6.2.1.1ColumnupsAlarmIdfirstnot-accessiblecurrentA unique identifier for an alarm condition. This value must remain constant.(*)
1.3.6.1.4.1.818.1.1.11.6.2.1.2ColumnupsAlarmDescrfirstread-onlycurrentA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con…
1.3.6.1.4.1.818.1.1.11.6.2.1.3ColumnupsAlarmTimefirstread-onlycurrentThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before ag…
1.3.6.1.4.1.818.1.1.11.6.3NodeupsWellKnownAlarmsfirst
1.3.6.1.4.1.818.1.1.11.6.3.1IdentityupsAlarmBatteryBadfirstcurrentOne or more batteries have been determined to require replacement.(*)
1.3.6.1.4.1.818.1.1.11.6.3.2IdentityupsAlarmOnBatteryfirstcurrentThe UPS is drawing power from the batteries.(*)
1.3.6.1.4.1.818.1.1.11.6.3.3IdentityupsAlarmLowBatteryfirstcurrentThe remaining battery run-time is less than or equal to upsConfigLowBattTime.(*)
1.3.6.1.4.1.818.1.1.11.6.3.4IdentityupsAlarmDepletedBatteryfirstcurrentThe UPS will be unable to sustain the present load when and if the utility power is lost.(*)
1.3.6.1.4.1.818.1.1.11.6.3.5IdentityupsAlarmTempBadfirstcurrentA temperature is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.11.6.3.6IdentityupsAlarmInputBadfirstcurrentAn input condition is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.11.6.3.7IdentityupsAlarmOutputBadfirstcurrentAn output condition (other than OutputOverload) is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.11.6.3.8IdentityupsAlarmOutputOverloadfirstcurrentThe output load exceeds the UPS output capacity.(*)
1.3.6.1.4.1.818.1.1.11.6.3.9IdentityupsAlarmOnBypassfirstcurrentThe Bypass is presently engaged on the UPS.(*)
1.3.6.1.4.1.818.1.1.11.6.3.10IdentityupsAlarmBypassBadfirstcurrentThe Bypass is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.11.6.3.11IdentityupsAlarmOutputOffAsRequestedfirstcurrentThe UPS has shutdown as requested, i.e., the output is off.(*)
1.3.6.1.4.1.818.1.1.11.6.3.12IdentityupsAlarmUpsOffAsRequestedfirstcurrentThe entire UPS has shutdown as commanded.(*)
1.3.6.1.4.1.818.1.1.11.6.3.13IdentityupsAlarmChargerFailedfirstcurrentAn uncorrected problem has been detected within the UPS charger subsystem.(*)
1.3.6.1.4.1.818.1.1.11.6.3.14IdentityupsAlarmUpsOutputOfffirstcurrentThe output of the UPS is in the off state.(*)
1.3.6.1.4.1.818.1.1.11.6.3.15IdentityupsAlarmUpsSystemOfffirstcurrentThe UPS system is in the off state.(*)
1.3.6.1.4.1.818.1.1.11.6.3.16IdentityupsAlarmFanFailurefirstcurrentThe failure of one or more fans in the UPS has been detected.(*)
1.3.6.1.4.1.818.1.1.11.6.3.17IdentityupsAlarmFuseFailurefirstcurrentThe failure of one or more fuses has been detected.(*)
1.3.6.1.4.1.818.1.1.11.6.3.18IdentityupsAlarmGeneralFaultfirstcurrentA general fault in the UPS has been detected.(*)
1.3.6.1.4.1.818.1.1.11.6.3.19IdentityupsAlarmDiagnosticTestFailedfirstcurrentThe result of the last diagnostic test indicates a failure.(*)
1.3.6.1.4.1.818.1.1.11.6.3.20IdentityupsAlarmCommunicationsLostfirstcurrentA problem has been encountered in the communications between the agent and the UPS.(*)
1.3.6.1.4.1.818.1.1.11.6.3.21IdentityupsAlarmAwaitingPowerfirstcurrentThe UPS output is off and the UPS is awaiting the return of input power.(*)
1.3.6.1.4.1.818.1.1.11.6.3.22IdentityupsAlarmShutdownPendingfirstcurrentA upsShutdownAfterDelay countdown is underway.(*)
1.3.6.1.4.1.818.1.1.11.6.3.23IdentityupsAlarmShutdownImminentfirstcurrentThe UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.(*)
1.3.6.1.4.1.818.1.1.11.6.3.24IdentityupsAlarmTestInProgressfirstcurrentA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of …
1.3.6.1.4.1.818.1.1.11.6.3.25IdentityupsAlarmReceptacleOfffirstcurrentThe receptacle are switch off
1.3.6.1.4.1.818.1.1.11.6.3.26IdentityupsAlarmHighSpeedBusFailurefirstcurrentA problem on the High Speed Bus communication is detected
1.3.6.1.4.1.818.1.1.11.6.3.27IdentityupsAlarmHighSpeedBusJACRCFailurefirstcurrentA CRC failure on High Speed Bus JA is detected.
1.3.6.1.4.1.818.1.1.11.6.3.28IdentityupsAlarmConnectivityBusFailurefirstcurrentA problem on the Connectivity Bus communication is detected.
1.3.6.1.4.1.818.1.1.11.6.3.29IdentityupsAlarmHighSpeedBusJBCRCFailurefirstcurrentA CRC failure on High Speed Bus JB is detected.
1.3.6.1.4.1.818.1.1.11.6.3.30IdentityupsAlarmCurrentSharingfirstcurrentThe UPS detects an high current sharing on the parallel system.
1.3.6.1.4.1.818.1.1.11.6.3.31IdentityupsAlarmDCRipplefirstcurrentThe UPS detects an high ripple voltage on his DC link.
1.3.6.1.4.1.818.1.1.11.6.4ScalarupsAlarmMaskAfirstread-onlycurrentSpecifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' com…
1.3.6.1.4.1.818.1.1.11.7NodeupsTestfirst
1.3.6.1.4.1.818.1.1.11.7.1ScalarupsTestIdfirstread-writecurrentThe test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this docu…
1.3.6.1.4.1.818.1.1.11.7.2ScalarupsTestSpinLockfirstread-writecurrentA spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress a…
1.3.6.1.4.1.818.1.1.11.7.3ScalarupsTestResultsSummaryfirstread-onlycurrentThe results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test complete…
1.3.6.1.4.1.818.1.1.11.7.4ScalarupsTestResultsDetailfirstread-onlycurrentAdditional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*)
1.3.6.1.4.1.818.1.1.11.7.5ScalarupsTestStartTimefirstread-onlycurrentThe value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of…
1.3.6.1.4.1.818.1.1.11.7.6ScalarupsTestElapsedTimefirstread-onlycurrentThe amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of …
1.3.6.1.4.1.818.1.1.11.7.7NodeupsWellKnownTestsfirst
1.3.6.1.4.1.818.1.1.11.7.7.1IdentityupsTestNoTestsInitiatedfirstcurrentNo tests have been initiated and no test is in progress.(*)
1.3.6.1.4.1.818.1.1.11.7.7.2IdentityupsTestAbortTestInProgressfirstcurrentThe test in progress is to be aborted / the test in progress was aborted.(*)
1.3.6.1.4.1.818.1.1.11.7.7.3IdentityupsTestGeneralSystemsTestfirstcurrentThe manufacturer's standard test of UPS device systems.(*)
1.3.6.1.4.1.818.1.1.11.7.7.4IdentityupsTestQuickBatteryTestfirstcurrentA test that is sufficient to determine if the battery needs replacement.(*)
1.3.6.1.4.1.818.1.1.11.7.7.5IdentityupsTestDeepBatteryCalibrationfirstcurrentThe system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high deg…
1.3.6.1.4.1.818.1.1.11.8NodeupsControlfirst
1.3.6.1.4.1.818.1.1.11.8.1ScalarupsShutdownTypefirstread-writecurrentThis object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reach…
1.3.6.1.4.1.818.1.1.11.8.2ScalarupsShutdownAfterDelayfirstread-writecurrentSetting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdo…
1.3.6.1.4.1.818.1.1.11.8.3ScalarupsStartupAfterDelayfirstread-writecurrentSetting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause …
1.3.6.1.4.1.818.1.1.11.8.4ScalarupsRebootWithDurationfirstread-writecurrentSetting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the ti…
1.3.6.1.4.1.818.1.1.11.8.5ScalarupsAutoRestartfirstread-writecurrentSetting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutd…
1.3.6.1.4.1.818.1.1.11.8.6ScalarupsReceptaclesNumfirstread-onlycurrentThe number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table.
1.3.6.1.4.1.818.1.1.11.8.7TableupsReceptacleFirstTablenot-accessiblecurrentA list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum.
1.3.6.1.4.1.818.1.1.11.8.7.1RowupsReceptacleFirstEntrynot-accessiblecurrentAn entry containing information applicable to a particular receptacle.
1.3.6.1.4.1.818.1.1.11.8.7.1.1ColumnupsReceptacleLineIndexfirstnot-accessiblecurrentThe receptacle line identifier.
1.3.6.1.4.1.818.1.1.11.8.7.1.2ColumnupsReceptacleOnOfffirstread-writecurrentThe present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptac…
1.3.6.1.4.1.818.1.1.11.8.8ScalarupsUPSModefirstread-writecurrentThe operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transfor…
1.3.6.1.4.1.818.1.1.11.8.9ScalarupsRectifierOnOfffirstread-writecurrentThe present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier …
1.3.6.1.4.1.818.1.1.11.8.10ScalarupsBatteryChargeMethodfirstread-writecurrentThe present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this objec…
1.3.6.1.4.1.818.1.1.11.8.11ScalarupsInverterOnOfffirstread-writecurrentThe present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off…
1.3.6.1.4.1.818.1.1.11.8.12ScalarupsBypassOnOfffirstread-writecurrentThe present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If…
1.3.6.1.4.1.818.1.1.11.8.13ScalarupsLoadSourcefirstread-writecurrentThe present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will …
1.3.6.1.4.1.818.1.1.11.9NodeupsConfigfirst
1.3.6.1.4.1.818.1.1.11.9.1ScalarupsConfigInputVoltagefirstread-writecurrentThe magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a v…
1.3.6.1.4.1.818.1.1.11.9.2ScalarupsConfigInputFreqfirstread-writecurrentThe nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is no…
1.3.6.1.4.1.818.1.1.11.9.3ScalarupsConfigOutputVoltagefirstread-writecurrentThe magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a …
1.3.6.1.4.1.818.1.1.11.9.4ScalarupsConfigOutputFreqfirstread-writecurrentThe nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is n…
1.3.6.1.4.1.818.1.1.11.9.5ScalarupsConfigOutputVAfirstread-onlycurrentThe magnitude of the nominal Volt-Amp rating.(*)
1.3.6.1.4.1.818.1.1.11.9.6ScalarupsConfigOutputPowerfirstread-onlycurrentThe magnitude of the nominal true power rating.(*)
1.3.6.1.4.1.818.1.1.11.9.7ScalarupsConfigLowBattTimefirstread-writecurrentThe value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the …
1.3.6.1.4.1.818.1.1.11.9.8ScalarupsConfigAudibleStatusfirstread-writecurrentThe requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this …
1.3.6.1.4.1.818.1.1.11.9.9ScalarupsConfigLowVoltageTransferPointfirstread-writecurrentThe minimum input line voltage allowed before the UPS system transfers to battery backup.(*)
1.3.6.1.4.1.818.1.1.11.9.10ScalarupsConfigHighVoltageTransferPointfirstread-writecurrentThe maximum line voltage allowed before the UPS system transfers to battery backup.(*)
1.3.6.1.4.1.818.1.1.11.9.11ScalarupsConfigBatteryCapacityfirstread-writecurrentThe installed battery capacity. This value is the 'factory'-value, not the value after calibration.
1.3.6.1.4.1.818.1.1.11.9.12ScalarupsConfigBatteryChargeCurrentfirstread-writecurrentThe maximum battery charge current, including external chargers.
1.3.6.1.4.1.818.1.1.11.9.13ScalarupsConfigNoLoadShutdownfirstread-writecurrentDis- or enable 'no load' shutdown from the contact interface.
1.3.6.1.4.1.818.1.1.11.9.14ScalarupsConfigStartDelayfirstread-writecurrentMinimum required autonomy time before the UPS may perform an autorestart.
1.3.6.1.4.1.818.1.1.11.10NodeupsGetSetfirst
1.3.6.1.4.1.818.1.1.11.10.1ScalarupsEventGetNextfirstread-writecurrentThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The val…
1.3.6.1.4.1.818.1.1.11.10.2ScalarupsEventGetPreviousfirstread-writecurrentThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The val…
1.3.6.1.4.1.818.1.1.11.10.3ScalarupsEventSetStartingTimeStampfirstread-writecurrentThe timestamp which is used as starting point for downloading events from the UPS event buffer
1.3.6.1.4.1.818.1.1.11.10.4ScalarupsEventRetreiveCurrentTimeStampfirstread-onlycurrentThe current timestamp is retreived from the UPS
1.3.6.1.4.1.818.1.1.11.10.5ScalarupsEventTableSizefirstread-onlycurrentThe number of entries in the event table. This object indicates the number of rows in the event table.
1.3.6.1.4.1.818.1.1.11.10.6TableupsEventFirstTablenot-accessiblecurrentA list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the…
1.3.6.1.4.1.818.1.1.11.10.6.1RowupsEventFirstEntrynot-accessiblecurrentAn entry containing information applicable to a particular event.
1.3.6.1.4.1.818.1.1.11.10.6.1.1ColumnupsEventLineIndexfirstnot-accessiblecurrentThe event line identifier.
1.3.6.1.4.1.818.1.1.11.10.6.1.2ColumnupsEventCodefirstread-onlycurrentThe event code in numerical format.
1.3.6.1.4.1.818.1.1.11.10.6.1.3ColumnupsEventStatusfirstread-onlycurrentThe status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status …
1.3.6.1.4.1.818.1.1.11.10.6.1.4ColumnupsEventTimefirstread-onlycurrentThe timestamp of the moment the event was generated.
1.3.6.1.4.1.818.1.1.11.10.7ScalarupsParametersReadfirstread-writecurrentThe number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value up…
1.3.6.1.4.1.818.1.1.11.10.8ScalarupsParametersWritefirstread-writecurrentThe number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be u…
1.3.6.1.4.1.818.1.1.11.10.9ScalarupsParametersStartAddressfirstread-writecurrentThe address which is used as starting point for downloading parameters from the UPS
1.3.6.1.4.1.818.1.1.11.10.10ScalarupsParameterTableSizefirstread-onlycurrentThe number of entries in the parameter table. This object indicates the number of rows in the parameter table.
1.3.6.1.4.1.818.1.1.11.10.11TableupsParameterFirstTablenot-accessiblecurrentA list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of t…
1.3.6.1.4.1.818.1.1.11.10.11.1RowupsParameterFirstEntrynot-accessiblecurrentAn entry containing information applicable to a particular parameter.
1.3.6.1.4.1.818.1.1.11.10.11.1.1ColumnupsParameterLineIndexfirstnot-accessiblecurrentThe parameter line identifier.
1.3.6.1.4.1.818.1.1.11.10.11.1.2ColumnupsParameterValuefirstread-writecurrentThe parameter value in numerical format.
1.3.6.1.4.1.818.1.1.11.10.12ScalarupsStatusfirstread-onlycurrentThe global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other comman…
1.3.6.1.4.1.818.1.1.11.10.13ScalarupsMainsStatisticsMBfailfirstread-onlycurrentCount of main bypass failures (>200 ms), since UPS installation.
1.3.6.1.4.1.818.1.1.11.10.14ScalarupsMainsStatisticsMRfailfirstread-onlycurrentCount of mains rectifier failures (>200 ms), since UPS installation.
1.3.6.1.4.1.818.1.1.11.10.15ScalarupsMainsStatisticsB2firstread-onlycurrentCount of transients on the mains bypass (0..2 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.11.10.16ScalarupsMainsStatisticsB5firstread-onlycurrentCount of transients on the mains bypass (2..5 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.11.10.17ScalarupsMainsStatisticsB10firstread-onlycurrentCount of transients on the mains bypass (5..10 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.11.10.18ScalarupsMainsStatisticsB200firstread-onlycurrentCount of transients on the mains bypass (10..200 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.11.10.19ScalarupsMainsStatisticsBypRelfirstread-onlycurrentBypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'.
1.3.6.1.4.1.818.1.1.11.10.20ScalarupsTimefirstread-writecurrentThe current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp for…
1.3.6.1.4.1.818.1.1.11.10.21ScalarupsRequestPermissionfirstread-writecurrentAn encrypted code is send to enable use of restricted write objects during a limited period of time.
1.3.6.1.4.1.818.1.1.11.10.22ScalarupsEventGetCodefirstread-writecurrentThe code which is used as starting point to downloading the events from the UPS event buffer.
1.3.6.1.4.1.818.1.1.11.10.23ScalarupsEventSpinLockfirstread-writecurrentA spin lock on the event subsystem.
1.3.6.1.4.1.818.1.1.11.10.24ScalarupsParameterSpinLockfirstread-writecurrentA spin lock on the parameters subsystem.
1.3.6.1.4.1.818.1.1.11.11NodegeUPSTrapsfirst
1.3.6.1.4.1.818.1.1.11.11.1NotificationupsTrapAlarmBatteryBadfirstcurrentOne or more batteries have been determined to require replacement.
1.3.6.1.4.1.818.1.1.11.11.2NotificationupsTrapAlarmOnBatteryfirstcurrentThe UPS is drawing power from the batteries.
1.3.6.1.4.1.818.1.1.11.11.3NotificationupsTrapAlarmLowBatteryfirstcurrentThe remaining battery run-time is less than or equal to upsConfigLowBattTime.
1.3.6.1.4.1.818.1.1.11.11.4NotificationupsTrapAlarmDepletedBatteryfirstcurrentThe UPS will be unable to sustain the present load when and if the utility power is lost)
1.3.6.1.4.1.818.1.1.11.11.5NotificationupsTrapAlarmTempBadfirstcurrentA temperature is out of tolerance.
1.3.6.1.4.1.818.1.1.11.11.6NotificationupsTrapAlarmInputBadfirstcurrentAn input condition is out of tolerance.
1.3.6.1.4.1.818.1.1.11.11.7NotificationupsTrapAlarmOutputBadfirstcurrentAn output condition (other than OutputOverload) is out of tolerance.
1.3.6.1.4.1.818.1.1.11.11.8NotificationupsTrapAlarmOutputOverloadfirstcurrentThe output load exceeds the UPS output capacity.
1.3.6.1.4.1.818.1.1.11.11.9NotificationupsTrapAlarmOnBypassfirstcurrentThe Bypass is presently engaged on the UPS.
1.3.6.1.4.1.818.1.1.11.11.10NotificationupsTrapAlarmBypassBadfirstcurrentThe Bypass is out of tolerance.
1.3.6.1.4.1.818.1.1.11.11.11NotificationupsTrapAlarmOutputOffAsRequestedfirstcurrentThe UPS has shutdown as requested, i.e., the output is off.
1.3.6.1.4.1.818.1.1.11.11.12NotificationupsTrapAlarmUpsOffAsRequestedfirstcurrentThe entire UPS has shutdown as commanded.
1.3.6.1.4.1.818.1.1.11.11.13NotificationupsTrapAlarmChargerFailedfirstcurrentAn uncorrected problem has been detected within the UPS charger subsystem.
1.3.6.1.4.1.818.1.1.11.11.14NotificationupsTrapAlarmUpsOutputOfffirstcurrentThe output of the UPS is in the off state.
1.3.6.1.4.1.818.1.1.11.11.15NotificationupsTrapAlarmUpsSystemOfffirstcurrentThe UPS system is in the off state.
1.3.6.1.4.1.818.1.1.11.11.16NotificationupsTrapAlarmFanFailurefirstcurrentThe failure of one or more fans in the UPS has been detected.
1.3.6.1.4.1.818.1.1.11.11.17NotificationupsTrapAlarmFuseFailurefirstcurrentThe failure of one or more fuses has been detected.
1.3.6.1.4.1.818.1.1.11.11.18NotificationupsTrapAlarmGeneralFaultfirstcurrentA general fault in the UPS has been detected.
1.3.6.1.4.1.818.1.1.11.11.19NotificationupsTrapAlarmDiagnosticTestFailedfirstcurrentThe result of the last diagnostic test indicates a failure.
1.3.6.1.4.1.818.1.1.11.11.20NotificationupsTrapAlarmCommunicationsLostfirstcurrentA problem has been encountered in the communication between the agent and the UPS.
1.3.6.1.4.1.818.1.1.11.11.21NotificationupsTrapAlarmAwaitingPowerfirstcurrentThe UPS output is off and the UPS is awaiting the return of the input power (*).
1.3.6.1.4.1.818.1.1.11.11.22NotificationupsTrapAlarmShutdownPendingfirstcurrentA upsShutdownAfterDelay countdown is underway.
1.3.6.1.4.1.818.1.1.11.11.23NotificationupsTrapAlarmShutdownImminentfirstcurrentThe UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.
1.3.6.1.4.1.818.1.1.11.11.24NotificationupsTrapAlarmTestInProgressfirstcurrentA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of …
1.3.6.1.4.1.818.1.1.11.11.25NotificationupsTrapAlarmReceptacleOfffirstcurrentA receptacle has been switched off.
1.3.6.1.4.1.818.1.1.11.11.26NotificationupsTrapAlarmHighspeedBusFailurefirstcurrentA problem on the Highspeed Bus communication is detected.
1.3.6.1.4.1.818.1.1.11.11.27NotificationupsTrapAlarmHighspeedBusJACRCFailurefirstcurrentA CRC failure on the Highspeed Bus JB is detected.
1.3.6.1.4.1.818.1.1.11.11.28NotificationupsTrapAlarmConnectivityBusFailurefirstcurrentA problem on the Connectivity Bus communication is detected
1.3.6.1.4.1.818.1.1.11.11.29NotificationupsTrapAlarmHighspeedBusJBCRCFailurefirstcurrentA CRC failure on the Highspeed Bus JB is detected.
1.3.6.1.4.1.818.1.1.11.11.30NotificationupsTrapAlarmCurrentSharingFailurefirstcurrentAn high current sharing on the parallel system is detected.
1.3.6.1.4.1.818.1.1.11.11.31NotificationupsTrapAlarmDCRippleFailurefirstcurrentAn high ripple voltage on his DC link is detected.
1.3.6.1.4.1.818.1.1.11.11.33NotificationupsTrapAlarmBatteryBadRestoredfirstcurrentA Battery bad condition is restored.
1.3.6.1.4.1.818.1.1.11.11.34NotificationupsTrapAlarmOnBatteryRestoredfirstcurrentThe UPS is drawing power from mains again.
1.3.6.1.4.1.818.1.1.11.11.35NotificationupsTrapAlarmLowBatteryRestoredfirstcurrentA Low Battery condition is restored.
1.3.6.1.4.1.818.1.1.11.11.36NotificationupsTrapAlarmDepletedBatteryRestoredfirstcurrentA Depleted Battery condition is restored.
1.3.6.1.4.1.818.1.1.11.11.37NotificationupsTrapAlarmTempBadRestoredfirstcurrentA bad temperature condition is restored.
1.3.6.1.4.1.818.1.1.11.11.38NotificationupsTrapAlarmInputBadRestoredfirstcurrentAn input bad condition is restored.
1.3.6.1.4.1.818.1.1.11.11.39NotificationupsTrapAlarmOutputBadRestoredfirstcurrentAn output bad condition is restored.
1.3.6.1.4.1.818.1.1.11.11.40NotificationupsTrapAlarmOutputOverloadRestoredfirstcurrentAn output overload condition is restored.
1.3.6.1.4.1.818.1.1.11.11.41NotificationupsTrapAlarmOnBypassRestoredfirstcurrentAn On Bypass condition is restored.
1.3.6.1.4.1.818.1.1.11.11.42NotificationupsTrapAlarmBypassBadRestoredfirstcurrentA Bypass bad condition is restored.
1.3.6.1.4.1.818.1.1.11.11.43NotificationupsTrapAlarmOutputOffAsRequestedRestoredfirstcurrentA request shutdown has been restored.
1.3.6.1.4.1.818.1.1.11.11.44NotificationupsTrapAlarmUpsOffAsRequestedRestoredfirstcurrentA entire UPS command has been restored.
1.3.6.1.4.1.818.1.1.11.11.45NotificationupsTrapAlarmChargerFailedRestoredfirstcurrentA Charger Failer condition is restored.
1.3.6.1.4.1.818.1.1.11.11.46NotificationupsTrapAlarmUpsOutputOnfirstcurrentThe output of the UPS switched in the on state.
1.3.6.1.4.1.818.1.1.11.11.47NotificationupsTrapAlarmUpsSystemOnfirstcurrentThe UPS system is switched in the on state.
1.3.6.1.4.1.818.1.1.11.11.48NotificationupsTrapAlarmFanFailureRestoredfirstcurrentA Fan failure condition is restored.
1.3.6.1.4.1.818.1.1.11.11.49NotificationupsTrapAlarmFuseFailureRestoredfirstcurrentA Fuse failure condition is restored.
1.3.6.1.4.1.818.1.1.11.11.50NotificationupsTrapAlarmGeneralFaultRestoredfirstcurrentA general fault is restored.
1.3.6.1.4.1.818.1.1.11.11.51NotificationupsTrapAlarmDiagnosticTestFailedRestoredfirstcurrentA last diagnostic test indicates a failure is restored.
1.3.6.1.4.1.818.1.1.11.11.52NotificationupsTrapAlarmCommunicationsLostRestoredfirstcurrentA problem in the communication between the agent and the UPS is restored.
1.3.6.1.4.1.818.1.1.11.11.53NotificationupsTrapAlarmAwaitingPowerRestoredfirstcurrentA awaiting power condition is restored (*).
1.3.6.1.4.1.818.1.1.11.11.54NotificationupsTrapAlarmShutdownPendingRestoredfirstcurrentA upsShutdownAfterDelay countdown is restored.
1.3.6.1.4.1.818.1.1.11.11.55NotificationupsTrapAlarmShutdownImminentRestoredfirstcurrentA shutdown imminent condition is restored.
1.3.6.1.4.1.818.1.1.11.11.56NotificationupsTrapAlarmTestInProgressRestoredfirstcurrentThe test is in progress is terminated.
1.3.6.1.4.1.818.1.1.11.11.57NotificationupsTrapAlarmReceptacleOnfirstcurrentA receptacle has been switched on.
1.3.6.1.4.1.818.1.1.11.11.58NotificationupsTrapAlarmHighspeedBusRestoredfirstcurrentA problem on the Highspeed Bus communication is restored.
1.3.6.1.4.1.818.1.1.11.11.59NotificationupsTrapAlarmHighspeedBusJACRCRestoredfirstcurrentA CRC failure on the Highspeed Bus JA is restored.
1.3.6.1.4.1.818.1.1.11.11.60NotificationupsTrapAlarmConnectivityBusRestoredfirstcurrentA problem on the Connectivity Bus communication is restored.
1.3.6.1.4.1.818.1.1.11.11.61NotificationupsTrapAlarmHighspeedBusJBCRCRestoredfirstcurrentA CRC failure on the Highspeed Bus JB is restored.
1.3.6.1.4.1.818.1.1.11.11.62NotificationupsTrapAlarmCurrentSharingRestoredfirstcurrentAn high current sharing on the parallel system is restored.
1.3.6.1.4.1.818.1.1.11.11.63NotificationupsTrapAlarmDCRippleRestoredfirstcurrentAn high ripple voltage on his DC link is restored.
1.3.6.1.4.1.818.1.1.11.11.129NotificationupsTrapAlarmValueLowfirstcurrentA measurement value reached a value below its low-level threshold.
1.3.6.1.4.1.818.1.1.11.11.130NotificationupsTrapAlarmValueHighfirstcurrentA measurement value reached a value higher than its high-level threshold.
1.3.6.1.4.1.818.1.1.11.11.133NotificationupsTrapAlarmValueLowRestoredfirstcurrentA ValueLow alarm condition is restored.
1.3.6.1.4.1.818.1.1.11.11.134NotificationupsTrapAlarmValueHighRestoredfirstcurrentA ValueHigh alarm condition is restored.
1.3.6.1.4.1.818.1.1.11.12NodeupsDiagnosticfirst
1.3.6.1.4.1.818.1.1.11.12.1ScalarupsDiagnosticBusJACommunicationStatusfirstread-onlycurrentBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA …
1.3.6.1.4.1.818.1.1.11.12.2ScalarupsDiagnosticBusJBCommunicationStatusfirstread-onlycurrentBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA …
1.3.6.1.4.1.818.1.1.11.12.3ScalarupsDiagnosticBatteryLifetimefirstread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.11.12.4ScalarupsDiagnosticFansLifetimefirstread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.11.12.5ScalarupsDiagnosticDCcapacitorsLifetimefirstread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.11.12.6ScalarupsDiagnosticACcapacitorsLifetimefirstread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.11.12.7ScalarupsDiagnosticGlobalServiceCheckfirstread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.12NodegeSecondUPS
1.3.6.1.4.1.818.1.1.12.1NodeupsIdentsecond
1.3.6.1.4.1.818.1.1.12.1.1ScalarupsIdentManufacturersecondread-onlycurrentThe name of the UPS manufacturer.(*)
1.3.6.1.4.1.818.1.1.12.1.2ScalarupsIdentModelsecondread-onlycurrentThe UPS Model designation.(*)
1.3.6.1.4.1.818.1.1.12.1.3ScalarupsIdentUPSSoftwareVersionsecondread-onlycurrentThe UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*)
1.3.6.1.4.1.818.1.1.12.1.4ScalarupsIdentAgentSoftwareVersionsecondread-onlycurrentThe UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*)
1.3.6.1.4.1.818.1.1.12.1.5ScalarupsIdentNamesecondread-writecurrentA string identifying the UPS. This object should be set by the administrator.(*)
1.3.6.1.4.1.818.1.1.12.1.6ScalarupsIdentAttachedDevicessecondread-writecurrentA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*)
1.3.6.1.4.1.818.1.1.12.1.7ScalarupsIdentUPSSerialNumbersecondread-onlycurrentThe UPS serial number
1.3.6.1.4.1.818.1.1.12.1.8ScalarupsIdentComProtVersionsecondread-onlycurrentThe IMV communication protocol version
1.3.6.1.4.1.818.1.1.12.1.9ScalarupsIdentOperatingTimesecondread-onlycurrentThe present value of the operating time. total 'on' time since UPS manufactured
1.3.6.1.4.1.818.1.1.12.2NodeupsBatterysecond
1.3.6.1.4.1.818.1.1.12.2.1ScalarupsBatteryStatussecondread-onlycurrentThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfi…
1.3.6.1.4.1.818.1.1.12.2.2ScalarupsSecondsOnBatterysecondread-onlycurrentIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res…
1.3.6.1.4.1.818.1.1.12.2.3ScalarupsEstimatedMinutesRemainingsecondread-onlycurrentAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and…
1.3.6.1.4.1.818.1.1.12.2.4ScalarupsEstimatedChargeRemainingsecondread-onlycurrentAn estimate of the battery charge remaining expressed as a percent of full charge.(*)
1.3.6.1.4.1.818.1.1.12.2.5ScalarupsBatteryVoltagesecondread-onlycurrentThe magnitude of the present battery voltage.(*)
1.3.6.1.4.1.818.1.1.12.2.6ScalarupsBatteryCurrentsecondread-onlycurrentThe present battery current.(*)
1.3.6.1.4.1.818.1.1.12.2.7ScalarupsBatteryTemperaturesecondread-onlycurrentThe ambient temperature at or near the UPS Battery casing.(*)
1.3.6.1.4.1.818.1.1.12.2.8ScalarupsBatteryRipplesecondread-onlycurrentThe present DC link RMS voltage ripple.(*)
1.3.6.1.4.1.818.1.1.12.3NodeupsInputsecond
1.3.6.1.4.1.818.1.1.12.3.1ScalarupsInputLineBadssecondread-onlycurrentA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the i…
1.3.6.1.4.1.818.1.1.12.3.2ScalarupsInputNumLinessecondread-onlycurrentThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*)
1.3.6.1.4.1.818.1.1.12.3.3TableupsInputSecondTablenot-accessiblecurrentA list of input table entries. The number of entries is given by the value of upsInputNumLines.(*)
1.3.6.1.4.1.818.1.1.12.3.3.1RowupsInputSecondEntrynot-accessiblecurrentAn entry containing information applicable to a particular input line.(*)
1.3.6.1.4.1.818.1.1.12.3.3.1.1ColumnupsInputLineIndexsecondnot-accessiblecurrentThe input line identifier.(*)
1.3.6.1.4.1.818.1.1.12.3.3.1.2ColumnupsInputFrequencysecondread-onlycurrentThe present input frequency.(*)
1.3.6.1.4.1.818.1.1.12.3.3.1.3ColumnupsInputVoltagesecondread-onlycurrentThe magnitude of the present input voltage.(*)
1.3.6.1.4.1.818.1.1.12.3.3.1.4ColumnupsInputCurrentsecondread-onlycurrentThe magnitude of the present input current.(*)
1.3.6.1.4.1.818.1.1.12.3.3.1.5ColumnupsInputTruePowersecondread-onlycurrentThe magnitude of the present input true power.(*)
1.3.6.1.4.1.818.1.1.12.3.3.1.6ColumnupsInputVoltageMinsecondread-onlycurrentThe lowest magnitude of the input voltage since last read out.
1.3.6.1.4.1.818.1.1.12.3.3.1.7ColumnupsInputVoltageMaxsecondread-onlycurrentThe highest magnitude of the input voltage since last read out.
1.3.6.1.4.1.818.1.1.12.4NodeupsOutputsecond
1.3.6.1.4.1.818.1.1.12.4.1ScalarupsOutputSourcesecondread-onlycurrentThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the…
1.3.6.1.4.1.818.1.1.12.4.2ScalarupsOutputFrequencysecondread-onlycurrentThe present output frequency.(*)
1.3.6.1.4.1.818.1.1.12.4.3ScalarupsOutputNumLinessecondread-onlycurrentThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*)
1.3.6.1.4.1.818.1.1.12.4.4TableupsOutputSecondTablenot-accessiblecurrentA list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*)
1.3.6.1.4.1.818.1.1.12.4.4.1RowupsOutputSecondEntrynot-accessiblecurrentAn entry containing information applicable to a particular output line.(*)
1.3.6.1.4.1.818.1.1.12.4.4.1.1ColumnupsOutputLineIndexsecondnot-accessiblecurrentThe output line identifier.(*)
1.3.6.1.4.1.818.1.1.12.4.4.1.2ColumnupsOutputVoltagesecondread-onlycurrentThe present output voltage.(*)
1.3.6.1.4.1.818.1.1.12.4.4.1.3ColumnupsOutputCurrentsecondread-onlycurrentThe present output current.(*)
1.3.6.1.4.1.818.1.1.12.4.4.1.4ColumnupsOutputPowersecondread-onlycurrentThe present output true power.(*)
1.3.6.1.4.1.818.1.1.12.4.4.1.5ColumnupsOutputPercentLoadsecondread-onlycurrentThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent…
1.3.6.1.4.1.818.1.1.12.4.4.1.6ColumnupsOutputPowerFactorsecondread-onlycurrentThe present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate …
1.3.6.1.4.1.818.1.1.12.4.4.1.7ColumnupsOutputPeakCurrentsecondread-onlycurrentThe present output peak current.(*)
1.3.6.1.4.1.818.1.1.12.4.4.1.8ColumnupsOutputShareCurrentsecondread-onlycurrentIn a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share…
1.3.6.1.4.1.818.1.1.12.5NodeupsBypasssecond
1.3.6.1.4.1.818.1.1.12.5.1ScalarupsBypassFrequencysecondread-onlycurrentThe present bypass frequency.(*)
1.3.6.1.4.1.818.1.1.12.5.2ScalarupsBypassNumLinessecondread-onlycurrentThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*)
1.3.6.1.4.1.818.1.1.12.5.3TableupsBypassSecondTablenot-accessiblecurrentA list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*)
1.3.6.1.4.1.818.1.1.12.5.3.1RowupsBypassSecondEntrynot-accessiblecurrentAn entry containing information applicable to a particular bypass input.(*)
1.3.6.1.4.1.818.1.1.12.5.3.1.1ColumnupsBypassLineIndexsecondnot-accessiblecurrentThe bypass line identifier.(*)
1.3.6.1.4.1.818.1.1.12.5.3.1.2ColumnupsBypassVoltagesecondread-onlycurrentThe present bypass voltage.(*)
1.3.6.1.4.1.818.1.1.12.5.3.1.3ColumnupsBypassCurrentsecondread-onlycurrentThe present bypass current.(*)
1.3.6.1.4.1.818.1.1.12.5.3.1.4ColumnupsBypassPowersecondread-onlycurrentThe present true power conveyed by the bypass.(*)
1.3.6.1.4.1.818.1.1.12.6NodeupsAlarmsecond
1.3.6.1.4.1.818.1.1.12.6.1ScalarupsAlarmsPresentsecondread-onlycurrentThe present number of active alarm conditions.(*)
1.3.6.1.4.1.818.1.1.12.6.2TableupsAlarmSecondTablenot-accessiblecurrentA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is …
1.3.6.1.4.1.818.1.1.12.6.2.1RowupsAlarmSecondEntrynot-accessiblecurrentAn entry containing information applicable to a particular alarm.(*)
1.3.6.1.4.1.818.1.1.12.6.2.1.1ColumnupsAlarmIdsecondnot-accessiblecurrentA unique identifier for an alarm condition. This value must remain constant.(*)
1.3.6.1.4.1.818.1.1.12.6.2.1.2ColumnupsAlarmDescrsecondread-onlycurrentA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con…
1.3.6.1.4.1.818.1.1.12.6.2.1.3ColumnupsAlarmTimesecondread-onlycurrentThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before ag…
1.3.6.1.4.1.818.1.1.12.6.3NodeupsWellKnownAlarmssecond
1.3.6.1.4.1.818.1.1.12.6.3.1IdentityupsAlarmBatteryBadsecondcurrentOne or more batteries have been determined to require replacement.(*)
1.3.6.1.4.1.818.1.1.12.6.3.2IdentityupsAlarmOnBatterysecondcurrentThe UPS is drawing power from the batteries.(*)
1.3.6.1.4.1.818.1.1.12.6.3.3IdentityupsAlarmLowBatterysecondcurrentThe remaining battery run-time is less than or equal to upsConfigLowBattTime.(*)
1.3.6.1.4.1.818.1.1.12.6.3.4IdentityupsAlarmDepletedBatterysecondcurrentThe UPS will be unable to sustain the present load when and if the utility power is lost.(*)
1.3.6.1.4.1.818.1.1.12.6.3.5IdentityupsAlarmTempBadsecondcurrentA temperature is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.12.6.3.6IdentityupsAlarmInputBadsecondcurrentAn input condition is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.12.6.3.7IdentityupsAlarmOutputBadsecondcurrentAn output condition (other than OutputOverload) is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.12.6.3.8IdentityupsAlarmOutputOverloadsecondcurrentThe output load exceeds the UPS output capacity.(*)
1.3.6.1.4.1.818.1.1.12.6.3.9IdentityupsAlarmOnBypasssecondcurrentThe Bypass is presently engaged on the UPS.(*)
1.3.6.1.4.1.818.1.1.12.6.3.10IdentityupsAlarmBypassBadsecondcurrentThe Bypass is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.12.6.3.11IdentityupsAlarmOutputOffAsRequestedsecondcurrentThe UPS has shutdown as requested, i.e., the output is off.(*)
1.3.6.1.4.1.818.1.1.12.6.3.12IdentityupsAlarmUpsOffAsRequestedsecondcurrentThe entire UPS has shutdown as commanded.(*)
1.3.6.1.4.1.818.1.1.12.6.3.13IdentityupsAlarmChargerFailedsecondcurrentAn uncorrected problem has been detected within the UPS charger subsystem.(*)
1.3.6.1.4.1.818.1.1.12.6.3.14IdentityupsAlarmUpsOutputOffsecondcurrentThe output of the UPS is in the off state.(*)
1.3.6.1.4.1.818.1.1.12.6.3.15IdentityupsAlarmUpsSystemOffsecondcurrentThe UPS system is in the off state.(*)
1.3.6.1.4.1.818.1.1.12.6.3.16IdentityupsAlarmFanFailuresecondcurrentThe failure of one or more fans in the UPS has been detected.(*)
1.3.6.1.4.1.818.1.1.12.6.3.17IdentityupsAlarmFuseFailuresecondcurrentThe failure of one or more fuses has been detected.(*)
1.3.6.1.4.1.818.1.1.12.6.3.18IdentityupsAlarmGeneralFaultsecondcurrentA general fault in the UPS has been detected.(*)
1.3.6.1.4.1.818.1.1.12.6.3.19IdentityupsAlarmDiagnosticTestFailedsecondcurrentThe result of the last diagnostic test indicates a failure.(*)
1.3.6.1.4.1.818.1.1.12.6.3.20IdentityupsAlarmCommunicationsLostsecondcurrentA problem has been encountered in the communications between the agent and the UPS.(*)
1.3.6.1.4.1.818.1.1.12.6.3.21IdentityupsAlarmAwaitingPowersecondcurrentThe UPS output is off and the UPS is awaiting the return of input power.(*)
1.3.6.1.4.1.818.1.1.12.6.3.22IdentityupsAlarmShutdownPendingsecondcurrentA upsShutdownAfterDelay countdown is underway.(*)
1.3.6.1.4.1.818.1.1.12.6.3.23IdentityupsAlarmShutdownImminentsecondcurrentThe UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.(*)
1.3.6.1.4.1.818.1.1.12.6.3.24IdentityupsAlarmTestInProgresssecondcurrentA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of …
1.3.6.1.4.1.818.1.1.12.6.3.25IdentityupsAlarmReceptacleOffsecondcurrentThe receptacle are switch off
1.3.6.1.4.1.818.1.1.12.6.3.26IdentityupsAlarmHighSpeedBusFailuresecondcurrentA problem on the High Speed Bus communication is detected
1.3.6.1.4.1.818.1.1.12.6.3.27IdentityupsAlarmHighSpeedBusJACRCFailuresecondcurrentA High Speed Bus CRC failure on Bus JB is detected.
1.3.6.1.4.1.818.1.1.12.6.3.28IdentityupsAlarmConnectivityBusFailuresecondcurrentA problem on the Connectivity Bus communication is detected.
1.3.6.1.4.1.818.1.1.12.6.3.29IdentityupsAlarmHighSpeedBusJBCRCFailuresecondcurrentA High Speed Bus CRC failure on Bus JB is detected.
1.3.6.1.4.1.818.1.1.12.6.3.30IdentityupsAlarmCurrentSharingsecondcurrentThe UPS detects an high current sharing on the parallel system.
1.3.6.1.4.1.818.1.1.12.6.3.31IdentityupsAlarmDCRipplesecondcurrentThe UPS detects an high ripple voltage on his DC link.
1.3.6.1.4.1.818.1.1.12.6.4ScalarupsAlarmMaskAsecondread-onlycurrentSpecifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' com…
1.3.6.1.4.1.818.1.1.12.7NodeupsTestsecond
1.3.6.1.4.1.818.1.1.12.7.1ScalarupsTestIdsecondread-writecurrentThe test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this docu…
1.3.6.1.4.1.818.1.1.12.7.2ScalarupsTestSpinLocksecondread-writecurrentA spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress a…
1.3.6.1.4.1.818.1.1.12.7.3ScalarupsTestResultsSummarysecondread-onlycurrentThe results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test complete…
1.3.6.1.4.1.818.1.1.12.7.4ScalarupsTestResultsDetailsecondread-onlycurrentAdditional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*)
1.3.6.1.4.1.818.1.1.12.7.5ScalarupsTestStartTimesecondread-onlycurrentThe value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of…
1.3.6.1.4.1.818.1.1.12.7.6ScalarupsTestElapsedTimesecondread-onlycurrentThe amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of …
1.3.6.1.4.1.818.1.1.12.7.7NodeupsWellKnownTestssecond
1.3.6.1.4.1.818.1.1.12.7.7.1IdentityupsTestNoTestsInitiatedsecondcurrentNo tests have been initiated and no test is in progress.(*)
1.3.6.1.4.1.818.1.1.12.7.7.2IdentityupsTestAbortTestInProgresssecondcurrentThe test in progress is to be aborted / the test in progress was aborted.(*)
1.3.6.1.4.1.818.1.1.12.7.7.3IdentityupsTestGeneralSystemsTestsecondcurrentThe manufacturer's standard test of UPS device systems.(*)
1.3.6.1.4.1.818.1.1.12.7.7.4IdentityupsTestQuickBatteryTestsecondcurrentA test that is sufficient to determine if the battery needs replacement.(*)
1.3.6.1.4.1.818.1.1.12.7.7.5IdentityupsTestDeepBatteryCalibrationsecondcurrentThe system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high deg…
1.3.6.1.4.1.818.1.1.12.8NodeupsControlsecond
1.3.6.1.4.1.818.1.1.12.8.1ScalarupsShutdownTypesecondread-writecurrentThis object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reach…
1.3.6.1.4.1.818.1.1.12.8.2ScalarupsShutdownAfterDelaysecondread-writecurrentSetting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdo…
1.3.6.1.4.1.818.1.1.12.8.3ScalarupsStartupAfterDelaysecondread-writecurrentSetting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause …
1.3.6.1.4.1.818.1.1.12.8.4ScalarupsRebootWithDurationsecondread-writecurrentSetting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the ti…
1.3.6.1.4.1.818.1.1.12.8.5ScalarupsAutoRestartsecondread-writecurrentSetting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutd…
1.3.6.1.4.1.818.1.1.12.8.6ScalarupsReceptaclesNumsecondread-onlycurrentThe number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table.
1.3.6.1.4.1.818.1.1.12.8.7TableupsReceptacleSecondTablenot-accessiblecurrentA list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum.
1.3.6.1.4.1.818.1.1.12.8.7.1RowupsReceptacleSecondEntrynot-accessiblecurrentAn entry containing information applicable to a particular receptacle.
1.3.6.1.4.1.818.1.1.12.8.7.1.1ColumnupsReceptacleLineIndexsecondnot-accessiblecurrentThe receptacle line identifier.
1.3.6.1.4.1.818.1.1.12.8.7.1.2ColumnupsReceptacleOnOffsecondread-writecurrentThe present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptac…
1.3.6.1.4.1.818.1.1.12.8.8ScalarupsUPSModesecondread-writecurrentThe operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transfor…
1.3.6.1.4.1.818.1.1.12.8.9ScalarupsRectifierOnOffsecondread-writecurrentThe present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier …
1.3.6.1.4.1.818.1.1.12.8.10ScalarupsBatteryChargeMethodsecondread-writecurrentThe present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this objec…
1.3.6.1.4.1.818.1.1.12.8.11ScalarupsInverterOnOffsecondread-writecurrentThe present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off…
1.3.6.1.4.1.818.1.1.12.8.12ScalarupsBypassOnOffsecondread-writecurrentThe present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If…
1.3.6.1.4.1.818.1.1.12.8.13ScalarupsLoadSourcesecondread-writecurrentThe present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will …
1.3.6.1.4.1.818.1.1.12.9NodeupsConfigsecond
1.3.6.1.4.1.818.1.1.12.9.1ScalarupsConfigInputVoltagesecondread-writecurrentThe magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a v…
1.3.6.1.4.1.818.1.1.12.9.2ScalarupsConfigInputFreqsecondread-writecurrentThe nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is no…
1.3.6.1.4.1.818.1.1.12.9.3ScalarupsConfigOutputVoltagesecondread-writecurrentThe magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a …
1.3.6.1.4.1.818.1.1.12.9.4ScalarupsConfigOutputFreqsecondread-writecurrentThe nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is n…
1.3.6.1.4.1.818.1.1.12.9.5ScalarupsConfigOutputVAsecondread-onlycurrentThe magnitude of the nominal Volt-Amp rating.(*)
1.3.6.1.4.1.818.1.1.12.9.6ScalarupsConfigOutputPowersecondread-onlycurrentThe magnitude of the nominal true power rating.(*)
1.3.6.1.4.1.818.1.1.12.9.7ScalarupsConfigLowBattTimesecondread-writecurrentThe value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the …
1.3.6.1.4.1.818.1.1.12.9.8ScalarupsConfigAudibleStatussecondread-writecurrentThe requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this …
1.3.6.1.4.1.818.1.1.12.9.9ScalarupsConfigLowVoltageTransferPointsecondread-writecurrentThe minimum input line voltage allowed before the UPS system transfers to battery backup.(*)
1.3.6.1.4.1.818.1.1.12.9.10ScalarupsConfigHighVoltageTransferPointsecondread-writecurrentThe maximum line voltage allowed before the UPS system transfers to battery backup.(*)
1.3.6.1.4.1.818.1.1.12.9.11ScalarupsConfigBatteryCapacitysecondread-writecurrentThe installed battery capacity. This value is the 'factory'-value, not the value after calibration.
1.3.6.1.4.1.818.1.1.12.9.12ScalarupsConfigBatteryChargeCurrentsecondread-writecurrentThe maximum battery charge current, including external chargers.
1.3.6.1.4.1.818.1.1.12.9.13ScalarupsConfigNoLoadShutdownsecondread-writecurrentDis- or enable 'no load' shutdown from the contact interface.
1.3.6.1.4.1.818.1.1.12.9.14ScalarupsConfigStartDelaysecondread-writecurrentMinimum required autonomy time before the UPS may perform an autorestart.
1.3.6.1.4.1.818.1.1.12.10NodeupsGetSetsecond
1.3.6.1.4.1.818.1.1.12.10.1ScalarupsEventGetNextsecondread-writecurrentThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The val…
1.3.6.1.4.1.818.1.1.12.10.2ScalarupsEventGetPrevioussecondread-writecurrentThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The val…
1.3.6.1.4.1.818.1.1.12.10.3ScalarupsEventSetStartingTimeStampsecondread-writecurrentThe timestamp which is used as starting point for downloading events from the UPS event buffer
1.3.6.1.4.1.818.1.1.12.10.4ScalarupsEventRetreiveCurrentTimeStampsecondread-onlycurrentThe current timestamp is retreived from the UPS
1.3.6.1.4.1.818.1.1.12.10.5ScalarupsEventTableSizesecondread-onlycurrentThe number of entries in the event table. This object indicates the number of rows in the event table.
1.3.6.1.4.1.818.1.1.12.10.6TableupsEventSecondTablenot-accessiblecurrentA list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the…
1.3.6.1.4.1.818.1.1.12.10.6.1RowupsEventSecondEntrynot-accessiblecurrentAn entry containing information applicable to a particular event.
1.3.6.1.4.1.818.1.1.12.10.6.1.1ColumnupsEventLineIndexsecondnot-accessiblecurrentThe event line identifier.
1.3.6.1.4.1.818.1.1.12.10.6.1.2ColumnupsEventCodesecondread-onlycurrentThe event code in numerical format.
1.3.6.1.4.1.818.1.1.12.10.6.1.3ColumnupsEventStatussecondread-onlycurrentThe status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status …
1.3.6.1.4.1.818.1.1.12.10.6.1.4ColumnupsEventTimesecondread-onlycurrentThe timestamp of the moment the event was generated.
1.3.6.1.4.1.818.1.1.12.10.7ScalarupsParametersReadsecondread-writecurrentThe number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value up…
1.3.6.1.4.1.818.1.1.12.10.8ScalarupsParametersWritesecondread-writecurrentThe number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be u…
1.3.6.1.4.1.818.1.1.12.10.9ScalarupsParametersStartAddresssecondread-writecurrentThe address which is used as starting point for downloading parameters from the UPS
1.3.6.1.4.1.818.1.1.12.10.10ScalarupsParameterTableSizesecondread-onlycurrentThe number of entries in the parameter table. This object indicates the number of rows in the parameter table.
1.3.6.1.4.1.818.1.1.12.10.11TableupsParameterSecondTablenot-accessiblecurrentA list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of t…
1.3.6.1.4.1.818.1.1.12.10.11.1RowupsParameterSecondEntrynot-accessiblecurrentAn entry containing information applicable to a particular parameter.
1.3.6.1.4.1.818.1.1.12.10.11.1.1ColumnupsParameterLineIndexsecondnot-accessiblecurrentThe parameter line identifier.
1.3.6.1.4.1.818.1.1.12.10.11.1.2ColumnupsParameterValuesecondread-writecurrentThe parameter value in numerical format.
1.3.6.1.4.1.818.1.1.12.10.12ScalarupsStatussecondread-onlycurrentThe global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other comman…
1.3.6.1.4.1.818.1.1.12.10.13ScalarupsMainsStatisticsMBfailsecondread-onlycurrentCount of main bypass failures (>200 ms), since UPS installation.
1.3.6.1.4.1.818.1.1.12.10.14ScalarupsMainsStatisticsMRfailsecondread-onlycurrentCount of mains rectifier failures (>200 ms), since UPS installation.
1.3.6.1.4.1.818.1.1.12.10.15ScalarupsMainsStatisticsB2secondread-onlycurrentCount of transients on the mains bypass (0..2 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.12.10.16ScalarupsMainsStatisticsB5secondread-onlycurrentCount of transients on the mains bypass (2..5 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.12.10.17ScalarupsMainsStatisticsB10secondread-onlycurrentCount of transients on the mains bypass (5..10 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.12.10.18ScalarupsMainsStatisticsB200secondread-onlycurrentCount of transients on the mains bypass (10..200 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.12.10.19ScalarupsMainsStatisticsBypRelsecondread-onlycurrentBypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'.
1.3.6.1.4.1.818.1.1.12.10.20ScalarupsTimesecondread-writecurrentThe current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp for…
1.3.6.1.4.1.818.1.1.12.10.21ScalarupsRequestPermissionsecondread-writecurrentAn encrypted code is send to enable use of restricted write objects during a limited period of time.
1.3.6.1.4.1.818.1.1.12.10.22ScalarupsEventGetCodesecondread-writecurrentThe code which is used as starting point to downloading the events from the UPS event buffer.
1.3.6.1.4.1.818.1.1.12.10.23ScalarupsEventSpinLocksecondread-writecurrentA spin lock on the event subsystem.
1.3.6.1.4.1.818.1.1.12.10.24ScalarupsParameterSpinLocksecondread-writecurrentA spin lock on the parameters subsystem.
1.3.6.1.4.1.818.1.1.12.11NodegeUPSTrapssecond
1.3.6.1.4.1.818.1.1.12.11.1NotificationupsTrapAlarmBatteryBadsecondcurrentOne or more batteries have been determined to require replacement.
1.3.6.1.4.1.818.1.1.12.11.2NotificationupsTrapAlarmOnBatterysecondcurrentThe UPS is drawing power from the batteries.
1.3.6.1.4.1.818.1.1.12.11.3NotificationupsTrapAlarmLowBatterysecondcurrentThe remaining battery run-time is less than or equal to upsConfigLowBattTime.
1.3.6.1.4.1.818.1.1.12.11.4NotificationupsTrapAlarmDepletedBatterysecondcurrentThe UPS will be unable to sustain the present load when and if the utility power is lost)
1.3.6.1.4.1.818.1.1.12.11.5NotificationupsTrapAlarmTempBadsecondcurrentA temperature is out of tolerance.
1.3.6.1.4.1.818.1.1.12.11.6NotificationupsTrapAlarmInputBadsecondcurrentAn input condition is out of tolerance.
1.3.6.1.4.1.818.1.1.12.11.7NotificationupsTrapAlarmOutputBadsecondcurrentAn output condition (other than OutputOverload) is out of tolerance.
1.3.6.1.4.1.818.1.1.12.11.8NotificationupsTrapAlarmOutputOverloadsecondcurrentThe output load exceeds the UPS output capacity.
1.3.6.1.4.1.818.1.1.12.11.9NotificationupsTrapAlarmOnBypasssecondcurrentThe Bypass is presently engaged on the UPS.
1.3.6.1.4.1.818.1.1.12.11.10NotificationupsTrapAlarmBypassBadsecondcurrentThe Bypass is out of tolerance.
1.3.6.1.4.1.818.1.1.12.11.11NotificationupsTrapAlarmOutputOffAsRequestedsecondcurrentThe UPS has shutdown as requested, i.e., the output is off.
1.3.6.1.4.1.818.1.1.12.11.12NotificationupsTrapAlarmUpsOffAsRequestedsecondcurrentThe entire UPS has shutdown as commanded.
1.3.6.1.4.1.818.1.1.12.11.13NotificationupsTrapAlarmChargerFailedsecondcurrentAn uncorrected problem has been detected within the UPS charger subsystem.
1.3.6.1.4.1.818.1.1.12.11.14NotificationupsTrapAlarmUpsOutputOffsecondcurrentThe output of the UPS is in the off state.
1.3.6.1.4.1.818.1.1.12.11.15NotificationupsTrapAlarmUpsSystemOffsecondcurrentThe UPS system is in the off state.
1.3.6.1.4.1.818.1.1.12.11.16NotificationupsTrapAlarmFanFailuresecondcurrentThe failure of one or more fans in the UPS has been detected.
1.3.6.1.4.1.818.1.1.12.11.17NotificationupsTrapAlarmFuseFailuresecondcurrentThe failure of one or more fuses has been detected.
1.3.6.1.4.1.818.1.1.12.11.18NotificationupsTrapAlarmGeneralFaultsecondcurrentA general fault in the UPS has been detected.
1.3.6.1.4.1.818.1.1.12.11.19NotificationupsTrapAlarmDiagnosticTestFailedsecondcurrentThe result of the last diagnostic test indicates a failure.
1.3.6.1.4.1.818.1.1.12.11.20NotificationupsTrapAlarmCommunicationsLostsecondcurrentA problem has been encountered in the communication between the agent and the UPS.
1.3.6.1.4.1.818.1.1.12.11.21NotificationupsTrapAlarmAwaitingPowersecondcurrentThe UPS output is off and the UPS is awaiting the return of the input power (*).
1.3.6.1.4.1.818.1.1.12.11.22NotificationupsTrapAlarmShutdownPendingsecondcurrentA upsShutdownAfterDelay countdown is underway.
1.3.6.1.4.1.818.1.1.12.11.23NotificationupsTrapAlarmShutdownImminentsecondcurrentThe UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.
1.3.6.1.4.1.818.1.1.12.11.24NotificationupsTrapAlarmTestInProgresssecondcurrentA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of …
1.3.6.1.4.1.818.1.1.12.11.25NotificationupsTrapAlarmReceptacleOffsecondcurrentA receptacle has been switched off.
1.3.6.1.4.1.818.1.1.12.11.26NotificationupsTrapAlarmHighspeedBusFailuresecondcurrentA problem on the Highspeed Bus communication is detected.
1.3.6.1.4.1.818.1.1.12.11.27NotificationupsTrapAlarmHighspeedBusJACRCFailuresecondcurrentA CRC failure on the Highspeed Bus JA is detected.
1.3.6.1.4.1.818.1.1.12.11.28NotificationupsTrapAlarmConnectivityBusFailuresecondcurrentA problem on the Connectivity Bus communication is detected.
1.3.6.1.4.1.818.1.1.12.11.29NotificationupsTrapAlarmHighspeedBusJBCRCFailuresecondcurrentA CRC failure on the Highspeed Bus JB is detected.
1.3.6.1.4.1.818.1.1.12.11.30NotificationupsTrapAlarmCurrentSharingFailuresecondcurrentAn high current sharing on the parallel system is detected.
1.3.6.1.4.1.818.1.1.12.11.31NotificationupsTrapAlarmDCRippleFailuresecondcurrentAn high ripple voltage on his DC link is detected.
1.3.6.1.4.1.818.1.1.12.11.33NotificationupsTrapAlarmBatteryBadRestoredsecondcurrentA Battery bad condition is restored.
1.3.6.1.4.1.818.1.1.12.11.34NotificationupsTrapAlarmOnBatteryRestoredsecondcurrentThe UPS is drawing power from mains again.
1.3.6.1.4.1.818.1.1.12.11.35NotificationupsTrapAlarmLowBatteryRestoredsecondcurrentA Low Battery condition is restored.
1.3.6.1.4.1.818.1.1.12.11.36NotificationupsTrapAlarmDepletedBatteryRestoredsecondcurrentA Depleted Battery condition is restored.
1.3.6.1.4.1.818.1.1.12.11.37NotificationupsTrapAlarmTempBadRestoredsecondcurrentA bad temperature condition is restored.
1.3.6.1.4.1.818.1.1.12.11.38NotificationupsTrapAlarmInputBadRestoredsecondcurrentAn input bad condition is restored.
1.3.6.1.4.1.818.1.1.12.11.39NotificationupsTrapAlarmOutputBadRestoredsecondcurrentAn output bad condition is restored.
1.3.6.1.4.1.818.1.1.12.11.40NotificationupsTrapAlarmOutputOverloadRestoredsecondcurrentAn output overload condition is restored.
1.3.6.1.4.1.818.1.1.12.11.41NotificationupsTrapAlarmOnBypassRestoredsecondcurrentAn On Bypass condition is restored.
1.3.6.1.4.1.818.1.1.12.11.42NotificationupsTrapAlarmBypassBadRestoredsecondcurrentA Bypass bad condition is restored.
1.3.6.1.4.1.818.1.1.12.11.43NotificationupsTrapAlarmOutputOffAsRequestedRestoredsecondcurrentA request shutdown has been restored.
1.3.6.1.4.1.818.1.1.12.11.44NotificationupsTrapAlarmUpsOffAsRequestedRestoredsecondcurrentA entire UPS command has been restored.
1.3.6.1.4.1.818.1.1.12.11.45NotificationupsTrapAlarmChargerFailedRestoredsecondcurrentA Charger Failer condition is restored.
1.3.6.1.4.1.818.1.1.12.11.46NotificationupsTrapAlarmUpsOutputOnsecondcurrentThe output of the UPS switched in the on state.
1.3.6.1.4.1.818.1.1.12.11.47NotificationupsTrapAlarmUpsSystemOnsecondcurrentThe UPS system is switched in the on state.
1.3.6.1.4.1.818.1.1.12.11.48NotificationupsTrapAlarmFanFailureRestoredsecondcurrentA Fan failure condition is restored.
1.3.6.1.4.1.818.1.1.12.11.49NotificationupsTrapAlarmFuseFailureRestoredsecondcurrentA Fuse failure condition is restored.
1.3.6.1.4.1.818.1.1.12.11.50NotificationupsTrapAlarmGeneralFaultRestoredsecondcurrentA general fault is restored.
1.3.6.1.4.1.818.1.1.12.11.51NotificationupsTrapAlarmDiagnosticTestFailedRestoredsecondcurrentA last diagnostic test indicates a failure is restored.
1.3.6.1.4.1.818.1.1.12.11.52NotificationupsTrapAlarmCommunicationsLostRestoredsecondcurrentA problem in the communication between the agent and the UPS is restored.
1.3.6.1.4.1.818.1.1.12.11.53NotificationupsTrapAlarmAwaitingPowerRestoredsecondcurrentA awaiting power condition is restored (*).
1.3.6.1.4.1.818.1.1.12.11.54NotificationupsTrapAlarmShutdownPendingRestoredsecondcurrentA upsShutdownAfterDelay countdown is restored.
1.3.6.1.4.1.818.1.1.12.11.55NotificationupsTrapAlarmShutdownImminentRestoredsecondcurrentA shutdown imminent condition is restored.
1.3.6.1.4.1.818.1.1.12.11.56NotificationupsTrapAlarmTestInProgressRestoredsecondcurrentThe test is in progress is terminated.
1.3.6.1.4.1.818.1.1.12.11.57NotificationupsTrapAlarmReceptacleOnsecondcurrentA receptacle has been switched on.
1.3.6.1.4.1.818.1.1.12.11.58NotificationupsTrapAlarmHighspeedBusRestoredsecondcurrentA problem on the Highspeed Bus communication is restored.
1.3.6.1.4.1.818.1.1.12.11.59NotificationupsTrapAlarmHighspeedBusJACRCRestoredsecondcurrentA CRC failure on the Highspeed Bus JA is restored.
1.3.6.1.4.1.818.1.1.12.11.60NotificationupsTrapAlarmConnectivityBusRestoredsecondcurrentA problem on the Connectivity Bus communication is restored.
1.3.6.1.4.1.818.1.1.12.11.61NotificationupsTrapAlarmHighspeedBusJBCRCRestoredsecondcurrentA CRC failure on the Highspeed Bus JB is restored.
1.3.6.1.4.1.818.1.1.12.11.62NotificationupsTrapAlarmCurrentSharingRestoredsecondcurrentAn high current sharing on the parallel system is restored.
1.3.6.1.4.1.818.1.1.12.11.63NotificationupsTrapAlarmDCRippleRestoredsecondcurrentAn high ripple voltage on his DC link is restored.
1.3.6.1.4.1.818.1.1.12.11.129NotificationupsTrapAlarmValueLowsecondcurrentA measurement value reached a value below its low-level threshold.
1.3.6.1.4.1.818.1.1.12.11.130NotificationupsTrapAlarmValueHighsecondcurrentA measurement value reached a value higher than its high-level threshold.
1.3.6.1.4.1.818.1.1.12.11.133NotificationupsTrapAlarmValueLowRestoredsecondcurrentA ValueLow alarm condition is restored.
1.3.6.1.4.1.818.1.1.12.11.134NotificationupsTrapAlarmValueHighRestoredsecondcurrentA ValueHigh alarm condition is restored.
1.3.6.1.4.1.818.1.1.12.12NodeupsDiagnosticsecond
1.3.6.1.4.1.818.1.1.12.12.1ScalarupsDiagnosticBusJACommunicationStatussecondread-onlycurrentBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA …
1.3.6.1.4.1.818.1.1.12.12.2ScalarupsDiagnosticBusJBCommunicationStatussecondread-onlycurrentBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA …
1.3.6.1.4.1.818.1.1.12.12.3ScalarupsDiagnosticBatteryLifetimesecondread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.12.12.4ScalarupsDiagnosticFansLifetimesecondread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.12.12.5ScalarupsDiagnosticDCcapacitorsLifetimesecondread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.12.12.6ScalarupsDiagnosticACcapacitorsLifetimesecondread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.12.12.7ScalarupsDiagnosticGlobalServiceChecksecondread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.13NodegeThirdUPS
1.3.6.1.4.1.818.1.1.13.1NodeupsIdentthird
1.3.6.1.4.1.818.1.1.13.1.1ScalarupsIdentManufacturerthirdread-onlycurrentThe name of the UPS manufacturer.(*)
1.3.6.1.4.1.818.1.1.13.1.2ScalarupsIdentModelthirdread-onlycurrentThe UPS Model designation.(*)
1.3.6.1.4.1.818.1.1.13.1.3ScalarupsIdentUPSSoftwareVersionthirdread-onlycurrentThe UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*)
1.3.6.1.4.1.818.1.1.13.1.4ScalarupsIdentAgentSoftwareVersionthirdread-onlycurrentThe UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*)
1.3.6.1.4.1.818.1.1.13.1.5ScalarupsIdentNamethirdread-writecurrentA string identifying the UPS. This object should be set by the administrator.(*)
1.3.6.1.4.1.818.1.1.13.1.6ScalarupsIdentAttachedDevicesthirdread-writecurrentA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*)
1.3.6.1.4.1.818.1.1.13.1.7ScalarupsIdentUPSSerialNumberthirdread-onlycurrentThe UPS serial number
1.3.6.1.4.1.818.1.1.13.1.8ScalarupsIdentComProtVersionthirdread-onlycurrentThe IMV communication protocol version
1.3.6.1.4.1.818.1.1.13.1.9ScalarupsIdentOperatingTimethirdread-onlycurrentThe present value of the operating time. total 'on' time since UPS manufactured
1.3.6.1.4.1.818.1.1.13.2NodeupsBatterythird
1.3.6.1.4.1.818.1.1.13.2.1ScalarupsBatteryStatusthirdread-onlycurrentThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfi…
1.3.6.1.4.1.818.1.1.13.2.2ScalarupsSecondsOnBatterythirdread-onlycurrentIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res…
1.3.6.1.4.1.818.1.1.13.2.3ScalarupsEstimatedMinutesRemainingthirdread-onlycurrentAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and…
1.3.6.1.4.1.818.1.1.13.2.4ScalarupsEstimatedChargeRemainingthirdread-onlycurrentAn estimate of the battery charge remaining expressed as a percent of full charge.(*)
1.3.6.1.4.1.818.1.1.13.2.5ScalarupsBatteryVoltagethirdread-onlycurrentThe magnitude of the present battery voltage.(*)
1.3.6.1.4.1.818.1.1.13.2.6ScalarupsBatteryCurrentthirdread-onlycurrentThe present battery current.(*)
1.3.6.1.4.1.818.1.1.13.2.7ScalarupsBatteryTemperaturethirdread-onlycurrentThe ambient temperature at or near the UPS Battery casing.(*)
1.3.6.1.4.1.818.1.1.13.2.8ScalarupsBatteryRipplethirdread-onlycurrentThe present DC link RMS voltage ripple.(*)
1.3.6.1.4.1.818.1.1.13.3NodeupsInputthird
1.3.6.1.4.1.818.1.1.13.3.1ScalarupsInputLineBadsthirdread-onlycurrentA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the i…
1.3.6.1.4.1.818.1.1.13.3.2ScalarupsInputNumLinesthirdread-onlycurrentThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*)
1.3.6.1.4.1.818.1.1.13.3.3TableupsInputThirdTablenot-accessiblecurrentA list of input table entries. The number of entries is given by the value of upsInputNumLines.(*)
1.3.6.1.4.1.818.1.1.13.3.3.1RowupsInputThirdEntrynot-accessiblecurrentAn entry containing information applicable to a particular input line.(*)
1.3.6.1.4.1.818.1.1.13.3.3.1.1ColumnupsInputLineIndexthirdnot-accessiblecurrentThe input line identifier.(*)
1.3.6.1.4.1.818.1.1.13.3.3.1.2ColumnupsInputFrequencythirdread-onlycurrentThe present input frequency.(*)
1.3.6.1.4.1.818.1.1.13.3.3.1.3ColumnupsInputVoltagethirdread-onlycurrentThe magnitude of the present input voltage.(*)
1.3.6.1.4.1.818.1.1.13.3.3.1.4ColumnupsInputCurrentthirdread-onlycurrentThe magnitude of the present input current.(*)
1.3.6.1.4.1.818.1.1.13.3.3.1.5ColumnupsInputTruePowerthirdread-onlycurrentThe magnitude of the present input true power.(*)
1.3.6.1.4.1.818.1.1.13.3.3.1.6ColumnupsInputVoltageMinthirdread-onlycurrentThe lowest magnitude of the input voltage since last read out.
1.3.6.1.4.1.818.1.1.13.3.3.1.7ColumnupsInputVoltageMaxthirdread-onlycurrentThe highest magnitude of the input voltage since last read out.
1.3.6.1.4.1.818.1.1.13.4NodeupsOutputthird
1.3.6.1.4.1.818.1.1.13.4.1ScalarupsOutputSourcethirdread-onlycurrentThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the…
1.3.6.1.4.1.818.1.1.13.4.2ScalarupsOutputFrequencythirdread-onlycurrentThe present output frequency.(*)
1.3.6.1.4.1.818.1.1.13.4.3ScalarupsOutputNumLinesthirdread-onlycurrentThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*)
1.3.6.1.4.1.818.1.1.13.4.4TableupsOutputThirdTablenot-accessiblecurrentA list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*)
1.3.6.1.4.1.818.1.1.13.4.4.1RowupsOutputThirdEntrynot-accessiblecurrentAn entry containing information applicable to a particular output line.(*)
1.3.6.1.4.1.818.1.1.13.4.4.1.1ColumnupsOutputLineIndexthirdnot-accessiblecurrentThe output line identifier.(*)
1.3.6.1.4.1.818.1.1.13.4.4.1.2ColumnupsOutputVoltagethirdread-onlycurrentThe present output voltage.(*)
1.3.6.1.4.1.818.1.1.13.4.4.1.3ColumnupsOutputCurrentthirdread-onlycurrentThe present output current.(*)
1.3.6.1.4.1.818.1.1.13.4.4.1.4ColumnupsOutputPowerthirdread-onlycurrentThe present output true power.(*)
1.3.6.1.4.1.818.1.1.13.4.4.1.5ColumnupsOutputPercentLoadthirdread-onlycurrentThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent…
1.3.6.1.4.1.818.1.1.13.4.4.1.6ColumnupsOutputPowerFactorthirdread-onlycurrentThe present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate …
1.3.6.1.4.1.818.1.1.13.4.4.1.7ColumnupsOutputPeakCurrentthirdread-onlycurrentThe present output peak current.(*)
1.3.6.1.4.1.818.1.1.13.4.4.1.8ColumnupsOutputShareCurrentthirdread-onlycurrentIn a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share…
1.3.6.1.4.1.818.1.1.13.5NodeupsBypassthird
1.3.6.1.4.1.818.1.1.13.5.1ScalarupsBypassFrequencythirdread-onlycurrentThe present bypass frequency.(*)
1.3.6.1.4.1.818.1.1.13.5.2ScalarupsBypassNumLinesthirdread-onlycurrentThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*)
1.3.6.1.4.1.818.1.1.13.5.3TableupsBypassThirdTablenot-accessiblecurrentA list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*)
1.3.6.1.4.1.818.1.1.13.5.3.1RowupsBypassThirdEntrynot-accessiblecurrentAn entry containing information applicable to a particular bypass input.(*)
1.3.6.1.4.1.818.1.1.13.5.3.1.1ColumnupsBypassLineIndexthirdnot-accessiblecurrentThe bypass line identifier.(*)
1.3.6.1.4.1.818.1.1.13.5.3.1.2ColumnupsBypassVoltagethirdread-onlycurrentThe present bypass voltage.(*)
1.3.6.1.4.1.818.1.1.13.5.3.1.3ColumnupsBypassCurrentthirdread-onlycurrentThe present bypass current.(*)
1.3.6.1.4.1.818.1.1.13.5.3.1.4ColumnupsBypassPowerthirdread-onlycurrentThe present true power conveyed by the bypass.(*)
1.3.6.1.4.1.818.1.1.13.6NodeupsAlarmthird
1.3.6.1.4.1.818.1.1.13.6.1ScalarupsAlarmsPresentthirdread-onlycurrentThe present number of active alarm conditions.(*)
1.3.6.1.4.1.818.1.1.13.6.2TableupsAlarmThirdTablenot-accessiblecurrentA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is …
1.3.6.1.4.1.818.1.1.13.6.2.1RowupsAlarmThirdEntrynot-accessiblecurrentAn entry containing information applicable to a particular alarm.(*)
1.3.6.1.4.1.818.1.1.13.6.2.1.1ColumnupsAlarmIdthirdnot-accessiblecurrentA unique identifier for an alarm condition. This value must remain constant.(*)
1.3.6.1.4.1.818.1.1.13.6.2.1.2ColumnupsAlarmDescrthirdread-onlycurrentA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con…
1.3.6.1.4.1.818.1.1.13.6.2.1.3ColumnupsAlarmTimethirdread-onlycurrentThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before ag…
1.3.6.1.4.1.818.1.1.13.6.3NodeupsWellKnownAlarmsthird
1.3.6.1.4.1.818.1.1.13.6.3.1IdentityupsAlarmBatteryBadthirdcurrentOne or more batteries have been determined to require replacement.(*)
1.3.6.1.4.1.818.1.1.13.6.3.2IdentityupsAlarmOnBatterythirdcurrentThe UPS is drawing power from the batteries.(*)
1.3.6.1.4.1.818.1.1.13.6.3.3IdentityupsAlarmLowBatterythirdcurrentThe remaining battery run-time is less than or equal to upsConfigLowBattTime.(*)
1.3.6.1.4.1.818.1.1.13.6.3.4IdentityupsAlarmDepletedBatterythirdcurrentThe UPS will be unable to sustain the present load when and if the utility power is lost.(*)
1.3.6.1.4.1.818.1.1.13.6.3.5IdentityupsAlarmTempBadthirdcurrentA temperature is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.13.6.3.6IdentityupsAlarmInputBadthirdcurrentAn input condition is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.13.6.3.7IdentityupsAlarmOutputBadthirdcurrentAn output condition (other than OutputOverload) is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.13.6.3.8IdentityupsAlarmOutputOverloadthirdcurrentThe output load exceeds the UPS output capacity.(*)
1.3.6.1.4.1.818.1.1.13.6.3.9IdentityupsAlarmOnBypassthirdcurrentThe Bypass is presently engaged on the UPS.(*)
1.3.6.1.4.1.818.1.1.13.6.3.10IdentityupsAlarmBypassBadthirdcurrentThe Bypass is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.13.6.3.11IdentityupsAlarmOutputOffAsRequestedthirdcurrentThe UPS has shutdown as requested, i.e., the output is off.(*)
1.3.6.1.4.1.818.1.1.13.6.3.12IdentityupsAlarmUpsOffAsRequestedthirdcurrentThe entire UPS has shutdown as commanded.(*)
1.3.6.1.4.1.818.1.1.13.6.3.13IdentityupsAlarmChargerFailedthirdcurrentAn uncorrected problem has been detected within the UPS charger subsystem.(*)
1.3.6.1.4.1.818.1.1.13.6.3.14IdentityupsAlarmUpsOutputOffthirdcurrentThe output of the UPS is in the off state.(*)
1.3.6.1.4.1.818.1.1.13.6.3.15IdentityupsAlarmUpsSystemOffthirdcurrentThe UPS system is in the off state.(*)
1.3.6.1.4.1.818.1.1.13.6.3.16IdentityupsAlarmFanFailurethirdcurrentThe failure of one or more fans in the UPS has been detected.(*)
1.3.6.1.4.1.818.1.1.13.6.3.17IdentityupsAlarmFuseFailurethirdcurrentThe failure of one or more fuses has been detected.(*)
1.3.6.1.4.1.818.1.1.13.6.3.18IdentityupsAlarmGeneralFaultthirdcurrentA general fault in the UPS has been detected.(*)
1.3.6.1.4.1.818.1.1.13.6.3.19IdentityupsAlarmDiagnosticTestFailedthirdcurrentThe result of the last diagnostic test indicates a failure.(*)
1.3.6.1.4.1.818.1.1.13.6.3.20IdentityupsAlarmCommunicationsLostthirdcurrentA problem has been encountered in the communications between the agent and the UPS.(*)
1.3.6.1.4.1.818.1.1.13.6.3.21IdentityupsAlarmAwaitingPowerthirdcurrentThe UPS output is off and the UPS is awaiting the return of input power.(*)
1.3.6.1.4.1.818.1.1.13.6.3.22IdentityupsAlarmShutdownPendingthirdcurrentA upsShutdownAfterDelay countdown is underway.(*)
1.3.6.1.4.1.818.1.1.13.6.3.23IdentityupsAlarmShutdownImminentthirdcurrentThe UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.(*)
1.3.6.1.4.1.818.1.1.13.6.3.24IdentityupsAlarmTestInProgressthirdcurrentA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of …
1.3.6.1.4.1.818.1.1.13.6.3.25IdentityupsAlarmReceptacleOffthirdcurrentThe receptacle are switch off
1.3.6.1.4.1.818.1.1.13.6.3.26IdentityupsAlarmHighSpeedBusFailurethirdcurrentA problem on the High Speed Bus communication is detected
1.3.6.1.4.1.818.1.1.13.6.3.27IdentityupsAlarmHighSpeedBusJACRCFailurethirdcurrentA High Speed Bus CRC failure on Bus JA is detected.
1.3.6.1.4.1.818.1.1.13.6.3.28IdentityupsAlarmConnectivityBusFailurethirdcurrentA problem on the Connectivity Bus communication is detected.
1.3.6.1.4.1.818.1.1.13.6.3.29IdentityupsAlarmHighSpeedBusJBCRCFailurethirdcurrentA High Speed Bus CRC failure on Bus JB is detected.
1.3.6.1.4.1.818.1.1.13.6.3.30IdentityupsAlarmCurrentSharingthirdcurrentThe UPS detects an high current sharing on the parallel system.
1.3.6.1.4.1.818.1.1.13.6.3.31IdentityupsAlarmDCRipplethirdcurrentThe UPS detects an high ripple voltage on his DC link.
1.3.6.1.4.1.818.1.1.13.6.4ScalarupsAlarmMaskAthirdread-onlycurrentSpecifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' com…
1.3.6.1.4.1.818.1.1.13.7NodeupsTestthird
1.3.6.1.4.1.818.1.1.13.7.1ScalarupsTestIdthirdread-writecurrentThe test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this docu…
1.3.6.1.4.1.818.1.1.13.7.2ScalarupsTestSpinLockthirdread-writecurrentA spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress a…
1.3.6.1.4.1.818.1.1.13.7.3ScalarupsTestResultsSummarythirdread-onlycurrentThe results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test complete…
1.3.6.1.4.1.818.1.1.13.7.4ScalarupsTestResultsDetailthirdread-onlycurrentAdditional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*)
1.3.6.1.4.1.818.1.1.13.7.5ScalarupsTestStartTimethirdread-onlycurrentThe value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of…
1.3.6.1.4.1.818.1.1.13.7.6ScalarupsTestElapsedTimethirdread-onlycurrentThe amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of …
1.3.6.1.4.1.818.1.1.13.7.7NodeupsWellKnownTeststhird
1.3.6.1.4.1.818.1.1.13.7.7.1IdentityupsTestNoTestsInitiatedthirdcurrentNo tests have been initiated and no test is in progress.(*)
1.3.6.1.4.1.818.1.1.13.7.7.2IdentityupsTestAbortTestInProgressthirdcurrentThe test in progress is to be aborted / the test in progress was aborted.(*)
1.3.6.1.4.1.818.1.1.13.7.7.3IdentityupsTestGeneralSystemsTestthirdcurrentThe manufacturer's standard test of UPS device systems.(*)
1.3.6.1.4.1.818.1.1.13.7.7.4IdentityupsTestQuickBatteryTestthirdcurrentA test that is sufficient to determine if the battery needs replacement.(*)
1.3.6.1.4.1.818.1.1.13.7.7.5IdentityupsTestDeepBatteryCalibrationthirdcurrentThe system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high deg…
1.3.6.1.4.1.818.1.1.13.8NodeupsControlthird
1.3.6.1.4.1.818.1.1.13.8.1ScalarupsShutdownTypethirdread-writecurrentThis object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reach…
1.3.6.1.4.1.818.1.1.13.8.2ScalarupsShutdownAfterDelaythirdread-writecurrentSetting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdo…
1.3.6.1.4.1.818.1.1.13.8.3ScalarupsStartupAfterDelaythirdread-writecurrentSetting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause …
1.3.6.1.4.1.818.1.1.13.8.4ScalarupsRebootWithDurationthirdread-writecurrentSetting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the ti…
1.3.6.1.4.1.818.1.1.13.8.5ScalarupsAutoRestartthirdread-writecurrentSetting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutd…
1.3.6.1.4.1.818.1.1.13.8.6ScalarupsReceptaclesNumthirdread-onlycurrentThe number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table.
1.3.6.1.4.1.818.1.1.13.8.7TableupsReceptacleThirdTablenot-accessiblecurrentA list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum.
1.3.6.1.4.1.818.1.1.13.8.7.1RowupsReceptacleThirdEntrynot-accessiblecurrentAn entry containing information applicable to a particular receptacle.
1.3.6.1.4.1.818.1.1.13.8.7.1.1ColumnupsReceptacleLineIndexthirdnot-accessiblecurrentThe receptacle line identifier.
1.3.6.1.4.1.818.1.1.13.8.7.1.2ColumnupsReceptacleOnOffthirdread-writecurrentThe present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptac…
1.3.6.1.4.1.818.1.1.13.8.8ScalarupsUPSModethirdread-writecurrentThe operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transfor…
1.3.6.1.4.1.818.1.1.13.8.9ScalarupsRectifierOnOffthirdread-writecurrentThe present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier …
1.3.6.1.4.1.818.1.1.13.8.10ScalarupsBatteryChargeMethodthirdread-writecurrentThe present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this objec…
1.3.6.1.4.1.818.1.1.13.8.11ScalarupsInverterOnOffthirdread-writecurrentThe present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off…
1.3.6.1.4.1.818.1.1.13.8.12ScalarupsBypassOnOffthirdread-writecurrentThe present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If…
1.3.6.1.4.1.818.1.1.13.8.13ScalarupsLoadSourcethirdread-writecurrentThe present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will …
1.3.6.1.4.1.818.1.1.13.9NodeupsConfigthird
1.3.6.1.4.1.818.1.1.13.9.1ScalarupsConfigInputVoltagethirdread-writecurrentThe magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a v…
1.3.6.1.4.1.818.1.1.13.9.2ScalarupsConfigInputFreqthirdread-writecurrentThe nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is no…
1.3.6.1.4.1.818.1.1.13.9.3ScalarupsConfigOutputVoltagethirdread-writecurrentThe magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a …
1.3.6.1.4.1.818.1.1.13.9.4ScalarupsConfigOutputFreqthirdread-writecurrentThe nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is n…
1.3.6.1.4.1.818.1.1.13.9.5ScalarupsConfigOutputVAthirdread-onlycurrentThe magnitude of the nominal Volt-Amp rating.(*)
1.3.6.1.4.1.818.1.1.13.9.6ScalarupsConfigOutputPowerthirdread-onlycurrentThe magnitude of the nominal true power rating.(*)
1.3.6.1.4.1.818.1.1.13.9.7ScalarupsConfigLowBattTimethirdread-writecurrentThe value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the …
1.3.6.1.4.1.818.1.1.13.9.8ScalarupsConfigAudibleStatusthirdread-writecurrentThe requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this …
1.3.6.1.4.1.818.1.1.13.9.9ScalarupsConfigLowVoltageTransferPointthirdread-writecurrentThe minimum input line voltage allowed before the UPS system transfers to battery backup.(*)
1.3.6.1.4.1.818.1.1.13.9.10ScalarupsConfigHighVoltageTransferPointthirdread-writecurrentThe maximum line voltage allowed before the UPS system transfers to battery backup.(*)
1.3.6.1.4.1.818.1.1.13.9.11ScalarupsConfigBatteryCapacitythirdread-writecurrentThe installed battery capacity. This value is the 'factory'-value, not the value after calibration.
1.3.6.1.4.1.818.1.1.13.9.12ScalarupsConfigBatteryChargeCurrentthirdread-writecurrentThe maximum battery charge current, including external chargers.
1.3.6.1.4.1.818.1.1.13.9.13ScalarupsConfigNoLoadShutdownthirdread-writecurrentDis- or enable 'no load' shutdown from the contact interface.
1.3.6.1.4.1.818.1.1.13.9.14ScalarupsConfigStartDelaythirdread-writecurrentMinimum required autonomy time before the UPS may perform an autorestart.
1.3.6.1.4.1.818.1.1.13.10NodeupsGetSetthird
1.3.6.1.4.1.818.1.1.13.10.1ScalarupsEventGetNextthirdread-writecurrentThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The val…
1.3.6.1.4.1.818.1.1.13.10.2ScalarupsEventGetPreviousthirdread-writecurrentThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The val…
1.3.6.1.4.1.818.1.1.13.10.3ScalarupsEventSetStartingTimeStampthirdread-writecurrentThe timestamp which is used as starting point for downloading events from the UPS event buffer
1.3.6.1.4.1.818.1.1.13.10.4ScalarupsEventRetreiveCurrentTimeStampthirdread-onlycurrentThe current timestamp is retreived from the UPS
1.3.6.1.4.1.818.1.1.13.10.5ScalarupsEventTableSizethirdread-onlycurrentThe number of entries in the event table. This object indicates the number of rows in the event table.
1.3.6.1.4.1.818.1.1.13.10.6TableupsEventThirdTablenot-accessiblecurrentA list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the…
1.3.6.1.4.1.818.1.1.13.10.6.1RowupsEventThirdEntrynot-accessiblecurrentAn entry containing information applicable to a particular event.
1.3.6.1.4.1.818.1.1.13.10.6.1.1ColumnupsEventLineIndexthirdnot-accessiblecurrentThe event line identifier.
1.3.6.1.4.1.818.1.1.13.10.6.1.2ColumnupsEventCodethirdread-onlycurrentThe event code in numerical format.
1.3.6.1.4.1.818.1.1.13.10.6.1.3ColumnupsEventStatusthirdread-onlycurrentThe status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status …
1.3.6.1.4.1.818.1.1.13.10.6.1.4ColumnupsEventTimethirdread-onlycurrentThe timestamp of the moment the event was generated.
1.3.6.1.4.1.818.1.1.13.10.7ScalarupsParametersReadthirdread-writecurrentThe number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value up…
1.3.6.1.4.1.818.1.1.13.10.8ScalarupsParametersWritethirdread-writecurrentThe number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be u…
1.3.6.1.4.1.818.1.1.13.10.9ScalarupsParametersStartAddressthirdread-writecurrentThe address which is used as starting point for downloading parameters from the UPS
1.3.6.1.4.1.818.1.1.13.10.10ScalarupsParameterTableSizethirdread-onlycurrentThe number of entries in the parameter table. This object indicates the number of rows in the parameter table.
1.3.6.1.4.1.818.1.1.13.10.11TableupsParameterThirdTablenot-accessiblecurrentA list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of t…
1.3.6.1.4.1.818.1.1.13.10.11.1RowupsParameterThirdEntrynot-accessiblecurrentAn entry containing information applicable to a particular parameter.
1.3.6.1.4.1.818.1.1.13.10.11.1.1ColumnupsParameterLineIndexthirdnot-accessiblecurrentThe parameter line identifier.
1.3.6.1.4.1.818.1.1.13.10.11.1.2ColumnupsParameterValuethirdread-writecurrentThe parameter value in numerical format.
1.3.6.1.4.1.818.1.1.13.10.12ScalarupsStatusthirdread-onlycurrentThe global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other comman…
1.3.6.1.4.1.818.1.1.13.10.13ScalarupsMainsStatisticsMBfailthirdread-onlycurrentCount of main bypass failures (>200 ms), since UPS installation.
1.3.6.1.4.1.818.1.1.13.10.14ScalarupsMainsStatisticsMRfailthirdread-onlycurrentCount of mains rectifier failures (>200 ms), since UPS installation.
1.3.6.1.4.1.818.1.1.13.10.15ScalarupsMainsStatisticsB2thirdread-onlycurrentCount of transients on the mains bypass (0..2 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.13.10.16ScalarupsMainsStatisticsB5thirdread-onlycurrentCount of transients on the mains bypass (2..5 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.13.10.17ScalarupsMainsStatisticsB10thirdread-onlycurrentCount of transients on the mains bypass (5..10 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.13.10.18ScalarupsMainsStatisticsB200thirdread-onlycurrentCount of transients on the mains bypass (10..200 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.13.10.19ScalarupsMainsStatisticsBypRelthirdread-onlycurrentBypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'.
1.3.6.1.4.1.818.1.1.13.10.20ScalarupsTimethirdread-writecurrentThe current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp for…
1.3.6.1.4.1.818.1.1.13.10.21ScalarupsRequestPermissionthirdread-writecurrentAn encrypted code is send to enable use of restricted write objects during a limited period of time.
1.3.6.1.4.1.818.1.1.13.10.22ScalarupsEventGetCodethirdread-writecurrentThe code which is used as starting point to downloading the events from the UPS event buffer.
1.3.6.1.4.1.818.1.1.13.10.23ScalarupsEventSpinLockthirdread-writecurrentA spin lock on the event subsystem.
1.3.6.1.4.1.818.1.1.13.10.24ScalarupsParameterSpinLockthirdread-writecurrentA spin lock on the parameters subsystem.
1.3.6.1.4.1.818.1.1.13.11NodegeUPSTrapsthird
1.3.6.1.4.1.818.1.1.13.11.1NotificationupsTrapAlarmBatteryBadthirdcurrentOne or more batteries have been determined to require replacement.
1.3.6.1.4.1.818.1.1.13.11.2NotificationupsTrapAlarmOnBatterythirdcurrentThe UPS is drawing power from the batteries.
1.3.6.1.4.1.818.1.1.13.11.3NotificationupsTrapAlarmLowBatterythirdcurrentThe remaining battery run-time is less than or equal to upsConfigLowBattTime.
1.3.6.1.4.1.818.1.1.13.11.4NotificationupsTrapAlarmDepletedBatterythirdcurrentThe UPS will be unable to sustain the present load when and if the utility power is lost)
1.3.6.1.4.1.818.1.1.13.11.5NotificationupsTrapAlarmTempBadthirdcurrentA temperature is out of tolerance.
1.3.6.1.4.1.818.1.1.13.11.6NotificationupsTrapAlarmInputBadthirdcurrentAn input condition is out of tolerance.
1.3.6.1.4.1.818.1.1.13.11.7NotificationupsTrapAlarmOutputBadthirdcurrentAn output condition (other than OutputOverload) is out of tolerance.
1.3.6.1.4.1.818.1.1.13.11.8NotificationupsTrapAlarmOutputOverloadthirdcurrentThe output load exceeds the UPS output capacity.
1.3.6.1.4.1.818.1.1.13.11.9NotificationupsTrapAlarmOnBypassthirdcurrentThe Bypass is presently engaged on the UPS.
1.3.6.1.4.1.818.1.1.13.11.10NotificationupsTrapAlarmBypassBadthirdcurrentThe Bypass is out of tolerance.
1.3.6.1.4.1.818.1.1.13.11.11NotificationupsTrapAlarmOutputOffAsRequestedthirdcurrentThe UPS has shutdown as requested, i.e., the output is off.
1.3.6.1.4.1.818.1.1.13.11.12NotificationupsTrapAlarmUpsOffAsRequestedthirdcurrentThe entire UPS has shutdown as commanded.
1.3.6.1.4.1.818.1.1.13.11.13NotificationupsTrapAlarmChargerFailedthirdcurrentAn uncorrected problem has been detected within the UPS charger subsystem.
1.3.6.1.4.1.818.1.1.13.11.14NotificationupsTrapAlarmUpsOutputOffthirdcurrentThe output of the UPS is in the off state.
1.3.6.1.4.1.818.1.1.13.11.15NotificationupsTrapAlarmUpsSystemOffthirdcurrentThe UPS system is in the off state.
1.3.6.1.4.1.818.1.1.13.11.16NotificationupsTrapAlarmFanFailurethirdcurrentThe failure of one or more fans in the UPS has been detected.
1.3.6.1.4.1.818.1.1.13.11.17NotificationupsTrapAlarmFuseFailurethirdcurrentThe failure of one or more fuses has been detected.
1.3.6.1.4.1.818.1.1.13.11.18NotificationupsTrapAlarmGeneralFaultthirdcurrentA general fault in the UPS has been detected.
1.3.6.1.4.1.818.1.1.13.11.19NotificationupsTrapAlarmDiagnosticTestFailedthirdcurrentThe result of the last diagnostic test indicates a failure.
1.3.6.1.4.1.818.1.1.13.11.20NotificationupsTrapAlarmCommunicationsLostthirdcurrentA problem has been encountered in the communication between the agent and the UPS.
1.3.6.1.4.1.818.1.1.13.11.21NotificationupsTrapAlarmAwaitingPowerthirdcurrentThe UPS output is off and the UPS is awaiting the return of the input power (*).
1.3.6.1.4.1.818.1.1.13.11.22NotificationupsTrapAlarmShutdownPendingthirdcurrentA upsShutdownAfterDelay countdown is underway.
1.3.6.1.4.1.818.1.1.13.11.23NotificationupsTrapAlarmShutdownImminentthirdcurrentThe UPS will turn off power to the load in less than 5 secondss; this may be either a timed shutdown or a low battery shutdown.
1.3.6.1.4.1.818.1.1.13.11.24NotificationupsTrapAlarmTestInProgressthirdcurrentA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of …
1.3.6.1.4.1.818.1.1.13.11.25NotificationupsTrapAlarmReceptacleOffthirdcurrentA receptacle has been switched off.
1.3.6.1.4.1.818.1.1.13.11.26NotificationupsTrapAlarmHighspeedBusFailurethirdcurrentA problem on the Highspeed Bus communication is detected.
1.3.6.1.4.1.818.1.1.13.11.27NotificationupsTrapAlarmHighspeedBusJACRCFailurethirdcurrentA CRC failure on the Highspeed Bus JA is detected.
1.3.6.1.4.1.818.1.1.13.11.28NotificationupsTrapAlarmConnectivityBusFailurethirdcurrentA problem on the Connectivity Bus communication is detected
1.3.6.1.4.1.818.1.1.13.11.29NotificationupsTrapAlarmHighspeedBusJBCRCFailurethirdcurrentA CRC failure on the Highspeed Bus JB is detected.
1.3.6.1.4.1.818.1.1.13.11.30NotificationupsTrapAlarmCurrentSharingFailurethirdcurrentAn high current sharing on the parallel system is detected.
1.3.6.1.4.1.818.1.1.13.11.31NotificationupsTrapAlarmDCRippleFailurethirdcurrentAn high ripple voltage on his DC link is detected.
1.3.6.1.4.1.818.1.1.13.11.33NotificationupsTrapAlarmBatteryBadRestoredthirdcurrentA Battery bad condition is restored.
1.3.6.1.4.1.818.1.1.13.11.34NotificationupsTrapAlarmOnBatteryRestoredthirdcurrentThe UPS is drawing power from mains again.
1.3.6.1.4.1.818.1.1.13.11.35NotificationupsTrapAlarmLowBatteryRestoredthirdcurrentA Low Battery condition is restored.
1.3.6.1.4.1.818.1.1.13.11.36NotificationupsTrapAlarmDepletedBatteryRestoredthirdcurrentA Depleted Battery condition is restored.
1.3.6.1.4.1.818.1.1.13.11.37NotificationupsTrapAlarmTempBadRestoredthirdcurrentA bad temperature condition is restored.
1.3.6.1.4.1.818.1.1.13.11.38NotificationupsTrapAlarmInputBadRestoredthirdcurrentAn input bad condition is restored.
1.3.6.1.4.1.818.1.1.13.11.39NotificationupsTrapAlarmOutputBadRestoredthirdcurrentAn output bad condition is restored.
1.3.6.1.4.1.818.1.1.13.11.40NotificationupsTrapAlarmOutputOverloadRestoredthirdcurrentAn output overload condition is restored.
1.3.6.1.4.1.818.1.1.13.11.41NotificationupsTrapAlarmOnBypassRestoredthirdcurrentAn On Bypass condition is restored.
1.3.6.1.4.1.818.1.1.13.11.42NotificationupsTrapAlarmBypassBadRestoredthirdcurrentA Bypass bad condition is restored.
1.3.6.1.4.1.818.1.1.13.11.43NotificationupsTrapAlarmOutputOffAsRequestedRestoredthirdcurrentA request shutdown has been restored.
1.3.6.1.4.1.818.1.1.13.11.44NotificationupsTrapAlarmUpsOffAsRequestedRestoredthirdcurrentA entire UPS command has been restored.
1.3.6.1.4.1.818.1.1.13.11.45NotificationupsTrapAlarmChargerFailedRestoredthirdcurrentA Charger Failer condition is restored.
1.3.6.1.4.1.818.1.1.13.11.46NotificationupsTrapAlarmUpsOutputOnthirdcurrentThe output of the UPS switched in the on state.
1.3.6.1.4.1.818.1.1.13.11.47NotificationupsTrapAlarmUpsSystemOnthirdcurrentThe UPS system is switched in the on state.
1.3.6.1.4.1.818.1.1.13.11.48NotificationupsTrapAlarmFanFailureRestoredthirdcurrentA Fan failure condition is restored.
1.3.6.1.4.1.818.1.1.13.11.49NotificationupsTrapAlarmFuseFailureRestoredthirdcurrentA Fuse failure condition is restored.
1.3.6.1.4.1.818.1.1.13.11.50NotificationupsTrapAlarmGeneralFaultRestoredthirdcurrentA general fault is restored.
1.3.6.1.4.1.818.1.1.13.11.51NotificationupsTrapAlarmDiagnosticTestFailedRestoredthirdcurrentA last diagnostic test indicates a failure is restored.
1.3.6.1.4.1.818.1.1.13.11.52NotificationupsTrapAlarmCommunicationsLostRestoredthirdcurrentA problem in the communication between the agent and the UPS is restored.
1.3.6.1.4.1.818.1.1.13.11.53NotificationupsTrapAlarmAwaitingPowerRestoredthirdcurrentA awaiting power condition is restored (*).
1.3.6.1.4.1.818.1.1.13.11.54NotificationupsTrapAlarmShutdownPendingRestoredthirdcurrentA upsShutdownAfterDelay countdown is restored.
1.3.6.1.4.1.818.1.1.13.11.55NotificationupsTrapAlarmShutdownImminentRestoredthirdcurrentA shutdown imminent condition is restored.
1.3.6.1.4.1.818.1.1.13.11.56NotificationupsTrapAlarmTestInProgressRestoredthirdcurrentThe test is in progress is terminated.
1.3.6.1.4.1.818.1.1.13.11.57NotificationupsTrapAlarmReceptacleOnthirdcurrentA receptacle has been switched on.
1.3.6.1.4.1.818.1.1.13.11.58NotificationupsTrapAlarmHighspeedBusRestorethirdcurrentA problem on the Highspeed Bus communication is restored.
1.3.6.1.4.1.818.1.1.13.11.59NotificationupsTrapAlarmHighspeedBusJACRCRestorethirdcurrentA CRC failure on the Highspeed Bus JA is restored.
1.3.6.1.4.1.818.1.1.13.11.60NotificationupsTrapAlarmConnectivityBusRestorethirdcurrentA problem on the Connectivity Bus communication is restored.
1.3.6.1.4.1.818.1.1.13.11.61NotificationupsTrapAlarmHighspeedBusJBCRCRestoredthirdcurrentA CRC failure on the Highspeed Bus JB is restored.
1.3.6.1.4.1.818.1.1.13.11.62NotificationupsTrapAlarmCurrentSharingRestoredthirdcurrentAn high current sharing on the parallel system is restored.
1.3.6.1.4.1.818.1.1.13.11.63NotificationupsTrapAlarmDCRippleRestoredthirdcurrentAn high ripple voltage on his DC link is restored.
1.3.6.1.4.1.818.1.1.13.11.129NotificationupsTrapAlarmValueLowthirdcurrentA measurement value reached a value below its low-level threshold.
1.3.6.1.4.1.818.1.1.13.11.130NotificationupsTrapAlarmValueHighthirdcurrentA measurement value reached a value higher than its high-level threshold.
1.3.6.1.4.1.818.1.1.13.11.133NotificationupsTrapAlarmValueLowRestoredthirdcurrentA ValueLow alarm condition is restored.
1.3.6.1.4.1.818.1.1.13.11.134NotificationupsTrapAlarmValueHighRestoredthirdcurrentA ValueHigh alarm condition is restored.
1.3.6.1.4.1.818.1.1.13.12NodeupsDiagnosticthird
1.3.6.1.4.1.818.1.1.13.12.1ScalarupsDiagnosticBusJACommunicationStatusthirdread-onlycurrentBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA …
1.3.6.1.4.1.818.1.1.13.12.2ScalarupsDiagnosticBusJBCommunicationStatusthirdread-onlycurrentBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA …
1.3.6.1.4.1.818.1.1.13.12.3ScalarupsDiagnosticBatteryLifetimethirdread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.13.12.4ScalarupsDiagnosticFansLifetimethirdread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.13.12.5ScalarupsDiagnosticDCcapacitorsLifetimethirdread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.13.12.6ScalarupsDiagnosticACcapacitorsLifetimethirdread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.13.12.7ScalarupsDiagnosticGlobalServiceCheckthirdread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.14NodegeFourthUPS
1.3.6.1.4.1.818.1.1.14.1NodeupsIdentfourth
1.3.6.1.4.1.818.1.1.14.1.1ScalarupsIdentManufacturerfourthread-onlycurrentThe name of the UPS manufacturer.(*)
1.3.6.1.4.1.818.1.1.14.1.2ScalarupsIdentModelfourthread-onlycurrentThe UPS Model designation.(*)
1.3.6.1.4.1.818.1.1.14.1.3ScalarupsIdentUPSSoftwareVersionfourthread-onlycurrentThe UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*)
1.3.6.1.4.1.818.1.1.14.1.4ScalarupsIdentAgentSoftwareVersionfourthread-onlycurrentThe UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*)
1.3.6.1.4.1.818.1.1.14.1.5ScalarupsIdentNamefourthread-writecurrentA string identifying the UPS. This object should be set by the administrator.(*)
1.3.6.1.4.1.818.1.1.14.1.6ScalarupsIdentAttachedDevicesfourthread-writecurrentA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*)
1.3.6.1.4.1.818.1.1.14.1.7ScalarupsIdentUPSSerialNumberfourthread-onlycurrentThe UPS serial number
1.3.6.1.4.1.818.1.1.14.1.8ScalarupsIdentComProtVersionfourthread-onlycurrentThe IMV communication protocol version
1.3.6.1.4.1.818.1.1.14.1.9ScalarupsIdentOperatingTimefourthread-onlycurrentThe present value of the operating time. total 'on' time since UPS manufactured
1.3.6.1.4.1.818.1.1.14.2NodeupsBatteryfourth
1.3.6.1.4.1.818.1.1.14.2.1ScalarupsBatteryStatusfourthread-onlycurrentThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfi…
1.3.6.1.4.1.818.1.1.14.2.2ScalarupsSecondsOnBatteryfourthread-onlycurrentIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res…
1.3.6.1.4.1.818.1.1.14.2.3ScalarupsEstimatedMinutesRemainingfourthread-onlycurrentAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and…
1.3.6.1.4.1.818.1.1.14.2.4ScalarupsEstimatedChargeRemainingfourthread-onlycurrentAn estimate of the battery charge remaining expressed as a percent of full charge.(*)
1.3.6.1.4.1.818.1.1.14.2.5ScalarupsBatteryVoltagefourthread-onlycurrentThe magnitude of the present battery voltage.(*)
1.3.6.1.4.1.818.1.1.14.2.6ScalarupsBatteryCurrentfourthread-onlycurrentThe present battery current.(*)
1.3.6.1.4.1.818.1.1.14.2.7ScalarupsBatteryTemperaturefourthread-onlycurrentThe ambient temperature at or near the UPS Battery casing.(*)
1.3.6.1.4.1.818.1.1.14.2.8ScalarupsBatteryRipplefourthread-onlycurrentThe present DC link RMS voltage ripple.(*)
1.3.6.1.4.1.818.1.1.14.3NodeupsInputfourth
1.3.6.1.4.1.818.1.1.14.3.1ScalarupsInputLineBadsfourthread-onlycurrentA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the i…
1.3.6.1.4.1.818.1.1.14.3.2ScalarupsInputNumLinesfourthread-onlycurrentThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*)
1.3.6.1.4.1.818.1.1.14.3.3TableupsInputFourthTablenot-accessiblecurrentA list of input table entries. The number of entries is given by the value of upsInputNumLines.(*)
1.3.6.1.4.1.818.1.1.14.3.3.1RowupsInputFourthEntrynot-accessiblecurrentAn entry containing information applicable to a particular input line.(*)
1.3.6.1.4.1.818.1.1.14.3.3.1.1ColumnupsInputLineIndexfourthnot-accessiblecurrentThe input line identifier.(*)
1.3.6.1.4.1.818.1.1.14.3.3.1.2ColumnupsInputFrequencyfourthread-onlycurrentThe present input frequency.(*)
1.3.6.1.4.1.818.1.1.14.3.3.1.3ColumnupsInputVoltagefourthread-onlycurrentThe magnitude of the present input voltage.(*)
1.3.6.1.4.1.818.1.1.14.3.3.1.4ColumnupsInputCurrentfourthread-onlycurrentThe magnitude of the present input current.(*)
1.3.6.1.4.1.818.1.1.14.3.3.1.5ColumnupsInputTruePowerfourthread-onlycurrentThe magnitude of the present input true power.(*)
1.3.6.1.4.1.818.1.1.14.3.3.1.6ColumnupsInputVoltageMinfourthread-onlycurrentThe lowest magnitude of the input voltage since last read out.
1.3.6.1.4.1.818.1.1.14.3.3.1.7ColumnupsInputVoltageMaxfourthread-onlycurrentThe highest magnitude of the input voltage since last read out.
1.3.6.1.4.1.818.1.1.14.4NodeupsOutputfourth
1.3.6.1.4.1.818.1.1.14.4.1ScalarupsOutputSourcefourthread-onlycurrentThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the…
1.3.6.1.4.1.818.1.1.14.4.2ScalarupsOutputFrequencyfourthread-onlycurrentThe present output frequency.(*)
1.3.6.1.4.1.818.1.1.14.4.3ScalarupsOutputNumLinesfourthread-onlycurrentThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*)
1.3.6.1.4.1.818.1.1.14.4.4TableupsOutputFourthTablenot-accessiblecurrentA list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*)
1.3.6.1.4.1.818.1.1.14.4.4.1RowupsOutputFourthEntrynot-accessiblecurrentAn entry containing information applicable to a particular output line.(*)
1.3.6.1.4.1.818.1.1.14.4.4.1.1ColumnupsOutputLineIndexfourthnot-accessiblecurrentThe output line identifier.(*)
1.3.6.1.4.1.818.1.1.14.4.4.1.2ColumnupsOutputVoltagefourthread-onlycurrentThe present output voltage.(*)
1.3.6.1.4.1.818.1.1.14.4.4.1.3ColumnupsOutputCurrentfourthread-onlycurrentThe present output current.(*)
1.3.6.1.4.1.818.1.1.14.4.4.1.4ColumnupsOutputPowerfourthread-onlycurrentThe present output true power.(*)
1.3.6.1.4.1.818.1.1.14.4.4.1.5ColumnupsOutputPercentLoadfourthread-onlycurrentThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent…
1.3.6.1.4.1.818.1.1.14.4.4.1.6ColumnupsOutputPowerFactorfourthread-onlycurrentThe present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate …
1.3.6.1.4.1.818.1.1.14.4.4.1.7ColumnupsOutputPeakCurrentfourthread-onlycurrentThe present output peak current.(*)
1.3.6.1.4.1.818.1.1.14.4.4.1.8ColumnupsOutputShareCurrentfourthread-onlycurrentIn a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share…
1.3.6.1.4.1.818.1.1.14.5NodeupsBypassfourth
1.3.6.1.4.1.818.1.1.14.5.1ScalarupsBypassFrequencyfourthread-onlycurrentThe present bypass frequency.(*)
1.3.6.1.4.1.818.1.1.14.5.2ScalarupsBypassNumLinesfourthread-onlycurrentThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*)
1.3.6.1.4.1.818.1.1.14.5.3TableupsBypassFourthTablenot-accessiblecurrentA list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*)
1.3.6.1.4.1.818.1.1.14.5.3.1RowupsBypassFourthEntrynot-accessiblecurrentAn entry containing information applicable to a particular bypass input.(*)
1.3.6.1.4.1.818.1.1.14.5.3.1.1ColumnupsBypassLineIndexfourthnot-accessiblecurrentThe bypass line identifier.(*)
1.3.6.1.4.1.818.1.1.14.5.3.1.2ColumnupsBypassVoltagefourthread-onlycurrentThe present bypass voltage.(*)
1.3.6.1.4.1.818.1.1.14.5.3.1.3ColumnupsBypassCurrentfourthread-onlycurrentThe present bypass current.(*)
1.3.6.1.4.1.818.1.1.14.5.3.1.4ColumnupsBypassPowerfourthread-onlycurrentThe present true power conveyed by the bypass.(*)
1.3.6.1.4.1.818.1.1.14.6NodeupsAlarmfourth
1.3.6.1.4.1.818.1.1.14.6.1ScalarupsAlarmsPresentfourthread-onlycurrentThe present number of active alarm conditions.(*)
1.3.6.1.4.1.818.1.1.14.6.2TableupsAlarmFourthTablenot-accessiblecurrentA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is …
1.3.6.1.4.1.818.1.1.14.6.2.1RowupsAlarmFourthEntrynot-accessiblecurrentAn entry containing information applicable to a particular alarm.(*)
1.3.6.1.4.1.818.1.1.14.6.2.1.1ColumnupsAlarmIdfourthnot-accessiblecurrentA unique identifier for an alarm condition. This value must remain constant.(*)
1.3.6.1.4.1.818.1.1.14.6.2.1.2ColumnupsAlarmDescrfourthread-onlycurrentA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con…
1.3.6.1.4.1.818.1.1.14.6.2.1.3ColumnupsAlarmTimefourthread-onlycurrentThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before ag…
1.3.6.1.4.1.818.1.1.14.6.3NodeupsWellKnownAlarmsfourth
1.3.6.1.4.1.818.1.1.14.6.3.1IdentityupsAlarmBatteryBadfourthcurrentOne or more batteries have been determined to require replacement.(*)
1.3.6.1.4.1.818.1.1.14.6.3.2IdentityupsAlarmOnBatteryfourthcurrentThe UPS is drawing power from the batteries.(*)
1.3.6.1.4.1.818.1.1.14.6.3.3IdentityupsAlarmLowBatteryfourthcurrentThe remaining battery run-time is less than or equal to upsConfigLowBattTime.(*)
1.3.6.1.4.1.818.1.1.14.6.3.4IdentityupsAlarmDepletedBatteryfourthcurrentThe UPS will be unable to sustain the present load when and if the utility power is lost.(*)
1.3.6.1.4.1.818.1.1.14.6.3.5IdentityupsAlarmTempBadfourthcurrentA temperature is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.14.6.3.6IdentityupsAlarmInputBadfourthcurrentAn input condition is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.14.6.3.7IdentityupsAlarmOutputBadfourthcurrentAn output condition (other than OutputOverload) is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.14.6.3.8IdentityupsAlarmOutputOverloadfourthcurrentThe output load exceeds the UPS output capacity.(*)
1.3.6.1.4.1.818.1.1.14.6.3.9IdentityupsAlarmOnBypassfourthcurrentThe Bypass is presently engaged on the UPS.(*)
1.3.6.1.4.1.818.1.1.14.6.3.10IdentityupsAlarmBypassBadfourthcurrentThe Bypass is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.14.6.3.11IdentityupsAlarmOutputOffAsRequestedfourthcurrentThe UPS has shutdown as requested, i.e., the output is off.(*)
1.3.6.1.4.1.818.1.1.14.6.3.12IdentityupsAlarmUpsOffAsRequestedfourthcurrentThe entire UPS has shutdown as commanded.(*)
1.3.6.1.4.1.818.1.1.14.6.3.13IdentityupsAlarmChargerFailedfourthcurrentAn uncorrected problem has been detected within the UPS charger subsystem.(*)
1.3.6.1.4.1.818.1.1.14.6.3.14IdentityupsAlarmUpsOutputOfffourthcurrentThe output of the UPS is in the off state.(*)
1.3.6.1.4.1.818.1.1.14.6.3.15IdentityupsAlarmUpsSystemOfffourthcurrentThe UPS system is in the off state.(*)
1.3.6.1.4.1.818.1.1.14.6.3.16IdentityupsAlarmFanFailurefourthcurrentThe failure of one or more fans in the UPS has been detected.(*)
1.3.6.1.4.1.818.1.1.14.6.3.17IdentityupsAlarmFuseFailurefourthcurrentThe failure of one or more fuses has been detected.(*)
1.3.6.1.4.1.818.1.1.14.6.3.18IdentityupsAlarmGeneralFaultfourthcurrentA general fault in the UPS has been detected.(*)
1.3.6.1.4.1.818.1.1.14.6.3.19IdentityupsAlarmDiagnosticTestFailedfourthcurrentThe result of the last diagnostic test indicates a failure.(*)
1.3.6.1.4.1.818.1.1.14.6.3.20IdentityupsAlarmCommunicationsLostfourthcurrentA problem has been encountered in the communications between the agent and the UPS.(*)
1.3.6.1.4.1.818.1.1.14.6.3.21IdentityupsAlarmAwaitingPowerfourthcurrentThe UPS output is off and the UPS is awaiting the return of input power.(*)
1.3.6.1.4.1.818.1.1.14.6.3.22IdentityupsAlarmShutdownPendingfourthcurrentA upsShutdownAfterDelay countdown is underway.(*)
1.3.6.1.4.1.818.1.1.14.6.3.23IdentityupsAlarmShutdownImminentfourthcurrentThe UPS will turn off power to the load in less than 5 fourths; this may be either a timed shutdown or a low battery shutdown.(*)
1.3.6.1.4.1.818.1.1.14.6.3.24IdentityupsAlarmTestInProgressfourthcurrentA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of …
1.3.6.1.4.1.818.1.1.14.6.3.25IdentityupsAlarmReceptacleOfffourthcurrentThe receptacle are switch off
1.3.6.1.4.1.818.1.1.14.6.3.26IdentityupsAlarmHighSpeedBusFailurefourthcurrentA problem on the High Speed Bus communication is detected
1.3.6.1.4.1.818.1.1.14.6.3.27IdentityupsAlarmHighSpeedBusJACRCFailurefourthcurrentA High Speed Bus CRC failure on Bus JA is detected.
1.3.6.1.4.1.818.1.1.14.6.3.28IdentityupsAlarmConnectivityBusFailurefourthcurrentA problem on the Connectivity Bus communication is detected
1.3.6.1.4.1.818.1.1.14.6.3.29IdentityupsAlarmHighSpeedBusJBCRCFailurefourthcurrentA High Speed Bus CRC failure on Bus JB is detected.
1.3.6.1.4.1.818.1.1.14.6.3.30IdentityupsAlarmCurrentSharingfourthcurrentThe UPS detects an high current sharing on the parallel system.
1.3.6.1.4.1.818.1.1.14.6.3.31IdentityupsAlarmDCRipplefourthcurrentThe UPS detects an high ripple voltage on his DC link.
1.3.6.1.4.1.818.1.1.14.6.4ScalarupsAlarmMaskAfourthread-onlycurrentSpecifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' com…
1.3.6.1.4.1.818.1.1.14.7NodeupsTestfourth
1.3.6.1.4.1.818.1.1.14.7.1ScalarupsTestIdfourthread-writecurrentThe test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this docu…
1.3.6.1.4.1.818.1.1.14.7.2ScalarupsTestSpinLockfourthread-writecurrentA spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress a…
1.3.6.1.4.1.818.1.1.14.7.3ScalarupsTestResultsSummaryfourthread-onlycurrentThe results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test complete…
1.3.6.1.4.1.818.1.1.14.7.4ScalarupsTestResultsDetailfourthread-onlycurrentAdditional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*)
1.3.6.1.4.1.818.1.1.14.7.5ScalarupsTestStartTimefourthread-onlycurrentThe value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of…
1.3.6.1.4.1.818.1.1.14.7.6ScalarupsTestElapsedTimefourthread-onlycurrentThe amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of …
1.3.6.1.4.1.818.1.1.14.7.7NodeupsWellKnownTestsfourth
1.3.6.1.4.1.818.1.1.14.7.7.1IdentityupsTestNoTestsInitiatedfourthcurrentNo tests have been initiated and no test is in progress.(*)
1.3.6.1.4.1.818.1.1.14.7.7.2IdentityupsTestAbortTestInProgressfourthcurrentThe test in progress is to be aborted / the test in progress was aborted.(*)
1.3.6.1.4.1.818.1.1.14.7.7.3IdentityupsTestGeneralSystemsTestfourthcurrentThe manufacturer's standard test of UPS device systems.(*)
1.3.6.1.4.1.818.1.1.14.7.7.4IdentityupsTestQuickBatteryTestfourthcurrentA test that is sufficient to determine if the battery needs replacement.(*)
1.3.6.1.4.1.818.1.1.14.7.7.5IdentityupsTestDeepBatteryCalibrationfourthcurrentThe system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high deg…
1.3.6.1.4.1.818.1.1.14.8NodeupsControlfourth
1.3.6.1.4.1.818.1.1.14.8.1ScalarupsShutdownTypefourthread-writecurrentThis object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reach…
1.3.6.1.4.1.818.1.1.14.8.2ScalarupsShutdownAfterDelayfourthread-writecurrentSetting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdo…
1.3.6.1.4.1.818.1.1.14.8.3ScalarupsStartupAfterDelayfourthread-writecurrentSetting this object will start the output after the indicated number of fourths, including starting the UPS, if necessary. Setting this object to 0 will cause …
1.3.6.1.4.1.818.1.1.14.8.4ScalarupsRebootWithDurationfourthread-writecurrentSetting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the ti…
1.3.6.1.4.1.818.1.1.14.8.5ScalarupsAutoRestartfourthread-writecurrentSetting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutd…
1.3.6.1.4.1.818.1.1.14.8.6ScalarupsReceptaclesNumfourthread-onlycurrentThe number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table.
1.3.6.1.4.1.818.1.1.14.8.7TableupsReceptacleFourthTablenot-accessiblecurrentA list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum.
1.3.6.1.4.1.818.1.1.14.8.7.1RowupsReceptacleFourthEntrynot-accessiblecurrentAn entry containing information applicable to a particular receptacle.
1.3.6.1.4.1.818.1.1.14.8.7.1.1ColumnupsReceptacleLineIndexfourthnot-accessiblecurrentThe receptacle line identifier.
1.3.6.1.4.1.818.1.1.14.8.7.1.2ColumnupsReceptacleOnOfffourthread-writecurrentThe present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptac…
1.3.6.1.4.1.818.1.1.14.8.8ScalarupsUPSModefourthread-writecurrentThe operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transfor…
1.3.6.1.4.1.818.1.1.14.8.9ScalarupsRectifierOnOfffourthread-writecurrentThe present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier …
1.3.6.1.4.1.818.1.1.14.8.10ScalarupsBatteryChargeMethodfourthread-writecurrentThe present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this objec…
1.3.6.1.4.1.818.1.1.14.8.11ScalarupsInverterOnOfffourthread-writecurrentThe present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off…
1.3.6.1.4.1.818.1.1.14.8.12ScalarupsBypassOnOfffourthread-writecurrentThe present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If…
1.3.6.1.4.1.818.1.1.14.8.13ScalarupsLoadSourcefourthread-writecurrentThe present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will …
1.3.6.1.4.1.818.1.1.14.9NodeupsConfigfourth
1.3.6.1.4.1.818.1.1.14.9.1ScalarupsConfigInputVoltagefourthread-writecurrentThe magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a v…
1.3.6.1.4.1.818.1.1.14.9.2ScalarupsConfigInputFreqfourthread-writecurrentThe nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is no…
1.3.6.1.4.1.818.1.1.14.9.3ScalarupsConfigOutputVoltagefourthread-writecurrentThe magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a …
1.3.6.1.4.1.818.1.1.14.9.4ScalarupsConfigOutputFreqfourthread-writecurrentThe nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is n…
1.3.6.1.4.1.818.1.1.14.9.5ScalarupsConfigOutputVAfourthread-onlycurrentThe magnitude of the nominal Volt-Amp rating.(*)
1.3.6.1.4.1.818.1.1.14.9.6ScalarupsConfigOutputPowerfourthread-onlycurrentThe magnitude of the nominal true power rating.(*)
1.3.6.1.4.1.818.1.1.14.9.7ScalarupsConfigLowBattTimefourthread-writecurrentThe value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the …
1.3.6.1.4.1.818.1.1.14.9.8ScalarupsConfigAudibleStatusfourthread-writecurrentThe requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this …
1.3.6.1.4.1.818.1.1.14.9.9ScalarupsConfigLowVoltageTransferPointfourthread-writecurrentThe minimum input line voltage allowed before the UPS system transfers to battery backup.(*)
1.3.6.1.4.1.818.1.1.14.9.10ScalarupsConfigHighVoltageTransferPointfourthread-writecurrentThe maximum line voltage allowed before the UPS system transfers to battery backup.(*)
1.3.6.1.4.1.818.1.1.14.9.11ScalarupsConfigBatteryCapacityfourthread-writecurrentThe installed battery capacity. This value is the 'factory'-value, not the value after calibration.
1.3.6.1.4.1.818.1.1.14.9.12ScalarupsConfigBatteryChargeCurrentfourthread-writecurrentThe maximum battery charge current, including external chargers.
1.3.6.1.4.1.818.1.1.14.9.13ScalarupsConfigNoLoadShutdownfourthread-writecurrentDis- or enable 'no load' shutdown from the contact interface.
1.3.6.1.4.1.818.1.1.14.9.14ScalarupsConfigStartDelayfourthread-writecurrentMinimum required autonomy time before the UPS may perform an autorestart.
1.3.6.1.4.1.818.1.1.14.10NodeupsGetSetfourth
1.3.6.1.4.1.818.1.1.14.10.1ScalarupsEventGetNextfourthread-writecurrentThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The val…
1.3.6.1.4.1.818.1.1.14.10.2ScalarupsEventGetPreviousfourthread-writecurrentThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The val…
1.3.6.1.4.1.818.1.1.14.10.3ScalarupsEventSetStartingTimeStampfourthread-writecurrentThe timestamp which is used as starting point for downloading events from the UPS event buffer
1.3.6.1.4.1.818.1.1.14.10.4ScalarupsEventRetreiveCurrentTimeStampfourthread-onlycurrentThe current timestamp is retreived from the UPS
1.3.6.1.4.1.818.1.1.14.10.5ScalarupsEventTableSizefourthread-onlycurrentThe number of entries in the event table. This object indicates the number of rows in the event table.
1.3.6.1.4.1.818.1.1.14.10.6TableupsEventFourthTablenot-accessiblecurrentA list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the…
1.3.6.1.4.1.818.1.1.14.10.6.1RowupsEventFourthEntrynot-accessiblecurrentAn entry containing information applicable to a particular event.
1.3.6.1.4.1.818.1.1.14.10.6.1.1ColumnupsEventLineIndexfourthnot-accessiblecurrentThe event line identifier.
1.3.6.1.4.1.818.1.1.14.10.6.1.2ColumnupsEventCodefourthread-onlycurrentThe event code in numerical format.
1.3.6.1.4.1.818.1.1.14.10.6.1.3ColumnupsEventStatusfourthread-onlycurrentThe status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status …
1.3.6.1.4.1.818.1.1.14.10.6.1.4ColumnupsEventTimefourthread-onlycurrentThe timestamp of the moment the event was generated.
1.3.6.1.4.1.818.1.1.14.10.7ScalarupsParametersReadfourthread-writecurrentThe number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value up…
1.3.6.1.4.1.818.1.1.14.10.8ScalarupsParametersWritefourthread-writecurrentThe number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be u…
1.3.6.1.4.1.818.1.1.14.10.9ScalarupsParametersStartAddressfourthread-writecurrentThe address which is used as starting point for downloading parameters from the UPS
1.3.6.1.4.1.818.1.1.14.10.10ScalarupsParameterTableSizefourthread-onlycurrentThe number of entries in the parameter table. This object indicates the number of rows in the parameter table.
1.3.6.1.4.1.818.1.1.14.10.11TableupsParameterFourthTablenot-accessiblecurrentA list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of t…
1.3.6.1.4.1.818.1.1.14.10.11.1RowupsParameterFourthEntrynot-accessiblecurrentAn entry containing information applicable to a particular parameter.
1.3.6.1.4.1.818.1.1.14.10.11.1.1ColumnupsParameterLineIndexfourthnot-accessiblecurrentThe parameter line identifier.
1.3.6.1.4.1.818.1.1.14.10.11.1.2ColumnupsParameterValuefourthread-writecurrentThe parameter value in numerical format.
1.3.6.1.4.1.818.1.1.14.10.12ScalarupsStatusfourthread-onlycurrentThe global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other comman…
1.3.6.1.4.1.818.1.1.14.10.13ScalarupsMainsStatisticsMBfailfourthread-onlycurrentCount of main bypass failures (>200 ms), since UPS installation.
1.3.6.1.4.1.818.1.1.14.10.14ScalarupsMainsStatisticsMRfailfourthread-onlycurrentCount of mains rectifier failures (>200 ms), since UPS installation.
1.3.6.1.4.1.818.1.1.14.10.15ScalarupsMainsStatisticsB2fourthread-onlycurrentCount of transients on the mains bypass (0..2 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.14.10.16ScalarupsMainsStatisticsB5fourthread-onlycurrentCount of transients on the mains bypass (2..5 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.14.10.17ScalarupsMainsStatisticsB10fourthread-onlycurrentCount of transients on the mains bypass (5..10 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.14.10.18ScalarupsMainsStatisticsB200fourthread-onlycurrentCount of transients on the mains bypass (10..200 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.14.10.19ScalarupsMainsStatisticsBypRelfourthread-onlycurrentBypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'.
1.3.6.1.4.1.818.1.1.14.10.20ScalarupsTimefourthread-writecurrentThe current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp for…
1.3.6.1.4.1.818.1.1.14.10.21ScalarupsRequestPermissionfourthread-writecurrentAn encrypted code is send to enable use of restricted write objects during a limited period of time.
1.3.6.1.4.1.818.1.1.14.10.22ScalarupsEventGetCodefourthread-writecurrentThe code which is used as starting point to downloading the events from the UPS event buffer.
1.3.6.1.4.1.818.1.1.14.10.23ScalarupsEventSpinLockfourthread-writecurrentA spin lock on the event subsystem.
1.3.6.1.4.1.818.1.1.14.10.24ScalarupsParameterSpinLockfourthread-writecurrentA spin lock on the parameters subsystem.
1.3.6.1.4.1.818.1.1.14.11NodegeUPSTrapsfourth
1.3.6.1.4.1.818.1.1.14.11.1NotificationupsTrapAlarmBatteryBadfourthcurrentOne or more batteries have been determined to require replacement.
1.3.6.1.4.1.818.1.1.14.11.2NotificationupsTrapAlarmOnBatteryfourthcurrentThe UPS is drawing power from the batteries.
1.3.6.1.4.1.818.1.1.14.11.3NotificationupsTrapAlarmLowBatteryfourthcurrentThe remaining battery run-time is less than or equal to upsConfigLowBattTime.
1.3.6.1.4.1.818.1.1.14.11.4NotificationupsTrapAlarmDepletedBatteryfourthcurrentThe UPS will be unable to sustain the present load when and if the utility power is lost)
1.3.6.1.4.1.818.1.1.14.11.5NotificationupsTrapAlarmTempBadfourthcurrentA temperature is out of tolerance.
1.3.6.1.4.1.818.1.1.14.11.6NotificationupsTrapAlarmInputBadfourthcurrentAn input condition is out of tolerance.
1.3.6.1.4.1.818.1.1.14.11.7NotificationupsTrapAlarmOutputBadfourthcurrentAn output condition (other than OutputOverload) is out of tolerance.
1.3.6.1.4.1.818.1.1.14.11.8NotificationupsTrapAlarmOutputOverloadfourthcurrentThe output load exceeds the UPS output capacity.
1.3.6.1.4.1.818.1.1.14.11.9NotificationupsTrapAlarmOnBypassfourthcurrentThe Bypass is presently engaged on the UPS.
1.3.6.1.4.1.818.1.1.14.11.10NotificationupsTrapAlarmBypassBadfourthcurrentThe Bypass is out of tolerance.
1.3.6.1.4.1.818.1.1.14.11.11NotificationupsTrapAlarmOutputOffAsRequestedfourthcurrentThe UPS has shutdown as requested, i.e., the output is off.
1.3.6.1.4.1.818.1.1.14.11.12NotificationupsTrapAlarmUpsOffAsRequestedfourthcurrentThe entire UPS has shutdown as commanded.
1.3.6.1.4.1.818.1.1.14.11.13NotificationupsTrapAlarmChargerFailedfourthcurrentAn uncorrected problem has been detected within the UPS charger subsystem.
1.3.6.1.4.1.818.1.1.14.11.14NotificationupsTrapAlarmUpsOutputOfffourthcurrentThe output of the UPS is in the off state.
1.3.6.1.4.1.818.1.1.14.11.15NotificationupsTrapAlarmUpsSystemOfffourthcurrentThe UPS system is in the off state.
1.3.6.1.4.1.818.1.1.14.11.16NotificationupsTrapAlarmFanFailurefourthcurrentThe failure of one or more fans in the UPS has been detected.
1.3.6.1.4.1.818.1.1.14.11.17NotificationupsTrapAlarmFuseFailurefourthcurrentThe failure of one or more fuses has been detected.
1.3.6.1.4.1.818.1.1.14.11.18NotificationupsTrapAlarmGeneralFaultfourthcurrentA general fault in the UPS has been detected.
1.3.6.1.4.1.818.1.1.14.11.19NotificationupsTrapAlarmDiagnosticTestFailedfourthcurrentThe result of the last diagnostic test indicates a failure.
1.3.6.1.4.1.818.1.1.14.11.20NotificationupsTrapAlarmCommunicationsLostfourthcurrentA problem has been encountered in the communication between the agent and the UPS.
1.3.6.1.4.1.818.1.1.14.11.21NotificationupsTrapAlarmAwaitingPowerfourthcurrentThe UPS output is off and the UPS is awaiting the return of the input power (*).
1.3.6.1.4.1.818.1.1.14.11.22NotificationupsTrapAlarmShutdownPendingfourthcurrentA upsShutdownAfterDelay countdown is underway.
1.3.6.1.4.1.818.1.1.14.11.23NotificationupsTrapAlarmShutdownImminentfourthcurrentThe UPS will turn off power to the load in less than 5 fourths; this may be either a timed shutdown or a low battery shutdown.
1.3.6.1.4.1.818.1.1.14.11.24NotificationupsTrapAlarmTestInProgressfourthcurrentA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of …
1.3.6.1.4.1.818.1.1.14.11.25NotificationupsTrapAlarmReceptacleOfffourthcurrentA receptacle has been switched off.
1.3.6.1.4.1.818.1.1.14.11.26NotificationupsTrapAlarmHighspeedBusFailurefourthcurrentA problem on the Highspeed Bus communication is detected.
1.3.6.1.4.1.818.1.1.14.11.27NotificationupsTrapAlarmHighspeedBusJACRCFailurefourthcurrentA CRC failure on the Highspeed Bus JA is detected.
1.3.6.1.4.1.818.1.1.14.11.28NotificationupsTrapAlarmConnectivityBusFailurefourthcurrentA problem on the Connectivity Bus communication is detected
1.3.6.1.4.1.818.1.1.14.11.29NotificationupsTrapAlarmHighspeedBusJBCRCFailurefourthcurrentA CRC failure on the Highspeed Bus JB is detected.
1.3.6.1.4.1.818.1.1.14.11.30NotificationupsTrapAlarmCurrentSharingFailurefourthcurrentAn high current sharing on the parallel system is detected.
1.3.6.1.4.1.818.1.1.14.11.31NotificationupsTrapAlarmDCRippleFailurefourthcurrentAn high ripple voltage on his DC link is detected.
1.3.6.1.4.1.818.1.1.14.11.33NotificationupsTrapAlarmBatteryBadRestoredfourthcurrentA Battery bad condition is restored.
1.3.6.1.4.1.818.1.1.14.11.34NotificationupsTrapAlarmOnBatteryRestoredfourthcurrentThe UPS is drawing power from mains again.
1.3.6.1.4.1.818.1.1.14.11.35NotificationupsTrapAlarmLowBatteryRestoredfourthcurrentA Low Battery condition is restored.
1.3.6.1.4.1.818.1.1.14.11.36NotificationupsTrapAlarmDepletedBatteryRestoredfourthcurrentA Depleted Battery condition is restored.
1.3.6.1.4.1.818.1.1.14.11.37NotificationupsTrapAlarmTempBadRestoredfourthcurrentA bad temperature condition is restored.
1.3.6.1.4.1.818.1.1.14.11.38NotificationupsTrapAlarmInputBadRestoredfourthcurrentAn input bad condition is restored.
1.3.6.1.4.1.818.1.1.14.11.39NotificationupsTrapAlarmOutputBadRestoredfourthcurrentAn output bad condition is restored.
1.3.6.1.4.1.818.1.1.14.11.40NotificationupsTrapAlarmOutputOverloadRestoredfourthcurrentAn output overload condition is restored.
1.3.6.1.4.1.818.1.1.14.11.41NotificationupsTrapAlarmOnBypassRestoredfourthcurrentAn On Bypass condition is restored.
1.3.6.1.4.1.818.1.1.14.11.42NotificationupsTrapAlarmBypassBadRestoredfourthcurrentA Bypass bad condition is restored.
1.3.6.1.4.1.818.1.1.14.11.43NotificationupsTrapAlarmOutputOffAsRequestedRestoredfourthcurrentA request shutdown has been restored.
1.3.6.1.4.1.818.1.1.14.11.44NotificationupsTrapAlarmUpsOffAsRequestedRestoredfourthcurrentA entire UPS command has been restored.
1.3.6.1.4.1.818.1.1.14.11.45NotificationupsTrapAlarmChargerFailedRestoredfourthcurrentA Charger Failer condition is restored.
1.3.6.1.4.1.818.1.1.14.11.46NotificationupsTrapAlarmUpsOutputOnfourthcurrentThe output of the UPS switched in the on state.
1.3.6.1.4.1.818.1.1.14.11.47NotificationupsTrapAlarmUpsSystemOnfourthcurrentThe UPS system is switched in the on state.
1.3.6.1.4.1.818.1.1.14.11.48NotificationupsTrapAlarmFanFailureRestoredfourthcurrentA Fan failure condition is restored.
1.3.6.1.4.1.818.1.1.14.11.49NotificationupsTrapAlarmFuseFailureRestoredfourthcurrentA Fuse failure condition is restored.
1.3.6.1.4.1.818.1.1.14.11.50NotificationupsTrapAlarmGeneralFaultRestoredfourthcurrentA general fault is restored.
1.3.6.1.4.1.818.1.1.14.11.51NotificationupsTrapAlarmDiagnosticTestFailedRestoredfourthcurrentA last diagnostic test indicates a failure is restored.
1.3.6.1.4.1.818.1.1.14.11.52NotificationupsTrapAlarmCommunicationsLostRestoredfourthcurrentA problem in the communication between the agent and the UPS is restored.
1.3.6.1.4.1.818.1.1.14.11.53NotificationupsTrapAlarmAwaitingPowerRestoredfourthcurrentA awaiting power condition is restored (*).
1.3.6.1.4.1.818.1.1.14.11.54NotificationupsTrapAlarmShutdownPendingRestoredfourthcurrentA upsShutdownAfterDelay countdown is restored.
1.3.6.1.4.1.818.1.1.14.11.55NotificationupsTrapAlarmShutdownImminentRestoredfourthcurrentA shutdown imminent condition is restored.
1.3.6.1.4.1.818.1.1.14.11.56NotificationupsTrapAlarmTestInProgressRestoredfourthcurrentThe test is in progress is terminated.
1.3.6.1.4.1.818.1.1.14.11.57NotificationupsTrapAlarmReceptacleOnfourthcurrentA receptacle has been switched on.
1.3.6.1.4.1.818.1.1.14.11.58NotificationupsTrapAlarmHighspeedBusRestorefourthcurrentA problem on the Highspeed Bus communication is restored.
1.3.6.1.4.1.818.1.1.14.11.59NotificationupsTrapAlarmHighspeedBusJACRCRestorefourthcurrentA CRC failure on the Highspeed Bus JA is restored.
1.3.6.1.4.1.818.1.1.14.11.60NotificationupsTrapAlarmConnectivityBusRestorefourthcurrentA problem on the Connectivity Bus communication is restored.
1.3.6.1.4.1.818.1.1.14.11.61NotificationupsTrapAlarmHighspeedBusJBCRCRestoredfourthcurrentA CRC failure on the Highspeed Bus JB is restored.
1.3.6.1.4.1.818.1.1.14.11.62NotificationupsTrapAlarmCurrentSharingRestoredfourthcurrentAn high current sharing on the parallel system is restored.
1.3.6.1.4.1.818.1.1.14.11.63NotificationupsTrapAlarmDCRippleRestoredfourthcurrentAn high ripple voltage on his DC link is restored.
1.3.6.1.4.1.818.1.1.14.11.129NotificationupsTrapAlarmValueLowfourthcurrentA measurement value reached a value below its low-level threshold.
1.3.6.1.4.1.818.1.1.14.11.130NotificationupsTrapAlarmValueHighfourthcurrentA measurement value reached a value higher than its high-level threshold.
1.3.6.1.4.1.818.1.1.14.11.133NotificationupsTrapAlarmValueLowRestoredfourthcurrentA ValueLow alarm condition is restored.
1.3.6.1.4.1.818.1.1.14.11.134NotificationupsTrapAlarmValueHighRestoredfourthcurrentA ValueHigh alarm condition is restored.
1.3.6.1.4.1.818.1.1.14.12NodeupsDiagnosticfourth
1.3.6.1.4.1.818.1.1.14.12.1ScalarupsDiagnosticBusJACommunicationStatusfourthread-onlycurrentBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA …
1.3.6.1.4.1.818.1.1.14.12.2ScalarupsDiagnosticBusJBCommunicationStatusfourthread-onlycurrentBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA …
1.3.6.1.4.1.818.1.1.14.12.3ScalarupsDiagnosticBatteryLifetimefourthread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.14.12.4ScalarupsDiagnosticFansLifetimefourthread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.14.12.5ScalarupsDiagnosticDCcapacitorsLifetimefourthread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.14.12.6ScalarupsDiagnosticACcapacitorsLifetimefourthread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.14.12.7ScalarupsDiagnosticGlobalServiceCheckfourthread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.15NodegeFifthUPS
1.3.6.1.4.1.818.1.1.15.1NodeupsIdentfifth
1.3.6.1.4.1.818.1.1.15.1.1ScalarupsIdentManufacturerfifthread-onlycurrentThe name of the UPS manufacturer.(*)
1.3.6.1.4.1.818.1.1.15.1.2ScalarupsIdentModelfifthread-onlycurrentThe UPS Model designation.(*)
1.3.6.1.4.1.818.1.1.15.1.3ScalarupsIdentUPSSoftwareVersionfifthread-onlycurrentThe UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*)
1.3.6.1.4.1.818.1.1.15.1.4ScalarupsIdentAgentSoftwareVersionfifthread-onlycurrentThe UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*)
1.3.6.1.4.1.818.1.1.15.1.5ScalarupsIdentNamefifthread-writecurrentA string identifying the UPS. This object should be set by the administrator.(*)
1.3.6.1.4.1.818.1.1.15.1.6ScalarupsIdentAttachedDevicesfifthread-writecurrentA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*)
1.3.6.1.4.1.818.1.1.15.1.7ScalarupsIdentUPSSerialNumberfifthread-onlycurrentThe UPS serial number
1.3.6.1.4.1.818.1.1.15.1.8ScalarupsIdentComProtVersionfifthread-onlycurrentThe IMV communication protocol version
1.3.6.1.4.1.818.1.1.15.1.9ScalarupsIdentOperatingTimefifthread-onlycurrentThe present value of the operating time. total 'on' time since UPS manufactured
1.3.6.1.4.1.818.1.1.15.2NodeupsBatteryfifth
1.3.6.1.4.1.818.1.1.15.2.1ScalarupsBatteryStatusfifthread-onlycurrentThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfi…
1.3.6.1.4.1.818.1.1.15.2.2ScalarupsSecondsOnBatteryfifthread-onlycurrentIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res…
1.3.6.1.4.1.818.1.1.15.2.3ScalarupsEstimatedMinutesRemainingfifthread-onlycurrentAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and…
1.3.6.1.4.1.818.1.1.15.2.4ScalarupsEstimatedChargeRemainingfifthread-onlycurrentAn estimate of the battery charge remaining expressed as a percent of full charge.(*)
1.3.6.1.4.1.818.1.1.15.2.5ScalarupsBatteryVoltagefifthread-onlycurrentThe magnitude of the present battery voltage.(*)
1.3.6.1.4.1.818.1.1.15.2.6ScalarupsBatteryCurrentfifthread-onlycurrentThe present battery current.(*)
1.3.6.1.4.1.818.1.1.15.2.7ScalarupsBatteryTemperaturefifthread-onlycurrentThe ambient temperature at or near the UPS Battery casing.(*)
1.3.6.1.4.1.818.1.1.15.2.8ScalarupsBatteryRipplefifthread-onlycurrentThe present DC link RMS voltage ripple.(*)
1.3.6.1.4.1.818.1.1.15.3NodeupsInputfifth
1.3.6.1.4.1.818.1.1.15.3.1ScalarupsInputLineBadsfifthread-onlycurrentA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the i…
1.3.6.1.4.1.818.1.1.15.3.2ScalarupsInputNumLinesfifthread-onlycurrentThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*)
1.3.6.1.4.1.818.1.1.15.3.3TableupsInputFifthTablenot-accessiblecurrentA list of input table entries. The number of entries is given by the value of upsInputNumLines.(*)
1.3.6.1.4.1.818.1.1.15.3.3.1RowupsInputFifthEntrynot-accessiblecurrentAn entry containing information applicable to a particular input line.(*)
1.3.6.1.4.1.818.1.1.15.3.3.1.1ColumnupsInputLineIndexfifthnot-accessiblecurrentThe input line identifier.(*)
1.3.6.1.4.1.818.1.1.15.3.3.1.2ColumnupsInputFrequencyfifthread-onlycurrentThe present input frequency.(*)
1.3.6.1.4.1.818.1.1.15.3.3.1.3ColumnupsInputVoltagefifthread-onlycurrentThe magnitude of the present input voltage.(*)
1.3.6.1.4.1.818.1.1.15.3.3.1.4ColumnupsInputCurrentfifthread-onlycurrentThe magnitude of the present input current.(*)
1.3.6.1.4.1.818.1.1.15.3.3.1.5ColumnupsInputTruePowerfifthread-onlycurrentThe magnitude of the present input true power.(*)
1.3.6.1.4.1.818.1.1.15.3.3.1.6ColumnupsInputVoltageMinfifthread-onlycurrentThe lowest magnitude of the input voltage since last read out.
1.3.6.1.4.1.818.1.1.15.3.3.1.7ColumnupsInputVoltageMaxfifthread-onlycurrentThe highest magnitude of the input voltage since last read out.
1.3.6.1.4.1.818.1.1.15.4NodeupsOutputfifth
1.3.6.1.4.1.818.1.1.15.4.1ScalarupsOutputSourcefifthread-onlycurrentThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the…
1.3.6.1.4.1.818.1.1.15.4.2ScalarupsOutputFrequencyfifthread-onlycurrentThe present output frequency.(*)
1.3.6.1.4.1.818.1.1.15.4.3ScalarupsOutputNumLinesfifthread-onlycurrentThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*)
1.3.6.1.4.1.818.1.1.15.4.4TableupsOutputFifthTablenot-accessiblecurrentA list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*)
1.3.6.1.4.1.818.1.1.15.4.4.1RowupsOutputFifthEntrynot-accessiblecurrentAn entry containing information applicable to a particular output line.(*)
1.3.6.1.4.1.818.1.1.15.4.4.1.1ColumnupsOutputLineIndexfifthnot-accessiblecurrentThe output line identifier.(*)
1.3.6.1.4.1.818.1.1.15.4.4.1.2ColumnupsOutputVoltagefifthread-onlycurrentThe present output voltage.(*)
1.3.6.1.4.1.818.1.1.15.4.4.1.3ColumnupsOutputCurrentfifthread-onlycurrentThe present output current.(*)
1.3.6.1.4.1.818.1.1.15.4.4.1.4ColumnupsOutputPowerfifthread-onlycurrentThe present output true power.(*)
1.3.6.1.4.1.818.1.1.15.4.4.1.5ColumnupsOutputPercentLoadfifthread-onlycurrentThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent…
1.3.6.1.4.1.818.1.1.15.4.4.1.6ColumnupsOutputPowerFactorfifthread-onlycurrentThe present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate …
1.3.6.1.4.1.818.1.1.15.4.4.1.7ColumnupsOutputPeakCurrentfifthread-onlycurrentThe present output peak current.(*)
1.3.6.1.4.1.818.1.1.15.4.4.1.8ColumnupsOutputShareCurrentfifthread-onlycurrentIn a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share…
1.3.6.1.4.1.818.1.1.15.5NodeupsBypassfifth
1.3.6.1.4.1.818.1.1.15.5.1ScalarupsBypassFrequencyfifthread-onlycurrentThe present bypass frequency.(*)
1.3.6.1.4.1.818.1.1.15.5.2ScalarupsBypassNumLinesfifthread-onlycurrentThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*)
1.3.6.1.4.1.818.1.1.15.5.3TableupsBypassFifthTablenot-accessiblecurrentA list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*)
1.3.6.1.4.1.818.1.1.15.5.3.1RowupsBypassFifthEntrynot-accessiblecurrentAn entry containing information applicable to a particular bypass input.(*)
1.3.6.1.4.1.818.1.1.15.5.3.1.1ColumnupsBypassLineIndexfifthnot-accessiblecurrentThe bypass line identifier.(*)
1.3.6.1.4.1.818.1.1.15.5.3.1.2ColumnupsBypassVoltagefifthread-onlycurrentThe present bypass voltage.(*)
1.3.6.1.4.1.818.1.1.15.5.3.1.3ColumnupsBypassCurrentfifthread-onlycurrentThe present bypass current.(*)
1.3.6.1.4.1.818.1.1.15.5.3.1.4ColumnupsBypassPowerfifthread-onlycurrentThe present true power conveyed by the bypass.(*)
1.3.6.1.4.1.818.1.1.15.6NodeupsAlarmfifth
1.3.6.1.4.1.818.1.1.15.6.1ScalarupsAlarmsPresentfifthread-onlycurrentThe present number of active alarm conditions.(*)
1.3.6.1.4.1.818.1.1.15.6.2TableupsAlarmFifthTablenot-accessiblecurrentA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is …
1.3.6.1.4.1.818.1.1.15.6.2.1RowupsAlarmFifthEntrynot-accessiblecurrentAn entry containing information applicable to a particular alarm.(*)
1.3.6.1.4.1.818.1.1.15.6.2.1.1ColumnupsAlarmIdfifthnot-accessiblecurrentA unique identifier for an alarm condition. This value must remain constant.(*)
1.3.6.1.4.1.818.1.1.15.6.2.1.2ColumnupsAlarmDescrfifthread-onlycurrentA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con…
1.3.6.1.4.1.818.1.1.15.6.2.1.3ColumnupsAlarmTimefifthread-onlycurrentThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before ag…
1.3.6.1.4.1.818.1.1.15.6.3NodeupsWellKnownAlarmsfifth
1.3.6.1.4.1.818.1.1.15.6.3.1IdentityupsAlarmBatteryBadfifthcurrentOne or more batteries have been determined to require replacement.(*)
1.3.6.1.4.1.818.1.1.15.6.3.2IdentityupsAlarmOnBatteryfifthcurrentThe UPS is drawing power from the batteries.(*)
1.3.6.1.4.1.818.1.1.15.6.3.3IdentityupsAlarmLowBatteryfifthcurrentThe remaining battery run-time is less than or equal to upsConfigLowBattTime.(*)
1.3.6.1.4.1.818.1.1.15.6.3.4IdentityupsAlarmDepletedBatteryfifthcurrentThe UPS will be unable to sustain the present load when and if the utility power is lost.(*)
1.3.6.1.4.1.818.1.1.15.6.3.5IdentityupsAlarmTempBadfifthcurrentA temperature is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.15.6.3.6IdentityupsAlarmInputBadfifthcurrentAn input condition is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.15.6.3.7IdentityupsAlarmOutputBadfifthcurrentAn output condition (other than OutputOverload) is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.15.6.3.8IdentityupsAlarmOutputOverloadfifthcurrentThe output load exceeds the UPS output capacity.(*)
1.3.6.1.4.1.818.1.1.15.6.3.9IdentityupsAlarmOnBypassfifthcurrentThe Bypass is presently engaged on the UPS.(*)
1.3.6.1.4.1.818.1.1.15.6.3.10IdentityupsAlarmBypassBadfifthcurrentThe Bypass is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.15.6.3.11IdentityupsAlarmOutputOffAsRequestedfifthcurrentThe UPS has shutdown as requested, i.e., the output is off.(*)
1.3.6.1.4.1.818.1.1.15.6.3.12IdentityupsAlarmUpsOffAsRequestedfifthcurrentThe entire UPS has shutdown as commanded.(*)
1.3.6.1.4.1.818.1.1.15.6.3.13IdentityupsAlarmChargerFailedfifthcurrentAn uncorrected problem has been detected within the UPS charger subsystem.(*)
1.3.6.1.4.1.818.1.1.15.6.3.14IdentityupsAlarmUpsOutputOfffifthcurrentThe output of the UPS is in the off state.(*)
1.3.6.1.4.1.818.1.1.15.6.3.15IdentityupsAlarmUpsSystemOfffifthcurrentThe UPS system is in the off state.(*)
1.3.6.1.4.1.818.1.1.15.6.3.16IdentityupsAlarmFanFailurefifthcurrentThe failure of one or more fans in the UPS has been detected.(*)
1.3.6.1.4.1.818.1.1.15.6.3.17IdentityupsAlarmFuseFailurefifthcurrentThe failure of one or more fuses has been detected.(*)
1.3.6.1.4.1.818.1.1.15.6.3.18IdentityupsAlarmGeneralFaultfifthcurrentA general fault in the UPS has been detected.(*)
1.3.6.1.4.1.818.1.1.15.6.3.19IdentityupsAlarmDiagnosticTestFailedfifthcurrentThe result of the last diagnostic test indicates a failure.(*)
1.3.6.1.4.1.818.1.1.15.6.3.20IdentityupsAlarmCommunicationsLostfifthcurrentA problem has been encountered in the communications between the agent and the UPS.(*)
1.3.6.1.4.1.818.1.1.15.6.3.21IdentityupsAlarmAwaitingPowerfifthcurrentThe UPS output is off and the UPS is awaiting the return of input power.(*)
1.3.6.1.4.1.818.1.1.15.6.3.22IdentityupsAlarmShutdownPendingfifthcurrentA upsShutdownAfterDelay countdown is underway.(*)
1.3.6.1.4.1.818.1.1.15.6.3.23IdentityupsAlarmShutdownImminentfifthcurrentThe UPS will turn off power to the load in less than 5 fifths; this may be either a timed shutdown or a low battery shutdown.(*)
1.3.6.1.4.1.818.1.1.15.6.3.24IdentityupsAlarmTestInProgressfifthcurrentA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of …
1.3.6.1.4.1.818.1.1.15.6.3.25IdentityupsAlarmReceptacleOfffifthcurrentThe receptacle are switch off
1.3.6.1.4.1.818.1.1.15.6.3.26IdentityupsAlarmHighSpeedBusFailurefifthcurrentA problem on the High Speed Bus communication is detected
1.3.6.1.4.1.818.1.1.15.6.3.27IdentityupsAlarmHighSpeedBusJACRCFailurefifthcurrentA High Speed Bus CRC failure on Bus JA is detected.
1.3.6.1.4.1.818.1.1.15.6.3.28IdentityupsAlarmConnectivityBusFailurefifthcurrentA problem on the Connectivity Bus communication is detected.
1.3.6.1.4.1.818.1.1.15.6.3.29IdentityupsAlarmHighSpeedBusJBCRCFailurefifthcurrentA High Speed Bus CRC failure on Bus JB is detected.
1.3.6.1.4.1.818.1.1.15.6.3.30IdentityupsAlarmCurrentSharingfifthcurrentThe UPS detects an high current sharing on the parallel system.
1.3.6.1.4.1.818.1.1.15.6.3.31IdentityupsAlarmDCRipplefifthcurrentThe UPS detects an high ripple voltage on his DC link.
1.3.6.1.4.1.818.1.1.15.6.4ScalarupsAlarmMaskAfifthread-onlycurrentSpecifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' com…
1.3.6.1.4.1.818.1.1.15.7NodeupsTestfifth
1.3.6.1.4.1.818.1.1.15.7.1ScalarupsTestIdfifthread-writecurrentThe test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this docu…
1.3.6.1.4.1.818.1.1.15.7.2ScalarupsTestSpinLockfifthread-writecurrentA spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress a…
1.3.6.1.4.1.818.1.1.15.7.3ScalarupsTestResultsSummaryfifthread-onlycurrentThe results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test complete…
1.3.6.1.4.1.818.1.1.15.7.4ScalarupsTestResultsDetailfifthread-onlycurrentAdditional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*)
1.3.6.1.4.1.818.1.1.15.7.5ScalarupsTestStartTimefifthread-onlycurrentThe value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of…
1.3.6.1.4.1.818.1.1.15.7.6ScalarupsTestElapsedTimefifthread-onlycurrentThe amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of …
1.3.6.1.4.1.818.1.1.15.7.7NodeupsWellKnownTestsfifth
1.3.6.1.4.1.818.1.1.15.7.7.1IdentityupsTestNoTestsInitiatedfifthcurrentNo tests have been initiated and no test is in progress.(*)
1.3.6.1.4.1.818.1.1.15.7.7.2IdentityupsTestAbortTestInProgressfifthcurrentThe test in progress is to be aborted / the test in progress was aborted.(*)
1.3.6.1.4.1.818.1.1.15.7.7.3IdentityupsTestGeneralSystemsTestfifthcurrentThe manufacturer's standard test of UPS device systems.(*)
1.3.6.1.4.1.818.1.1.15.7.7.4IdentityupsTestQuickBatteryTestfifthcurrentA test that is sufficient to determine if the battery needs replacement.(*)
1.3.6.1.4.1.818.1.1.15.7.7.5IdentityupsTestDeepBatteryCalibrationfifthcurrentThe system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high deg…
1.3.6.1.4.1.818.1.1.15.8NodeupsControlfifth
1.3.6.1.4.1.818.1.1.15.8.1ScalarupsShutdownTypefifthread-writecurrentThis object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reach…
1.3.6.1.4.1.818.1.1.15.8.2ScalarupsShutdownAfterDelayfifthread-writecurrentSetting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdo…
1.3.6.1.4.1.818.1.1.15.8.3ScalarupsStartupAfterDelayfifthread-writecurrentSetting this object will start the output after the indicated number of fifths, including starting the UPS, if necessary. Setting this object to 0 will cause t…
1.3.6.1.4.1.818.1.1.15.8.4ScalarupsRebootWithDurationfifthread-writecurrentSetting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the ti…
1.3.6.1.4.1.818.1.1.15.8.5ScalarupsAutoRestartfifthread-writecurrentSetting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutd…
1.3.6.1.4.1.818.1.1.15.8.6ScalarupsReceptaclesNumfifthread-onlycurrentThe number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table.
1.3.6.1.4.1.818.1.1.15.8.7TableupsReceptacleFifthTablenot-accessiblecurrentA list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum.
1.3.6.1.4.1.818.1.1.15.8.7.1RowupsReceptacleFifthEntrynot-accessiblecurrentAn entry containing information applicable to a particular receptacle.
1.3.6.1.4.1.818.1.1.15.8.7.1.1ColumnupsReceptacleLineIndexfifthnot-accessiblecurrentThe receptacle line identifier.
1.3.6.1.4.1.818.1.1.15.8.7.1.2ColumnupsReceptacleOnOfffifthread-writecurrentThe present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptac…
1.3.6.1.4.1.818.1.1.15.8.8ScalarupsUPSModefifthread-writecurrentThe operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transfor…
1.3.6.1.4.1.818.1.1.15.8.9ScalarupsRectifierOnOfffifthread-writecurrentThe present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier …
1.3.6.1.4.1.818.1.1.15.8.10ScalarupsBatteryChargeMethodfifthread-writecurrentThe present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this objec…
1.3.6.1.4.1.818.1.1.15.8.11ScalarupsInverterOnOfffifthread-writecurrentThe present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off…
1.3.6.1.4.1.818.1.1.15.8.12ScalarupsBypassOnOfffifthread-writecurrentThe present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If…
1.3.6.1.4.1.818.1.1.15.8.13ScalarupsLoadSourcefifthread-writecurrentThe present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will …
1.3.6.1.4.1.818.1.1.15.9NodeupsConfigfifth
1.3.6.1.4.1.818.1.1.15.9.1ScalarupsConfigInputVoltagefifthread-writecurrentThe magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a v…
1.3.6.1.4.1.818.1.1.15.9.2ScalarupsConfigInputFreqfifthread-writecurrentThe nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is no…
1.3.6.1.4.1.818.1.1.15.9.3ScalarupsConfigOutputVoltagefifthread-writecurrentThe magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a …
1.3.6.1.4.1.818.1.1.15.9.4ScalarupsConfigOutputFreqfifthread-writecurrentThe nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is n…
1.3.6.1.4.1.818.1.1.15.9.5ScalarupsConfigOutputVAfifthread-onlycurrentThe magnitude of the nominal Volt-Amp rating.(*)
1.3.6.1.4.1.818.1.1.15.9.6ScalarupsConfigOutputPowerfifthread-onlycurrentThe magnitude of the nominal true power rating.(*)
1.3.6.1.4.1.818.1.1.15.9.7ScalarupsConfigLowBattTimefifthread-writecurrentThe value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the …
1.3.6.1.4.1.818.1.1.15.9.8ScalarupsConfigAudibleStatusfifthread-writecurrentThe requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this …
1.3.6.1.4.1.818.1.1.15.9.9ScalarupsConfigLowVoltageTransferPointfifthread-writecurrentThe minimum input line voltage allowed before the UPS system transfers to battery backup.(*)
1.3.6.1.4.1.818.1.1.15.9.10ScalarupsConfigHighVoltageTransferPointfifthread-writecurrentThe maximum line voltage allowed before the UPS system transfers to battery backup.(*)
1.3.6.1.4.1.818.1.1.15.9.11ScalarupsConfigBatteryCapacityfifthread-writecurrentThe installed battery capacity. This value is the 'factory'-value, not the value after calibration.
1.3.6.1.4.1.818.1.1.15.9.12ScalarupsConfigBatteryChargeCurrentfifthread-writecurrentThe maximum battery charge current, including external chargers.
1.3.6.1.4.1.818.1.1.15.9.13ScalarupsConfigNoLoadShutdownfifthread-writecurrentDis- or enable 'no load' shutdown from the contact interface.
1.3.6.1.4.1.818.1.1.15.9.14ScalarupsConfigStartDelayfifthread-writecurrentMinimum required autonomy time before the UPS may perform an autorestart.
1.3.6.1.4.1.818.1.1.15.10NodeupsGetSetfifth
1.3.6.1.4.1.818.1.1.15.10.1ScalarupsEventGetNextfifthread-writecurrentThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The val…
1.3.6.1.4.1.818.1.1.15.10.2ScalarupsEventGetPreviousfifthread-writecurrentThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The val…
1.3.6.1.4.1.818.1.1.15.10.3ScalarupsEventSetStartingTimeStampfifthread-writecurrentThe timestamp which is used as starting point for downloading events from the UPS event buffer
1.3.6.1.4.1.818.1.1.15.10.4ScalarupsEventRetreiveCurrentTimeStampfifthread-onlycurrentThe current timestamp is retreived from the UPS
1.3.6.1.4.1.818.1.1.15.10.5ScalarupsEventTableSizefifthread-onlycurrentThe number of entries in the event table. This object indicates the number of rows in the event table.
1.3.6.1.4.1.818.1.1.15.10.6TableupsEventFifthTablenot-accessiblecurrentA list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the…
1.3.6.1.4.1.818.1.1.15.10.6.1RowupsEventFifthEntrynot-accessiblecurrentAn entry containing information applicable to a particular event.
1.3.6.1.4.1.818.1.1.15.10.6.1.1ColumnupsEventLineIndexfifthnot-accessiblecurrentThe event line identifier.
1.3.6.1.4.1.818.1.1.15.10.6.1.2ColumnupsEventCodefifthread-onlycurrentThe event code in numerical format.
1.3.6.1.4.1.818.1.1.15.10.6.1.3ColumnupsEventStatusfifthread-onlycurrentThe status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status …
1.3.6.1.4.1.818.1.1.15.10.6.1.4ColumnupsEventTimefifthread-onlycurrentThe timestamp of the moment the event was generated.
1.3.6.1.4.1.818.1.1.15.10.7ScalarupsParametersReadfifthread-writecurrentThe number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value up…
1.3.6.1.4.1.818.1.1.15.10.8ScalarupsParametersWritefifthread-writecurrentThe number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be u…
1.3.6.1.4.1.818.1.1.15.10.9ScalarupsParametersStartAddressfifthread-writecurrentThe address which is used as starting point for downloading parameters from the UPS
1.3.6.1.4.1.818.1.1.15.10.10ScalarupsParameterTableSizefifthread-onlycurrentThe number of entries in the parameter table. This object indicates the number of rows in the parameter table.
1.3.6.1.4.1.818.1.1.15.10.11TableupsParameterFifthTablenot-accessiblecurrentA list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of t…
1.3.6.1.4.1.818.1.1.15.10.11.1RowupsParameterFifthEntrynot-accessiblecurrentAn entry containing information applicable to a particular parameter.
1.3.6.1.4.1.818.1.1.15.10.11.1.1ColumnupsParameterLineIndexfifthnot-accessiblecurrentThe parameter line identifier.
1.3.6.1.4.1.818.1.1.15.10.11.1.2ColumnupsParameterValuefifthread-writecurrentThe parameter value in numerical format.
1.3.6.1.4.1.818.1.1.15.10.12ScalarupsStatusfifthread-onlycurrentThe global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other comman…
1.3.6.1.4.1.818.1.1.15.10.13ScalarupsMainsStatisticsMBfailfifthread-onlycurrentCount of main bypass failures (>200 ms), since UPS installation.
1.3.6.1.4.1.818.1.1.15.10.14ScalarupsMainsStatisticsMRfailfifthread-onlycurrentCount of mains rectifier failures (>200 ms), since UPS installation.
1.3.6.1.4.1.818.1.1.15.10.15ScalarupsMainsStatisticsB2fifthread-onlycurrentCount of transients on the mains bypass (0..2 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.15.10.16ScalarupsMainsStatisticsB5fifthread-onlycurrentCount of transients on the mains bypass (2..5 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.15.10.17ScalarupsMainsStatisticsB10fifthread-onlycurrentCount of transients on the mains bypass (5..10 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.15.10.18ScalarupsMainsStatisticsB200fifthread-onlycurrentCount of transients on the mains bypass (10..200 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.15.10.19ScalarupsMainsStatisticsBypRelfifthread-onlycurrentBypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'.
1.3.6.1.4.1.818.1.1.15.10.20ScalarupsTimefifthread-writecurrentThe current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp for…
1.3.6.1.4.1.818.1.1.15.10.21ScalarupsRequestPermissionfifthread-writecurrentAn encrypted code is send to enable use of restricted write objects during a limited period of time.
1.3.6.1.4.1.818.1.1.15.10.22ScalarupsEventGetCodefifthread-writecurrentThe code which is used as starting point to downloading the events from the UPS event buffer.
1.3.6.1.4.1.818.1.1.15.10.23ScalarupsEventSpinLockfifthread-writecurrentA spin lock on the event subsystem.
1.3.6.1.4.1.818.1.1.15.10.24ScalarupsParameterSpinLockfifthread-writecurrentA spin lock on the parameters subsystem.
1.3.6.1.4.1.818.1.1.15.11NodegeUPSTrapsfifth
1.3.6.1.4.1.818.1.1.15.11.1NotificationupsTrapAlarmBatteryBadfifthcurrentOne or more batteries have been determined to require replacement.
1.3.6.1.4.1.818.1.1.15.11.2NotificationupsTrapAlarmOnBatteryfifthcurrentThe UPS is drawing power from the batteries.
1.3.6.1.4.1.818.1.1.15.11.3NotificationupsTrapAlarmLowBatteryfifthcurrentThe remaining battery run-time is less than or equal to upsConfigLowBattTime.
1.3.6.1.4.1.818.1.1.15.11.4NotificationupsTrapAlarmDepletedBatteryfifthcurrentThe UPS will be unable to sustain the present load when and if the utility power is lost)
1.3.6.1.4.1.818.1.1.15.11.5NotificationupsTrapAlarmTempBadfifthcurrentA temperature is out of tolerance.
1.3.6.1.4.1.818.1.1.15.11.6NotificationupsTrapAlarmInputBadfifthcurrentAn input condition is out of tolerance.
1.3.6.1.4.1.818.1.1.15.11.7NotificationupsTrapAlarmOutputBadfifthcurrentAn output condition (other than OutputOverload) is out of tolerance.
1.3.6.1.4.1.818.1.1.15.11.8NotificationupsTrapAlarmOutputOverloadfifthcurrentThe output load exceeds the UPS output capacity.
1.3.6.1.4.1.818.1.1.15.11.9NotificationupsTrapAlarmOnBypassfifthcurrentThe Bypass is presently engaged on the UPS.
1.3.6.1.4.1.818.1.1.15.11.10NotificationupsTrapAlarmBypassBadfifthcurrentThe Bypass is out of tolerance.
1.3.6.1.4.1.818.1.1.15.11.11NotificationupsTrapAlarmOutputOffAsRequestedfifthcurrentThe UPS has shutdown as requested, i.e., the output is off.
1.3.6.1.4.1.818.1.1.15.11.12NotificationupsTrapAlarmUpsOffAsRequestedfifthcurrentThe entire UPS has shutdown as commanded.
1.3.6.1.4.1.818.1.1.15.11.13NotificationupsTrapAlarmChargerFailedfifthcurrentAn uncorrected problem has been detected within the UPS charger subsystem.
1.3.6.1.4.1.818.1.1.15.11.14NotificationupsTrapAlarmUpsOutputOfffifthcurrentThe output of the UPS is in the off state.
1.3.6.1.4.1.818.1.1.15.11.15NotificationupsTrapAlarmUpsSystemOfffifthcurrentThe UPS system is in the off state.
1.3.6.1.4.1.818.1.1.15.11.16NotificationupsTrapAlarmFanFailurefifthcurrentThe failure of one or more fans in the UPS has been detected.
1.3.6.1.4.1.818.1.1.15.11.17NotificationupsTrapAlarmFuseFailurefifthcurrentThe failure of one or more fuses has been detected.
1.3.6.1.4.1.818.1.1.15.11.18NotificationupsTrapAlarmGeneralFaultfifthcurrentA general fault in the UPS has been detected.
1.3.6.1.4.1.818.1.1.15.11.19NotificationupsTrapAlarmDiagnosticTestFailedfifthcurrentThe result of the last diagnostic test indicates a failure.
1.3.6.1.4.1.818.1.1.15.11.20NotificationupsTrapAlarmCommunicationsLostfifthcurrentA problem has been encountered in the communication between the agent and the UPS.
1.3.6.1.4.1.818.1.1.15.11.21NotificationupsTrapAlarmAwaitingPowerfifthcurrentThe UPS output is off and the UPS is awaiting the return of the input power (*).
1.3.6.1.4.1.818.1.1.15.11.22NotificationupsTrapAlarmShutdownPendingfifthcurrentA upsShutdownAfterDelay countdown is underway.
1.3.6.1.4.1.818.1.1.15.11.23NotificationupsTrapAlarmShutdownImminentfifthcurrentThe UPS will turn off power to the load in less than 5 fifths; this may be either a timed shutdown or a low battery shutdown.
1.3.6.1.4.1.818.1.1.15.11.24NotificationupsTrapAlarmTestInProgressfifthcurrentA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of …
1.3.6.1.4.1.818.1.1.15.11.25NotificationupsTrapAlarmReceptacleOfffifthcurrentA receptacle has been switched off.
1.3.6.1.4.1.818.1.1.15.11.26NotificationupsTrapAlarmHighspeedBusFailurefifthcurrentA problem on the Highspeed Bus communication is detected.
1.3.6.1.4.1.818.1.1.15.11.27NotificationupsTrapAlarmHighspeedBusJACRCFailurefifthcurrentA High Speed Bus CRC failure on Bus JA is detected.
1.3.6.1.4.1.818.1.1.15.11.28NotificationupsTrapAlarmConnectivityBusFailurefifthcurrentA problem on the Connectivity Bus communication is detected
1.3.6.1.4.1.818.1.1.15.11.29NotificationupsTrapAlarmHighspeedBusJBCRCFailurefifthcurrentA CRC failure on the Highspeed Bus JB is detected.
1.3.6.1.4.1.818.1.1.15.11.30NotificationupsTrapAlarmCurrentSharingFailurefifthcurrentAn high current sharing on the parallel system is detected.
1.3.6.1.4.1.818.1.1.15.11.31NotificationupsTrapAlarmDCRippleFailurefifthcurrentAn high ripple voltage on his DC link is detected.
1.3.6.1.4.1.818.1.1.15.11.33NotificationupsTrapAlarmBatteryBadRestoredfifthcurrentA Battery bad condition is restored.
1.3.6.1.4.1.818.1.1.15.11.34NotificationupsTrapAlarmOnBatteryRestoredfifthcurrentThe UPS is drawing power from mains again.
1.3.6.1.4.1.818.1.1.15.11.35NotificationupsTrapAlarmLowBatteryRestoredfifthcurrentA Low Battery condition is restored.
1.3.6.1.4.1.818.1.1.15.11.36NotificationupsTrapAlarmDepletedBatteryRestoredfifthcurrentA Depleted Battery condition is restored.
1.3.6.1.4.1.818.1.1.15.11.37NotificationupsTrapAlarmTempBadRestoredfifthcurrentA bad temperature condition is restored.
1.3.6.1.4.1.818.1.1.15.11.38NotificationupsTrapAlarmInputBadRestoredfifthcurrentAn input bad condition is restored.
1.3.6.1.4.1.818.1.1.15.11.39NotificationupsTrapAlarmOutputBadRestoredfifthcurrentAn output bad condition is restored.
1.3.6.1.4.1.818.1.1.15.11.40NotificationupsTrapAlarmOutputOverloadRestoredfifthcurrentAn output overload condition is restored.
1.3.6.1.4.1.818.1.1.15.11.41NotificationupsTrapAlarmOnBypassRestoredfifthcurrentAn On Bypass condition is restored.
1.3.6.1.4.1.818.1.1.15.11.42NotificationupsTrapAlarmBypassBadRestoredfifthcurrentA Bypass bad condition is restored.
1.3.6.1.4.1.818.1.1.15.11.43NotificationupsTrapAlarmOutputOffAsRequestedRestoredfifthcurrentA request shutdown has been restored.
1.3.6.1.4.1.818.1.1.15.11.44NotificationupsTrapAlarmUpsOffAsRequestedRestoredfifthcurrentA entire UPS command has been restored.
1.3.6.1.4.1.818.1.1.15.11.45NotificationupsTrapAlarmChargerFailedRestoredfifthcurrentA Charger Failer condition is restored.
1.3.6.1.4.1.818.1.1.15.11.46NotificationupsTrapAlarmUpsOutputOnfifthcurrentThe output of the UPS switched in the on state.
1.3.6.1.4.1.818.1.1.15.11.47NotificationupsTrapAlarmUpsSystemOnfifthcurrentThe UPS system is switched in the on state.
1.3.6.1.4.1.818.1.1.15.11.48NotificationupsTrapAlarmFanFailureRestoredfifthcurrentA Fan failure condition is restored.
1.3.6.1.4.1.818.1.1.15.11.49NotificationupsTrapAlarmFuseFailureRestoredfifthcurrentA Fuse failure condition is restored.
1.3.6.1.4.1.818.1.1.15.11.50NotificationupsTrapAlarmGeneralFaultRestoredfifthcurrentA general fault is restored.
1.3.6.1.4.1.818.1.1.15.11.51NotificationupsTrapAlarmDiagnosticTestFailedRestoredfifthcurrentA last diagnostic test indicates a failure is restored.
1.3.6.1.4.1.818.1.1.15.11.52NotificationupsTrapAlarmCommunicationsLostRestoredfifthcurrentA problem in the communication between the agent and the UPS is restored.
1.3.6.1.4.1.818.1.1.15.11.53NotificationupsTrapAlarmAwaitingPowerRestoredfifthcurrentA awaiting power condition is restored (*).
1.3.6.1.4.1.818.1.1.15.11.54NotificationupsTrapAlarmShutdownPendingRestoredfifthcurrentA upsShutdownAfterDelay countdown is restored.
1.3.6.1.4.1.818.1.1.15.11.55NotificationupsTrapAlarmShutdownImminentRestoredfifthcurrentA shutdown imminent condition is restored.
1.3.6.1.4.1.818.1.1.15.11.56NotificationupsTrapAlarmTestInProgressRestoredfifthcurrentThe test is in progress is terminated.
1.3.6.1.4.1.818.1.1.15.11.57NotificationupsTrapAlarmReceptacleOnfifthcurrentA receptacle has been switched on.
1.3.6.1.4.1.818.1.1.15.11.58NotificationupsTrapAlarmHighspeedBusRestorefifthcurrentA problem on the Highspeed Bus communication is restored.
1.3.6.1.4.1.818.1.1.15.11.59NotificationupsTrapAlarmHighspeedBusJACRCRestorefifthcurrentA CRC failure on the Highspeed Bus JA is restored.
1.3.6.1.4.1.818.1.1.15.11.60NotificationupsTrapAlarmConnectivityBusRestorefifthcurrentA problem on the Connectivity Bus communication is restored.
1.3.6.1.4.1.818.1.1.15.11.61NotificationupsTrapAlarmHighspeedBusJBCRCRestoredfifthcurrentA CRC failure on the Highspeed Bus JB is restored.
1.3.6.1.4.1.818.1.1.15.11.62NotificationupsTrapAlarmCurrentSharingRestoredfifthcurrentAn high current sharing on the parallel system is restored.
1.3.6.1.4.1.818.1.1.15.11.63NotificationupsTrapAlarmDCRippleRestoredfifthcurrentAn high ripple voltage on his DC link is restored.
1.3.6.1.4.1.818.1.1.15.11.129NotificationupsTrapAlarmValueLowfifthcurrentA measurement value reached a value below its low-level threshold.
1.3.6.1.4.1.818.1.1.15.11.130NotificationupsTrapAlarmValueHighfifthcurrentA measurement value reached a value higher than its high-level threshold.
1.3.6.1.4.1.818.1.1.15.11.133NotificationupsTrapAlarmValueLowRestoredfifthcurrentA ValueLow alarm condition is restored.
1.3.6.1.4.1.818.1.1.15.11.134NotificationupsTrapAlarmValueHighRestoredfifthcurrentA ValueHigh alarm condition is restored.
1.3.6.1.4.1.818.1.1.15.12NodeupsDiagnosticfifth
1.3.6.1.4.1.818.1.1.15.12.1ScalarupsDiagnosticBusJACommunicationStatusfifthread-onlycurrentBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA …
1.3.6.1.4.1.818.1.1.15.12.2ScalarupsDiagnosticBusJBCommunicationStatusfifthread-onlycurrentBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA …
1.3.6.1.4.1.818.1.1.15.12.3ScalarupsDiagnosticBatteryLifetimefifthread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.15.12.4ScalarupsDiagnosticFansLifetimefifthread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.15.12.5ScalarupsDiagnosticDCcapacitorsLifetimefifthread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.15.12.6ScalarupsDiagnosticACcapacitorsLifetimefifthread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.15.12.7ScalarupsDiagnosticGlobalServiceCheckfifthread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.16NodegeSixthUPS
1.3.6.1.4.1.818.1.1.16.1NodeupsIdentsixth
1.3.6.1.4.1.818.1.1.16.1.1ScalarupsIdentManufacturersixthread-onlycurrentThe name of the UPS manufacturer.(*)
1.3.6.1.4.1.818.1.1.16.1.2ScalarupsIdentModelsixthread-onlycurrentThe UPS Model designation.(*)
1.3.6.1.4.1.818.1.1.16.1.3ScalarupsIdentUPSSoftwareVersionsixthread-onlycurrentThe UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*)
1.3.6.1.4.1.818.1.1.16.1.4ScalarupsIdentAgentSoftwareVersionsixthread-onlycurrentThe UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*)
1.3.6.1.4.1.818.1.1.16.1.5ScalarupsIdentNamesixthread-writecurrentA string identifying the UPS. This object should be set by the administrator.(*)
1.3.6.1.4.1.818.1.1.16.1.6ScalarupsIdentAttachedDevicessixthread-writecurrentA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*)
1.3.6.1.4.1.818.1.1.16.1.7ScalarupsIdentUPSSerialNumbersixthread-onlycurrentThe UPS serial number
1.3.6.1.4.1.818.1.1.16.1.8ScalarupsIdentComProtVersionsixthread-onlycurrentThe IMV communication protocol version
1.3.6.1.4.1.818.1.1.16.1.9ScalarupsIdentOperatingTimesixthread-onlycurrentThe present value of the operating time. total 'on' time since UPS manufactured
1.3.6.1.4.1.818.1.1.16.2NodeupsBatterysixth
1.3.6.1.4.1.818.1.1.16.2.1ScalarupsBatteryStatussixthread-onlycurrentThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfi…
1.3.6.1.4.1.818.1.1.16.2.2ScalarupsSecondsOnBatterysixthread-onlycurrentIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res…
1.3.6.1.4.1.818.1.1.16.2.3ScalarupsEstimatedMinutesRemainingsixthread-onlycurrentAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and…
1.3.6.1.4.1.818.1.1.16.2.4ScalarupsEstimatedChargeRemainingsixthread-onlycurrentAn estimate of the battery charge remaining expressed as a percent of full charge.(*)
1.3.6.1.4.1.818.1.1.16.2.5ScalarupsBatteryVoltagesixthread-onlycurrentThe magnitude of the present battery voltage.(*)
1.3.6.1.4.1.818.1.1.16.2.6ScalarupsBatteryCurrentsixthread-onlycurrentThe present battery current.(*)
1.3.6.1.4.1.818.1.1.16.2.7ScalarupsBatteryTemperaturesixthread-onlycurrentThe ambient temperature at or near the UPS Battery casing.(*)
1.3.6.1.4.1.818.1.1.16.2.8ScalarupsBatteryRipplesixthread-onlycurrentThe present DC link RMS voltage ripple.(*)
1.3.6.1.4.1.818.1.1.16.3NodeupsInputsixth
1.3.6.1.4.1.818.1.1.16.3.1ScalarupsInputLineBadssixthread-onlycurrentA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the i…
1.3.6.1.4.1.818.1.1.16.3.2ScalarupsInputNumLinessixthread-onlycurrentThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*)
1.3.6.1.4.1.818.1.1.16.3.3TableupsInputSixthTablenot-accessiblecurrentA list of input table entries. The number of entries is given by the value of upsInputNumLines.(*)
1.3.6.1.4.1.818.1.1.16.3.3.1RowupsInputSixthEntrynot-accessiblecurrentAn entry containing information applicable to a particular input line.(*)
1.3.6.1.4.1.818.1.1.16.3.3.1.1ColumnupsInputLineIndexsixthnot-accessiblecurrentThe input line identifier.(*)
1.3.6.1.4.1.818.1.1.16.3.3.1.2ColumnupsInputFrequencysixthread-onlycurrentThe present input frequency.(*)
1.3.6.1.4.1.818.1.1.16.3.3.1.3ColumnupsInputVoltagesixthread-onlycurrentThe magnitude of the present input voltage.(*)
1.3.6.1.4.1.818.1.1.16.3.3.1.4ColumnupsInputCurrentsixthread-onlycurrentThe magnitude of the present input current.(*)
1.3.6.1.4.1.818.1.1.16.3.3.1.5ColumnupsInputTruePowersixthread-onlycurrentThe magnitude of the present input true power.(*)
1.3.6.1.4.1.818.1.1.16.3.3.1.6ColumnupsInputVoltageMinsixthread-onlycurrentThe lowest magnitude of the input voltage since last read out.
1.3.6.1.4.1.818.1.1.16.3.3.1.7ColumnupsInputVoltageMaxsixthread-onlycurrentThe highest magnitude of the input voltage since last read out.
1.3.6.1.4.1.818.1.1.16.4NodeupsOutputsixth
1.3.6.1.4.1.818.1.1.16.4.1ScalarupsOutputSourcesixthread-onlycurrentThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the…
1.3.6.1.4.1.818.1.1.16.4.2ScalarupsOutputFrequencysixthread-onlycurrentThe present output frequency.(*)
1.3.6.1.4.1.818.1.1.16.4.3ScalarupsOutputNumLinessixthread-onlycurrentThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*)
1.3.6.1.4.1.818.1.1.16.4.4TableupsOutputSixthTablenot-accessiblecurrentA list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*)
1.3.6.1.4.1.818.1.1.16.4.4.1RowupsOutputSixthEntrynot-accessiblecurrentAn entry containing information applicable to a particular output line.(*)
1.3.6.1.4.1.818.1.1.16.4.4.1.1ColumnupsOutputLineIndexsixthnot-accessiblecurrentThe output line identifier.(*)
1.3.6.1.4.1.818.1.1.16.4.4.1.2ColumnupsOutputVoltagesixthread-onlycurrentThe present output voltage.(*)
1.3.6.1.4.1.818.1.1.16.4.4.1.3ColumnupsOutputCurrentsixthread-onlycurrentThe present output current.(*)
1.3.6.1.4.1.818.1.1.16.4.4.1.4ColumnupsOutputPowersixthread-onlycurrentThe present output true power.(*)
1.3.6.1.4.1.818.1.1.16.4.4.1.5ColumnupsOutputPercentLoadsixthread-onlycurrentThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent…
1.3.6.1.4.1.818.1.1.16.4.4.1.6ColumnupsOutputPowerFactorsixthread-onlycurrentThe present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate …
1.3.6.1.4.1.818.1.1.16.4.4.1.7ColumnupsOutputPeakCurrentsixthread-onlycurrentThe present output peak current.(*)
1.3.6.1.4.1.818.1.1.16.4.4.1.8ColumnupsOutputShareCurrentsixthread-onlycurrentIn a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share…
1.3.6.1.4.1.818.1.1.16.5NodeupsBypasssixth
1.3.6.1.4.1.818.1.1.16.5.1ScalarupsBypassFrequencysixthread-onlycurrentThe present bypass frequency.(*)
1.3.6.1.4.1.818.1.1.16.5.2ScalarupsBypassNumLinessixthread-onlycurrentThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*)
1.3.6.1.4.1.818.1.1.16.5.3TableupsBypassSixthTablenot-accessiblecurrentA list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*)
1.3.6.1.4.1.818.1.1.16.5.3.1RowupsBypassSixthEntrynot-accessiblecurrentAn entry containing information applicable to a particular bypass input.(*)
1.3.6.1.4.1.818.1.1.16.5.3.1.1ColumnupsBypassLineIndexsixthnot-accessiblecurrentThe bypass line identifier.(*)
1.3.6.1.4.1.818.1.1.16.5.3.1.2ColumnupsBypassVoltagesixthread-onlycurrentThe present bypass voltage.(*)
1.3.6.1.4.1.818.1.1.16.5.3.1.3ColumnupsBypassCurrentsixthread-onlycurrentThe present bypass current.(*)
1.3.6.1.4.1.818.1.1.16.5.3.1.4ColumnupsBypassPowersixthread-onlycurrentThe present true power conveyed by the bypass.(*)
1.3.6.1.4.1.818.1.1.16.6NodeupsAlarmsixth
1.3.6.1.4.1.818.1.1.16.6.1ScalarupsAlarmsPresentsixthread-onlycurrentThe present number of active alarm conditions.(*)
1.3.6.1.4.1.818.1.1.16.6.2TableupsAlarmSixthTablenot-accessiblecurrentA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is …
1.3.6.1.4.1.818.1.1.16.6.2.1RowupsAlarmSixthEntrynot-accessiblecurrentAn entry containing information applicable to a particular alarm.(*)
1.3.6.1.4.1.818.1.1.16.6.2.1.1ColumnupsAlarmIdsixthnot-accessiblecurrentA unique identifier for an alarm condition. This value must remain constant.(*)
1.3.6.1.4.1.818.1.1.16.6.2.1.2ColumnupsAlarmDescrsixthread-onlycurrentA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con…
1.3.6.1.4.1.818.1.1.16.6.2.1.3ColumnupsAlarmTimesixthread-onlycurrentThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before ag…
1.3.6.1.4.1.818.1.1.16.6.3NodeupsWellKnownAlarmssixth
1.3.6.1.4.1.818.1.1.16.6.3.1IdentityupsAlarmBatteryBadsixthcurrentOne or more batteries have been determined to require replacement.(*)
1.3.6.1.4.1.818.1.1.16.6.3.2IdentityupsAlarmOnBatterysixthcurrentThe UPS is drawing power from the batteries.(*)
1.3.6.1.4.1.818.1.1.16.6.3.3IdentityupsAlarmLowBatterysixthcurrentThe remaining battery run-time is less than or equal to upsConfigLowBattTime.(*)
1.3.6.1.4.1.818.1.1.16.6.3.4IdentityupsAlarmDepletedBatterysixthcurrentThe UPS will be unable to sustain the present load when and if the utility power is lost.(*)
1.3.6.1.4.1.818.1.1.16.6.3.5IdentityupsAlarmTempBadsixthcurrentA temperature is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.16.6.3.6IdentityupsAlarmInputBadsixthcurrentAn input condition is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.16.6.3.7IdentityupsAlarmOutputBadsixthcurrentAn output condition (other than OutputOverload) is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.16.6.3.8IdentityupsAlarmOutputOverloadsixthcurrentThe output load exceeds the UPS output capacity.(*)
1.3.6.1.4.1.818.1.1.16.6.3.9IdentityupsAlarmOnBypasssixthcurrentThe Bypass is presently engaged on the UPS.(*)
1.3.6.1.4.1.818.1.1.16.6.3.10IdentityupsAlarmBypassBadsixthcurrentThe Bypass is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.16.6.3.11IdentityupsAlarmOutputOffAsRequestedsixthcurrentThe UPS has shutdown as requested, i.e., the output is off.(*)
1.3.6.1.4.1.818.1.1.16.6.3.12IdentityupsAlarmUpsOffAsRequestedsixthcurrentThe entire UPS has shutdown as commanded.(*)
1.3.6.1.4.1.818.1.1.16.6.3.13IdentityupsAlarmChargerFailedsixthcurrentAn uncorrected problem has been detected within the UPS charger subsystem.(*)
1.3.6.1.4.1.818.1.1.16.6.3.14IdentityupsAlarmUpsOutputOffsixthcurrentThe output of the UPS is in the off state.(*)
1.3.6.1.4.1.818.1.1.16.6.3.15IdentityupsAlarmUpsSystemOffsixthcurrentThe UPS system is in the off state.(*)
1.3.6.1.4.1.818.1.1.16.6.3.16IdentityupsAlarmFanFailuresixthcurrentThe failure of one or more fans in the UPS has been detected.(*)
1.3.6.1.4.1.818.1.1.16.6.3.17IdentityupsAlarmFuseFailuresixthcurrentThe failure of one or more fuses has been detected.(*)
1.3.6.1.4.1.818.1.1.16.6.3.18IdentityupsAlarmGeneralFaultsixthcurrentA general fault in the UPS has been detected.(*)
1.3.6.1.4.1.818.1.1.16.6.3.19IdentityupsAlarmDiagnosticTestFailedsixthcurrentThe result of the last diagnostic test indicates a failure.(*)
1.3.6.1.4.1.818.1.1.16.6.3.20IdentityupsAlarmCommunicationsLostsixthcurrentA problem has been encountered in the communications between the agent and the UPS.(*)
1.3.6.1.4.1.818.1.1.16.6.3.21IdentityupsAlarmAwaitingPowersixthcurrentThe UPS output is off and the UPS is awaiting the return of input power.(*)
1.3.6.1.4.1.818.1.1.16.6.3.22IdentityupsAlarmShutdownPendingsixthcurrentA upsShutdownAfterDelay countdown is underway.(*)
1.3.6.1.4.1.818.1.1.16.6.3.23IdentityupsAlarmShutdownImminentsixthcurrentThe UPS will turn off power to the load in less than 5 sixths; this may be either a timed shutdown or a low battery shutdown.(*)
1.3.6.1.4.1.818.1.1.16.6.3.24IdentityupsAlarmTestInProgresssixthcurrentA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of …
1.3.6.1.4.1.818.1.1.16.6.3.25IdentityupsAlarmReceptacleOffsixthcurrentThe receptacle are switch off
1.3.6.1.4.1.818.1.1.16.6.3.26IdentityupsAlarmHighSpeedBusFailuresixthcurrentA problem on the High Speed Bus communication is detected
1.3.6.1.4.1.818.1.1.16.6.3.27IdentityupsAlarmHighSpeedBusJACRCFailuresixthcurrentA High Speed Bus CRC failure on Bus JA is detected.
1.3.6.1.4.1.818.1.1.16.6.3.28IdentityupsAlarmConnectivityBusFailuresixthcurrentA problem on the Connectivity Bus communication is detected.
1.3.6.1.4.1.818.1.1.16.6.3.29IdentityupsAlarmHighSpeedBusJBCRCFailuresixthcurrentA High Speed Bus CRC failure on Bus JB is detected.
1.3.6.1.4.1.818.1.1.16.6.3.30IdentityupsAlarmCurrentSharingsixthcurrentThe UPS detects an high current sharing on the parallel system.
1.3.6.1.4.1.818.1.1.16.6.3.31IdentityupsAlarmDCRipplesixthcurrentThe UPS detects an high ripple voltage on his DC link.
1.3.6.1.4.1.818.1.1.16.6.4ScalarupsAlarmMaskAsixthread-onlycurrentSpecifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' com…
1.3.6.1.4.1.818.1.1.16.7NodeupsTestsixth
1.3.6.1.4.1.818.1.1.16.7.1ScalarupsTestIdsixthread-writecurrentThe test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this docu…
1.3.6.1.4.1.818.1.1.16.7.2ScalarupsTestSpinLocksixthread-writecurrentA spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress a…
1.3.6.1.4.1.818.1.1.16.7.3ScalarupsTestResultsSummarysixthread-onlycurrentThe results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test complete…
1.3.6.1.4.1.818.1.1.16.7.4ScalarupsTestResultsDetailsixthread-onlycurrentAdditional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*)
1.3.6.1.4.1.818.1.1.16.7.5ScalarupsTestStartTimesixthread-onlycurrentThe value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of…
1.3.6.1.4.1.818.1.1.16.7.6ScalarupsTestElapsedTimesixthread-onlycurrentThe amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of …
1.3.6.1.4.1.818.1.1.16.7.7NodeupsWellKnownTestssixth
1.3.6.1.4.1.818.1.1.16.7.7.1IdentityupsTestNoTestsInitiatedsixthcurrentNo tests have been initiated and no test is in progress.(*)
1.3.6.1.4.1.818.1.1.16.7.7.2IdentityupsTestAbortTestInProgresssixthcurrentThe test in progress is to be aborted / the test in progress was aborted.(*)
1.3.6.1.4.1.818.1.1.16.7.7.3IdentityupsTestGeneralSystemsTestsixthcurrentThe manufacturer's standard test of UPS device systems.(*)
1.3.6.1.4.1.818.1.1.16.7.7.4IdentityupsTestQuickBatteryTestsixthcurrentA test that is sufficient to determine if the battery needs replacement.(*)
1.3.6.1.4.1.818.1.1.16.7.7.5IdentityupsTestDeepBatteryCalibrationsixthcurrentThe system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high deg…
1.3.6.1.4.1.818.1.1.16.8NodeupsControlsixth
1.3.6.1.4.1.818.1.1.16.8.1ScalarupsShutdownTypesixthread-writecurrentThis object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reach…
1.3.6.1.4.1.818.1.1.16.8.2ScalarupsShutdownAfterDelaysixthread-writecurrentSetting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdo…
1.3.6.1.4.1.818.1.1.16.8.3ScalarupsStartupAfterDelaysixthread-writecurrentSetting this object will start the output after the indicated number of sixths, including starting the UPS, if necessary. Setting this object to 0 will cause t…
1.3.6.1.4.1.818.1.1.16.8.4ScalarupsRebootWithDurationsixthread-writecurrentSetting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the ti…
1.3.6.1.4.1.818.1.1.16.8.5ScalarupsAutoRestartsixthread-writecurrentSetting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutd…
1.3.6.1.4.1.818.1.1.16.8.6ScalarupsReceptaclesNumsixthread-onlycurrentThe number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table.
1.3.6.1.4.1.818.1.1.16.8.7TableupsReceptacleSixthTablenot-accessiblecurrentA list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum.
1.3.6.1.4.1.818.1.1.16.8.7.1RowupsReceptacleSixthEntrynot-accessiblecurrentAn entry containing information applicable to a particular receptacle.
1.3.6.1.4.1.818.1.1.16.8.7.1.1ColumnupsReceptacleLineIndexsixthnot-accessiblecurrentThe receptacle line identifier.
1.3.6.1.4.1.818.1.1.16.8.7.1.2ColumnupsReceptacleOnOffsixthread-writecurrentThe present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptac…
1.3.6.1.4.1.818.1.1.16.8.8ScalarupsUPSModesixthread-writecurrentThe operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transfor…
1.3.6.1.4.1.818.1.1.16.8.9ScalarupsRectifierOnOffsixthread-writecurrentThe present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier …
1.3.6.1.4.1.818.1.1.16.8.10ScalarupsBatteryChargeMethodsixthread-writecurrentThe present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this objec…
1.3.6.1.4.1.818.1.1.16.8.11ScalarupsInverterOnOffsixthread-writecurrentThe present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off…
1.3.6.1.4.1.818.1.1.16.8.12ScalarupsBypassOnOffsixthread-writecurrentThe present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If…
1.3.6.1.4.1.818.1.1.16.8.13ScalarupsLoadSourcesixthread-writecurrentThe present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will …
1.3.6.1.4.1.818.1.1.16.9NodeupsConfigsixth
1.3.6.1.4.1.818.1.1.16.9.1ScalarupsConfigInputVoltagesixthread-writecurrentThe magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a v…
1.3.6.1.4.1.818.1.1.16.9.2ScalarupsConfigInputFreqsixthread-writecurrentThe nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is no…
1.3.6.1.4.1.818.1.1.16.9.3ScalarupsConfigOutputVoltagesixthread-writecurrentThe magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a …
1.3.6.1.4.1.818.1.1.16.9.4ScalarupsConfigOutputFreqsixthread-writecurrentThe nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is n…
1.3.6.1.4.1.818.1.1.16.9.5ScalarupsConfigOutputVAsixthread-onlycurrentThe magnitude of the nominal Volt-Amp rating.(*)
1.3.6.1.4.1.818.1.1.16.9.6ScalarupsConfigOutputPowersixthread-onlycurrentThe magnitude of the nominal true power rating.(*)
1.3.6.1.4.1.818.1.1.16.9.7ScalarupsConfigLowBattTimesixthread-writecurrentThe value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the …
1.3.6.1.4.1.818.1.1.16.9.8ScalarupsConfigAudibleStatussixthread-writecurrentThe requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this …
1.3.6.1.4.1.818.1.1.16.9.9ScalarupsConfigLowVoltageTransferPointsixthread-writecurrentThe minimum input line voltage allowed before the UPS system transfers to battery backup.(*)
1.3.6.1.4.1.818.1.1.16.9.10ScalarupsConfigHighVoltageTransferPointsixthread-writecurrentThe maximum line voltage allowed before the UPS system transfers to battery backup.(*)
1.3.6.1.4.1.818.1.1.16.9.11ScalarupsConfigBatteryCapacitysixthread-writecurrentThe installed battery capacity. This value is the 'factory'-value, not the value after calibration.
1.3.6.1.4.1.818.1.1.16.9.12ScalarupsConfigBatteryChargeCurrentsixthread-writecurrentThe maximum battery charge current, including external chargers.
1.3.6.1.4.1.818.1.1.16.9.13ScalarupsConfigNoLoadShutdownsixthread-writecurrentDis- or enable 'no load' shutdown from the contact interface.
1.3.6.1.4.1.818.1.1.16.9.14ScalarupsConfigStartDelaysixthread-writecurrentMinimum required autonomy time before the UPS may perform an autorestart.
1.3.6.1.4.1.818.1.1.16.10NodeupsGetSetsixth
1.3.6.1.4.1.818.1.1.16.10.1ScalarupsEventGetNextsixthread-writecurrentThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The val…
1.3.6.1.4.1.818.1.1.16.10.2ScalarupsEventGetPrevioussixthread-writecurrentThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The val…
1.3.6.1.4.1.818.1.1.16.10.3ScalarupsEventSetStartingTimeStampsixthread-writecurrentThe timestamp which is used as starting point for downloading events from the UPS event buffer
1.3.6.1.4.1.818.1.1.16.10.4ScalarupsEventRetreiveCurrentTimeStampsixthread-onlycurrentThe current timestamp is retreived from the UPS
1.3.6.1.4.1.818.1.1.16.10.5ScalarupsEventTableSizesixthread-onlycurrentThe number of entries in the event table. This object indicates the number of rows in the event table.
1.3.6.1.4.1.818.1.1.16.10.6TableupsEventSixthTablenot-accessiblecurrentA list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the…
1.3.6.1.4.1.818.1.1.16.10.6.1RowupsEventSixthEntrynot-accessiblecurrentAn entry containing information applicable to a particular event.
1.3.6.1.4.1.818.1.1.16.10.6.1.1ColumnupsEventLineIndexsixthnot-accessiblecurrentThe event line identifier.
1.3.6.1.4.1.818.1.1.16.10.6.1.2ColumnupsEventCodesixthread-onlycurrentThe event code in numerical format.
1.3.6.1.4.1.818.1.1.16.10.6.1.3ColumnupsEventStatussixthread-onlycurrentThe status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status …
1.3.6.1.4.1.818.1.1.16.10.6.1.4ColumnupsEventTimesixthread-onlycurrentThe timestamp of the moment the event was generated.
1.3.6.1.4.1.818.1.1.16.10.7ScalarupsParametersReadsixthread-writecurrentThe number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value up…
1.3.6.1.4.1.818.1.1.16.10.8ScalarupsParametersWritesixthread-writecurrentThe number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be u…
1.3.6.1.4.1.818.1.1.16.10.9ScalarupsParametersStartAddresssixthread-writecurrentThe address which is used as starting point for downloading parameters from the UPS
1.3.6.1.4.1.818.1.1.16.10.10ScalarupsParameterTableSizesixthread-onlycurrentThe number of entries in the parameter table. This object indicates the number of rows in the parameter table.
1.3.6.1.4.1.818.1.1.16.10.11TableupsParameterSixthTablenot-accessiblecurrentA list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of t…
1.3.6.1.4.1.818.1.1.16.10.11.1RowupsParameterSixthEntrynot-accessiblecurrentAn entry containing information applicable to a particular parameter.
1.3.6.1.4.1.818.1.1.16.10.11.1.1ColumnupsParameterLineIndexsixthnot-accessiblecurrentThe parameter line identifier.
1.3.6.1.4.1.818.1.1.16.10.11.1.2ColumnupsParameterValuesixthread-writecurrentThe parameter value in numerical format.
1.3.6.1.4.1.818.1.1.16.10.12ScalarupsStatussixthread-onlycurrentThe global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other comman…
1.3.6.1.4.1.818.1.1.16.10.13ScalarupsMainsStatisticsMBfailsixthread-onlycurrentCount of main bypass failures (>200 ms), since UPS installation.
1.3.6.1.4.1.818.1.1.16.10.14ScalarupsMainsStatisticsMRfailsixthread-onlycurrentCount of mains rectifier failures (>200 ms), since UPS installation.
1.3.6.1.4.1.818.1.1.16.10.15ScalarupsMainsStatisticsB2sixthread-onlycurrentCount of transients on the mains bypass (0..2 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.16.10.16ScalarupsMainsStatisticsB5sixthread-onlycurrentCount of transients on the mains bypass (2..5 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.16.10.17ScalarupsMainsStatisticsB10sixthread-onlycurrentCount of transients on the mains bypass (5..10 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.16.10.18ScalarupsMainsStatisticsB200sixthread-onlycurrentCount of transients on the mains bypass (10..200 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.16.10.19ScalarupsMainsStatisticsBypRelsixthread-onlycurrentBypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'.
1.3.6.1.4.1.818.1.1.16.10.20ScalarupsTimesixthread-writecurrentThe current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp for…
1.3.6.1.4.1.818.1.1.16.10.21ScalarupsRequestPermissionsixthread-writecurrentAn encrypted code is send to enable use of restricted write objects during a limited period of time.
1.3.6.1.4.1.818.1.1.16.10.22ScalarupsEventGetCodesixthread-writecurrentThe code which is used as starting point to downloading the events from the UPS event buffer.
1.3.6.1.4.1.818.1.1.16.10.23ScalarupsEventSpinLocksixthread-writecurrentA spin lock on the event subsystem.
1.3.6.1.4.1.818.1.1.16.10.24ScalarupsParameterSpinLocksixthread-writecurrentA spin lock on the parameters subsystem.
1.3.6.1.4.1.818.1.1.16.11NodegeUPSTrapssixth
1.3.6.1.4.1.818.1.1.16.11.1NotificationupsTrapAlarmBatteryBadsixthcurrentOne or more batteries have been determined to require replacement.
1.3.6.1.4.1.818.1.1.16.11.2NotificationupsTrapAlarmOnBatterysixthcurrentThe UPS is drawing power from the batteries.
1.3.6.1.4.1.818.1.1.16.11.3NotificationupsTrapAlarmLowBatterysixthcurrentThe remaining battery run-time is less than or equal to upsConfigLowBattTime.
1.3.6.1.4.1.818.1.1.16.11.4NotificationupsTrapAlarmDepletedBatterysixthcurrentThe UPS will be unable to sustain the present load when and if the utility power is lost)
1.3.6.1.4.1.818.1.1.16.11.5NotificationupsTrapAlarmTempBadsixthcurrentA temperature is out of tolerance.
1.3.6.1.4.1.818.1.1.16.11.6NotificationupsTrapAlarmInputBadsixthcurrentAn input condition is out of tolerance.
1.3.6.1.4.1.818.1.1.16.11.7NotificationupsTrapAlarmOutputBadsixthcurrentAn output condition (other than OutputOverload) is out of tolerance.
1.3.6.1.4.1.818.1.1.16.11.8NotificationupsTrapAlarmOutputOverloadsixthcurrentThe output load exceeds the UPS output capacity.
1.3.6.1.4.1.818.1.1.16.11.9NotificationupsTrapAlarmOnBypasssixthcurrentThe Bypass is presently engaged on the UPS.
1.3.6.1.4.1.818.1.1.16.11.10NotificationupsTrapAlarmBypassBadsixthcurrentThe Bypass is out of tolerance.
1.3.6.1.4.1.818.1.1.16.11.11NotificationupsTrapAlarmOutputOffAsRequestedsixthcurrentThe UPS has shutdown as requested, i.e., the output is off.
1.3.6.1.4.1.818.1.1.16.11.12NotificationupsTrapAlarmUpsOffAsRequestedsixthcurrentThe entire UPS has shutdown as commanded.
1.3.6.1.4.1.818.1.1.16.11.13NotificationupsTrapAlarmChargerFailedsixthcurrentAn uncorrected problem has been detected within the UPS charger subsystem.
1.3.6.1.4.1.818.1.1.16.11.14NotificationupsTrapAlarmUpsOutputOffsixthcurrentThe output of the UPS is in the off state.
1.3.6.1.4.1.818.1.1.16.11.15NotificationupsTrapAlarmUpsSystemOffsixthcurrentThe UPS system is in the off state.
1.3.6.1.4.1.818.1.1.16.11.16NotificationupsTrapAlarmFanFailuresixthcurrentThe failure of one or more fans in the UPS has been detected.
1.3.6.1.4.1.818.1.1.16.11.17NotificationupsTrapAlarmFuseFailuresixthcurrentThe failure of one or more fuses has been detected.
1.3.6.1.4.1.818.1.1.16.11.18NotificationupsTrapAlarmGeneralFaultsixthcurrentA general fault in the UPS has been detected.
1.3.6.1.4.1.818.1.1.16.11.19NotificationupsTrapAlarmDiagnosticTestFailedsixthcurrentThe result of the last diagnostic test indicates a failure.
1.3.6.1.4.1.818.1.1.16.11.20NotificationupsTrapAlarmCommunicationsLostsixthcurrentA problem has been encountered in the communication between the agent and the UPS.
1.3.6.1.4.1.818.1.1.16.11.21NotificationupsTrapAlarmAwaitingPowersixthcurrentThe UPS output is off and the UPS is awaiting the return of the input power (*).
1.3.6.1.4.1.818.1.1.16.11.22NotificationupsTrapAlarmShutdownPendingsixthcurrentA upsShutdownAfterDelay countdown is underway.
1.3.6.1.4.1.818.1.1.16.11.23NotificationupsTrapAlarmShutdownImminentsixthcurrentThe UPS will turn off power to the load in less than 5 sixths; this may be either a timed shutdown or a low battery shutdown.
1.3.6.1.4.1.818.1.1.16.11.24NotificationupsTrapAlarmTestInProgresssixthcurrentA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of …
1.3.6.1.4.1.818.1.1.16.11.25NotificationupsTrapAlarmReceptacleOffsixthcurrentA receptacle has been switched off.
1.3.6.1.4.1.818.1.1.16.11.26NotificationupsTrapAlarmHighspeedBusFailuresixthcurrentA problem on the Highspeed Bus communication is detected.
1.3.6.1.4.1.818.1.1.16.11.27NotificationupsTrapAlarmHighspeedBusJACRCFailuresixthcurrentA CRC failure on the Highspeed Bus JA is detected.
1.3.6.1.4.1.818.1.1.16.11.28NotificationupsTrapAlarmConnectivityBusFailuresixthcurrentA problem on the Connectivity Bus communication is detected.
1.3.6.1.4.1.818.1.1.16.11.29NotificationupsTrapAlarmHighspeedBusJBCRCFailuresixthcurrentA CRC failure on the Highspeed Bus JB is detected.
1.3.6.1.4.1.818.1.1.16.11.30NotificationupsTrapAlarmCurrentSharingFailuresixthcurrentAn high current sharing on the parallel system is detected.
1.3.6.1.4.1.818.1.1.16.11.31NotificationupsTrapAlarmDCRippleFailuresixthcurrentAn high ripple voltage on his DC link is detected.
1.3.6.1.4.1.818.1.1.16.11.33NotificationupsTrapAlarmBatteryBadRestoredsixthcurrentA Battery bad condition is restored.
1.3.6.1.4.1.818.1.1.16.11.34NotificationupsTrapAlarmOnBatteryRestoredsixthcurrentThe UPS is drawing power from mains again.
1.3.6.1.4.1.818.1.1.16.11.35NotificationupsTrapAlarmLowBatteryRestoredsixthcurrentA Low Battery condition is restored.
1.3.6.1.4.1.818.1.1.16.11.36NotificationupsTrapAlarmDepletedBatteryRestoredsixthcurrentA Depleted Battery condition is restored.
1.3.6.1.4.1.818.1.1.16.11.37NotificationupsTrapAlarmTempBadRestoredsixthcurrentA bad temperature condition is restored.
1.3.6.1.4.1.818.1.1.16.11.38NotificationupsTrapAlarmInputBadRestoredsixthcurrentAn input bad condition is restored.
1.3.6.1.4.1.818.1.1.16.11.39NotificationupsTrapAlarmOutputBadRestoredsixthcurrentAn output bad condition is restored.
1.3.6.1.4.1.818.1.1.16.11.40NotificationupsTrapAlarmOutputOverloadRestoredsixthcurrentAn output overload condition is restored.
1.3.6.1.4.1.818.1.1.16.11.41NotificationupsTrapAlarmOnBypassRestoredsixthcurrentAn On Bypass condition is restored.
1.3.6.1.4.1.818.1.1.16.11.42NotificationupsTrapAlarmBypassBadRestoredsixthcurrentA Bypass bad condition is restored.
1.3.6.1.4.1.818.1.1.16.11.43NotificationupsTrapAlarmOutputOffAsRequestedRestoredsixthcurrentA request shutdown has been restored.
1.3.6.1.4.1.818.1.1.16.11.44NotificationupsTrapAlarmUpsOffAsRequestedRestoredsixthcurrentA entire UPS command has been restored.
1.3.6.1.4.1.818.1.1.16.11.45NotificationupsTrapAlarmChargerFailedRestoredsixthcurrentA Charger Failer condition is restored.
1.3.6.1.4.1.818.1.1.16.11.46NotificationupsTrapAlarmUpsOutputOnsixthcurrentThe output of the UPS switched in the on state.
1.3.6.1.4.1.818.1.1.16.11.47NotificationupsTrapAlarmUpsSystemOnsixthcurrentThe UPS system is switched in the on state.
1.3.6.1.4.1.818.1.1.16.11.48NotificationupsTrapAlarmFanFailureRestoredsixthcurrentA Fan failure condition is restored.
1.3.6.1.4.1.818.1.1.16.11.49NotificationupsTrapAlarmFuseFailureRestoredsixthcurrentA Fuse failure condition is restored.
1.3.6.1.4.1.818.1.1.16.11.50NotificationupsTrapAlarmGeneralFaultRestoredsixthcurrentA general fault is restored.
1.3.6.1.4.1.818.1.1.16.11.51NotificationupsTrapAlarmDiagnosticTestFailedRestoredsixthcurrentA last diagnostic test indicates a failure is restored.
1.3.6.1.4.1.818.1.1.16.11.52NotificationupsTrapAlarmCommunicationsLostRestoredsixthcurrentA problem in the communication between the agent and the UPS is restored.
1.3.6.1.4.1.818.1.1.16.11.53NotificationupsTrapAlarmAwaitingPowerRestoredsixthcurrentA awaiting power condition is restored (*).
1.3.6.1.4.1.818.1.1.16.11.54NotificationupsTrapAlarmShutdownPendingRestoredsixthcurrentA upsShutdownAfterDelay countdown is restored.
1.3.6.1.4.1.818.1.1.16.11.55NotificationupsTrapAlarmShutdownImminentRestoredsixthcurrentA shutdown imminent condition is restored.
1.3.6.1.4.1.818.1.1.16.11.56NotificationupsTrapAlarmTestInProgressRestoredsixthcurrentThe test is in progress is terminated.
1.3.6.1.4.1.818.1.1.16.11.57NotificationupsTrapAlarmReceptacleOnsixthcurrentA receptacle has been switched on.
1.3.6.1.4.1.818.1.1.16.11.58NotificationupsTrapAlarmHighspeedBusRestoresixthcurrentA problem on the Highspeed Bus communication is restored.
1.3.6.1.4.1.818.1.1.16.11.59NotificationupsTrapAlarmHighspeedBusJACRCRestoresixthcurrentA CRC failure on the Highspeed Bus JA is restored.
1.3.6.1.4.1.818.1.1.16.11.60NotificationupsTrapAlarmConnectivityBusRestoresixthcurrentA problem on the Connectivity Bus communication is restored.
1.3.6.1.4.1.818.1.1.16.11.61NotificationupsTrapAlarmHighspeedBusJBCRCRestoredsixthcurrentA CRC failure on the Highspeed Bus JB is restored.
1.3.6.1.4.1.818.1.1.16.11.62NotificationupsTrapAlarmCurrentSharingRestoredsixthcurrentAn high current sharing on the parallel system is restored.
1.3.6.1.4.1.818.1.1.16.11.63NotificationupsTrapAlarmDCRippleRestoredsixthcurrentAn high ripple voltage on his DC link is restored.
1.3.6.1.4.1.818.1.1.16.11.129NotificationupsTrapAlarmValueLowsixthcurrentA measurement value reached a value below its low-level threshold.
1.3.6.1.4.1.818.1.1.16.11.130NotificationupsTrapAlarmValueHighsixthcurrentA measurement value reached a value higher than its high-level threshold.
1.3.6.1.4.1.818.1.1.16.11.133NotificationupsTrapAlarmValueLowRestoredsixthcurrentA ValueLow alarm condition is restored.
1.3.6.1.4.1.818.1.1.16.11.134NotificationupsTrapAlarmValueHighRestoredsixthcurrentA ValueHigh alarm condition is restored.
1.3.6.1.4.1.818.1.1.16.12NodeupsDiagnosticsixth
1.3.6.1.4.1.818.1.1.16.12.1ScalarupsDiagnosticBusJACommunicationStatussixthread-onlycurrentBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA …
1.3.6.1.4.1.818.1.1.16.12.2ScalarupsDiagnosticBusJBCommunicationStatussixthread-onlycurrentBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA …
1.3.6.1.4.1.818.1.1.16.12.3ScalarupsDiagnosticBatteryLifetimesixthread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.16.12.4ScalarupsDiagnosticFansLifetimesixthread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.16.12.5ScalarupsDiagnosticDCcapacitorsLifetimesixthread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.16.12.6ScalarupsDiagnosticACcapacitorsLifetimesixthread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.16.12.7ScalarupsDiagnosticGlobalServiceChecksixthread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.17NodegeSeventhUPS
1.3.6.1.4.1.818.1.1.17.1NodeupsIdentseventh
1.3.6.1.4.1.818.1.1.17.1.1ScalarupsIdentManufacturerseventhread-onlycurrentThe name of the UPS manufacturer.(*)
1.3.6.1.4.1.818.1.1.17.1.2ScalarupsIdentModelseventhread-onlycurrentThe UPS Model designation.(*)
1.3.6.1.4.1.818.1.1.17.1.3ScalarupsIdentUPSSoftwareVersionseventhread-onlycurrentThe UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*)
1.3.6.1.4.1.818.1.1.17.1.4ScalarupsIdentAgentSoftwareVersionseventhread-onlycurrentThe UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*)
1.3.6.1.4.1.818.1.1.17.1.5ScalarupsIdentNameseventhread-writecurrentA string identifying the UPS. This object should be set by the administrator.(*)
1.3.6.1.4.1.818.1.1.17.1.6ScalarupsIdentAttachedDevicesseventhread-writecurrentA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*)
1.3.6.1.4.1.818.1.1.17.1.7ScalarupsIdentUPSSerialNumberseventhread-onlycurrentThe UPS serial number
1.3.6.1.4.1.818.1.1.17.1.8ScalarupsIdentComProtVersionseventhread-onlycurrentThe IMV communication protocol version
1.3.6.1.4.1.818.1.1.17.1.9ScalarupsIdentOperatingTimeseventhread-onlycurrentThe present value of the operating time. total 'on' time since UPS manufactured
1.3.6.1.4.1.818.1.1.17.2NodeupsBatteryseventh
1.3.6.1.4.1.818.1.1.17.2.1ScalarupsBatteryStatusseventhread-onlycurrentThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfi…
1.3.6.1.4.1.818.1.1.17.2.2ScalarupsSecondsOnBatteryseventhread-onlycurrentIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res…
1.3.6.1.4.1.818.1.1.17.2.3ScalarupsEstimatedMinutesRemainingseventhread-onlycurrentAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and…
1.3.6.1.4.1.818.1.1.17.2.4ScalarupsEstimatedChargeRemainingseventhread-onlycurrentAn estimate of the battery charge remaining expressed as a percent of full charge.(*)
1.3.6.1.4.1.818.1.1.17.2.5ScalarupsBatteryVoltageseventhread-onlycurrentThe magnitude of the present battery voltage.(*)
1.3.6.1.4.1.818.1.1.17.2.6ScalarupsBatteryCurrentseventhread-onlycurrentThe present battery current.(*)
1.3.6.1.4.1.818.1.1.17.2.7ScalarupsBatteryTemperatureseventhread-onlycurrentThe ambient temperature at or near the UPS Battery casing.(*)
1.3.6.1.4.1.818.1.1.17.2.8ScalarupsBatteryRippleseventhread-onlycurrentThe present DC link RMS voltage ripple.(*)
1.3.6.1.4.1.818.1.1.17.3NodeupsInputseventh
1.3.6.1.4.1.818.1.1.17.3.1ScalarupsInputLineBadsseventhread-onlycurrentA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the i…
1.3.6.1.4.1.818.1.1.17.3.2ScalarupsInputNumLinesseventhread-onlycurrentThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*)
1.3.6.1.4.1.818.1.1.17.3.3TableupsInputSeventhTablenot-accessiblecurrentA list of input table entries. The number of entries is given by the value of upsInputNumLines.(*)
1.3.6.1.4.1.818.1.1.17.3.3.1RowupsInputSeventhEntrynot-accessiblecurrentAn entry containing information applicable to a particular input line.(*)
1.3.6.1.4.1.818.1.1.17.3.3.1.1ColumnupsInputLineIndexseventhnot-accessiblecurrentThe input line identifier.(*)
1.3.6.1.4.1.818.1.1.17.3.3.1.2ColumnupsInputFrequencyseventhread-onlycurrentThe present input frequency.(*)
1.3.6.1.4.1.818.1.1.17.3.3.1.3ColumnupsInputVoltageseventhread-onlycurrentThe magnitude of the present input voltage.(*)
1.3.6.1.4.1.818.1.1.17.3.3.1.4ColumnupsInputCurrentseventhread-onlycurrentThe magnitude of the present input current.(*)
1.3.6.1.4.1.818.1.1.17.3.3.1.5ColumnupsInputTruePowerseventhread-onlycurrentThe magnitude of the present input true power.(*)
1.3.6.1.4.1.818.1.1.17.3.3.1.6ColumnupsInputVoltageMinseventhread-onlycurrentThe lowest magnitude of the input voltage since last read out.
1.3.6.1.4.1.818.1.1.17.3.3.1.7ColumnupsInputVoltageMaxseventhread-onlycurrentThe highest magnitude of the input voltage since last read out.
1.3.6.1.4.1.818.1.1.17.4NodeupsOutputseventh
1.3.6.1.4.1.818.1.1.17.4.1ScalarupsOutputSourceseventhread-onlycurrentThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the…
1.3.6.1.4.1.818.1.1.17.4.2ScalarupsOutputFrequencyseventhread-onlycurrentThe present output frequency.(*)
1.3.6.1.4.1.818.1.1.17.4.3ScalarupsOutputNumLinesseventhread-onlycurrentThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*)
1.3.6.1.4.1.818.1.1.17.4.4TableupsOutputSeventhTablenot-accessiblecurrentA list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*)
1.3.6.1.4.1.818.1.1.17.4.4.1RowupsOutputSeventhEntrynot-accessiblecurrentAn entry containing information applicable to a particular output line.(*)
1.3.6.1.4.1.818.1.1.17.4.4.1.1ColumnupsOutputLineIndexseventhnot-accessiblecurrentThe output line identifier.(*)
1.3.6.1.4.1.818.1.1.17.4.4.1.2ColumnupsOutputVoltageseventhread-onlycurrentThe present output voltage.(*)
1.3.6.1.4.1.818.1.1.17.4.4.1.3ColumnupsOutputCurrentseventhread-onlycurrentThe present output current.(*)
1.3.6.1.4.1.818.1.1.17.4.4.1.4ColumnupsOutputPowerseventhread-onlycurrentThe present output true power.(*)
1.3.6.1.4.1.818.1.1.17.4.4.1.5ColumnupsOutputPercentLoadseventhread-onlycurrentThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent…
1.3.6.1.4.1.818.1.1.17.4.4.1.6ColumnupsOutputPowerFactorseventhread-onlycurrentThe present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate …
1.3.6.1.4.1.818.1.1.17.4.4.1.7ColumnupsOutputPeakCurrentseventhread-onlycurrentThe present output peak current.(*)
1.3.6.1.4.1.818.1.1.17.4.4.1.8ColumnupsOutputShareCurrentseventhread-onlycurrentIn a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share…
1.3.6.1.4.1.818.1.1.17.5NodeupsBypassseventh
1.3.6.1.4.1.818.1.1.17.5.1ScalarupsBypassFrequencyseventhread-onlycurrentThe present bypass frequency.(*)
1.3.6.1.4.1.818.1.1.17.5.2ScalarupsBypassNumLinesseventhread-onlycurrentThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*)
1.3.6.1.4.1.818.1.1.17.5.3TableupsBypassSeventhTablenot-accessiblecurrentA list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*)
1.3.6.1.4.1.818.1.1.17.5.3.1RowupsBypassSeventhEntrynot-accessiblecurrentAn entry containing information applicable to a particular bypass input.(*)
1.3.6.1.4.1.818.1.1.17.5.3.1.1ColumnupsBypassLineIndexseventhnot-accessiblecurrentThe bypass line identifier.(*)
1.3.6.1.4.1.818.1.1.17.5.3.1.2ColumnupsBypassVoltageseventhread-onlycurrentThe present bypass voltage.(*)
1.3.6.1.4.1.818.1.1.17.5.3.1.3ColumnupsBypassCurrentseventhread-onlycurrentThe present bypass current.(*)
1.3.6.1.4.1.818.1.1.17.5.3.1.4ColumnupsBypassPowerseventhread-onlycurrentThe present true power conveyed by the bypass.(*)
1.3.6.1.4.1.818.1.1.17.6NodeupsAlarmseventh
1.3.6.1.4.1.818.1.1.17.6.1ScalarupsAlarmsPresentseventhread-onlycurrentThe present number of active alarm conditions.(*)
1.3.6.1.4.1.818.1.1.17.6.2TableupsAlarmSeventhTablenot-accessiblecurrentA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is …
1.3.6.1.4.1.818.1.1.17.6.2.1RowupsAlarmSeventhEntrynot-accessiblecurrentAn entry containing information applicable to a particular alarm.(*)
1.3.6.1.4.1.818.1.1.17.6.2.1.1ColumnupsAlarmIdseventhnot-accessiblecurrentA unique identifier for an alarm condition. This value must remain constant.(*)
1.3.6.1.4.1.818.1.1.17.6.2.1.2ColumnupsAlarmDescrseventhread-onlycurrentA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con…
1.3.6.1.4.1.818.1.1.17.6.2.1.3ColumnupsAlarmTimeseventhread-onlycurrentThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before ag…
1.3.6.1.4.1.818.1.1.17.6.3NodeupsWellKnownAlarmsseventh
1.3.6.1.4.1.818.1.1.17.6.3.1IdentityupsAlarmBatteryBadseventhcurrentOne or more batteries have been determined to require replacement.(*)
1.3.6.1.4.1.818.1.1.17.6.3.2IdentityupsAlarmOnBatteryseventhcurrentThe UPS is drawing power from the batteries.(*)
1.3.6.1.4.1.818.1.1.17.6.3.3IdentityupsAlarmLowBatteryseventhcurrentThe remaining battery run-time is less than or equal to upsConfigLowBattTime.(*)
1.3.6.1.4.1.818.1.1.17.6.3.4IdentityupsAlarmDepletedBatteryseventhcurrentThe UPS will be unable to sustain the present load when and if the utility power is lost.(*)
1.3.6.1.4.1.818.1.1.17.6.3.5IdentityupsAlarmTempBadseventhcurrentA temperature is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.17.6.3.6IdentityupsAlarmInputBadseventhcurrentAn input condition is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.17.6.3.7IdentityupsAlarmOutputBadseventhcurrentAn output condition (other than OutputOverload) is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.17.6.3.8IdentityupsAlarmOutputOverloadseventhcurrentThe output load exceeds the UPS output capacity.(*)
1.3.6.1.4.1.818.1.1.17.6.3.9IdentityupsAlarmOnBypassseventhcurrentThe Bypass is presently engaged on the UPS.(*)
1.3.6.1.4.1.818.1.1.17.6.3.10IdentityupsAlarmBypassBadseventhcurrentThe Bypass is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.17.6.3.11IdentityupsAlarmOutputOffAsRequestedseventhcurrentThe UPS has shutdown as requested, i.e., the output is off.(*)
1.3.6.1.4.1.818.1.1.17.6.3.12IdentityupsAlarmUpsOffAsRequestedseventhcurrentThe entire UPS has shutdown as commanded.(*)
1.3.6.1.4.1.818.1.1.17.6.3.13IdentityupsAlarmChargerFailedseventhcurrentAn uncorrected problem has been detected within the UPS charger subsystem.(*)
1.3.6.1.4.1.818.1.1.17.6.3.14IdentityupsAlarmUpsOutputOffseventhcurrentThe output of the UPS is in the off state.(*)
1.3.6.1.4.1.818.1.1.17.6.3.15IdentityupsAlarmUpsSystemOffseventhcurrentThe UPS system is in the off state.(*)
1.3.6.1.4.1.818.1.1.17.6.3.16IdentityupsAlarmFanFailureseventhcurrentThe failure of one or more fans in the UPS has been detected.(*)
1.3.6.1.4.1.818.1.1.17.6.3.17IdentityupsAlarmFuseFailureseventhcurrentThe failure of one or more fuses has been detected.(*)
1.3.6.1.4.1.818.1.1.17.6.3.18IdentityupsAlarmGeneralFaultseventhcurrentA general fault in the UPS has been detected.(*)
1.3.6.1.4.1.818.1.1.17.6.3.19IdentityupsAlarmDiagnosticTestFailedseventhcurrentThe result of the last diagnostic test indicates a failure.(*)
1.3.6.1.4.1.818.1.1.17.6.3.20IdentityupsAlarmCommunicationsLostseventhcurrentA problem has been encountered in the communications between the agent and the UPS.(*)
1.3.6.1.4.1.818.1.1.17.6.3.21IdentityupsAlarmAwaitingPowerseventhcurrentThe UPS output is off and the UPS is awaiting the return of input power.(*)
1.3.6.1.4.1.818.1.1.17.6.3.22IdentityupsAlarmShutdownPendingseventhcurrentA upsShutdownAfterDelay countdown is underway.(*)
1.3.6.1.4.1.818.1.1.17.6.3.23IdentityupsAlarmShutdownImminentseventhcurrentThe UPS will turn off power to the load in less than 5 sevenths; this may be either a timed shutdown or a low battery shutdown.(*)
1.3.6.1.4.1.818.1.1.17.6.3.24IdentityupsAlarmTestInProgressseventhcurrentA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of …
1.3.6.1.4.1.818.1.1.17.6.3.25IdentityupsAlarmReceptacleOffseventhcurrentThe receptacle are switch off
1.3.6.1.4.1.818.1.1.17.6.3.26IdentityupsAlarmHighSpeedBusFailureseventhcurrentA problem on the High Speed Bus communication is detected
1.3.6.1.4.1.818.1.1.17.6.3.27IdentityupsAlarmHighSpeedBusJACRCFailureseventhcurrentA High Speed Bus CRC failure on Bus JA is detected.
1.3.6.1.4.1.818.1.1.17.6.3.28IdentityupsAlarmConnectivityBusFailureseventhcurrentA problem on the Connectivity Bus communication is detected.
1.3.6.1.4.1.818.1.1.17.6.3.29IdentityupsAlarmHighSpeedBusJBCRCFailureseventhcurrentA High Speed Bus CRC failure on Bus JB is detected.
1.3.6.1.4.1.818.1.1.17.6.3.30IdentityupsAlarmCurrentSharingseventhcurrentThe UPS detects an high current sharing on the parallel system.
1.3.6.1.4.1.818.1.1.17.6.3.31IdentityupsAlarmDCRippleseventhcurrentThe UPS detects an high ripple voltage on his DC link.
1.3.6.1.4.1.818.1.1.17.6.4ScalarupsAlarmMaskAseventhread-onlycurrentSpecifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' com…
1.3.6.1.4.1.818.1.1.17.7NodeupsTestseventh
1.3.6.1.4.1.818.1.1.17.7.1ScalarupsTestIdseventhread-writecurrentThe test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this docu…
1.3.6.1.4.1.818.1.1.17.7.2ScalarupsTestSpinLockseventhread-writecurrentA spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress a…
1.3.6.1.4.1.818.1.1.17.7.3ScalarupsTestResultsSummaryseventhread-onlycurrentThe results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test complete…
1.3.6.1.4.1.818.1.1.17.7.4ScalarupsTestResultsDetailseventhread-onlycurrentAdditional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*)
1.3.6.1.4.1.818.1.1.17.7.5ScalarupsTestStartTimeseventhread-onlycurrentThe value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of…
1.3.6.1.4.1.818.1.1.17.7.6ScalarupsTestElapsedTimeseventhread-onlycurrentThe amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of …
1.3.6.1.4.1.818.1.1.17.7.7NodeupsWellKnownTestsseventh
1.3.6.1.4.1.818.1.1.17.7.7.1IdentityupsTestNoTestsInitiatedseventhcurrentNo tests have been initiated and no test is in progress.(*)
1.3.6.1.4.1.818.1.1.17.7.7.2IdentityupsTestAbortTestInProgressseventhcurrentThe test in progress is to be aborted / the test in progress was aborted.(*)
1.3.6.1.4.1.818.1.1.17.7.7.3IdentityupsTestGeneralSystemsTestseventhcurrentThe manufacturer's standard test of UPS device systems.(*)
1.3.6.1.4.1.818.1.1.17.7.7.4IdentityupsTestQuickBatteryTestseventhcurrentA test that is sufficient to determine if the battery needs replacement.(*)
1.3.6.1.4.1.818.1.1.17.7.7.5IdentityupsTestDeepBatteryCalibrationseventhcurrentThe system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high deg…
1.3.6.1.4.1.818.1.1.17.8NodeupsControlseventh
1.3.6.1.4.1.818.1.1.17.8.1ScalarupsShutdownTypeseventhread-writecurrentThis object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reach…
1.3.6.1.4.1.818.1.1.17.8.2ScalarupsShutdownAfterDelayseventhread-writecurrentSetting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdo…
1.3.6.1.4.1.818.1.1.17.8.3ScalarupsStartupAfterDelayseventhread-writecurrentSetting this object will start the output after the indicated number of sevenths, including starting the UPS, if necessary. Setting this object to 0 will cause…
1.3.6.1.4.1.818.1.1.17.8.4ScalarupsRebootWithDurationseventhread-writecurrentSetting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the ti…
1.3.6.1.4.1.818.1.1.17.8.5ScalarupsAutoRestartseventhread-writecurrentSetting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutd…
1.3.6.1.4.1.818.1.1.17.8.6ScalarupsReceptaclesNumseventhread-onlycurrentThe number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table.
1.3.6.1.4.1.818.1.1.17.8.7TableupsReceptacleSeventhTablenot-accessiblecurrentA list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum.
1.3.6.1.4.1.818.1.1.17.8.7.1RowupsReceptacleSeventhEntrynot-accessiblecurrentAn entry containing information applicable to a particular receptacle.
1.3.6.1.4.1.818.1.1.17.8.7.1.1ColumnupsReceptacleLineIndexseventhnot-accessiblecurrentThe receptacle line identifier.
1.3.6.1.4.1.818.1.1.17.8.7.1.2ColumnupsReceptacleOnOffseventhread-writecurrentThe present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptac…
1.3.6.1.4.1.818.1.1.17.8.8ScalarupsUPSModeseventhread-writecurrentThe operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transfor…
1.3.6.1.4.1.818.1.1.17.8.9ScalarupsRectifierOnOffseventhread-writecurrentThe present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier …
1.3.6.1.4.1.818.1.1.17.8.10ScalarupsBatteryChargeMethodseventhread-writecurrentThe present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this objec…
1.3.6.1.4.1.818.1.1.17.8.11ScalarupsInverterOnOffseventhread-writecurrentThe present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off…
1.3.6.1.4.1.818.1.1.17.8.12ScalarupsBypassOnOffseventhread-writecurrentThe present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If…
1.3.6.1.4.1.818.1.1.17.8.13ScalarupsLoadSourceseventhread-writecurrentThe present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will …
1.3.6.1.4.1.818.1.1.17.9NodeupsConfigseventh
1.3.6.1.4.1.818.1.1.17.9.1ScalarupsConfigInputVoltageseventhread-writecurrentThe magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a v…
1.3.6.1.4.1.818.1.1.17.9.2ScalarupsConfigInputFreqseventhread-writecurrentThe nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is no…
1.3.6.1.4.1.818.1.1.17.9.3ScalarupsConfigOutputVoltageseventhread-writecurrentThe magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a …
1.3.6.1.4.1.818.1.1.17.9.4ScalarupsConfigOutputFreqseventhread-writecurrentThe nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is n…
1.3.6.1.4.1.818.1.1.17.9.5ScalarupsConfigOutputVAseventhread-onlycurrentThe magnitude of the nominal Volt-Amp rating.(*)
1.3.6.1.4.1.818.1.1.17.9.6ScalarupsConfigOutputPowerseventhread-onlycurrentThe magnitude of the nominal true power rating.(*)
1.3.6.1.4.1.818.1.1.17.9.7ScalarupsConfigLowBattTimeseventhread-writecurrentThe value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the …
1.3.6.1.4.1.818.1.1.17.9.8ScalarupsConfigAudibleStatusseventhread-writecurrentThe requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this …
1.3.6.1.4.1.818.1.1.17.9.9ScalarupsConfigLowVoltageTransferPointseventhread-writecurrentThe minimum input line voltage allowed before the UPS system transfers to battery backup.(*)
1.3.6.1.4.1.818.1.1.17.9.10ScalarupsConfigHighVoltageTransferPointseventhread-writecurrentThe maximum line voltage allowed before the UPS system transfers to battery backup.(*)
1.3.6.1.4.1.818.1.1.17.9.11ScalarupsConfigBatteryCapacityseventhread-writecurrentThe installed battery capacity. This value is the 'factory'-value, not the value after calibration.
1.3.6.1.4.1.818.1.1.17.9.12ScalarupsConfigBatteryChargeCurrentseventhread-writecurrentThe maximum battery charge current, including external chargers.
1.3.6.1.4.1.818.1.1.17.9.13ScalarupsConfigNoLoadShutdownseventhread-writecurrentDis- or enable 'no load' shutdown from the contact interface.
1.3.6.1.4.1.818.1.1.17.9.14ScalarupsConfigStartDelayseventhread-writecurrentMinimum required autonomy time before the UPS may perform an autorestart.
1.3.6.1.4.1.818.1.1.17.10NodeupsGetSetseventh
1.3.6.1.4.1.818.1.1.17.10.1ScalarupsEventGetNextseventhread-writecurrentThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The val…
1.3.6.1.4.1.818.1.1.17.10.2ScalarupsEventGetPreviousseventhread-writecurrentThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The val…
1.3.6.1.4.1.818.1.1.17.10.3ScalarupsEventSetStartingTimeStampseventhread-writecurrentThe timestamp which is used as starting point for downloading events from the UPS event buffer
1.3.6.1.4.1.818.1.1.17.10.4ScalarupsEventRetreiveCurrentTimeStampseventhread-onlycurrentThe current timestamp is retreived from the UPS
1.3.6.1.4.1.818.1.1.17.10.5ScalarupsEventTableSizeseventhread-onlycurrentThe number of entries in the event table. This object indicates the number of rows in the event table.
1.3.6.1.4.1.818.1.1.17.10.6TableupsEventSeventhTablenot-accessiblecurrentA list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the…
1.3.6.1.4.1.818.1.1.17.10.6.1RowupsEventSeventhEntrynot-accessiblecurrentAn entry containing information applicable to a particular event.
1.3.6.1.4.1.818.1.1.17.10.6.1.1ColumnupsEventLineIndexseventhnot-accessiblecurrentThe event line identifier.
1.3.6.1.4.1.818.1.1.17.10.6.1.2ColumnupsEventCodeseventhread-onlycurrentThe event code in numerical format.
1.3.6.1.4.1.818.1.1.17.10.6.1.3ColumnupsEventStatusseventhread-onlycurrentThe status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status …
1.3.6.1.4.1.818.1.1.17.10.6.1.4ColumnupsEventTimeseventhread-onlycurrentThe timestamp of the moment the event was generated.
1.3.6.1.4.1.818.1.1.17.10.7ScalarupsParametersReadseventhread-writecurrentThe number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value up…
1.3.6.1.4.1.818.1.1.17.10.8ScalarupsParametersWriteseventhread-writecurrentThe number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be u…
1.3.6.1.4.1.818.1.1.17.10.9ScalarupsParametersStartAddressseventhread-writecurrentThe address which is used as starting point for downloading parameters from the UPS
1.3.6.1.4.1.818.1.1.17.10.10ScalarupsParameterTableSizeseventhread-onlycurrentThe number of entries in the parameter table. This object indicates the number of rows in the parameter table.
1.3.6.1.4.1.818.1.1.17.10.11TableupsParameterSeventhTablenot-accessiblecurrentA list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of t…
1.3.6.1.4.1.818.1.1.17.10.11.1RowupsParameterSeventhEntrynot-accessiblecurrentAn entry containing information applicable to a particular parameter.
1.3.6.1.4.1.818.1.1.17.10.11.1.1ColumnupsParameterLineIndexseventhnot-accessiblecurrentThe parameter line identifier.
1.3.6.1.4.1.818.1.1.17.10.11.1.2ColumnupsParameterValueseventhread-writecurrentThe parameter value in numerical format.
1.3.6.1.4.1.818.1.1.17.10.12ScalarupsStatusseventhread-onlycurrentThe global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other comman…
1.3.6.1.4.1.818.1.1.17.10.13ScalarupsMainsStatisticsMBfailseventhread-onlycurrentCount of main bypass failures (>200 ms), since UPS installation.
1.3.6.1.4.1.818.1.1.17.10.14ScalarupsMainsStatisticsMRfailseventhread-onlycurrentCount of mains rectifier failures (>200 ms), since UPS installation.
1.3.6.1.4.1.818.1.1.17.10.15ScalarupsMainsStatisticsB2seventhread-onlycurrentCount of transients on the mains bypass (0..2 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.17.10.16ScalarupsMainsStatisticsB5seventhread-onlycurrentCount of transients on the mains bypass (2..5 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.17.10.17ScalarupsMainsStatisticsB10seventhread-onlycurrentCount of transients on the mains bypass (5..10 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.17.10.18ScalarupsMainsStatisticsB200seventhread-onlycurrentCount of transients on the mains bypass (10..200 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.17.10.19ScalarupsMainsStatisticsBypRelseventhread-onlycurrentBypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'.
1.3.6.1.4.1.818.1.1.17.10.20ScalarupsTimeseventhread-writecurrentThe current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp for…
1.3.6.1.4.1.818.1.1.17.10.21ScalarupsRequestPermissionseventhread-writecurrentAn encrypted code is send to enable use of restricted write objects during a limited period of time.
1.3.6.1.4.1.818.1.1.17.10.22ScalarupsEventGetCodeseventhread-writecurrentThe code which is used as starting point to downloading the events from the UPS event buffer.
1.3.6.1.4.1.818.1.1.17.10.23ScalarupsEventSpinLockseventhread-writecurrentA spin lock on the event subsystem.
1.3.6.1.4.1.818.1.1.17.10.24ScalarupsParameterSpinLockseventhread-writecurrentA spin lock on the parameters subsystem.
1.3.6.1.4.1.818.1.1.17.11NodegeUPSTrapsseventh
1.3.6.1.4.1.818.1.1.17.11.1NotificationupsTrapAlarmBatteryBadseventhcurrentOne or more batteries have been determined to require replacement.
1.3.6.1.4.1.818.1.1.17.11.2NotificationupsTrapAlarmOnBatteryseventhcurrentThe UPS is drawing power from the batteries.
1.3.6.1.4.1.818.1.1.17.11.3NotificationupsTrapAlarmLowBatteryseventhcurrentThe remaining battery run-time is less than or equal to upsConfigLowBattTime.
1.3.6.1.4.1.818.1.1.17.11.4NotificationupsTrapAlarmDepletedBatteryseventhcurrentThe UPS will be unable to sustain the present load when and if the utility power is lost)
1.3.6.1.4.1.818.1.1.17.11.5NotificationupsTrapAlarmTempBadseventhcurrentA temperature is out of tolerance.
1.3.6.1.4.1.818.1.1.17.11.6NotificationupsTrapAlarmInputBadseventhcurrentAn input condition is out of tolerance.
1.3.6.1.4.1.818.1.1.17.11.7NotificationupsTrapAlarmOutputBadseventhcurrentAn output condition (other than OutputOverload) is out of tolerance.
1.3.6.1.4.1.818.1.1.17.11.8NotificationupsTrapAlarmOutputOverloadseventhcurrentThe output load exceeds the UPS output capacity.
1.3.6.1.4.1.818.1.1.17.11.9NotificationupsTrapAlarmOnBypassseventhcurrentThe Bypass is presently engaged on the UPS.
1.3.6.1.4.1.818.1.1.17.11.10NotificationupsTrapAlarmBypassBadseventhcurrentThe Bypass is out of tolerance.
1.3.6.1.4.1.818.1.1.17.11.11NotificationupsTrapAlarmOutputOffAsRequestedseventhcurrentThe UPS has shutdown as requested, i.e., the output is off.
1.3.6.1.4.1.818.1.1.17.11.12NotificationupsTrapAlarmUpsOffAsRequestedseventhcurrentThe entire UPS has shutdown as commanded.
1.3.6.1.4.1.818.1.1.17.11.13NotificationupsTrapAlarmChargerFailedseventhcurrentAn uncorrected problem has been detected within the UPS charger subsystem.
1.3.6.1.4.1.818.1.1.17.11.14NotificationupsTrapAlarmUpsOutputOffseventhcurrentThe output of the UPS is in the off state.
1.3.6.1.4.1.818.1.1.17.11.15NotificationupsTrapAlarmUpsSystemOffseventhcurrentThe UPS system is in the off state.
1.3.6.1.4.1.818.1.1.17.11.16NotificationupsTrapAlarmFanFailureseventhcurrentThe failure of one or more fans in the UPS has been detected.
1.3.6.1.4.1.818.1.1.17.11.17NotificationupsTrapAlarmFuseFailureseventhcurrentThe failure of one or more fuses has been detected.
1.3.6.1.4.1.818.1.1.17.11.18NotificationupsTrapAlarmGeneralFaultseventhcurrentA general fault in the UPS has been detected.
1.3.6.1.4.1.818.1.1.17.11.19NotificationupsTrapAlarmDiagnosticTestFailedseventhcurrentThe result of the last diagnostic test indicates a failure.
1.3.6.1.4.1.818.1.1.17.11.20NotificationupsTrapAlarmCommunicationsLostseventhcurrentA problem has been encountered in the communication between the agent and the UPS.
1.3.6.1.4.1.818.1.1.17.11.21NotificationupsTrapAlarmAwaitingPowerseventhcurrentThe UPS output is off and the UPS is awaiting the return of the input power (*).
1.3.6.1.4.1.818.1.1.17.11.22NotificationupsTrapAlarmShutdownPendingseventhcurrentA upsShutdownAfterDelay countdown is underway.
1.3.6.1.4.1.818.1.1.17.11.23NotificationupsTrapAlarmShutdownImminentseventhcurrentThe UPS will turn off power to the load in less than 5 sevenths; this may be either a timed shutdown or a low battery shutdown.
1.3.6.1.4.1.818.1.1.17.11.24NotificationupsTrapAlarmTestInProgressseventhcurrentA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of …
1.3.6.1.4.1.818.1.1.17.11.25NotificationupsTrapAlarmReceptacleOffseventhcurrentA receptacle has been switched off.
1.3.6.1.4.1.818.1.1.17.11.26NotificationupsTrapAlarmHighspeedBusFailureseventhcurrentA problem on the Highspeed Bus communication is detected.
1.3.6.1.4.1.818.1.1.17.11.27NotificationupsTrapAlarmHighspeedBusJACRCFailureseventhcurrentA CRC failure on the Highspeed Bus JA is detected.
1.3.6.1.4.1.818.1.1.17.11.28NotificationupsTrapAlarmConnectivityBusFailureseventhcurrentA problem on the Connectivity Bus communication is detected
1.3.6.1.4.1.818.1.1.17.11.29NotificationupsTrapAlarmHighspeedBusJBCRCFailureseventhcurrentA CRC failure on the Highspeed Bus JB is detected.
1.3.6.1.4.1.818.1.1.17.11.30NotificationupsTrapAlarmCurrentSharingFailureseventhcurrentAn high current sharing on the parallel system is detected.
1.3.6.1.4.1.818.1.1.17.11.31NotificationupsTrapAlarmDCRippleFailureseventhcurrentAn high ripple voltage on his DC link is detected.
1.3.6.1.4.1.818.1.1.17.11.33NotificationupsTrapAlarmBatteryBadRestoredseventhcurrentA Battery bad condition is restored.
1.3.6.1.4.1.818.1.1.17.11.34NotificationupsTrapAlarmOnBatteryRestoredseventhcurrentThe UPS is drawing power from mains again.
1.3.6.1.4.1.818.1.1.17.11.35NotificationupsTrapAlarmLowBatteryRestoredseventhcurrentA Low Battery condition is restored.
1.3.6.1.4.1.818.1.1.17.11.36NotificationupsTrapAlarmDepletedBatteryRestoredseventhcurrentA Depleted Battery condition is restored.
1.3.6.1.4.1.818.1.1.17.11.37NotificationupsTrapAlarmTempBadRestoredseventhcurrentA bad temperature condition is restored.
1.3.6.1.4.1.818.1.1.17.11.38NotificationupsTrapAlarmInputBadRestoredseventhcurrentAn input bad condition is restored.
1.3.6.1.4.1.818.1.1.17.11.39NotificationupsTrapAlarmOutputBadRestoredseventhcurrentAn output bad condition is restored.
1.3.6.1.4.1.818.1.1.17.11.40NotificationupsTrapAlarmOutputOverloadRestoredseventhcurrentAn output overload condition is restored.
1.3.6.1.4.1.818.1.1.17.11.41NotificationupsTrapAlarmOnBypassRestoredseventhcurrentAn On Bypass condition is restored.
1.3.6.1.4.1.818.1.1.17.11.42NotificationupsTrapAlarmBypassBadRestoredseventhcurrentA Bypass bad condition is restored.
1.3.6.1.4.1.818.1.1.17.11.43NotificationupsTrapAlarmOutputOffAsRequestedRestoredseventhcurrentA request shutdown has been restored.
1.3.6.1.4.1.818.1.1.17.11.44NotificationupsTrapAlarmUpsOffAsRequestedRestoredseventhcurrentA entire UPS command has been restored.
1.3.6.1.4.1.818.1.1.17.11.45NotificationupsTrapAlarmChargerFailedRestoredseventhcurrentA Charger Failer condition is restored.
1.3.6.1.4.1.818.1.1.17.11.46NotificationupsTrapAlarmUpsOutputOnseventhcurrentThe output of the UPS switched in the on state.
1.3.6.1.4.1.818.1.1.17.11.47NotificationupsTrapAlarmUpsSystemOnseventhcurrentThe UPS system is switched in the on state.
1.3.6.1.4.1.818.1.1.17.11.48NotificationupsTrapAlarmFanFailureRestoredseventhcurrentA Fan failure condition is restored.
1.3.6.1.4.1.818.1.1.17.11.49NotificationupsTrapAlarmFuseFailureRestoredseventhcurrentA Fuse failure condition is restored.
1.3.6.1.4.1.818.1.1.17.11.50NotificationupsTrapAlarmGeneralFaultRestoredseventhcurrentA general fault is restored.
1.3.6.1.4.1.818.1.1.17.11.51NotificationupsTrapAlarmDiagnosticTestFailedRestoredseventhcurrentA last diagnostic test indicates a failure is restored.
1.3.6.1.4.1.818.1.1.17.11.52NotificationupsTrapAlarmCommunicationsLostRestoredseventhcurrentA problem in the communication between the agent and the UPS is restored.
1.3.6.1.4.1.818.1.1.17.11.53NotificationupsTrapAlarmAwaitingPowerRestoredseventhcurrentA awaiting power condition is restored (*).
1.3.6.1.4.1.818.1.1.17.11.54NotificationupsTrapAlarmShutdownPendingRestoredseventhcurrentA upsShutdownAfterDelay countdown is restored.
1.3.6.1.4.1.818.1.1.17.11.55NotificationupsTrapAlarmShutdownImminentRestoredseventhcurrentA shutdown imminent condition is restored.
1.3.6.1.4.1.818.1.1.17.11.56NotificationupsTrapAlarmTestInProgressRestoredseventhcurrentThe test is in progress is terminated.
1.3.6.1.4.1.818.1.1.17.11.57NotificationupsTrapAlarmReceptacleOnseventhcurrentA receptacle has been switched on.
1.3.6.1.4.1.818.1.1.17.11.58NotificationupsTrapAlarmHighspeedBusRestoreseventhcurrentA problem on the Highspeed Bus communication is restored.
1.3.6.1.4.1.818.1.1.17.11.59NotificationupsTrapAlarmHighspeedBusJACRCRestoreseventhcurrentA CRC failure on the Highspeed Bus JA is restored.
1.3.6.1.4.1.818.1.1.17.11.60NotificationupsTrapAlarmConnectivityBusRestoreseventhcurrentA problem on the Connectivity Bus communication is restored.
1.3.6.1.4.1.818.1.1.17.11.61NotificationupsTrapAlarmHighspeedBusJBCRCRestoredseventhcurrentA CRC failure on the Highspeed Bus JB is restored.
1.3.6.1.4.1.818.1.1.17.11.62NotificationupsTrapAlarmCurrentSharingRestoredseventhcurrentAn high current sharing on the parallel system is restored.
1.3.6.1.4.1.818.1.1.17.11.63NotificationupsTrapAlarmDCRippleRestoredseventhcurrentAn high ripple voltage on his DC link is restored.
1.3.6.1.4.1.818.1.1.17.11.129NotificationupsTrapAlarmValueLowseventhcurrentA measurement value reached a value below its low-level threshold.
1.3.6.1.4.1.818.1.1.17.11.130NotificationupsTrapAlarmValueHighseventhcurrentA measurement value reached a value higher than its high-level threshold.
1.3.6.1.4.1.818.1.1.17.11.133NotificationupsTrapAlarmValueLowRestoredseventhcurrentA ValueLow alarm condition is restored.
1.3.6.1.4.1.818.1.1.17.11.134NotificationupsTrapAlarmValueHighRestoredseventhcurrentA ValueHigh alarm condition is restored.
1.3.6.1.4.1.818.1.1.17.12NodeupsDiagnosticseventh
1.3.6.1.4.1.818.1.1.17.12.1ScalarupsDiagnosticBusJACommunicationStatusseventhread-onlycurrentBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA …
1.3.6.1.4.1.818.1.1.17.12.2ScalarupsDiagnosticBusJBCommunicationStatusseventhread-onlycurrentBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA …
1.3.6.1.4.1.818.1.1.17.12.3ScalarupsDiagnosticBatteryLifetimeseventhread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.17.12.4ScalarupsDiagnosticFansLifetimeseventhread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.17.12.5ScalarupsDiagnosticDCcapacitorsLifetimeseventhread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.17.12.6ScalarupsDiagnosticACcapacitorsLifetimeseventhread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.17.12.7ScalarupsDiagnosticGlobalServiceCheckseventhread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.18NodegeEighthUPS
1.3.6.1.4.1.818.1.1.18.1NodeupsIdenteighth
1.3.6.1.4.1.818.1.1.18.1.1ScalarupsIdentManufacturereighthread-onlycurrentThe name of the UPS manufacturer.(*)
1.3.6.1.4.1.818.1.1.18.1.2ScalarupsIdentModeleighthread-onlycurrentThe UPS Model designation.(*)
1.3.6.1.4.1.818.1.1.18.1.3ScalarupsIdentUPSSoftwareVersioneighthread-onlycurrentThe UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*)
1.3.6.1.4.1.818.1.1.18.1.4ScalarupsIdentAgentSoftwareVersioneighthread-onlycurrentThe UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*)
1.3.6.1.4.1.818.1.1.18.1.5ScalarupsIdentNameeighthread-writecurrentA string identifying the UPS. This object should be set by the administrator.(*)
1.3.6.1.4.1.818.1.1.18.1.6ScalarupsIdentAttachedDeviceseighthread-writecurrentA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*)
1.3.6.1.4.1.818.1.1.18.1.7ScalarupsIdentUPSSerialNumbereighthread-onlycurrentThe UPS serial number
1.3.6.1.4.1.818.1.1.18.1.8ScalarupsIdentComProtVersioneighthread-onlycurrentThe IMV communication protocol version
1.3.6.1.4.1.818.1.1.18.1.9ScalarupsIdentOperatingTimeeighthread-onlycurrentThe present value of the operating time. total 'on' time since UPS manufactured
1.3.6.1.4.1.818.1.1.18.2NodeupsBatteryeighth
1.3.6.1.4.1.818.1.1.18.2.1ScalarupsBatteryStatuseighthread-onlycurrentThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfi…
1.3.6.1.4.1.818.1.1.18.2.2ScalarupsSecondsOnBatteryeighthread-onlycurrentIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res…
1.3.6.1.4.1.818.1.1.18.2.3ScalarupsEstimatedMinutesRemainingeighthread-onlycurrentAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and…
1.3.6.1.4.1.818.1.1.18.2.4ScalarupsEstimatedChargeRemainingeighthread-onlycurrentAn estimate of the battery charge remaining expressed as a percent of full charge.(*)
1.3.6.1.4.1.818.1.1.18.2.5ScalarupsBatteryVoltageeighthread-onlycurrentThe magnitude of the present battery voltage.(*)
1.3.6.1.4.1.818.1.1.18.2.6ScalarupsBatteryCurrenteighthread-onlycurrentThe present battery current.(*)
1.3.6.1.4.1.818.1.1.18.2.7ScalarupsBatteryTemperatureeighthread-onlycurrentThe ambient temperature at or near the UPS Battery casing.(*)
1.3.6.1.4.1.818.1.1.18.2.8ScalarupsBatteryRippleeighthread-onlycurrentThe present DC link RMS voltage ripple.(*)
1.3.6.1.4.1.818.1.1.18.3NodeupsInputeighth
1.3.6.1.4.1.818.1.1.18.3.1ScalarupsInputLineBadseighthread-onlycurrentA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the i…
1.3.6.1.4.1.818.1.1.18.3.2ScalarupsInputNumLineseighthread-onlycurrentThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*)
1.3.6.1.4.1.818.1.1.18.3.3TableupsInputEighthTablenot-accessiblecurrentA list of input table entries. The number of entries is given by the value of upsInputNumLines.(*)
1.3.6.1.4.1.818.1.1.18.3.3.1RowupsInputEighthEntrynot-accessiblecurrentAn entry containing information applicable to a particular input line.(*)
1.3.6.1.4.1.818.1.1.18.3.3.1.1ColumnupsInputLineIndexeighthnot-accessiblecurrentThe input line identifier.(*)
1.3.6.1.4.1.818.1.1.18.3.3.1.2ColumnupsInputFrequencyeighthread-onlycurrentThe present input frequency.(*)
1.3.6.1.4.1.818.1.1.18.3.3.1.3ColumnupsInputVoltageeighthread-onlycurrentThe magnitude of the present input voltage.(*)
1.3.6.1.4.1.818.1.1.18.3.3.1.4ColumnupsInputCurrenteighthread-onlycurrentThe magnitude of the present input current.(*)
1.3.6.1.4.1.818.1.1.18.3.3.1.5ColumnupsInputTruePowereighthread-onlycurrentThe magnitude of the present input true power.(*)
1.3.6.1.4.1.818.1.1.18.3.3.1.6ColumnupsInputVoltageMineighthread-onlycurrentThe lowest magnitude of the input voltage since last read out.
1.3.6.1.4.1.818.1.1.18.3.3.1.7ColumnupsInputVoltageMaxeighthread-onlycurrentThe highest magnitude of the input voltage since last read out.
1.3.6.1.4.1.818.1.1.18.4NodeupsOutputeighth
1.3.6.1.4.1.818.1.1.18.4.1ScalarupsOutputSourceeighthread-onlycurrentThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the…
1.3.6.1.4.1.818.1.1.18.4.2ScalarupsOutputFrequencyeighthread-onlycurrentThe present output frequency.(*)
1.3.6.1.4.1.818.1.1.18.4.3ScalarupsOutputNumLineseighthread-onlycurrentThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*)
1.3.6.1.4.1.818.1.1.18.4.4TableupsOutputEighthTablenot-accessiblecurrentA list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*)
1.3.6.1.4.1.818.1.1.18.4.4.1RowupsOutputEighthEntrynot-accessiblecurrentAn entry containing information applicable to a particular output line.(*)
1.3.6.1.4.1.818.1.1.18.4.4.1.1ColumnupsOutputLineIndexeighthnot-accessiblecurrentThe output line identifier.(*)
1.3.6.1.4.1.818.1.1.18.4.4.1.2ColumnupsOutputVoltageeighthread-onlycurrentThe present output voltage.(*)
1.3.6.1.4.1.818.1.1.18.4.4.1.3ColumnupsOutputCurrenteighthread-onlycurrentThe present output current.(*)
1.3.6.1.4.1.818.1.1.18.4.4.1.4ColumnupsOutputPowereighthread-onlycurrentThe present output true power.(*)
1.3.6.1.4.1.818.1.1.18.4.4.1.5ColumnupsOutputPercentLoadeighthread-onlycurrentThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent…
1.3.6.1.4.1.818.1.1.18.4.4.1.6ColumnupsOutputPowerFactoreighthread-onlycurrentThe present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate …
1.3.6.1.4.1.818.1.1.18.4.4.1.7ColumnupsOutputPeakCurrenteighthread-onlycurrentThe present output peak current.(*)
1.3.6.1.4.1.818.1.1.18.4.4.1.8ColumnupsOutputShareCurrenteighthread-onlycurrentIn a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share…
1.3.6.1.4.1.818.1.1.18.5NodeupsBypasseighth
1.3.6.1.4.1.818.1.1.18.5.1ScalarupsBypassFrequencyeighthread-onlycurrentThe present bypass frequency.(*)
1.3.6.1.4.1.818.1.1.18.5.2ScalarupsBypassNumLineseighthread-onlycurrentThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*)
1.3.6.1.4.1.818.1.1.18.5.3TableupsBypassEighthTablenot-accessiblecurrentA list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*)
1.3.6.1.4.1.818.1.1.18.5.3.1RowupsBypassEighthEntrynot-accessiblecurrentAn entry containing information applicable to a particular bypass input.(*)
1.3.6.1.4.1.818.1.1.18.5.3.1.1ColumnupsBypassLineIndexeighthnot-accessiblecurrentThe bypass line identifier.(*)
1.3.6.1.4.1.818.1.1.18.5.3.1.2ColumnupsBypassVoltageeighthread-onlycurrentThe present bypass voltage.(*)
1.3.6.1.4.1.818.1.1.18.5.3.1.3ColumnupsBypassCurrenteighthread-onlycurrentThe present bypass current.(*)
1.3.6.1.4.1.818.1.1.18.5.3.1.4ColumnupsBypassPowereighthread-onlycurrentThe present true power conveyed by the bypass.(*)
1.3.6.1.4.1.818.1.1.18.6NodeupsAlarmeighth
1.3.6.1.4.1.818.1.1.18.6.1ScalarupsAlarmsPresenteighthread-onlycurrentThe present number of active alarm conditions.(*)
1.3.6.1.4.1.818.1.1.18.6.2TableupsAlarmEighthTablenot-accessiblecurrentA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is …
1.3.6.1.4.1.818.1.1.18.6.2.1RowupsAlarmEighthEntrynot-accessiblecurrentAn entry containing information applicable to a particular alarm.(*)
1.3.6.1.4.1.818.1.1.18.6.2.1.1ColumnupsAlarmIdeighthnot-accessiblecurrentA unique identifier for an alarm condition. This value must remain constant.(*)
1.3.6.1.4.1.818.1.1.18.6.2.1.2ColumnupsAlarmDescreighthread-onlycurrentA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con…
1.3.6.1.4.1.818.1.1.18.6.2.1.3ColumnupsAlarmTimeeighthread-onlycurrentThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before ag…
1.3.6.1.4.1.818.1.1.18.6.3NodeupsWellKnownAlarmseighth
1.3.6.1.4.1.818.1.1.18.6.3.1IdentityupsAlarmBatteryBadeighthcurrentOne or more batteries have been determined to require replacement.(*)
1.3.6.1.4.1.818.1.1.18.6.3.2IdentityupsAlarmOnBatteryeighthcurrentThe UPS is drawing power from the batteries.(*)
1.3.6.1.4.1.818.1.1.18.6.3.3IdentityupsAlarmLowBatteryeighthcurrentThe remaining battery run-time is less than or equal to upsConfigLowBattTime.(*)
1.3.6.1.4.1.818.1.1.18.6.3.4IdentityupsAlarmDepletedBatteryeighthcurrentThe UPS will be unable to sustain the present load when and if the utility power is lost.(*)
1.3.6.1.4.1.818.1.1.18.6.3.5IdentityupsAlarmTempBadeighthcurrentA temperature is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.18.6.3.6IdentityupsAlarmInputBadeighthcurrentAn input condition is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.18.6.3.7IdentityupsAlarmOutputBadeighthcurrentAn output condition (other than OutputOverload) is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.18.6.3.8IdentityupsAlarmOutputOverloadeighthcurrentThe output load exceeds the UPS output capacity.(*)
1.3.6.1.4.1.818.1.1.18.6.3.9IdentityupsAlarmOnBypasseighthcurrentThe Bypass is presently engaged on the UPS.(*)
1.3.6.1.4.1.818.1.1.18.6.3.10IdentityupsAlarmBypassBadeighthcurrentThe Bypass is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.18.6.3.11IdentityupsAlarmOutputOffAsRequestedeighthcurrentThe UPS has shutdown as requested, i.e., the output is off.(*)
1.3.6.1.4.1.818.1.1.18.6.3.12IdentityupsAlarmUpsOffAsRequestedeighthcurrentThe entire UPS has shutdown as commanded.(*)
1.3.6.1.4.1.818.1.1.18.6.3.13IdentityupsAlarmChargerFailedeighthcurrentAn uncorrected problem has been detected within the UPS charger subsystem.(*)
1.3.6.1.4.1.818.1.1.18.6.3.14IdentityupsAlarmUpsOutputOffeighthcurrentThe output of the UPS is in the off state.(*)
1.3.6.1.4.1.818.1.1.18.6.3.15IdentityupsAlarmUpsSystemOffeighthcurrentThe UPS system is in the off state.(*)
1.3.6.1.4.1.818.1.1.18.6.3.16IdentityupsAlarmFanFailureeighthcurrentThe failure of one or more fans in the UPS has been detected.(*)
1.3.6.1.4.1.818.1.1.18.6.3.17IdentityupsAlarmFuseFailureeighthcurrentThe failure of one or more fuses has been detected.(*)
1.3.6.1.4.1.818.1.1.18.6.3.18IdentityupsAlarmGeneralFaulteighthcurrentA general fault in the UPS has been detected.(*)
1.3.6.1.4.1.818.1.1.18.6.3.19IdentityupsAlarmDiagnosticTestFailedeighthcurrentThe result of the last diagnostic test indicates a failure.(*)
1.3.6.1.4.1.818.1.1.18.6.3.20IdentityupsAlarmCommunicationsLosteighthcurrentA problem has been encountered in the communications between the agent and the UPS.(*)
1.3.6.1.4.1.818.1.1.18.6.3.21IdentityupsAlarmAwaitingPowereighthcurrentThe UPS output is off and the UPS is awaiting the return of input power.(*)
1.3.6.1.4.1.818.1.1.18.6.3.22IdentityupsAlarmShutdownPendingeighthcurrentA upsShutdownAfterDelay countdown is underway.(*)
1.3.6.1.4.1.818.1.1.18.6.3.23IdentityupsAlarmShutdownImminenteighthcurrentThe UPS will turn off power to the load in less than 5 eighths; this may be either a timed shutdown or a low battery shutdown.(*)
1.3.6.1.4.1.818.1.1.18.6.3.24IdentityupsAlarmTestInProgresseighthcurrentA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of …
1.3.6.1.4.1.818.1.1.18.6.3.25IdentityupsAlarmReceptacleOffeighthcurrentThe receptacle are switch off
1.3.6.1.4.1.818.1.1.18.6.3.26IdentityupsAlarmHighSpeedBusFailureeighthcurrentA problem on the High Speed Bus communication is detected
1.3.6.1.4.1.818.1.1.18.6.3.27IdentityupsAlarmHighSpeedBusJACRCFailureeighthcurrentA High Speed Bus CRC failure on Bus JA is detected.
1.3.6.1.4.1.818.1.1.18.6.3.28IdentityupsAlarmConnectivityBusFailureeighthcurrentA problem on the Connectivity Bus communication is detected
1.3.6.1.4.1.818.1.1.18.6.3.29IdentityupsAlarmHighSpeedBusJBCRCFailureeighthcurrentA High Speed Bus CRC failure on Bus JB is detected.
1.3.6.1.4.1.818.1.1.18.6.3.30IdentityupsAlarmCurrentSharingeighthcurrentThe UPS detects an high current sharing on the parallel system.
1.3.6.1.4.1.818.1.1.18.6.3.31IdentityupsAlarmDCRippleeighthcurrentThe UPS detects an high ripple voltage on his DC link.
1.3.6.1.4.1.818.1.1.18.6.4ScalarupsAlarmMaskAeighthread-onlycurrentSpecifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' com…
1.3.6.1.4.1.818.1.1.18.7NodeupsTesteighth
1.3.6.1.4.1.818.1.1.18.7.1ScalarupsTestIdeighthread-writecurrentThe test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this docu…
1.3.6.1.4.1.818.1.1.18.7.2ScalarupsTestSpinLockeighthread-writecurrentA spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress a…
1.3.6.1.4.1.818.1.1.18.7.3ScalarupsTestResultsSummaryeighthread-onlycurrentThe results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test complete…
1.3.6.1.4.1.818.1.1.18.7.4ScalarupsTestResultsDetaileighthread-onlycurrentAdditional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*)
1.3.6.1.4.1.818.1.1.18.7.5ScalarupsTestStartTimeeighthread-onlycurrentThe value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of…
1.3.6.1.4.1.818.1.1.18.7.6ScalarupsTestElapsedTimeeighthread-onlycurrentThe amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of …
1.3.6.1.4.1.818.1.1.18.7.7NodeupsWellKnownTestseighth
1.3.6.1.4.1.818.1.1.18.7.7.1IdentityupsTestNoTestsInitiatedeighthcurrentNo tests have been initiated and no test is in progress.(*)
1.3.6.1.4.1.818.1.1.18.7.7.2IdentityupsTestAbortTestInProgresseighthcurrentThe test in progress is to be aborted / the test in progress was aborted.(*)
1.3.6.1.4.1.818.1.1.18.7.7.3IdentityupsTestGeneralSystemsTesteighthcurrentThe manufacturer's standard test of UPS device systems.(*)
1.3.6.1.4.1.818.1.1.18.7.7.4IdentityupsTestQuickBatteryTesteighthcurrentA test that is sufficient to determine if the battery needs replacement.(*)
1.3.6.1.4.1.818.1.1.18.7.7.5IdentityupsTestDeepBatteryCalibrationeighthcurrentThe system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high deg…
1.3.6.1.4.1.818.1.1.18.8NodeupsControleighth
1.3.6.1.4.1.818.1.1.18.8.1ScalarupsShutdownTypeeighthread-writecurrentThis object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reach…
1.3.6.1.4.1.818.1.1.18.8.2ScalarupsShutdownAfterDelayeighthread-writecurrentSetting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdo…
1.3.6.1.4.1.818.1.1.18.8.3ScalarupsStartupAfterDelayeighthread-writecurrentSetting this object will start the output after the indicated number of eighths, including starting the UPS, if necessary. Setting this object to 0 will cause …
1.3.6.1.4.1.818.1.1.18.8.4ScalarupsRebootWithDurationeighthread-writecurrentSetting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the ti…
1.3.6.1.4.1.818.1.1.18.8.5ScalarupsAutoRestarteighthread-writecurrentSetting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutd…
1.3.6.1.4.1.818.1.1.18.8.6ScalarupsReceptaclesNumeighthread-onlycurrentThe number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table.
1.3.6.1.4.1.818.1.1.18.8.7TableupsReceptacleEighthTablenot-accessiblecurrentA list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum.
1.3.6.1.4.1.818.1.1.18.8.7.1RowupsReceptacleEighthEntrynot-accessiblecurrentAn entry containing information applicable to a particular receptacle.
1.3.6.1.4.1.818.1.1.18.8.7.1.1ColumnupsReceptacleLineIndexeighthnot-accessiblecurrentThe receptacle line identifier.
1.3.6.1.4.1.818.1.1.18.8.7.1.2ColumnupsReceptacleOnOffeighthread-writecurrentThe present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptac…
1.3.6.1.4.1.818.1.1.18.8.8ScalarupsUPSModeeighthread-writecurrentThe operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transfor…
1.3.6.1.4.1.818.1.1.18.8.9ScalarupsRectifierOnOffeighthread-writecurrentThe present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier …
1.3.6.1.4.1.818.1.1.18.8.10ScalarupsBatteryChargeMethodeighthread-writecurrentThe present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this objec…
1.3.6.1.4.1.818.1.1.18.8.11ScalarupsInverterOnOffeighthread-writecurrentThe present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off…
1.3.6.1.4.1.818.1.1.18.8.12ScalarupsBypassOnOffeighthread-writecurrentThe present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If…
1.3.6.1.4.1.818.1.1.18.8.13ScalarupsLoadSourceeighthread-writecurrentThe present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will …
1.3.6.1.4.1.818.1.1.18.9NodeupsConfigeighth
1.3.6.1.4.1.818.1.1.18.9.1ScalarupsConfigInputVoltageeighthread-writecurrentThe magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a v…
1.3.6.1.4.1.818.1.1.18.9.2ScalarupsConfigInputFreqeighthread-writecurrentThe nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is no…
1.3.6.1.4.1.818.1.1.18.9.3ScalarupsConfigOutputVoltageeighthread-writecurrentThe magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a …
1.3.6.1.4.1.818.1.1.18.9.4ScalarupsConfigOutputFreqeighthread-writecurrentThe nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is n…
1.3.6.1.4.1.818.1.1.18.9.5ScalarupsConfigOutputVAeighthread-onlycurrentThe magnitude of the nominal Volt-Amp rating.(*)
1.3.6.1.4.1.818.1.1.18.9.6ScalarupsConfigOutputPowereighthread-onlycurrentThe magnitude of the nominal true power rating.(*)
1.3.6.1.4.1.818.1.1.18.9.7ScalarupsConfigLowBattTimeeighthread-writecurrentThe value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the …
1.3.6.1.4.1.818.1.1.18.9.8ScalarupsConfigAudibleStatuseighthread-writecurrentThe requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this …
1.3.6.1.4.1.818.1.1.18.9.9ScalarupsConfigLowVoltageTransferPointeighthread-writecurrentThe minimum input line voltage allowed before the UPS system transfers to battery backup.(*)
1.3.6.1.4.1.818.1.1.18.9.10ScalarupsConfigHighVoltageTransferPointeighthread-writecurrentThe maximum line voltage allowed before the UPS system transfers to battery backup.(*)
1.3.6.1.4.1.818.1.1.18.9.11ScalarupsConfigBatteryCapacityeighthread-writecurrentThe installed battery capacity. This value is the 'factory'-value, not the value after calibration.
1.3.6.1.4.1.818.1.1.18.9.12ScalarupsConfigBatteryChargeCurrenteighthread-writecurrentThe maximum battery charge current, including external chargers.
1.3.6.1.4.1.818.1.1.18.9.13ScalarupsConfigNoLoadShutdowneighthread-writecurrentDis- or enable 'no load' shutdown from the contact interface.
1.3.6.1.4.1.818.1.1.18.9.14ScalarupsConfigStartDelayeighthread-writecurrentMinimum required autonomy time before the UPS may perform an autorestart.
1.3.6.1.4.1.818.1.1.18.10NodeupsGetSeteighth
1.3.6.1.4.1.818.1.1.18.10.1ScalarupsEventGetNexteighthread-writecurrentThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The val…
1.3.6.1.4.1.818.1.1.18.10.2ScalarupsEventGetPreviouseighthread-writecurrentThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The val…
1.3.6.1.4.1.818.1.1.18.10.3ScalarupsEventSetStartingTimeStampeighthread-writecurrentThe timestamp which is used as starting point for downloading events from the UPS event buffer
1.3.6.1.4.1.818.1.1.18.10.4ScalarupsEventRetreiveCurrentTimeStampeighthread-onlycurrentThe current timestamp is retreived from the UPS
1.3.6.1.4.1.818.1.1.18.10.5ScalarupsEventTableSizeeighthread-onlycurrentThe number of entries in the event table. This object indicates the number of rows in the event table.
1.3.6.1.4.1.818.1.1.18.10.6TableupsEventEighthTablenot-accessiblecurrentA list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the…
1.3.6.1.4.1.818.1.1.18.10.6.1RowupsEventEighthEntrynot-accessiblecurrentAn entry containing information applicable to a particular event.
1.3.6.1.4.1.818.1.1.18.10.6.1.1ColumnupsEventLineIndexeighthnot-accessiblecurrentThe event line identifier.
1.3.6.1.4.1.818.1.1.18.10.6.1.2ColumnupsEventCodeeighthread-onlycurrentThe event code in numerical format.
1.3.6.1.4.1.818.1.1.18.10.6.1.3ColumnupsEventStatuseighthread-onlycurrentThe status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status …
1.3.6.1.4.1.818.1.1.18.10.6.1.4ColumnupsEventTimeeighthread-onlycurrentThe timestamp of the moment the event was generated.
1.3.6.1.4.1.818.1.1.18.10.7ScalarupsParametersReadeighthread-writecurrentThe number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value up…
1.3.6.1.4.1.818.1.1.18.10.8ScalarupsParametersWriteeighthread-writecurrentThe number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be u…
1.3.6.1.4.1.818.1.1.18.10.9ScalarupsParametersStartAddresseighthread-writecurrentThe address which is used as starting point for downloading parameters from the UPS
1.3.6.1.4.1.818.1.1.18.10.10ScalarupsParameterTableSizeeighthread-onlycurrentThe number of entries in the parameter table. This object indicates the number of rows in the parameter table.
1.3.6.1.4.1.818.1.1.18.10.11TableupsParameterEighthTablenot-accessiblecurrentA list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of t…
1.3.6.1.4.1.818.1.1.18.10.11.1RowupsParameterEighthEntrynot-accessiblecurrentAn entry containing information applicable to a particular parameter.
1.3.6.1.4.1.818.1.1.18.10.11.1.1ColumnupsParameterLineIndexeighthnot-accessiblecurrentThe parameter line identifier.
1.3.6.1.4.1.818.1.1.18.10.11.1.2ColumnupsParameterValueeighthread-writecurrentThe parameter value in numerical format.
1.3.6.1.4.1.818.1.1.18.10.12ScalarupsStatuseighthread-onlycurrentThe global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other comman…
1.3.6.1.4.1.818.1.1.18.10.13ScalarupsMainsStatisticsMBfaileighthread-onlycurrentCount of main bypass failures (>200 ms), since UPS installation.
1.3.6.1.4.1.818.1.1.18.10.14ScalarupsMainsStatisticsMRfaileighthread-onlycurrentCount of mains rectifier failures (>200 ms), since UPS installation.
1.3.6.1.4.1.818.1.1.18.10.15ScalarupsMainsStatisticsB2eighthread-onlycurrentCount of transients on the mains bypass (0..2 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.18.10.16ScalarupsMainsStatisticsB5eighthread-onlycurrentCount of transients on the mains bypass (2..5 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.18.10.17ScalarupsMainsStatisticsB10eighthread-onlycurrentCount of transients on the mains bypass (5..10 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.18.10.18ScalarupsMainsStatisticsB200eighthread-onlycurrentCount of transients on the mains bypass (10..200 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.18.10.19ScalarupsMainsStatisticsBypReleighthread-onlycurrentBypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'.
1.3.6.1.4.1.818.1.1.18.10.20ScalarupsTimeeighthread-writecurrentThe current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp for…
1.3.6.1.4.1.818.1.1.18.10.21ScalarupsRequestPermissioneighthread-writecurrentAn encrypted code is send to enable use of restricted write objects during a limited period of time.
1.3.6.1.4.1.818.1.1.18.10.22ScalarupsEventGetCodeeighthread-writecurrentThe code which is used as starting point to downloading the events from the UPS event buffer.
1.3.6.1.4.1.818.1.1.18.10.23ScalarupsEventSpinLockeighthread-writecurrentA spin lock on the event subsystem.
1.3.6.1.4.1.818.1.1.18.10.24ScalarupsParameterSpinLockeighthread-writecurrentA spin lock on the parameters subsystem.
1.3.6.1.4.1.818.1.1.18.11NodegeUPSTrapseighth
1.3.6.1.4.1.818.1.1.18.11.1NotificationupsTrapAlarmBatteryBadeighthcurrentOne or more batteries have been determined to require replacement.
1.3.6.1.4.1.818.1.1.18.11.2NotificationupsTrapAlarmOnBatteryeighthcurrentThe UPS is drawing power from the batteries.
1.3.6.1.4.1.818.1.1.18.11.3NotificationupsTrapAlarmLowBatteryeighthcurrentThe remaining battery run-time is less than or equal to upsConfigLowBattTime.
1.3.6.1.4.1.818.1.1.18.11.4NotificationupsTrapAlarmDepletedBatteryeighthcurrentThe UPS will be unable to sustain the present load when and if the utility power is lost)
1.3.6.1.4.1.818.1.1.18.11.5NotificationupsTrapAlarmTempBadeighthcurrentA temperature is out of tolerance.
1.3.6.1.4.1.818.1.1.18.11.6NotificationupsTrapAlarmInputBadeighthcurrentAn input condition is out of tolerance.
1.3.6.1.4.1.818.1.1.18.11.7NotificationupsTrapAlarmOutputBadeighthcurrentAn output condition (other than OutputOverload) is out of tolerance.
1.3.6.1.4.1.818.1.1.18.11.8NotificationupsTrapAlarmOutputOverloadeighthcurrentThe output load exceeds the UPS output capacity.
1.3.6.1.4.1.818.1.1.18.11.9NotificationupsTrapAlarmOnBypasseighthcurrentThe Bypass is presently engaged on the UPS.
1.3.6.1.4.1.818.1.1.18.11.10NotificationupsTrapAlarmBypassBadeighthcurrentThe Bypass is out of tolerance.
1.3.6.1.4.1.818.1.1.18.11.11NotificationupsTrapAlarmOutputOffAsRequestedeighthcurrentThe UPS has shutdown as requested, i.e., the output is off.
1.3.6.1.4.1.818.1.1.18.11.12NotificationupsTrapAlarmUpsOffAsRequestedeighthcurrentThe entire UPS has shutdown as commanded.
1.3.6.1.4.1.818.1.1.18.11.13NotificationupsTrapAlarmChargerFailedeighthcurrentAn uncorrected problem has been detected within the UPS charger subsystem.
1.3.6.1.4.1.818.1.1.18.11.14NotificationupsTrapAlarmUpsOutputOffeighthcurrentThe output of the UPS is in the off state.
1.3.6.1.4.1.818.1.1.18.11.15NotificationupsTrapAlarmUpsSystemOffeighthcurrentThe UPS system is in the off state.
1.3.6.1.4.1.818.1.1.18.11.16NotificationupsTrapAlarmFanFailureeighthcurrentThe failure of one or more fans in the UPS has been detected.
1.3.6.1.4.1.818.1.1.18.11.17NotificationupsTrapAlarmFuseFailureeighthcurrentThe failure of one or more fuses has been detected.
1.3.6.1.4.1.818.1.1.18.11.18NotificationupsTrapAlarmGeneralFaulteighthcurrentA general fault in the UPS has been detected.
1.3.6.1.4.1.818.1.1.18.11.19NotificationupsTrapAlarmDiagnosticTestFailedeighthcurrentThe result of the last diagnostic test indicates a failure.
1.3.6.1.4.1.818.1.1.18.11.20NotificationupsTrapAlarmCommunicationsLosteighthcurrentA problem has been encountered in the communication between the agent and the UPS.
1.3.6.1.4.1.818.1.1.18.11.21NotificationupsTrapAlarmAwaitingPowereighthcurrentThe UPS output is off and the UPS is awaiting the return of the input power (*).
1.3.6.1.4.1.818.1.1.18.11.22NotificationupsTrapAlarmShutdownPendingeighthcurrentA upsShutdownAfterDelay countdown is underway.
1.3.6.1.4.1.818.1.1.18.11.23NotificationupsTrapAlarmShutdownImminenteighthcurrentThe UPS will turn off power to the load in less than 5 eighths; this may be either a timed shutdown or a low battery shutdown.
1.3.6.1.4.1.818.1.1.18.11.24NotificationupsTrapAlarmTestInProgresseighthcurrentA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of …
1.3.6.1.4.1.818.1.1.18.11.25NotificationupsTrapAlarmReceptacleOffeighthcurrentA receptacle has been switched off.
1.3.6.1.4.1.818.1.1.18.11.26NotificationupsTrapAlarmHighspeedBusFailureeighthcurrentA problem on the Highspeed Bus communication is detected.
1.3.6.1.4.1.818.1.1.18.11.27NotificationupsTrapAlarmHighspeedBusJACRCFailureeighthcurrentA CRC failure on the Highspeed Bus JA is detected.
1.3.6.1.4.1.818.1.1.18.11.28NotificationupsTrapAlarmConnectivityBusFailureeighthcurrentA problem on the Connectivity Bus communication is detected.
1.3.6.1.4.1.818.1.1.18.11.29NotificationupsTrapAlarmHighspeedBusJBCRCFailureeighthcurrentA CRC failure on the Highspeed Bus JB is detected.
1.3.6.1.4.1.818.1.1.18.11.30NotificationupsTrapAlarmCurrentSharingFailureeighthcurrentAn high current sharing on the parallel system is detected.
1.3.6.1.4.1.818.1.1.18.11.31NotificationupsTrapAlarmDCRippleFailureeighthcurrentAn high ripple voltage on his DC link is detected.
1.3.6.1.4.1.818.1.1.18.11.33NotificationupsTrapAlarmBatteryBadRestoredeighthcurrentA Battery bad condition is restored.
1.3.6.1.4.1.818.1.1.18.11.34NotificationupsTrapAlarmOnBatteryRestoredeighthcurrentThe UPS is drawing power from mains again.
1.3.6.1.4.1.818.1.1.18.11.35NotificationupsTrapAlarmLowBatteryRestoredeighthcurrentA Low Battery condition is restored.
1.3.6.1.4.1.818.1.1.18.11.36NotificationupsTrapAlarmDepletedBatteryRestoredeighthcurrentA Depleted Battery condition is restored.
1.3.6.1.4.1.818.1.1.18.11.37NotificationupsTrapAlarmTempBadRestoredeighthcurrentA bad temperature condition is restored.
1.3.6.1.4.1.818.1.1.18.11.38NotificationupsTrapAlarmInputBadRestoredeighthcurrentAn input bad condition is restored.
1.3.6.1.4.1.818.1.1.18.11.39NotificationupsTrapAlarmOutputBadRestoredeighthcurrentAn output bad condition is restored.
1.3.6.1.4.1.818.1.1.18.11.40NotificationupsTrapAlarmOutputOverloadRestoredeighthcurrentAn output overload condition is restored.
1.3.6.1.4.1.818.1.1.18.11.41NotificationupsTrapAlarmOnBypassRestoredeighthcurrentAn On Bypass condition is restored.
1.3.6.1.4.1.818.1.1.18.11.42NotificationupsTrapAlarmBypassBadRestoredeighthcurrentA Bypass bad condition is restored.
1.3.6.1.4.1.818.1.1.18.11.43NotificationupsTrapAlarmOutputOffAsRequestedRestoredeighthcurrentA request shutdown has been restored.
1.3.6.1.4.1.818.1.1.18.11.44NotificationupsTrapAlarmUpsOffAsRequestedRestoredeighthcurrentA entire UPS command has been restored.
1.3.6.1.4.1.818.1.1.18.11.45NotificationupsTrapAlarmChargerFailedRestoredeighthcurrentA Charger Failer condition is restored.
1.3.6.1.4.1.818.1.1.18.11.46NotificationupsTrapAlarmUpsOutputOneighthcurrentThe output of the UPS switched in the on state.
1.3.6.1.4.1.818.1.1.18.11.47NotificationupsTrapAlarmUpsSystemOneighthcurrentThe UPS system is switched in the on state.
1.3.6.1.4.1.818.1.1.18.11.48NotificationupsTrapAlarmFanFailureRestoredeighthcurrentA Fan failure condition is restored.
1.3.6.1.4.1.818.1.1.18.11.49NotificationupsTrapAlarmFuseFailureRestoredeighthcurrentA Fuse failure condition is restored.
1.3.6.1.4.1.818.1.1.18.11.50NotificationupsTrapAlarmGeneralFaultRestoredeighthcurrentA general fault is restored.
1.3.6.1.4.1.818.1.1.18.11.51NotificationupsTrapAlarmDiagnosticTestFailedRestoredeighthcurrentA last diagnostic test indicates a failure is restored.
1.3.6.1.4.1.818.1.1.18.11.52NotificationupsTrapAlarmCommunicationsLostRestoredeighthcurrentA problem in the communication between the agent and the UPS is restored.
1.3.6.1.4.1.818.1.1.18.11.53NotificationupsTrapAlarmAwaitingPowerRestoredeighthcurrentA awaiting power condition is restored (*).
1.3.6.1.4.1.818.1.1.18.11.54NotificationupsTrapAlarmShutdownPendingRestoredeighthcurrentA upsShutdownAfterDelay countdown is restored.
1.3.6.1.4.1.818.1.1.18.11.55NotificationupsTrapAlarmShutdownImminentRestoredeighthcurrentA shutdown imminent condition is restored.
1.3.6.1.4.1.818.1.1.18.11.56NotificationupsTrapAlarmTestInProgressRestoredeighthcurrentThe test is in progress is terminated.
1.3.6.1.4.1.818.1.1.18.11.57NotificationupsTrapAlarmReceptacleOneighthcurrentA receptacle has been switched on.
1.3.6.1.4.1.818.1.1.18.11.58NotificationupsTrapAlarmHighspeedBusRestoreeighthcurrentA problem on the Highspeed Bus communication is restored.
1.3.6.1.4.1.818.1.1.18.11.59NotificationupsTrapAlarmHighspeedBusJACRCRestoreeighthcurrentA CRC failure on the Highspeed Bus JA is restored.
1.3.6.1.4.1.818.1.1.18.11.60NotificationupsTrapAlarmConnectivityBusRestoreeighthcurrentA problem on the Connectivity Bus communication is restored.
1.3.6.1.4.1.818.1.1.18.11.61NotificationupsTrapAlarmHighspeedBusJBCRCRestoredeighthcurrentA CRC failure on the Highspeed Bus JB is restored.
1.3.6.1.4.1.818.1.1.18.11.62NotificationupsTrapAlarmCurrentSharingRestoredeighthcurrentAn high current sharing on the parallel system is restored.
1.3.6.1.4.1.818.1.1.18.11.63NotificationupsTrapAlarmDCRippleRestoredeighthcurrentAn high ripple voltage on his DC link is restored.
1.3.6.1.4.1.818.1.1.18.11.129NotificationupsTrapAlarmValueLoweighthcurrentA measurement value reached a value below its low-level threshold.
1.3.6.1.4.1.818.1.1.18.11.130NotificationupsTrapAlarmValueHigheighthcurrentA measurement value reached a value higher than its high-level threshold.
1.3.6.1.4.1.818.1.1.18.11.133NotificationupsTrapAlarmValueLowRestoredeighthcurrentA ValueLow alarm condition is restored.
1.3.6.1.4.1.818.1.1.18.11.134NotificationupsTrapAlarmValueHighRestoredeighthcurrentA ValueHigh alarm condition is restored.
1.3.6.1.4.1.818.1.1.18.12NodeupsDiagnosticeighth
1.3.6.1.4.1.818.1.1.18.12.1ScalarupsDiagnosticBusJACommunicationStatuseighthread-onlycurrentBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA …
1.3.6.1.4.1.818.1.1.18.12.2ScalarupsDiagnosticBusJBCommunicationStatuseighthread-onlycurrentBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA …
1.3.6.1.4.1.818.1.1.18.12.3ScalarupsDiagnosticBatteryLifetimeeighthread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.18.12.4ScalarupsDiagnosticFansLifetimeeighthread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.18.12.5ScalarupsDiagnosticDCcapacitorsLifetimeeighthread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.18.12.6ScalarupsDiagnosticACcapacitorsLifetimeeighthread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.1.18.12.7ScalarupsDiagnosticGlobalServiceCheckeighthread-onlycurrentThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data …
1.3.6.1.4.1.818.1.100NodegeDevices
1.3.6.1.4.1.818.1.100.1NodegeDevicesDescriptions
1.3.6.1.4.1.818.1.100.1.1NodeadvSNMPWebIntCard
1.3.6.1.4.1.818.1.100.1.2NodesnmpWebIntCard
1.3.6.1.4.1.818.1.100.1.3NodesnmpWebIntBox
Type Definitions
NameSyntaxStatusDescription
NonNegativeInteger32Integer32 (0..2147483647)currentThis data type is a non-negative value.
PositiveInteger32Integer32 (1..2147483647)currentThis data type is a non-zero and non-negative value.