GESINGLEUPS-MIB
261 objects
The MIB module to describe GE Digital Energy Uninterruptible Power Supplies.
Imported Objects
| SNMPv2-SMI | Counter32 enterprises Gauge32 Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-IDENTITY OBJECT-TYPE Unsigned32 |
| SNMPv2-TC | AutonomousType DisplayString TestAndIncr TEXTUAL-CONVENTION TimeInterval TimeStamp |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.818 | Identityimv | The MIB module to describe GE Digital Energy Uninterruptible Power Supplies. | ||
| 1.3.6.1.4.1.818.1 | NodegeHardware | |||
| 1.3.6.1.4.1.818.1.1 | NodegeUPS | |||
| 1.3.6.1.4.1.818.1.1.1 | ScalargeDiscoveredUPSsMask | read-only | current | Reading this variable returns bit mask indicating which UPSs in a parallel system are alive. Management software should poll only these UPSs on their snmp bran… |
| 1.3.6.1.4.1.818.1.1.2 | ScalargeRequestPacket | read-write | current | Put the string, formatted as a IMV/CP4 packet, directly to internally RS485 bus. This OID could be used for accede directly to the internally RS485 bus from a … |
| 1.3.6.1.4.1.818.1.1.3 | ScalargeReplyPacket | read-only | current | Contain the reply of the IMV/CP4 request packet sent using the OID geRequestPacket. Every time that a write command has be made at the OID ge RequestPacket, th… |
| 1.3.6.1.4.1.818.1.1.10 | NodegeGenericUPS | |||
| 1.3.6.1.4.1.818.1.1.10.1 | NodeupsIdentgen | |||
| 1.3.6.1.4.1.818.1.1.10.1.1 | ScalarupsIdentManufacturergen | read-only | current | The name of the UPS manufacturer.(*) |
| 1.3.6.1.4.1.818.1.1.10.1.2 | ScalarupsIdentModelgen | read-only | current | The UPS Model designation.(*) |
| 1.3.6.1.4.1.818.1.1.10.1.3 | ScalarupsIdentUPSSoftwareVersiongen | read-only | current | The UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*) |
| 1.3.6.1.4.1.818.1.1.10.1.4 | ScalarupsIdentAgentSoftwareVersiongen | read-only | current | The UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*) |
| 1.3.6.1.4.1.818.1.1.10.1.5 | ScalarupsIdentNamegen | read-write | current | A string identifying the UPS. This object should be set by the administrator.(*) |
| 1.3.6.1.4.1.818.1.1.10.1.6 | ScalarupsIdentAttachedDevicesgen | read-write | current | A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*) |
| 1.3.6.1.4.1.818.1.1.10.1.7 | ScalarupsIdentUPSSerialNumbergen | read-only | current | The UPS serial number |
| 1.3.6.1.4.1.818.1.1.10.1.8 | ScalarupsIdentComProtVersiongen | read-only | current | The IMV communication protocol version |
| 1.3.6.1.4.1.818.1.1.10.1.9 | ScalarupsIdentOperatingTimegen | read-only | current | The present value of the operating time. total 'on' time since UPS manufactured |
| 1.3.6.1.4.1.818.1.1.10.2 | NodeupsBatterygen | |||
| 1.3.6.1.4.1.818.1.1.10.2.1 | ScalarupsBatteryStatusgen | read-only | current | The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfi… |
| 1.3.6.1.4.1.818.1.1.10.2.2 | ScalarupsSecondsOnBatterygen | read-only | current | If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res… |
| 1.3.6.1.4.1.818.1.1.10.2.3 | ScalarupsEstimatedMinutesRemaininggen | read-only | current | An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and… |
| 1.3.6.1.4.1.818.1.1.10.2.4 | ScalarupsEstimatedChargeRemaininggen | read-only | current | An estimate of the battery charge remaining expressed as a percent of full charge.(*) |
| 1.3.6.1.4.1.818.1.1.10.2.5 | ScalarupsBatteryVoltagegen | read-only | current | The magnitude of the present battery voltage.(*) |
| 1.3.6.1.4.1.818.1.1.10.2.6 | ScalarupsBatteryCurrentgen | read-only | current | The present battery current.(*) |
| 1.3.6.1.4.1.818.1.1.10.2.7 | ScalarupsBatteryTemperaturegen | read-only | current | The ambient temperature at or near the UPS Battery casing.(*) |
| 1.3.6.1.4.1.818.1.1.10.2.8 | ScalarupsBatteryRipplegen | read-only | current | The present DC link RMS voltage ripple.(*) |
| 1.3.6.1.4.1.818.1.1.10.3 | NodeupsInputgen | |||
| 1.3.6.1.4.1.818.1.1.10.3.1 | ScalarupsInputLineBadsgen | read-only | current | A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the i… |
| 1.3.6.1.4.1.818.1.1.10.3.2 | ScalarupsInputNumLinesgen | read-only | current | The number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*) |
| 1.3.6.1.4.1.818.1.1.10.3.3 | TableupsInputGenTable | not-accessible | current | A list of input table entries. The number of entries is given by the value of upsInputNumLines.(*) |
| 1.3.6.1.4.1.818.1.1.10.3.3.1 | RowupsInputGenEntry | not-accessible | current | An entry containing information applicable to a particular input line.(*) |
| 1.3.6.1.4.1.818.1.1.10.3.3.1.1 | ColumnupsInputLineIndexgen | not-accessible | current | The input line identifier.(*) |
| 1.3.6.1.4.1.818.1.1.10.3.3.1.2 | ColumnupsInputFrequencygen | read-only | current | The present input frequency.(*) |
| 1.3.6.1.4.1.818.1.1.10.3.3.1.3 | ColumnupsInputVoltagegen | read-only | current | The magnitude of the present input voltage.(*) |
| 1.3.6.1.4.1.818.1.1.10.3.3.1.4 | ColumnupsInputCurrentgen | read-only | current | The magnitude of the present input current.(*) |
| 1.3.6.1.4.1.818.1.1.10.3.3.1.5 | ColumnupsInputTruePowergen | read-only | current | The magnitude of the present input true power.(*) |
| 1.3.6.1.4.1.818.1.1.10.3.3.1.6 | ColumnupsInputVoltageMingen | read-only | current | The lowest magnitude of the input voltage since last read out. |
| 1.3.6.1.4.1.818.1.1.10.3.3.1.7 | ColumnupsInputVoltageMaxgen | read-only | current | The highest magnitude of the input voltage since last read out. |
| 1.3.6.1.4.1.818.1.1.10.4 | NodeupsOutputgen | |||
| 1.3.6.1.4.1.818.1.1.10.4.1 | ScalarupsOutputSourcegen | read-only | current | The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the… |
| 1.3.6.1.4.1.818.1.1.10.4.2 | ScalarupsOutputFrequencygen | read-only | current | The present output frequency.(*) |
| 1.3.6.1.4.1.818.1.1.10.4.3 | ScalarupsOutputNumLinesgen | read-only | current | The number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*) |
| 1.3.6.1.4.1.818.1.1.10.4.4 | TableupsOutputGenTable | not-accessible | current | A list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*) |
| 1.3.6.1.4.1.818.1.1.10.4.4.1 | RowupsOutputGenEntry | not-accessible | current | An entry containing information applicable to a particular output line.(*) |
| 1.3.6.1.4.1.818.1.1.10.4.4.1.1 | ColumnupsOutputLineIndexgen | not-accessible | current | The output line identifier.(*) |
| 1.3.6.1.4.1.818.1.1.10.4.4.1.2 | ColumnupsOutputVoltagegen | read-only | current | The present output voltage.(*) |
| 1.3.6.1.4.1.818.1.1.10.4.4.1.3 | ColumnupsOutputCurrentgen | read-only | current | The present output current.(*) |
| 1.3.6.1.4.1.818.1.1.10.4.4.1.4 | ColumnupsOutputPowergen | read-only | current | The present output true power.(*) |
| 1.3.6.1.4.1.818.1.1.10.4.4.1.5 | ColumnupsOutputPercentLoadgen | read-only | current | The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent… |
| 1.3.6.1.4.1.818.1.1.10.4.4.1.6 | ColumnupsOutputPowerFactorgen | read-only | current | The present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate … |
| 1.3.6.1.4.1.818.1.1.10.4.4.1.7 | ColumnupsOutputPeakCurrentgen | read-only | current | The present output peak current.(*) |
| 1.3.6.1.4.1.818.1.1.10.4.4.1.8 | ColumnupsOutputShareCurrentgen | read-only | current | In a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share… |
| 1.3.6.1.4.1.818.1.1.10.5 | NodeupsBypassgen | |||
| 1.3.6.1.4.1.818.1.1.10.5.1 | ScalarupsBypassFrequencygen | read-only | current | The present bypass frequency.(*) |
| 1.3.6.1.4.1.818.1.1.10.5.2 | ScalarupsBypassNumLinesgen | read-only | current | The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*) |
| 1.3.6.1.4.1.818.1.1.10.5.3 | TableupsBypassGenTable | not-accessible | current | A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*) |
| 1.3.6.1.4.1.818.1.1.10.5.3.1 | RowupsBypassGenEntry | not-accessible | current | An entry containing information applicable to a particular bypass input.(*) |
| 1.3.6.1.4.1.818.1.1.10.5.3.1.1 | ColumnupsBypassLineIndexgen | not-accessible | current | The bypass line identifier.(*) |
| 1.3.6.1.4.1.818.1.1.10.5.3.1.2 | ColumnupsBypassVoltagegen | read-only | current | The present bypass voltage.(*) |
| 1.3.6.1.4.1.818.1.1.10.5.3.1.3 | ColumnupsBypassCurrentgen | read-only | current | The present bypass current.(*) |
| 1.3.6.1.4.1.818.1.1.10.5.3.1.4 | ColumnupsBypassPowergen | read-only | current | The present true power conveyed by the bypass.(*) |
| 1.3.6.1.4.1.818.1.1.10.6 | NodeupsAlarmgen | |||
| 1.3.6.1.4.1.818.1.1.10.6.1 | ScalarupsAlarmsPresentgen | read-only | current | The present number of active alarm conditions.(*) |
| 1.3.6.1.4.1.818.1.1.10.6.2 | TableupsAlarmGenTable | not-accessible | current | A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is … |
| 1.3.6.1.4.1.818.1.1.10.6.2.1 | RowupsAlarmGenEntry | not-accessible | current | An entry containing information applicable to a particular alarm.(*) |
| 1.3.6.1.4.1.818.1.1.10.6.2.1.1 | ColumnupsAlarmIdgen | not-accessible | current | A unique identifier for an alarm condition. This value must remain constant.(*) |
| 1.3.6.1.4.1.818.1.1.10.6.2.1.2 | ColumnupsAlarmDescrgen | read-only | current | A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con… |
| 1.3.6.1.4.1.818.1.1.10.6.2.1.3 | ColumnupsAlarmTimegen | read-only | current | The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before ag… |
| 1.3.6.1.4.1.818.1.1.10.6.3 | NodeupsWellKnownAlarmsgen | |||
| 1.3.6.1.4.1.818.1.1.10.6.3.1 | IdentityupsAlarmBatteryBadgen | current | One or more batteries have been determined to require replacement.(*) | |
| 1.3.6.1.4.1.818.1.1.10.6.3.2 | IdentityupsAlarmOnBatterygen | current | The UPS is drawing power from the batteries.(*) | |
| 1.3.6.1.4.1.818.1.1.10.6.3.3 | IdentityupsAlarmLowBatterygen | current | The remaining battery run-time is less than or equal to upsConfigLowBattTime.(*) | |
| 1.3.6.1.4.1.818.1.1.10.6.3.4 | IdentityupsAlarmDepletedBatterygen | current | The UPS will be unable to sustain the present load when and if the utility power is lost.(*) | |
| 1.3.6.1.4.1.818.1.1.10.6.3.5 | IdentityupsAlarmTempBadgen | current | A temperature is out of tolerance.(*) | |
| 1.3.6.1.4.1.818.1.1.10.6.3.6 | IdentityupsAlarmInputBadgen | current | An input condition is out of tolerance.(*) | |
| 1.3.6.1.4.1.818.1.1.10.6.3.7 | IdentityupsAlarmOutputBadgen | current | An output condition (other than OutputOverload) is out of tolerance.(*) | |
| 1.3.6.1.4.1.818.1.1.10.6.3.8 | IdentityupsAlarmOutputOverloadgen | current | The output load exceeds the UPS output capacity.(*) | |
| 1.3.6.1.4.1.818.1.1.10.6.3.9 | IdentityupsAlarmOnBypassgen | current | The Bypass is presently engaged on the UPS.(*) | |
| 1.3.6.1.4.1.818.1.1.10.6.3.10 | IdentityupsAlarmBypassBadgen | current | The Bypass is out of tolerance.(*) | |
| 1.3.6.1.4.1.818.1.1.10.6.3.11 | IdentityupsAlarmOutputOffAsRequestedgen | current | The UPS has shutdown as requested, i.e., the output is off.(*) | |
| 1.3.6.1.4.1.818.1.1.10.6.3.12 | IdentityupsAlarmUpsOffAsRequestedgen | current | The entire UPS has shutdown as commanded.(*) | |
| 1.3.6.1.4.1.818.1.1.10.6.3.13 | IdentityupsAlarmChargerFailedgen | current | An uncorrected problem has been detected within the UPS charger subsystem.(*) | |
| 1.3.6.1.4.1.818.1.1.10.6.3.14 | IdentityupsAlarmUpsOutputOffgen | current | The output of the UPS is in the off state.(*) | |
| 1.3.6.1.4.1.818.1.1.10.6.3.15 | IdentityupsAlarmUpsSystemOffgen | current | The UPS system is in the off state.(*) | |
| 1.3.6.1.4.1.818.1.1.10.6.3.16 | IdentityupsAlarmFanFailuregen | current | The failure of one or more fans in the UPS has been detected.(*) | |
| 1.3.6.1.4.1.818.1.1.10.6.3.17 | IdentityupsAlarmFuseFailuregen | current | The failure of one or more fuses has been detected.(*) | |
| 1.3.6.1.4.1.818.1.1.10.6.3.18 | IdentityupsAlarmGeneralFaultgen | current | A general fault in the UPS has been detected.(*) | |
| 1.3.6.1.4.1.818.1.1.10.6.3.19 | IdentityupsAlarmDiagnosticTestFailedgen | current | The result of the last diagnostic test indicates a failure.(*) | |
| 1.3.6.1.4.1.818.1.1.10.6.3.20 | IdentityupsAlarmCommunicationsLostgen | current | A problem has been encountered in the communications between the agent and the UPS.(*) | |
| 1.3.6.1.4.1.818.1.1.10.6.3.21 | IdentityupsAlarmAwaitingPowergen | current | The UPS output is off and the UPS is awaiting the return of input power.(*) | |
| 1.3.6.1.4.1.818.1.1.10.6.3.22 | IdentityupsAlarmShutdownPendinggen | current | A upsShutdownAfterDelay countdown is underway.(*) | |
| 1.3.6.1.4.1.818.1.1.10.6.3.23 | IdentityupsAlarmShutdownImminentgen | current | The UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.(*) | |
| 1.3.6.1.4.1.818.1.1.10.6.3.24 | IdentityupsAlarmTestInProgressgen | current | A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of … | |
| 1.3.6.1.4.1.818.1.1.10.6.3.25 | IdentityupsAlarmReceptacleOffgen | current | The receptacle are switch off | |
| 1.3.6.1.4.1.818.1.1.10.6.3.26 | IdentityupsAlarmHighSpeedBusFailuregen | current | A problem on the High Speed Bus communication is detected | |
| 1.3.6.1.4.1.818.1.1.10.6.3.27 | IdentityupsAlarmHighSpeedBusJACRCFailuregen | current | A High Speed Bus CRC failure on Bus JA is detected | |
| 1.3.6.1.4.1.818.1.1.10.6.3.28 | IdentityupsAlarmConnectivityBusFailuregen | current | A problem on the Connectivity Bus communication is detected | |
| 1.3.6.1.4.1.818.1.1.10.6.3.29 | IdentityupsAlarmHighSpeedBusJBCRCFailuregen | current | A High Speed Bus CRC failure on Bus JB is detected | |
| 1.3.6.1.4.1.818.1.1.10.6.3.30 | IdentityupsAlarmCurrentSharinggen | current | The UPS detects an high current sharing on the parallel system | |
| 1.3.6.1.4.1.818.1.1.10.6.3.31 | IdentityupsAlarmDCRipplegen | current | The UPS detects an high ripple voltage on his DC link | |
| 1.3.6.1.4.1.818.1.1.10.6.4 | ScalarupsAlarmMaskAgen | read-only | current | Specifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' com… |
| 1.3.6.1.4.1.818.1.1.10.7 | NodeupsTestgen | |||
| 1.3.6.1.4.1.818.1.1.10.7.1 | ScalarupsTestIdgen | read-write | current | The test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this docu… |
| 1.3.6.1.4.1.818.1.1.10.7.2 | ScalarupsTestSpinLockgen | read-write | current | A spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress a… |
| 1.3.6.1.4.1.818.1.1.10.7.3 | ScalarupsTestResultsSummarygen | read-only | current | The results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test complete… |
| 1.3.6.1.4.1.818.1.1.10.7.4 | ScalarupsTestResultsDetailgen | read-only | current | Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*) |
| 1.3.6.1.4.1.818.1.1.10.7.5 | ScalarupsTestStartTimegen | read-only | current | The value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of… |
| 1.3.6.1.4.1.818.1.1.10.7.6 | ScalarupsTestElapsedTimegen | read-only | current | The amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of … |
| 1.3.6.1.4.1.818.1.1.10.7.7 | NodeupsWellKnownTestsgen | |||
| 1.3.6.1.4.1.818.1.1.10.7.7.1 | IdentityupsTestNoTestsInitiatedgen | current | No tests have been initiated and no test is in progress.(*) | |
| 1.3.6.1.4.1.818.1.1.10.7.7.2 | IdentityupsTestAbortTestInProgressgen | current | The test in progress is to be aborted / the test in progress was aborted.(*) | |
| 1.3.6.1.4.1.818.1.1.10.7.7.3 | IdentityupsTestGeneralSystemsTestgen | current | The manufacturer's standard test of UPS device systems.(*) | |
| 1.3.6.1.4.1.818.1.1.10.7.7.4 | IdentityupsTestQuickBatteryTestgen | current | A test that is sufficient to determine if the battery needs replacement.(*) | |
| 1.3.6.1.4.1.818.1.1.10.7.7.5 | IdentityupsTestDeepBatteryCalibrationgen | current | The system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high deg… | |
| 1.3.6.1.4.1.818.1.1.10.8 | NodeupsControlgen | |||
| 1.3.6.1.4.1.818.1.1.10.8.1 | ScalarupsShutdownTypegen | read-write | current | This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reach… |
| 1.3.6.1.4.1.818.1.1.10.8.2 | ScalarupsShutdownAfterDelaygen | read-write | current | Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdo… |
| 1.3.6.1.4.1.818.1.1.10.8.3 | ScalarupsStartupAfterDelaygen | read-write | current | Setting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause … |
| 1.3.6.1.4.1.818.1.1.10.8.4 | ScalarupsRebootWithDurationgen | read-write | current | Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the ti… |
| 1.3.6.1.4.1.818.1.1.10.8.5 | ScalarupsAutoRestartgen | read-write | current | Setting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutd… |
| 1.3.6.1.4.1.818.1.1.10.8.6 | ScalarupsReceptaclesNumgen | read-only | current | The number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table. |
| 1.3.6.1.4.1.818.1.1.10.8.7 | TableupsReceptacleGenTable | not-accessible | current | A list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum. |
| 1.3.6.1.4.1.818.1.1.10.8.7.1 | RowupsReceptacleGenEntry | not-accessible | current | An entry containing information applicable to a particular receptacle. |
| 1.3.6.1.4.1.818.1.1.10.8.7.1.1 | ColumnupsReceptacleLineIndexgen | not-accessible | current | The receptacle line identifier. |
| 1.3.6.1.4.1.818.1.1.10.8.7.1.2 | ColumnupsReceptacleOnOffgen | read-write | current | The present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptac… |
| 1.3.6.1.4.1.818.1.1.10.8.8 | ScalarupsUPSModegen | read-write | current | The operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transfor… |
| 1.3.6.1.4.1.818.1.1.10.8.9 | ScalarupsRectifierOnOffgen | read-write | current | The present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier … |
| 1.3.6.1.4.1.818.1.1.10.8.10 | ScalarupsBatteryChargeMethodgen | read-write | current | The present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this objec… |
| 1.3.6.1.4.1.818.1.1.10.8.11 | ScalarupsInverterOnOffgen | read-write | current | The present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off… |
| 1.3.6.1.4.1.818.1.1.10.8.12 | ScalarupsBypassOnOffgen | read-write | current | The present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If… |
| 1.3.6.1.4.1.818.1.1.10.8.13 | ScalarupsLoadSourcegen | read-write | current | The present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will … |
| 1.3.6.1.4.1.818.1.1.10.9 | NodeupsConfiggen | |||
| 1.3.6.1.4.1.818.1.1.10.9.1 | ScalarupsConfigInputVoltagegen | read-write | current | The magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a v… |
| 1.3.6.1.4.1.818.1.1.10.9.2 | ScalarupsConfigInputFreqgen | read-write | current | The nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is no… |
| 1.3.6.1.4.1.818.1.1.10.9.3 | ScalarupsConfigOutputVoltagegen | read-write | current | The magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a … |
| 1.3.6.1.4.1.818.1.1.10.9.4 | ScalarupsConfigOutputFreqgen | read-write | current | The nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is n… |
| 1.3.6.1.4.1.818.1.1.10.9.5 | ScalarupsConfigOutputVAgen | read-only | current | The magnitude of the nominal Volt-Amp rating.(*) |
| 1.3.6.1.4.1.818.1.1.10.9.6 | ScalarupsConfigOutputPowergen | read-only | current | The magnitude of the nominal true power rating.(*) |
| 1.3.6.1.4.1.818.1.1.10.9.7 | ScalarupsConfigLowBattTimegen | read-write | current | The value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the … |
| 1.3.6.1.4.1.818.1.1.10.9.8 | ScalarupsConfigAudibleStatusgen | read-write | current | The requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this … |
| 1.3.6.1.4.1.818.1.1.10.9.9 | ScalarupsConfigLowVoltageTransferPointgen | read-write | current | The minimum input line voltage allowed before the UPS system transfers to battery backup.(*) |
| 1.3.6.1.4.1.818.1.1.10.9.10 | ScalarupsConfigHighVoltageTransferPointgen | read-write | current | The maximum line voltage allowed before the UPS system transfers to battery backup.(*) |
| 1.3.6.1.4.1.818.1.1.10.9.11 | ScalarupsConfigBatteryCapacitygen | read-write | current | The installed battery capacity. This value is the 'factory'-value, not the value after calibration. |
| 1.3.6.1.4.1.818.1.1.10.9.12 | ScalarupsConfigBatteryChargeCurrentgen | read-write | current | The maximum battery charge current, including external chargers. |
| 1.3.6.1.4.1.818.1.1.10.9.13 | ScalarupsConfigNoLoadShutdowngen | read-write | current | Dis- or enable 'no load' shutdown from the contact interface. |
| 1.3.6.1.4.1.818.1.1.10.9.14 | ScalarupsConfigStartDelaygen | read-write | current | Minimum required autonomy time before the UPS may perform an autorestart. |
| 1.3.6.1.4.1.818.1.1.10.10 | NodeupsGetSetgen | |||
| 1.3.6.1.4.1.818.1.1.10.10.1 | ScalarupsEventGetNextgen | read-write | current | The number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The val… |
| 1.3.6.1.4.1.818.1.1.10.10.2 | ScalarupsEventGetPreviousgen | read-write | current | The number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The val… |
| 1.3.6.1.4.1.818.1.1.10.10.3 | ScalarupsEventSetStartingTimeStampgen | read-write | current | The timestamp which is used as starting point for downloading events from the UPS event buffer |
| 1.3.6.1.4.1.818.1.1.10.10.4 | ScalarupsEventRetreiveCurrentTimeStampgen | read-only | current | The current timestamp is retreived from the UPS |
| 1.3.6.1.4.1.818.1.1.10.10.5 | ScalarupsEventTableSizegen | read-only | current | The number of entries in the event table. This object indicates the number of rows in the event table. |
| 1.3.6.1.4.1.818.1.1.10.10.6 | TableupsEventGenTable | not-accessible | current | A list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the… |
| 1.3.6.1.4.1.818.1.1.10.10.6.1 | RowupsEventGenEntry | not-accessible | current | An entry containing information applicable to a particular event. |
| 1.3.6.1.4.1.818.1.1.10.10.6.1.1 | ColumnupsEventLineIndexgen | not-accessible | current | The event line identifier. |
| 1.3.6.1.4.1.818.1.1.10.10.6.1.2 | ColumnupsEventCodegen | read-only | current | The event code in numerical format. |
| 1.3.6.1.4.1.818.1.1.10.10.6.1.3 | ColumnupsEventStatusgen | read-only | current | The status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status … |
| 1.3.6.1.4.1.818.1.1.10.10.6.1.4 | ColumnupsEventTimegen | read-only | current | The timestamp of the moment the event was generated. |
| 1.3.6.1.4.1.818.1.1.10.10.7 | ScalarupsParametersReadgen | read-write | current | The number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value up… |
| 1.3.6.1.4.1.818.1.1.10.10.8 | ScalarupsParametersWritegen | read-write | current | The number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be u… |
| 1.3.6.1.4.1.818.1.1.10.10.9 | ScalarupsParametersStartAddressgen | read-write | current | The address which is used as starting point for downloading parameters from the UPS |
| 1.3.6.1.4.1.818.1.1.10.10.10 | ScalarupsParameterTableSizegen | read-only | current | The number of entries in the parameter table. This object indicates the number of rows in the parameter table. |
| 1.3.6.1.4.1.818.1.1.10.10.11 | TableupsParameterGenTable | not-accessible | current | A list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of t… |
| 1.3.6.1.4.1.818.1.1.10.10.11.1 | RowupsParameterGenEntry | not-accessible | current | An entry containing information applicable to a particular parameter. |
| 1.3.6.1.4.1.818.1.1.10.10.11.1.1 | ColumnupsParameterLineIndexgen | not-accessible | current | The parameter line identifier. |
| 1.3.6.1.4.1.818.1.1.10.10.11.1.2 | ColumnupsParameterValuegen | read-write | current | The parameter value in numerical format. |
| 1.3.6.1.4.1.818.1.1.10.10.12 | ScalarupsStatusgen | read-only | current | The global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other comman… |
| 1.3.6.1.4.1.818.1.1.10.10.13 | ScalarupsMainsStatisticsMBfailgen | read-only | current | Count of main bypass failures (>200 ms), since UPS installation. |
| 1.3.6.1.4.1.818.1.1.10.10.14 | ScalarupsMainsStatisticsMRfailgen | read-only | current | Count of mains rectifier failures (>200 ms), since UPS installation. |
| 1.3.6.1.4.1.818.1.1.10.10.15 | ScalarupsMainsStatisticsB2gen | read-only | current | Count of transients on the mains bypass (0..2 ms), during the last 7 days. |
| 1.3.6.1.4.1.818.1.1.10.10.16 | ScalarupsMainsStatisticsB5gen | read-only | current | Count of transients on the mains bypass (2..5 ms), during the last 7 days. |
| 1.3.6.1.4.1.818.1.1.10.10.17 | ScalarupsMainsStatisticsB10gen | read-only | current | Count of transients on the mains bypass (5..10 ms), during the last 7 days. |
| 1.3.6.1.4.1.818.1.1.10.10.18 | ScalarupsMainsStatisticsB200gen | read-only | current | Count of transients on the mains bypass (10..200 ms), during the last 7 days. |
| 1.3.6.1.4.1.818.1.1.10.10.19 | ScalarupsMainsStatisticsBypRelgen | read-only | current | Bypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'. |
| 1.3.6.1.4.1.818.1.1.10.10.20 | ScalarupsTimegen | read-write | current | The current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp for… |
| 1.3.6.1.4.1.818.1.1.10.10.21 | ScalarupsRequestPermissiongen | read-write | current | An encrypted code is send to enable use of restricted write objects during a limited period of time. |
| 1.3.6.1.4.1.818.1.1.10.10.22 | ScalarupsEventGetCodegen | read-write | current | The code which is used as starting point to downloading the events from the UPS event buffer. |
| 1.3.6.1.4.1.818.1.1.10.10.23 | ScalarupsEventSpinLockgen | read-write | current | A spin lock on the event subsystem. |
| 1.3.6.1.4.1.818.1.1.10.10.24 | ScalarupsParameterSpinLockgen | read-write | current | A spin lock on the parameters subsystem. |
| 1.3.6.1.4.1.818.1.1.10.11 | NodegeUPSTrapsgen | |||
| 1.3.6.1.4.1.818.1.1.10.11.1 | NotificationupsTrapAlarmBatteryBadgen | current | One or more batteries have been determined to require replacement. | |
| 1.3.6.1.4.1.818.1.1.10.11.2 | NotificationupsTrapAlarmOnBatterygen | current | The UPS is drawing power from the batteries. | |
| 1.3.6.1.4.1.818.1.1.10.11.3 | NotificationupsTrapAlarmLowBatterygen | current | The remaining battery run-time is less than or equal to upsConfigLowBattTime. | |
| 1.3.6.1.4.1.818.1.1.10.11.4 | NotificationupsTrapAlarmDepletedBatterygen | current | The UPS will be unable to sustain the present load when and if the utility power is lost) | |
| 1.3.6.1.4.1.818.1.1.10.11.5 | NotificationupsTrapAlarmTempBadgen | current | A temperature is out of tolerance. | |
| 1.3.6.1.4.1.818.1.1.10.11.6 | NotificationupsTrapAlarmInputBadgen | current | An input condition is out of tolerance. | |
| 1.3.6.1.4.1.818.1.1.10.11.7 | NotificationupsTrapAlarmOutputBadgen | current | An output condition (other than OutputOverload) is out of tolerance. | |
| 1.3.6.1.4.1.818.1.1.10.11.8 | NotificationupsTrapAlarmOutputOverloadgen | current | The output load exceeds the UPS output capacity. | |
| 1.3.6.1.4.1.818.1.1.10.11.9 | NotificationupsTrapAlarmOnBypassgen | current | The Bypass is presently engaged on the UPS. | |
| 1.3.6.1.4.1.818.1.1.10.11.10 | NotificationupsTrapAlarmBypassBadgen | current | The Bypass is out of tolerance. | |
| 1.3.6.1.4.1.818.1.1.10.11.11 | NotificationupsTrapAlarmOutputOffAsRequestedgen | current | The UPS has shutdown as requested, i.e., the output is off. | |
| 1.3.6.1.4.1.818.1.1.10.11.12 | NotificationupsTrapAlarmUpsOffAsRequestedgen | current | The entire UPS has shutdown as commanded. | |
| 1.3.6.1.4.1.818.1.1.10.11.13 | NotificationupsTrapAlarmChargerFailedgen | current | An uncorrected problem has been detected within the UPS charger subsystem. | |
| 1.3.6.1.4.1.818.1.1.10.11.14 | NotificationupsTrapAlarmUpsOutputOffgen | current | The output of the UPS is in the off state. | |
| 1.3.6.1.4.1.818.1.1.10.11.15 | NotificationupsTrapAlarmUpsSystemOffgen | current | The UPS system is in the off state. | |
| 1.3.6.1.4.1.818.1.1.10.11.16 | NotificationupsTrapAlarmFanFailuregen | current | The failure of one or more fans in the UPS has been detected. | |
| 1.3.6.1.4.1.818.1.1.10.11.17 | NotificationupsTrapAlarmFuseFailuregen | current | The failure of one or more fuses has been detected. | |
| 1.3.6.1.4.1.818.1.1.10.11.18 | NotificationupsTrapAlarmGeneralFaultgen | current | A general fault in the UPS has been detected. | |
| 1.3.6.1.4.1.818.1.1.10.11.19 | NotificationupsTrapAlarmDiagnosticTestFailedgen | current | The result of the last diagnostic test indicates a failure. | |
| 1.3.6.1.4.1.818.1.1.10.11.20 | NotificationupsTrapAlarmCommunicationsLostgen | current | A problem has been encountered in the communication between the agent and the UPS. | |
| 1.3.6.1.4.1.818.1.1.10.11.21 | NotificationupsTrapAlarmAwaitingPowergen | current | The UPS output is off and the UPS is awaiting the return of the input power (*). | |
| 1.3.6.1.4.1.818.1.1.10.11.22 | NotificationupsTrapAlarmShutdownPendinggen | current | A upsShutdownAfterDelay countdown is underway. | |
| 1.3.6.1.4.1.818.1.1.10.11.23 | NotificationupsTrapAlarmShutdownImminentgen | current | The UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown. | |
| 1.3.6.1.4.1.818.1.1.10.11.24 | NotificationupsTrapAlarmTestInProgressgen | current | A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of … | |
| 1.3.6.1.4.1.818.1.1.10.11.25 | NotificationupsTrapAlarmReceptacleOffgen | current | A receptacle has been switched off. | |
| 1.3.6.1.4.1.818.1.1.10.11.26 | NotificationupsTrapAlarmHighspeedBusFailuregen | current | A problem on the Highspeed Bus communication is detected. | |
| 1.3.6.1.4.1.818.1.1.10.11.27 | NotificationupsTrapAlarmHighspeedBusJACRCFailuregen | current | A CRC failure on the Highspeed Bus JA is detected. | |
| 1.3.6.1.4.1.818.1.1.10.11.28 | NotificationupsTrapAlarmConnectivityBusFailuregen | current | A Connectivity Bus failure is detected | |
| 1.3.6.1.4.1.818.1.1.10.11.29 | NotificationupsTrapAlarmHighspeedBusJBCRCFailuregen | current | A CRC failure on the Highspeed Bus JB is detected. | |
| 1.3.6.1.4.1.818.1.1.10.11.30 | NotificationupsTrapAlarmCurrentSharingFailuregen | current | An high current sharing on the parallel system is detected. | |
| 1.3.6.1.4.1.818.1.1.10.11.31 | NotificationupsTrapAlarmDCRippleFailuregen | current | An high ripple voltage on his DC link is detected. | |
| 1.3.6.1.4.1.818.1.1.10.11.33 | NotificationupsTrapAlarmBatteryBadRestoredgen | current | A Battery bad condition is restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.34 | NotificationupsTrapAlarmOnBatteryRestoredgen | current | The UPS is drawing power from mains again. | |
| 1.3.6.1.4.1.818.1.1.10.11.35 | NotificationupsTrapAlarmLowBatteryRestoredgen | current | A Low Battery condition is restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.36 | NotificationupsTrapAlarmDepletedBatteryRestoredgen | current | A Depleted Battery condition is restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.37 | NotificationupsTrapAlarmTempBadRestoredgen | current | A bad temperature condition is restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.38 | NotificationupsTrapAlarmInputBadRestoredgen | current | An input bad condition is restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.39 | NotificationupsTrapAlarmOutputBadRestoredgen | current | An output bad condition is restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.40 | NotificationupsTrapAlarmOutputOverloadRestoredgen | current | An output overload condition is restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.41 | NotificationupsTrapAlarmOnBypassRestoredgen | current | An On Bypass condition is restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.42 | NotificationupsTrapAlarmBypassBadRestoredgen | current | A Bypass bad condition is restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.43 | NotificationupsTrapAlarmOutputOffAsRequestedRestoredgen | current | A request shutdown has been restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.44 | NotificationupsTrapAlarmUpsOffAsRequestedRestoredgen | current | A entire UPS command has been restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.45 | NotificationupsTrapAlarmChargerFailedRestoredgen | current | A Charger Failer condition is restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.46 | NotificationupsTrapAlarmUpsOutputOngen | current | The output of the UPS switched in the on state. | |
| 1.3.6.1.4.1.818.1.1.10.11.47 | NotificationupsTrapAlarmUpsSystemOngen | current | The UPS system is switched in the on state. | |
| 1.3.6.1.4.1.818.1.1.10.11.48 | NotificationupsTrapAlarmFanFailureRestoredgen | current | A Fan failure condition is restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.49 | NotificationupsTrapAlarmFuseFailureRestoredgen | current | A Fuse failure condition is restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.50 | NotificationupsTrapAlarmGeneralFaultRestoredgen | current | A general fault is restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.51 | NotificationupsTrapAlarmDiagnosticTestFailedRestoredgen | current | A last diagnostic test indicates a failure is restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.52 | NotificationupsTrapAlarmCommunicationsLostRestoredgen | current | A problem in the communication between the agent and the UPS is restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.53 | NotificationupsTrapAlarmAwaitingPowerRestoredgen | current | A awaiting power condition is restored (*). | |
| 1.3.6.1.4.1.818.1.1.10.11.54 | NotificationupsTrapAlarmShutdownPendingRestoredgen | current | A upsShutdownAfterDelay countdown is restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.55 | NotificationupsTrapAlarmShutdownImminentRestoredgen | current | A shutdown imminent condition is restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.56 | NotificationupsTrapAlarmTestInProgressRestoredgen | current | The test is in progress is terminated. | |
| 1.3.6.1.4.1.818.1.1.10.11.57 | NotificationupsTrapAlarmReceptacleOn | current | A receptacle has been switched on. | |
| 1.3.6.1.4.1.818.1.1.10.11.58 | NotificationupsTrapAlarmHighspeedBusRestoredgen | current | A problem on the Highspeed Bus communication is restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.59 | NotificationupsTrapAlarmHighspeedBusJACRCRestoredAgen | current | A CRC failure on the Highspeed Bus JA is restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.60 | NotificationupsTrapAlarmConnectivityBusRestoredgen | current | A problem on the Connectivity Bus communication is restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.61 | NotificationupsTrapAlarmHighspeedBusJBCRCRestoredBgen | current | A CRC failure on the Highspeed Bus JB is restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.62 | NotificationupsTrapAlarmCurrentSharingRestoredgen | current | An high current sharing on the parallel system is restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.63 | NotificationupsTrapAlarmDCRippleRestoredgen | current | An high ripple voltage on his DC link is restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.129 | NotificationupsTrapAlarmValueLowgen | current | A measurement value reached a value below its low-level threshold. | |
| 1.3.6.1.4.1.818.1.1.10.11.130 | NotificationupsTrapAlarmValueHighgen | current | A measurement value reached a value higher than its high-level threshold. | |
| 1.3.6.1.4.1.818.1.1.10.11.133 | NotificationupsTrapAlarmValueLowRestoredgen | current | A ValueLow alarm condition is restored. | |
| 1.3.6.1.4.1.818.1.1.10.11.134 | NotificationupsTrapAlarmValueHighRestoredgen | current | A ValueHigh alarm condition is restored. | |
| 1.3.6.1.4.1.818.1.1.10.12 | NodeupsDiagnosticgen | |||
| 1.3.6.1.4.1.818.1.1.10.12.1 | ScalarupsDiagnosticBusJACommunicationStatusgen | read-only | current | Bit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA … |
| 1.3.6.1.4.1.818.1.1.10.12.2 | ScalarupsDiagnosticBusJBCommunicationStatusgen | read-only | current | Bit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA … |
| 1.3.6.1.4.1.818.1.1.10.12.3 | ScalarupsDiagnosticBatteryLifetimegen | read-only | current | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data … |
| 1.3.6.1.4.1.818.1.1.10.12.4 | ScalarupsDiagnosticFansLifetimegen | read-only | current | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data … |
| 1.3.6.1.4.1.818.1.1.10.12.5 | ScalarupsDiagnosticDCcapacitorsLifetimegen | read-only | current | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data … |
| 1.3.6.1.4.1.818.1.1.10.12.6 | ScalarupsDiagnosticACcapacitorsLifetimegen | read-only | current | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data … |
| 1.3.6.1.4.1.818.1.1.10.12.7 | ScalarupsDiagnosticGlobalServiceCheckgen | read-only | current | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data … |
| 1.3.6.1.4.1.818.1.100 | NodegeDevices | |||
| 1.3.6.1.4.1.818.1.100.1 | NodegeDevicesDescriptions | |||
| 1.3.6.1.4.1.818.1.100.1.1 | NodeadvSNMPWebIntCard | |||
| 1.3.6.1.4.1.818.1.100.1.2 | NodesnmpWebIntCard | |||
| 1.3.6.1.4.1.818.1.100.1.3 | NodesnmpWebIntBox |
Type Definitions
| Name | Syntax | Status | Description |
|---|---|---|---|
| NonNegativeInteger32 | Integer32 (0..2147483647) | current | This data type is a non-negative value. |
| PositiveInteger32 | Integer32 (1..2147483647) | current | This data type is a non-zero and non-negative value. |