MIB Viewer

GUDEADS-ENC2111-MIB

59 objects
No module-level DESCRIPTION found.
Imported Objects
SNMPv2-CONFNOTIFICATION-GROUP OBJECT-GROUP
SNMPv2-SMIenterprises Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE Unsigned32
OIDNameAccessStatusDescription
1.3.6.1.4.1.28507Identitygudeads
1.3.6.1.4.1.28507.60NodegadsENC2111
1.3.6.1.4.1.28507.60.1Nodeenc2111Objects
1.3.6.1.4.1.28507.60.1.1Nodeenc2111CommonConfig
1.3.6.1.4.1.28507.60.1.1.1Nodeenc2111SNMPaccess
1.3.6.1.4.1.28507.60.1.1.1.1Scalarenc2111TrapCtrlread-writecurrent0 = off 1 = Ver. 1 2 = Ver. 2c 3 = Ver. 3
1.3.6.1.4.1.28507.60.1.1.1.2Tableenc2111TrapIPTablenot-accessiblecurrentlist of all Trap receiver
1.3.6.1.4.1.28507.60.1.1.1.2.1Rowenc2111TrapIPEntrynot-accessiblecurrentan entry containing management informations regarding the list of trap receivers
1.3.6.1.4.1.28507.60.1.1.1.2.1.1Columnenc2111TrapIPIndexread-onlycurrentA unique value, greater than zero, for each receiver slot.
1.3.6.1.4.1.28507.60.1.1.1.2.1.2Columnenc2111TrapAddrread-writecurrentDNS name or IP address specifying one Trap receiver slot. A port can optionally be specified: 'name:port' An empty string disables this slot.
1.3.6.1.4.1.28507.60.1.2Nodeenc2111DeviceConfig
1.3.6.1.4.1.28507.60.1.3Nodeenc2111IntActors
1.3.6.1.4.1.28507.60.1.3.1Nodeenc2111relayports
1.3.6.1.4.1.28507.60.1.3.1.1Scalarenc2111portNumberread-onlycurrentThe number of Relay Ports
1.3.6.1.4.1.28507.60.1.3.1.2Tableenc2111portTablenot-accessiblecurrentlist of all EPC Relay Ports
1.3.6.1.4.1.28507.60.1.3.1.2.1Rowenc2111portEntrynot-accessiblecurrentAn entry containing management information applicable to a particular relay port.
1.3.6.1.4.1.28507.60.1.3.1.2.1.1Columnenc2111PortIndexread-onlycurrentA unique value, greater than zero, for each Relay Port.
1.3.6.1.4.1.28507.60.1.3.1.2.1.2Columnenc2111PortNameread-writecurrentA textual string containing name of a Relay Port.
1.3.6.1.4.1.28507.60.1.3.1.2.1.3Columnenc2111PortStateread-writecurrentcurrent state of a Relay Port
1.3.6.1.4.1.28507.60.1.3.1.2.1.4Columnenc2111PortSwitchCountread-onlycurrentThe total number of switch actions ocurred on a Relay Port. Does not count switch commands which will not switch the ralay state, so just real relay switches a…
1.3.6.1.4.1.28507.60.1.3.1.2.1.5Columnenc2111PortStartupModeread-writecurrentset Mode of startup sequence (off, on , remember last state)
1.3.6.1.4.1.28507.60.1.3.1.2.1.6Columnenc2111PortStartupDelayread-writecurrentDelay in sec for startup action
1.3.6.1.4.1.28507.60.1.3.1.2.1.7Columnenc2111PortRepowerTimeread-writecurrentDelay in sec for repower port after switching off
1.3.6.1.4.1.28507.60.1.4Nodeenc2111ExtActors
1.3.6.1.4.1.28507.60.1.5Nodeenc2111IntSensors
1.3.6.1.4.1.28507.60.1.5.6Nodeenc2111Inputs
1.3.6.1.4.1.28507.60.1.5.6.1Scalarenc2111ActiveInputsread-onlycurrentNumber of suppported Input Channels.
1.3.6.1.4.1.28507.60.1.5.6.2Tableenc2111InputTablenot-accessiblecurrent
1.3.6.1.4.1.28507.60.1.5.6.2.1Rowenc2111InputEntrynot-accessiblecurrent
1.3.6.1.4.1.28507.60.1.5.6.2.1.1Columnenc2111InputIndexread-onlycurrent
1.3.6.1.4.1.28507.60.1.5.6.2.1.2Columnenc2111Inputread-onlycurrentInput state of device
1.3.6.1.4.1.28507.60.1.5.7Nodeenc2111VoltageInfo
1.3.6.1.4.1.28507.60.1.5.7.1Scalarenc2111State12Vread-onlycurrentShow state of internal 12V
1.3.6.1.4.1.28507.60.1.5.7.2Scalarenc2111State3Vread-onlycurrentShow state of internal 3.3V
1.3.6.1.4.1.28507.60.1.5.10Scalarenc2111POEread-onlycurrentsignals POE availability
1.3.6.1.4.1.28507.60.1.6Nodeenc2111ExtSensors
1.3.6.1.4.1.28507.60.1.6.1Tableenc2111SensorTablenot-accessiblecurrent
1.3.6.1.4.1.28507.60.1.6.1.1Rowenc2111SensorEntrynot-accessiblecurrent
1.3.6.1.4.1.28507.60.1.6.1.1.1Columnenc2111SensorIndexread-onlycurrent
1.3.6.1.4.1.28507.60.1.6.1.1.2Columnenc2111TempSensorread-onlycurrentactual temperature
1.3.6.1.4.1.28507.60.1.6.1.1.3Columnenc2111HygroSensorread-onlycurrentactual humidity
1.3.6.1.4.1.28507.60.1.6.1.1.4Columnenc2111InputSensorread-onlycurrentlogical state of input sensor
1.3.6.1.4.1.28507.60.1.6.1.1.5Columnenc2111AirPressureread-onlycurrentactual air pressure
1.3.6.1.4.1.28507.60.1.6.1.1.6Columnenc2111DewPointread-onlycurrentdew point for actual temperature and humidity
1.3.6.1.4.1.28507.60.1.6.1.1.7Columnenc2111DewPointDiffread-onlycurrentdifference between dew point and actual temperature (Temp - DewPoint)
1.3.6.1.4.1.28507.60.2Nodeenc2111Conf
1.3.6.1.4.1.28507.60.2.1Nodeenc2111Groups
1.3.6.1.4.1.28507.60.2.1.1Groupenc2111BasicGroupcurrentBasic objects.
1.3.6.1.4.1.28507.60.2.1.2Groupenc2111NotificationGroupcurrent
1.3.6.1.4.1.28507.60.2.2Nodeenc2111Compls
1.3.6.1.4.1.28507.60.3Nodeevents
1.3.6.1.4.1.28507.60.3.1Notificationenc2111SwitchEvtPortcurrentEvent is triggered when a port is switched
1.3.6.1.4.1.28507.60.3.2Notificationenc2111InputEvtcurrentChange of device input.
1.3.6.1.4.1.28507.60.3.3Notificationenc2111TempEvtSencurrenttemperature limits exceeded
1.3.6.1.4.1.28507.60.3.4Notificationenc2111HygroEvtSencurrenthygro limits exceeded
1.3.6.1.4.1.28507.60.3.5Notificationenc2111InputEvtSencurrentchange of logical input sensor state
1.3.6.1.4.1.28507.60.3.6Notificationenc2111AirPressureEvtSencurrentAir Pressure limits exceeded
1.3.6.1.4.1.28507.60.3.7Notificationenc2111DewPtDiffEvtSencurrentDew Point Difference limits exceeded
1.3.6.1.4.1.28507.60.3.8Notificationenc2111POEEvtcurrentPower over Ethernet changed