MIB Viewer

GUDEADS-ENC2191-MIB

59 objects
No module-level DESCRIPTION found.
Imported Objects
SNMPv2-CONFNOTIFICATION-GROUP OBJECT-GROUP
SNMPv2-SMIenterprises Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE Unsigned32
OIDNameAccessStatusDescription
1.3.6.1.4.1.28507Identitygudeads
1.3.6.1.4.1.28507.61NodegadsENC2191
1.3.6.1.4.1.28507.61.1Nodeenc2191Objects
1.3.6.1.4.1.28507.61.1.1Nodeenc2191CommonConfig
1.3.6.1.4.1.28507.61.1.1.1Nodeenc2191SNMPaccess
1.3.6.1.4.1.28507.61.1.1.1.1Scalarenc2191TrapCtrlread-writecurrent0 = off 1 = Ver. 1 2 = Ver. 2c 3 = Ver. 3
1.3.6.1.4.1.28507.61.1.1.1.2Tableenc2191TrapIPTablenot-accessiblecurrentlist of all Trap receiver
1.3.6.1.4.1.28507.61.1.1.1.2.1Rowenc2191TrapIPEntrynot-accessiblecurrentan entry containing management informations regarding the list of trap receivers
1.3.6.1.4.1.28507.61.1.1.1.2.1.1Columnenc2191TrapIPIndexread-onlycurrentA unique value, greater than zero, for each receiver slot.
1.3.6.1.4.1.28507.61.1.1.1.2.1.2Columnenc2191TrapAddrread-writecurrentDNS name or IP address specifying one Trap receiver slot. A port can optionally be specified: 'name:port' An empty string disables this slot.
1.3.6.1.4.1.28507.61.1.2Nodeenc2191DeviceConfig
1.3.6.1.4.1.28507.61.1.3Nodeenc2191IntActors
1.3.6.1.4.1.28507.61.1.3.1Nodeenc2191relayports
1.3.6.1.4.1.28507.61.1.3.1.1Scalarenc2191portNumberread-onlycurrentThe number of Relay Ports
1.3.6.1.4.1.28507.61.1.3.1.2Tableenc2191portTablenot-accessiblecurrentlist of all EPC Relay Ports
1.3.6.1.4.1.28507.61.1.3.1.2.1Rowenc2191portEntrynot-accessiblecurrentAn entry containing management information applicable to a particular relay port.
1.3.6.1.4.1.28507.61.1.3.1.2.1.1Columnenc2191PortIndexread-onlycurrentA unique value, greater than zero, for each Relay Port.
1.3.6.1.4.1.28507.61.1.3.1.2.1.2Columnenc2191PortNameread-writecurrentA textual string containing name of a Relay Port.
1.3.6.1.4.1.28507.61.1.3.1.2.1.3Columnenc2191PortStateread-writecurrentcurrent state of a Relay Port
1.3.6.1.4.1.28507.61.1.3.1.2.1.4Columnenc2191PortSwitchCountread-onlycurrentThe total number of switch actions ocurred on a Relay Port. Does not count switch commands which will not switch the ralay state, so just real relay switches a…
1.3.6.1.4.1.28507.61.1.3.1.2.1.5Columnenc2191PortStartupModeread-writecurrentset Mode of startup sequence (off, on , remember last state)
1.3.6.1.4.1.28507.61.1.3.1.2.1.6Columnenc2191PortStartupDelayread-writecurrentDelay in sec for startup action
1.3.6.1.4.1.28507.61.1.3.1.2.1.7Columnenc2191PortRepowerTimeread-writecurrentDelay in sec for repower port after switching off
1.3.6.1.4.1.28507.61.1.4Nodeenc2191ExtActors
1.3.6.1.4.1.28507.61.1.5Nodeenc2191IntSensors
1.3.6.1.4.1.28507.61.1.5.6Nodeenc2191Inputs
1.3.6.1.4.1.28507.61.1.5.6.1Scalarenc2191ActiveInputsread-onlycurrentNumber of suppported Input Channels.
1.3.6.1.4.1.28507.61.1.5.6.2Tableenc2191InputTablenot-accessiblecurrent
1.3.6.1.4.1.28507.61.1.5.6.2.1Rowenc2191InputEntrynot-accessiblecurrent
1.3.6.1.4.1.28507.61.1.5.6.2.1.1Columnenc2191InputIndexread-onlycurrent
1.3.6.1.4.1.28507.61.1.5.6.2.1.2Columnenc2191Inputread-onlycurrentInput state of device
1.3.6.1.4.1.28507.61.1.5.7Nodeenc2191VoltageInfo
1.3.6.1.4.1.28507.61.1.5.7.1Scalarenc2191State12Vread-onlycurrentShow state of internal 12V
1.3.6.1.4.1.28507.61.1.5.7.2Scalarenc2191State3Vread-onlycurrentShow state of internal 3.3V
1.3.6.1.4.1.28507.61.1.5.10Scalarenc2191POEread-onlycurrentsignals POE availability
1.3.6.1.4.1.28507.61.1.6Nodeenc2191ExtSensors
1.3.6.1.4.1.28507.61.1.6.1Tableenc2191SensorTablenot-accessiblecurrent
1.3.6.1.4.1.28507.61.1.6.1.1Rowenc2191SensorEntrynot-accessiblecurrent
1.3.6.1.4.1.28507.61.1.6.1.1.1Columnenc2191SensorIndexread-onlycurrent
1.3.6.1.4.1.28507.61.1.6.1.1.2Columnenc2191TempSensorread-onlycurrentactual temperature
1.3.6.1.4.1.28507.61.1.6.1.1.3Columnenc2191HygroSensorread-onlycurrentactual humidity
1.3.6.1.4.1.28507.61.1.6.1.1.4Columnenc2191InputSensorread-onlycurrentlogical state of input sensor
1.3.6.1.4.1.28507.61.1.6.1.1.5Columnenc2191AirPressureread-onlycurrentactual air pressure
1.3.6.1.4.1.28507.61.1.6.1.1.6Columnenc2191DewPointread-onlycurrentdew point for actual temperature and humidity
1.3.6.1.4.1.28507.61.1.6.1.1.7Columnenc2191DewPointDiffread-onlycurrentdifference between dew point and actual temperature (Temp - DewPoint)
1.3.6.1.4.1.28507.61.2Nodeenc2191Conf
1.3.6.1.4.1.28507.61.2.1Nodeenc2191Groups
1.3.6.1.4.1.28507.61.2.1.1Groupenc2191BasicGroupcurrentBasic objects.
1.3.6.1.4.1.28507.61.2.1.2Groupenc2191NotificationGroupcurrent
1.3.6.1.4.1.28507.61.2.2Nodeenc2191Compls
1.3.6.1.4.1.28507.61.3Nodeevents
1.3.6.1.4.1.28507.61.3.1Notificationenc2191SwitchEvtPortcurrentEvent is triggered when a port is switched
1.3.6.1.4.1.28507.61.3.2Notificationenc2191InputEvtcurrentChange of device input.
1.3.6.1.4.1.28507.61.3.3Notificationenc2191TempEvtSencurrenttemperature limits exceeded
1.3.6.1.4.1.28507.61.3.4Notificationenc2191HygroEvtSencurrenthygro limits exceeded
1.3.6.1.4.1.28507.61.3.5Notificationenc2191InputEvtSencurrentchange of logical input sensor state
1.3.6.1.4.1.28507.61.3.6Notificationenc2191AirPressureEvtSencurrentAir Pressure limits exceeded
1.3.6.1.4.1.28507.61.3.7Notificationenc2191DewPtDiffEvtSencurrentDew Point Difference limits exceeded
1.3.6.1.4.1.28507.61.3.8Notificationenc2191POEEvtcurrentPower over Ethernet changed