GUDEADS-EPC8221-MIB
81 objects
No module-level DESCRIPTION found.
Imported Objects
| SNMPv2-CONF | NOTIFICATION-GROUP OBJECT-GROUP |
| SNMPv2-SMI | enterprises Gauge32 Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE Unsigned32 |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.28507 | Identitygudeads | |||
| 1.3.6.1.4.1.28507.56 | NodegadsEPC8221 | |||
| 1.3.6.1.4.1.28507.56.1 | Nodeepc8221Objects | |||
| 1.3.6.1.4.1.28507.56.1.1 | Nodeepc8221CommonConfig | |||
| 1.3.6.1.4.1.28507.56.1.1.1 | Nodeepc8221SNMPaccess | |||
| 1.3.6.1.4.1.28507.56.1.1.1.1 | Scalarepc8221TrapCtrl | read-write | current | 0 = off 1 = Ver. 1 2 = Ver. 2c 3 = Ver. 3 |
| 1.3.6.1.4.1.28507.56.1.1.1.2 | Tableepc8221TrapIPTable | not-accessible | current | list of all Trap receiver |
| 1.3.6.1.4.1.28507.56.1.1.1.2.1 | Rowepc8221TrapIPEntry | not-accessible | current | an entry containing management informations regarding the list of trap receivers |
| 1.3.6.1.4.1.28507.56.1.1.1.2.1.1 | Columnepc8221TrapIPIndex | read-only | current | A unique value, greater than zero, for each receiver slot. |
| 1.3.6.1.4.1.28507.56.1.1.1.2.1.2 | Columnepc8221TrapAddr | read-write | current | DNS name or IP address specifying one Trap receiver slot. A port can optionally be specified: 'name:port' An empty string disables this slot. |
| 1.3.6.1.4.1.28507.56.1.2 | Nodeepc8221DeviceConfig | |||
| 1.3.6.1.4.1.28507.56.1.3 | Nodeepc8221IntActors | |||
| 1.3.6.1.4.1.28507.56.1.3.1 | Nodeepc8221relayports | |||
| 1.3.6.1.4.1.28507.56.1.3.1.1 | Scalarepc8221portNumber | read-only | current | The number of Relay Ports |
| 1.3.6.1.4.1.28507.56.1.3.1.2 | Tableepc8221portTable | not-accessible | current | list of all EPC Relay Ports |
| 1.3.6.1.4.1.28507.56.1.3.1.2.1 | Rowepc8221portEntry | not-accessible | current | An entry containing management information applicable to a particular relay port. |
| 1.3.6.1.4.1.28507.56.1.3.1.2.1.1 | Columnepc8221PortIndex | read-only | current | A unique value, greater than zero, for each Relay Port. |
| 1.3.6.1.4.1.28507.56.1.3.1.2.1.2 | Columnepc8221PortName | read-write | current | A textual string containing name of a Relay Port. |
| 1.3.6.1.4.1.28507.56.1.3.1.2.1.3 | Columnepc8221PortState | read-write | current | current state of a Relay Port |
| 1.3.6.1.4.1.28507.56.1.3.1.2.1.4 | Columnepc8221PortSwitchCount | read-only | current | The total number of switch actions ocurred on a Relay Port. Does not count switch commands which will not switch the ralay state, so just real relay switches a… |
| 1.3.6.1.4.1.28507.56.1.3.1.2.1.5 | Columnepc8221PortStartupMode | read-write | current | set Mode of startup sequence (off, on , remember last state) |
| 1.3.6.1.4.1.28507.56.1.3.1.2.1.6 | Columnepc8221PortStartupDelay | read-write | current | Delay in sec for startup action |
| 1.3.6.1.4.1.28507.56.1.3.1.2.1.7 | Columnepc8221PortRepowerTime | read-write | current | Delay in sec for repower port after switching off |
| 1.3.6.1.4.1.28507.56.1.3.10 | Scalarepc8221Buzzer | read-write | current | turn Buzzer on and off |
| 1.3.6.1.4.1.28507.56.1.4 | Nodeepc8221ExtActors | |||
| 1.3.6.1.4.1.28507.56.1.5 | Nodeepc8221IntSensors | |||
| 1.3.6.1.4.1.28507.56.1.5.1 | Nodeepc8221PowerChan | |||
| 1.3.6.1.4.1.28507.56.1.5.1.1 | Scalarepc8221ActivePowerChan | read-only | current | Number of suppported Power Channels. |
| 1.3.6.1.4.1.28507.56.1.5.1.2 | Tableepc8221PowerTable | not-accessible | current | All available Channel Interfaces. |
| 1.3.6.1.4.1.28507.56.1.5.1.2.1 | Rowepc8221PowerEntry | not-accessible | current | An entry containing management information applicable to a particular Power Channel. |
| 1.3.6.1.4.1.28507.56.1.5.1.2.1.1 | Columnepc8221PowerIndex | read-only | current | Index of Power Channel entries |
| 1.3.6.1.4.1.28507.56.1.5.1.2.1.2 | Columnepc8221ChanStatus | read-only | current | 0 = data not active, 1 = data valid |
| 1.3.6.1.4.1.28507.56.1.5.1.2.1.3 | Columnepc8221AbsEnergyActive | read-only | current | Absolute Active Energy counter. |
| 1.3.6.1.4.1.28507.56.1.5.1.2.1.4 | Columnepc8221PowerActive | read-only | current | Active Power |
| 1.3.6.1.4.1.28507.56.1.5.1.2.1.5 | Columnepc8221Current | read-only | current | Actual Curent on Power Channel. |
| 1.3.6.1.4.1.28507.56.1.5.1.2.1.6 | Columnepc8221Voltage | read-only | current | Actual Voltage on Power Channel |
| 1.3.6.1.4.1.28507.56.1.5.1.2.1.7 | Columnepc8221Frequency | read-only | current | Frequency of Power Channel |
| 1.3.6.1.4.1.28507.56.1.5.1.2.1.8 | Columnepc8221PowerFactor | read-only | current | Power Factor of Channel between -1.0 and 1.00 |
| 1.3.6.1.4.1.28507.56.1.5.1.2.1.9 | Columnepc8221Pangle | read-only | current | Phase Angle between Voltage and L Line Current between -180.0 and 180.0 |
| 1.3.6.1.4.1.28507.56.1.5.1.2.1.10 | Columnepc8221PowerApparent | read-only | current | L Line Mean Apparent Power |
| 1.3.6.1.4.1.28507.56.1.5.1.2.1.11 | Columnepc8221PowerReactive | read-only | current | L Line Mean Reactive Power |
| 1.3.6.1.4.1.28507.56.1.5.1.2.1.12 | Columnepc8221AbsEnergyReactive | read-only | current | Absolute Reactive Energy counter. |
| 1.3.6.1.4.1.28507.56.1.5.1.2.1.13 | Columnepc8221AbsEnergyActiveResettable | read-write | current | Resettable Absolute Active Energy counter. Writing '0' resets all resettable counter. |
| 1.3.6.1.4.1.28507.56.1.5.1.2.1.14 | Columnepc8221AbsEnergyReactiveResettable | read-only | current | Resettable Absolute Reactive Energy counter. |
| 1.3.6.1.4.1.28507.56.1.5.1.2.1.15 | Columnepc8221ResetTime | read-only | current | Time in seconds since last Energy Counter reset. |
| 1.3.6.1.4.1.28507.56.1.5.1.2.1.16 | Columnepc8221ForwEnergyActive | read-only | current | Forward Active Energy counter. |
| 1.3.6.1.4.1.28507.56.1.5.1.2.1.17 | Columnepc8221ForwEnergyReactive | read-only | current | Forward Reactive Energy counter. |
| 1.3.6.1.4.1.28507.56.1.5.1.2.1.18 | Columnepc8221ForwEnergyActiveResettable | read-only | current | Resettable Forward Active Energy counter. |
| 1.3.6.1.4.1.28507.56.1.5.1.2.1.19 | Columnepc8221ForwEnergyReactiveResettable | read-only | current | Resettable Forward Reactive Energy counter. |
| 1.3.6.1.4.1.28507.56.1.5.1.2.1.20 | Columnepc8221RevEnergyActive | read-only | current | Reverse Active Energy counter. |
| 1.3.6.1.4.1.28507.56.1.5.1.2.1.21 | Columnepc8221RevEnergyReactive | read-only | current | Reverse Reactive Energy counter. |
| 1.3.6.1.4.1.28507.56.1.5.1.2.1.22 | Columnepc8221RevEnergyActiveResettable | read-only | current | Resettable Reverse Active Energy counter. |
| 1.3.6.1.4.1.28507.56.1.5.1.2.1.23 | Columnepc8221RevEnergyReactiveResettable | read-only | current | Resettable Reverse Reactive Energy counter. |
| 1.3.6.1.4.1.28507.56.1.5.2 | Tableepc8221OVPTable | not-accessible | current | Overvoltage Protection Table This table may not be present on devices without OVP feature |
| 1.3.6.1.4.1.28507.56.1.5.2.1 | Rowepc8221OVPEntry | not-accessible | current | |
| 1.3.6.1.4.1.28507.56.1.5.2.1.1 | Columnepc8221OVPIndex | read-only | current | |
| 1.3.6.1.4.1.28507.56.1.5.2.1.2 | Columnepc8221OVPStatus | read-only | current | shows the status of the built-in Overvoltage Protection |
| 1.3.6.1.4.1.28507.56.1.6 | Nodeepc8221ExtSensors | |||
| 1.3.6.1.4.1.28507.56.1.6.1 | Tableepc8221SensorTable | not-accessible | current | |
| 1.3.6.1.4.1.28507.56.1.6.1.1 | Rowepc8221SensorEntry | not-accessible | current | |
| 1.3.6.1.4.1.28507.56.1.6.1.1.1 | Columnepc8221SensorIndex | read-only | current | |
| 1.3.6.1.4.1.28507.56.1.6.1.1.2 | Columnepc8221TempSensor | read-only | current | actual temperature |
| 1.3.6.1.4.1.28507.56.1.6.1.1.3 | Columnepc8221HygroSensor | read-only | current | actual humidity |
| 1.3.6.1.4.1.28507.56.1.6.1.1.4 | Columnepc8221InputSensor | read-only | current | logical state of input sensor |
| 1.3.6.1.4.1.28507.56.1.6.1.1.5 | Columnepc8221AirPressure | read-only | current | actual air pressure |
| 1.3.6.1.4.1.28507.56.1.6.1.1.6 | Columnepc8221DewPoint | read-only | current | dew point for actual temperature and humidity |
| 1.3.6.1.4.1.28507.56.1.6.1.1.7 | Columnepc8221DewPointDiff | read-only | current | difference between dew point and actual temperature (Temp - DewPoint) |
| 1.3.6.1.4.1.28507.56.2 | Nodeepc8221Conf | |||
| 1.3.6.1.4.1.28507.56.2.1 | Nodeepc8221Groups | |||
| 1.3.6.1.4.1.28507.56.2.1.1 | Groupepc8221BasicGroup | current | Basic objects. | |
| 1.3.6.1.4.1.28507.56.2.1.2 | Groupepc8221NotificationGroup | current | ||
| 1.3.6.1.4.1.28507.56.2.2 | Nodeepc8221Compls | |||
| 1.3.6.1.4.1.28507.56.3 | Nodeevents | |||
| 1.3.6.1.4.1.28507.56.3.1 | Notificationepc8221SwitchEvtPort | current | Event is triggered when a port is switched | |
| 1.3.6.1.4.1.28507.56.3.2 | Notificationepc8221TempEvtSen | current | temperature limits exceeded | |
| 1.3.6.1.4.1.28507.56.3.3 | Notificationepc8221HygroEvtSen | current | hygro limits exceeded | |
| 1.3.6.1.4.1.28507.56.3.4 | Notificationepc8221InputEvtSen | current | change of logical input sensor state | |
| 1.3.6.1.4.1.28507.56.3.5 | Notificationepc8221AirPressureEvtSen | current | Air Pressure limits exceeded | |
| 1.3.6.1.4.1.28507.56.3.6 | Notificationepc8221DewPtDiffEvtSen | current | Dew Point Difference limits exceeded | |
| 1.3.6.1.4.1.28507.56.3.7 | Notificationepc8221OVPEvt | current | Event is triggered when the OVP status changes | |
| 1.3.6.1.4.1.28507.56.3.8 | Notificationepc8221LineAmperageEvt | current | Event is triggered when a measured current is crossing the entered limits |