MIB Viewer

GUDEADS-EPC8221-MIB

81 objects
No module-level DESCRIPTION found.
Imported Objects
SNMPv2-CONFNOTIFICATION-GROUP OBJECT-GROUP
SNMPv2-SMIenterprises Gauge32 Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE Unsigned32
OIDNameAccessStatusDescription
1.3.6.1.4.1.28507Identitygudeads
1.3.6.1.4.1.28507.56NodegadsEPC8221
1.3.6.1.4.1.28507.56.1Nodeepc8221Objects
1.3.6.1.4.1.28507.56.1.1Nodeepc8221CommonConfig
1.3.6.1.4.1.28507.56.1.1.1Nodeepc8221SNMPaccess
1.3.6.1.4.1.28507.56.1.1.1.1Scalarepc8221TrapCtrlread-writecurrent0 = off 1 = Ver. 1 2 = Ver. 2c 3 = Ver. 3
1.3.6.1.4.1.28507.56.1.1.1.2Tableepc8221TrapIPTablenot-accessiblecurrentlist of all Trap receiver
1.3.6.1.4.1.28507.56.1.1.1.2.1Rowepc8221TrapIPEntrynot-accessiblecurrentan entry containing management informations regarding the list of trap receivers
1.3.6.1.4.1.28507.56.1.1.1.2.1.1Columnepc8221TrapIPIndexread-onlycurrentA unique value, greater than zero, for each receiver slot.
1.3.6.1.4.1.28507.56.1.1.1.2.1.2Columnepc8221TrapAddrread-writecurrentDNS name or IP address specifying one Trap receiver slot. A port can optionally be specified: 'name:port' An empty string disables this slot.
1.3.6.1.4.1.28507.56.1.2Nodeepc8221DeviceConfig
1.3.6.1.4.1.28507.56.1.3Nodeepc8221IntActors
1.3.6.1.4.1.28507.56.1.3.1Nodeepc8221relayports
1.3.6.1.4.1.28507.56.1.3.1.1Scalarepc8221portNumberread-onlycurrentThe number of Relay Ports
1.3.6.1.4.1.28507.56.1.3.1.2Tableepc8221portTablenot-accessiblecurrentlist of all EPC Relay Ports
1.3.6.1.4.1.28507.56.1.3.1.2.1Rowepc8221portEntrynot-accessiblecurrentAn entry containing management information applicable to a particular relay port.
1.3.6.1.4.1.28507.56.1.3.1.2.1.1Columnepc8221PortIndexread-onlycurrentA unique value, greater than zero, for each Relay Port.
1.3.6.1.4.1.28507.56.1.3.1.2.1.2Columnepc8221PortNameread-writecurrentA textual string containing name of a Relay Port.
1.3.6.1.4.1.28507.56.1.3.1.2.1.3Columnepc8221PortStateread-writecurrentcurrent state of a Relay Port
1.3.6.1.4.1.28507.56.1.3.1.2.1.4Columnepc8221PortSwitchCountread-onlycurrentThe total number of switch actions ocurred on a Relay Port. Does not count switch commands which will not switch the ralay state, so just real relay switches a…
1.3.6.1.4.1.28507.56.1.3.1.2.1.5Columnepc8221PortStartupModeread-writecurrentset Mode of startup sequence (off, on , remember last state)
1.3.6.1.4.1.28507.56.1.3.1.2.1.6Columnepc8221PortStartupDelayread-writecurrentDelay in sec for startup action
1.3.6.1.4.1.28507.56.1.3.1.2.1.7Columnepc8221PortRepowerTimeread-writecurrentDelay in sec for repower port after switching off
1.3.6.1.4.1.28507.56.1.3.10Scalarepc8221Buzzerread-writecurrentturn Buzzer on and off
1.3.6.1.4.1.28507.56.1.4Nodeepc8221ExtActors
1.3.6.1.4.1.28507.56.1.5Nodeepc8221IntSensors
1.3.6.1.4.1.28507.56.1.5.1Nodeepc8221PowerChan
1.3.6.1.4.1.28507.56.1.5.1.1Scalarepc8221ActivePowerChanread-onlycurrentNumber of suppported Power Channels.
1.3.6.1.4.1.28507.56.1.5.1.2Tableepc8221PowerTablenot-accessiblecurrentAll available Channel Interfaces.
1.3.6.1.4.1.28507.56.1.5.1.2.1Rowepc8221PowerEntrynot-accessiblecurrentAn entry containing management information applicable to a particular Power Channel.
1.3.6.1.4.1.28507.56.1.5.1.2.1.1Columnepc8221PowerIndexread-onlycurrentIndex of Power Channel entries
1.3.6.1.4.1.28507.56.1.5.1.2.1.2Columnepc8221ChanStatusread-onlycurrent0 = data not active, 1 = data valid
1.3.6.1.4.1.28507.56.1.5.1.2.1.3Columnepc8221AbsEnergyActiveread-onlycurrentAbsolute Active Energy counter.
1.3.6.1.4.1.28507.56.1.5.1.2.1.4Columnepc8221PowerActiveread-onlycurrentActive Power
1.3.6.1.4.1.28507.56.1.5.1.2.1.5Columnepc8221Currentread-onlycurrentActual Curent on Power Channel.
1.3.6.1.4.1.28507.56.1.5.1.2.1.6Columnepc8221Voltageread-onlycurrentActual Voltage on Power Channel
1.3.6.1.4.1.28507.56.1.5.1.2.1.7Columnepc8221Frequencyread-onlycurrentFrequency of Power Channel
1.3.6.1.4.1.28507.56.1.5.1.2.1.8Columnepc8221PowerFactorread-onlycurrentPower Factor of Channel between -1.0 and 1.00
1.3.6.1.4.1.28507.56.1.5.1.2.1.9Columnepc8221Pangleread-onlycurrentPhase Angle between Voltage and L Line Current between -180.0 and 180.0
1.3.6.1.4.1.28507.56.1.5.1.2.1.10Columnepc8221PowerApparentread-onlycurrentL Line Mean Apparent Power
1.3.6.1.4.1.28507.56.1.5.1.2.1.11Columnepc8221PowerReactiveread-onlycurrentL Line Mean Reactive Power
1.3.6.1.4.1.28507.56.1.5.1.2.1.12Columnepc8221AbsEnergyReactiveread-onlycurrentAbsolute Reactive Energy counter.
1.3.6.1.4.1.28507.56.1.5.1.2.1.13Columnepc8221AbsEnergyActiveResettableread-writecurrentResettable Absolute Active Energy counter. Writing '0' resets all resettable counter.
1.3.6.1.4.1.28507.56.1.5.1.2.1.14Columnepc8221AbsEnergyReactiveResettableread-onlycurrentResettable Absolute Reactive Energy counter.
1.3.6.1.4.1.28507.56.1.5.1.2.1.15Columnepc8221ResetTimeread-onlycurrentTime in seconds since last Energy Counter reset.
1.3.6.1.4.1.28507.56.1.5.1.2.1.16Columnepc8221ForwEnergyActiveread-onlycurrentForward Active Energy counter.
1.3.6.1.4.1.28507.56.1.5.1.2.1.17Columnepc8221ForwEnergyReactiveread-onlycurrentForward Reactive Energy counter.
1.3.6.1.4.1.28507.56.1.5.1.2.1.18Columnepc8221ForwEnergyActiveResettableread-onlycurrentResettable Forward Active Energy counter.
1.3.6.1.4.1.28507.56.1.5.1.2.1.19Columnepc8221ForwEnergyReactiveResettableread-onlycurrentResettable Forward Reactive Energy counter.
1.3.6.1.4.1.28507.56.1.5.1.2.1.20Columnepc8221RevEnergyActiveread-onlycurrentReverse Active Energy counter.
1.3.6.1.4.1.28507.56.1.5.1.2.1.21Columnepc8221RevEnergyReactiveread-onlycurrentReverse Reactive Energy counter.
1.3.6.1.4.1.28507.56.1.5.1.2.1.22Columnepc8221RevEnergyActiveResettableread-onlycurrentResettable Reverse Active Energy counter.
1.3.6.1.4.1.28507.56.1.5.1.2.1.23Columnepc8221RevEnergyReactiveResettableread-onlycurrentResettable Reverse Reactive Energy counter.
1.3.6.1.4.1.28507.56.1.5.2Tableepc8221OVPTablenot-accessiblecurrentOvervoltage Protection Table This table may not be present on devices without OVP feature
1.3.6.1.4.1.28507.56.1.5.2.1Rowepc8221OVPEntrynot-accessiblecurrent
1.3.6.1.4.1.28507.56.1.5.2.1.1Columnepc8221OVPIndexread-onlycurrent
1.3.6.1.4.1.28507.56.1.5.2.1.2Columnepc8221OVPStatusread-onlycurrentshows the status of the built-in Overvoltage Protection
1.3.6.1.4.1.28507.56.1.6Nodeepc8221ExtSensors
1.3.6.1.4.1.28507.56.1.6.1Tableepc8221SensorTablenot-accessiblecurrent
1.3.6.1.4.1.28507.56.1.6.1.1Rowepc8221SensorEntrynot-accessiblecurrent
1.3.6.1.4.1.28507.56.1.6.1.1.1Columnepc8221SensorIndexread-onlycurrent
1.3.6.1.4.1.28507.56.1.6.1.1.2Columnepc8221TempSensorread-onlycurrentactual temperature
1.3.6.1.4.1.28507.56.1.6.1.1.3Columnepc8221HygroSensorread-onlycurrentactual humidity
1.3.6.1.4.1.28507.56.1.6.1.1.4Columnepc8221InputSensorread-onlycurrentlogical state of input sensor
1.3.6.1.4.1.28507.56.1.6.1.1.5Columnepc8221AirPressureread-onlycurrentactual air pressure
1.3.6.1.4.1.28507.56.1.6.1.1.6Columnepc8221DewPointread-onlycurrentdew point for actual temperature and humidity
1.3.6.1.4.1.28507.56.1.6.1.1.7Columnepc8221DewPointDiffread-onlycurrentdifference between dew point and actual temperature (Temp - DewPoint)
1.3.6.1.4.1.28507.56.2Nodeepc8221Conf
1.3.6.1.4.1.28507.56.2.1Nodeepc8221Groups
1.3.6.1.4.1.28507.56.2.1.1Groupepc8221BasicGroupcurrentBasic objects.
1.3.6.1.4.1.28507.56.2.1.2Groupepc8221NotificationGroupcurrent
1.3.6.1.4.1.28507.56.2.2Nodeepc8221Compls
1.3.6.1.4.1.28507.56.3Nodeevents
1.3.6.1.4.1.28507.56.3.1Notificationepc8221SwitchEvtPortcurrentEvent is triggered when a port is switched
1.3.6.1.4.1.28507.56.3.2Notificationepc8221TempEvtSencurrenttemperature limits exceeded
1.3.6.1.4.1.28507.56.3.3Notificationepc8221HygroEvtSencurrenthygro limits exceeded
1.3.6.1.4.1.28507.56.3.4Notificationepc8221InputEvtSencurrentchange of logical input sensor state
1.3.6.1.4.1.28507.56.3.5Notificationepc8221AirPressureEvtSencurrentAir Pressure limits exceeded
1.3.6.1.4.1.28507.56.3.6Notificationepc8221DewPtDiffEvtSencurrentDew Point Difference limits exceeded
1.3.6.1.4.1.28507.56.3.7Notificationepc8221OVPEvtcurrentEvent is triggered when the OVP status changes
1.3.6.1.4.1.28507.56.3.8Notificationepc8221LineAmperageEvtcurrentEvent is triggered when a measured current is crossing the entered limits