MIB Viewer

GUDEADS-EPC8226-MIB

109 objects
No module-level DESCRIPTION found.
Imported Objects
SNMPv2-CONFNOTIFICATION-GROUP OBJECT-GROUP
SNMPv2-SMIenterprises Gauge32 Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE Unsigned32
OIDNameAccessStatusDescription
1.3.6.1.4.1.28507Identitygudeads
1.3.6.1.4.1.28507.58NodegadsEPC8226
1.3.6.1.4.1.28507.58.1Nodeepc8226Objects
1.3.6.1.4.1.28507.58.1.1Nodeepc8226CommonConfig
1.3.6.1.4.1.28507.58.1.1.1Nodeepc8226SNMPaccess
1.3.6.1.4.1.28507.58.1.1.1.1Scalarepc8226TrapCtrlread-writecurrent0 = off 1 = Ver. 1 2 = Ver. 2c 3 = Ver. 3
1.3.6.1.4.1.28507.58.1.1.1.2Tableepc8226TrapIPTablenot-accessiblecurrentlist of all Trap receiver
1.3.6.1.4.1.28507.58.1.1.1.2.1Rowepc8226TrapIPEntrynot-accessiblecurrentan entry containing management informations regarding the list of trap receivers
1.3.6.1.4.1.28507.58.1.1.1.2.1.1Columnepc8226TrapIPIndexread-onlycurrentA unique value, greater than zero, for each receiver slot.
1.3.6.1.4.1.28507.58.1.1.1.2.1.2Columnepc8226TrapAddrread-writecurrentDNS name or IP address specifying one Trap receiver slot. A port can optionally be specified: 'name:port' An empty string disables this slot.
1.3.6.1.4.1.28507.58.1.2Nodeepc8226DeviceConfig
1.3.6.1.4.1.28507.58.1.3Nodeepc8226IntActors
1.3.6.1.4.1.28507.58.1.3.1Nodeepc8226relayports
1.3.6.1.4.1.28507.58.1.3.1.1Scalarepc8226portNumberread-onlycurrentThe number of Relay Ports
1.3.6.1.4.1.28507.58.1.3.1.2Tableepc8226portTablenot-accessiblecurrentlist of all EPC Relay Ports
1.3.6.1.4.1.28507.58.1.3.1.2.1Rowepc8226portEntrynot-accessiblecurrentAn entry containing management information applicable to a particular relay port.
1.3.6.1.4.1.28507.58.1.3.1.2.1.1Columnepc8226PortIndexread-onlycurrentA unique value, greater than zero, for each Relay Port.
1.3.6.1.4.1.28507.58.1.3.1.2.1.2Columnepc8226PortNameread-writecurrentA textual string containing name of a Relay Port.
1.3.6.1.4.1.28507.58.1.3.1.2.1.3Columnepc8226PortStateread-writecurrentcurrent state of a Relay Port
1.3.6.1.4.1.28507.58.1.3.1.2.1.4Columnepc8226PortSwitchCountread-onlycurrentThe total number of switch actions ocurred on a Relay Port. Does not count switch commands which will not switch the ralay state, so just real relay switches a…
1.3.6.1.4.1.28507.58.1.3.1.2.1.5Columnepc8226PortStartupModeread-writecurrentset Mode of startup sequence (off, on , remember last state)
1.3.6.1.4.1.28507.58.1.3.1.2.1.6Columnepc8226PortStartupDelayread-writecurrentDelay in sec for startup action
1.3.6.1.4.1.28507.58.1.3.1.2.1.7Columnepc8226PortRepowerTimeread-writecurrentDelay in sec for repower port after switching off
1.3.6.1.4.1.28507.58.1.3.10Scalarepc8226Buzzerread-writecurrentturn Buzzer on and off
1.3.6.1.4.1.28507.58.1.4Nodeepc8226ExtActors
1.3.6.1.4.1.28507.58.1.5Nodeepc8226IntSensors
1.3.6.1.4.1.28507.58.1.5.1Nodeepc8226PowerChan
1.3.6.1.4.1.28507.58.1.5.1.1Scalarepc8226ActivePowerChanread-onlycurrentNumber of suppported Power Channels.
1.3.6.1.4.1.28507.58.1.5.1.2Tableepc8226PowerTablenot-accessiblecurrentAll available Channel Interfaces.
1.3.6.1.4.1.28507.58.1.5.1.2.1Rowepc8226PowerEntrynot-accessiblecurrentAn entry containing management information applicable to a particular Power Channel.
1.3.6.1.4.1.28507.58.1.5.1.2.1.1Columnepc8226PowerIndexread-onlycurrentIndex of Power Channel entries
1.3.6.1.4.1.28507.58.1.5.1.2.1.2Columnepc8226ChanStatusread-onlycurrent0 = data not active, 1 = data valid
1.3.6.1.4.1.28507.58.1.5.1.2.1.3Columnepc8226AbsEnergyActiveread-onlycurrentAbsolute Active Energy counter.
1.3.6.1.4.1.28507.58.1.5.1.2.1.4Columnepc8226PowerActiveread-onlycurrentActive Power
1.3.6.1.4.1.28507.58.1.5.1.2.1.5Columnepc8226Currentread-onlycurrentActual Curent on Power Channel.
1.3.6.1.4.1.28507.58.1.5.1.2.1.6Columnepc8226Voltageread-onlycurrentActual Voltage on Power Channel
1.3.6.1.4.1.28507.58.1.5.1.2.1.7Columnepc8226Frequencyread-onlycurrentFrequency of Power Channel
1.3.6.1.4.1.28507.58.1.5.1.2.1.8Columnepc8226PowerFactorread-onlycurrentPower Factor of Channel between -1.0 and 1.00
1.3.6.1.4.1.28507.58.1.5.1.2.1.9Columnepc8226Pangleread-onlycurrentPhase Angle between Voltage and L Line Current between -180.0 and 180.0
1.3.6.1.4.1.28507.58.1.5.1.2.1.10Columnepc8226PowerApparentread-onlycurrentL Line Mean Apparent Power
1.3.6.1.4.1.28507.58.1.5.1.2.1.11Columnepc8226PowerReactiveread-onlycurrentL Line Mean Reactive Power
1.3.6.1.4.1.28507.58.1.5.1.2.1.12Columnepc8226AbsEnergyReactiveread-onlycurrentAbsolute Reactive Energy counter.
1.3.6.1.4.1.28507.58.1.5.1.2.1.13Columnepc8226AbsEnergyActiveResettableread-writecurrentResettable Absolute Active Energy counter. Writing '0' resets all resettable counter.
1.3.6.1.4.1.28507.58.1.5.1.2.1.14Columnepc8226AbsEnergyReactiveResettableread-onlycurrentResettable Absolute Reactive Energy counter.
1.3.6.1.4.1.28507.58.1.5.1.2.1.15Columnepc8226ResetTimeread-onlycurrentTime in seconds since last Energy Counter reset.
1.3.6.1.4.1.28507.58.1.5.1.2.1.16Columnepc8226ForwEnergyActiveread-onlycurrentForward Active Energy counter.
1.3.6.1.4.1.28507.58.1.5.1.2.1.17Columnepc8226ForwEnergyReactiveread-onlycurrentForward Reactive Energy counter.
1.3.6.1.4.1.28507.58.1.5.1.2.1.18Columnepc8226ForwEnergyActiveResettableread-onlycurrentResettable Forward Active Energy counter.
1.3.6.1.4.1.28507.58.1.5.1.2.1.19Columnepc8226ForwEnergyReactiveResettableread-onlycurrentResettable Forward Reactive Energy counter.
1.3.6.1.4.1.28507.58.1.5.1.2.1.20Columnepc8226RevEnergyActiveread-onlycurrentReverse Active Energy counter.
1.3.6.1.4.1.28507.58.1.5.1.2.1.21Columnepc8226RevEnergyReactiveread-onlycurrentReverse Reactive Energy counter.
1.3.6.1.4.1.28507.58.1.5.1.2.1.22Columnepc8226RevEnergyActiveResettableread-onlycurrentResettable Reverse Active Energy counter.
1.3.6.1.4.1.28507.58.1.5.1.2.1.23Columnepc8226RevEnergyReactiveResettableread-onlycurrentResettable Reverse Reactive Energy counter.
1.3.6.1.4.1.28507.58.1.5.2Tableepc8226OVPTablenot-accessiblecurrentOvervoltage Protection Table This table may not be present on devices without OVP feature
1.3.6.1.4.1.28507.58.1.5.2.1Rowepc8226OVPEntrynot-accessiblecurrent
1.3.6.1.4.1.28507.58.1.5.2.1.1Columnepc8226OVPIndexread-onlycurrent
1.3.6.1.4.1.28507.58.1.5.2.1.2Columnepc8226OVPStatusread-onlycurrentshows the status of the built-in Overvoltage Protection
1.3.6.1.4.1.28507.58.1.5.5Nodeepc8226SinglePortPowerChan
1.3.6.1.4.1.28507.58.1.5.5.1Scalarepc8226spActivePowerChanread-onlycurrentNumber of Single Port Power Channels. Value is zero on EPC 8220 series.
1.3.6.1.4.1.28507.58.1.5.5.2Tableepc8226spPowerTablenot-accessiblecurrentAll available Single Port Power Channel Interfaces. Indices 0-5 mean Ports A1 to A6, 6-11 are Ports B1 to B6. This table may not be present on devices that hav…
1.3.6.1.4.1.28507.58.1.5.5.2.1Rowepc8226spPowerEntrynot-accessiblecurrentAn entry containing management information applicable to a particular Single Port Power Channel.
1.3.6.1.4.1.28507.58.1.5.5.2.1.1Columnepc8226spPowerIndexread-onlycurrentIndex of Single Port Power Channel entries. Indices 0-5 mean Ports A1 to A6, 6-11 are Ports B1 to B6.
1.3.6.1.4.1.28507.58.1.5.5.2.1.2Columnepc8226spChanStatusread-onlycurrent0 = data not active, 1 = data valid
1.3.6.1.4.1.28507.58.1.5.5.2.1.3Columnepc8226spAbsEnergyActiveread-onlycurrentAbsolute Active Energy counter.
1.3.6.1.4.1.28507.58.1.5.5.2.1.4Columnepc8226spPowerActiveread-onlycurrentActive Power
1.3.6.1.4.1.28507.58.1.5.5.2.1.5Columnepc8226spCurrentread-onlycurrentActual Curent on Power Channel.
1.3.6.1.4.1.28507.58.1.5.5.2.1.6Columnepc8226spVoltageread-onlycurrentActual Voltage on Power Channel
1.3.6.1.4.1.28507.58.1.5.5.2.1.7Columnepc8226spFrequencyread-onlycurrentFrequency of Power Channel
1.3.6.1.4.1.28507.58.1.5.5.2.1.8Columnepc8226spPowerFactorread-onlycurrentPower Factor of Channel between -1.0 and 1.00
1.3.6.1.4.1.28507.58.1.5.5.2.1.9Columnepc8226spPangleread-onlycurrentPhase Angle between Voltage and L Line Current between -180.0 and 180.0
1.3.6.1.4.1.28507.58.1.5.5.2.1.10Columnepc8226spPowerApparentread-onlycurrentL Line Mean Apparent Power
1.3.6.1.4.1.28507.58.1.5.5.2.1.11Columnepc8226spPowerReactiveread-onlycurrentL Line Mean Reactive Power
1.3.6.1.4.1.28507.58.1.5.5.2.1.12Columnepc8226spAbsEnergyReactiveread-onlycurrentAbsolute Reactive Energy counter.
1.3.6.1.4.1.28507.58.1.5.5.2.1.13Columnepc8226spAbsEnergyActiveResettableread-writecurrentResettable Absolute Active Energy counter. Writing '0' resets all resettable counter.
1.3.6.1.4.1.28507.58.1.5.5.2.1.14Columnepc8226spAbsEnergyReactiveResettableread-onlycurrentResettable Absolute Reactive Energy counter.
1.3.6.1.4.1.28507.58.1.5.5.2.1.15Columnepc8226spResetTimeread-onlycurrentTime in seconds since last Energy Counter reset.
1.3.6.1.4.1.28507.58.1.5.5.2.1.16Columnepc8226spForwEnergyActiveread-onlycurrentForward Active Energy counter.
1.3.6.1.4.1.28507.58.1.5.5.2.1.17Columnepc8226spForwEnergyReactiveread-onlycurrentForward Reactive Energy counter.
1.3.6.1.4.1.28507.58.1.5.5.2.1.18Columnepc8226spForwEnergyActiveResettableread-onlycurrentResettable Forward Active Energy counter.
1.3.6.1.4.1.28507.58.1.5.5.2.1.19Columnepc8226spForwEnergyReactiveResettableread-onlycurrentResettable Forward Reactive Energy counter.
1.3.6.1.4.1.28507.58.1.5.5.2.1.20Columnepc8226spRevEnergyActiveread-onlycurrentReverse Active Energy counter.
1.3.6.1.4.1.28507.58.1.5.5.2.1.21Columnepc8226spRevEnergyReactiveread-onlycurrentReverse Reactive Energy counter.
1.3.6.1.4.1.28507.58.1.5.5.2.1.22Columnepc8226spRevEnergyActiveResettableread-onlycurrentResettable Reverse Active Energy counter.
1.3.6.1.4.1.28507.58.1.5.5.2.1.23Columnepc8226spRevEnergyReactiveResettableread-onlycurrentResettable Reverse Reactive Energy counter.
1.3.6.1.4.1.28507.58.1.6Nodeepc8226ExtSensors
1.3.6.1.4.1.28507.58.1.6.1Tableepc8226SensorTablenot-accessiblecurrent
1.3.6.1.4.1.28507.58.1.6.1.1Rowepc8226SensorEntrynot-accessiblecurrent
1.3.6.1.4.1.28507.58.1.6.1.1.1Columnepc8226SensorIndexread-onlycurrent
1.3.6.1.4.1.28507.58.1.6.1.1.2Columnepc8226TempSensorread-onlycurrentactual temperature
1.3.6.1.4.1.28507.58.1.6.1.1.3Columnepc8226HygroSensorread-onlycurrentactual humidity
1.3.6.1.4.1.28507.58.1.6.1.1.4Columnepc8226InputSensorread-onlycurrentlogical state of input sensor
1.3.6.1.4.1.28507.58.1.6.1.1.5Columnepc8226AirPressureread-onlycurrentactual air pressure
1.3.6.1.4.1.28507.58.1.6.1.1.6Columnepc8226DewPointread-onlycurrentdew point for actual temperature and humidity
1.3.6.1.4.1.28507.58.1.6.1.1.7Columnepc8226DewPointDiffread-onlycurrentdifference between dew point and actual temperature (Temp - DewPoint)
1.3.6.1.4.1.28507.58.2Nodeepc8226Conf
1.3.6.1.4.1.28507.58.2.1Nodeepc8226Groups
1.3.6.1.4.1.28507.58.2.1.1Groupepc8226BasicGroupcurrentBasic objects.
1.3.6.1.4.1.28507.58.2.1.2Groupepc8226NotificationGroupcurrent
1.3.6.1.4.1.28507.58.2.2Nodeepc8226Compls
1.3.6.1.4.1.28507.58.3Nodeevents
1.3.6.1.4.1.28507.58.3.1Notificationepc8226SwitchEvtPortcurrentEvent is triggered when a port is switched
1.3.6.1.4.1.28507.58.3.2Notificationepc8226TempEvtSencurrenttemperature limits exceeded
1.3.6.1.4.1.28507.58.3.3Notificationepc8226HygroEvtSencurrenthygro limits exceeded
1.3.6.1.4.1.28507.58.3.4Notificationepc8226InputEvtSencurrentchange of logical input sensor state
1.3.6.1.4.1.28507.58.3.5Notificationepc8226AirPressureEvtSencurrentAir Pressure limits exceeded
1.3.6.1.4.1.28507.58.3.6Notificationepc8226DewPtDiffEvtSencurrentDew Point Difference limits exceeded
1.3.6.1.4.1.28507.58.3.7Notificationepc8226OVPEvtcurrentEvent is triggered when the OVP status changes
1.3.6.1.4.1.28507.58.3.8Notificationepc8226LineAmperageEvtcurrentEvent is triggered when a measured current is crossing the entered limits
1.3.6.1.4.1.28507.58.3.9Notificationepc8226PortAmperageEvtcurrentEvent is triggered when a measured current is crossing the entered limits