MIB Viewer

GUDEADS-ESB7214-MIB

63 objects
Expert Power Control 7214 MIB
Imported Objects
SNMPv2-CONFNOTIFICATION-GROUP OBJECT-GROUP
SNMPv2-SMIenterprises Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE Unsigned32
OIDNameAccessStatusDescription
1.3.6.1.4.1.28507IdentitygudeadsExpert Power Control 7214 MIB
1.3.6.1.4.1.28507.67NodegadsESB7214
1.3.6.1.4.1.28507.67.1Nodeesb7214Objects
1.3.6.1.4.1.28507.67.1.1Nodeesb7214CommonConfig
1.3.6.1.4.1.28507.67.1.1.1Nodeesb7214SNMPaccess
1.3.6.1.4.1.28507.67.1.1.1.1Scalaresb7214TrapCtrlread-writecurrent0 = off 1 = Ver. 1 2 = Ver. 2c 3 = Ver. 3
1.3.6.1.4.1.28507.67.1.1.1.2Tableesb7214TrapIPTablenot-accessiblecurrentlist of all Trap receiver
1.3.6.1.4.1.28507.67.1.1.1.2.1Rowesb7214TrapIPEntrynot-accessiblecurrentan entry containing management informations regarding the list of trap receivers
1.3.6.1.4.1.28507.67.1.1.1.2.1.1Columnesb7214TrapIPIndexread-onlycurrentA unique value, greater than zero, for each receiver slot.
1.3.6.1.4.1.28507.67.1.1.1.2.1.2Columnesb7214TrapAddrread-writecurrentDNS name or IP address specifying one Trap receiver slot. A port can optionally be specified: 'name:port' An empty string disables this slot.
1.3.6.1.4.1.28507.67.1.2Nodeesb7214DeviceConfig
1.3.6.1.4.1.28507.67.1.3Nodeesb7214IntActors
1.3.6.1.4.1.28507.67.1.3.1Nodeesb7214relayports
1.3.6.1.4.1.28507.67.1.3.1.1Scalaresb7214portNumberread-onlycurrentThe number of Relay Ports
1.3.6.1.4.1.28507.67.1.3.1.2Tableesb7214portTablenot-accessiblecurrentlist of all EPC Relay Ports
1.3.6.1.4.1.28507.67.1.3.1.2.1Rowesb7214portEntrynot-accessiblecurrentAn entry containing management information applicable to a particular relay port.
1.3.6.1.4.1.28507.67.1.3.1.2.1.1Columnesb7214PortIndexread-onlycurrentA unique value, greater than zero, for each Relay Port.
1.3.6.1.4.1.28507.67.1.3.1.2.1.2Columnesb7214PortNameread-writecurrentA textual string containing name of a Relay Port.
1.3.6.1.4.1.28507.67.1.3.1.2.1.3Columnesb7214PortStateread-writecurrentcurrent state of a Relay Port
1.3.6.1.4.1.28507.67.1.3.1.2.1.4Columnesb7214PortSwitchCountread-onlycurrentThe total number of switch actions ocurred on a Relay Port. Does not count switch commands which will not switch the ralay state, so just real relay switches a…
1.3.6.1.4.1.28507.67.1.3.1.2.1.5Columnesb7214PortStartupModeread-writecurrentset Mode of startup sequence (off, on , remember last state)
1.3.6.1.4.1.28507.67.1.3.1.2.1.6Columnesb7214PortStartupDelayread-writecurrentDelay in sec for startup action
1.3.6.1.4.1.28507.67.1.3.1.2.1.7Columnesb7214PortRepowerTimeread-writecurrentDelay in sec for repower port after switching off
1.3.6.1.4.1.28507.67.1.4Nodeesb7214ExtActors
1.3.6.1.4.1.28507.67.1.5Nodeesb7214IntSensors
1.3.6.1.4.1.28507.67.1.5.6Nodeesb7214Inputs
1.3.6.1.4.1.28507.67.1.5.6.1Scalaresb7214ActiveInputsread-onlycurrentNumber of suppported Input Channels.
1.3.6.1.4.1.28507.67.1.5.6.2Tableesb7214InputTablenot-accessiblecurrent
1.3.6.1.4.1.28507.67.1.5.6.2.1Rowesb7214InputEntrynot-accessiblecurrent
1.3.6.1.4.1.28507.67.1.5.6.2.1.1Columnesb7214InputIndexread-onlycurrent
1.3.6.1.4.1.28507.67.1.5.6.2.1.2Columnesb7214Inputread-onlycurrentInput state of device
1.3.6.1.4.1.28507.67.1.5.6.2.1.32Columnesb7214InputNameread-writecurrentA textual string containing name of the Input
1.3.6.1.4.1.28507.67.1.5.10Scalaresb7214POEread-onlycurrentsignals POE availability
1.3.6.1.4.1.28507.67.1.5.13Tableesb7214PwrSupplyTablenot-accessiblecurrentPower Supply Table - shows if Power Supply is avail
1.3.6.1.4.1.28507.67.1.5.13.1Rowesb7214PwrSupplyEntrynot-accessiblecurrent
1.3.6.1.4.1.28507.67.1.5.13.1.1Columnesb7214PwrSupplyIndexread-onlycurrentIndex of Power Supply entries
1.3.6.1.4.1.28507.67.1.5.13.1.2Columnesb7214PwrSupplyStatusread-onlycurrentshows status of the Power Supply 1 = fst, 2 = snd etc.
1.3.6.1.4.1.28507.67.1.6Nodeesb7214ExtSensors
1.3.6.1.4.1.28507.67.1.6.1Tableesb7214SensorTablenot-accessiblecurrent
1.3.6.1.4.1.28507.67.1.6.1.1Rowesb7214SensorEntrynot-accessiblecurrent
1.3.6.1.4.1.28507.67.1.6.1.1.1Columnesb7214SensorIndexread-onlycurrent
1.3.6.1.4.1.28507.67.1.6.1.1.2Columnesb7214TempSensorread-onlycurrentactual temperature
1.3.6.1.4.1.28507.67.1.6.1.1.3Columnesb7214HygroSensorread-onlycurrentactual humidity
1.3.6.1.4.1.28507.67.1.6.1.1.4Columnesb7214InputSensorread-onlycurrentlogical state of input sensor
1.3.6.1.4.1.28507.67.1.6.1.1.5Columnesb7214AirPressureread-onlycurrentactual air pressure
1.3.6.1.4.1.28507.67.1.6.1.1.6Columnesb7214DewPointread-onlycurrentdew point for actual temperature and humidity
1.3.6.1.4.1.28507.67.1.6.1.1.7Columnesb7214DewPointDiffread-onlycurrentdifference between dew point and actual temperature (Temp - DewPoint)
1.3.6.1.4.1.28507.67.1.6.1.1.32Columnesb7214ExtSensorNameread-writecurrentA textual string containing name of a external Sensor
1.3.6.1.4.1.28507.67.2Nodeesb7214Conf
1.3.6.1.4.1.28507.67.2.1Nodeesb7214Groups
1.3.6.1.4.1.28507.67.2.1.1Groupesb7214BasicGroupcurrentBasic objects.
1.3.6.1.4.1.28507.67.2.1.2Groupesb7214NotificationGroupcurrent
1.3.6.1.4.1.28507.67.2.2Nodeesb7214Compls
1.3.6.1.4.1.28507.67.3Nodeevents
1.3.6.1.4.1.28507.67.3.1Notificationesb7214SwitchEvtPortcurrentEvent is triggered when a port is switched
1.3.6.1.4.1.28507.67.3.2Notificationesb7214InputEvtcurrentChange of device input.
1.3.6.1.4.1.28507.67.3.3Notificationesb7214TempEvtSencurrenttemperature limits exceeded
1.3.6.1.4.1.28507.67.3.4Notificationesb7214HygroEvtSencurrenthygro limits exceeded
1.3.6.1.4.1.28507.67.3.5Notificationesb7214InputEvtSencurrentchange of logical input sensor state
1.3.6.1.4.1.28507.67.3.6Notificationesb7214AirPressureEvtSencurrentAir Pressure limits exceeded
1.3.6.1.4.1.28507.67.3.7Notificationesb7214DewPtDiffEvtSencurrentDew Point Difference limits exceeded
1.3.6.1.4.1.28507.67.3.8Notificationesb7214POEEvtcurrentPower over Ethernet changed
1.3.6.1.4.1.28507.67.3.9Notificationesb7214PwrSupplyChangeEvtcurrentEvent is triggered when Power Supply state changes