MIB Viewer

GUDEADS-PDU8306-MIB

50 objects
No module-level DESCRIPTION found.
Imported Objects
SNMPv2-CONFNOTIFICATION-GROUP OBJECT-GROUP
SNMPv2-SMIenterprises Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE Unsigned32
OIDNameAccessStatusDescription
1.3.6.1.4.1.28507Identitygudeads
1.3.6.1.4.1.28507.44NodegadsPDU8306
1.3.6.1.4.1.28507.44.0Nodeevents
1.3.6.1.4.1.28507.44.0.1Notificationpdu8306TempEvtSen1currenttemperature limits exceeded
1.3.6.1.4.1.28507.44.0.2Notificationpdu8306HygroEvtSen1currenthygro limits exceeded
1.3.6.1.4.1.28507.44.0.3Notificationpdu8306MeasurementBoxEvtcurrentSignals a change of the connection to the external Measurement Box.
1.3.6.1.4.1.28507.44.1Nodepdu8306Objects
1.3.6.1.4.1.28507.44.1.1Nodepdu8306CommonConfig
1.3.6.1.4.1.28507.44.1.1.1Nodepdu8306SNMPaccess
1.3.6.1.4.1.28507.44.1.1.1.1Scalarpdu8306TrapCtrlread-writecurrent0 = off 1 = Ver. 1 2 = Ver. 2c
1.3.6.1.4.1.28507.44.1.1.1.2Tablepdu8306TrapIPTablenot-accessiblecurrentlist of all Trap receiver
1.3.6.1.4.1.28507.44.1.1.1.2.1Rowpdu8306TrapIPEntrynot-accessiblecurrentan entry containing management informations regarding the list of trap receivers
1.3.6.1.4.1.28507.44.1.1.1.2.1.1Columnpdu8306TrapIPIndexnot-accessiblecurrentA unique value, greater than zero, for each receiver slot.
1.3.6.1.4.1.28507.44.1.1.1.2.1.2Columnpdu8306TrapAddrread-writecurrentDNS name or IP address specifying one Trap receiver slot. A port can optionally be specified: 'name:port' An empty string disables this slot.
1.3.6.1.4.1.28507.44.1.2Nodepdu8306DeviceConfig
1.3.6.1.4.1.28507.44.1.3Nodepdu8306IntActors
1.3.6.1.4.1.28507.44.1.4Nodepdu8306ExtActors
1.3.6.1.4.1.28507.44.1.5Nodepdu8306IntSensors
1.3.6.1.4.1.28507.44.1.5.1Nodepdu8306PowerChan
1.3.6.1.4.1.28507.44.1.5.1.1Scalarpdu8306ActivePowerChanread-onlycurrentNumber of suppported Power Channels.
1.3.6.1.4.1.28507.44.1.5.1.2Tablepdu8306PowerTablenot-accessiblecurrentAll available Channel Interfaces.
1.3.6.1.4.1.28507.44.1.5.1.2.1Rowpdu8306PowerEntrynot-accessiblecurrentAn entry containing management information applicable to a particular Power Channel.
1.3.6.1.4.1.28507.44.1.5.1.2.1.1Columnpdu8306PowerIndexnot-accessiblecurrentIndex of Power Channel entries
1.3.6.1.4.1.28507.44.1.5.1.2.1.2Columnpdu8306ChanStatusread-onlycurrent0 = data not active, 1 = data valid
1.3.6.1.4.1.28507.44.1.5.1.2.1.3Columnpdu8306AbsEnergyActiveread-onlycurrentAbsolute Active Energy counter.
1.3.6.1.4.1.28507.44.1.5.1.2.1.4Columnpdu8306PowerActiveread-onlycurrentActive Power
1.3.6.1.4.1.28507.44.1.5.1.2.1.5Columnpdu8306Currentread-onlycurrentActual Curent on Power Channel.
1.3.6.1.4.1.28507.44.1.5.1.2.1.6Columnpdu8306Voltageread-onlycurrentActual Voltage on Power Channel
1.3.6.1.4.1.28507.44.1.5.1.2.1.7Columnpdu8306Frequencyread-onlycurrentFrequency of Power Channel
1.3.6.1.4.1.28507.44.1.5.1.2.1.8Columnpdu8306PowerFactorread-onlycurrentPower Factor of Channel between -1.0 and 1.00
1.3.6.1.4.1.28507.44.1.5.1.2.1.9Columnpdu8306Pangleread-onlycurrentPhase Angle between Voltage and L Line Current between -180.0 and 180.0
1.3.6.1.4.1.28507.44.1.5.1.2.1.10Columnpdu8306PowerApparentread-onlycurrentL Line Mean Apparent Power
1.3.6.1.4.1.28507.44.1.5.1.2.1.11Columnpdu8306PowerReactiveread-onlycurrentL Line Mean Reactive Power
1.3.6.1.4.1.28507.44.1.5.1.2.1.12Columnpdu8306EnergyReactiveread-onlycurrentAbsolute Reactive Energy counter.
1.3.6.1.4.1.28507.44.1.5.1.2.1.13Columnpdu8306EnergyActiveResettableread-onlycurrentResettable Absolute Active Energy counter.
1.3.6.1.4.1.28507.44.1.5.1.2.1.14Columnpdu8306EnergyReactiveResettableread-onlycurrentResettable Absolute Reactive Energy counter.
1.3.6.1.4.1.28507.44.1.5.1.2.1.15Columnpdu8306ResetTimeread-onlycurrentTime in seconds since last Energy Counter reset.
1.3.6.1.4.1.28507.44.1.5.12Scalarpdu8306MeasurementBoxConnectedread-onlycurrentShows if the external Measurement Box is connected.
1.3.6.1.4.1.28507.44.1.6Nodepdu8306ExtSensors
1.3.6.1.4.1.28507.44.1.6.1Tablepdu8306SensorTablenot-accessiblecurrent
1.3.6.1.4.1.28507.44.1.6.1.1Rowpdu8306SensorEntrynot-accessiblecurrent
1.3.6.1.4.1.28507.44.1.6.1.1.1Columnpdu8306SensorIndexnot-accessiblecurrent
1.3.6.1.4.1.28507.44.1.6.1.1.2Columnpdu8306TempSensorread-onlycurrentactual temperature, a value of -9999 indicates that data is not available
1.3.6.1.4.1.28507.44.1.6.1.1.3Columnpdu8306HygroSensorread-onlycurrentactual humidity, a value of -9999 indicates that data is not available
1.3.6.1.4.1.28507.44.1.6.1.1.4Columnpdu8306InputSensorread-onlycurrentlogical state of input sensor
1.3.6.1.4.1.28507.44.2Nodepdu8306Conf
1.3.6.1.4.1.28507.44.2.1Nodepdu8306Groups
1.3.6.1.4.1.28507.44.2.1.1Grouppdu8306BasicGroupcurrentBasic objects.
1.3.6.1.4.1.28507.44.2.1.2Grouppdu8306NotificationGroupcurrent
1.3.6.1.4.1.28507.44.2.2Nodepdu8306Compls