MIB Viewer

GUDEADS-PDU8311-MIB

64 objects
No module-level DESCRIPTION found.
Imported Objects
SNMPv2-CONFNOTIFICATION-GROUP OBJECT-GROUP
SNMPv2-SMIenterprises Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE Unsigned32
OIDNameAccessStatusDescription
1.3.6.1.4.1.28507Identitygudeads
1.3.6.1.4.1.28507.62NodegadsPDU8311
1.3.6.1.4.1.28507.62.1Nodepdu8311Objects
1.3.6.1.4.1.28507.62.1.1Nodepdu8311CommonConfig
1.3.6.1.4.1.28507.62.1.1.1Nodepdu8311SNMPaccess
1.3.6.1.4.1.28507.62.1.1.1.1Scalarpdu8311TrapCtrlread-writecurrent0 = off 1 = Ver. 1 2 = Ver. 2c 3 = Ver. 3
1.3.6.1.4.1.28507.62.1.1.1.2Tablepdu8311TrapIPTablenot-accessiblecurrentlist of all Trap receiver
1.3.6.1.4.1.28507.62.1.1.1.2.1Rowpdu8311TrapIPEntrynot-accessiblecurrentan entry containing management informations regarding the list of trap receivers
1.3.6.1.4.1.28507.62.1.1.1.2.1.1Columnpdu8311TrapIPIndexread-onlycurrentA unique value, greater than zero, for each receiver slot.
1.3.6.1.4.1.28507.62.1.1.1.2.1.2Columnpdu8311TrapAddrread-writecurrentDNS name or IP address specifying one Trap receiver slot. A port can optionally be specified: 'name:port' An empty string disables this slot.
1.3.6.1.4.1.28507.62.1.2Nodepdu8311DeviceConfig
1.3.6.1.4.1.28507.62.1.3Nodepdu8311IntActors
1.3.6.1.4.1.28507.62.1.4Nodepdu8311ExtActors
1.3.6.1.4.1.28507.62.1.5Nodepdu8311IntSensors
1.3.6.1.4.1.28507.62.1.5.1Nodepdu8311PowerChan
1.3.6.1.4.1.28507.62.1.5.1.1Scalarpdu8311ActivePowerChanread-onlycurrentNumber of suppported Power Channels.
1.3.6.1.4.1.28507.62.1.5.1.2Tablepdu8311PowerTablenot-accessiblecurrentAll available Channel Interfaces.
1.3.6.1.4.1.28507.62.1.5.1.2.1Rowpdu8311PowerEntrynot-accessiblecurrentAn entry containing management information applicable to a particular Power Channel.
1.3.6.1.4.1.28507.62.1.5.1.2.1.1Columnpdu8311PowerIndexread-onlycurrentIndex of Power Channel entries
1.3.6.1.4.1.28507.62.1.5.1.2.1.2Columnpdu8311ChanStatusread-onlycurrent0 = data not active, 1 = data valid
1.3.6.1.4.1.28507.62.1.5.1.2.1.3Columnpdu8311AbsEnergyActiveread-onlycurrentAbsolute Active Energy counter.
1.3.6.1.4.1.28507.62.1.5.1.2.1.4Columnpdu8311PowerActiveread-onlycurrentActive Power
1.3.6.1.4.1.28507.62.1.5.1.2.1.5Columnpdu8311Currentread-onlycurrentActual Current on Power Channel.
1.3.6.1.4.1.28507.62.1.5.1.2.1.6Columnpdu8311Voltageread-onlycurrentActual Voltage on Power Channel
1.3.6.1.4.1.28507.62.1.5.1.2.1.7Columnpdu8311Frequencyread-onlycurrentFrequency of Power Channel
1.3.6.1.4.1.28507.62.1.5.1.2.1.8Columnpdu8311PowerFactorread-onlycurrentPower Factor of Channel between -1.0 and 1.00
1.3.6.1.4.1.28507.62.1.5.1.2.1.9Columnpdu8311Pangleread-onlycurrentPhase Angle between Voltage and L Line Current between -180.0 and 180.0
1.3.6.1.4.1.28507.62.1.5.1.2.1.10Columnpdu8311PowerApparentread-onlycurrentL Line Mean Apparent Power
1.3.6.1.4.1.28507.62.1.5.1.2.1.11Columnpdu8311PowerReactiveread-onlycurrentL Line Mean Reactive Power
1.3.6.1.4.1.28507.62.1.5.1.2.1.12Columnpdu8311AbsEnergyReactiveread-onlycurrentAbsolute Reactive Energy counter.
1.3.6.1.4.1.28507.62.1.5.1.2.1.13Columnpdu8311AbsEnergyActiveResettableread-writecurrentResettable Absolute Active Energy counter. Writing '0' resets all resettable counter.
1.3.6.1.4.1.28507.62.1.5.1.2.1.14Columnpdu8311AbsEnergyReactiveResettableread-onlycurrentResettable Absolute Reactive Energy counter.
1.3.6.1.4.1.28507.62.1.5.1.2.1.15Columnpdu8311ResetTimeread-onlycurrentTime in seconds since last Energy Counter reset.
1.3.6.1.4.1.28507.62.1.5.1.2.1.16Columnpdu8311ForwEnergyActiveread-onlycurrentForward Active Energy counter.
1.3.6.1.4.1.28507.62.1.5.1.2.1.17Columnpdu8311ForwEnergyReactiveread-onlycurrentForward Reactive Energy counter.
1.3.6.1.4.1.28507.62.1.5.1.2.1.18Columnpdu8311ForwEnergyActiveResettableread-onlycurrentResettable Forward Active Energy counter.
1.3.6.1.4.1.28507.62.1.5.1.2.1.19Columnpdu8311ForwEnergyReactiveResettableread-onlycurrentResettable Forward Reactive Energy counter.
1.3.6.1.4.1.28507.62.1.5.1.2.1.20Columnpdu8311RevEnergyActiveread-onlycurrentReverse Active Energy counter.
1.3.6.1.4.1.28507.62.1.5.1.2.1.21Columnpdu8311RevEnergyReactiveread-onlycurrentReverse Reactive Energy counter.
1.3.6.1.4.1.28507.62.1.5.1.2.1.22Columnpdu8311RevEnergyActiveResettableread-onlycurrentResettable Reverse Active Energy counter.
1.3.6.1.4.1.28507.62.1.5.1.2.1.23Columnpdu8311RevEnergyReactiveResettableread-onlycurrentResettable Reverse Reactive Energy counter.
1.3.6.1.4.1.28507.62.1.5.1.2.1.24Columnpdu8311ResidualCurrentread-onlycurrentActual Residual Current on Power Channel. According Typ A IEC 60755. Only visible on models that support this feature.
1.3.6.1.4.1.28507.62.1.6Nodepdu8311ExtSensors
1.3.6.1.4.1.28507.62.1.6.1Tablepdu8311SensorTablenot-accessiblecurrent
1.3.6.1.4.1.28507.62.1.6.1.1Rowpdu8311SensorEntrynot-accessiblecurrent
1.3.6.1.4.1.28507.62.1.6.1.1.1Columnpdu8311SensorIndexread-onlycurrent
1.3.6.1.4.1.28507.62.1.6.1.1.2Columnpdu8311TempSensorread-onlycurrentactual temperature
1.3.6.1.4.1.28507.62.1.6.1.1.3Columnpdu8311HygroSensorread-onlycurrentactual humidity
1.3.6.1.4.1.28507.62.1.6.1.1.4Columnpdu8311InputSensorread-onlycurrentlogical state of input sensor
1.3.6.1.4.1.28507.62.1.6.1.1.5Columnpdu8311AirPressureread-onlycurrentactual air pressure
1.3.6.1.4.1.28507.62.1.6.1.1.6Columnpdu8311DewPointread-onlycurrentdew point for actual temperature and humidity
1.3.6.1.4.1.28507.62.1.6.1.1.7Columnpdu8311DewPointDiffread-onlycurrentdifference between dew point and actual temperature (Temp - DewPoint)
1.3.6.1.4.1.28507.62.2Nodepdu8311Conf
1.3.6.1.4.1.28507.62.2.1Nodepdu8311Groups
1.3.6.1.4.1.28507.62.2.1.1Grouppdu8311BasicGroupcurrentBasic objects.
1.3.6.1.4.1.28507.62.2.1.2Grouppdu8311NotificationGroupcurrent
1.3.6.1.4.1.28507.62.2.2Nodepdu8311Compls
1.3.6.1.4.1.28507.62.3Nodeevents
1.3.6.1.4.1.28507.62.3.1Notificationpdu8311TempEvtSencurrenttemperature limits exceeded
1.3.6.1.4.1.28507.62.3.2Notificationpdu8311HygroEvtSencurrenthygro limits exceeded
1.3.6.1.4.1.28507.62.3.3Notificationpdu8311InputEvtSencurrentchange of logical input sensor state
1.3.6.1.4.1.28507.62.3.4Notificationpdu8311AirPressureEvtSencurrentAir Pressure limits exceeded
1.3.6.1.4.1.28507.62.3.5Notificationpdu8311DewPtDiffEvtSencurrentDew Point Difference limits exceeded
1.3.6.1.4.1.28507.62.3.6Notificationpdu8311LineAmperageEvtcurrentEvent is triggered when a measured current is crossing the entered limits