GUDEADS-PDU8311-MIB
64 objects
No module-level DESCRIPTION found.
Imported Objects
| SNMPv2-CONF | NOTIFICATION-GROUP OBJECT-GROUP |
| SNMPv2-SMI | enterprises Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE Unsigned32 |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.28507 | Identitygudeads | |||
| 1.3.6.1.4.1.28507.62 | NodegadsPDU8311 | |||
| 1.3.6.1.4.1.28507.62.1 | Nodepdu8311Objects | |||
| 1.3.6.1.4.1.28507.62.1.1 | Nodepdu8311CommonConfig | |||
| 1.3.6.1.4.1.28507.62.1.1.1 | Nodepdu8311SNMPaccess | |||
| 1.3.6.1.4.1.28507.62.1.1.1.1 | Scalarpdu8311TrapCtrl | read-write | current | 0 = off 1 = Ver. 1 2 = Ver. 2c 3 = Ver. 3 |
| 1.3.6.1.4.1.28507.62.1.1.1.2 | Tablepdu8311TrapIPTable | not-accessible | current | list of all Trap receiver |
| 1.3.6.1.4.1.28507.62.1.1.1.2.1 | Rowpdu8311TrapIPEntry | not-accessible | current | an entry containing management informations regarding the list of trap receivers |
| 1.3.6.1.4.1.28507.62.1.1.1.2.1.1 | Columnpdu8311TrapIPIndex | read-only | current | A unique value, greater than zero, for each receiver slot. |
| 1.3.6.1.4.1.28507.62.1.1.1.2.1.2 | Columnpdu8311TrapAddr | read-write | current | DNS name or IP address specifying one Trap receiver slot. A port can optionally be specified: 'name:port' An empty string disables this slot. |
| 1.3.6.1.4.1.28507.62.1.2 | Nodepdu8311DeviceConfig | |||
| 1.3.6.1.4.1.28507.62.1.3 | Nodepdu8311IntActors | |||
| 1.3.6.1.4.1.28507.62.1.4 | Nodepdu8311ExtActors | |||
| 1.3.6.1.4.1.28507.62.1.5 | Nodepdu8311IntSensors | |||
| 1.3.6.1.4.1.28507.62.1.5.1 | Nodepdu8311PowerChan | |||
| 1.3.6.1.4.1.28507.62.1.5.1.1 | Scalarpdu8311ActivePowerChan | read-only | current | Number of suppported Power Channels. |
| 1.3.6.1.4.1.28507.62.1.5.1.2 | Tablepdu8311PowerTable | not-accessible | current | All available Channel Interfaces. |
| 1.3.6.1.4.1.28507.62.1.5.1.2.1 | Rowpdu8311PowerEntry | not-accessible | current | An entry containing management information applicable to a particular Power Channel. |
| 1.3.6.1.4.1.28507.62.1.5.1.2.1.1 | Columnpdu8311PowerIndex | read-only | current | Index of Power Channel entries |
| 1.3.6.1.4.1.28507.62.1.5.1.2.1.2 | Columnpdu8311ChanStatus | read-only | current | 0 = data not active, 1 = data valid |
| 1.3.6.1.4.1.28507.62.1.5.1.2.1.3 | Columnpdu8311AbsEnergyActive | read-only | current | Absolute Active Energy counter. |
| 1.3.6.1.4.1.28507.62.1.5.1.2.1.4 | Columnpdu8311PowerActive | read-only | current | Active Power |
| 1.3.6.1.4.1.28507.62.1.5.1.2.1.5 | Columnpdu8311Current | read-only | current | Actual Current on Power Channel. |
| 1.3.6.1.4.1.28507.62.1.5.1.2.1.6 | Columnpdu8311Voltage | read-only | current | Actual Voltage on Power Channel |
| 1.3.6.1.4.1.28507.62.1.5.1.2.1.7 | Columnpdu8311Frequency | read-only | current | Frequency of Power Channel |
| 1.3.6.1.4.1.28507.62.1.5.1.2.1.8 | Columnpdu8311PowerFactor | read-only | current | Power Factor of Channel between -1.0 and 1.00 |
| 1.3.6.1.4.1.28507.62.1.5.1.2.1.9 | Columnpdu8311Pangle | read-only | current | Phase Angle between Voltage and L Line Current between -180.0 and 180.0 |
| 1.3.6.1.4.1.28507.62.1.5.1.2.1.10 | Columnpdu8311PowerApparent | read-only | current | L Line Mean Apparent Power |
| 1.3.6.1.4.1.28507.62.1.5.1.2.1.11 | Columnpdu8311PowerReactive | read-only | current | L Line Mean Reactive Power |
| 1.3.6.1.4.1.28507.62.1.5.1.2.1.12 | Columnpdu8311AbsEnergyReactive | read-only | current | Absolute Reactive Energy counter. |
| 1.3.6.1.4.1.28507.62.1.5.1.2.1.13 | Columnpdu8311AbsEnergyActiveResettable | read-write | current | Resettable Absolute Active Energy counter. Writing '0' resets all resettable counter. |
| 1.3.6.1.4.1.28507.62.1.5.1.2.1.14 | Columnpdu8311AbsEnergyReactiveResettable | read-only | current | Resettable Absolute Reactive Energy counter. |
| 1.3.6.1.4.1.28507.62.1.5.1.2.1.15 | Columnpdu8311ResetTime | read-only | current | Time in seconds since last Energy Counter reset. |
| 1.3.6.1.4.1.28507.62.1.5.1.2.1.16 | Columnpdu8311ForwEnergyActive | read-only | current | Forward Active Energy counter. |
| 1.3.6.1.4.1.28507.62.1.5.1.2.1.17 | Columnpdu8311ForwEnergyReactive | read-only | current | Forward Reactive Energy counter. |
| 1.3.6.1.4.1.28507.62.1.5.1.2.1.18 | Columnpdu8311ForwEnergyActiveResettable | read-only | current | Resettable Forward Active Energy counter. |
| 1.3.6.1.4.1.28507.62.1.5.1.2.1.19 | Columnpdu8311ForwEnergyReactiveResettable | read-only | current | Resettable Forward Reactive Energy counter. |
| 1.3.6.1.4.1.28507.62.1.5.1.2.1.20 | Columnpdu8311RevEnergyActive | read-only | current | Reverse Active Energy counter. |
| 1.3.6.1.4.1.28507.62.1.5.1.2.1.21 | Columnpdu8311RevEnergyReactive | read-only | current | Reverse Reactive Energy counter. |
| 1.3.6.1.4.1.28507.62.1.5.1.2.1.22 | Columnpdu8311RevEnergyActiveResettable | read-only | current | Resettable Reverse Active Energy counter. |
| 1.3.6.1.4.1.28507.62.1.5.1.2.1.23 | Columnpdu8311RevEnergyReactiveResettable | read-only | current | Resettable Reverse Reactive Energy counter. |
| 1.3.6.1.4.1.28507.62.1.5.1.2.1.24 | Columnpdu8311ResidualCurrent | read-only | current | Actual Residual Current on Power Channel. According Typ A IEC 60755. Only visible on models that support this feature. |
| 1.3.6.1.4.1.28507.62.1.6 | Nodepdu8311ExtSensors | |||
| 1.3.6.1.4.1.28507.62.1.6.1 | Tablepdu8311SensorTable | not-accessible | current | |
| 1.3.6.1.4.1.28507.62.1.6.1.1 | Rowpdu8311SensorEntry | not-accessible | current | |
| 1.3.6.1.4.1.28507.62.1.6.1.1.1 | Columnpdu8311SensorIndex | read-only | current | |
| 1.3.6.1.4.1.28507.62.1.6.1.1.2 | Columnpdu8311TempSensor | read-only | current | actual temperature |
| 1.3.6.1.4.1.28507.62.1.6.1.1.3 | Columnpdu8311HygroSensor | read-only | current | actual humidity |
| 1.3.6.1.4.1.28507.62.1.6.1.1.4 | Columnpdu8311InputSensor | read-only | current | logical state of input sensor |
| 1.3.6.1.4.1.28507.62.1.6.1.1.5 | Columnpdu8311AirPressure | read-only | current | actual air pressure |
| 1.3.6.1.4.1.28507.62.1.6.1.1.6 | Columnpdu8311DewPoint | read-only | current | dew point for actual temperature and humidity |
| 1.3.6.1.4.1.28507.62.1.6.1.1.7 | Columnpdu8311DewPointDiff | read-only | current | difference between dew point and actual temperature (Temp - DewPoint) |
| 1.3.6.1.4.1.28507.62.2 | Nodepdu8311Conf | |||
| 1.3.6.1.4.1.28507.62.2.1 | Nodepdu8311Groups | |||
| 1.3.6.1.4.1.28507.62.2.1.1 | Grouppdu8311BasicGroup | current | Basic objects. | |
| 1.3.6.1.4.1.28507.62.2.1.2 | Grouppdu8311NotificationGroup | current | ||
| 1.3.6.1.4.1.28507.62.2.2 | Nodepdu8311Compls | |||
| 1.3.6.1.4.1.28507.62.3 | Nodeevents | |||
| 1.3.6.1.4.1.28507.62.3.1 | Notificationpdu8311TempEvtSen | current | temperature limits exceeded | |
| 1.3.6.1.4.1.28507.62.3.2 | Notificationpdu8311HygroEvtSen | current | hygro limits exceeded | |
| 1.3.6.1.4.1.28507.62.3.3 | Notificationpdu8311InputEvtSen | current | change of logical input sensor state | |
| 1.3.6.1.4.1.28507.62.3.4 | Notificationpdu8311AirPressureEvtSen | current | Air Pressure limits exceeded | |
| 1.3.6.1.4.1.28507.62.3.5 | Notificationpdu8311DewPtDiffEvtSen | current | Dew Point Difference limits exceeded | |
| 1.3.6.1.4.1.28507.62.3.6 | Notificationpdu8311LineAmperageEvt | current | Event is triggered when a measured current is crossing the entered limits |