MIB Viewer

GUDEADS-PDU835X-MIB

77 objects
No module-level DESCRIPTION found.
Imported Objects
SNMPv2-CONFNOTIFICATION-GROUP OBJECT-GROUP
SNMPv2-SMIenterprises Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE Unsigned32
OIDNameAccessStatusDescription
1.3.6.1.4.1.28507Identitygudeads
1.3.6.1.4.1.28507.52NodegadsPDU835X
1.3.6.1.4.1.28507.52.0Nodeevents
1.3.6.1.4.1.28507.52.0.1Notificationpdu835XTempEvtSen1currenttemperature limits exceeded
1.3.6.1.4.1.28507.52.0.2Notificationpdu835XTempEvtSen2currenttemperature limits exceeded
1.3.6.1.4.1.28507.52.0.3Notificationpdu835XHygroEvtSen1currenthygro limits exceeded
1.3.6.1.4.1.28507.52.0.4Notificationpdu835XHygroEvtSen2currenthygro limits exceeded
1.3.6.1.4.1.28507.52.0.5Notificationpdu835XInputEvtSen1currentchange of logical input sensor state
1.3.6.1.4.1.28507.52.0.6Notificationpdu835XInputEvtSen2currentchange of logical input sensor state
1.3.6.1.4.1.28507.52.0.7Notificationpdu835XMeasurementBoxEvt1currentSignals a change of the connection to the external Measurement Box.
1.3.6.1.4.1.28507.52.0.8Notificationpdu835XMeasurementBoxEvt2currentSignals a change of the connection to the external Measurement Box.
1.3.6.1.4.1.28507.52.0.9Notificationpdu835XAmperageEvt1currentEvent is triggered when a measured current is crossing the entered limits
1.3.6.1.4.1.28507.52.0.10Notificationpdu835XAmperageEvt2currentEvent is triggered when a measured current is crossing the entered limits
1.3.6.1.4.1.28507.52.0.11Notificationpdu835XAmperageEvt3currentEvent is triggered when a measured current is crossing the entered limits
1.3.6.1.4.1.28507.52.0.12Notificationpdu835XAmperageEvt4currentEvent is triggered when a measured current is crossing the entered limits
1.3.6.1.4.1.28507.52.0.13Notificationpdu835XAmperageEvt5currentEvent is triggered when a measured current is crossing the entered limits
1.3.6.1.4.1.28507.52.0.14Notificationpdu835XAmperageEvt6currentEvent is triggered when a measured current is crossing the entered limits
1.3.6.1.4.1.28507.52.1Nodepdu835XObjects
1.3.6.1.4.1.28507.52.1.1Nodepdu835XCommonConfig
1.3.6.1.4.1.28507.52.1.1.1Nodepdu835XSNMPaccess
1.3.6.1.4.1.28507.52.1.1.1.1Scalarpdu835XTrapCtrlread-writecurrent0 = off 1 = Ver. 1 2 = Ver. 2c
1.3.6.1.4.1.28507.52.1.1.1.2Tablepdu835XTrapIPTablenot-accessiblecurrentlist of all Trap receiver
1.3.6.1.4.1.28507.52.1.1.1.2.1Rowpdu835XTrapIPEntrynot-accessiblecurrentan entry containing management informations regarding the list of trap receivers
1.3.6.1.4.1.28507.52.1.1.1.2.1.1Columnpdu835XTrapIPIndexnot-accessiblecurrentA unique value, greater than zero, for each receiver slot.
1.3.6.1.4.1.28507.52.1.1.1.2.1.2Columnpdu835XTrapAddrread-writecurrentDNS name or IP address specifying one Trap receiver slot. A port can optionally be specified: 'name:port' An empty string disables this slot.
1.3.6.1.4.1.28507.52.1.2Nodepdu835XDeviceConfig
1.3.6.1.4.1.28507.52.1.3Nodepdu835XIntActors
1.3.6.1.4.1.28507.52.1.3.10Scalarpdu835XBuzzerread-writecurrentturn Buzzer on and off
1.3.6.1.4.1.28507.52.1.4Nodepdu835XExtActors
1.3.6.1.4.1.28507.52.1.5Nodepdu835XIntSensors
1.3.6.1.4.1.28507.52.1.5.1Nodepdu835XPowerChan
1.3.6.1.4.1.28507.52.1.5.1.1Scalarpdu835XActivePowerChanread-onlycurrentNumber of supported Power Channels.
1.3.6.1.4.1.28507.52.1.5.1.2Tablepdu835XPowerTablenot-accessiblecurrentAll available Channel Interfaces.
1.3.6.1.4.1.28507.52.1.5.1.2.1Rowpdu835XPowerEntrynot-accessiblecurrentAn entry containing management information applicable to a particular Power Channel.
1.3.6.1.4.1.28507.52.1.5.1.2.1.1Columnpdu835XPowerIndexnot-accessiblecurrentIndex of Power Channel entries
1.3.6.1.4.1.28507.52.1.5.1.2.1.2Columnpdu835XChanStatusread-onlycurrent0 = data not active, 1 = data valid
1.3.6.1.4.1.28507.52.1.5.1.2.1.3Columnpdu835XAbsEnergyActiveread-onlycurrentAbsolute Active Energy counter.
1.3.6.1.4.1.28507.52.1.5.1.2.1.4Columnpdu835XPowerActiveread-onlycurrentActive Power
1.3.6.1.4.1.28507.52.1.5.1.2.1.5Columnpdu835XCurrentread-onlycurrentActual Curent on Power Channel.
1.3.6.1.4.1.28507.52.1.5.1.2.1.6Columnpdu835XVoltageread-onlycurrentActual Voltage on Power Channel
1.3.6.1.4.1.28507.52.1.5.1.2.1.7Columnpdu835XFrequencyread-onlycurrentFrequency of Power Channel
1.3.6.1.4.1.28507.52.1.5.1.2.1.8Columnpdu835XPowerFactorread-onlycurrentPower Factor of Channel between -1.0 and 1.00
1.3.6.1.4.1.28507.52.1.5.1.2.1.9Columnpdu835XPangleread-onlycurrentPhase Angle between Voltage and L Line Current between -180.0 and 180.0
1.3.6.1.4.1.28507.52.1.5.1.2.1.10Columnpdu835XPowerApparentread-onlycurrentL Line Mean Apparent Power
1.3.6.1.4.1.28507.52.1.5.1.2.1.11Columnpdu835XPowerReactiveread-onlycurrentL Line Mean Reactive Power
1.3.6.1.4.1.28507.52.1.5.1.2.1.12Columnpdu835XAbsEnergyReactiveread-onlycurrentAbsolute Reactive Energy counter.
1.3.6.1.4.1.28507.52.1.5.1.2.1.13Columnpdu835XAbsEnergyActiveResettableread-onlycurrentResettable Absolute Active Energy counter.
1.3.6.1.4.1.28507.52.1.5.1.2.1.14Columnpdu835XAbsEnergyReactiveResettableread-onlycurrentResettable Absolute Reactive Energy counter.
1.3.6.1.4.1.28507.52.1.5.1.2.1.15Columnpdu835XResetTimeread-onlycurrentTime in seconds since last Energy Counter reset.
1.3.6.1.4.1.28507.52.1.5.1.2.1.16Columnpdu835XForwEnergyActiveread-onlycurrentForward Active Energy counter.
1.3.6.1.4.1.28507.52.1.5.1.2.1.17Columnpdu835XForwEnergyReactiveread-onlycurrentForward Reactive Energy counter.
1.3.6.1.4.1.28507.52.1.5.1.2.1.18Columnpdu835XForwEnergyActiveResettableread-onlycurrentResettable Forward Active Energy counter.
1.3.6.1.4.1.28507.52.1.5.1.2.1.19Columnpdu835XForwEnergyReactiveResettableread-onlycurrentResettable Forward Reactive Energy counter.
1.3.6.1.4.1.28507.52.1.5.1.2.1.20Columnpdu835XRevEnergyActiveread-onlycurrentReverse Active Energy counter.
1.3.6.1.4.1.28507.52.1.5.1.2.1.21Columnpdu835XRevEnergyReactiveread-onlycurrentReverse Reactive Energy counter.
1.3.6.1.4.1.28507.52.1.5.1.2.1.22Columnpdu835XRevEnergyActiveResettableread-onlycurrentResettable Reverse Active Energy counter.
1.3.6.1.4.1.28507.52.1.5.1.2.1.23Columnpdu835XRevEnergyReactiveResettableread-onlycurrentResettable Reverse Reactive Energy counter.
1.3.6.1.4.1.28507.52.1.5.3Nodepdu835XPowerGroup
1.3.6.1.4.1.28507.52.1.5.3.1Scalarpdu835XActivePowerGroupsread-onlycurrentNumber of Power Groups. May vary with different PDU models.
1.3.6.1.4.1.28507.52.1.5.3.2Tablepdu835XPowerGroupTablenot-accessiblecurrent
1.3.6.1.4.1.28507.52.1.5.3.2.1Rowpdu835XEntrynot-accessiblecurrentAn entry containing management information applicable to a particular Power Group. Entries may not exist on every PDU model.
1.3.6.1.4.1.28507.52.1.5.3.2.1.1Columnpdu835XPowerGroupIndexnot-accessiblecurrent
1.3.6.1.4.1.28507.52.1.5.3.2.1.2Columnpdu835XRCurrent3Pread-onlycurrentActual Residual Current. Entry may not exist on models that support not this type of measurement.
1.3.6.1.4.1.28507.52.1.5.3.2.1.3Columnpdu835XNCurrent3Pread-onlycurrentActual Current of the neutral wire. Entry may not exist on models that support not this type of measurement.
1.3.6.1.4.1.28507.52.1.5.3.2.1.4Columnpdu835XMeasurementBoxConnectedread-onlycurrentShows if the external Measurement Box is connected.
1.3.6.1.4.1.28507.52.1.6Nodepdu835XExtSensors
1.3.6.1.4.1.28507.52.1.6.1Tablepdu835XSensorTablenot-accessiblecurrent
1.3.6.1.4.1.28507.52.1.6.1.1Rowpdu835XSensorEntrynot-accessiblecurrent
1.3.6.1.4.1.28507.52.1.6.1.1.1Columnpdu835XSensorIndexnot-accessiblecurrent
1.3.6.1.4.1.28507.52.1.6.1.1.2Columnpdu835XTempSensorread-onlycurrentactual temperature, a value of -9999 indicates that data is not available
1.3.6.1.4.1.28507.52.1.6.1.1.3Columnpdu835XHygroSensorread-onlycurrentactual humidity, a value of -9999 indicates that data is not available
1.3.6.1.4.1.28507.52.1.6.1.1.4Columnpdu835XInputSensorread-onlycurrentlogical state of input sensor
1.3.6.1.4.1.28507.52.2Nodepdu835XConf
1.3.6.1.4.1.28507.52.2.1Nodepdu835XGroups
1.3.6.1.4.1.28507.52.2.1.1Grouppdu835XBasicGroupcurrentBasic objects.
1.3.6.1.4.1.28507.52.2.1.2Grouppdu835XNotificationGroupcurrent
1.3.6.1.4.1.28507.52.2.2Nodepdu835XCompls