MIB Viewer

HAWK-I2-MIB

291 objects
The MIB module for the Sinetica Hawk-i2.
Imported Objects
INET-ADDRESS-MIBInetAddress InetAddressType
RFC1213-MIB-- DisplayString sysDescr sysName --
SNMPv2-CONF-- MODULE-COMPLIANCE NOTIFICATION-GROUP -- OBJECT-GROUP
SNMPv2-SMIenterprises MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE Unsigned32
SNMPv2-TCMacAddress -- DateAndTime RowStatus TEXTUAL-CONVENTION TruthValue
OIDNameAccessStatusDescription
1.3.6.1.4.1.3711Nodesinetica
1.3.6.1.4.1.3711.24Identityhawki2MIBThe MIB module for the Sinetica Hawk-i2.
1.3.6.1.4.1.3711.24.0Nodetraps
1.3.6.1.4.1.3711.24.0.1NotificationalarmCriticalcurrentCritical alarm.
1.3.6.1.4.1.3711.24.0.2NotificationalarmWarningcurrentWarning alarm.
1.3.6.1.4.1.3711.24.0.3NotificationalarmInformationcurrentInformation alarm.
1.3.6.1.4.1.3711.24.0.4NotificationalarmClearedcurrentAlarm cleared.
1.3.6.1.4.1.3711.24.1Nodev1
1.3.6.1.4.1.3711.24.1.1Nodeobjects
1.3.6.1.4.1.3711.24.1.1.1Nodeinputs
1.3.6.1.4.1.3711.24.1.1.1.1NodeipCommon
1.3.6.1.4.1.3711.24.1.1.1.1.1NodeipEnable
1.3.6.1.4.1.3711.24.1.1.1.1.1.1ScalaripSelectread-writecurrentSelects the channel to be enabled or disabled by ipInsert. A value of 0 selects no channel.
1.3.6.1.4.1.3711.24.1.1.1.1.1.2ScalaripInsertread-writecurrentInserts or removes the channel selected by ipSelect - causes an entry for that channel to be created or deleted in the relevant tables. - Read behaviour is und…
1.3.6.1.4.1.3711.24.1.1.1.2NodeipTHA
1.3.6.1.4.1.3711.24.1.1.1.2.1ScalaripTempScaleFlagread-writecurrentTemperature scale (Celsius/Fahrenheit) for temperature monitoring.
1.3.6.1.4.1.3711.24.1.1.1.2.2TableipTHATablenot-accessiblecurrentA table giving data for all enabled inputs with analogue-type monitoring.
1.3.6.1.4.1.3711.24.1.1.1.2.2.1RowipTHAEntrynot-accessiblecurrentA conceptual row containing information about one analogue-type input.
1.3.6.1.4.1.3711.24.1.1.1.2.2.1.1ColumnipTHAChanread-onlycurrentThe input number.
1.3.6.1.4.1.3711.24.1.1.1.2.2.1.2ColumnipTHARSread-onlycurrentThe analogue-type input table row status.
1.3.6.1.4.1.3711.24.1.1.1.2.2.1.3ColumnipTHANameread-writecurrentThe name of this input
1.3.6.1.4.1.3711.24.1.1.1.2.2.1.4ColumnipTHALocnread-onlycurrentA system-defined name for the physical location of this input, e.g. MCU.
1.3.6.1.4.1.3711.24.1.1.1.2.2.1.5ColumnipTHAAutoDetectread-writecurrentIndicates that the type of data this input is monitoring is selected automatically.
1.3.6.1.4.1.3711.24.1.1.1.2.2.1.6ColumnipTHATyperead-writecurrentIndicates the type of data this input is monitoring.
1.3.6.1.4.1.3711.24.1.1.1.2.2.1.7ColumnipTHAValueread-onlycurrentThe current reading in the relevant measurement units.
1.3.6.1.4.1.3711.24.1.1.1.2.2.1.8ColumnipTHAScalingread-writecurrentScaling factor for ipTHAValue when ipTHAType=analogue.
1.3.6.1.4.1.3711.24.1.1.1.2.2.1.9ColumnipTHAOffsetread-writecurrentCalibration offset in the same units as for ipTHAValue.
1.3.6.1.4.1.3711.24.1.1.1.2.2.1.10ColumnipTHAHysteresisread-writecurrentHysteresis on threshold levels in the same units as for ipTHAValue.
1.3.6.1.4.1.3711.24.1.1.1.2.3NodeipTHATrapsCfg
1.3.6.1.4.1.3711.24.1.1.1.2.3.1TableipTHAThreshTablenot-accessiblecurrentA table listing the trap threshold levels for all enabled inputs with analogue-type monitoring.
1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1RowipTHAThreshEntrynot-accessiblecurrentA conceptual row containing threshold information for one analogue-type input.
1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.1ColumnipTHAThreshChanread-onlycurrentThe input number.
1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.2ColumnipTHAThreshRSread-onlycurrentThe analogue-type input table row status.
1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.3ColumnipTHAUCLread-writecurrentThe Upper Critical Limit for this input in the same units as for ipTHAValue.
1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.4ColumnipTHAUWLread-writecurrentThe Upper Warning Limit for this input in the same units as for ipTHAValue.
1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.5ColumnipTHALWLread-writecurrentThe Lower Warning Limit for this input in the same units as for ipTHAValue.
1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.6ColumnipTHALCLread-writecurrentThe Lower Critical Limit for this input in the same units as for ipTHAValue.
1.3.6.1.4.1.3711.24.1.1.1.2.3.2TableipTHATrapEnTablenot-accessiblecurrentThe table that controls trap enabling for all enabled inputs with analogue-type monitoring.
1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1RowipTHATrapEnEntrynot-accessiblecurrentA conceptual row containing trap enabling information for one analogue-type input.
1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.1ColumnipTHATrapEnChanread-onlycurrentThe input number.
1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.2ColumnipTHATrapEnRSread-onlycurrentThe analogue-type input table row status.
1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.3ColumnipTHAUCLTrapEnread-writecurrentEnables and disables input UCL alarm traps.
1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.4ColumnipTHAUWLTrapEnread-writecurrentEnables and disables input UWL alarm traps.
1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.5ColumnipTHALWLTrapEnread-writecurrentEnables and disables input LWL alarm traps.
1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.6ColumnipTHALCLTrapEnread-writecurrentEnables and disables input LCL alarm traps.
1.3.6.1.4.1.3711.24.1.1.1.2.3.3TableipTHATrapPerTablenot-accessiblecurrentThe table that controls trap repetition for all enabled inputs with analogue-type monitoring.
1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1RowipTHATrapPerEntrynot-accessiblecurrentA conceptual row containing trap repetition information for one analogue-type input.
1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.1ColumnipTHATrapPerChanread-onlycurrentThe input number.
1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.2ColumnipTHATrapPerRSread-onlycurrentThe table row status.
1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.3ColumnipTHATrapUCLPerread-writecurrentSet to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds
1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.4ColumnipTHATrapUWLPerread-writecurrentSet to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds
1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.5ColumnipTHATrapLWLPerread-writecurrentSet to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds
1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.6ColumnipTHATrapLCLPerread-writecurrentSet to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds
1.3.6.1.4.1.3711.24.1.1.1.3NodeipContact
1.3.6.1.4.1.3711.24.1.1.1.3.1TableipContTablenot-accessiblecurrentA table listing the parameters and data for all enabled inputs with contact-type monitoring.
1.3.6.1.4.1.3711.24.1.1.1.3.1.1RowipContEntrynot-accessiblecurrentA conceptual row containing information about one contact input.
1.3.6.1.4.1.3711.24.1.1.1.3.1.1.1ColumnipContChanread-onlycurrentThe input number.
1.3.6.1.4.1.3711.24.1.1.1.3.1.1.2ColumnipContRSread-onlycurrentThe contact input table row status.
1.3.6.1.4.1.3711.24.1.1.1.3.1.1.3ColumnipContNameread-writecurrentThe name of this input
1.3.6.1.4.1.3711.24.1.1.1.3.1.1.4ColumnipContLocnread-onlycurrentA system-defined name for the physical location of this input, e.g. MCU.
1.3.6.1.4.1.3711.24.1.1.1.3.1.1.5ColumnipContAutoDetectread-writecurrentIndicates that the type of data this input is monitoring is selected automatically.
1.3.6.1.4.1.3711.24.1.1.1.3.1.1.6ColumnipContNormStateread-writecurrentThe normal state for this contact.
1.3.6.1.4.1.3711.24.1.1.1.3.1.1.7ColumnipContCurrStateread-onlycurrentThe current state of this contact.
1.3.6.1.4.1.3711.24.1.1.1.3.1.1.8ColumnipContTrigModeread-writecurrentThe contact trigger mode, level, +ve edge, -ve edge.
1.3.6.1.4.1.3711.24.1.1.1.3.1.1.9ColumnipContResetread-writecurrentResets the contact after triggering in edge mode.
1.3.6.1.4.1.3711.24.1.1.1.3.1.1.10ColumnipContTrapEnread-writecurrentConfigure contact input traps.
1.3.6.1.4.1.3711.24.1.1.1.3.1.1.11ColumnipContTrapPeriodread-writecurrentSet to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds
1.3.6.1.4.1.3711.24.1.1.2Nodeoutputs
1.3.6.1.4.1.3711.24.1.1.2.1NodeopEnable
1.3.6.1.4.1.3711.24.1.1.2.1.1ScalaropSelectread-writecurrentSelects the channel to be enabled or disabled by opEnable. A value of 0 selects no channel.
1.3.6.1.4.1.3711.24.1.1.2.1.2ScalaropInsertread-writecurrentEnables or disables the channel selected by opSelect - causes an entry for that channel to be created or deleted in the relevant tables. - Read behaviour is un…
1.3.6.1.4.1.3711.24.1.1.2.2TableopTablenot-accessiblecurrentA table listing the parameters and data for all outputs that are enabled and available (i.e. its extension unit is connected).
1.3.6.1.4.1.3711.24.1.1.2.2.1RowopEntrynot-accessiblecurrentA conceptual row containing information about one output.
1.3.6.1.4.1.3711.24.1.1.2.2.1.1ColumnopChanread-onlycurrentThe output number.
1.3.6.1.4.1.3711.24.1.1.2.2.1.2ColumnopRSread-onlycurrentThe contact input table row status.
1.3.6.1.4.1.3711.24.1.1.2.2.1.3ColumnopNameread-writecurrentA user-defined name for this output.
1.3.6.1.4.1.3711.24.1.1.2.2.1.4ColumnopLocnread-onlycurrentA system-defined name for the physical location of this output, e.g. MCU.
1.3.6.1.4.1.3711.24.1.1.2.2.1.5ColumnopNormStateread-writecurrentSets or reads the required normal state of this output.
1.3.6.1.4.1.3711.24.1.1.2.2.1.6ColumnopCurrStateread-onlycurrentReads the current state of this output.
1.3.6.1.4.1.3711.24.1.1.2.2.1.7ColumnopOnDelTimeread-writecurrentSets the 'on' delay time for this output.
1.3.6.1.4.1.3711.24.1.1.2.2.1.8ColumnopOffDelTimeread-writecurrentSets the 'off' delay time for this output.
1.3.6.1.4.1.3711.24.1.1.2.2.1.9ColumnopBooleanEqnread-writecurrentBoolean equation string
1.3.6.1.4.1.3711.24.1.1.2.2.1.10ColumnopTrapEnread-writecurrentConfigure output traps.
1.3.6.1.4.1.3711.24.1.1.2.2.1.11ColumnopTrapPeriodread-writecurrentSet to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds
1.3.6.1.4.1.3711.24.1.1.2.2.1.12ColumnopControlStateread-writecurrentReads the current control state of an output.
1.3.6.1.4.1.3711.24.1.1.4Nodekeypads
1.3.6.1.4.1.3711.24.1.1.4.1NodekpEnable
1.3.6.1.4.1.3711.24.1.1.4.1.1ScalarkpSelectread-writecurrentSelects the keypad to be enabled or disabled by kpEnable. A value of 0 selects no keypad.
1.3.6.1.4.1.3711.24.1.1.4.1.2ScalarkpInsertread-writecurrentEnables or disables the keypad selected by kpSelect - causes an entry for that keypad to be created or deleted in the relevant tables. - Read behaviour is unde…
1.3.6.1.4.1.3711.24.1.1.4.2TablekpCtlTablenot-accessiblecurrentA table listing the parameters and data for the keypads.
1.3.6.1.4.1.3711.24.1.1.4.2.1RowkpCtlEntrynot-accessiblecurrentA conceptual row containing information about one keypad.
1.3.6.1.4.1.3711.24.1.1.4.2.1.1ColumnkpNumberread-onlycurrentThe keypad number.
1.3.6.1.4.1.3711.24.1.1.4.2.1.2ColumnkpRSread-onlycurrentThe keypad table row status.
1.3.6.1.4.1.3711.24.1.1.4.2.1.3ColumnkpManufacturerread-writecurrentThe name of the manufacturer of the keypad.
1.3.6.1.4.1.3711.24.1.1.4.2.1.4ColumnkpNameread-writecurrentA name identifying the keypad.
1.3.6.1.4.1.3711.24.1.1.4.2.1.5ColumnkpDoorLatchTimeOutread-writecurrentTime-out value in seconds for which the door latch is held open.
1.3.6.1.4.1.3711.24.1.1.4.2.1.6ColumnkpRtnToStndbyTimeOutread-writecurrentTime-out value in seconds for Return to Standby Mode
1.3.6.1.4.1.3711.24.1.1.4.2.1.7ColumnkpEntryCodeValidread-onlycurrentSet if previous keypad entry was valid.
1.3.6.1.4.1.3711.24.1.1.4.2.1.8ColumnkpDoorOpenTimeOutread-writecurrentTime-out value in seconds for Door Open.
1.3.6.1.4.1.3711.24.1.1.4.2.1.9ColumnkpRemoteDoorOpenread-writecurrentSet to open the door.
1.3.6.1.4.1.3711.24.1.1.4.2.1.10ColumnkpInUseTrapEnread-writecurrent'keypad in use' trap enable
1.3.6.1.4.1.3711.24.1.1.5Nodeacus
1.3.6.1.4.1.3711.24.1.1.5.1NodeacuEnable
1.3.6.1.4.1.3711.24.1.1.5.1.1ScalaracuSelectread-writecurrentSelects the ACU to be enabled or disabled by acuEnable. A value of 0 selects no ACU.
1.3.6.1.4.1.3711.24.1.1.5.1.2ScalaracuInsertread-writecurrentEnables or disables the ACU selected by acuSelect - causes an entry for that ACU to be created or deleted in the relevant tables. - Read behaviour is undefined.
1.3.6.1.4.1.3711.24.1.1.5.2TableacuCtlTablenot-accessiblecurrentA table listing the parameters and data for the ACUs.
1.3.6.1.4.1.3711.24.1.1.5.2.1RowacuCtlEntrynot-accessiblecurrentA conceptual row containing information about one ACU.
1.3.6.1.4.1.3711.24.1.1.5.2.1.1ColumnacuNumberread-onlycurrentThe ACU number.
1.3.6.1.4.1.3711.24.1.1.5.2.1.2ColumnacuCtlRSread-onlycurrentThe ACU table row status.
1.3.6.1.4.1.3711.24.1.1.5.2.1.3ColumnacuManufacturerread-writecurrentThe name of the manufacturer of the ACU.
1.3.6.1.4.1.3711.24.1.1.5.2.1.4ColumnacuNameread-writecurrentA name identifying the ACU.
1.3.6.1.4.1.3711.24.1.1.5.2.1.5ColumnacuDoorLatchTimeOutread-writecurrentTime-out value in seconds for which the door latch is held open.
1.3.6.1.4.1.3711.24.1.1.5.2.1.6ColumnacuRtnToStndbyTimeOutread-writecurrentTime-out value in seconds for Return to Standby Mode
1.3.6.1.4.1.3711.24.1.1.5.2.1.7ColumnacuEntryCodeValidread-onlycurrentSet if previous ACU entry was valid.
1.3.6.1.4.1.3711.24.1.1.5.2.1.8ColumnacuDoorOpenTimeOutread-writecurrentTime-out value in seconds for Door Open.
1.3.6.1.4.1.3711.24.1.1.5.2.1.9ColumnacuRemoteDoorOpenread-writecurrentSet to open the door.
1.3.6.1.4.1.3711.24.1.1.5.2.1.10ColumnacuInUseTrapEnread-writecurrent'ACU in use' trap enable
1.3.6.1.4.1.3711.24.1.1.6Nodeaccess
1.3.6.1.4.1.3711.24.1.1.6.1NodeaccUserCtl
1.3.6.1.4.1.3711.24.1.1.6.1.1ScalaraccUserInstanceread-writecurrentA value of 0 causes an access user to be created in the relevant tables. A non-zero value causes the nominated access user table entries to be deleted.
1.3.6.1.4.1.3711.24.1.1.6.1.2TableaccUserTablenot-accessiblecurrentA table controlling the access users.
1.3.6.1.4.1.3711.24.1.1.6.1.2.1RowaccUserEntrynot-accessiblecurrentA conceptual row containing information about one ACU user.
1.3.6.1.4.1.3711.24.1.1.6.1.2.1.1ColumnaccUserNumberread-onlycurrentThe the access user-table entry number.
1.3.6.1.4.1.3711.24.1.1.6.1.2.1.2ColumnaccUserRSread-onlycurrentThe access user table row status.
1.3.6.1.4.1.3711.24.1.1.6.1.2.1.3ColumnaccUserNameread-writecurrentA name identifying the access user.
1.3.6.1.4.1.3711.24.1.1.6.1.2.1.4ColumnaccUserCoderead-writecurrentThe user's access code.
1.3.6.1.4.1.3711.24.1.1.6.1.2.1.5ColumnaccUserPrivilegesread-writecurrentThe ACUs and keypads that the user is allowed to gain access through - comma-separated numerical strings.
1.3.6.1.4.1.3711.24.1.1.6.1.2.1.6ColumnaccUserExpiresread-writecurrentA text string which specifies when the access code in the row expires. The format is defined by the application.
1.3.6.1.4.1.3711.24.1.1.6.1.3ScalaraccUserSetupread-writecurrentA free form octet string for programming accUserTable. The format is defined by the application.
1.3.6.1.4.1.3711.24.1.1.7Nodepdus
1.3.6.1.4.1.3711.24.1.1.7.1NodepduCommon
1.3.6.1.4.1.3711.24.1.1.7.1.1NodepdusEnable
1.3.6.1.4.1.3711.24.1.1.7.1.1.1ScalarpduSelectread-writecurrentSelects the PDU to be enabled or disabled by pduEnable. A value of 0 selects no PDU.
1.3.6.1.4.1.3711.24.1.1.7.1.1.2ScalarpduInsertread-writecurrentEnables or disables the PDU selected by pduSelect - causes an entry for that PDU to be created or deleted in the relevant tables. - Read behaviour is undefined.
1.3.6.1.4.1.3711.24.1.1.7.1.2TablepduTablenot-accessiblecurrentA table containing information about each enabled PDU.
1.3.6.1.4.1.3711.24.1.1.7.1.2.1RowpduEntrynot-accessiblecurrentA conceptual row containing information about one PDU.
1.3.6.1.4.1.3711.24.1.1.7.1.2.1.1ColumnpduNumberread-onlycurrentThe PDU number.
1.3.6.1.4.1.3711.24.1.1.7.1.2.1.2ColumnpduRSread-onlycurrentThe PDU table row status.
1.3.6.1.4.1.3711.24.1.1.7.1.2.1.3ColumnpduNameread-writecurrentA string identifying the PDU.
1.3.6.1.4.1.3711.24.1.1.7.1.2.1.4ColumnpduOutEnread-writecurrentEnables/disables PDU power outlet control - causes an entry for outlets to be created in each relevant PDU table.
1.3.6.1.4.1.3711.24.1.1.7.1.2.1.5ColumnpduMonEnread-writecurrentEnables/disables PDU power monitoring - causes an entry for monitoring to be created in each relevant PDU table.
1.3.6.1.4.1.3711.24.1.1.7.1.2.1.6ColumnpduCommsFailread-onlycurrentIndicates comms. status for the PDU.
1.3.6.1.4.1.3711.24.1.1.7.2NodepduOutlets
1.3.6.1.4.1.3711.24.1.1.7.2.1NodepduOutAll
1.3.6.1.4.1.3711.24.1.1.7.2.1.1ScalarpduOutCycleAllread-writecurrentSets the required state of all power outlets on all connected PDUs.
1.3.6.1.4.1.3711.24.1.1.7.2.1.2ScalarpduOutCycleAllPwdread-writecurrentControls access to setting the required state of all power outlets on all connected PDUs.
1.3.6.1.4.1.3711.24.1.1.7.2.1.3ScalarpduOutCycleAllAbortread-writecurrentAbort command for pduOutCycleAll.
1.3.6.1.4.1.3711.24.1.1.7.2.1.4ScalarpduOutGlobalCycleDelayread-writecurrentSets the delay period for pduOutCycleAll and pduOutCycle commands before they start to execute.
1.3.6.1.4.1.3711.24.1.1.7.2.1.5ScalarpduOutGlobalRebootTimeread-writecurrentSets the off to on delay period for a pdu outlet reboot.
1.3.6.1.4.1.3711.24.1.1.7.2.1.6ScalarpduOutGlobalCycleAbortTimeread-writecurrentTime delay to abort power outlet setting task.
1.3.6.1.4.1.3711.24.1.1.7.2.2TablepduOutCmnTablenot-accessiblecurrentA table containing information about the power outlets of all PDUs enabled for outlet control.
1.3.6.1.4.1.3711.24.1.1.7.2.2.1RowpduOutCmnEntrynot-accessiblecurrentA conceptual row containing information about the power outlets of one PDU.
1.3.6.1.4.1.3711.24.1.1.7.2.2.1.1ColumnpduOutCmnPduNumberread-onlycurrentThe PDU number.
1.3.6.1.4.1.3711.24.1.1.7.2.2.1.2ColumnpduOutCmnRSread-onlycurrentThe PDU table row status.
1.3.6.1.4.1.3711.24.1.1.7.2.2.1.3ColumnpduNumOfOutletsread-writecurrentThe number of switchable outlets on the PDU - determines the number of entries to be created in the outlet table for the relevant PDU.
1.3.6.1.4.1.3711.24.1.1.7.2.2.1.4ColumnpduOutCycleread-writecurrentSets the required state of all power outlets on the PDU.
1.3.6.1.4.1.3711.24.1.1.7.2.2.1.5ColumnpduOutCyclePwdread-writecurrentPassword controling access to setting the required state of all power outlets on the PDU.
1.3.6.1.4.1.3711.24.1.1.7.2.2.1.6ColumnpduOutCycleAbortTaskread-writecurrentAbort power outlet setting task.
1.3.6.1.4.1.3711.24.1.1.7.2.2.1.7ColumnpduOutCycleAbortTimeread-writecurrentTime delay to abort power outlet setting task.
1.3.6.1.4.1.3711.24.1.1.7.2.3TablepduOutTablenot-accessiblecurrentA table listing the states and descriptions for each outlet on the PDU.
1.3.6.1.4.1.3711.24.1.1.7.2.3.1RowpduOutEntrynot-accessiblecurrentA row containing information about one PDU outlet.
1.3.6.1.4.1.3711.24.1.1.7.2.3.1.1ColumnpduOutPduNumberread-onlycurrentThe PDU number on which the outlet resides.
1.3.6.1.4.1.3711.24.1.1.7.2.3.1.2ColumnpduOutNumberread-onlycurrentThe outlet number.
1.3.6.1.4.1.3711.24.1.1.7.2.3.1.3ColumnpduOutRSread-onlycurrentThe PDU table row status.
1.3.6.1.4.1.3711.24.1.1.7.2.3.1.4ColumnpduOutNameread-writecurrentA name identifying the outlet.
1.3.6.1.4.1.3711.24.1.1.7.2.3.1.5ColumnpduOutOnread-writecurrentThe current state for this outlet.
1.3.6.1.4.1.3711.24.1.1.7.2.3.1.6ColumnpduOutPwdread-writecurrentThe password for this outlet.
1.3.6.1.4.1.3711.24.1.1.7.2.3.1.7ColumnpduOutCycleDelayread-onlycurrentThe on/off delay for this outlet in seconds.
1.3.6.1.4.1.3711.24.1.1.7.2.3.1.8ColumnpduOutRebootPeriodread-onlycurrentThe pduOutOn reboot off period for this outlet in seconds.
1.3.6.1.4.1.3711.24.1.1.7.3NodepduMonitor
1.3.6.1.4.1.3711.24.1.1.7.3.1TablepduMonTablenot-accessiblecurrentA table containing monitor information for all PDUs enabled for monitoring.
1.3.6.1.4.1.3711.24.1.1.7.3.1.1RowpduMonEntrynot-accessiblecurrentA conceptual row containing monitor information for one PDU.
1.3.6.1.4.1.3711.24.1.1.7.3.1.1.1ColumnpduMonPduNumberread-onlycurrentThe PDU number.
1.3.6.1.4.1.3711.24.1.1.7.3.1.1.2ColumnpduMonRSread-onlycurrentThe PDU table row status.
1.3.6.1.4.1.3711.24.1.1.7.3.1.1.3ColumnpduRMSVoltsValueread-onlycurrentRMS Volts value in volts
1.3.6.1.4.1.3711.24.1.1.7.3.1.1.4ColumnpduRMSAmpsValueread-onlycurrentRMS current value in 0.1 Amps
1.3.6.1.4.1.3711.24.1.1.7.3.1.1.5ColumnpduTotalEnergyValueread-onlycurrentTotal energy value in 0.1 kWh
1.3.6.1.4.1.3711.24.1.1.7.3.1.1.6ColumnpduMeanKVAValueread-onlycurrentKilo Volt-Amperes value in 0.1 kVA
1.3.6.1.4.1.3711.24.1.1.7.3.1.1.7ColumnpduMeanKWattsValueread-onlycurrentKilo Watts value in 0.1 kW
1.3.6.1.4.1.3711.24.1.1.7.3.1.1.8ColumnpduPwrFactorValueread-onlycurrentPower factor value in 0.01
1.3.6.1.4.1.3711.24.1.1.7.3.2TablepduTrapThreshTablenot-accessiblecurrentA table containing information about the trap threshold values for all PDUs enabled for monitoring.
1.3.6.1.4.1.3711.24.1.1.7.3.2.1RowpduTrapThreshEntrynot-accessiblecurrentA conceptual row containing information about the trap threshold values for one PDU.
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.1ColumnpduTrapThreshPduNumberread-onlycurrentThe PDU number.
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.2ColumnpduTrapThreshRSread-onlycurrentThe PDU table row status.
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.3ColumnpduRMSVoltsUCLread-writecurrentrms UCL value in volts
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.4ColumnpduRMSVoltsUWLread-writecurrentrms UWL value in volts
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.5ColumnpduRMSVoltsLWLread-writecurrentrms LWL value in volts
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.6ColumnpduRMSVoltsLCLread-writecurrentrms LCL value in volts
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.7ColumnpduRMSAmpsUCLread-writecurrentrms UCL value in 0.1 amps
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.8ColumnpduRMSAmpsUWLread-writecurrentrms UWL value in 0.1 amps
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.9ColumnpduRMSAmpsLWLread-writecurrentrms LWL value in 0.1 amps
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.10ColumnpduRMSAmpsLCLread-writecurrentrms LCL value in 0.1 amps
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.11ColumnpduEnergyUCLread-writecurrentTotal energy UCL value in 0.1 kWh
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.12ColumnpduEnergyUWLread-writecurrentTotal energy UWL value in 0.1 kWh
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.13ColumnpduMeanKVAUCLread-writecurrentMean kVA UCL value in 0.1 kVA
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.14ColumnpduMeanKVAUWLread-writecurrentMean kVA UWL value in 0.1 kVA
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.15ColumnpduMeanKVALWLread-writecurrentMean kVA LWL value in 0.1 kVA
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.16ColumnpduMeanKVALCLread-writecurrentMean kVA LCL value in 0.1 kVA
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.17ColumnpduMeanKWattsUCLread-writecurrentMean power UCL value in 0.1 kW
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.18ColumnpduMeanKWattsUWLread-writecurrentMean power UWL value in 0.1 kW
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.19ColumnpduMeanKWattsLWLread-writecurrentMean power LWL value in 0.1 kW
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.20ColumnpduMeanKWattsLCLread-writecurrentMean power LCL value in 0.1 kW
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.21ColumnpduPwrFactorUCLread-writecurrentPower factor UCL value in 0.01
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.22ColumnpduPwrFactorUWLread-writecurrentPower factor UWL value in 0.01
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.23ColumnpduPwrFactorLWLread-writecurrentPower factor LWL value in 0.01
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.24ColumnpduPwrFactorLCLread-writecurrentPower factor LCL value in 0.01
1.3.6.1.4.1.3711.24.1.1.7.3.3TablepduTrapEnTablenot-accessiblecurrentThe table which controls threshold value trap enabling for all PDUs enabled for monitoring.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1RowpduTrapEnEntrynot-accessiblecurrentA conceptual row containing information about one PDU.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.1ColumnpduTrapEnPduNumberread-onlycurrentThe PDU number.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.2ColumnpduTrapEnRSread-onlycurrentThe PDU table row status.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.3ColumnpduRMSVoltsUCLTrapEnread-writecurrentEnables Volts UCL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.4ColumnpduRMSVoltsUWLTrapEnread-writecurrentEnables UWL Volts trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.5ColumnpduRMSVoltsLWLTrapEnread-writecurrentEnables LWL Volts trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.6ColumnpduRMSVoltsLCLTrapEnread-writecurrentEnables LCL Volts trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.7ColumnpduRMSAmpsUCLTrapEnread-writecurrentEnables UCL current trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.8ColumnpduRMSAmpsUWLTrapEnread-writecurrentEnables UWL current trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.9ColumnpduRMSAmpsLWLTrapEnread-writecurrentEnables LWL current trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.10ColumnpduRMSAmpsLCLTrapEnread-writecurrentEnables LCL current trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.11ColumnpduEnergyUCLTrapEnread-writecurrentEnables UCL total energy trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.12ColumnpduEnergyUWLTrapEnread-writecurrentEnables UWL total energy trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.13ColumnpduMeanKVAUCLTrapEnread-writecurrentEnables mean kVA UCL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.14ColumnpduMeanKVAUWLTrapEnread-writecurrentEnables mean kVA UWL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.15ColumnpduMeanKVALWLTrapEnread-writecurrentEnables mean kVA LWL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.16ColumnpduMeanKVALCLTrapEnread-writecurrentEnables mean kVA LCL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.17ColumnpduMeanKWattsUCLTrapEnread-writecurrentEnables mean power UCL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.18ColumnpduMeanKWattsUWLTrapEnread-writecurrentEnables mean power UWL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.19ColumnpduMeanKWattsLWLTrapEnread-writecurrentEnables mean power LWL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.20ColumnpduMeanKWattsLCLTrapEnread-writecurrentEnables mean power LCL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.21ColumnpduPwrFactorUCLTrapEnread-writecurrentEnables power factor UCL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.22ColumnpduPwrFactorUWLTrapEnread-writecurrentEnables power factor UWL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.23ColumnpduPwrFactorLWLTrapEnread-writecurrentEnables power factor LWL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.24ColumnpduPwrFactorLCLTrapEnread-writecurrentEnables power factor LCL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.4TablepduTrapPerTablenot-accessiblecurrentThe table which controls threshold value trap repetition for all PDUs enabled for monitoring.
1.3.6.1.4.1.3711.24.1.1.7.3.4.1RowpduTrapPerEntrynot-accessiblecurrentA conceptual row containing information about one PDU.
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.1ColumnpduTrapPduNumberread-onlycurrentThe PDU number.
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.2ColumnpduTrapPerRSread-onlycurrentThe PDU table row status.
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.3ColumnpduRMSVoltsUCLTrapPerread-writecurrentSets UCL Volts trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.4ColumnpduRMSVoltsUWLTrapPerread-writecurrentSets UWL Volts trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.5ColumnpduRMSVoltsLWLTrapPerread-writecurrentSets LWL Volts trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.6ColumnpduRMSVoltsLCLTrapPerread-writecurrentSets LCL Volts trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.7ColumnpduRMSAmpsUCLTrapPerread-writecurrentSets UCL current trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.8ColumnpduRMSAmpsUWLTrapPerread-writecurrentSets UWL current trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.9ColumnpduRMSAmpsLWLTrapPerread-writecurrentSets LWL current trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.10ColumnpduRMSAmpsLCLTrapPerread-writecurrentSets LCL current trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.11ColumnpduEnergyUCLTrapPerread-writecurrentSets UCL total energy trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.12ColumnpduEnergyUWLTrapPerread-writecurrentSets UWL total energy trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.13ColumnpduMeanKVAUCLTrapPerread-writecurrentSets mean kVA UCL trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.14ColumnpduMeanKVAUWLTrapPerread-writecurrentSets mean kVA UWL trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.15ColumnpduMeanKVALWLTrapPerread-writecurrentSets mean kVA LWL trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.16ColumnpduMeanKVALCLTrapPerread-writecurrentSets mean kVA LCL trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.17ColumnpduMeanKWattsUCLTrapPerread-writecurrentSets mean power UCL trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.18ColumnpduMeanKWattsUWLTrapPerread-writecurrentSets mean power UWL trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.19ColumnpduMeanKWattsLWLTrapPerread-writecurrentSets mean power LWL trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.20ColumnpduMeanKWattsLCLTrapPerread-writecurrentSets mean power LCL trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.21ColumnpduPwrFactorUCLTrapPerread-writecurrentSets power factor UCL trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.22ColumnpduPwrFactorUWLTrapPerread-writecurrentSets power factor UWL trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.23ColumnpduPwrFactorLWLTrapPerread-writecurrentSets power factor LWL trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.24ColumnpduPwrFactorLCLTrapPerread-writecurrentSets power factor LCL trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.99Nodeinventory
1.3.6.1.4.1.3711.24.1.1.99.1ScalarinvProdSignatureread-onlycurrentProduct data signature.
1.3.6.1.4.1.3711.24.1.1.99.2ScalarinvProdFormatVerread-onlycurrentProduct data format version.
1.3.6.1.4.1.3711.24.1.1.99.3ScalarinvManufCoderead-onlycurrentManufacturer code.
1.3.6.1.4.1.3711.24.1.1.99.4ScalarinvOrderNumread-onlycurrentOrder number.
1.3.6.1.4.1.3711.24.1.1.99.5ScalarinvBatchNumread-onlycurrentBatch number.
1.3.6.1.4.1.3711.24.1.1.99.6ScalarinvProdTestTimeread-onlycurrentData and time of production test.
1.3.6.1.4.1.3711.24.1.1.99.7ScalarinvUnitNameread-onlycurrentUnit name.
1.3.6.1.4.1.3711.24.1.1.99.8ScalarinvUnitPartNumread-onlycurrentUnit part number.
1.3.6.1.4.1.3711.24.1.1.99.9ScalarinvHwRevisionread-onlycurrentHardware revision number.
1.3.6.1.4.1.3711.24.1.1.99.10ScalarinvFwRevisionread-onlycurrentFirmware revision number.
1.3.6.1.4.1.3711.24.1.1.99.11ScalarinvSerialNumread-onlycurrentSerial number.
1.3.6.1.4.1.3711.24.1.1.99.12ScalarinvDefaultIPAddrTyperead-onlycurrentThe type of the IP addresses.
1.3.6.1.4.1.3711.24.1.1.99.13ScalarinvDefaultIPAddrread-onlycurrentDefault unit IP address.
1.3.6.1.4.1.3711.24.1.1.99.14ScalarinvDefaultSubNetMaskread-onlycurrentDefault unit sub-network mask.
1.3.6.1.4.1.3711.24.1.1.99.15ScalarinvDefaultGWAddrread-onlycurrentDefault unit default gateway address.
1.3.6.1.4.1.3711.24.1.1.99.16ScalarinvMacAddrread-onlycurrentUnit medium access control (MAC) address.
1.3.6.1.4.1.3711.24.1.1.99.20ScalarinvOkread-onlycurrentConfirms that the inventory record isn't corrupted.
1.3.6.1.4.1.3711.24.1.1.99.50ScalarinvInputCountread-onlycurrentThe maximum number of inputs that can be connected to the unit
1.3.6.1.4.1.3711.24.1.1.99.51ScalarinvOutputCountread-onlycurrentThe maximum number of outputs that can be connected to the unit
1.3.6.1.4.1.3711.24.1.1.99.52ScalarinvKeypadCountread-onlycurrentThe maximum number of keypads that can be connected to the unit
1.3.6.1.4.1.3711.24.1.1.99.53ScalarinvAcuCountread-onlycurrentThe maximum number of ACU's that can be connected to the unit
1.3.6.1.4.1.3711.24.1.1.99.54ScalarinvAccessUserCountread-onlycurrentThe maximum number of user entries on the unit
1.3.6.1.4.1.3711.24.1.1.99.55ScalarinvPduCountread-onlycurrentThe maximum number of PDU's that can be connected to the unit
1.3.6.1.4.1.3711.24.1.1.100NodetrapInfo
1.3.6.1.4.1.3711.24.1.1.100.1ScalartrapCoderead-onlycurrentA decimal number to be carried on notifications of types 1 to 4 identifying the event which caused it. The format of this number is BBEEffCCT where BB is the n…
1.3.6.1.4.1.3711.24.1.1.100.2ScalartrapDescriptionread-onlycurrentA string to be carried on notifications of types 1 to 4 identifying the event which caused it. The format of this string is as follows. Field 1 - type of notif…
Type Definitions
NameSyntaxStatusDescription
ContactStateINTEGER { open(1), closed(2) }currentRepresents the state of a set of contacts.
EnableStateINTEGER { enabled(1), disabled(2) }currentRepresents the state of an enabling flag.
InputContactStateINTEGER { open(1), closed(2), armed(3), triggered(4) }currentRepresents the state of a set of input contacts.
InputDataTypeINTEGER { autodetect(1), temperature(2), humidity(3), analogue(4), contact(5), inactive(255) }currentRepresents the type of data read at an input.
OutputControlStateINTEGER { activate(1), deactivate(2), logic(3) }currentRepresents the control setiing for an output.
RelayStateINTEGER { on(1), off(2) }currentRepresents the energised state of a relay.