MIB Viewer

HM2-INDUSTRIAL-PROTOCOLS-MIB

113 objects
Hirschmann Industrial Protocols MIB. Copyright (C) 2013. All Rights Reserved.
OIDNameAccessStatusDescription
1.3.6.1.4.1.248.11.101Identityhm2IndustrialProtocolsMibHirschmann Industrial Protocols MIB. Copyright (C) 2013. All Rights Reserved.
1.3.6.1.4.1.248.11.101.0Nodehm2IndustrialProtocolsNotifications
1.3.6.1.4.1.248.11.101.1Nodehm2IndustrialProtocolsMibObjects
1.3.6.1.4.1.248.11.101.1.1Nodehm2Iec61850Group
1.3.6.1.4.1.248.11.101.1.1.1Nodehm2Iec61850ConfigGroup
1.3.6.1.4.1.248.11.101.1.1.1.1Scalarhm2Iec61850MmsServerAdminStatusread-writecurrentEnables/disables the IEC61850 MMS server functionality on this device. If disabled(2), the IEC61850 MMS Server is deactivated, but the IEC61850 MIBs can be acc…
1.3.6.1.4.1.248.11.101.1.1.1.2Scalarhm2Iec61850MmsServerWriteAccessStatusread-writecurrentEnables/disables the read/write capability of the IEC61850 MMS. If disabled(2), the IEC61850 MMS Server is accessible read-only, if enabled(1) the device confi…
1.3.6.1.4.1.248.11.101.1.1.1.3Scalarhm2Iec61850MmsServerPortNumberread-writecurrentThe port number of the IEC61850 MMS server. Setting the port to zero is not allowed.
1.3.6.1.4.1.248.11.101.1.1.1.4Scalarhm2Iec61850MmsServerMaxSessionsCountread-writecurrentMax number of IEC61850 MMS sessions permitted on this switch.
1.3.6.1.4.1.248.11.101.1.1.1.5Scalarhm2Iec61850MmsServerTechnicalKeyread-writecurrentThe IEC61850 MMS server technical key setting corresponds to the IEC61850 IED name. This name is used to identify the device via a IEC61850 MMS client. The siz…
1.3.6.1.4.1.248.11.101.1.1.1.10Scalarhm2Iec61850MmsTlsServerAdminStatusread-writecurrentEnables/disables the IEC61850 MMS over TLS server functionality on this device. If disabled(2), the IEC61850 MMS over TLS Server is deactivated, but the IEC618…
1.3.6.1.4.1.248.11.101.1.1.1.11Scalarhm2Iec61850MmsTlsServerWriteAccessStatusread-writecurrentEnables/disables the read/write capability of the IEC61850 MMS. If disabled(2), the IEC61850 MMS over TLS Server is accessible read-only, if enabled(1) the dev…
1.3.6.1.4.1.248.11.101.1.1.1.12Scalarhm2Iec61850MmsTlsServerPortNumberread-writecurrentThe port number of the IEC61850 MMS over TLS server. Setting the port to zero is not allowed.
1.3.6.1.4.1.248.11.101.1.1.1.13Scalarhm2Iec61850MmsTlsServerMaxSessionsCountread-writecurrentMax number of IEC61850 MMS over TLS sessions permitted on this switch.
1.3.6.1.4.1.248.11.101.1.1.1.20Scalarhm2Iec61850MmsTlsServerKeysPresentread-onlycurrentIndicates what key files are present on the device, if any.
1.3.6.1.4.1.248.11.101.1.1.1.21Scalarhm2Iec61850MmsTlsServerKeyOperStatusread-onlycurrentIndicates what key files are currently being generated or deleted, if any.
1.3.6.1.4.1.248.11.101.1.1.1.22Scalarhm2Iec61850MmsTlsServerRSAKeyControlread-writecurrentControls RSA key generation and deletion. Always returns noop(1).
1.3.6.1.4.1.248.11.101.1.1.1.23Scalarhm2Iec61850MmsTlsServerDSAKeyControlread-writecurrentControls DSA key generation and deletion. Always returns noop(1).
1.3.6.1.4.1.248.11.101.1.1.1.24Scalarhm2Iec61850MmsTlsServerFingerPrintDSAread-onlycurrentThe local DSA fingerprint for IEC61850 MMS over TLS connections.
1.3.6.1.4.1.248.11.101.1.1.1.25Scalarhm2Iec61850MmsTlsServerFingerPrintRSAread-onlycurrentThe local RSA fingerprint for IEC61850 MMS over TLS connections.
1.3.6.1.4.1.248.11.101.1.1.1.26Scalarhm2Iec61850MmsServerStatusread-onlycurrentReturns current MMS server status. As the MMS server takes a long time to start or to stop, this will return the actual server state, not just if it is enabled…
1.3.6.1.4.1.248.11.101.1.1.2Nodehm2Iec61850StatisticsGroup
1.3.6.1.4.1.248.11.101.1.1.2.1Scalarhm2Iec61850MmsServerSessionsCountread-onlycurrentCurrent number of active IEC61850 MMS sessions on this switch.
1.3.6.1.4.1.248.11.101.1.1.2.10Scalarhm2Iec61850MmsTlsServerSessionsCountread-onlycurrentCurrent number of active IEC61850 MMS over TLS sessions on this switch.
1.3.6.1.4.1.248.11.101.1.2Nodehm2ProfinetIOGroup
1.3.6.1.4.1.248.11.101.1.2.1Nodehm2ProfinetIOConfigGroup
1.3.6.1.4.1.248.11.101.1.2.1.1Scalarhm2PNIOAdminStatusread-writecurrentEnables/disables the ProfinetIO functionality on this device. If disabled(2), the ProfinetIO protocol is inactive, but the ProfinetIO MIBs can be accessed. The…
1.3.6.1.4.1.248.11.101.1.2.1.2Scalarhm2PNIODeviceIDread-onlycurrentIdentifier of the device family. Values 1 .. 65635 are valid device IDs.
1.3.6.1.4.1.248.11.101.1.2.1.3Scalarhm2PNIOModuleIdentNumberread-onlycurrentIdentifier ID of the device of port or module.
1.3.6.1.4.1.248.11.101.1.2.1.4Scalarhm2PNIOOrderIDread-onlycurrentProduct (switch) order ID. The size is restricted to 64 characters.
1.3.6.1.4.1.248.11.101.1.2.1.5Scalarhm2PNIODeviceTypeDetailsread-onlycurrentSwitch device type details, for example: 4 Port Rail Switch.
1.3.6.1.4.1.248.11.101.1.2.1.6Scalarhm2PNIOSoftwareReleaseread-onlycurrentThis value is a string that contains Version number of software in profinetio format, for example: 01.0.03.
1.3.6.1.4.1.248.11.101.1.2.1.7Scalarhm2PNIOHardwareReleaseread-onlycurrentVersion number of switch hardware in profinetio format.
1.3.6.1.4.1.248.11.101.1.2.1.8Scalarhm2PNIOOrderID9thread-onlycurrentProduct (switch) order ID. The size is restricted to 32 characters (In the form of the 9-th numbers).
1.3.6.1.4.1.248.11.101.1.2.1.9Scalarhm2PNIONameOfStationread-writecurrentDevice name. The size is restricted to 240 characters. It must be conform to the restrictions as decribed in PNIO protocol specification.
1.3.6.1.4.1.248.11.101.1.2.1.10Scalarhm2PNIONumActiveApplicationRelationsread-onlycurrentReturns the number of active application relations.
1.3.6.1.4.1.248.11.101.1.2.1.11Scalarhm2PNIOClearIpParameterread-writecurrentClears the IP parameters if set to true and PNIO is enabled.
1.3.6.1.4.1.248.11.101.1.2.1.20Tablehm2PNIODcpModeTablenot-accessiblecurrentTable of DCP mode entries
1.3.6.1.4.1.248.11.101.1.2.1.20.1Rowhm2PNIODcpModeEntrynot-accessiblecurrentDCP mode entry
1.3.6.1.4.1.248.11.101.1.2.1.20.1.1Columnhm2PNIODcpModePortIDnot-accessiblecurrentPort ID for the DCP mode table entry
1.3.6.1.4.1.248.11.101.1.2.1.20.1.2Columnhm2PNIODcpModeread-writecurrentDCP mode for one port. Allowed values none(0), ingress(1), egress(2) or both(3) which is default.
1.3.6.1.4.1.248.11.101.1.2.1.21Scalarhm2PNIOIm1Dataread-writecurrentI&M1 data contains 2 fields: Tag function is a 32 byte visible string that indicates the submodule's function or task. Tag location is a 22 byte visible string…
1.3.6.1.4.1.248.11.101.1.2.1.22Scalarhm2PNIOIm2Dataread-writecurrentI&M2 is a Date and time function in the YYYY-MM-DD HH:MM format. For example, 2018-08-10 10:50
1.3.6.1.4.1.248.11.101.1.2.1.23Scalarhm2PNIOIm3Dataread-writecurrentI&M3 is a general Descriptor function that is a 54 byte visible string for holding additional information.
1.3.6.1.4.1.248.11.101.1.2.1.24Scalarhm2PNIOIm4Dataread-writecurrentI&M4 is used for a signature with PROFIsafe.
1.3.6.1.4.1.248.11.101.1.2.1.25Scalarhm2PNIOClearStationNameread-writecurrentClear Station Name if set to true and PNIO is enabled.
1.3.6.1.4.1.248.11.101.1.2.1.26Scalarhm2PNIOPdevParametersread-writecurrentPDEV parameters of ApplicationRelation
1.3.6.1.4.1.248.11.101.1.2.2Nodehm2ProfinetIOStatisticsGroup
1.3.6.1.4.1.248.11.101.1.3Nodehm2EthernetIPGroup
1.3.6.1.4.1.248.11.101.1.3.1Nodehm2EthernetIPConfigGroup
1.3.6.1.4.1.248.11.101.1.3.1.1Scalarhm2EtherNetIPAdminStatusread-writecurrentEnables/disables the EtherNet/IP(TM) operation on this device. If disabled, the EtherNet/IP protocol is deactivated, but the EtherNet/IP MIBs can be accessed. …
1.3.6.1.4.1.248.11.101.1.3.1.2Scalarhm2EtherNetIPErrorCoderead-onlycurrentRead the error code within EtherNet/IP(TM) action.
1.3.6.1.4.1.248.11.101.1.3.1.3Scalarhm2EtherNetIPProductCoderead-onlycurrentRead the Product Code as shown in the Identity Object of EtherNet/IP(TM). Values 1 .. 65635 are valid product codes.
1.3.6.1.4.1.248.11.101.1.3.1.4Scalarhm2EtherNetIPMajorRevisionread-onlycurrentRead the major revision number as shown in the Identity Object of EtherNet/IP(TM). Values 1 .. 255 are valid revisions.
1.3.6.1.4.1.248.11.101.1.3.1.5Scalarhm2EtherNetIPMinorRevisionread-onlycurrentRead the minor revision number as shown in the Identity Object of EtherNet/IP(TM). Values 1 .. 255 are valid revisions.
1.3.6.1.4.1.248.11.101.1.3.1.6Scalarhm2EtherNetIPProductNameread-onlycurrentRead the product name as shown in the Identity Object of EtherNet/IP(TM). The size is restricted to 32 Characters.
1.3.6.1.4.1.248.11.101.1.3.1.7Scalarhm2EtherNetIPCatalogNameread-onlycurrentRead the catolog name as provided in the EDS file for EtherNet/IP(TM). The size is restricted to 255 Characters.
1.3.6.1.4.1.248.11.101.1.3.1.8Scalarhm2EtherNetIPWriteAccessStatusread-writecurrentEnables/disables the read/write capability of the EtherNet/IP protocol. If disabled(2), the EtherNet/IP protocol is accessible the get requests only, if enable…
1.3.6.1.4.1.248.11.101.1.3.1.9Scalarhm2EtherNetIPVlanread-writecurrentSet the VLAN ID of EtherNet/IP. Possible values for the VLAN ID are -1 to 4042. A value of -1 corresponds to management VLAN(the default). A value 0 is for pri…
1.3.6.1.4.1.248.11.101.1.3.1.10Scalarhm2EtherNetIPInterfaceread-writecurrentSets the mode of the various interface for EtherNet/IP for this device. EtherNet/IP traffic configure with physical interface EtherNet/IP traffic configure wit…
1.3.6.1.4.1.248.11.101.1.3.2Nodehm2EthernetIPStatisticsGroup
1.3.6.1.4.1.248.11.101.1.3.2.1Scalarhm2EtherNetIPConnEstablishedread-onlycurrentStatistics: number of connections that have been established within EtherNet/IP.
1.3.6.1.4.1.248.11.101.1.3.2.2Scalarhm2EtherNetIPConnTimeoutsread-onlycurrentStatistics: number of connection timeouts that have been occurred within EtherNet/IP.
1.3.6.1.4.1.248.11.101.1.3.2.3Scalarhm2EtherNetIPVendorObjRequestsread-onlycurrentStatistics: number of requests to the vendor specific objects within EtherNet/IP.
1.3.6.1.4.1.248.11.101.1.3.3Nodehm2EthernetIPTCPIPObjectGroup
1.3.6.1.4.1.248.11.101.1.3.3.1Scalarhm2EtherNetIPMcastTTLValueread-writecurrentTime-to-Live value for IP multicast packets.
1.3.6.1.4.1.248.11.101.1.3.3.2Scalarhm2EtherNetIPMcastAllocControlread-writecurrentControls how the device shall allocate IP multicast addresses. A value of 0 means multicast addresses shall be generated using the default allocation algorithm…
1.3.6.1.4.1.248.11.101.1.3.3.3Scalarhm2EtherNetIPMcastCountread-writecurrentThe maximum number of IP multicast addresses to be allocated.
1.3.6.1.4.1.248.11.101.1.3.3.4Scalarhm2EtherNetIPMcastStartAddressread-writecurrentThe starting multicast address from which Num Mcast addresses are allocated.
1.3.6.1.4.1.248.11.101.1.3.3.5Scalarhm2EtherNetIPLastConflictDetectedACDActivityread-writecurrentThe ARP Response PDU (a copy of the ARP message that caused the address conflict) in binary format. Can only be written to a value of zero.
1.3.6.1.4.1.248.11.101.1.3.3.6Scalarhm2EtherNetIPSelectACDStatusread-writecurrentSets the status of the ip address conflict detection mechanism on this device. The new value of this element is applied after the device executes a restart.
1.3.6.1.4.1.248.11.101.1.3.3.7Scalarhm2EtherNetIPEncapsulationInactivityread-writecurrentsets the EncapsulationInactivity timeout. After a period of no Encapsulation activity on a TCP connection originator and target shall close the TCP connection.
1.3.6.1.4.1.248.11.101.1.3.4Nodehm2EthernetIPQoSObjectGroup
1.3.6.1.4.1.248.11.101.1.3.4.1Scalarhm2EtherNetIPQosDscpUrgentValueread-writecurrentDSCP value for CIP transport Urgent priority messages.
1.3.6.1.4.1.248.11.101.1.3.4.2Scalarhm2EtherNetIPQosDscpScheduledValueread-writecurrentDSCP value for CIP transport Scheduled priority messages.
1.3.6.1.4.1.248.11.101.1.3.4.3Scalarhm2EtherNetIPQosDscpHighValueread-writecurrentDSCP value for CIP transport High priority messages.
1.3.6.1.4.1.248.11.101.1.3.4.4Scalarhm2EtherNetIPQosDscpLowValueread-writecurrentDSCP value for CIP transport Low priority messages.
1.3.6.1.4.1.248.11.101.1.3.4.5Scalarhm2EtherNetIPQosDscpExplicitValueread-writecurrentDSCP value for CIP transport Explicit priority messages.
1.3.6.1.4.1.248.11.101.1.3.4.6Scalarhm2EtherNetIPQosValueread-writecurrentThis object indicates a changes which be applied after the device executes a restart.
1.3.6.1.4.1.248.11.101.1.4Nodehm2ModbusGroup
1.3.6.1.4.1.248.11.101.1.4.1Nodehm2ModbusConfigGroup
1.3.6.1.4.1.248.11.101.1.4.1.1Scalarhm2ModbusTcpServerAdminStatusread-writecurrentEnables/disables the Modbus TCP server functionality on this device. If disabled(2), the Modbus TCP Server is deactivated, but the Modbus MIBs can be accessed.…
1.3.6.1.4.1.248.11.101.1.4.1.2Scalarhm2ModbusTcpServerWriteAccessStatusread-writecurrentEnables/disables the read/write capability of the Modbus TCP server. If disabled(2), the Modbus TCP Server is accessible read-only, if enabled(1) the device co…
1.3.6.1.4.1.248.11.101.1.4.1.3Scalarhm2ModbusTcpServerPortNumberread-writecurrentThe port number of the Modbus TCP server. Setting the port to zero is not allowed.
1.3.6.1.4.1.248.11.101.1.4.1.4Scalarhm2ModbusTcpServerMaxSessionsCountread-writecurrentMaximum number of concurrent sessions allowed by the Modbus TCP server.
1.3.6.1.4.1.248.11.101.1.4.2Nodehm2ModbusStatisticsGroup
1.3.6.1.4.1.248.11.101.1.4.2.1Scalarhm2ModbusTcpServerSessionsCountread-onlycurrentCurrent number of active sessions to the Modbus TCP server.
1.3.6.1.4.1.248.11.101.1.5Nodehm2Iec62541Group
1.3.6.1.4.1.248.11.101.1.5.1Nodehm2Iec62541ConfigGroup
1.3.6.1.4.1.248.11.101.1.5.1.1Scalarhm2Iec62541OpcUaServerAdminStatusread-writecurrentEnables/disables the Iec62541 OPC/UA server functionality on this device. If disabled(2), the Iec62541 OPC/UA Server is deactivated, but the Iec62541 OPC/UA MI…
1.3.6.1.4.1.248.11.101.1.5.1.2Scalarhm2Iec62541OpcUaServerPortNumberread-writecurrentThe port number of the Iec62541 OPC/UA server. Setting the port to zero is not allowed.
1.3.6.1.4.1.248.11.101.1.5.1.3Scalarhm2Iec62541OpcUaMaxSessionsCountread-writecurrentMaximum number of OpcUa sessions. An integer value from 1 to 5 specifies the maximum number of OpcUa sessions that can be established. The full range is not su…
1.3.6.1.4.1.248.11.101.1.5.1.4Scalarhm2Iec62541OpcUaSecurityPolicyread-writecurrentThe security policy of the Iec62541 OPC/UA server.
1.3.6.1.4.1.248.11.101.1.5.1.10Tablehm2Iec62541OpcUaUserConfigTablenot-accessiblecurrentOpcUa User configuration table. This table provides the functionality the OpcUa Server uses for any interaction started by the user - authentication, password …
1.3.6.1.4.1.248.11.101.1.5.1.10.1Rowhm2Iec62541OpcUaUserConfigEntrynot-accessiblecurrentOpcUa User configuration entry.
1.3.6.1.4.1.248.11.101.1.5.1.10.1.1Columnhm2Iec62541OpcUaUserNameaccessible-for-notifycurrentOpcUa user name.
1.3.6.1.4.1.248.11.101.1.5.1.10.1.2Columnhm2Iec62541OpcUaUserPasswordread-createcurrentOpcUa user password This object will always return '********' when read.
1.3.6.1.4.1.248.11.101.1.5.1.10.1.3Columnhm2Iec62541OpcUaUserAccessRoleread-createcurrentOpcUa user's access role. The user's access role can be set while the row is active.
1.3.6.1.4.1.248.11.101.1.5.1.10.1.5Columnhm2Iec62541OpcUaUserStatusread-createcurrentOpcUa user status. active(1) - This user account is active. notInService(2) - Row has been suspended. notReady(3) - Row has incomplete values. createAndGo(4) -…
1.3.6.1.4.1.248.11.101.3Nodehm2IndustrialProtocolsMibSNMPExtensionGroup
1.3.6.1.4.1.248.11.101.3.1Nodehm2Iec61850SESGroup
1.3.6.1.4.1.248.11.101.3.2Nodehm2ProfinetIOSESGroup
1.3.6.1.4.1.248.11.101.3.2.1Identityhm2ProfinetIOInvalidStationNamecurrentInvalid station name.
1.3.6.1.4.1.248.11.101.3.2.2Identityhm2ProfinetIOARActivecurrentSet not allowed, a Profinet application relation is active.
1.3.6.1.4.1.248.11.101.3.3Nodehm2EthernetIPSESGroup
1.3.6.1.4.1.248.11.101.3.3.1Identityhm2EthernetIPUsedVlanIdcurrentVLAN not available, it is already used by another protocol.
1.3.6.1.4.1.248.11.101.3.3.2Identityhm2EthernetIPNoVlanIdcurrentVLAN does not exist.
1.3.6.1.4.1.248.11.101.3.3.3Identityhm2EthernetIPDynamicVlancurrentDynamic VLANs are not allowed. Use a static VLAN.
1.3.6.1.4.1.248.11.101.3.3.4Identityhm2EthernetIPVlanUnawarecurrentEtherNet/IP Separate VLAN cannot be used together with the VLAN Unaware Mode.
1.3.6.1.4.1.248.11.101.3.4Nodehm2ModbusSESGroup
1.3.6.1.4.1.248.11.101.3.5Nodehm2Iec62541SESGroup
Type Definitions
NameSyntaxStatusDescription
Hm2Iec62541OpcUaSecurityPoliciesINTEGER { none (1), basic128Rsa15 (2), basic256 (3), basic256Sha256 (4) }currentOPC/UA server security policy.
Hm2Iec62541OpcUaUserAccessRolesINTEGER { readOnly (1) }currentuser access roles.